APC® by Schneider Electric Solutions for Cisco® Unified Computing System (UCS) Blade Applications
The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a cohesive system designed to reduce TCO and increase business agility. The system integrates a low-latency, lossless 10GE unified network fabric with enterprise-class, x86-architecture servers. The system is an integrated, scalable, multi-chassis platform in which all resources participate in a unified management domain.
Blade server applications present unique challenges in terms of rack level power distribution, cable management and physical access space requirements for hot-swappable blade components.
This application guide provides recommendations for enclosures, rack power distribution, and cable management to best address the specific physical infrastructure needs of the Cisco UCS 5108 Blade Server Chassis. The recommended solutions in this guide are based on physical verification and testing of an actual Cisco UCS 5108 Blade Server Chassis mounted in APC enclosures.
APC Solutions for Cisco®
Catalyst® SwitchesThe Cisco / APC relationship began in 1998 with a focus on non-stop networking and has since grown to include the integration of various platforms, the sharing of intellectual property for white papers and design specifications as well as joint field engagements.
Power protection is a crucial component of VoIP & IP Telephony networks and helps to ensure that they meet the demands for “always available” systems. To achieve the highest levels of availability, it is essential that Layer 0 solutions support VoIP & IP Telephony networks, in line with your business requirements. This document discusses the power needs of Cisco® Catalyst® Switches and appropriate APC UPS solutions.
APC’s Smart-UPS® is Ideal for Protecting and Supporting Cisco Catalyst Family Switches Which Cisco equipment needs APC Smart-UPS?
> Catalyst 2950 Series, Catalyst 3750 Series, Catalyst 3550 Series, Catalyst 4500 Series
> Catalyst 6500/6500E Series
www.apc.com> Cisco Partnership Information: www.apc.com/techpartners> Wiring Closet Design Tool: configurator.apcc.com> Wiring Closet Solutions: http://apc.com/products/family/index.cfm?id
On Demand trainings at www. Datacenteruniversity.com
APC White Papers> White Paper #88: Power and Cooling Considerations for Power over Ethernet (PoE)
APC Application Notes> Application Note #50: APC Power Protection for Cisco VoIP and IP Telephony Solutions
Resources Available from APC
©2008 American Power Conversion Corporation. All rights reserved. O/ther trademarks are property of their respective owners. /Specifications are subject to change without notice. Last Updated on 8/18/08132 Fairgrounds Rd. West Kingston, RI 02892 USA • Call: 800-800-4APC • Fax: 401-789-3710 • e-mail: [email protected]
APC Smart-UPS® support for Cisco®
CallManager®:APC Smart-UPS supports Cisco CallManager 6.x out-of-the-box with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of CallManager in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially or over the network.
APC Smart-UPS® support for Cisco®
Unity Express® and CUCM 6.x:APC Smart-UPS supports Cisco Unity Express with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of voicemail and automated attendant services in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially and requires the APC Unity Express UPS Simple Signaling Cable (APC Part#AP9840)
Additionally, APC Smart-UPS 750XL and Smart-UPS 1500/1500RM gracefully shutdown Cisco Unified Communications Manager versions 6.x via a point-to-point direct Universal Serial Bus (USB) connection in the event of an extended power outage.
Choose Smart-UPS® RT or Symmetra®
RM/LX for Catalyst 6500 and High Density Environments:Smart-UPS RT, double conversion online family of UPSs offers performance for high density voice and data networks. Supports up to 20kVA in a 12U rack or stack form factor.
Symmetra offers scalability and the additional protection of N+1 redundancy. Symmetra supports from 2-6kVA (RM) in a rack-optimized form or up to 16kVA (LX) in a rack or tower form.
How to choose the right APC Smart-UPS® for a Cisco® Catalyst®
Family Switch?
Step 1: Consider Your Application> What model Cisco Catalyst Switch will the Smart-UPS support?> What is the input voltage for the switch?> Will the Cisco Catalyst Switch support PoE devices? If so, how many and what PoE class?> What is the plug type for the Cisco Catalyst Switch?> How many power supplies does the switch have?> What will be the total loading on the UPS VA and Watts, both initially and in the future?> How much runtime is required if the power goes out?
