MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 2 of 22
REVISION LIST
SECTION REV DATE DESCRIPTION OF AMENDMENT00 16/11/2010 ISSUED FOR APPROVAL
B0 02/03/2011 ISSUED FOR ORDER
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 3/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 3 of 22
CONTENTS
1 GENERAL ................................................................................................................. 4
2 DEFINITION OF TERMS.......................................................................................... 4
3 SCOPE OF SUPPLY .................................................................................................. 4
4 GENERAL REQUIREMENT..................................................................................15 5
5 PRECEDENCE ........................................................................................................ 17
6
VENDOR DOCUMENT REQUIREMENT.............................................................. 17
7 PROCUREMENT PLAN.......................................................................................... 18
8 QUALITY REQUIREMENT.................................................................................... 18
9 SPARE REQUIREMENTS......................................................................................18 8
10 PERFORMANCE & WARRANTEE / GUARANTEE. ..........................................20 20
11 SPECIAL
REQUIREMENT………………………………………………………….…20Error!
Bookmark not defined.
12 DEFECTS LIABILITY .........................................................................................21 21
13 APPLICABLE DOCUMENTS ..............................................................................21 21
Annexure -1 (Local Control Station Name plate details) Rev C0…………
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 4/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 4 of 22
1 GENERAL
Petrovietnam Central Bio-fuel Joint Stock Company proposes to built the “Dung
Quat Biofuels” Ethanol plant to supply high quality Bio-Ethanol to blend with
gasoline for production. The plant is located in an area of 24 ha in Dung QuatEconomic zone with other industrial projects including Dung Quat refinery . The
Plant will be of high environmental standard, respecting all Vietnamese safety,
Health standard and laws.
Alfa laval India ltd (ALIL) through APTI is process Licensor.PTSC Quang Ngai Co. Ltd is nominated as an EPC contractor (hereinafterreferred to as contractor) for Engineering, Procurement, Construction, and
Commissioning for Dung Quat Bio-Ethanol plant project in Quang Ngai
Province, S.R Vietnam (hereinafter called as Project).
PTSC Quang Ngai Co. Ltd has appointed Aker Powergas Pvt. Ltd Pune as a
Detailed Design & Engineering contractor for Balance of Plant (herein after
referred as BOP)
2 DEFINITION OF TERMS
OWNER: Petro Vietnam Central Biofuel Joint stock Company.CONTRACTOR: PTSC Quang Ngai Co. Ltd / Aker Powergas Pvt. Ltd Pune .
PROJECT: Dung Quat Bio-Ethanol plant.
VENDOR: Supplier of equipments and other accessories mentioned in this MR / Technical Specification.
MR: Material Requisition
APVL : Approved Project Vendor List
3 SCOPE OF SUPPLY
This MR is for Balance of Plant (BOP) only
Contractor is planning to procure Industrial and Flameproof Local control
stations and Light Fittings.
Technical details are described in following documents.
1) Specification for Flameproof and Industrial Local control Stations (LCS),
doc. no. 8455001-007-SP-0013.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 5/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 5 of 22
2) Specification for Industrial and flameproof Type Light fittings, doc. no.
8455001-007-SP-0016.
.
A) MTO FOR LOCAL CONTROL STATIONS (LCS)
A.1) Industrial type LCS / Push Button Stations
Sr.
No
Type of PB
Station (refer
scheme)
Description of LCS/Push Button Station
Type
Cable size
(C=Core)
Quantity
(Nos.)
1 SAAO Industrial Start/Stop Push Button Station 4C x 2.5sqmm.cu. Arm.
33
2 SACOIndustrial Start/Stop Push Button Station withAmmeter (refer annexure-1 for details of
Ammeter)
6C x 2.5sqmm.cu. Arm 12
3 SALOIndustrial Start/Stop Push Button Station with
Local - Remote selector switch
6C x 2.5sqmm.
cu. ArmUnit Rat
4 SAHOIndustrial Start/Stop Push Button Station withLocal -Remote selector switch and Ammeter
10C x 2.5sqmm.cu. Arm
Unit Rat
5 SABO Industrial Stop Push Button Station3C x 2.5sqmm.
cu. Arm18
6 SAVO Industrial Stop Push Button Station withAmmeter
4C x 2.5sqmm.cu. Arm
Unit Rat
A.2) Flameproof type LCS / Push Button Stations
Vendor to supply all Flameproof LCS with Atex/Baseefa certificationLCS type for Hazardous area shall be as below:
a. For Zone 1 – EEx ”d”
b. For Zone 2 – EEx ”d” OR EEx”de”
Sr.No
Type of PBStation (refer
scheme)
Description of LCS/Push Button StationType
Cable size(C=Core)
Quantity(Nos.)
1 F2AOStart/Stop Push Button Station suitable for
Zone-2, IIA/IIB, Temp. class - T3 as per IEC.
4C x 2.5sqmm.
cu. Arm.27
2 F2CO
Start/Stop Push Button Station with Ammeter
for Zone-2, IIA/IIB, Temp. class - T3 as perIEC. (refer annexure-1 for details of
Ammeter)
6C x 2.5sqmm.
cu. Arm7
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 6/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 6 of 22
3 F2LOStart/Stop Push Button Station with Local -Remote selector switch for Zone-2, IIA/IIB,
Temp. class - T3 as per IEC.
6C x 2.5sqmm.cu. Arm Unit Rat
4 F2HO
Start/Stop Push Button Station with Local -
Remote selector switch and Ammeter for
Zone-2, IIA/IIB, Temp. class - T3 as per IEC.
10C x 2.5sqmm.
cu. Arm Unit Rat
5 F2BOStop Push Button Station for Zone-2, IIA/IIB,
Temp. class - T3 as per IEC.
3C x 2.5sqmm.
cu. ArmUnit Rat
6 F2VOStop Push Button Station with Ammeter for
Zone-2, IIA/IIB, Temp. class - T3 as per IEC.
