SIEMENS PTD-HA/3000467425/ED2.121.001.W-0 Document no.- Rev - 2 RELAY SETTING CALCULATION 220 KV DURSHED FEEDER - 2 DISTANCE PROTECTION RELAY NEW 400/220KV SUBSTATION AT WARANGAL LOA REF: C-55807-S119A-7/LOA-1/2020 DATED 31.03.2006 POWERGRID CORPORATION OF INDIA LIMITED Name Department Telephone Place Date Signature Author: Approval: LAXMINARAYAN PTD-HA 0124-2846155 GURGAON - Rev Date Revised items Remarks 1 04.10.08 FOR APPROVAL KNR RL 2 19.12.08 SETTING REVISED ALL KNR RL Total pages 25 Siemens Ltd., PTD Division Copying this document, and giving it to others and the use or communication of the contents thereof, without express authority. Offenders are liable to the payment of damages. All rights are reserved i the grant of patent or registration of a utility model or design TRANSMISSION SYSTEM ASSOCIATED WITH GRID STRENGTHENING FOR TAMILNADU & ANDRA PRADESH Page no Name of reviser Name of Approver

7SA522 arelay Setting Calculation

  • Upload
    1453h

  • View
    1.596

  • Download
    505

Embed Size (px)

DESCRIPTION

sample

Citation preview

Page 1: 7SA522  arelay Setting Calculation

SIEMENSPTD-HA/3000467425/ED2.121.001.W-0

Document no.- Rev - 2

RELAY SETTING CALCULATION

220 KV DURSHED FEEDER - 2 DISTANCE PROTECTION RELAY

NEW 400/220KV SUBSTATION AT WARANGAL

LOA REF: C-55807-S119A-7/LOA-1/2020 DATED 31.03.2006

POWERGRID CORPORATION OF INDIA LIMITED

Name Department Telephone Place Date Signature

Author:

Approval: LAXMINARAYAN PTD-HA 0124-2846155 GURGAON -

Rev Date Revised items Remarks

1 04.10.08 FOR APPROVAL KNR RL

2 19.12.08 SETTING REVISED ALL KNR RL

Total pages 25

Siemens Ltd., PTD Division

Copying this document, and giving it to others and the use or communication of the contents thereof, are forbidden

without express authority. Offenders are liable to the payment of damages. All rights are reserved in the event of

the grant of patent or registration of a utility model or design

TRANSMISSION SYSTEM ASSOCIATED WITH GRID STRENGTHENING FOR TAMILNADU & ANDRA PRADESH

Page

no

Name of

reviser

Name of

Approver

Page 2: 7SA522  arelay Setting Calculation
Page 3: 7SA522  arelay Setting Calculation

1 of 25

400/220 KV xxxxxxxxx SUBSTATION

220kV yyyyyyyyyy FEEDER

SIEMENS DISTANCE PROTECTION RELAY SETTING CALCULATION

1.0 Relay Data:

1.01 ANSI No. = 21

1.02 Description = Distance + Over Voltage Prot.

1.03 Make = SIEMENS

1.04 Model No. = 7SA522

2.0 Input Data:

2.01 System voltage = 220 KV

2.02 Source substation = WARANGAL 400/220KV

2.03 Conductor used = ACSR Kundah

2.04 Protected Line length = 75 Km

2.05 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

2.06 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

2.07 Longest Line length = 71 Km

2.08 Conductor used = ACSR KUNDAH

2.09 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

2.10 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

2.11 Shortest Line length (.) = 53 Km

2.12 Conductor used = ACSR KUNDAH

Page 4: 7SA522  arelay Setting Calculation

2 of 25

2.13 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

2.14 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

2.15 3Ф fault current at WARANGAL 220 KV Substation Magnitude Angle

= 40000 -79

2.16 1Ф fault current at WARANGAL 220 KV Substation Magnitude Angle

= 40000 -79

2.17 Tower Footing Resistance = 10 Ω

2.18 Direction - Zone I = Forward

2.19 Direction - Zone II = Forward

2.20 Direction - Zone III = Forward

2.21 Direction - Zone IV = Reverse

2.22 Direction - Zone V = Disabled

2.23 Direction - Zone 1B = Forward

2.24 Time delay - Zone I = 0 sec

2.25 Time delay - Zone II = 0.4 sec

2.26 Time delay - Zone III = 1 sec

2.27 Time delay - Zone IV = 1 sec

2.28 Time delay - Zone V = ∞ sec

2.29 Time delay - Zone 1B = 0 sec

3.0 220 KV WARANGAL C.T Parameters

3.01 C.T Ratio = 1600-800/1A

3.02 Selected Ratio = 800 / 1

3.03 Class = PS

3.04 KPV = 800 V

Page 5: 7SA522  arelay Setting Calculation

3 of 25

3.05 Iex = <=50 ma

3.06 Rct = 4 Ω

4.0 220 KV WARANGAL P.T Parameters

4.01 P.T Ratio = ( 220 KV / √ 3 ) / ( 0.11KV / √ 3 )

4.02 Class = 3P

4.03 Burden = 50 VA

5.0 Transformer Data at Next 220KV Substation

5.01 Voltage level & Type = 220KV / 132KV Auto transformer

5.02 220KV / 132KV Auto transformer = 2 Nos.

5.03 Rating of Transformer = 100 MVA

5.04 Vector Group = YNa0d11

5.05 Percent Impedances HV-MV

a) Z1 at Principal Tap = 12.50% ± 10%

b) Z0 at Principal Tap = 11.50%

5.06 High Voltage = 220 KV

5.07 Medium Voltage = 132 KV

5.08 Low Voltage = 11 KV

6.0 MAIN I DISTANCE PROTECTION:

6.1 Protected Line parameters:

6.1.1 Conductor used = ACSR Kundah

6.1.2 Line Length = 75 KM

6.1.3 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

6.1.4 Positive Sequence impedance of the Line Magnitude Angle

Per unit length(Z1) in Ω/KM = √(R12 + X12) tan-1(X1/R1)

