2
DN-6877:B • 06/08/2009 — Page 1 of 2 BACNET-GW-3 BACnet Gateway Network Systems DN-6877:B • A0-190 General The BACNET-GW-3 provides an interface between NOTI- FIER’s fire panel network NOTI•FIRE•NET™ (either the stan- dard or the high-speed version) and a network using the BACnet/IP communication protocol. BACnet protocol is an American National Standard (ANSI/ASHRAE 135-1995). With the Gateway interface, devices on NOTI•FIRE•NET fire alarm control panels are represented as BACnet objects to the BAC- net client. The user subscribes to Event Notification objects per FACP, and the BACnet device receives events from objects on the FACP as a result of this subscription. The BACNET-GW-3 can be connected to a stand-alone ONYX® panel with an available network port, or it can be con- nected to NOTI•FIRE•NET via the network port on any net- work control module. Connected to NOTI•FIRE•NET, each BACNET-GW-3 can support a maximum of 14 other nodes or 15,000 objects. Multiple BACNET-GW-3s can be used to inter- face with larger networks. Features Compatible with ONYX Series panels: NFS2-3030, NFS2- 640, NFS-320, NFS-3030, NFS-640. Compatible with NOTI•FIRE•NET devices: NFS2-3030, NFS2-640, NFS-320, NCA-2, DVC, and ONYXWorks™; NFS-3030, NFS-640, NCA, and AFP1010/AM2020; NCS.. The BACNET-GW-3 can monitor up to 14 NOTI•FIRE•NET nodes with a maximum combined object count of 15,000 (object count includes all detectors, monitor modules, notifi- cation appliance circuits, etc.). Multiple BACNET-GW-3s can be used for large networks (more than 15 nodes total). PC programmable using the BACNET-GW-3 Configuration Tool, an offline programming utility used to configure the BACNET-GW-3. The Configuration Tool is used on a com- patible computer that is using Windows® XP OS. The NOTIFIER BACNET-GW-3 can behave as a foreign device when communicating with a third-party BBMD (BAC- net Broadcast Management Devices). Compatible with standard and high-speed NOTI•FIRE•NET Specifications Complies with: UL 864 9th Edition; and CAN/ULC-S559- 04, 1st Edition Standard for Control Units for Fire Alarm Systems. Complies with NFPA 72 National Fire Alarm Code. Conforms to BACnet Standard Annex J for IP and Support Device Objects, Binary Output Objects, Life Safety Points/ Zones, and Multi-State Inputs. Power supply: 24 VDC @450mA nominal and supervised battery backup. Operating temperature: 32°F to 120°F (0°C to 49°C). Connections The BACNET-GW-3 is connected to NOTI•FIRE•NET via the network port on the network control module to the Gate- way. BACNET-GW-3 is connected to the BACnet front end via a standard RJ45 Ethernet connector (CN2). The BACNET-GW-3 assembly installs in one row of a CAB-3 or CAB-4 Series cabinet using a CHS-4 or CHS-4L chassis. The PNET-1 surge suppressor is connected to the BACnet Ethernet via a RJ45 Ethernet connector. Agency Listings and Approvals The listings and approvals below apply to the BACNET-GW-3. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL Listed: file S635. ULC Listed: file S635. Product Line Information The BACNET-GW-3 (ordered as such) includes everything required to set up an interface to an existing NOTIFIER system or network with the exception of a chassis and the Network Control Module (NCM). It includes: PC board for the BACNET-GW-3. Software on CD-ROM (Configuration Tool). RJ45 to RJ45 Standard Ethernet Network Cable (PN 75585). NUP to NUP cable (PN 75556). Additional required components (from other vendors): IBM-compatible PC with Windows XP. Standard Ethernet network cable with RJ45 connectors. PIC Statement/BACnet Information The BACNET-GW-3 PIC Statement is available at www.notifier.com. Select products and then network sys- tems. For information on the BACnet protocol, see www.bac- net.org. 6877cov.psd

BACnet-GW-3- DN_6877

Embed Size (px)

Citation preview

Page 1: BACnet-GW-3- DN_6877

DN-6877:B • 06/08/2009 — Page 1 of 2

BACNET-GW-3BACnet Gateway

Network Systems

DN-6877:B • A0-190

GeneralThe BACNET-GW-3 provides an interface between NOTI-FIER’s fire panel network NOTI•FIRE•NET™ (either the stan-dard or the high-speed version) and a network using theBACnet/IP communication protocol. BACnet protocol is anAmerican National Standard (ANSI/ASHRAE 135-1995). Withthe Gateway interface, devices on NOTI•FIRE•NET fire alarmcontrol panels are represented as BACnet objects to the BAC-net client. The user subscribes to Event Notification objectsper FACP, and the BACnet device receives events from objectson the FACP as a result of this subscription.