4C x 2.5sqmm.
cu. ArmUnit Rat
Notes to Vendor for Industrial and Flameproof LCS –
1 Local control station quantity is based on inputs received from Mechanical / Package vendor.2. Vendor shall provide cable glands and end plug for Local control station as mentioned in
specification. Gland/end plug Gland sizes shall be as per cable sizes mentioned in above “cable
sizes”3. Refer Specification Scheme for wiring details.
4. Canopy shall be provided for all LCS as per specification.
5. Unit rate shall be furnished by Vendor.6. Vendor to furnish detail catalogue of LCS.
A.3) Flameproof type Welding socket / Receptacle / Junction box
Vendor to supply all Flameproof Welding socket / Receptacle / Junction box
with Atex/ Baseefa certification.
Sr.
NoDescription
Quantity
(Nos.)
1
Welding Receptacle - Flameproof Ex'd' type (Zone-2, Gas group IIA/IIB,
Temp. class T3 as per IEC), 400V, 63A, 50Hz, TPN, IP65, 5 pin type Three phase
100mA ELMCB along with plug complete with interlocked isolators socket outletheavy duty type complying with requirements of IEC 60309, suitable for mounting
on walls / columns. Welding Receptacle shall have loop-in-loop-out facility (2nos.of cable ET entries & looping terminals) suitable for 4Cx25sq.mmCu/XLPE/SWA/PVC cable. 2 nos FLP Cable glands for each socket shall be
supplied by vendor also MS/FRP powder coated canopy (RAL 7032) shall be
supplied.
3
2
Single phase receptacle- Flameproof Ex'd' type (Zone-2, Gas group IIA/IIB,
Temp. class T3 as per IEC), 230V, 16A, 50Hz, 3 pin type single phase 30mA DPELMCB along with plug complete with interlocked isolators socket outlet heavy
duty type complying with requirements of IEC 60309, suitable for mounting on
3
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 7/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 7 of 22
walls / columns. Receptacle shall have loop-in-loop-out facility (2nos. of cable ETentries & looping terminals) suitable for 3Cx4sq.mm Cu/XLPE/SWA/PVC cable.
2 nos FLP Cable glands for each socket shall be supplied by vendor also MS/FRP
powder coated canopy (RAL 7032) shall be supplied.
3.
4 Way Lighting Junction Box - Increased safety type - Ex'e' type (Zone-2, Gas
group IIA/IIB, Temp. class T3 as per IEC), suitable for 230V, 10A, 50Hz. 4 Way3/4" with ET entry Increased safety Ex 'e' type single phase JB die cast
aluminium/FRP material terminals suitable for 3C x2.5sqmm. Cu
XLPE/SWA/PVC armoured cable and feasible to mount on structures / columns / wall, for lighting circuit distribution. (Vendor shall supply 3 cable glands and 1 no.
end plug along with each JB)
14
4
4 Way Lighting Junction Box - Flameproof Ex'd' type (Zone-1, Gas group
IIA/IIB, Temp. class T3 as per IEC), suitable for 230V, 10A, 50Hz. 4 Way 3/4"
with ET entry Ex 'd' type single phase JB die cast aluminium/FRP materialterminals suitable for 3C x2.5sqmm. Cu XLPE/SWA/PVC armoured cable and
feasible to mount on structures / columns / wall, for lighting circuit distribution. .
(Vendor shall supply 3 cable glands and 1 no. end plug along with each JB)
6
5
1 no. switch (DP MCB) in Flameproof enclosure - Ex'd' type (Zone-2, Gasgroup IIA/IIB, Temp. class T3 as per IEC), 230V, 16A, 50Hz, shall have loop-in-
loop-out facility (2nos. of cable ET entries & looping terminals) suitable for3Cx2.5sq.mm Cu/XLPE/SWA/PVC cable. 2 nos FLP Cable glands for each socket
shall be supplied by vendor also MS/FRP powder coated canopy (RAL 7032) shallbe supplied. For lighting switch
3
Notes to Vendor–
1. Vendor shall provide cable glands and end plug as mentioned. Gland/end plug Gland sizes shalbe as per cable sizes mentioned above.
2. Vendor to furnish detail catalogue of LCS.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 8/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 8 of 22
B) MTO FOR LIGHT FITTINGS
B.1) Industrial type Light Fittings (Along with lamps)
Sr.
no.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
Fluorescent Light Fitting
1 4x18 W, Recess mounted Fluorescent Light fitting, mirror
optic and Anti glare luminaries suitable for FTL (T8),
LxW (600mmx600m)
* 5 - 5
2 4x18 W, Recess mounted Fluorescent Light fitting , mirror
optic and Anti glare luminaries and inbuilt battery pack
(Ni- Cad) for 60min back up suitable for FTL (T8), LxW(600mmx600m)
* 1 - 1
3 4x18 W, Recess mounted Fluorescent Light fitting, mirroroptic luminaries suitable for FTL (T8), LxW
(600mmx600m)
* 90 3 93
4 4x18 W, Recess mounted Fluorescent Light fitting , mirror
optic luminaries and inbuilt battery pack (Ni- Cad) for
60min back up suitable for FTL (T8), LxW
(600mmx600m)
* 24 2 26
5 2 x 36 W, Industrial Fluorescent Light fitting with stove
enameled reflector suitable for FTL (T8) (wall/Suspendedmounting)
* 10 - 10
6 2 x 36 W,Industrial Fluorescent Light fitting with stove
enameled reflector and inbuilt battery pack (Ni-cad) for60min back up suitable for FTL (T8) (wall/Suspended
mounting)
* 3 - 3
7 2 x 36 W, Industrial Fluorescent Light fitting with
polycarbonate cover and reflector suitable for FTL (T8)
(suitable for Suspended/wall mounting) suitable for FTL(T8) (suitable for Suspended/wall mounting)
* 131 4 135
8 2 x 36 W, Industrial Fluorescent Light fitting withpolycarbonate cover ,inbuilt battery pack (Ni- cad) for
60min back up and reflector suitable for FTL (T8) (suitable
for Suspended/wall mounting)
*41 2 43
9 2 x 36 W, Industrial Fluorescent Light fitting with
corrosion proof and reflector suitable for FTL (T8)(suitable for Suspended/wall mounting)
* 6 - 6
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 9/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 9 of 22
Sr.