Step 2: Use the UPS Selector or Call APC for Assistancewww.apc.com/tools/ups_selector/ or 1-800-800-4272 in North America. In other countries, please contact your local APC office from the list provided on APC.com.
Step 3: Purchase an APC Smart-UPS®
> APC Smart-UPS® is the best solution for the Cisco Catalyst Switch family in the wiring closet. > For mission-critical or remote closets, you may also consider the NetBotz® family of accessories which provide real-time environmental monitoring and visibility to your wiring closet environment. > For dense closet and server room environments, consider InRow® RD.> All of these components are InfraStruXure® Certified to integrate seamlessly with the APC InfraStruXure® system.
APC Smart-UPS® and Smart-UPS® XLThe Smart-UPS & Smart-UPS XL use Line-interactive topology offering high reliability and efficiency with good voltage regulation.
> Smart-UPS series offers power outputs from 750VA to 5kVA (480W to 4kW)
> Smart-UPS XL units are available that allow connection of additional battery strings to increase the system run time.
APC Advanced PDUs• Integrates power management capabilities with
other APC products including Symmetra® PX UPS, row and room PDUs, InRow cooling, NetShelter®
SX enclosures, and InfraStruXure® Central, Capacity and Change Manager
• Features zero U, low profile design, optimized for high-density rack power solutions to minimize interference between the PDU and hot-swap blade components
• Superior current monitoring protection including active monitoring of 3 phases for upstream panel breaker and on-board input breakers
APC Full Featured Enclosures• APC NetShelter® SX enclosures offer the most
standard, out-of-box features to ease installation and speed deployment
• Single enclosure design is flexible enough to accommodate various networking and server applications.
• Sizes Available: 42U & 48U heights, 600mm (24”) & 750mm (30”) widths, and 1070mm (42”) & 1200mm (47.2”) depths.
APC Rack Enclosures and Rack Mount Power Distributions Units (PDUs)
APC is a world leader in data center infrastructure - cooling, UPS, power distribution, racks and management.
Power Requirements for Cisco UCS 5108
Source “A”(2) C20
Connectors
Source “B”(2) C20
Connectors
The UCS 5108 Blade Server Chassis includes four, single phase, hot- swappable redundant power supplies with IEC C20 Inlet connections.
In a typical power configuration, two IEC C20 inlets on the UCS 5108 are connected to each power source.
The total power consumption per chassis for typical enterprise applications is 2.0 – 2.5 kW; while a typical peak power consumption is 2.8 – 3.0 kW. In order to allow for loss of one power source, each power source should be sized and provisioned for approximately 3.0kW per chassis loading scenario as indicated below.
Note: High performance computing applications with extremely heavy loading conditions have been tested and measured to draw a peak power consumption of 3.2kW per chassis. Under these conditions, users should provision 3.2kW per chassis.
