Upload
antoine-ouzilleau
View
221
Download
0
Embed Size (px)
Citation preview
8/10/2019 Arc Flash Hazard in w Pp
1/8
1
Abstract The topic of this paper is the arc-flash hazard in
Wind Power Plants (WPP). A brief introduction of the concept
of arc flash is followed by the presentation of a methodology to
perform an arc-flash hazard analysis on a WPP collector system.
Issues such as faults being fed by multiple sources, as well as the
modeling of the fault current of the wind turbine generator are
addressed. The paper concludes with two examples using the
presented methodology.
Index Terms Arc-flash hazard, shock hazard, wind powerplants.
I. INTRODUCTION
This paper investigates and discusses the arc-flash hazard
in a Wind Power Plant (WPP) collector system. It will define
an arc-flash calculation methodology for multiple sources and
provide two examples of the methodology.
The approach this paper will be as follows: Section II dis-
cusses the arc-flash hazard in general the causes of arcs, the
available models to calculate incident energy levels and cer-
tain concerns, which are specific to wind power plants. Sec-
tion III describes the possible mitigation strategies defining
an arc-flash protection boundary, the types of personal protec-
tive equipment (PPE) available, and possible means of reduc-
ing incident energy levels through various technologies. Sec-
tion IV presents a detailed, structured method to calculate arc-
flash incident energy levels in a WPP. Section V concludes
the paper with two examples.
II. ARC-FLASH HAZARD
A. General Description of Arc-flash Hazard
An electric arc is the result of the electrical breakdown of
an insulator (typically air) resulting in current flowing through
the insulator. An arc-flash fault is often caused by:
Human mistake (e.g., dropping a tool, accidental con-tact with live parts)
Environment (e.g., contamination, water vapor)
Equipment failure (e.g., insufficient insulation, deteri-orated insulation, corrosion)
Overvoltage conditions
A combination of the above.
In power systems the path of the arc can be between two
phases, multiple phases, single phase and ground, and multiple
phases and ground. The arc flash is surrounded by a conduc-
tive plasma cloud and often vaporized conductive material,
which increases the likelihood of a single-phase fault making
contact with nearby phases and escalating into a three-phasefault. This is more likely to happen on systems with low insu-
lation level and at locations with small clearance between
conductors, such as low-voltage systems and switchgear
equipment. For these cases a single-phase fault often escalates
into a three-phase fault within a few milliseconds (Schau and
Stade, 1995).
A large amount of energy is released during an arc flash,
primarily in the form of heat. The burn hazard during an arc
flash is the main concern for worker safety (e.g. Lee, 1982).
Additionally, the energy released in the form of pressure is of
concern for worker safety since the pressure wave can directly
injure the worker or can destroy objects resulting in shrapnel
that can injure the worker (Lee, 1987). The part of the arcflash that is associated with the release of a pressure wave is
commonly referred to as the arc blast (Dugan, 2007).
The arc-flash fault current is generally smaller than the
bolted fault current of the system due to the impedance of the
arc. The incident energy is the energy impressed on a surface
at a certain distance from the arc and is used as a measure to
quantify the burn hazard from an arc-flash.
Arc-flash energy is transferred to the surroundings by con-
duction, convection, and radiation energies (Wilkins et al.,
2004). For enclosed equipment, a substantial part of the
arc-flash energy is also converted to pressure. Figure 1 illu-
strates the energy dissipation for open-space and enclosed-
space configuration. For arcs in open spaces, the geometry of
the energy emission is spherical and consequently the fraction
of the total arc energy that is emitted as radiant energy is pro-
portional to 1/D2. On the other hand, there is a focusing effect
for the enclosed-space configuration, which increases the
energy emitted in the direction of the opening. Consequently,
the radiation emitted from the box is less divergent than for
the spherical geometry resulting in a distance relationship of
1/Dxwith the distance exponential x being smaller than 2.
Arc-Flash Hazard in Wind Power Plants
IEEE PES Wind Plant Collector System Design Working Group
Contributing Members: M. Bradt, M. R. Behnke, T.A. Bellei, W. G. Bloethe, C. Brooks, E.H. Camm,
W. Dilling, B. Goltz, J. Li, J. Niemira, K. Nuckles, J. Patio, M. Reza, B. Richardson, N. Samaan, J. Schoene,T. Smith, I. Snyder, M. Starke, K. Tay, R. Walling, G. Zahalka
978-1-4244-6547-7/10/$26.00 2010 IEEE
8/10/2019 Arc Flash Hazard in w Pp
2/8
2
Figure 1: Distance dependence of incident energy for open-space and
enclosed-space configurations.