no.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
10 2 x 36 W, Industrial Fluorescent Light fitting with
corrosion proof and inbuilt battery pack (Ni-cad) for 60min
back up and reflector suitable for FTL (T8) (suitable forSuspended/wall mounting)
*Unit
rate- Unit rat
11 2x36 W, Recess mounted Fluorescent Light fitting, mirroroptic and anti glare luminaries suitable for FTL (T8),
*Unitrate
- Unit rat
12
2x36 W, Recess mounted Fluorescent Light fitting , mirroroptic and anti glare luminaries and inbuilt battery pack (Ni-Cad) for 60min back up suitable for FTL (T8)
* Unitrate
- Unit rat
13 2x36 W, Recess mounted Fluorescent Light fitting, mirror
optic luminaries suitable for FTL (T8)*
Unit
rate- Unit rat
14 2x36 W, Recess mounted Fluorescent Light fitting , mirror
optic luminaries and inbuilt battery pack (Ni- Cad) for
60min back up suitable for FTL (T8),
*Unit
rate- Unit rat
Well Glass light fitting
1 Integral Well Glass light fitting with 70W Metal Halide
lamp (E) IP65 (suitable for Suspended/bracket mounting)* 101 4 105
2 Integral Well Glass light fitting with 70W Metal Halide
lamp (E) IP65 (suitable for Pole mounting)* 98 4 102
3 Integral Well Glass light fitting with 150W Metal Halide
lamp (E) IP65 (suitable for Suspended mounting)*
Unit
rate- Unit rat
High / Mid bay light fitting
1 Integral 1x150W Metal Halide (E) with control gear box,enclosed Mid bay Luminaries with aluminum reflector, U
hook for suspension mounting
* 32 4 36
2 Integral 1x250W Metal Halide (E), with control gear boxenclosed Mid bay Luminaries with aluminum reflector, U
hook for suspension mounting
* 13 1 14
3Non - Integral 1x400W Metal Halide (E), enclosed high
bay Luminaries wide beam with aluminum reflector, U
hook for suspension mounting
*Unit
rate- Unit rat
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 10/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 10 of 22
Sr.
no.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
Flood light Fitting
1 Non - Integral Symmetric (wide) beam Flood light fitting
with control gear box 1x250W MH lamp (E), Suitable for
Bracket mounting, IP65
*Unit
rate- Unit rat
2 Non - Integral Symmetric (wide beam) Flood light fitting
with control gear box 1x 400W MH lamp (E), Suitable for
Bracket mounting, IP65
* 2
4
(const.
work)6
Other Light Fitting
1Bulk head CFL / GLS Light Fitting with inbuilt batterypack (Ni-cad) for 60min back up. (Suitable for
Suspended/wall mounting) IP-65
*Unit
rate- Unit rat
2 2x30 watt Aviation / AIR CRAFT WARNING light fitting
with NEON lamp as per ICAO Regulations*
Unit
rate- Unit rat
3 6VA, 230V, Ni-Cad 60 min Battery Backup with lamp
LED for EXIT SIGN* 22 3 25
4 230V, 60W GLS Vessel lamp with switch * Unitrate -
Unit rat
5 230V, 60W GLS Hand Lamp with wire mesh and 20
meters trailing cable and socket*
Unit
rate - Unit rat
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 11/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 11 of 22
B.2) Increased Safety type Light Fittings (Ex “e”) (Along with lamps)
Vendor to supply all Increased safety Light fitting with Atex/Baseefa certification
SUITABLE FOR ZONE -2, IIA/IIB, TEMP CLASS T3
SR
No.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
Increased safety Well Glass light fitting
1 Integral Well Glass Increased safety Ex"e" light fitting forarea classification Zone 2, Gas gr IIB,T3 with 70W Metal
Halide lamp (E),IP-65 (suitable for Suspended/wall
mounting)
*Unit
rate- Unit rat
2 Integral Well Glass Increased safety Ex"e" light fitting for
area classification Zone 2, Gas gr IIB,T3 with 70W Metal
Halide lamp (E),IP-65 (suitable for Pole mounting)
* 61 4 65
3 Integral Well Glass Increased safety Ex"e" light fitting for
area classification Zone 2, Gas gr IIB,T3 with 150W MetalHalide lamp (E),IP-65 (suitable for Suspended/wall
mounting)
*Unitrate
- Unit rat
Increased safety High / Mid bay light fitting
1 Increased safety Non - Integral 1x150W Metal Halide,
Increased safety Ex"e" light fitting for area classificationZone 2, Gas gr IIB,T3, enclosed Mid bay Luminaries with
aluminum reflector, U hook for suspension mounting
*Unitrate
- Unit rat
2 Increased safety Non - Integral 1x250W Metal Halide,
Increased safety Ex"e" light fitting for area classification
Zone 2, Gas gr IIB,T3 enclosed Mid bay Luminaries withaluminum reflector, U hook for suspension mounting
*
Unit
rate- Unit rat
3 Increased safety Non - Integral 1x400W Metal Halide,Increased safety Ex"e" light fitting for area classificationZone 2, Gas gr IIB,T3 enclosed high bay Luminaries wide
beam with aluminum reflector, U hook for suspension
mounting
*Unitrate
- Unit rat
Increased safety Other Light Fitting
1 Increased safety Ex"e" light fitting for area classification
Zone 2, Gas gr IIB,T3, Aviation / AIR CRAFT*
Unit
rate- Unit rat
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 12/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 12 of 22
SR
No.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
WARNING light fitting with NEON lamp as per ICAO
Regulations
2 Increased safety Ex"e" light fitting for area classification
Zone 2, Gas gr IIB,T3,6VA, 230V, 3 HR Battery Backup
with lamp LED EXIT SIGN
*Unit
rate - Unit rat
3 Increased safety Ex"e" light fitting for area classification
Zone 2, Gas gr IIB,T3,230V, 60W GLS Vessel lamp with
switch
*Unit
rate - Unit rat
A.3) Flameproof type Light Fittings (Ex “d”) (Along with lamps)
Vendor to supply all Increased safety Light fitting with Atex/Baseefa certification
SUITABLE FOR ZONE-1, IIA/IIB, TEMP CLASS T3
Sr.
