    Design Specifications

    Anchor

    Anchor system fischer Injection system FIS VTInjection resin FIS VT 380 CFixing element Threaded rod , zinc plated steel,FIS A M 16 x 250 8.8

    property class 8.8Anchorage depth 192 mm

    Design Data Specification by manufacturer, ENSO-Data see printout

    Geometry / Loads / Scale units

    mm, kN, kNm

    Value of design actions (includingpartial safety factor for the load)

    Not drawn to scale

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 1

  • 7/24/2019 C FIX Gondola

    2/9

    Input data

    Design method Design method ENSO BondedBase material Normal weight concrete, C45, BS 8110Concrete condition Non-cracked, dry holeTemperature range 24 C long term temperature, 40 C short term temperatureReinforcement Normal or no reinforcement. No edge reinforcementDrilling method Hammer drillingInstallation type Pre-positioned installationAnnular gap Annular gap not filledType of loading Static or quasi-staticBase plate location Base plate flush installed on base materialBase plate geometry 300 mm x 300 mm x 30 mmProfile type Customized profile

    Design actions *

    NSdkN

    VSd,xkN

    VSd,ykN

    MSd,xkNm

    MSd,ykNm

    MT,SdkNm

    0.00 24.00 0.00 0.00 86.00 1.00

    * The required partial safety factors for actions are included

    Resulting anchor forces

    Anchor no.Tensile action

    kNShear Action

    kNShear Action x

    kNShear Action y

    kN

    1 88.02 2.36 2.25 -0.68

    2 0.00 2.36 2.25 0.68

    3 88.02 2.84 2.75 -0.68

    4 0.00 2.84 2.75 0.68

    5 88.02 3.32 3.25 -0.68

    6 0.00 3.32 3.25 0.68

    7 88.02 3.81 3.75 -0.68

    8 0.00 3.81 3.75 0.68

    Force: Tension Compression

    max. concrete compressive strain : 0.97 max. concrete compressive stress : 32.9 N/mmResulting tensile actions : 352.10 kN , X/Y position ( -118 / 0 )Resulting compression actions : 352.10 kN , X/Y position ( 126 / 0 )

    Resistance to tension loads

    Proof ActionkN

    CapacitykN

    Utilisation N%

    Steel failure * 88.02 84.00 104.8

    Combined pull-out and concrete cone failure 352.10 129.58 271.7

    Concrete cone failure 352.10 141.86 248.2

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 2

  • 7/24/2019 C FIX Gondola

    3/9

    * Most unfavourable anchor

    Steel failure

    (NRd,s)

    NRk,skN

    Ms NRd,skN

    NSdkN

    N,s%

    126.00 1.50 84.00 88.02 104.8

    Combined pull-out and concrete cone failure

    (NRd,p)

    Eq. (5.2)

    Eq. (5.2a)

    Eq. (5.2c)

    Eq. (5.2d)

    Eq. (5.2e)

    Eq. (5.2f)

    Eq. (5.2g)

    Eq. (5.2h)

    Eq. (5.2i)

    NRk,pkN

    Mp NRd,pkN

    NSdkN

    N,p%

    233.24 1.80 129.58 352.10 271.7

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 3

  • 7/24/2019 C FIX Gondola

    4/9

    Concrete cone failure

    (NRd,c)

    Eq. (5.3)

    Eq. (5.3a)

    Eq. (5.3c)

    Eq. (5.3d)

    Eq. (5.3e)

    NRk,ckN

    Mc NRd,ckN

    NSdkN

    N,c%

    255.36 1.80 141.86 352.10 248.2

    Resistance to shear loads

    Proof ActionkN

    CapacitykN

    Utilisation V%

    *Steel failure without lever arm 3.81 50.40 7.6

    Concrete pry-out failure 3.32 23.06 14.4

    * Most unfavourable anchor

    Steel failure without lever arm

    (VRd,s)

    VRk,skN

    Ms VRd,skN

    VSdkN

    Vs%

    63.00 1.25 50.40 3.81 7.6

    Concrete pry-out failure

    (VRd,cp)

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 4

  • 7/24/2019 C FIX Gondola

    5/9

    Eq. (5.7a)

    Eq. (5.3)

    Eq. (5.3a)

    Eq. (5.3c)

    Eq. (5.3d)

    Eq. (5.3e)

    VRk,cpkN

    Ms VRd,cpkN

    VSdkN

    V,cp%

    34.60 1.50 23.06 3.32 14.4

    Utilization of tension and shear loads

    Tension loads Utilisation N%

    Steel failure * 104.8

    Combined pull-out and concrete cone failure 271.7

    Concrete cone failure 248.2

    Shear Loads Utilisation V

    %

    Steel failure without lever arm * 7.6

    Concrete pry-out failure 14.4

    * Most unfavourable anchor

    Resistance to combined tensile and shear loads

    ErrorEq. (5.9a)

    Eq. (5.9b)

    Eq. (5.9c)