Page 6: 7SA522  arelay Setting Calculation

4 of 25

= 0.41067 78.91

= 0.41067 < 78.91°

6.1.5 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

6.1.6 Zero Sequence impedance of the Line Magnitude Angle

Per Unit Length (Z0) in Ω/KM =

= 1.53138 80.41

= 1.53138 < 80.41°

6.2 Longest Line parameters at Next 220KV Substation

6.2.1 Conductor used = ACSR KUNDAH

6.2.2 Line Length Assumed = 71 KM

6.2.3 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

6.2.4 Positive Sequence impedance of the Line Magnitude Angle

Per unit length(Z1) in Ω/KM =

= 0.41067 78.91

= 0.41067 < 78.91°

6.2.5 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

6.2.6 Zero Sequence impedance of the Line Magnitude Angle

Per Unit Length (Z0) in Ω/KM =

= 1.53138 80.41

= 1.53138 < 80.41°

6.3 Shortest Line parameters at Next 220KV Substation

√(R02 + X02) tan-1(X0/R0)

√(R12 + X12) tan-1(X1/R1)

√(R02 + X02) tan-1(X0/R0)

Page 7: 7SA522  arelay Setting Calculation

5 of 25

6.3.1 Conductor used = ACSR KUNDAH

6.3.2 Line Length Assumed = 53 KM

6.3.3 Positive & Negative Sequence Line Impedance /KM

(R1=R2) = 0.079 Ω/KM

(X1=X2) = 0.403 Ω/KM

6.3.4 Positive Sequence impedance of the Line Magnitude Angle

Per unit length(Z1) in Ω/KM =

= 0.41067 78.9

= 0.41067 < 78.91°

6.3.5 Zero Sequence Line impedance per KM

R0 = 0.255 Ω/KM

X0 = 1.51 Ω/KM

6.3.6 Zero Sequence impedance of the Line Magnitude Angle

Per Unit Length (Z0) in Ω/KM =

= 1.53138 80.4

= 1.53138 < 80.41°

6.4 Transformer Rating at Next 220kV Substation

6.4.1 220KV / 132KV Auto transformer = 2 Nos

6.4.2 Rating of Transformer = 100 MVA

6.4.3 Vector Group = YNa0d11

6.4.4 Percent Impedances HV-MV

Z1 at Principal Tap = 12.50% ± 10%

Z0 at Principal Tap = 11.50%

6.4.5 Magnetising Inrush Current = 6 times of the rated current

= 6 x 262.44

= 1574.64 A

6.4.6 Line Current(HV) =

√(R12 + X12) tan-1(X1/R1)

√(R02 + X02) tan-1(X0/R0)

Rating/(√3 x V)

Page 8: 7SA522  arelay Setting Calculation

6 of 25

= 100000 / (1.732 x 220 )

= 262.44 A

6.4.7 Line Current(MV) =

= 100000 / (1.732 x 132 )

= 437.4 A

6.4.8 Line Current(LV) =

= 100000 / (1.732 x 11 )

= 5248.79 A

6.5 System Parameter:

6.5.1 3-Phase Fault Level:

a) Magnitude Angle

WARANGAL 220 Kv Substation = 40000 -79

= 40000 < -79°

= 40 KA

Therefore, maximum 3 Φ Fault Level = √3 x Isc x V

= √3 x 40x 220

= 15241.6 MVA

b) Minimum 3 Φ Fault current

(assumed-30% of max) = 12000 Amps

= 12 KA

c) X/R Ratio As per Calculations = X1 / R1

= 0.403 / 0.079

= 5.101

6.5.2 1-Phase Fault Level:

a) Magnitude Angle

220KV BUS of Warangal SubStation = 40000 -79

= 40000 < -79°

= 40 KA

Rating/(√3 x V)

Rating/(√3 x V)

Maxium 3Ф Fault Current as per Calculation at

Maxium 1Ф Fault Current as per Calculation at

Page 9: 7SA522  arelay Setting Calculation

7 of 25

Therefore, maximum 1 Φ Fault Level = Isc x V

= 40x 220

= 8800 MVA

b) Minimum 1 Φ Fault current

(assumed-30% of max) = 12000 Amps

= 12 KA

c) X/R Ratio As per Calculations = X1 / R1

0.403 / 0.079

5.101

6.6 Conversion of CT & PT Secondary Values:

Zsec = C.T Ratio

P.T Ratio

= 800 / 1

( 220/ √3 ) / ( 0.11 / √3 )

= 0.4

6.7 Line Impedances of the Protected Line:

6.7.1 Positive Sequence Impedance of the = Positive sequence impedance x

Protected Line(Z1) Protected line length

= ( 0.41067 < 78.91°) x 75

Magnitude Angle

= 30.80025 78.91 ohms

6.7.2 Positive sequence Impedance of the = Positive sequence impedance x C.F

Line per unit Length (X) refered to sec. in Ω/KM

= ( 0.41067 < 78.91°) x 0.4

x Zpri

x Zpri

X Zpri

Page 10: 7SA522  arelay Setting Calculation

8 of 25

Magnitude Angle

= 0.164268 78.91 ohms

6.7.3 Line Angle = 78.91

6.7.4 Distance Angle = 78.91

(Assumed equal to Line Angle)

6.7.5 Zero Sequence Impedance of the = Zero sequence impedance x

Protected Line(Z0) Protected line length

= 1.53138 x 75

Magnitude Angle

= 114.8535 80.41 ohms

6.7.6

= 1/3 * ((R0/R1) - 1)

= 1/3 x (( 0.255 / 0.079 ) -1)

= 0.743

6.7.7

= 1/3 * ((X0/X1) - 1)

= 1/3 x (( 1.51 / 0.403 ) -1)

= 0.916

6.7.8 Zero Sequence Compensation Factor Ko

= 1/3 * ((Z0/Z1) - 1)

= 1/3 x ((1.53138 / 0.41067) - 1)

Magnitude Angle

= 0.910 -178

Zero Sequence Compensation Factor RE/RL

Zero Sequence Compensation Factor XE/XL

Page 11: 7SA522  arelay Setting Calculation

9 of 25

6.8 Apparent Maximum Power:

6.8.1 Apparent Maximum Power: = 150.00 MVA

= 150.00 MVA

6.8.2 Rated full load current = 393.66 Amps

6.8.3 Source Impedance =

Magnitude Angle

= 3.18 78.91

6.9 Maximum Allowable Reach:

6.9.1 Min. Load Impedance at 0.8 p.f =

= ( 220^2 / ( 150 )) x 0.4 )