B. Arc-Flash Models
Arc-flash models estimate the incident heat energies a per-
son near an arc fault is exposed to. The incident energy levels
calculated in an arc-flash hazard analysis determines arc-flash
hazard categories, which in turn guide the decision regarding
the appropriate Personal Protective Equipment (PPE) for a
person that works near energized equipment. The calculatedincident energies are vastly model dependent (e.g., Ammer-
man et al., 2008) and there is currently no consensus on which
model to employ in an arc-flash hazard analysis.
Models that are based on empirical data include the IEEE
1584 model for system voltages below 15 kV, the Doughty
model, sometimes referred to the NFPA 70E model, (Doughty
et al., 2000), and the Wilkins model (Wilkins et al., 2005).
The IEEE 1584 and Doughty models are purely empirical
while the Wilkins model is based both on empirical data and
circuit theory making it a semi-empirical or behavioral model.
In general, empirical and semi-empirical models are fitted to
test data and consequently are only applicable for the tested
range of the relevant parameters and for conditions that re-semble the test conditions.
Models that are based on theory include the Duke Power
model, which is available in the public domain, the commer-
cially available ARCPRO model, and models that are based on
theory published by Lee (1982). The Duke Power model and
the ARCPRO models are the models integrated into the Heat
Flux calculator software and the ARCPRO software, respec-
tively. The models were developed for single-phase arc faults
in open air. The single-phase, open-air incident energies can
be converted to incident energies during three-phase faults and
faults in enclosed spaces using adjustment factors. Note that
most arc faults start as single-phase faults and escalate to
three-phase faults within a few milliseconds. A complete de-
scription of the theory behind the Duke Power model and the
ARCPRO model is not publicly available and consequently it
is difficult to evaluate the physical soundness of the model.
The ARCPRO model was internally verified for part of the
accepted range of input parameters (Kinectrics, 2004) inde-
pendent verification for the completed range of input parame-ters is lacking. IEEE 1584 recommends using a theoretical
model for system voltages of 15 kV and above. This model is
based on the very conservative maximum power transfer as-
sumption (Lee, 1983). Lee does not present equations for the
incident energy calculations in his paper and there is an inter-
pretation of Lees work for calculating incident energies that is
different than the IEEE 1584 interpretation (Martin and Beat-
tie, 2005). These Lee-based models are different from all oth-
er models presented in this paper in that the incident energies
calculated with the Lee-based models are proportional to the
system voltage; all other models show no or very little direct
dependence of incident energy and system voltage above 5
kV. The proportionality of incident energy and system vol-tages in the Lee-based models results in apparently unrealisti-
cally large incident energy levels for large system voltages.
Input parameters for all arc-flash models are the available
bolted fault current and the arc duration. The bolted fault cur-
rent can be determined in a short-circuit analysis and the arc
duration is typically determined by the time it takes for the
protection device (typically fuses and/or protective relays) to
clear the fault. The incident energy is also sensitive to the
working distance and the arc length1. An arc-flash hazard
analysis is often performed with arc lengths and working dis-
tances from IEEE 1584 which gives typical values for given
system voltages and equipment types (open air, switchgear,
etc.).
Note that none of the models discussed here seems to prop-
erly account for the arc-flash energy balance. Arc-flash ener-
gy in the form of convective heating inside the plasma cloud is
ignored in the IEEE 1584 theoretical model used for system
voltages of 15 kV and above, which results in an overestima-
tion of the incident energy for working distances outside the
plasma cloud. The effect of the plasma cloud is also ignored
in the calorimetric measurements from which the IEEE 1584
data were obtained since the sensors were located outside the
plasma cloud, where the arc-flash energy is primarily radiative
(Wilkins et al., 2005). This should not affect the accuracy of
the IEEE 1584 empirical model for working distances outsidethe plasma cloud, but will likely result in an underestimation
of the incident energies predicted by the IEEE 1584 empirical
model if the working distance is inside the plasma cloud
boundary. This is a concern if the plasma cloud expands far
enough to reach the worker thereby exposing the worker to
1The arc is often assumed to be straight and under this assumption the arc
length is equal to the distance between bus bars. However, for long arcs thatcan develop in systems with high voltages and large bus-bar spacing, this
assumption is not accurate since the arc is often warped and therefore consi-
derably longer than the bus bar distance.