No.
LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
Flameproof Well Glass light fitting
1 Integral Well Glass flame proof Ex"d" light fitting for area
classification Zone 1, Gas gr IIB,T3 with 70W Metal
Halide lamp (E),IP-65 (suitable for Suspended/bracketmounting)
* 8 1 9
2 Integral Well Glass flame proof Ex"d" light fitting for areaclassification Zone 1, Gas gr IIB,T3 with 70W Metal
Halide lamp (E),IP-65 (suitable for Pole mounting)
*3 - 3
3 Integral Well Glass flame proof Ex"d" light fitting for areaclassification Zone 1, Gas gr IIB,T3 with 150W Metal
Halide lamp (E),IP-65 (suitable for Suspended mounting)
* Unitrate
- Unit rat
Flameproof High / Mid bay light fitting
1 Integral 1x150W Metal Halide (E), with control gear box,
flame proof Ex"d" light fitting for area classification Zone1, Gas gr IIB,T3, enclosed Mid bay Luminaries with
aluminum reflector, U hook for suspension mounting
* 4 - 4
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 13/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 13 of 22
Sr.
No.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
2 Non - Integral 1x250W Metal Halide (E), with control gear
box, flame proof Ex"d" light fitting for area classification
Zone 1, Gas gr IIB,T3enclosed Mid bay Luminaries withaluminum reflector, U hook for suspension mounting
*Unit
rate- Unit rat
3 Non - Integral 1x400W Metal Halide (E), flame proof Ex"d" light fitting for area classification Zone 1, Gas gr
IIB,T3enclosed High bay Luminaries with aluminum
reflector, U hook for suspension mounting
*Unit
rate- Unit rat
Flameproof safety Other Light Fitting
1 flame proof Ex"d" light fitting for area classification Zone
1, Gas gr IIB,T3, IP65, Aviation / AIR CRAFT
WARNING light fitting with NEON lamp as per ICAORegulations
*
Unit
rate
- Unit rat
2 flame proof Ex"d" light fitting for area classification Zone
1, Gas gr IIB,T3, IP65, 6VA, 230V, 3 HR Battery Backupwith lamp LED EXIT SIGN
*
Unit
rate - Unit rat
3 flame proof Ex"d" light fitting for area classification Zone1, Gas gr IIB,T3, IP65, 230V, 60W GLS Vessel lamp with
switch
*Unitrate - Unit rat
B.4) Hazardous dust proof type Light Fittings (Along with lamps)
(ZONE-20) – Combustible Dust
(Not required)SUITABLE FOR ZONE-20, COMBUSTIBLE DUST, TEMP CLASS T3
SR
No. LIGHT FITTING DESCRIPTION
Vendor
ModelNo.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
Hazardous Dustproof Well Glass light fitting
1 Integral Well Glass dustproof light fitting for areaclassification Zone20, T3 with 70W Metal Halide lamp
(E),IP-65 (suitable for Suspended/bracket mounting)
*Unitrate - Unit rat
2 Integral Well Glass dustproof light fitting for area
classification Zone20, T3 with 70W Metal Halide lamp*
Unit
rate - Unit rat
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 14/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 14 of 22
SR
No.LIGHT FITTING DESCRIPTION
Vendor
Model
No.
Actual
Qtys.
Spare
Qtys.
Final
Quantit
(E),IP-65 (suitable for Pole mounting)
3 Integral Well Glass dustproof light fitting for area
classification Zone20, T3 with 150W Metal Halide lamp
(E),IP-65 (suitable for Suspended mounting)
*
Unit
rate
- Unit rat
Hazardous Dustproof High / Mid bay light fitting
1 Non - Integral 1x150W Metal Halide (E), with control gearbox dustproof light fitting for area classification Zone20,
T3 enclosed Mid bay Luminaries with aluminum reflector,
U hook for suspension mounting
*Unitrate
- Unit rat
2 Non - Integral 1x250W Metal Halide (E), with control gear
box dustproof light fitting for area classification Zone20,T3 ,enclosed Mid bay Luminaries with aluminum reflector,
U hook for suspension mounting
*Unitrate
- Unit rat
Hazardous Dustproof Other Light Fitting
1 Dustproof light fitting for area classification Zone20, T3
,6VA, 230V, 3 HR Battery Backup with lamp LED EXITSIGN
*
Unit
rate - Unit rat
Notes to Vendor for Industrial and Flameproof Light Fittings –
1 Light fitting quantity is based on Lighting Layouts received from Piping / civil/ Packagevendor.
2. Vendor shall provide cable glands and end plug of light fittings and control gear box as
mentioned in specification. Cable glands/end plug sizes shall be 3core x 2.5 sq.mm. copper
armoured cable.3. Unit rate shall be furnished by Vendor.
4. All Light fittings hardwares like bolts, nut, washers etc. required for mounting shall be suppliedby Vendor.
5. All light fittings shall be quoted along with lamps.
4. Vendor to furnish detail catalogue for each light fitting type.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 15/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 15 of 22
C) SCOPE MATRIX FOR VENDOR & CONTRACTOR FOR BOP
Supply Installation
Site
Supervision
during
installation
Pre-
commissioning
test
Testing and
Commissionin
Industrial and
Flameproof Local
Control Stations
(LCS)
Vendor Contractor Contractor Contractor Contractor
Industrial andFlameproof Light
Fittings
Vendor Contractor Contractor Contractor Contractor
Installation
accessories as
indicated in
specifications
Vendor Contractor Contractor Contractor Contractor
Note to PTSC – Light fittings / Local control station MR for non-BOP areas
will be issued separately by following agencies- 1. Main Process Plant - by Alfa Laval
2. Non Plant building - by PVE3. Packages (Co-Gen/ Cassava/WWTP etc) - by respective Package Vendors
4. Local control station quantity for following packages by respective package
vendor i.e. cooling tower, DM storage, Fresh water & fire water tank area, CO2recovery area, Chiller unit building , compressor area and DDFS area however
Light fitting quantity shall be by APG.