= 129.07 Ω

6.9.2 Maximum reach of Load Impedance = 80% of min. Load impedance

= 0.8 x 129.07

= 103.256 Ω

7.0 Computation of Fault Resistance Tolerance for Reach Setting :

7.1 Tower Footing Resistance = 10 Ω

7.2

= 1.26 Ω

7.3 For Phase to Phase Fault: Rt-Φ

(Considering 50% of Arc Resistance including a safety margin of 20%)

Resistance Tolerance with respect to Secondary = 0.312 Ω

7.4 For Phase to Earth Fault :- Resistance Tolerance with respect to secondary-Rt-e

= 1.2 x (1+I2/I1*((Rarc+RTF)/(1+RE/RL)) x C.F

= 1.2 x (1+ 3 x ((10 + 1.26 ) / (1 + 0.743 )) x 0.4

= 9.783 Ω

Where,

I2/I1 is ratio of current at the opposite end and local end = 3

(2202/Max. 3 ph Fault MVA)

(KV2 / (MVA)) x CF

Arc Resistance (RArc) = = 76KV2/Short ckt. KVA at min. Fault Current

Page 12: 7SA522  arelay Setting Calculation

10 of 25

8.0 DISTANCE RELAY PROTETION FOR 220KV Line feeder - 1

8.1 Zone I : Reach Setting Proposed at 80% of the protected Line

8.1.1 Direction = Forward

8.1.2 Resistive Reach For Φ to Φ Faults, = (80%x L x R(Z1) x C.F)+(R-TolerenceΦ-Φ)

R(Z1): = ( 0.8 x 75 x 0.079 x 0.4 ) + 0.312

= 2.208 Ω

8.1.3 Resistive Reach For Φ to E Faults, = (R(Z1) x Ko)+R-TolerencePh-E

RE(Z1): = ( 0.8 x 75 x 0.079 x 0.4 ) x 0.91 ) + 9.783

= 11.508 Ω

Page 13: 7SA522  arelay Setting Calculation

11 of 25

8.1.4 Reactance Reach,X(Z1) = 80% ofProtected line * X1 * C.F

= 0.8 x 75 x 0.403 x 0.4

= 9.672 Ω

8.1.5 Time Delay: = 0 secs

Selected Setting:

Zone Direction

Zone I 11.508 Forward 2.208 9.672 80% 0

8.2 Zone II: Reach Setting Proposed at (100% of the protected Line +

50% of the shortest line at Next substation)

8.2.1 Direction = Forward

8.2.2 Resistive Reach For Φ to Φ Faults,R(Z2): = (((100% of Prot. line length x R1) +

(50% of short line x R1)) x C.F)+Rt-Φ

= ((1 x 75 x 0.079) +

(0.5 x 53 x 0.079) x 0.4)+(0.312)

= 3.519 Ω

8.2.3 = (R(Z2) x Ko) + Rt-e

[ { (1 x 75 x 0.079) +

(0.5 x 53 x 0.079) x 0.4 } x

= 0.91 ] + 9.783

= 12.702 Ω

8.2.4 Reactance Reach,X(Z2) = ((100% of Prot. line length x X1) +

(50% of short line x X1) x C.F

((1 x 75 x 0.403) +

(0.5 x 53 x 0.403) x 0.4

= 16.362 Ω

8.2.5 Time Delay: = 0.4 secs

Selected Setting:

Resistive Reach for Ph to Earth Fault,RE(Z1)

Resistive Reach for Ph to Ph Fault,R

(Z1)

Reactance Reach, X(Z1)

Protected Length

Time Delay

Resistive Reach For Φ to E Faults,RE(Z2):

Page 14: 7SA522  arelay Setting Calculation

12 of 25

Zone Direction

Zone II 12.702 Forward 16.362 3.519 100% 0.4

8.3 Zone III: Reach Setting

8.3.1 Base Impedance of the Transformer =

= 220^2 / 100

= 484 Ω

8.3.2 Equivelent Transformer Impedance = (KV2 / MVA)*Zo

= (220^2 / 100) x 0.115

= 55.66 Ω

8.3.3 Impedance of two transformers running in Parallel = 28 Ω

8.3.4 Impedance of Protected line at 100% = (Protected line x Z1 x C.F)

= (75 x 0.41067 x 0.4)

= 12.3

8.3.5 Total Impedance of both Transformers & = 40.3 Ω

Protected Line At 100%

(Comparing the above value with the reach of prot. line and the longest line at the remote)

8.3.6 Zone-3 impedance = (110% PL+100% OF NEXT)

= 63 Ω

Largest line at the Remote StationPrimary value

As the transformer capacities are variable the reach is as calculted from the above 8.3.8 is

taken for reach setting which is nearer to the calculated value at8.3.5

8.3.7 Direction = Forward

8.3.8 Resistive Reach For Φ to Φ Faults, = { [(110% of Protected line length x R1) +

R(Z3) (100% of longest line x R1) ] x C.F } + Rt-Φ

[(1.1 x 75 x 0.079) + (71 x 0.079) ]

x 0.4)+ 0.312

5.162 Ω

8.3.9 Resistive Reach For Φ to E Faults, = { [(110% of Protected line length x R1) +

Resistive Reach for Ph to Earth Fault,RE(Z2)

Reactance Reach,

X(Z2)

Resistive Reach for Ph to Ph Fault,R(Z2)

Protected Length

Time Delay

KV2 / MVA

Page 15: 7SA522  arelay Setting Calculation

13 of 25

RE(Z3) (100% of longest line x R1) ] x C.F } + Rt-e

[(1.1 x 75 x 0.079) + (71 x 0.079) ]

x 0.4)+ 9.783

14.633 Ω

8.3.10 Reactance Reach, X(Z3) = { 110% of Protected line length x X1) +

(100% of longest line x X1) ] x C.F }

[(1.1 x 75 x 0.403) + (71 x 0.403) ] x 0.4)

24.74

Ω

8.3.11 Time Delay: = 1 secs

Selected Setting: (110% PL+100% OF NEXT)