The BACNET-GW-3 can be connected to a stand-aloneONYX® panel with an available network port, or it can be con-nected to NOTI•FIRE•NET via the network port on any net-work control module. Connected to NOTI•FIRE•NET, eachBACNET-GW-3 can support a maximum of 14 other nodes or15,000 objects. Multiple BACNET-GW-3s can be used to inter-face with larger networks.

Features• Compatible with ONYX Series panels: NFS2-3030, NFS2-

640, NFS-320, NFS-3030, NFS-640.• Compatible with NOTI•FIRE•NET devices: NFS2-3030,

NFS2-640, NFS-320, NCA-2, DVC, and ONYXWorks™;NFS-3030, NFS-640, NCA, and AFP1010/AM2020; NCS..

• The BACNET-GW-3 can monitor up to 14 NOTI•FIRE•NETnodes with a maximum combined object count of 15,000(object count includes all detectors, monitor modules, notifi-cation appliance circuits, etc.).

• Multiple BACNET-GW-3s can be used for large networks(more than 15 nodes total).

• PC programmable using the BACNET-GW-3 ConfigurationTool, an offline programming utility used to configure theBACNET-GW-3. The Configuration Tool is used on a com-patible computer that is using Windows® XP OS.

• The NOTIFIER BACNET-GW-3 can behave as a foreigndevice when communicating with a third-party BBMD (BAC-net Broadcast Management Devices).

• Compatible with standard and high-speed NOTI•FIRE•NET

Specifications• Complies with: UL 864 9th Edition; and CAN/ULC-S559-

04, 1st Edition Standard for Control Units for Fire AlarmSystems.

• Complies with NFPA 72 National Fire Alarm Code.• Conforms to BACnet Standard Annex J for IP and Support

Device Objects, Binary Output Objects, Life Safety Points/Zones, and Multi-State Inputs.

• Power supply: 24 VDC @450mA nominal and supervisedbattery backup.

• Operating temperature: 32°F to 120°F (0°C to 49°C).

Connections• The BACNET-GW-3 is connected to NOTI•FIRE•NET via

the network port on the network control module to the Gate-way.

• BACNET-GW-3 is connected to the BACnet front end via astandard RJ45 Ethernet connector (CN2).

• The BACNET-GW-3 assembly installs in one row of aCAB-3 or CAB-4 Series cabinet using a CHS-4 or CHS-4Lchassis. The PNET-1 surge suppressor is connected to theBACnet Ethernet via a RJ45 Ethernet connector.

Agency Listings and ApprovalsThe listings and approvals below apply to the BACNET-GW-3.In some cases, certain modules or applications may not belisted by certain approval agencies, or listing may be in pro-cess. Consult factory for latest listing status.

• UL Listed: file S635.• ULC Listed: file S635.

Product Line InformationThe BACNET-GW-3 (ordered as such) includes everythingrequired to set up an interface to an existing NOTIFIER systemor network with the exception of a chassis and the NetworkControl Module (NCM). It includes:

• PC board for the BACNET-GW-3.

• Software on CD-ROM (Configuration Tool). • RJ45 to RJ45 Standard Ethernet Network Cable (PN 75585). • NUP to NUP cable (PN 75556).

Additional required components (from other vendors):

• IBM-compatible PC with Windows XP.• Standard Ethernet network cable with RJ45 connectors.

PIC Statement/BACnet InformationThe BACNET-GW-3 PIC Statement is available atwww.notifier.com. Select products and then network sys-tems. For information on the BACnet protocol, see www.bac-net.org.

6877

cov.

psd

Page 2: BACnet-GW-3- DN_6877

Page 2 of 2 — DN-6877:B • 06/08/2009

NOTIFIER®, ONYX®, and ONYXWorks® are registered trademarks of andNOTI•FIRE•NET™ is a trademark of Honeywell International Inc. BACnet® isa registered trademark of the American Society of Heating, Refrigerating andAir-Conditioning Engineers (ASHRAE). Microsoft® and Windows® areregistered trademarks of Microsoft Corporation. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.www.notifier.com

Made in the U.S. A.

System Architecture

Single-Panel Diagram

Single NFN Network Diagram

FACP

BACnet/IP Client

BACNET-GW-3

IP connection over Ethernet

NUP connection

FACP

FACP

BACnet/IP Client

BACnet/IP Client

Network Control Module

BACNET-GW-3

FACP

FACP

IP Network NOTI•FIRE•NET Network

IP connection over Ethernet

NUP to

NUP