8/10/2019 Arc Flash Hazard in w Pp
3/8
3
energy levels that are potentially much higher than predicted
by any of the models discussed here. There is no consensus in
the literature about the dimension of the plasma cloud. Lee
(1982) assumed a spherical dimension for the plasma cloud
and predicted for one configuration an arc plasma diameter of
170 mm. On the other hand, for the same configuration,
Stokes and Sweeting (2005) experimentally determined a
much larger plasma expansion they measured an arc plasma
dimension of 3m x 1.5m from a photograph. Also, for en-closed space configurations the plasma cloud is likely to ex-
pand farther in the direction of the worker due to the focusing
effect (see Section IIA)
C. Arc-flash Concerns specific to Wind Plants
Typically, during wind plant commissioning, the equip-
ment inside the wind turbine tower has to be approached in an
energized state. This is a problem if the arc-flash analysis
predicts large incident energies at locations inside the turbine.
Temporary protection settings (e.g., relays set on instantane-
ous trip) may be applied to reduce the incident energy at loca-
tions with excessively high incident energy levels.
In particular, the arc-flash hazard inside the wind turbinetower may be more severe than predicted by the arc-flash ha-
zard analysis because of the following concerns:
Convective heat transfer that is not properly accountedfor in models used for the arc-flash hazard analysis in-
creases the incident energy if the worker is inside the
plasma cloud (see Section IIB). A worker location insidethe plasma cloud is likely due to (1) the focusing effect of
the arc-flash in the enclosed space configuration, which
directs the plasma towards the worker and (2) the tightspace inside the turbine tower, which may result in a re-
duced working distance.
The arc-blast hazard (the hazard due to the pressure
from the arc fault) is potentially more severe inside theturbine tower because of (1) the focusing effect of the
blast in the enclosed-space configuration, which increasesthe pressure exerted on the worker, (2) the inability of the
worker to move away from the blast, and (3) the fall ha-
zard inside the turbine tower. Note that the arc-flash ha-zard analysis does typically not assess the blast hazard.
The two-second rule in IEEE 1584 (i.e., using twoseconds as the maximum time a person is exposed to an
arc-flash because the person will be able to move to safety
within that time) does not necessarily apply due to the re-stricted ability to move inside the turbine tower.
The duration of the arcing fault current contribution
from the turbine may depend on the turbine protection on-ly (i.e., there may not be any fuses/relay protection be-
tween the turbine and the arc fault location that discon-
nects the turbine from the fault). Consequently, to prop-erly account for the fault current contribution from the
turbines, some insight into the protection mechanism of
the turbine is required, which may not be always availableto the person performing the arc-flash analysis.
III. ARC-FLASH HAZARD PROTECTION
A. Protection Boundary
IEEE 1584 defines the arc-flash protection boundary to be
the area around an energized object in which a person without
PPE is at risk of receiving at least second degree burns from
an arc-flash originating from the energized object. Skin expo-
sure to energy levels that exceed 1.2 cal/cm2 can cause
second-degree burns. Persons within this area are required to
wear PPE. The flash protection boundary is determined in an
arc-flash analysis.
B. Protection Equipment
NFPA 70E (2004) classifies the arc-flash hazard according
to maximum incident energy a person can be exposed to. The
NFPA 70E hazard categories are listed in Table 1. Protection
requirements, such as Personal Protective Equipment (PPE),
are selected based on the hazard category. The PPE should
limit the energy exposure of the chest and face during an arc-
ing fault to curable burn energies (below 1.2 cal/cm2accord-
ing to IEEE 1584). In some cases the maximum incident
energy level may exceed 40 cal/cm2. For these cases, risk
consideration will play a major role. There is PPE available
above 40 cal/cm2, however the preferred approach is to always
work such high levels de-energized.
TABLE 1:NFPA70EHAZARD CATEGORIES
Category
Energy
Level
(cal/cm2)
Protective Clothing/PPE
0
8/10/2019 Arc Flash Hazard in w Pp
4/8
8/10/2019 Arc Flash Hazard in w Pp
5/8
5
Figure 4: Scope of paper.
