20
Data Aire, Inc. dap4 BACnet Protocol Integration Instructions Data Aire, Inc. 230 West BlueRidge Ave, Orange, CA 92865 Document number: 600000959 August 2011 Revision 1.0

Data Aire, Inc. dap4 BACnet Protocol Integration Instructions · 2019. 6. 21. · Data Aire’s dap4 BACnet BMS Document: 600-000-959 3 I. BACnet IP - Setup Procedures for dap4 Ethernet

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

  •  

     

     

     

      

     

     

    Data Aire, Inc. 

    dap4 

    BACnet Protocol Integration Instructions  

     

     

     

     

     

     

     

    Data Aire, Inc. 230 West BlueRidge Ave, 

    Orange, CA 92865  

    Document number: 600‐000‐959 August 2011 Revision 1.0 

      

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     2

    Table of Content

    I. BACnet IP –Setup Procedures for dap4 Ethernet Card ........................................ 3 II. BACnet MS/TP – Setup Procedures for dap4 MS/TP Card .................................. 6

    A. Startup Checklist for dap4 BACnet MS/TP card B. General Procedure for setting up BACnet MS/TP Card

    III. Troubleshooting Flow Charts ................................................................................ 9 IV. BACnet Object Definition .................................................................................... 12

     

     

     

     

     

     

                     

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     3

     

    I. BACnet IP - Setup Procedures for dap4 Ethernet Card Note: When connecting to the Ethernet card, a crossover cable must be used

    1. Configure BMS PORT 1 into BACnet protocol in Menu G: Network Config of the dap4

    controller.

    2. All Ethernet cards were set up for a DHCP server. You must give the card its factory IP address to access the card and then switch it to the Ethernet protocol.

    3. To do a factory reboot of the card, shut of power to the dap4 controller. Next, press

    and hold the button on the card. Now, power on the dap4 controller. Wait approximately 20 seconds until the status LED begins to blink red 3 times slowly. After the first Red blink, release the push button. After releasing the button, wait approximately 50 seconds and the card is now able to be communicated to.

    4. The default settings for the card are as follows.

    IP address – 172.16.0.1 Net Mask – 255.255.0.0 Device Inst - 77000

    5. Once you have reset the Ethernet card, you must now configure your network card in your PC to 172.16.0.* * any value other then 1.

    6. After your PC’s network card is configured, open internet explorer and enter the card’s

    IP address (172.16.0.1.) 7. The following prompt will be displayed on your PC’s Screen (user name – admin,

    password – fadmin)

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     4

    8. After entering the correct information to log on to the Ethernet card, you will be taken to

    the following screen.

    9. Click the configuration tab on the left. Then click on the BACnet tab across the top of the screen.

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     5

    10. This field is where you can change the settings for the card. The device instance of the card is changed beside the pCOWeb Device Inst text. Each card must have its own unique device instance.

    11. The variable ranges can be set on the same page. Scroll to the bottom to change

    these ranges.

    12. After you have set up your card, click Submit.

    13. After your changes have been accepted, you may now change you IP address (if applicable.) While still under the configuration tab, click network across the top of the screen.

    14. Under Eth0, change the IP address and Netmask to your desired values. 15. Scroll to the bottom of the screen and click submit.

    16. It will take approximately 5 minutes for the IP address change to take

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     6

    II. BACnet MS/TP - Setup Procedures for dap4 MS/TP Card

    A. Startup Checklist for dap4 BACnet MS/TP card

    1. Configure BMS PORT 1 into BACnet protocol in Menu G: Network Config of the dap4 controller.

    2. MS/TP card is installed in dap4 control (if yes, skip to step 5. If no, contact the manufacturer of your unit to make sure that the card is configured before proceeding to next step.)

    3. Disconnect the power supply from the dap4 and remove the serial card cover

    4. insert card in dap4 control. Line up the white terminal block on the card with pins in the serial card slot. Press firmly until card is fully seated in dap4.

