RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 1
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
103 Group Change OPTION Disabled Disabled Enabled
110 Trip Mode 3pole only 1 & 3 pole 1-/3pole
112 Phase Distance Quadrilateral Quadrilateral MHO Disabled
113 Earth Distance Quadrilateral Quadrilateral MHO Disabled
120 Power Swing Disabled Enabled Enabled
121 Teleprot. Dist. PUTT POTT (Line Specific
Setting) POTT UNBLOCKING BLOCKING Disabled
122 DTT Direct Trip Disabled Disabled Enabled
124 SOTF Overcurr. Disabled Enabled Enabled
125 Weak infeed Disabled Disabled Enabled
126 Back-Up O/C Disabled TOC IEC (Enabled for prtn in case of VT fail & for Stub Prtn)
TOC IEC TOC ANSI
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 2
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
131 Earth Fault O/C Disabled TOC IEC TOC IEC TOC ANSI TOC Logarithm. Definite Time
132 Teleprot. E/F Dir. Comp. Pickup Disabled UNBLOCKING BLOCKING Disabled
133 Auto Reclose Disabled Disabled 1 AR-cycle 2 AR-cycles 3 AR-cycles 4 AR-cycles 5 AR-cycles 6 AR-cycles 7 AR-cycles 8 AR-cycles ADT
134 AR Control Mode Pickup w/Tact Pickup w/Tact
Pickup w/o Tact Trip w/Tact Trip w/o Tact
135 Synchro-Check Disabled Disabled Enabled
137 Overvoltage Disabled Enabled
(not required for 220kV lines)
Enabled
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 3
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
138 Fault Locator Disabled Enabled Enabled
139 BREAKER FAILURE Disabled Disabled Enabled
140 Trip Circ. Superv Disabled Disabled 1 trip circuit 2 trip circuit 3 trip circuit
Power System Data
201 CT Starpoint Towards Line Towards Line towards Busbar
203 Unom PRIMARY 1.0.1200.0 KV 400
(Line Specific Setting)
204 Unom SECONDARY 80.125 V 110
205 CT PRIMARY 10.5000 A 2000 (Line Specific
Setting)
206 CT SECONDARY 1A 1 5A
210 U4 transformer not connected Not
connected Udelta transformer Usync transformer Ux reference transformer
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 4
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
211 Uph/Udelta 0.10.9.99 1.73
212 Usync connect L1-E L1-E L2-E L3-E L1-L2 L2-L3 L3-L1
214 Usync-Uline 0.36 0
215 U-line / Usync 0.80.1.20 1
220 14 transformer Not connected Neutral current (Line Specific Setting -
1.For D/C lines= Neutral Current of Parallel line with wiring of
Mutual compensation,
2.For S/C lines= Not Connected or if neutral is
wired in I4 wdg.of relay then Neutral Current of
protected line)
Neutral Current (of
of parallel line
the protected line)
Neutral Current of the parallel line Starpoint Curr.of earthed power transf.
221 I4/Iph CT 0.010.5.000 1
230 Rated Frequency 50 Hz 50 Hz 60 Hz
235 PHASE SEQ L1L2L3 L1L2L3 L1L3L2
236 Distance Unit km km
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 5
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
miles
237 Format Z0/Z1 Zero seq. comp.factors
Zero seq. comp.