The dynamics of the generators behavior creates asyn-
chronous fault values and how that impacts quantification of
an arc-flash energy and on the response of the LVCB and its
trip logic is beyond the scope of this paper, which is focusing
on the collector system. Instead, a constant conservative fault
current from the WTG is assumed for the examples in Section
V.
B. Short-Circuit Study
1) Collect the system and installation data
It is imperative that the component data used for the
short-circuit study be accurate. The study must consider all
sources (e.g. utilities, generators, and motors) as well as the
impedances of the connecting system, transformers, and
cables. A single-line diagram is essential in finding the avail-
able fault currents at each WTG site and the WPP substation
bus.
2) Calculate arcing fault currents
Bolted fault currents can be calculated using any commercial-
ly available power engineering software that is capable of per-forming a short-circuit analysis. The reader must consider all
possible scenarios during operation and then utilize the com-
ponent data, along with the single-line diagram to obtain the
bolted fault current at each piece of equipment. Also all three
initial short-circuit conditions must be calculated, which arecommonly called: momentary, interrupting, and time-delayed
(or steady-state). For the example below the momentary will
be estimated at five time steady-state and interrupting will be
estimated at three times the steady-state.
Using the IEEE 1584 empirical model for the low-voltage
electrical equipment, only three-phase fault currents are neces-
sary to calculate arcing-fault currents or other standard percen-
tages can be used. For software such as ARCPRO and the
Duke Heat Flux calculator use SLG fault currents instead of
three-phase fault currents in their theoretical models. The
impact of a three-phase event using ARCPRO can then be
accomplished with the suggested multipliers to adjust the out-
put results to the three-phase open-air or cabinet (in-a-box)conditions.
3) Fault currents fed from multiple sources
In WPP, a fault almost anywhere will result in the fault be-
ing fed by two or more sources (e.g. a single generator, a
group of WTGs, and/or the external utility system). In such
scenarios, fault current contributions from various sources
need to be considered separately based on their protecting
device for use in the next subsection.
C. Coordination Study
1) Determine the fault clearing times
Using the time-current characteristic (TCC) curves and the
arcing-fault current, it becomes straightforward to determinethe time taken for a protecting overcurrent protective device to
clear a fault. This can be determined by drawing a vertical
line representing the arcing fault current and then determining
where it intersects with the maximum clearing time TCC
curve for the protecting device. For fuses this would be the
total clearing curve, because it represent the maximum time to
complete the open. For the LVCB, this could be on the manu-
factures overcurrent clearing curve in either direction or from
a signal from the WTG control module to trip, which will have
a different time delay than the overcurrent. Such LVCB time
delays could include logic responding to the low voltage ride-
through (LVRT) or other generator abnormal conditions. For
the MVCB relays at the collector feeder exits this will be theselected TCC curve, which must include the maximum break-
er opening/clearing times and any intentional coordination
delays.
At most WPP substations, there are differential protective
schemes which will detect faults within the differential zones.
The respective clearing devices within those zones will define
the clearing times for fault and arc-flash events within their
reach with the maximum time decay being associated with the
slowest breaker.
2) Clearing times for faults with multiple sources
For faults being fed from multiple sources, clearing times
for each source will need to be determined. For each fault
current calculated from subsection IV.B, a clearing time can
be found using the method discussed in IV.C.(1). The fault
current and its associated clearing time will be used to com-
pute the incident energy in the next section.
D. Arc-Flash Hazard Study
The method presented here is a simplified approach and
should provide a conservative value for the total incident
energy from an arc-flash event. The steps are:
1) Determine locations where the arc-flash is to be esti-
mated, such as the generic ones indicated inFigure 5.
Generator
Low-Voltage
Circuit Break-
er
Step Up
Transformer
Medium VoltageCircuit Breaker
(MVCB)
Low Voltage
(LV) equip-
ment locatedin or near the
wind turbine
tower
Medium Vol-tage (MV)
equipment
located on the
feeders and in
the Substation
: Possible fault locations
8/10/2019 Arc Flash Hazard in w Pp
6/8
6
2) Determine and/or establish the parameters and assump-
tions at each location, such as open air or cabinet situation,
likely working distance and arc gap distance. Use actual val-
ues for the distances or typical values from IEEE 1584.
The next three steps will be iterated at each selected fault
location based on how the multiple sources of fault current
contribute to the total fault current at that location through
time. The only step that may be skipped may be step 3, which
is the need to rerun the fault calculation after each deviceclears. Engineering judgment regarding the impact on values
after each loop may be small enough to allow working only
with each of the separate fault flows that would be contribut-
ing to the event. The initial fault calculation run may be ade-
quate.