Rack Enclosures with up to two UCS 6100 Series Fabric Internconnects
AND
"A" Power Source Total Req'd Receptacles (per
Source/Rack PDU)
"B" Power Source Total Req'd Receptacles (per
Source/Rack PDU)
Total Power Provision Recommendation*
(1) UCS 5108 Chassis (2) C19, (2) C13 (2) C19, (2) C13 3.5 kW(2) UCS 5108 Chassis (4) C19, (2) C13 (4) C19, (2) C13 6.5 kW(3) UCS 5108 Chassis (6) C19, (2) C13 (6) C19, (2) C13 9.5 kW(4) UCS 5108 Chassis (8) C19, (2) C13 (8) C19, (2) C13 12.5 kW(5) UCS 5108 Chassis (10) C19, (2) C13 (10) C19, (2) C13 15.5 kW(6) UCS 5108 Chassis (12) C19, (2) C13 (12) C19, (2) C13 18.5 kW
* Each Rack Power Distribution Unit should be provisioned to this Total Power Provision Recommendation in order to account for potential source redundancy loss; Total Power Provision recommendations include power for up to two UCS 6100 Series Fabric Interconnects
Rack PDU Selection Tables
415V 3-phase
1 to 3 2 to 5 6 1 to 3
9.5 15.5 18.5 9.5
45.7 74.5 88.9 39.6
50A, 3-phase 60A, 3-phase (2x) 50A, 3-ph 20A, 3-phase
(1)AP7898 (1)AP7866 or (1)AP7866A (2)AP7567A (1)AP7557NA
60A (12.5kW)
77.9A (16.2kW)
138.6A (28.8kW)
48A (11.5kW)
Max Power Required (kW)*
Rack PDU Model
Total Rack PDU Rating(single phase amps)
* Total power and amps required includes power provision for up to two UCS 6100 Series Fabric Interconnects
Number of UCS 5108 Blade Chassis per Enclosure
208V 3-phase
Max Amps Required (1ph output)*
Recommended Branch Circuit
STEP 2 ---->
STEP 3 ---->
North America Solutions
International Solutions (230/400V 3-phase Power)
Steps to select the correct rack PDU to match site/application requirements:
1. Select your region; choose North America or International (for any location outside North America)
2. If North America, select 3-phase power system (208V 3-phase or 415V 3-phase)
3. Select the desired number of UCS 5108 chassis per rack
Table Results Indicate:
• Recommended total amps (single phase output) required to power the selected number of UCS 5108 chassis plus up to two UCS 6100 Series Fabric Interconnects
• Recommended branch circuit type and size
• Recommended APC rack PDU (metered rack PDUs are recommended to actively monitor and provide alarm warnings to protect critical power circuits from accidental overloads)
• Total rack PDU rated output (total max single phase amps output)
1 to 3 4 to 6
9.5 18.5
41.3 80.4
16A, 3-phase 32A, 3-phase
(1)AP7857 (1)AP7856 or (1)AP7856A
48A (11kW)
96A (22kW)
Total Rack PDU Rating (single phase amps)
Max Power Required (kW)*
Max Amps Required (1ph output)*
Recommended Branch Circuit
Rack PDU Model
STEP 2 ---->
STEP 3 ---->
400V 3-phaseNumber of UCS 5108 Blade
Chassis per Enclosure
* Total power and amps required includes power provision for up to two UCS 6100 Series Fabric Interconnects
Rack Enclosure Recommendation
Steps to select the correct enclosure to match site/application requirements:
1. Choose Region and Density: Select the number of chassis expected per enclosure
2. Choose enclosure width: Wider enclosures offer the best use of cable management space and access to blade modules, however site specific limitations may require standard 600mm width enclosure
3. Choose enclosure depth: Deeper enclosures are an alternative to wider enclosures for increased cable management and PDU space
4. Choose the Configuration: Reference the diagrams in this document for configuration recommendations and planning considerations
5. Choose Enclosure and Cable Management from the reference diagrams
The clearance access space required to access the hot swap blade chassis modules require special consideration in the selection and configuration of a proper rack enclosure to match the space requirements for access, power distribution, and data cabling. The specific selection of a properly sized rack enclosure depends upon your site specific data, cabling and rack power positioning preferences.