RE/RL and XE/XL
factors RE/RL and
XE/XL Zero seq.comp. Factor KO and angle(KO)
239 T-CB close 0.01..0.60 sec 0.05 sec (
Not required )
240 Tmin TRIP CMD 0.02..30.00 sec 0.10 sec
241 Tmax CLS CMD 0.01..30.00 sec
0.10 sec ( Not required )
242 T-CB test-dead 0.00..30.00 sec 1.0 Second
302 CHANGE Group A Group A Group B Group C Group D Binary Input Protocol
D R Settings
402A WAVE FORM CAPTURE
Save with Pickup
Save With Pick Up
(If Auto-down loading of DR
is on then save with pickup,
otherwise save with Trip)
Save with TRIP Start with TRIP
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 6
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
403A SCOPE OF WAVE FORM DATA Fault event
Power System Fault
Power System fault
410 MAX LENGTH 0.30..5.00 sec 3.00 sec
411 PRE. TRING. TIME 0.05..5.00 sec 0.5
412 POST REC. TIME 0.05..5.00 sec 2
415 Binin CAPT.TIME 0.10..5.00 sec 1.0 seconds
610 Flt Disp. LED/LCD
DIsplay Targets on every
Display Targets on
every Pickup Pickup Display Targets on DROP only
Line Parametrs ( In ohms/perkm/per phase primary ohms )
R1 = 0.0288
(Line Specific Setting, given
data is for 400kV Twin Moose D/C
line )
X1 = 0.328
Ro = 0.285 Xo = 1.02
RoM = 0 XoM = 0
Zone Reaches ( In percentage )
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 7
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Z1 = 80.00%
(Line Specific Settings)
Z1B = 120.00% Z2 = 120.00% Z3 = 653.00% Z4 Reverse = 20.00% Z5 = 653.00%
Station Name 400/220kV Angul
Line Name
400kV S/C Angul-Meramundali
General Protection Data
1103 Full Scale Volt. 1.0.001200 kV 400
(Line Specific Setting, given
data is for 400kV Twin Moose D/C
line )
1104 Full Scale Curr. 10..5000 A 2000
1105 Line Angle 30..89 85
1110 x' 0.005..6.500 Ohm/km 0.1804
1111 Line Length 1.0..1000.0 km 18
1112 x' 0.005..10.500 Ohm/mile NA
1113 Line Length 0.6..650.0 Miles NA
1116 RE/RL(Z1) -33.7 2.97 (Line Specific Setting, given
data is for 400kV Twin Moose D/C
1117 XE/XL(Z1) -33.7 0.70
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 8
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
1118 RE/RL(Z1B..Z5) -33.7 2.97 line, however, max value of
RE/RL is to be limited to 2 even if it is
coming more than 2 as per
conductor parameters)
1119 XE/XL(Z1B..Z5) -33.7 0.70
1120 K0(Z1) 0.000.4.00 0.74
1121 Angle KO(Z1) -135.00135 -15.30 (Line Specific Setting, given
data is for 400kV Twin Moose D/C
line )
1122 KO(Z1) 0.000.4.000 0.74
1123 Angle KO(>Z1) -135.00135 -15.30
1126 RM/RL Paraline 0.00..8.00 0.00
1127 XM/XL Para Line 0.00..8.00 0.00
1128 RATIO Par. Comp 50.95% 0.85
1130 Pole Open Current 0.05..1.00 A 0.1 Amps (around 10% of 1Amp)
1131 Pole Open Voltage 2.70 A 20 V (around 30% of 63.5volt)
1132 Sl Time all Cl. 0.01..30.00 0.2 seconds
1133 Minimum Time for Line Open 0.05 -30 0.5 seconds before SOTF
1134 Line Closure Manual Close BI only Current OR voltage or Manual close BI
Current OR voltage or Manual close BI
Cbaux OR Current or
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 9
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Man- ual close BI Current flow or Manual close BI
1135 Reset Trip CMD with Pole Open Current
with Pole Open Current
Threshold only Threshold only
with Cbaux AND Pole Open Current