Zone Direction

Zone III 14.633 Forward 24.74 5.162 110% 1

8.4 Zone IV: Reach Setting Proposed at 25% of Zone1

8.4.1 Direction = Reverse

8.4.2 Resistive Reach For Φ to Φ Faults,R(Z4): = 0.25 x R(Z1)

= 0.25 x 2.208

= 0.55 Ω

8.4.3 =

= 0.25 x 11.508

= 2.88 Ω

8.4.4 Reactance Reach,X(Z4) = 0.25 * X(Z1)

= 0.25 x 9.672

= 2.42 Ω

8.4.5 Time Delay: = 1 secs

Selected Setting:

Zone Direction

Zone IV 2.877 Reverse 2.418 0.552 25% 1

Resistive Reach for Ph to Earth Fault,RE(Z2)

Reactance Reach,

X(Z2)

Resistive Reach for Ph to Ph Fault,R(Z2)

Protected Length

Time Delay

Resistive Reach For Φ to E Faults,RE(Z4): 0.25 x RE(Z1)

Resistive Reach for Ph to Earth Fault,RE(Z2)

Reactance Reach,

X(Z2)

Resistive Reach for Ph to Ph Fault,R(Z2)

Protected Length

Time Delay

Page 16: 7SA522  arelay Setting Calculation

14 of 25

8.5 Zone V Relay Setting Disabled

8.6 Controlled Zone (Z1B) Reach Setting Proposed at 120% of the Protected Line

8.6.1 Direction = 1 Forward

8.6.2 Resistive Reach For Φ to Φ Faults,R(ZIB)

at 120% of the Protected Line = (120% of Protd linex R1xC.F)+Rt-Ph

= 1.2 x 0.079 x 75 x 0.4) + 0.312

= 3.16 Ω

8.6.3

at 120% of the Protected Line = (120% of Protd line x R1 x Ko x C.F)

+ Rt-E

= (1.2 x 75 x 0.079 x 0.4 x 0.91)

+ 9.783

= 12.371 Ω

8.6.4 Reactance Reach, X(ZIB)

at 120% of the Protected Line = 120% of Protected line * X1 * C.F

= 1.2 x 0.403 x 75 x 0.4

= 14.508 Ω

8.6.5 Time Delay = 0 secs

Selected Setting:

Zone Direction

Zone IB 12.37 Forward 14.51 3.16 120% 0

9 OVER VOLTAGE PROTECTION:

9.1 1 Voltage Protection : Enabled

9.2 2 Over Voltage Phase - Earth Protection:

9.3 = ON

9.4 Initial Stage for Minor Over voltage 110%of Un= 69.85 Volts

9.5 Time Delay for Initial Stage Setting = 5 Secs

Resistive Reach For Φ to E Faults,RE(ZIB)

Resistive Reach for Ph to Earth Fault,RE(Z2)

Reactance Reach,

X(Z2)

Resistive Reach for Ph to Ph Fault,R(Z2)

Protected Length

Time Delay

Uph-e>(>): Phase Voltage Stages

Uph-e> :

TUph-e> :

Page 17: 7SA522  arelay Setting Calculation

15 of 25

9.6 Stage for Higher Voltage 150%ofUn= 95.25 Volts

9.7 Time delay for Longer Setting = 0 Secs

9.8 = 0.95

9.9 CURR.SUP.Uph-e>: = ON

11.0 DIRECTIONAL EARTH FAULT

11.1 Zero Sequence Source =

Impedance (Z0s) √3 x 220 x Min.1ph Fault Current

= 3 x 220^2 / (√3 x 220 x 12)

= 31.7552 Ω

11.2 Line Impedance of the Protected Line = Forward Ω

11.3 Earth Fault Current Pick-up = 20% of rated Full load current / C.T ratio

Setting(3I0>)

= (0.2 x MVA / (√3 x KV)) / C.T ratio

= (0.2 x 150000 / (1.732 x 220)) / ( 800 / 1)

= 0.098415 ≈ 0.1 A

11.4 = Disabled

11.5 Direction = Forward

11.6 Curve = Normal Inverse

11.7 TMS = 0.34

11.8 = Enabled

11.9 Characteristic Angle = Enabled

11.10 Tele protection Earth Fault: = N/A

Directional Comparison Pick-up

13.0 SOTF O/C

12.1 SOTF OVER CURRENT = Enabled

12.2 The magnitude of the current for picking up of

the switchon to fault I>>> = 2.5 times the FLC

= 2.5 x 150000 / (1.732 x 220)

Uph-e>> :

TUph-e>> :

Uph-e>(>) RESET: Drop out to Pick Up Ratio

3 x KV2

Earth Fault Current Pick-up setting(3I0>>)