    5. Fit the cover supplied with the BACnet MS/TP card.

    6. Run 18 AWG twisted pair shielded cable from your network to the BACnet MS/TP card. Make sure (+) goes to the middle of the terminal block while (–) goes to the right connection

    7. Power on the dap4 control.

    8. Status lights match following sequence:

    Starting sequence: on power-up, or after restarting BACnet MS/TP card, the Status LED switches in the following sequence:

    - 2 seconds after restarting: quick flash red-green-red-green - 5 seconds after restarting: green on steady - Around 50 seconds after restarting, the starting sequence has been completed, the

    Status LED flashes to indicate the quality of communications with the dap4. - Quick green-OFF-green: communication with the dap4 is OK (dap4 ON-LINE); - Slow red-OFF-red: communication has not been established with the dap4 (dap4

    OFF-LINE) - Green-red-green: BACnet MS/TP card detects errors or a temporary lack of response

    from the dap4.

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     7

    The RS485 LED (right) indicates the status of communication with the BACnet MS/TP network (RS485). Starting sequence: on power-up or after rebooting BACnet MS/TP card, the RS485 LED switches in the following sequence:

    - After approximately 50 seconds after restarting BACnet MS/TP card: slow green–red–green–red: at the end, BACnet will be active. Status of communication with the BACnet MS/TP network: once the starting sequence has been completed, the RS485 LED flashes to indicate the quality of communication with the BACnet MS/TP network:

    - Green with occasional red flashes if communication is OK.

    B. General Procedure for setting up BACnet MS/TP Card

    Before starting the following steps, a RS485-USB adapter and Carel software BACset must be present. BACset, free software compatible for BACnet is available for download at http://www.carel.com.au/carelksa/web/eng/home.jsp. Get the latest version by going into the pCOweb tab and select BACnet.

    1. After BACset has been installed, click on the MS/TP protocol. If you are using a router, select the correct router configuration. Once these two fields have been selected, click ok.

    2. The following screen will now be presented.

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     8

    3. All cards from factory come with a factory default device instance of 77000. This value must match the device instance of the card in order to be able to read/write to the card.

    4. The MS/TP station address (MAC Address) is defaulted to 0. Set this field to your desired address. *If you have 5 cards, all 5 cards must have different station addresses (1, 2, 3, 4, 5)*

    5. Max Master field must be changed to the highest station address on the network. If the highest station address is 10, Max Master must be set to 10.

    6. Assuming the dap4 controller is not the true master of the communications system, Max Info Frames should be set =< the Max Info Frames of your BAS.

    7. The following fields should be changed to the maximum number of variables being communicated by the dap4 controller. If you have 40 analog variables, Max pCO Analogs should be set to 40.

    8. Once all fields have been set accordingly, click Write at the top of the BACset program. The Read/Write status bar will start at 0% and go to 100%. Once at 100%, the write has been completed.

    9. After all of the prior steps have been completed, you may now change the device instance of the card. *Note* This value must be different from card to card. There can be no conflicting device instances on the same network.

    10. To change the device instance, click enable on the enable/disable device instance write. Once this is selected, you will be able to enter a value in the device instance write box that was originally grayed out. *All cards must have a different device instance and cannot conflict with any other unit’s device instance in the system*

    11. Change the device instance to desired value and then click Write.

    12. Once the status bar is at 100%, the card now has the new device instance.

    C. Troubleshooting Flow Charts BACnet IP and MS/TP

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     9

    In addition, if the following error occurs when starting BACset in the MS/TP protocol, continue to the following section.

    1. Open BACset and click on the BACnet/IP protocol.

    Values are being communicated through BACnet protocol and considered reliable 

    All values are “0” from startup and/or deemed unreliable 

    Dap4 control set for BAUD rate of 19200, station address of 1 and protocol BACnet   

    Adjust setting on dap4 control, contact Data Aire service if required 

    Card has latest firmware on it? 

    Go to http://ksa.carel.com , under Connectivity tab, click pCOweb, then choose the latest firmware 

    Has BMS supervisory system autodiscovered all points correctly? 