Step 1 Step 2 Step 3 Step 4
Choose Region & Density
Choose Enclosure Width
Choose Enclosure Depth
Verify Configuration (as shown in diagrams)
1070mm deep (~42 in) Diagram A(note limited available space)
1200mm deep (~47 in) Diagram B1 or B2
1070mm deep (~42 in) Diagram C1 or C2
1200mm deep (~47 in) Diagram C1 or C2
600mm wide(24 in) 1200mm deep (~47 in) Diagram D
1070mm deep (~42 in) Diagram E
1200mm deep (~47 in) Diagram E
1070mm deep (~42 in) Diagram A(note limited available space)
1200mm deep (~47 in) Diagram B1 or B2
1070mm deep (~42 in) Diagram C1 or C2
1200mm deep (~47 in) Diagram C1 or C2
750mm wide(30 in)
600mm wide(24 in)
750mm wide(30 in)
750mm wide(30 in)
600mm wide(24 in)
International(1 to 6 chassis)
North America(1 to 5 chassis)
North America(6 chassis)
Chassis hot swap component access
CiscoUCS 5108Chassis
1070
mm
600 mm
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
Diagram “A” 600mm wide x 1070mm deep
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
In this configuration, data cabling space is very limited; use AR8621 tool-less hook & loop cable managers and fasten to vertical mounting rails (small space cavity between the rack PDU and UCS chassis is shown in yellow)
Place rack PDUs on each side of the enclosure with receptacles facing the rear door to allow access to hot swap blade components (outlet direction shown by arrow)
AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis
ORDER ITEMS
• Rack enclosure 42U (AR3100) or 48U (AR3107)
• Rack PDU (from selection table)
• Bracket kit AR7711 (one per rack PDU)
• Cable management AR8621 (2 each)
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
Use AR7711 bracket (one per side) to orient rack PDUs 90°
(receptacles facing enclosure rear door)
CiscoUCS 5108Chassis
Chassis hot swap component access
600 mm
1200
mm
Diagram “B1” 600mm wide x 1200mm deep
In this configuration, data cabling space is abundant; users can select 1 to 3 cable management kits (AR7710) depending on expected volume of data cables.
Place rack PDUs as shown in this image to allow for hot swap component access; note: PDUs cannot be located the opposite side due to interference with fan component access space
In this configuration, hot swap component access is tight, but has been tested to properly work.
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis
ORDER ITEMS
• Rack enclosure 42U (AR3300) or 48U (AR3307)
• Rack PDU (from selection table)
• Cable Management kit(s) AR7710 (order 1 to 3 units)
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
CiscoUCS 5108Chassis
Chassis hot swap component access
1200
mm
600 mm
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
ON
OFF
20
Diagram “B2” 600mm wide x 1200mm deep
In this configuration, data cabling space is abundant; users can select 1 or 2 cable management kits (AR7710) depending on expected volume of data cables.
Place rack PDUs on each side of the enclosure with receptacles facing the rear door to allow access to hot swap blade components (outlet direction shown by arrow)
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis
ORDER ITEMS
• Rack enclosure 42U (AR3300) or 48U (AR3307)
• Rack PDU (from selection table)
• Bracket kit AR771 (one per rack PDU)
• Cable Management kit(s) AR7710 (order 1 to 3 units)
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
Use AR7711 bracket (one per side) to orient rack PDUs 90°
(receptacles facing enclosure rear door)
Diagram “C1” 750mm wide x 1070mm and 1200mm deep
Chassis hot swap component access
CiscoUCS 5108Chassis
1070
mm
750 mm
Data cabling can be managed by use of either (1) AR7710 or (2)AR8442 (for more capacity)
Rack PDUs can be placed on either side of rack enclosure
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis
ORDER ITEMS
• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)
• Rack PDU (from selection table)
• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 or (1)
AR7710 1200mm: either (1 to 3) AR7710 or (1 to 6)
AR8442
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
Chassis hot swap component access
1200
mm
1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)
Diagram “C2” 750mm wide x 1070mm and 1200mm deep
Chassis hot swap component access
CiscoUCS 5108Chassis
750 mm
1070
mmData cabling can be
managed by use of AR8442 (1 or 2 units)
Rack PDUs placed on both sides of the rack enclosure
AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis
ORDER ITEMS
• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)
• Rack PDU (from selection table)
• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 1200mm: either (1 or 2) AR7710 or (1 to 6)
AR8442
• Power cords (C19 to C20 type)
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
Chassis hot swap component access
1200
mm
1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)
CiscoUCS 5108Chassis
Chassis hot swap component access
600 mm
1200
mm
Diagram “D” 600mm wide x 1200mm deep
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
ORDER ITEMS
• Rack enclosure 42U (AR3300) or 48U (AR3307)
• Rack PDU (from selection table)
• Cable Management kit(s) AR7710 (order 1 to 3 units)
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
Space is extremely limited in this configuration; hot swap modules must be removed at an angle to avoid interference with PDU
Place rack PDUs as shown in this image to allow for hot swap component access
Note: PDUs cannot be located on the opposite side due to interference with fan component access space
In this configuration, data cabling space is abundant; users can select 1 to 3 cable management kits (AR7710) depending on expected volume of data cables.