Zero Sequence Voltage Stage 3U0>

Page 18: 7SA522  arelay Setting Calculation

16 of 25

= 984 A

12.3 Setting adopted = 2.5 times FLC/ CTR I>>> 1.23 A

Page 19: 7SA522  arelay Setting Calculation

15 of 25

400/220 KV WARANGAL SUBSTATION

220kV yyyyyyyyyy FEEDER

SIEMENS DISTANCE PROTECTION RELAY SETTING

1 Device Configuration

No. Function Scope

103 Setting Group Change Option Disabled

110 Trip mode 3 pole

112 Phase Distance Quadrilateral

113 Earth Distance Quadrilateral

120 Power Swing detection Enabled

121 Teleprotection for Distance prot. POTT

122 DTT Direct Transfer Trip Disabled

124 Instantaneous HighSpeed SOTF Overcurrent Enabled

125 Weak Infeed (Trip and/or Echo) Disabled

126 Backup overcurrent Disabled

131 Earth fault overcurrent Time Overcurrent Curve IEC

132 Teleprotection for Earth fault overcurr. Disabled

133 Auto-Reclose Function 1 AR-cycle

134 Auto-Reclose control mode with Trip and Action time

135 Synchronism and Voltage Check Disabled

136 Over / Underfrequency Protection Disabled

137 Under / Overvoltage Protection Enabled

138 Fault Locator Enabled

140 Trip Circuit Supervision Disabled

2 General Device Settings

2.1 Group Device

No. Settings Value

610 Fault Display on LED / LCD Display Targets on TRIP only

Page 20: 7SA522  arelay Setting Calculation

16 of 25

640 Start image Default Display image 1

3 Power System Data 1

3.1 Group Power System Data 1; Group Transformers

No. Settings Value

201 CT Starpoint towards Line

203 Rated Primary Voltage 220 KV

204 Rated Secondary Voltage (Ph-Ph) 110 V

205 CT Rated Primary Current 800.00 A

206 CT Rated Secondary Current 1A

210 U4 voltage transformer is Usy2 transformer

211 Matching ratio Phase-VT To Open-Delta-VT 1.73

215 Matching ratio Usy1 / Usy2 1

220 I4 current transformer is Neutral Current (of the protected line)

221 Matching ratio I4/Iph for CT's 1

3.2 Group Power System Data 1; Group Power System

No. Settings Value

207 System Starpoint is Solid Earthed

230 Rated Frequency 50 Hz

235 Phase Sequence L1 L2 L3

236 Distance measurement unit km

237 Setting format for zero seq.comp. format Zero seq. comp. factors RE/RL and XE/XL

0238A Earth Fault O/C: setting for 1pole AR all stages together

3.3 Group Power System Data 1; Group Breaker

No. Settings Value

0240A Minimum TRIP Command Duration 0.10 sec

0241A Maximum Close Command Duration 0.10 sec

242 Dead Time for CB test-autoreclosure 1.00 sec

4 Settings groups

Page 21: 7SA522  arelay Setting Calculation

17 of 25

4.1 Group Power System Data 2; Group Power System

No. Settings Value

1103 Measurement: Full Scale Voltage (100%) 220 KV

1104 Measurement: Full Scale Current (100%) 800.00 A

1105 Line Angle 78.91

1211 Angle of inclination, distance charact. 78.91

1107 P,Q operational measured values sign not reversed

1110 x' - Line Reactance per length unit 0.164268

1111 Line Length 53.0 KM

1116 Zero seq. comp. factor RE/RL for Z1 0.74

1117 Zero seq. comp. factor XE/XL for Z1 0.92

1118 Zero seq. comp.factor RE/RL for Z1B...Z5 0.74

1119 Zero seq. comp.factor XE/XL for Z1B...Z5 0.92

4.2 Group Power System Data 2; Group Line Status

No. Settings Value

1130A Pole Open Current Threshold 0.10 A

1131A Pole Open Voltage Threshold 30 V

1132A Seal-in Time after ALL closures 0.20 sec

1133A minimal time for line open before SOTF 0.25 sec

1134 Recognition of Line Closures with CBaux OR Current or Manual close BI

1135 RESET of Trip Command with CBaux open AND I < PoleOpenCurrent

1136 open pole detector with measurement (U/I,trip,pickup,CBaux)

1140A CT Saturation Threshold 5.0 A

1150A Seal-in Time after MANUAL closures 0.30 sec

1151 Manual CLOSE COMMAND generation NO

1152 MANUAL Closure Impulse after CONTROL <none>

4.3 Group Power System Data 2; Group Trip 1-/3-pole

No. Settings Value

Page 22: 7SA522  arelay Setting Calculation

18 of 25

1155 3 pole coupling with Trip

1156A Trip type with 2phase faults 3pole

4.4 Group Distance protection, general settings; Group General

No. Settings Value

1201 Distance protection ON

1202 Phase Current threshold for dist. Meas. 0.10 A

1211 Angle of inclination, distance charact. 78.91

1208 Series compensated line NO

1232 Instantaneous trip after SwitchOnToFault with Zone Z1B

1241 R load, minimum Load Impedance (ph-e) 129.1 Ohms

1242 PHI load, maximum Load Angle (ph-e) 37 °

1243 R load, minimum Load Impedance (ph-ph) 258.1 Ohms

1244 PHI load, maximum Load Angle (ph-ph) 45 °

1317A Single pole trip for faults in Z2 NO

1357 YES

4.5 Group Distance protection, general settings; Group Earth faults

No. Settings Value

1203 3I0 threshold for neutral current pickup 0.10 A

1204 3U0 threshold zero seq. voltage pickup 5 V

1207A 3I0>-pickup-stabilisation (3I0> /Iphmax) 0.15

1209A criterion of earth fault recognition 3I0> OR 3U0>

1221A Loop selection with 2Ph-E faults all loops

4.6 Group Distance protection, general settings; Group Time Delays

No. Settings Value

1210 Condition for zone timer start with distance pickup

1305 T1-1phase, delay for single phase faults 0.00 sec

1306 T1multi-ph, delay for multi phase faults 0.00 sec

1315 T2-1phase, delay for single phase faults 0.40 sec

Z1B enabled before 1st AR (int. or ext.)

Page 23: 7SA522  arelay Setting Calculation

19 of 25

1316 T2multi-ph, delay for multi phase faults 0.40 sec

1325 T3 delay 1.00 sec

1335 T4 delay 1.00 sec

1345 T5 delay N/A

1355 T1B-1phase, delay for single ph. Faults 0.00 sec

1356 T1B-multi-ph, delay for multi ph. Faults 0.00 sec

4.7 Group Distance zones (quadrilateral); Group Zone Z1

No. Settings Value

1301 Operating mode Z1 Forward

1302 R(Z1), Resistance for ph-ph-faults 2.208 Ohms

1303 X(Z1), Reactance 9.672 Ohms

1304 RE(Z1), Resistance for ph-e faults 11.508 Ohms

1305 T1-1phase, delay for single phase faults 0.00 sec

1306 T1multi-ph, delay for multi phase faults 0.00 sec

1307 Zone Reduction Angle (load compensation) 0 °

4.8 Group Distance zones (quadrilateral); Group Zone Z1Bexten.

No. Settings Value

1351 Operating mode Z1B (_verreach zone) Forward

1352 R(Z1B), Resistance for ph-ph-faults 3.156 Ohms

1353 X(Z1B), Reactance 14.508 Ohms

1354 RE(Z1B), Resistance for ph-e faults 12.371 Ohms

1355 T1B-1phase, delay for single ph. Faults 0.00 sec

1356 T1B-multi-ph, delay for multi ph. Faults 0.00 sec

1357 YES

4.9 Group Distance zones (quadrilateral); Group Zone Z2

No. Settings Value

1311 Operating mode Z2 Forward

1312 R(Z2), Resistance for ph-ph-faults 3.519 Ohms

Z1B enabled before 1st AR (int. or ext.)