4 GENERAL REQUIREMENT
4.1 Equipment design shall be as per latest edition of codes & standards as specified
in the respective equipment specification.
4.2 Equipment shall be designed such that it shall be easy to operate & maintain.
4.3 Equipment qualification criteria shall be as follows;
Offered equipment shall similar in all respect (i.e. all operating & designparameters requirement). When compared with at least 2 No of models design,
Supplied, installed from same manufacturing plant as that of offered model;
which are successfully operating for 2 or more years. In case of non provenmanufacturer written approval from contractor/Owner shall be obtained. If
improved safety benefits are offered, these may be included only with
Contractor’s prior written approval.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 16/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 16 of 22
4.4 Deviation if any for this specification or for standard mentioned in this
specification any where shall be clearly specified along with the offer as
‘Deviations from Specification’.
4.5 Compliance by vendor with provisions of this specification does not relieve him
of his responsibility to furnish equipment and accessories of proper design to
meet the specified service conditions and or local codes or standards governing
health and safety.
4.6 Any change in design data or unit specification resulting in capacity/performance
modifications shall be done only after prior approval of the contractor/Owner.
4.7 Equipment selected shall operate at specified operating conditions as specified in
the respective specification & data sheet.
4.8 The maximum allowable noise level shall be as per TCVN 5949 from theequipment in any direction. If this not possible necessary acoustic treatment shall
be quoted separately.
Where acoustic treatment is blocking individual equipment access, vendor shouldclearly indicate necessary instructions in operating and maintenance manual
regarding use safety ear plugs and regarding indication of warning notice at
appropriate places.
4.9 All equipment shall be of good industrial quality such as to have a minimum life
expectancy of 20 years assuming normal levels of care and maintenance.
4.10 Equipment packing shall be suitable for marine environment outdoor storage for
6 months.
4.11 Electrical and Instrument items shall be sealed in polythene envelopes. Desiccantshall be enclosed within the envelope for motors, switchgear and control panels, etc.
Warning labels shall indicate that desiccant is contained within.
4.12 As far as possible amount of dismantling shall be minimal for minimizing the
quantity of loose supply. All the ancillary equipments & spares shall be suitablytagged & shall be clearly mentioned in the Vendor’s shipment list.
4.13 Vendor to note that these specifications depict minimum requirements of therequired package. Hence, it is expected from the Vendor to submit to the
Purchaser for agreement all calculations sheets and possible solutions that couldgive technical and/or economical improvement. Vendors are encouraged to
suggest modifications which will improve system design and performance.
4.14 Vendor shall follow project specific documentation & numbering procedure as
attached.
4.15 Vendor list shall be followed as separate document prepared by Contractor.
Document description shall be Approved Project Vendor List (APVL).
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 17/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 17 of 22
5 PRECEDENCE
In case of any conflict following document shall govern with order of precedenceas follows;
Local statutory laws & requirements.
Equipment data sheet & specification.
Purchase requisition.
Applicable codes & standards.
6 VENDOR DOCUMENT REQUIREMENT
Vendor to follow project specific numbering procedure and frames/templates for
all vendor drawings.(The details will be furnished later for successful vendor).
All drawings shall be in AUTOCAD2004.
Vendor shall submit following documents/drawings as minimums during offer.
1) GA & foundation drawings of all the equipments.
2) Procurement plan for equipments & materials. (Showing the way how
the vendor will proceed with this job, describes the country of originof equipments & material for e.g. raw material).
3) All document as required by drawing data schedule.
4) Documentation as required by requisitioned, together with schedule of documents.
5) Proceed spare part list, including parts recommended by VENDOR for
first ,second & third year of operation & maintenance such as
frequency, duration, training if required after sales service (Vendormaintenance service).
6) Statement the preparation and supply of spare parts &interchangeablity register (SPIR) shall be part of the purchaser order
for first, second & third year operating spares & maintenance such asfrequency, duration, training if required after sales service (Vendor
maintenance service or Owners trained operators) in accordance with
SPIR system.
7) Project inspection requirement and material certificate requirements.
8) Operation and maintenance manual (5sets).
9) Quality assurance plan.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 18/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 18 of 22
10) Non conformance with the specification shall be clear & listed
separately.
11) Monthly progress report.
12) For Vendor data and document schedule, Please refer to Annexure of attached document.
7 PROCUREMENT PLAN
Vendor to submit Procurement plan for Equipments mentioned in this MR. It has to
satisfy with the requirement of the contract and schedule for procurement.
8 QUALITY REQUIREMENT
The material used for making the equipments shall be brand new. No used / scrapped
materials are to be used. Each raw materials used for this equipment shall have
factory issued certificate.All bought out items shall have test certificates & from manufacturer.
Equipment should have the name plate it comprises of Serial number, Tag no.and all
technical details with punch year of manufacturing etc.
9 SPARE REQUIREMENTS
9.1 Installation , Pre-Commissioning, Commissioning and Start up Spares
The vendor shall be responsible for providing spares required to prepare the unit for
start-up, and to safeguard the operation of the unit during storage, installation, pre-commissioning, commissioning and start-up periods in accordance with vendor
recommendation and the applicable project specifications.