Diagram “E” 750mm wide x 1070mm and 1200mm deep
Chassis hot swap component access
CiscoUCS 5108Chassis
1070
mm
750 mm
Data cabling can be managed by use of either (1) AR7710 or (2)AR8442 (for more capacity)
Rack PDUs can be placed on either side of rack enclosure
PDUs are ½ enclosure height; place 4 units on the same rack side to reduce interference from incoming power cords
ORDER ITEMS
• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)
• Rack PDU (from selection table)
• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 1200mm: either (1 to 3) AR7710 or (1 to 6)
AR8442
• Power cords (C19 to C20 type)
Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)
TOP VIEWPROFILE VIEWREAR OF ENCLOSURE
Chassis hot swap component access
1200
mm
1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)
Cable Management Accessories
AR8442Toolless Vertical Cable Organizer
AR7710 Toolless, Low-Profile
Vertical Cable Organizer
AR8621 Toolless Hook and Loop
Cable Managers
AR8443A & AR8444Fiber Spool Kits
AR7580 High Density Cable Manager
(for wide racks)
AR7711Zero U Accessory Bracket
All trademarks are property of their owners.
For more information visit: www.apc.com or www.thedcofthefuture.com
Call APC at: 800-272-2722
AP
C b
y S
chne
ider
Ele
ctric
–N
ame
–D
ate
Net
She
lter N
exus
701
8 S
olut
ion
Ext
erna
l Exp
ansi
on D
ucts
for S
ide
Airf
low
●Nex
us 7
018
switc
h cl
eara
nce
requ
irem
ents
to
supp
ort s
ide-
to-s
ide
airf
low
resu
lt in
a 4
0”
wid
e en
clos
ure
●APC
AR
3350
Enc
losu
re :
42U
x 3
0”W
x 4
7”D
●A
dd 2
AR
7580
ver
tical
cab
le m
anag
ers
●O
ptio
nal A
R77
16 n
etw
orki
ng ro
of a
vaila
ble
for l
arge
bun
dles
of c
able
rout
ing
over
hear
d
●5”
wid
e si
de e
xter
nal e
xpan
sion
duc
ts
●P
art n
umbe
r for
kit:
QR
AC
K-Q
SV
O46
270
●R
ever
sibl
e -m
ount
ed o
n rig
ht s
ide
as in
take
, m
ount
ed o
n le
ft si
de a
s ex
haus
t
●P
rodu
ct is
cur
rent
ly u
nder
eva
luat
ion
by
Cis
co
●AR
3340
dee
p ne
twor
king
enc
losu
re a
vaila
ble
in
fall
2010
with
inte
grat
ed v
ertic
al c
able
man
ager
s,
pre-
set r
ails
for N
exus
, and
net
wor
king
roof
.
Per
fora
ted
front
to m
atch
doo
rs
AP
C b
y S
chne
ider
Ele
ctric
–N
ame
–D
ate
Net
She
lter N
exus
701
8 S
olut
ion
Ext
erna
l Exp
ansi
on D
ucts
for S
ide
Airf
low
Rea
r ver
tical
baf
fle to
bl
ock
re-c
irc a
ir ac
ross
bac
k of
sw
itch
Fron
t ver
tical
baf
fle
to b
lock
exh
aust
air
Hor
izon
tal t
op b
affle
to
bloc
k re
-circ
air
acro
ss
top
of s
witc
hH
oriz
onta
l top
baf
fle to
is
olat
e ex
haus
t air
acro
ss to
p of
sw
itch
Sid
e ex
tens
ions
are
re
vers
ible
–sa
me
parts
le
ft an
d rig
ht
APC Solutions for Cisco®
Catalyst® SwitchesThe Cisco / APC relationship began in 1998 with a focus on non-stop networking and has since grown to include the integration of various platforms, the sharing of intellectual property for white papers and design specifications as well as joint field engagements.