Page 24: 7SA522  arelay Setting Calculation

20 of 25

1313 X(Z2), Reactance 16.362 Ohms

1314 RE(Z2), Resistance for ph-e faults 12.702 Ohms

1315 T2-1phase, delay for single phase faults 0.40 sec

1316 T2multi-ph, delay for multi phase faults 0.40 sec

1317A Single pole trip for faults in Z2 NO

4.10 Group Distance zones (quadrilateral); Group Zone Z3

No. Settings Value

1321 Operating mode Z3 Forward

1322 R(Z3), Resistance for ph-ph-faults 5.162 Ohms

1323 X(Z3), Reactance 24.740 Ohms

1324 RE(Z3), Resistance for ph-e faults 14.633 Ohms

1325 T3 delay 1.00 sec

4.11 Group Distance zones (quadrilateral); Group Zone Z4

No. Settings Value

1331 Operating mode Z4 Reverse

1332 R(Z4), Resistance for ph-ph-faults 0.552 Ohms

1333 X(Z4), Reactance 2.418 Ohms

1334 RE(Z4), Resistance for ph-e faults 2.877 Ohms

1335 T4 delay 1.00 sec

4.12 Group Distance zones (quadrilateral); Group Zone Z5

No. Settings Value

1341 Operating mode Z5 Inactive

1342 R(Z5), Resistance for ph-ph-faults N/A

1343 X(Z5)+, Reactance for Forward direction N/A

1344 RE(Z5), Resistance for ph-e faults N/A

1345 T5 delay N/A

1346 X(Z5)-, Reactance for Reverse direction N/A

4.13 Group Power Swing

Page 25: 7SA522  arelay Setting Calculation

21 of 25

No. Settings Value

2002 Power Swing Operating mode Z2 to Z5 Block

2006 Power swing trip YES

2007 Trip delay after Power Swing Blocking 0.08 sec

4.14 Group Teleprotection for Distance prot.

No. Settings Value

2101 Teleprotection for Distance protection PUTT(Z1B)

2102 Type of Line Two Terminals

2103A Time for send signal prolongation 0.07 sec

2109A Transient Block.: Duration external flt. oo sec

2110A Transient Block.: Blk.T. after ext. flt. 0.05 sec

4.15 Group Instantaneous HighSpeed SOTF Overcurrent

No. Settings Value

2401 Inst. High Speed SOTF-O/C is ON

2404 I>>> Pickup 2.5 A

4.16 Group Measurement Supervision; Group Balance / Summ.

No. Settings Value

2901 Measurement Supervision ON

2902A Voltage Threshold for Balance Monitoring 10

2903A Balance Factor for Voltage Monitor 0.8

2904A Current Balance Monitor 0.1

2905A Balance Factor for Current Monitor 0.05

2906A Summated Current Monitoring Threshold 0.10 A

2907A Summated Current Monitoring Factor 0.1

2908A T Balance Factor for Voltage Monitor 5 sec

2909A T Current Balance Monitor 5 sec

4.17 Group Measurement Supervision; Group Fuse Fail. Mon.

No. Settings Value

Page 26: 7SA522  arelay Setting Calculation

22 of 25

2910 Fuse Failure Monitor ON

2911A Minimum Voltage Threshold U> 50 V

2912A Maximum Current Threshold I< 0.20 A

2913A Maximum Voltage Threshold U< (3phase) 5 V

2914A Delta Current Threshold (3phase) 0.10 A

2915 Voltage Failure Supervision with current supervision

2916A Delay Voltage Failure Supervision 3.00 sec

4.18 Group Measurement Supervision; Group VT mcb

No. Settings Value

2921 VT mcb operating time 0 ms

4.19 Group Measurement Supervision; Group Load Angle

No. Settings Value

2941 Limit setting PhiA 200 °

2942 Limit setting PhiB 340 °

2943 Minimum value I1> 0.05 A

2944 Minimum value U1> 20 V

4.20 Group Earth fault overcurrent; Group General

No. Settings Value

3101 Earth Fault overcurrent function ON

3102 Block E/F for Distance protection with every Pickup

3174 Block E/F for Distance Protection Pickup in each zone

3103 Block E/F for 1pole Dead time YES

3104A Stabilisation Slope with Iphase 10%

3109 Single pole trip with earth flt.prot. YES

3170 2nd harmonic ratio for inrush restraint 15%

3171 Max.Current, overriding inrush restraint 7.50 A

3172 Instantaneous mode after SwitchOnToFault with Pickup and direction

3173 Trip time delay after SOTF 0.00 sec

Page 27: 7SA522  arelay Setting Calculation

23 of 25

4.21 Group Earth fault overcurrent; Group 3I0>>>

No. Settings Value

3110 Operating mode Inactive

3111 3I0>>> Pickup N/A

3112 T 3I0>>> Time delay N/A

3113 Instantaneous trip via Teleprot./BI N/A

3114 Instantaneous trip after SwitchOnToFault N/A

3115 Inrush Blocking N/A

4.22 Group Earth fault overcurrent; Group 3I0>>

No. Settings Value