3) Perform a short circuit fault calculation run on a particu-
lar location to obtain its fault flows for the momentary, inter-
rupting, and steady-state conditions from all sources and de-
termine how much is flowing through the protecting devices to
the fault location.
4) Determine the total clearing times for all the protecting
devices that are allowing fault flow to the fault location, such
as:a) At the collector feeder breaker relay use the TCC curve
and find the respective time for the fault flow passing through
it (taking into account a faster trip of the breaker due to a
higher momentary current) from the substation and external
power system, or
b) In the LV secondary cabinet of a wind turbine step-up
transformer use the transformer fuses, the LVCB TCC, or the
control logic to the LVCB to estimate the time depending on
the fault flow direction use either the transformer fuses or
the control logic to trip and clear the LVCB to estimate the
time.
5) Determine the amount of incident energy occurring at
this location by using an arc-flash model (such as the IEEE
1584 model, the ARCPRO model, or another model) with all
the respective contributing fault current sources (step 3) and
the clearing time of the next fastest clearing device (step 4).
For instance:
a) At a 34.5kV substation collector feeder exit - use
ARCPRO with the parameters from step 2, such as the open-
air three-phase case at 15-inch working distance and a 6-inch
arc gap (NESC Table 410-1), or
b) in a 600V secondary cabinet of a step-up transformer
use IEEE 1584 with the parameters from step 2, such as the
under-1000V and in-a-box options that will provide a 24-inch
working distance and an 1.25-inch arc gap (IEEE 1584 Tables2 and 3).
6) Loop steps 3 though 5 for each successively slower pro-
tecting device as it removes its respective amount of contribut-
ing fault flow from this location from the quickest device to
slowest device, until all the fault flow is eliminated.
7) Sum the arc-flash incident energy from each of the suc-
cessively passes for this location. This sum will be the total
incident energy for this location.
8) Finally, repeat the steps 3 through 7 for all selected loca-
tions.
V. EXAMPLES
Example 1 A fault and arc-flash occur at a 34.5kV
MVCB breaker exit on the collector-side of a collector feeder
with two turbines generating at an LV of 600V. Each WTG is
rated 2 MW, uses a 2500 kVA step-up transformer, and has a
rated current of about 33A at 34.5 kV. SeeFigure 5.
Figure 5: Example of fault and arc-flash in air at MV feeder.
There are three sources contributing to the fault: the system
and each of the two turbines. Since this is an open-air loca-
tion, the NESC default values from Table 410-1 offer a good
baseline. Fault flows to this location will determine the loops,
which are two in this case, Flow 1 and 2. The fault flow from
the substation bus (Flow 1) will be seen by the MVCB relay
and it will clear its portion of the fault flow first. For this ex-
ample (Figure 5), a fault flow for Flow 1 will be 5 kA and the
clearing time, which was obtained from reading the TCC plot
for the collector feeder relay at 5 kA, will be 0.10 seconds.
However, there is a second delayed fault flow (Flow 2)
that continues from the two turbines. At the wind turbines the
clearing devices are the LVCBs at 600 V and the two internal
transformer fuses on the 34.5-kV side. If the contributing cur-
rent from any one turbine is not large enough to trip the LVCB
on overcurrent, then the control scheme for the LVCB will
respond to a low-voltage condition and wait a predefined
amount of time based on the actual voltage that each turbine
sees against the predetermined low voltage ride-through
(LVRT) envelope. Note that the LVRT time delay is depen-dent on how low the voltage drops. Typically, if it goes below
15% of nominal it will be at its shortest delay, which will be
0.15 seconds in this example. However, the delay could be
longer if the voltage during the fault is higher than 15%. For
this example, the assumption will be that the control schemes
on all WT LVCBs on the collector feeder will simultaneously
see a sustained zero voltage to initiate a trip to their LVCB at
the minimum time delay. The total time delay for Flow 2 will
be 0.35 seconds. In this example, the 0.35 seconds consists of
0.15 seconds delay from the LVRT envelope and 0.10 seconds
Crow BarWT TowerTop
WT TowerMiddle
WT TowerBaseLV CB
Crow BarWT TowerTop
WT TowerMiddle
WT TowerBaseLVCB
Exp.Fuse
C.L.Fuse
WTTransf
FeedThruw/ Sw.