1136 Open Pole Detector Off With
Measurement with Cbaux AND Pole Open Current With Measurement
1140 I-Ctsat. Thres. 0.2..50.0 A 20 Amps
(approx. limited to fault level)
1150 Sl Time Man.Cl 0.01..30.00 sec 0.2 Seconds
1151 SYN.MAN.CL
with Synchronism-check No without Synchronism-check NO
1155 3pole coupling with Pickup With Trip with Trip
1156 Trip2ph Flt 3 pole 3 pole 1 pole, leading phase 1 pole, lagging
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 10
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
phase
Distance Protection data
1201 FCT Distance ON ON OFF
1202 Minimum Iph> 0.10..4.00 A 0.1
1203 310> Threshold 0.05..4.00 A 0.10
1204 3U0> Threshold 1..100 V 5 V
1207 310>/Iphmax 0.05..0.30 0.15
1208 Series Compensation Yes/ No No (Line Specific
Setting)
1209 EF Recognition 3I0> or 3U0> 3I0> or 3U0> 3I0> and 3U0>
1210 Start timers On Dis P/U On Dis P/U On Zone P/U
1215 Parall. Line Comp NO YES (Line Specific
Setting) YES
1221 2Ph-E faults Blcok leading ph-e loop All loops block lagging ph-e loop all loops only phase-phase loops only phase-earth loops
1232 SOFT Zone with Pickup(non-
with Zone Z1B
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 11
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
directional) with Zone Z1B Inactive
1241 R load (ph-E) 0.10..250.00 Ohm
Guidelines- RLoad (Primary value): 400kV Twin Conductor = 86ohm 400kV Tripple/Quad Conductor=
65ohm, 765kV Quad Conductor= 135ohm, 220kV Single Conductor= 98ohm,
(In relay to be fed in secondary ohms), Angle Load - Short
Lines(upto 200kM) =26deg, Long Lines(more than 200kM &
220kV) =35deg
1242 Angle Load (ph-E) 20.60 degree
1243 R load (ph-ph) 0.10..250.00 Ohm
1244 Angle load (ph-ph) 20..60 degree
Distance Protection with polygonal tripping Chatracteristic
1301 Op. mode Z1 Forward Forward Reverse Non-directional Inactive
1302 R(Z1) (ph-ph) 0.05..250.00 Ohm 8.25
1303 X(Z1) 0.05..250.00 Ohm 2.60
1304 RE(Z1) Ph-E 0.05..250.00 Ohm 30.25
1305 T1 - 1 phase 0.00..30.00 sec 0.00 sec
1306 T1 - multi-phase 0.00..30.00 sec 0.00 sec
1307 Zone reduction 0..30 degree 5 degree
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 12
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
1311 Op.mode Z2 Forward Forward Reverse Non-Directional Inactive
1312 R(Z2) ( ph-ph) 0.05..250.00 Ohm 16.50
1313 X (Z2) 0.05..250.00 Ohm 3.90
1314 R(Z2) O-E 0.05..250.00 Ohm 38.50
1315 T2-1 phase 0.00 - 30.00 sec 0.3 Secs (line specific)
1316 T2- multi phase 0.00 - 30.00 sec 0.3 secs
1317 Trip 1 pole Z2 NO NO YES
1321 Op. mode Z3 Forward Forward Reverse Non-Directional Inactive
1322 R(Z3) ph-ph 0.05..250.00 Ohm 27.50
1323 X(Z3) 0.05..250.00 Ohm 21.20
1324 R(Z3) ph-E 0.05..250.00 46.75
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 13
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Ohm
1325 T3 DELAY 0.00..30.00 sec 1.0 secs
(region specific)
1325 T3 DELAY 0.00..30.00 sec 1.0 secs
1331 Op. mode Z4 Forward Reverse Reverse Non-Directional Inactive
1332 R(Z4) ph-ph 0.05..250.00 Ohm 8.25 (equal to Z3 reach for long line-more 100kM, equal to
Z1 reach for short line)
1333 X ( Z4 ) 0.05..250.00 Ohm 0.65
(10 to 20% of protected line)
1334 R(Z4) ph-E 0.05..250.00 Ohm 30.25
1335 T4 DELAY 0.00..30.00 sec 1.1 sec (Tz3+0.1sec)