3120 Operating mode Inactive

3121 3I0>> Pickup N/A

3122 T 3I0>> Time Delay N/A

3123 Instantaneous trip via Teleprot./BI N/A

3124 Instantaneous trip after SwitchOnToFault N/A

3125 Inrush Blocking N/A

4.23 Group Earth fault overcurrent; Group 3I0>

No. Settings Value

3130 Operating mode Inactive

3131 3I0> Pickup N/A

3132 T 3I0> Time Delay N/A

3133 Instantaneous trip via Teleprot./BI N/A

3134 Instantaneous trip after SwitchOnToFault N/A

3135 Inrush Blocking N/A

4.24 Group Earth fault overcurrent; Group 3I0 InverseTime

No. Settings Value

3140 Operating mode Forward

3141 3I0p Pickup 0.10 A

Page 28: 7SA522  arelay Setting Calculation

24 of 25

3143 3I0p Time Dial 0.34 sec

3147 Additional Time Delay 0.00 sec

3148 Instantaneous trip via Teleprot./BI YES

3149 Instantaneous trip after SwitchOnToFault NO

3150 Inrush Blocking YES

3151 IEC Curve Normal Inverse

4.25 Group Earth fault overcurrent; Group Direction

No. Settings Value

3160 Polarization with U0 + IY (dual polarized)

3162A ALPHA, lower angle for forward direction 338 °

3163A BETA, upper angle for forward direction 122 °

3164 Min. zero seq.voltage 3U0 for polarizing N/A

3166 Min. neg. seq. polarizing voltage 3U2 5.0 V

3167 Min. neg. seq. polarizing current 3I2 0.50 A

3168 Compensation angle PHI comp. for Sr 255 °

3169 Forward direction power threshold 0.3 VA

4.26 Group Automatic Reclosure; Group General

No. Settings Value

3401 Auto-Reclose function ON

3402 CB ready interrogation at 1st trip NO

3403 Reclaim time after successful AR cycle 3.00 sec

3404 AR blocking duration after manual close 1.00 sec

3406 Evolving fault recognition with Trip

3407 Evolving fault (during the dead time) starts 3pole AR-cycle

3408 AR start-signal monitoring time 0.20 sec

3409 Circuit Breaker (CB) Supervision Time 3.00 sec

3410 Send delay for remote close command ∞sec

3411A Maximum dead time extension ∞sec

Page 29: 7SA522  arelay Setting Calculation

25 of 25

4.27 Group Automatic Reclosure; Group 1st AR-cyle

No. Settings Value

3450 Start of AR allowed in this cycle YES

3451 Action time 0.20 sec

3456 Dead time after 1pole trip 1.20 sec

3457 Dead time after 3pole trip 0.50 sec

3458 Dead time after evolving fault 1.20 sec

3459 CB ready interrogation before reclosing NO

3460 Request for synchro-check after 3pole AR NO

4.28 Group Automatic Reclosure; Group 3pTRIP/DLC/RDT

No. Settings Value

3430 3pole TRIP by AR YES

3431 Dead Line Check or Reduced Dead Time Without

3438 Supervision time for dead/ live voltage 0.10 sec

3440 Voltage threshold for live line or bus 48 V

3441 Voltage threshold for dead line or bus 30 V

4.29 Group Automatic Reclosure; Group Start AR with..

No. Settings Value

3420 AR with distance protection YES

3421 AR with switch-onto-fault overcurrent NO

3423 AR with earth fault overcurrent prot. NO

4.30 Group Voltage Protection; Group U> Phase-Earth

No. Settings Value

3701 Operating mode Uph-e overvoltage prot. ON

3702 Uph-e> Pickup 69.9 V

3703 T Uph-e> Time Delay 5.00 sec

3704 Uph-e>> Pickup 95.3 V

3705 T Uph-e>> Time Delay 0.10 sec

Page 30: 7SA522  arelay Setting Calculation

26 of 25

3709A Uph-e>(>) Reset ratio 0.95

4.31 Group Fault Locator

No. Settings Value

3802 Start fault locator with Pickup

3806 Load Compensation YES

Page 31: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

45 OF 205

400/220 KV WARANGAL SUBSTATION

220kV yyyyyyyyyy FEEDER

ABB DISTANCE PROTECTION RELAY SETTING CALCULATION

Type : ABB make REL670

System Particulars

A Line Parameters

1 Rated line voltage 220 KV

2 Line Length 75 KM

3 Max power flow in the line (assumed) 150 MVA

4 Postive sequence resistance 0.079 ohms/km

5 Postive sequence reactance 0.403 ohms/km

6 Zero sequence resistance 0.255 ohms/km

7 Zero sequence reactance 1.51 ohms/km

8 Zero sequence mutual resistance (MR) 0 ohms/km

(If Parallel line in service Mutual Impedance is 60% of zero seq.)

9 Zero sequence mutual reactance (MX) 0 ohms/km

B Adjoining line parameters

B.1 Adjacent Line(Short Line)