OutsideTowerStep-upTransformerTank
Exp.Fuse
C.L.Fuse
WTTransf
FeedThruw/ Sw.
OutsideTowerStep-upTransformerTank
Wind Turbine 1 Wind Turbine 2
Sub Transf
SYSTEM
MV CB
CollectorSub
Flow 1
HV
MV
LV LV
Flow 2
MV
: Possible fault location
8/10/2019 Arc Flash Hazard in w Pp
7/8
7
for the control circuit and LVCB clearing time to respond to
an external trip signal, as well as the initial 0.1 seconds for the
feeder circuit breaker to clear. As mentioned, it will be as-
sumed that both turbines will respond identically and at the
same time. However, this methodology is flexible enough to
allow for multiple delayed devices clearing at different times.
It is understood that the fault current from the WTG for the
initial few cycles will be obtained from the momentary condi-
tion of the short circuit, or around five times the rated current,and then drop off very quickly as the turbine responds electri-
cally. However, fault current from the WTG, before it drops
off as seen on the 34.5-kV system at the MVCB will be small
compared to the contribution from the substation and external
system. By the time the MVCB clears, the WTG contribu-
tions will either be at the interrupting or steady-state condi-
tion. For our example, the interrupting condition will be used,
or about 99 Amps (three times the rated current of 33 A).
Since both turbines are contributing to the fault flow, the de-
layed contribution is approximately 198 Amps. With these
values the incident energy is calculated with the respective
calculator, which is this case for both loops of the method
produced the values in Figure 6 for a total of 8.4 cal/cm2.
Figure 6: Arc-flash results for a fault in air at MV feeder ((not-to-
scale).
Example 2 Using the same WPP setup, the fault and arc-
flash now occurs in the LV (600 V) cabinet of the first wind
turbine step-up transformer. See Figure 7.
At this location there are also three sources, but two fault
flows. One flow is from the generator associated with this
transformer (Flow 3), and the other is from the collector feeder(Flow 4), which represents the contributions from the other
turbine, the substation and the external power system. Since
this location is in a cabinet (a.k.a. in-a-box) and is on the low-
voltage side, the assumptions and equations from IEEE 1584
empirically will be the best choice and will provide a good
baseline. Therefore, the working distance, gap size, and de-
fault values will come from their respective tables in the IEEE
1584 document. Because this fault is at 600 V, the Ampere
level of the fault flows (Flows 3 and 4) will be much higher
compared to a similar power level on the 34.5-kV system.
Since the fault currents are much higher on the 600 V side, the
arc-flash values are certain to be larger as well.
Assuming the MVCB feeder relay, the transformer fuses
and the LVCB are all coordinated, then the sequence of clear-
ing can be determined from the TCC plot that was used in
their coordination. That coordination would have the trans-
former fuses clearing before the feeder breaker to keep the
feeder energized while the generator is taken off-line. There-
fore the clearing sequence for this location will be between theLVCB and the fuses, with the fuses generally taking the longer
time and the LVCB tripping first to clear the local generator.
The LVCBs clearing time will be defined the same way here
as it was in the first example by the LVRT with a total time of
0.35 seconds. The clearing time will be shorter if the overcur-
rent mechanism responds before the LVRT trip.
Figure 7: Example of fault and arc-flash in an LV cabinet.
The fault flow from the wind turbine generator, Flow 3, in
Figure 7, will be the momentary condition fault current value
which could be nearly five times the rated current, or about
10,000 Amp plus the steady state fault flow from the collector
feeder, Flow 4, of 35 kA. The momentary condition is used
because it represents a conservative value. Thus, a total fault
flow of about 45 kA will result for 0.35 seconds. After the
LVCB clears the fault flow (Flow 3) from the local WTG, the
fault flow from the collector (Flow 4) will still be contributing.
The total clearing time for this portion is found by locating
this fault flow of 35 kA on the TCC of the transformer fuse set
and finding where it crosses the total clear curve of the firstfuse in the transformer to open. For this example 0.55 seconds
will be used. However, this delayed clearing will have its arc-
flash contribution bounded by the duration of the difference
between the fuse total clearing time and the LVCB clearing
time of 0.35 seconds, which will provide a final interval of 0.2
seconds of fault flow from the collector feeder, before the
transformer fuse opens. Figure 8 shows both intervals and
their respective incident energy contributions with the total
being about 34.2 cal/cm2.