    Contact Data Aire Service to make sure BACnet card is configured 

    correctly 

    Communication works correctly   

    Have BMS contractor auto‐discover all the units in question 

    Values appear reliable, but “freeze” or periodically go to “0” and a power start is required

    Yes 

    No 

    Yes 

    Yes 

    Yes 

    No 

    No 

    Yes 

    No 

    Yes 

    No 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     10

    2. If you receive the following error when attempting to open BACnet/IP, please skip to step 10.

    3. At this point you should be able to double-click the bac door client that is running in your system tray. (Icon on the far left.)

    4. Select the configure menu. 5. Set the MS/TP parameters Com Port (restart) to be correct for your 485 converter

    6. Click OK

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     11

    7. Close BACset.

    8. Reopen BACset and select the MS/TP protocol.

    9. You should now be able to run BACset.

    10. Go to your network adapter properties and remove the BACMAC protocol.

    11. Re-boot

    12. Open up BACnet/IP

    13. You should see the same error but when it searches for a new IP it should find the proper one.

    14. Go back to step 3 and follow the recommended procedure to configure you COM port

      

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     12

    BACnet Object Definitions  

    Type  Object Description  Read/Write Object Name  Instance No. Analog  Temperature of return air     R  Ret_Air_Tmp  AV1 

    Analog  Maximum Return air temp in last 24hrs  R  Maximum  AV2 

    Analog  Minimum Return air temp in last 24hrs  R  Minumum  AV3 

    Analog  Temperature setpoint       R/W  Temp_Setpoint  AV4 Analog  comp is staged on     R/W  Temp_Deadband  AV5 Analog  Humidity Sensor Calibration      R  Ain_offs  AV6 Analog  Calibration        R  Ain_offs  AV7 Analog  Temperature of chilled water  *   R  CW_Tmp  AV8 Analog  Temperature of discharge air   *  R  Disch_Air_Tmp  AV9 Analog  Calibration ‐ Optional discharge*   R  Ain_offs  AV10 Analog  Sensor Calibration ‐ Optional   *  R  Ain_offs  AV11 Analog  Chilled water is requested *   R/W  EngSaver_Setpoint  AV12 Analog  Value of the analog input  *  R  Opt1_Analog  AV13 Analog  Value of the analog input  *  R  Opt2_Analog  AV14 Analog  Value of the analog input  *  R  Opt3_Analog  AV15 Analog  Value of the analog input  *  R  Opt4_Analog  AV16 

    Analog  Analog Sensor 1 Minimum Value  *  R  Y1  AV17 

    Analog  Analog Sensor 1 Maximum Value  *  R  Y2  AV18 

    Analog  Analog Sensor 1 Calibration   *  R  Ain_offs  AV19 

    Analog  Analog Sensor 2 Minimum Value *   R  Y1  AV20 

    Analog  Analog Sensor 2 Maximum Value  *  R  Y2  AV21 

    Analog  Analog Sensor 2 Calibration   *  R  Ain_offs  AV22 

    Analog  Analog Sensor 3 Minimum Value  *  R  Y1  AV23 

    Analog  Analog Sensor 3 Maximum Value  *  R  Y2  AV24 

    Analog  Analog Sensor 3 Calibration   *  R  Ain_offs  AV25 

    Analog  Analog Sensor 4 Minimum Value  *  R  Y1  AV26 

    Analog  Analog Sensor 4 Maximum Value  *  R  Y2  AV27 

    Analog  Analog Sensor 4 Calibration   *  R  Ain_offs  AV28 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     13

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Integer  Lower limit alarm of discharge air temp *  R/W   Disch_Air_Lo_SP  AV1001 

    Integer  Relative humidity displayed as xx%   R   Humidity_dis  AV1002 

    Integer Cooling Stages On = Cooling stages are currently on â€“ This point applies to DX unit only  

    R/W   Stages_On  AV1003 

    Integer  Number of heat stages running   R   Heaters_On  AV1004 

    Integer  Maximum humidity in last 24hrs  R   Maximum   AV1005 

    Integer  Minimum humidity in last 24hrs  R   Minumum   AV1006 

    Integer 

    Cooling Utilization Over Last Hour ‐Percentage of cooling is used in the last hour of operation; this point applies to DX unit. 