The Vendor shall provide, with his bid, a list of the recommended installation, pre-
commissioning, and start up spares for all materials under this Requisition including
sub-order items for Purchaser’s evaluation. The Vendor shall develop such spare
parts list in Purchaser’s format based on his final design and equipment selection andsubmit for Purchaser’s review during detail design.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 19/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 19 of 22
As failures and replacements are more frequent during this portion of the Project,
Vendor shall ensure recommending sufficient spares for progressing site work
without delay. If parts other than recommended are damaged or shortages onrecommended spares occur under normal site working condition, vendor shall
provide such parts immediately on demand by the fastest means (i.e. airway
shipment) without impact to the Purchaser. (Normal site working condition isdefined as the condition that Purchaser’s personnel execute site work in accordance
with the instructions by Vendor manual and / or the instructions by Vendor’s
personnel for on-site supervision).
These spares shall be supplied together with the main equipment items to which theyrelate as part of the scope of supply of the Vendor, in a separate box.
9.2 Two (2) Year Operation Spares
The vendor shall be responsible for providing two (2) year operation spares inaccordance with vendor recommendation and Technical Specifications for Owner’s
consideration as an option along with his bid. The vendor shall provide, with his bid,
a priced list of the two (2) year operation spares for all materials under thisRequisition including sub-order items for Purchaser’s evaluation.
The vendor shall develop such spare parts list in Purchaser’s format based on hisfinal design and equipment selection and submit for Purchaser’s review during detail
design.
These spares shall be supplied together with the main equipment items to which they
relate as part of the scope of supply of the Vendor, in a separate box.
9.3 Capital Spares
The vendor shall be responsible for providing insurance spares in accordance with
vendor recommendations and Technical specifications for Owner consideration as anoption. Priced list shall be submitted with his bid. The capital spare parts shall
include the followings, as a minimum.
These spares shall be supplied together with the main equipment items to which they
relate as part of the scope of supply of the vendor, in a separate box.
9.4 Special Tools
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 20/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 20 of 22
The vendor shall be responsible for providing special tools required for the
maintenance or installation of the equipment. Special tools are defined as “any tool,
which is manufactured specifically for use on Vendor’s equipment or material and isrequired for installation, operation and maintenance of any items furnished by the
vendor.
These spares shall be supplied together with the main equipment items to which they
relate as part of the scope of supply of the Vendor, in a separate box.
9.5 Consumables
The vendor shall be responsible for providing commissioning and start-up
consumables (i.e. chemicals, papers, etc.) other than grease and lube/flushing oil, if any. Grease and lube / flushing oil are Purchaser supply. The vendor shall develop
consumables list for Purchaser’s review during detail design.
These consumables shall be supplied together with the main equipment items to
which they relate as part of the scope of supply of the vendor, in a separate box.
10 PERFORMANCE & WARRANTEE / GUARANTEE.
Package & its accessories shall be guaranteed for performance of the all equipmentswithin package operating at specified conditions & rating for a period of 24 months
from date of acceptance certificate.
The equipment and its accessories shall be guaranteed against faulty design
defective or wrong selection materials or poor workmanship or failure from normaluse during the guarantee period.
Vendor shall make necessary and desirable alternation repairs and replacement free
of charge to the purchaser in the event of failure of the equipment.
11 SPECIAL REQUIREMENT
11.1 No prototype or unproven equipment or equipment built to unknown
manufacturing standards shall be incorporated. In this respect, proven shall meana minimum of two (2) separate systems or installations successfully operating for
two (2) or more years. In cases of doubt, the approval of CONTRACTOR shall
be obtained in writing and contractor’s decision shall be final. If improved safetybenefits are offered, these may be included only with Contractor’s prior written
approval.
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 21/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 21 of 22
11.2 The design shall lead to simplicity of operation and maintenance.
11.3 The design of equipment and the selection of construction materials shall be such
as to accommodate all pressures, temperatures, stresses, corrosive conditions etc,which may occur during construction, PRECOMMISSIONING,
COMMISSIONING, and normal operations and as a result of extreme operating
conditions.
12 DEFECTS LIABILITY
The defect liability period for replaced and / or repaired parts of the plant shall expire
thirty five (35) months from the date of the initial acceptance certificate.
13 APPLICABLE DOCUMENTS
Sr.no. Document description Document no. Rev
I General Project Procedure
1 Document Numbering Procedure 8455001-000-PP-0004 08
2 Procurement Procedure 8455001-000-PP-0002 043 Project Quality assurance plan 8455001-000-PP-0008 02
4 Quality assurance manual 8455001-000-PP-0011 00
5 Packing, Marking & Shipping Instructions 8455001-000-PP-0096 00
6 Non-conformance with Project
Specification8455001-000-PP-0051 02
7 Document control procedure 8455001-000-PP-0097 00
8 Vendor document numbering procedure 8455001-000-PP-0112 00
9. Final Vendor data and manufacturer data
record book 8455001-000-PP-0111 00
II Project Standards & Specification
1 Specification for Industrial and
Flameproof Local control station8455001-007-SP-0013 B0
2 Specification for Industrial Type Light
fittings8455001-007-SP-0016 B0
3 Protective Finishes For Electrical
Equipment For Outdoor Use8455001-007-SP-0003 01
4 Requirements for Spare Parts 8455001-2000-GI-M0001 02
5 Training Specification 8455001-000-SP-0002 B0
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 22/28
MATERIAL REQUISITION FOR INDUSTRIAL AND
FLAMEPROOF LOCAL CONTROL STATIONS (LCS)
AND LIGHT FITTINGS
Project NoDiscipline
Code/
Area No.
Doc.Classification
Code
Sequence No. Rev. Page
8455001 3000 RQ E0006 B0 22 of 22
6 Instrument/Electrical Interfacespecification
8455001-005-SP-0024 00
III Applicable Codes & Standards
1 Electrical Engineering standards 8455001-007-SP-0001 B0
IV Hazardous area classification Drawing 8455001-3000-79-R0001 B0
Note – Vendor to follow latest revision of the document.
ANNEXURE -1
Local Control Station name plate details.