Time Duration of Arc-flash (sec)
0.0 0.10
5kA
0.21kA
0.10 sec
0.25 sec
Total 8.4 cal/cm2
7.8 cal/cm2
0.6 cal/cm
2
FaultCurrentat theSite ofthe Arc-flashEvent
0.35
8/10/2019 Arc Flash Hazard in w Pp
8/8
8
Figure 8: Arc-flash results for a fault in an LV cabinet (not-to-
scale).
VI. CONCLUSIONThis paper has investigated and discussed the arc-flash ha-
zard on a WPP collector system. A brief discussion of the arc-
flash hazard and its causes were presented along with a me-
thodology and two examples for tallying the total incident
energy from multiple sources.
The use of the various conditions of fault current in the me-
thodology, are presented as a conservative measure for esti-
mating the arc-flash incident energy, but it must be understood
that the real behavior of the fault current from the WTG is
very unpredictable and situation dependent. From these two
brief examples it can be seen that one of the highest levels of
the arc-flash hazard in a WPP collector system can be on theLV cable and inclusive cabinets between the LVCB and the
step-up transformer. However, these results could be very
different if another arc-flash calculator were used, such as the
IEEE 1584 theoretical model, which has a dependence on vol-
tage.
VII. REFERENCES
[1] Ammerman, R.F., T. Gammon, P.K. Sen, and J.P. Nelson, ComparativeStudy of Arc Modeling and Arc-flash Incident Energy Exposures, Pe-
troleum and Chemical Industry Technical Conference, pp. 1-12, Cincin-
nati, OH, 22-24 Sept. 2008.
[2] Dalziel, Charles F., The effects of electric shock on man, IRE Trans-actions on Medical Electronics (PGME-5), May 1956.
[3] Doughty, R.L., T.E. Neal, T.A. Dear, and A.H. Bingham, Testing up-
date on protective clothing & equipment for electric arc exposure,Conf. Rec. IEEE PCIC, pp. 323-336, Sept. 1997.
[4] Doughty, R.L., T.E. Neal, H.L. Floyd II, Predicting Incident Energy toBetter Manage the Electric Arc Hazard on 600-V Power Distribution
Systems, IEEE Trans. On Industry Applications, Vol. 36, No.1, Janu-
ary/February 2000.
[5] Dugan, T.B., Reducing the flash hazard, IEEE Industry ApplicationsMagazine, May/June 2007.
[6] Kinectrics, Users Guide for ArcPro, 2004.[7] King, Clayton, Maintaining line worker safety through maintenance
and testing of protective grounding equipment, T&D construction, op-eration & live-line maintenance proceedings, pp. 101-107, 26-30 April
1998.
[8] Lee, R.H., The Other Electrical Hazard: Electric Arc Blast Burns,IEEE Transactions on Industry Applications, Vol. 1A-18, No.3,
May/June 1982.[9] Lee, R.H., Pressures Developed by Arcs, IEEE Transactions on Indus-
try Applications, Vol. 1A-23, No.4, July/August 1987.
[10] Martin, L., J. Beattie, Arc Protection Recommendations for SaskPowerTransmission and Distribution,, TS&R Report Number 05-345, 2005.
[11] Schau, H. and D. Stade, Requirements to be met by protection andswitching devices from the arcing protection point of view, 5 thInterna-
tional Conference on Electric Fuses and their Application, September
1995.
[12] Reilly, J.P., H. Antoni, M.A. Chilbert, Applied Biolectricity, ISBN0387984070, Springer, 1998.
[13] Wallace, K., L. Garrett, and S. Patel, Protective Grounding Methodsand Requirements on Distribution Line Wood Pole Construction, Pro-
ceedings of the 11th International Conference on Transmission & Distri-bution Construction, 15-19 October 2006.
[14] Wilkins, R., M. Allison, and M. Lang, Improved Method for Arc-flashHazard Analysis, IEEE Industrial and Commercial Power Systems
Technical Conference, pp. 55-62, 2-6 May 2004.
Fault
Currentat theSite ofthe Arc-flashEvent
0.0 0.35
45kA
0.55
35kA
0.20 sec
0.35 sec
23.6 cal/cm2
10.6 cal/cm2
Total 34.2 cal/cm2
Time Duration of Arc-flash (sec)