Power protection is a crucial component of VoIP & IP Telephony networks and helps to ensure that they meet the demands for “always available” systems. To achieve the highest levels of availability, it is essential that Layer 0 solutions support VoIP & IP Telephony networks, in line with your business requirements. This document discusses the power needs of Cisco® Catalyst® Switches and appropriate APC UPS solutions.
APC’s Smart-UPS® is Ideal for Protecting and Supporting Cisco Catalyst Family Switches Which Cisco equipment needs APC Smart-UPS?
> Catalyst 2950 Series, Catalyst 3750 Series, Catalyst 3550 Series, Catalyst 4500 Series
> Catalyst 6500/6500E Series
www.apc.com> Cisco Partnership Information: www.apc.com/techpartners> Wiring Closet Design Tool: configurator.apcc.com> Wiring Closet Solutions: http://apc.com/products/family/index.cfm?id
On Demand trainings at www. Datacenteruniversity.com
APC White Papers> White Paper #88: Power and Cooling Considerations for Power over Ethernet (PoE)
APC Application Notes> Application Note #50: APC Power Protection for Cisco VoIP and IP Telephony Solutions
Resources Available from APC
©2008 American Power Conversion Corporation. All rights reserved. O/ther trademarks are property of their respective owners. /Specifications are subject to change without notice. Last Updated on 8/18/08132 Fairgrounds Rd. West Kingston, RI 02892 USA • Call: 800-800-4APC • Fax: 401-789-3710 • e-mail: [email protected]
APC Smart-UPS® support for Cisco®
CallManager®:APC Smart-UPS supports Cisco CallManager 6.x out-of-the-box with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of CallManager in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially or over the network.
APC Smart-UPS® support for Cisco®
Unity Express® and CUCM 6.x:APC Smart-UPS supports Cisco Unity Express with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of voicemail and automated attendant services in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially and requires the APC Unity Express UPS Simple Signaling Cable (APC Part#AP9840)
Additionally, APC Smart-UPS 750XL and Smart-UPS 1500/1500RM gracefully shutdown Cisco Unified Communications Manager versions 6.x via a point-to-point direct Universal Serial Bus (USB) connection in the event of an extended power outage.
Choose Smart-UPS® RT or Symmetra®
RM/LX for Catalyst 6500 and High Density Environments:Smart-UPS RT, double conversion online family of UPSs offers performance for high density voice and data networks. Supports up to 20kVA in a 12U rack or stack form factor.
Symmetra offers scalability and the additional protection of N+1 redundancy. Symmetra supports from 2-6kVA (RM) in a rack-optimized form or up to 16kVA (LX) in a rack or tower form.
How to choose the right APC Smart-UPS® for a Cisco® Catalyst®
Family Switch?
Step 1: Consider Your Application> What model Cisco Catalyst Switch will the Smart-UPS support?> What is the input voltage for the switch?> Will the Cisco Catalyst Switch support PoE devices? If so, how many and what PoE class?> What is the plug type for the Cisco Catalyst Switch?> How many power supplies does the switch have?> What will be the total loading on the UPS VA and Watts, both initially and in the future?> How much runtime is required if the power goes out?
Step 2: Use the UPS Selector or Call APC for Assistancewww.apc.com/tools/ups_selector/ or 1-800-800-4272 in North America. In other countries, please contact your local APC office from the list provided on APC.com.
Step 3: Purchase an APC Smart-UPS®
> APC Smart-UPS® is the best solution for the Cisco Catalyst Switch family in the wiring closet. > For mission-critical or remote closets, you may also consider the NetBotz® family of accessories which provide real-time environmental monitoring and visibility to your wiring closet environment. > For dense closet and server room environments, consider InRow® RD.> All of these components are InfraStruXure® Certified to integrate seamlessly with the APC InfraStruXure® system.
APC Smart-UPS® and Smart-UPS® XLThe Smart-UPS & Smart-UPS XL use Line-interactive topology offering high reliability and efficiency with good voltage regulation.
> Smart-UPS series offers power outputs from 750VA to 5kVA (480W to 4kW)
> Smart-UPS XL units are available that allow connection of additional battery strings to increase the system run time.