Refer Annexure-1 (Revision C0) for LCS MTO tag Plate
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 23/28
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 24/28
Page : 2 of 6
EDMA Ver 1.3
Project No.: 8455001 Document No.:
Project : DUNG QUAT BIO-FUELS ETHANOL PLAN
Client : PTSC Quang Ngai Co. Ltd. Issued For:
Equipment kW
Number Rating
PC-2003A JOCKEY PUMP-1 01-EMCC-03-01 15
PC-2003B JOCKEY PUMP-2 01-EMCC-03-01 15
PC-7305A POTABLE WATER PUMP 01-MCC-03-01 3.7
PC-7305B POTABLE WATER PUMP 01-MCC-03-01 3.7
PC-7302A DMW TRANSFER PUMP 01-MCC-03-01 3.7
PC-7302B DMW TRANSFER PUMP 01-MCC-03-01 3.7
PC-9011 CAUSTIC TRANSFER PUMP 02-MCC-03-06 0.25
PC-6107 BIO ETHANOL PIT EVACUATION PUMP 02-MCC-03-05 18.5
AG-9004 CAUSTIC TANK AGITATOR MOTOR 02-MCC-03-06 0.75
PC-8202A CHILLED WATER PUMPS -II 02-MCC-03-06 11
PC-8202B CHILLED WATER PUMPS -II 02-MCC-03-06 11
AG-8301 THIN SLOP TANK AGITATOR MOTOR 02-MCC-03-06 15PC-7901 EFFLUENT TRANSFER PUMP-I 02-MCC-03-06 5.5
PC-7902 EFFLUENT TRANSFER PUMP-II 02-MCC-03-06 5.5
PC-7903 EFFLUENT TRANSFER PUMP-III 02-MCC-03-06 5.5
PC-7904 EFFLUENT TRANSFER PUMP-IV 02-MCC-03-06 5.5
PC-7906 SEWAGE WATER PUMP-1 02-MCC-03-06 4
PC-7907 SEWAGE WATER PUMP-II 02-MCC-03-05 5.5
PC-7101A COOLING WATER PUMP-1 01-SMV-02-01 425
PC-7101D COOLING WATER PUMP-4 01-SMV-02-01 425
PC-7101B COOLING WATER PUMP-2 01-SMV-02-01 425
PC-7101C COOLING WATER PUMP-3 01-SMV-02-01 425
PC-2001 FIRE FIGHTING SYSTEM MOTOR 01-SMV-02-01 480
PC-8116B BOILER FEED WATER PUMP 01-SMV-02-01 315
PC-8116A BOILER FEED WATER PUMP 01-SMV-02-01 315
Z-8101A STG - PA FAN MOTOR 01-SMV-02-01 355
Z-8102A STG - SA FAN MOTOR 01-SMV-02-01 200
FA-8104A STG - ID FAN MOTOR 01-SMV-02-01 355
Z-8201 PROCESS WATER CHILLER MOTOR 02-SMV-02-01 250
SPARE
SPARE
SPARE
SPARE
Aker Powergas Pvt. Ltd., Pune
INDUSTRIAL LOCAL CONTROL STATION
SAAO : MOTOR INDUSTRIAL LOCAL START / STOP PUSH BUTTON
Description on Name plate Board No. Remarks
Annexure -1
Rev No.: C0 , Rev Date: 28/02/2011
ORDER
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 25/28
Page : 3 of 6
EDMA Ver 1.3
Project No.: 8455001 Document No.:
Project : DUNG QUAT BIO-FUELS ETHANOL PLANT
Client : PTSC Quang Ngai Co. Ltd. Issued For:
Equipment Ammeter CT kW
Number Ratio Rating
PC-8201A CHILLED WATER PUMPS -I 75/1 02-MCC-03-06 37
PC-8201B CHILLED WATER PUMPS -I 75/1 02-MCC-03-06 37
PC-8301ATHIN SLOP TRANSFER PUMP
(BY ALIL)150/1 02-MCC-03-06 55
PC-8301BTHIN SLOP TRANSFER PUMP
(BY ALIL)150/1 02-MCC-03-06 55
Z-7101-1COOLING TOWER FAN-1
(START/STOP LCS)250/1 01-PCC-03-01 110
Z-7101-2
COOLING TOWER FAN-2
(START/STOP LCS) 250/1 01-PCC-03-01 110
Z-7101-3COOLING TOWER FAN-3
(START/STOP LCS)250/1 01-PCC-03-01 110
Z-7101-4COOLING TOWER FAN-4
(START/STOP LCS)250/1 01-PCC-03-01 110
PC-7301APROCESS WATER TRANSFER
PUMP250/1 01-PCC-03-01 110
PC-7301BPROCESS WATER TRANSFER
PUMP250/1 01-PCC-03-01 110
SPARE 150/1
SPARE 250/1
Aker Powergas Pvt. Ltd., Pune
INDUSTRIAL LOCAL CONTROL STATION
SACO : INDUSTRIAL LOCAL START / STOP PUSHBUTTON WITH AMMETER
Description on Name plate Board No. Remarks
Annexure -1
Rev No.: C0 , Rev Date: 28/02/2011
ORDER
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 26/28
Page : 4 of 6
EDMA Ver 1.3
Project No.: 8455001 Document No.:
Project : DUNG QUAT BIO-FUELS ETHANOL PLAN
Client : PTSC Quang Ngai Co. Ltd. Issued For:
Equipment kVA
Number Rating
02-TRN-02-06 DISTRIBUTION TRANSFORMER 02-SMV-02-01 1600
02-TRN-02-05 DISTRIBUTION TRANSFORMER 02-SMV-02-01 1600
02-TRN-02-04 DISTRIBUTION TRANSFORMER 02-SMV-02-01 2500
02-TRN-02-03 DISTRIBUTION TRANSFORMER 02-SMV-02-01 2500
02-TRN-02-02 DISTRIBUTION TRANSFORMER 02-SMV-02-01 2500