     R   Comp_duty   AV1007 

    Integer 

    Heating Utilization Over Last Hour ‐Percentage of heating is used in the last hour of operation  

    R   Heat_duty   AV1008 

    Integer 

    Humidifier Utilization Over Last Hour ‐Percentage of humidifier is used in the last hour of operation  

    R  Hum_duty  AV1009 

    Integer Compressor 1 Runtime ‐This point applies to DX unit with one compressor ‐high  

    R   C1_Hours_H   AV1010 

    Integer Compressor 1 Runtime ‐This point applies to DX unit with one compressor ‐low  

    R   C1_Hours_L   AV1011 

    Integer Compressor 2 Runtime ‐This point applies to DX unit with dual compressor ‐ high  

    R   C2_Hours_H  AV1012 

    Integer Compressor 2 Runtime ‐This point applies to DX unit with dual compressor ‐ low  

    R   C2_Hours_L   AV1013 

    Integer   Heater 1 Runtime ‐ high   R   Ht1_Hours_H   AV1014 Integer   Heater 1 Runtime ‐ low   R   Ht1_Hours_L  AV1015 Integer   Current second   R   CURRENT_SECOND   AV1016 Integer   Current minute   R   CURRENT_MINUTE   AV1017 Integer   Current hour   R   CURRENT_HOUR  AV1018 Integer   Current day   R   CURRENT_DAY  AV1019 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     14

    Type  Object Description  Read/Write Object Name  Instance No. Integer  Current month   R   CURRENT_MONTH   AV1020 Integer  Current year   R   CURRENT_YEAR   AV1021 

    Integer Alarm settting of return air temp to determine there is a fire  

    R/W   Firestat_SP   AV1022 

    Integer  Humidity upper limit alarm   R/W   Hum_Hi_SP   AV1023 

    Integer  Upper limit alarm of return air temp   R/W   Ret_Air_Hi_SP   AV1024 

    Integer  Humidity lower limit alarm   R/W   Hum_Lo_SP   AV1025 

    Integer  Lower limit alarm of return air temp   R/W   Ret_Air_Lo_SP  AV1026 

    Integer  Amount hum must change from setpoint before acting   R/W   Hum_deadband  AV1027 

    Integer  Humidity setpoint   R/W   Hum_setpoint  AV1028 

    Integer  Time before the system starts up   R/W   Start_dly   AV1029 

    Integer  Optional Alarm 1 Delay   R   Del  AV1030 Integer  Optional Alarm 2 Delay   R   Del   AV1031 Integer  Optional Alarm 3 Delay   R   Del   AV1032 

    Integer  Message on optional alarm screen, some also add function   R   Alarm1_txt  AV1033 

    Integer  Message on optional alarm screen, some also add function   R   Alarm2_txt   AV1034 

    Integer  Message on optional alarm screen, some also add function   R   Alarm3_txt   AV1035 

    Integer  Message on optional alarm screen, some also add function   R   Alarm4_txt   AV1036 

    Integer 

    Comps 0=none, 1=one,Carel Side BMS Side 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit  

    R   Comp_sel  AV1037 

    Integer 

    0=none, 1= comp limited,2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited  

    R   Dehum_mode   AV1038 

    Integer  Number of heat stages   R   Reheat_sel  AV1039 

    Integer 0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod 

     R   Hum_sel   AV1040 

    Integer  Text displayed on all alarm screens   R   Alm_Contact_msg   AV1041 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     15

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Integer 0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm  

    R   PowerUp_sel   AV1042 

    Integer  0=None, 1=short beeps, 2=long beep, 3=Constant   R   Buzzer_Select   AV1043 

    Integer  % of 10volts of analog output #1  R  CW_disp  AV1044 

    Integer 

    Chilled Water Utilization Over Last Hour ‐ This applies to Chilled water or Energy saver units.  

    R   WtrVlv_duty  AV1045 

    Integer  Humidifier Runtime ‐ high   R   Hum_Hours_H  AV1046 Integer  Humidifier Runtime ‐ low   R   Hum_Hours_L   AV1047 Integer  Blower Runtime ‐ high   R   Blower_Hours_H   AV1048 Integer  Blower Runtime ‐ low   R   Blower_Hours_L   AV1049 Integer  Optional Alarm 4 Delay   R   Del  AV1050 

    Integer 0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4...  