1341 Op. mode Z5 Forward Non
Directional To act as
Non directional starter with infinite time delay and
reach equal to 120% of
Zone3 reach
Reverse Non-Directional Inactive
1342 R(Z5) ph-ph 0.05..250.00 Ohm 33.00
1343 X ( Z5 ) 0.05..250.00 Ohm 21.20
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 14
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
1344 R(Z5) ph-E 0.05..250.00 Ohm 50.48
1345 T5 DELAY 0.00..30.00 sec infinite (oo)
1346 X(Z5) - 0.05..250.00 Ohm 21.20
1351 Op. mode Z1B Forward Forward Reverse Non-Directional Inactive
1352 R(Z1B) ph-ph 0.05..250.00 Ohm 16.50
1353 X(Z1B) 0.05..250.00 Ohm 3.90
(line specific = Zone2 reach)
1354 R(Z1B) ph-E 0.05..250.00 Ohm 38.50
1355 T1B-1 phase 0.00 - 30.00 sec 0.0 secs
1356 T1B- multi phase 0.00 - 30.00 sec 0.00 sec
1356 T1B- multi phase 0.00 - 30.00 sec 0.00 sec
1357 1st AR-> Z1B NO No YES
Power Swing Settings
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 15
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
2002 P/S Op. mode all zones blocked
Z2 to Z5 blocked
Z1/Z1B blocked Z2 to Z5 bocked 1.Z1B,Z2 blocked
2006 Power Swing trip NO NO (Applicable only for Out of Step Tripping)
YES
2007 Trip Delay after Power swing blocking 0.08 to 5 sec 2sec
(unblocking time for power swing)
Distance protection teleprotection Schemes
2101 FCT Telep. Dis. ON ON YES
2102 Type of Line Two terminals Two
terminals Three terminals
2103 Send Prolong 0.00 - 30.00 sec 0.07 sec
2107 Delay for alarm 0.00 - 30.00 sec NA
2108 Release Delay 0.00 - 30.00 sec NA
2109 TrBlk Wait Time 0.00 - 30.00 sec NA
2110 TrBlk Block Time 0.00 - 30.00 NA
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 16
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
sec
2201 FCT Direct Trip ON NO OFF
2202 Trip time DELAY 0.00 - 30.00 sec NA
2401 FCT SOTF-O/C ON ON OFF
2404 I>>> 0.00 - 25.00 A 1.5 Amps (for long lines 1.5pu, for short lines 2.5pu)
Weak End Infeed
2501 FCT Weak Inteed OFF OFF Echo only Echo and Trip
Back up O/C current Function Settings
2601 Operating Mode ON Only Active with Loss of
Only Active with Loss of
VT sec. Circuit
VT sec. Circuit OFF
2630 Iph> STUB 0.10..25.00 A 2.0A
2631 T Iph STUB 0.00..30.00 sec 0.1 sec
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 17
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
2632 310> STUB 0.05..25.00 A 2.0 A
2633 T 310> STUB 0.00..30.00 sec 0.1 sec
2634 I -STUB Tele/B1 NO NO YES
2635 I -STUB SOTF NO NO YES
YES
2680 SOTF Time DELAY 0.00..30.00 sec 0.2 Secs
Supervision function Settings
2901 MEASURE SUPERV ON OFF YES
2910 FUSE FAIL MON ON ON OFF
2911 FFM U> (min) 10.100 V 50 Volts
2912 FFM U> (max) 0.10..1.00 A 0.2 Amps
2913 FFM U
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 18
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Earth Fault Overcurrent Settings
3101 FCT EarthFltO/C ON ON OFF
3102 BLOCK for Dist. With every Pickup
With every Pickup
with single-phase Pickup with multi-phase Pickup NO
3103 BLOCK 1pDead Tim YES YES NO
3104 lph-STAB Slope 0- 30 % 10%
3105 31oMin Teleprot 0.01..1.00 A NA
3105 31oMin Teleprot 0.003..1.000 A NA
3109 Trip 1 pole in E/F Yes/ No No
3110 Op. mode 310 >>> Forward Inactive Reverse Non-Directional Inactive