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 5

  • 7/24/2019 C FIX Gondola

    6/9

    Base plate thickness

    Stress distribution pattern within theanchor plate

    Base plate details

    Anchor plate thickness t = 30 mmBase plate material S 275E-modulus E = 210,000 N/mmYield strength =Rp,0,2 275 N/mmSafety factor =M 1.1Poisson's ratio = 0.3Utilisation = 76 %

    Profile type Customized profile

    Technical remarks

    All data and information in the software is based on fischer products and common engineering knowledge. Pleasecheck all the proof results against local valid standards and approvals. As fischer is not the design office, theattached is no guarantee for incorrect input or assumptions. Any recommendations have to be approved by thebuilding-authority or project engineer. Results are valid only for anchor system calculated in the attached. If anypart of the system is changed, it will invalidate this report and new calculations would be required.The transmission of the anchor loads to the supports of the concrete member shall be shown for the ultimate limit state andthe serviceability limit state; for this purpose, the normal verifications shall be carried out under due consideration of theactions introduced by the anchors. For these verifications the additional provisions given in the current design method shallbe taken into account.

    As a pre-condition the anchor plate is assumed to be flat when subjected to the actions. Therefore, the plate must besufficiently stiff. The C-Fix anchor plate design is based on a proof of stresses and does not allow a statement aboutthe stiffness of the plate. The proof of the necessary stiffness is not carried out by C-Fix.

    During the design process, the following hints and warnings were issued:

    Anchors have to be greater than 30.0 mm to the edge of the profile.

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 6

  • 7/24/2019 C FIX Gondola

    7/9

    Installation data

    Anchor

    Anchor system fischer Injection system FIS VTInjection resin FIS VT 380 C (other cartridge sizes

    available)Art.-No. 59118

    Fixing element Threaded rod ,zinc plated steel,

    FIS A M 16 x 250 8.8property class 8.8

    Art.-No. 517940

    Accessory FIS Easy mixer Art.-No. 61223FIS Extension tube 9mm Art.-No. 48983Dispenser FIS AC Art.-No. 96497Compressed-air cleaning tool Art.-No. 93286compressed air (oil-free), min. 6 bar By job site.BSD 18 Art.-No. 1493

    SDS chuck with internal thread Art.-No. 511961Hammer drill bit SDS Plus IV18/200/250

    Art.-No. 504162

    Installation details

    Thread diameter M 16Drill hole diameter d0 = 18 mmDrill hole depth h1 = 192 mmAnchorage depth hef= 192 mmDrilling method Hammer drillingDrill hole cleaning 4 times blowing,

    4 times brushing,4 times blowingrequired activities according thegiven instruction in the approval

    Installation type Pre-positioned installationAnnular gap Annular gap not filledMaximum torque Tinst,max = 60.0 NmSocket size 24 mmBase plate thickness t = 30 mmTotal fixing thickness tfix = 30 mm

    Volume of resin per drillhole

    22 ml/11 scale divisions

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 7

  • 7/24/2019 C FIX Gondola

    8/9

    Base plate detailsBase plate material S 275Base plate thickness t = 30 mmClearance hole in baseplate

    df=18 mm

    Attachment

    Profile type Customized profile

    Profile dimensions mm

    Height 256

    Width 146

    Web thickness 6

    Flange thickness 11

    Anchor coordinates

    Anchor no.x

    mmy

    mm

    1 -118 120

    2 102 120

    3 -118 40

    4 102 40

    5 -118 -40

    6 102 -40

    7 -118 -120

    8 102 -120

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.

    Page 8

  • 7/24/2019 C FIX Gondola

    9/9

    ENSO-Datasheet

    Anchor

    Injection resin FIS VT 380 CFixing element Threaded rod ,

    zinc plated steel,FIS A M 16 x 250 8.8

    property class 8.8

    Characteristic resistances 1)

    Characteristic resistance for steel failure under tension

    Characteristic resistance 8.8 NRk,s kN 126.00

    Partial safety factor Ms,N - 1.50

    Characteristic bond strength for concrete C20/25 2)

    Non-cracked Rk,ucr N/mm 11.5

    Partial safety factor M,p - 1.80

    Characteristic resistance for concrete cone failure and spalling 2)

    Effective anchorage depth hef mm 192

    Factor k for uncracked concrete kucr - 10.10

    Characteristic distances for member thickness 1,000 mm

    Partial safety factor M,c - 1.80

    Characteristic resistance shear load without lever arm

    Characteristic resistance 8.8 VRk,s kN 63.00

    Partial safety factor Ms,V - 1.25

    Characteristic resistance for pryout

    Factor k for Pryout k - 2.00

    Partial safety factor M,cp - 1.50

    Minimum dimensions and measures

    min. member thickness hmin mm 228

    min. spacing smin mm 65

    min. edge distance cmin mm 65

    1) For all not listet parameters see ENSO-Design method.

    2) Drilling method Hammer drilling

    Drill hole condition dry hole

    Temperature range 24 C long term temperature, 40 C short term temperature

    C-FIX 1.15.0.3997Database version2015.10.7.11.26Date14/10/2015

    The input values and the design results should be checked against local valid standards and approvals. Please respect the disclaimer of warranty inthe license agreement of the Software.