    R   Assist_sel  AV1051 

    Integer Water valve type 0=none,1=chill, 2=Engy, 3=Aux chill,4=Disc Reg  

    R   WtrVlv_sel   AV1052 

    Integer  Water valve voltage 0= 0‐10, 1=2‐10, 2=7‐10, 3=6‐9, 4=4‐7   R   WtrVlv_Volts_sel   AV1053 

    Integer  % of 10volts of analog output #2  R   Hum_Volts   AV1054 Integer  Dehumidifier Runtime ‐ High   R   Dehum_Hours_H   AV1055 Integer  Dehumidifier Runtime ‐ Low   R   Dehum_Hours_L  AV1056 

    Integer Time between drain cycles 0=12hr, 1=24hr, 2=48hr,3=96hr, 4=None  

    R   AutoFlush_dly   AV1058 

    Integer  Value sent to optional analog output#1   R   Y4_Out  AV1059 

    Integer  Value sent to optional analog output#2   R   Y5_Out  AV1060 

    Integer Current Fan Airflow ‐ Based on calculated Pressure Differential formula*  

     R  Air_Flow   AV1061 

    Integer  Name of the sensor *  R   Opt_Snsr1_name   AV1062 Integer  Analog Sensor 1 Type {0=NTC 

    1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} * 

     R   Ain_type   AV1063 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     16

    Type  Object Description  Read/Write Object Name Instance 

    No. Integer  Name of the sensor  *  R  Opt_Snsr2_name  AV1064 

    Integer 

    Analog Sensor 2 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} * 

     R   Ain_type   AV1065 

    Integer   Name of the sensor *  R  Opt_Snsr3_name  AV1066 

    Integer 

    Analog Sensor 3 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} * 

     R   Ain_type   AV1067 

    Integer  Name of the sensor *  R  Opt_Snsr4_name  AV1068 

    Integer 

    Analog Sensor 4 Type {0=NTC 1=PT1000 2=0‐1VDC 3=0‐10VDC 4=4‐20mA 5=ON/OFF 6=0‐5VDC 7=NTC HT 8=‐50T90 9=10T170} * 

    R   Ain_type   AV1069 

    Integer  CW Fan speed (%) sent via BMS   R/W   CW_Fan_Speed_bms   AV1070 Integer  DX Fan speed (%) sent via BMS   R/W   DX_Fan_Speed_bms   AV1071 

    Integer  Maximum Fan speed (% of output) modulation.   R/W   Fan_Speed_max   AV1072 

    Integer Minimum Fan speed (% of output) modulation from pressure.  

    R/W   Fan_Speed_min  AV1073 

    Integer  Fan pressure setpoint (0.01inches of water) *  R/W   Fan_Pr_sp   AV1074 

    Integer  Fan pressure band (0.01 inches of water)  *  R/W   Fan_pr_band   AV1075 

    Integer Maximum air flow limit of setpoint from BMS or valve modulation.  

    R/W   Fan_AF_max  AV1076 

    Integer Minimum air flow limit of setpoint from BMS or valve modulation.  

    R/W   Fan_AF_min   AV1077 

    Integer  Fan K Factor   R/W   Fan_Kfactor  AV1078 

    Integer  Number of fans installed in this unit   R/W   Num_Fans   AV1079 

    Integer  Heater 2 Runtime ‐ high   R   Ht2_Hours_H   AV1081 Integer  Heater 2 Runtime ‐ low   R   Ht2_Hours_L   AV1082 Integer  Heater 3 Runtime ‐ high   R   Ht3_Hours_H  AV1083 Integer  Heater 3 Runtime ‐ low   R   Ht3_Hours_L  AV1084 Integer  Energy Saver Runtime ‐ This 

    optional point applies to energy saver units only –high      * 

     R   Engy_Hours_H  AV1085 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     17

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Integer Energy Saver Runtime ‐ This optional point applies to energy saver units only ‐ low  