02-TRN-02-01 DISTRIBUTION TRANSFORMER 02-SMV-02-01 2500
01-TRN-02-01 DISTRIBUTION TRANSFORMER 01-SMV-02-01 2000
01-TRN-02-02 DISTRIBUTION TRANSFORMER 01-SMV-02-01 2000
01-CAP-02-01 MV CAPACITOR PANEL 01-SMV-02-01 500
01-CAP-02-02 MV CAPACITOR PANEL 01-SMV-02-01 1000
01-TRN-01-02 POWER TRANSFORMER (8MVA) 01-SMV-02-01 8000
01-TRN-01-01 POWER TRANSFORMER (8MVA) 01-SMV-02-01 8000
Z-7101-1COOLING TOWER FAN-1 (EM. STOP LCS TO
BE WIRED FROM START/STOP LCS)01-PCC-03-01 110 kW
Z-7101-2COOLING TOWER FAN-2 (EM. STOP LCS TO
BE WIRED FROM START/STOP LCS)01-PCC-03-01 110 kW
Z-7101-3COOLING TOWER FAN-3 (EM. STOP LCS TO
BE WIRED FROM START/STOP LCS)01-PCC-03-01 110 kW
Z-7101-4COOLING TOWER FAN-4 (EM. STOP LCS TO
BE WIRED FROM START/STOP LCS)01-PCC-03-01 110 kW
SPARE
SPARE
Aker Powergas Pvt. Ltd., Pune
FIELD DEVICE LIST
SAB0 : INDUSTRIAL EMERGENCY LOCAL STOP PUSHBUTTON
Description on Name plate Board No. Remarks
Annexure -1
Rev No.: C0 , Rev Date: 28/02/2011
ORDER
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 27/28
Page : 5 of 6
EDMA Ver 1.3
Project No.: 8455001 Document No.:
Project : DUNG QUAT BIO-FUELS ETHANOL PLANT
Client : PTSC Quang Ngai Co. Ltd. Issued For:
Equipment kW
Number Rating
PC-6108 BIO ETHANOL PIT EVACUATION PUMP 02-MCC-03-05 7.5
PC-6109 DENATURANT DOSING PUMP 02-MCC-03-05 1.1
PC-9010 AQ.NH3 BUND EVACUTION PUMP 02-MCC-03-05 1.1
PC-9012 CAUSTIC BUND EVACUATION PUMP 02-MCC-03-06 1.1
PC-7905 EFFLUENT TRANSFER PUMP-V 02-MCC-03-05 5.5
PC-9001 H2SO4 TRANSFER PUMP 02-MCC-03-05 2.2
PC-9005 H2SO4 UNLOADING PUMP 02-MCC-03-05 3.7
PC-9006 H2SO4 BUND EVACUATION PUMP 02-MCC-03-05 1.1
PC-9003 AQ.NH3 TRANSFER PUMP 02-MCC-03-05 0.25
PC-9009 AQ.NH3 UNLOADING PUMP 02-MCC-03-05 1.1
PC-6102A OFFSPEC-BIO-ETHANOL TRANSFER PUMP 02-MCC-03-05 5.5
PC-6102B OFFSPEC-BIO-ETHANOL TRANSFER PUMP 02-MCC-03-05 5.5
PC-6106 DENATURANT UNLOADING PUMP 02-MCC-03-05 2.2
PC-6103A DENATURANT DOSING PUMP 02-MCC-03-06 2.2
PC-6103B DENATURANT DOSING PUMP 02-MCC-03-06 2.2
PC-7201A LP CONDENSATE TRANSFER PUMP 02-MCC-03-06 5.5
PC-7201B LP CONDENSATE TRANSFER PUMP 02-MCC-03-06 5.5
SPARE CABLE SPARE CABLE 02-MCC-03-05 1.1
PC-2101A SLURRY MIX PUMP A 02-SMV-02-01 185
HM-8503C CASSAVA HAMMER MILL-3 02-SMV-02-01 250
HM-8503A CASSAVA HAMMER MILL-1 02-SMV-02-01 250
HM-8503B CASSAVA HAMMER MILL-2 02-SMV-02-01 250PC-2101B SLURRY MIX PUMP B 02-SMV-02-01 185
SPARE
SPARE
SPARE
SPARE
Aker Powergas Pvt. Ltd., Pune
FIELD DEVICE LIST
F2AO : MV MOTOR FLP LOCAL START / STOP PUSH BUTTON
Description on Name plate Board No. Remarks
Annexure -1
Rev No.: C0 , Rev Date: 28/02/2011
ORDER
5/16/2018 8455001-3000-RQ-E0006 Rev.B0 MR for Industrial and Flameproof LCS and Light Fittings. - slidepdf.com
http://slidepdf.com/reader/full/8455001-3000-rq-e0006-revb0-mr-for-industrial-and-flameproof-lcs-and-light-fittings 28/28
Page : 6 of 6
EDMA Ver 1.3
Project No.: 8455001 Document No.:
Project : DUNG QUAT BIO-FUELS ETHANOL PLANT
Client : PTSC Quang Ngai Co. Ltd. Issued For:
Equipment Ammeter CT kW
Number Ratio Rating
PC-6104ACOMMERCIAL BIO-ETHANOL
TRANSFER PUMP75/1 02-MCC-03-05 30
PC-6104BCOMMERCIAL BIO-ETHANOL
TRANSFER PUMP75/1 02-MCC-03-05 30
PC-8302AWHOLE STILLAGE TRANSFER
PUMP (BY ALIL)75/1 02-MCC-03-06 37
PC-8302BWHOLE STILLAGE TRANSFER
PUMP (BY ALIL)75/1 02-MCC-03-06 37
PC-6101A BIO-ETHANOL TRANSFER PUMP 75/1 02-MCC-03-06 30
PC-6101B BIO-ETHANOL TRANSFER PUMP 75/1 02-MCC-03-06 30SPARE 75/1
Aker Powergas Pvt. Ltd., Pune
FIELD DEVICE LIST
F2CO : FLAMEPROOF LOCAL START / STOP PUSHBUTTON WITH AMMETER
Description on Name plate Board No. Remarks
Annexure -1
Rev No.: C0 , Rev Date: 28/02/2011
ORDER