3120 Op. mode 310>> Forward Inactive Reverse Non-Directional Inactive
YES
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 19
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
3130 Op. mode 310> Forward Inactive Reverse Non-Directional Inactive
3140 Op. mode 310p Forward Forward Reverse Non-Directional Inactive
3141 310p PICKUP 0.20..25.00 A 0.1
3143 310p Time Dial 0.05..3.00 sec 0.58 (Line Specific
Setting)
3144 310p Time Dial 0.50..15.00 NA
3145 310p Time Dial 0.50..15.00 sec NA
3146 T 310p MaxT DELAY 0.00..30.00 sec NA
3147 Add.T-DELAY 0.00..30.00 sec 0
3148 310p Telep/B1 NO NO YES
3149 310p SOTF-Trip NO NO YES
3150 310p InrushBlk NO NO
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 20
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
YES
3151 IEC curve Normal Inverse
Normal Inverse
Very Inverse Extremely Inverse Long time Inverse
3152 ANSI Curve Inverse NA Short Inverse Long Inverse Moderately Inverse Very Inverse Extremely Inverse Definite Inverse
3153 LOG Curve Logarithmic Inverse NA
3154 310p Startpoint 1.0..4.0 NA
3160 POLARIZATION with UO and 1Y (dual
with U2 and I2 (negative sequence)
polorized) with 1Y (transformer star point current) with U2 and I2 (negative sequence)
3162 Dir. ALPHA 0..360 degree 338 degree
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 21
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
3163 Dir. BETA 0..360 degree 122 degree
3164 3U0> 0.5..10.0 V 2 V
3165 IY> 0.05..1.00 A 0.2 A
3166 3U2> 0.5..10.0 V 5 V
3167 312> 0.05..1.00 A 0.1
3170 2nd InrushRest 10..45% NA
3171 Imax InrushRest 0.50..25.00 A NA
3172 SOTF Op. Mode with Pickup (non- NA directional) with Pickup and direction
3173 SOTF Time DELAY 0.00..30.00 sec NA
Teleprotection for Earth fault Relay
3201 FCT Telep. E/F ON OFF OFF
3210 TrBlk lock time 0.00..30.00 sec NA
Auto reclose Function
3401 Automatic Reclosure ON / OFF OFF
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 22
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Synchronism Function
3501 FCT Synchronism ON/ OFF OFF
Voltage Protection Function
3701 FCT U Phase - e OFF ON (line specific) ALARM ONLY ON U> Alarm U>>Trip
3702 Uph -e> 1.0-170 Volts 69.30 (stg1=110% - line specific)
3703 T Uph -e > 0.00-30.00 secs
4 sec for Ckt-I & 5 sec for Ckt-II
3704 Uph -e>> 1.0-170 Volts 94.50 (stg2=150%)
3705 T Uph -e >> 0.00-30.00 secs 0.1 secs
3721 3 Uo > Staus OFF OFF ALARM ONLY ON
3722 3 Uo 1.00 -220 volts 31.75
3723 3 Uo Reset ratio 0.50 - 0.95 0.95
3724 T 3 Uo 0.00- 0.30 secs 0.1
3725 T sen Impulse 3Uo 0.05-0.50secs 0.1
RELAY SETTING FORMAT
Format No. MR/ENGG/07 Rev-0
RECOMMENDED RELAY SETTINGS FOR
PRPD : ANIL KUMAR
DEPTT:
ENGINEERING
400 kV Meramundali S/C LINE-2 MAIN I Relay ( 7SA522)
CHKD : PK RAY REV : 00 DATE: 24/12/2013
REV : NO.: 00
SUBSTATION: 765/400KV ANGUL
APPD : VIBHAY KUMAR
THIS SHEET: 23
NEXT SHEET:
ABOVE SETTINGS IMPLEMENTED ON DATE ..
Signature (s/s in charge)
NOTE : SITE TO RETURN THIS SIGNED COPY TO ENGINEERING AFTER IMPLEMENTATION
Fault Locator Settings
3802 START Pick Up Trip Trip
3805 Parallel line Compensation NO YES (line specific)
YES
3806 Load Compensation NO YES YES
Breaker Failure Function Settings
3901 FCT Breaker Failure ON OFF OFF
Trip Circuit supervision
4001 FCT Trip Supervision ON OFF OFF