    R   Engy_Hours_L   AV1086 

    Integer Chilled Water Runtime ‐ This applies to chilled water units only ‐ high 

     R   CW_Hours_H  AV1087 

    Integer Chilled Water Runtime ‐ This applies to chilled water units only ‐ low 

     R   CW_Hours_L  AV1088 

    Integer 

    Compressor 3 Runtime ‐ This applies when unit has four stages tandem compressors ‐high  

    R   C3_Hours_H  AV1089 

    Integer 

    Compressor 3 Runtime ‐ This applies when unit has four stages tandem compressors ‐low  

    R   C3_Hours_L  AV1090 

    Integer 

    Compressor 4 Runtime ‐ This applies when unit has four stages tandem compressors. ‐high  

    R   C4_Hours_L  AV1091 

    Integer 

    Compressor 4 Runtime ‐ This applies when unit has four stages tandem compressors. ‐low  

    R   C4_Hours_H  AV1092 

    Integer  Condenser Runtime ‐ high   R   Cond_Hours_H   AV1093 Integer  Condenser Runtime ‐ low   R   Cond_Hours_L  AV1094 

    Integer  Fan speed (% of output) when compressor cooling.   R   DX_Fan_Speed  AV1095 

    Integer  Fan speed (% of output) when cold water cooling.   R   CW_Fan_Speed  AV1096 

    Integer  Fan air flow setpoint for DX unit (cfm) *  R   Fan_AF_DX_sp  AV1097 

    Integer  Fan air flow setpoint for CW unit (cfm)  *  R   Fan_AF_CW_sp  AV1098 

    Integer  Zone Airflow Setpoint kcfm *   R/W   ZM_Airflow_SP   AV1099 Digital  Dehumidify mode is running   R   Dehum_On   BV1 Digital  Humidifier is running   R   Hum_On  BV2 Digital  Energy saver is running   R   Engy_On  BV3 

    Digital  Cooling inhibit from Zone Master *  R   Cool_Inhibit  BV4 

    Digital  Heat inhibited due to alarm condition   R   Heat_Held   BV5 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     18

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Digital  Humidifier stopped due to alarm   R   Humidifier_inhibit  BV6 

    Digital  Dehum is inhibited   R   Dehum_Inhibit   BV7 Digital  Reheat during dehum   R   Rht_during_dehum   BV8 Digital  Water under floor alarm   R   Floor_Wtr_alm  BV9 Digital  No air flow alarm   R   Air_Flow_alm   BV10 Digital  Dirty filter from digital input   R   Filter_alm   BV11 

    Digital  Alarm from humidifier digital input *  R   Humidifier_alm   BV12 

    Digital  Temperature of return air above firestat alarm set point   R   Firestat_alm   BV13 

    Digital  One or more comps has short cycled   R   Shortcycle_alm   BV14 

    Digital  Sensor is out of range   R   Humidity_fail   BV15 Digital  Sensor is out of range   R   Ret_Air_fail  BV16 

    Digital  Maintenance Schedule Due alarm   R   Maint_alm   BV17 

    Digital  High pressure alarm   R   C1_HP_alm  BV18 Digital  Low pressure alarm   R   C1_LP_alm  BV19 Digital  High pressure alarm   R   C2_HP_alm  BV20 Digital  Low pressure alarm   R   C2_LP_alm  BV21 

    Digital  Smoke detected from digital input  *   R   Smoke_alm  BV22 

    Digital  No water flow alarm  *   R   Wtr_Flow_alm  BV23 Digital  Sensor is out of range   R   Disch_Air_fail  BV24 

    Digital  Temperature of return air above alarm set point   R   RA_Tmp_hi_alm  BV25 

    Digital  Temperature of return air below alarm set point   R   RA_Tmp_lo_alm  BV26 

    Digital  Humidity above alarm set point   R   Hum_hi_alm  BV27 Digital  Humidity below alarm set point   R   Hum_lo_alm  BV28 Digital  Fan overload  R  Fan_Overload  BV29 

    Digital 

    Standby pump on: Check primary pump ‐Optional alarm. Pump failure input signal required * 

