    Improving Electrical Power Qualityfor the Water Industries

  • 8/8/2019 Arteche PQfor Water

    2/20

    2

    Types of CommonPower Quality Problems

    Harmonic Distortion

    Radio FrequencyInterference

    PWM Voltage

    Voltage SagVoltage Swell

    Voltage Transient

    Low Power Factor

    30 90 180 270

    Voltage Current

    -

  • 8/8/2019 Arteche PQfor Water

    3/20

    3

    What are the PQ IssuesFacing the Water Industries?

    1) Power Factor

    Motors typically cause low power factor

    2) Harmonics

    VFDs cause harmonics

    3) Motor life when controlled by VFDs

    Motors can be susceptible to PWM voltage

    produced by VFDs

  • 8/8/2019 Arteche PQfor Water

    4/20

  • 8/8/2019 Arteche PQfor Water

    5/20

    5

    1.) What are the benefits ofImproving Power Factor?

    High Power Factor saves energy

    High Power factor can reduce energy

    costs (eliminate PF penalties)

    High Power Factor reduces load (KVA)on existing transformers more

    capacity available for new loads

  • 8/8/2019 Arteche PQfor Water

    6/20

    6

    0

    10

    2030

    40

    50

    60

    70

    80

    90

    100

    1 0.8 0.6 0.4 0.2

    Working Power KkW)

    Reactive Power (kVAr)

    Utility supplies Reactive VARs you pay for it!

    Motors demand bothReactive VARs and

    working power (watts)

    Useful Power

    ActualKVA

    Available Transformer KVA vs. Power Factor

  • 8/8/2019 Arteche PQfor Water

    7/20

  • 8/8/2019 Arteche PQfor Water

    8/20

    8

    2.) What are the benefits ofReducing Harmonics?

    Improve facility voltage quality

    Reduce TRMS current and KVAsupplied by transformer

    Stop C/B tripping and fuse blowing

    Protect power factor capacitors

  • 8/8/2019 Arteche PQfor Water

    9/20

    9

    Harmonics Cause SystemVoltage Distortion

    ASD ASD ASD

    Load Current

    -1 0

    -1 0

    - 0

    - 0

    - 0

    - 0

    0

    0

    0

    0

    0

    1 0

    1 0

    . . 1 . 1 . . . . . 4 . 4 .

    THiD = 7.54%

    Voltage is Distorted

    Other

    LinearLoads

    Loads fed with distorted voltage may malfunction

  • 8/8/2019 Arteche PQfor Water

    10/20

    10

    ARTECHE SOLUTIONS

    FOR HARMONICS PROBLEMS

    Dynamic Filter

    Active Filter

    Line Reactor

    Tuned Filter

    Low Pass FilterAutomatic Filter

    12 & 18 Pulse Upgrade Kit

  • 8/8/2019 Arteche PQfor Water

    11/20

    11

    HARMONIC MITIGATION

  • 8/8/2019 Arteche PQfor Water

    12/20

  • 8/8/2019 Arteche PQfor Water

    13/20

    13

    ARTECHE PQ HarmonicMitigation Alternatives

    0%

    10%

    20%

    30%

    40%

    50%

    Line

    reactor

    Tuned

    filter

    Low

    pass

    filter

    12-pulse 18-pulse Active

    filter

    We can combine multiple technologies to achieve the besteconomical solutions for one or more loads.

  • 8/8/2019 Arteche PQfor Water

    14/20

    14

    Best Economical Solution toMinimize Harmonics

    % Harmonic Current Distortion vs. %ZeffStandard (KS) Version LPF

    01

    2

    3

    4

    5

    6

    100%

    87.5%

    75%

    62.5%

    50%

    37.5%

    30%

    25%

    12.5%5%

    % LOAD

    %T

    HD-I

    0.10% Zeff

    0.25% Zeff

    0.5% Zeff

    1% Zeff

    2% Zeff

    3% Zeff

    4% Zeff

    5% Zeff

    Available as: OEM Kits Panel version Metal Enclosed

    No Filter With Arteche LPF

  • 8/8/2019 Arteche PQfor Water

    15/20

    15

    Single Phase Harmonic Filters

    3rd Harmonic FilterPlug-In

    Low Pass Harmonic Filter

    3rd Harmonic FilterBranch Circuit

    Distributed GenerationHarmonic Filter

  • 8/8/2019 Arteche PQfor Water

    16/20

    16

    18-Pulse Upgrade KitFOR WWTPs

    Data for full load

    Upgrade VFDs from 6-pulse to18-pulse:New installations, orRetrofits

  • 8/8/2019 Arteche PQfor Water

    17/20

    17

    3.) What are the benefits of convertingPWM to Sine Wave Voltage?

    You can use any length of motor cable.

    Motors run cooler when supplied with

    sine wave voltage.

    Motors last longer when supplied withsine wave voltage.

  • 8/8/2019 Arteche PQfor Water

    18/20

    18

    Sine Wave Filters

    :32:04.56 14:32:04.57 14:32:04.58 14:32:04.59 14:32:04.60 14:32:04.61 14:32:04.

    Volts

    - 0

    - 0

    - 0

    0

    0

    0

    0

    23:59.82

    14:23:59.83

    14:23:59.84

    14:23:59.85

    14:23:59.86

    14:23:59.87

    14:23:59.

    o s

    Convert PWM voltage waveforms to sine waves!

    Our standard SWF is for Carrier Frequency of 5kHZ or higher.Others available on request.

  • 8/8/2019 Arteche PQfor Water

    19/20

    19

    Economical Solutions for all

    of your Power Quality Needs.FACILITY (CENTRALIZED) SOLUTIONS

    HarmonicFilters

    Power FactorCapacitors

    HarmonicFilters

    Power FactorCapacitors

    LOW VOLTAGE

    Up to 600 Volts

    MEDIUM VOLTAGE

    Up to 34.5 kV

    Harmonic Filters

    Power FactorCapacitors

    AUTOMATIC SOLUTIONS

    Harmonic Filters Power FactorCorrection

    Systems

    Low Voltage(600V)

    Medium Voltage(up to 35kV)

    DYNAMIC SYSTEMS

    Sub-cycleresponse time

    Harmonic Filters

    Power FactorCapacitors

    600 volt class up to 35kV class

    INDIVIDUAL (LOCALIZED) SOLUTIONS

    600Volt Class

    up to 34.5kV