    R  Stdby_Pump_On  BV30  

    Digital  Custom alarm #1 ‐Optional alarm. External alarm input required. Factory programmed custom message required * 

     R   Cust_msg_Sw1   BV31 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     19

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Digital 

    Custom alarm #2 ‐Optional alarm. External alarm input required. Factory programmed custom message required * 

     R   Cust_msg_Sw2    BV32 

    Digital 

    Custom alarm #3 ‐Optional alarm. External alarm input required. Factory programmed custom message required * 

     R   Cust_msg_Sw3   BV33 

    Digital 

    Custom alarm #4 ‐Optional alarm. External alarm input required. Factory programmed custom message required  * 

     R    Cust_msg_Sw4   BV34 

    Digital  Humidifier stopped due to custom alarm switch   R   HumSw_Inhibit   BV35 

    Digital  Heat inhibited due to custom switch alarm condition   R   Heat_inhibit   BV36 

    Digital  Reheat and humidification inhibited from operation   R   Rht_Hum_inhibit   BV37 

    Digital  Temperature of discharge air below alarm set point  *  R   Disch_Tmp_lo_alm   BV38 

    Digital 

    Manual override: Check bypassswitches ‐ Standard alarm.Carel Side BMS Side Manual override switch is on  

    R   Override_Alm   BV39 

    Digital  High condensation from digital input   *  R   Condensation_alm  BV40 

    Digital 

    Unit in standby, all functions held off ‐ Optional alarm. Control input signal required Factory setting required   * 

    R   Unit_In_Standby  BV41 

    Digital  Sensor is out of range   R   CW_sns_fail  BV42 

    Digital  Humidifier stopped due to custom alarm switch   R   HumSw_Chk_Cyl   BV43 

    Digital  Cooling operation inhibited by BMS   R/W   BMS_Cooling_inhibit   BV44 

    Digital  Heat inhibited due to BMS   R/W   BMS_Heat_inhibit   BV45 

    Digital  Humidifier operation inhibited by BMS   R/W   BMS_Humidifier_inhibit  BV46 

    Digital  Dehumidify mode inhibited by bms   R/W   BMS_Dehum_inhibit   BV47 

    Digital  Inhibit fan by bms   R/W   Fan_Inhibit_bms   BV48 Digital  Reduce control humidity cycling       R   Hum_Expect  BV49 

    *: These points are optional – Optional sensors or components required 

  • Data Aire’s dap4 BACnet BMS

    Document: 600-000-959     20

    Type  Object Description  Read/Write Object Name Instance 

    No. 

    Digital  Temperature Mode 0=°C 1=°F   R/W   USASHR_F_C  BV50 

    Digital  Lead compressor select 0= C1,1= C2   R   Lead_Comp  BV52 

    Digital  Water valve direct or reverse acting   R   WtrVlv_dir  BV53 

    Digital Alarm: UPS power on: Check main power ‐Optional alarm. External alarm input required * 

    R   Ups_On_alm  BV54 

    Digital  Loss of power requires manual reset of alarm   R   PwrUp_alm   BV55 

    Digital Local alarm #1: See tag inside door =Optional alarm. External alarm input required  

    R   SeeTag_cust_alm1   BV56 

    Digital Local alarm #2: See tag inside door =Optional alarm. External alarm input required  

    R   SeeTag_cust_alm2   BV57 

    Digital Local alarm #3: See tag inside door =Optional alarm. External alarm input required  

    R   SeeTag_cust_alm3   BV58 

    Digital Local alarm #4: See tag inside door =Optional alarm. External alarm input required  

    R   SeeTag_cust_alm4   BV59 

    Digital  Enable short cycle alarm of the compressors   R   ShortCycle_alm_en   BV60 

    Digital 

    Supervisor (BMS) On‐Off. Show the state OFFbyBMS in main mask (1: Off; 0: On). See Instance BV62 for detail 

    R/W  Superv_Off  BV61 

    Digital This variable must change at least once every 5 minutes or unit will turn on 

    R/W  BMS_Heartbeat  BV62 

     *: These points are optional – Optional sensors or components required