1 Length of adjacent line 53 KM

2 Postive sequence resistance 0.079 ohms/km

3 Postive sequence reactance 0.403 ohms/km

4 Zero sequence resistance 0.255 ohms/km

5 Zero sequence reactance 1.51 ohms/km

B.2 longest line

1 Length of longest line 71 KM

2 Postive sequence resistance 0.079 ohms/km

3 Postive sequence reactance 0.403 ohms/km

4 Zero sequence resistance 0.255 ohms/km

5 Zero sequence reactance 1.51 ohms/km

Page 32: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

46 OF 205

B.3 Transformer

1 Transformer impedance in p.u 0.125

2 Transformer rating 100 MVA

C Source impedance

1 Local End max. Fault MVA =1.732*220*40 15241.6 MVA

2 Local End min. Fault MVA =30 % of 15241.6 4572 MVA

3 Local End Z magnitude = (220 x 220) / 15241.6 3.176 ohms

4 Local End Z argument 84 deg.

5 Remote End Max. Fault MVA (Assumed -Not available) 7500 MVA

6 Remote End Min. Fault MVA (Assumed -Not available) 3000 MVA

7 Remote End Z magnitude = (220 x 220) / 7500 6.45 ohms

8 Remote End Z argument 84 deg.

9 Postive sequence resistance at local end = line length x + ve seq. R 5.925 ohms

Page 33: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

47 OF 205

10 Postive sequence reactance at local end = line length x +ve seq.X 30.225 ohms

11 Postive sequence resistance at remote end = line length x +ve seq. R 4.187 ohms

12 Postive sequence reactance at remote end = line length x +ve seq. X 21.359 ohms

D CT and PT Detail

1 CT primary rating 800 A

2 CT secondary rating 1 A

3 PT primary rating 220000 V

4 PT secondary rating 110 V

E Relay Detail

1 Rated current 1 A

2 Rated voltage 110 V

F System Parameters

1 Arc Resistance + Tower footing resistance - Rfn 50.000 ohms

2 Rf for phase to phase fault 10.000

3 Imp Ratio = CTR / PTR 0.400

4 % for zone-1 setting 0.800

5 % of the adjoining line for Zone2 0.500

6 % of the adjoining line for Zone 3 1.100

G Protected Line Impedance in CT secondary

1 Postive sequence resistance = line length x + ve seq. R x Imp Ratio = 2.370 ohms

2 Postive sequence reactance = line length x + ve seq. X x Imp Ratio = 12.090 ohms

3 Zero sequence resistance = line length x Z0 x Imp Ratio = 7.650 ohms

4 Zero sequence reactance = line length x Z0X x Imp Ratio = 45.300 ohms

5 Zero sequence mutual resistance = line length x MR x Imp Ratio = 0.000 ohms

6 Zero sequence mutual reactance = line length x MX x Imp Ratio = 0.000 ohms

H Adjacent Line Impedance in CT secondary

1 Postive sequence resistance = line length x + ve seq. R x Imp Ratio = 1.675 ohms

2 Postive sequence reactance = line length x + ve seq. X x Imp Ratio = 8.544 ohms

3 Zero sequence resistance = line length x Z0 x Imp Ratio = 5.406 ohms

4 Zero sequence reactance = line length x Z0X x Imp Ratio = 32.012 ohms

I Longest Line Impedance in CT secondary

1 Postive sequence resistance = line length x + ve seq. R x Imp Ratio = 2.244 ohms

Page 34: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

48 OF 205

2 Postive sequence reactance = line length x + ve seq. X x Imp Ratio = 11.445 ohms

3 Zero sequence resistance = line length x Z0 x Imp Ratio = 7.242 ohms

4 Zero sequence reactance = line length x Z0X x Imp Ratio = 42.884 ohms

J Zone I : Reach Setting Proposed at 80% of the protected Line

1 Reach For Postive sequence resistance

(80% line length x Postive sequence resistance x Imp Ratio

=0.8 x 75 x 0.079 x 0.4 1.896 ohms

2 Reach For Postive sequence reactance

(80% line length x Postive sequence reactance x Imp Ratio

=0.8 x 75 x 0.403 x 0.4 9.672 ohms

3 Reach For Zero sequence resistance

(80% line length x Zero sequence resistance x Imp Ratio

=0.8 x 75 x 0.255 x 0.4 6.120 ohms

4 Reach For Zero sequence reactance

(80% line length x Zero sequence reactance x Imp Ratio

=0.8 x 75 x 1.51 x 0.4 36.240 ohms

5 Fault Resistance - ph-e

= 1.896 + ( 9.672 x TAN ( 25 ) = 6.406

= 4.5 x 1.896 = 8.5320

= 50 x 0.4 = 20.000

Maximum of 6.406 and 20 = 20.000

Minimum of 8.532 and 20 = 8.532 ohms

Hence fault resistance between phase to earth = 8.532 ohms

6 Fault Resistance - ph-ph

= 1.896 + ( 9.672 x TAN ( 25 ) = 6.406

= 3 x 1.896 = 5.688

= 10 x 0.4 = 4.000

Page 35: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

49 OF 205

Maximum of 6.406 and 4 = 6.406

Minimum of 5.688 and 6.406 = 5.688

Hence fault resistance between phase to phase =2 times of the above 11.376 ohms

K Zone II: Reach Setting at (100% of the protected Line +

50% of the shortest line at Next substation)

1 Reach For Postive sequence resistance

100% line length x Postive sequence resistance x Imp Ratio +

50% shortest line length x Postive sequence resistance x Imp Ratio

=75 x 0.079 x 0.4 + 0.5 x 75 x 0.079 x 0.4 3.207 ohms

2 Reach For Postive sequence reactance

100% line length x Postive sequence reactance x Imp Ratio +

50% shortest line length x Postive sequence reactance x Imp Ratio

=75 x 0.403 x 0.4 + 0.5 x 75 x 0.403 x 0.4 16.362 ohms

3 Reach For Zero sequence resistance

100% line length x Zero sequence resistance x Imp Ratio +

50% shortest line length x Zero sequence resistance x Imp Ratio

=75 x 0.255 x 0.4 + 0.5 x 75 x 0.255 x 0.4 10.353 ohms

4 Reach For Zero sequence reactance

100% line length x Zero sequence reactance x Imp Ratio +

50% shortest line length x Zero sequence reactance x Imp Ratio

=75 x 1.51 x 0.4 + 0.5 x 75 x 1.51 x 0.4 61.306 ohms

5 Fault Resistance - ph-e 14.432 ohms

6 Fault Resistance - ph-ph 19.242 ohms

L Zone III: Reach Setting Proposed at 110% of the prot Line & 100%of the longest line

1 Reach For Postive sequence resistance

Page 36: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

50 OF 205

110% line length x Postive sequence resistance x Imp Ratio +

100% Longest line length x Postive sequence resistance x Imp Ratio

= 1.1 x 75 x 0.079 x 0.4 + 71 x 0.079 x 0.4 4.851 ohms

2 Reach For Postive sequence reactance

110% line length x Postive sequence reactance x Imp Ratio +

100% Longest line length x Postive sequence reactance x Imp Ratio

= 1.1 x 75 x 0.403 x 0.4 + 71 x 0.403 x 0.4 24.744 ohms

3 Reach For Zero sequence resistance

110% line length x Zero sequence resistance x Imp Ratio +

100% Longest line length x Zero sequence resistance x Imp Ratio

= 1.1 x 75 x 0.255 x 0.4 + 71 x 0.255 x 0.4 15.657 ohms

3 Reach For Zero sequence reactance

110% line length x Zero sequence reactance x Imp Ratio +

100% Longest line length x Zero sequence reactance x Imp Ratio

= 1.1 x 75 x 1.51 x 0.4 + 71 x 1.51 x 0.4 92.714 ohms

5 Fault Resistance - ph-e 20.000 ohms

6 Fault Resistance - ph-ph 29.104 ohms

M Power Swing Block Function

1

2 27.219

3 32.671

4 34.023

5 40.839

Reactive direction are set so that the inner characteristic covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10%of additional safely margin

Reactive Reach of the Inner characteristic of the Power swing blocking element = 1.1* X3

Reactive Reach of the Inner characteristic of the Power swing blocking element = 1.1(2R3+Rf)

Reactive Reach of the Outer characteristic of the Power swing blocking element

Reactive Reach of the Outer characteristic of the Power swing blocking element

Page 37: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

51 OF 205

N Source Impedance refered to CT secondary

1 Local End Z magnitude 1.270

2 Local End Z argument 80.000

3 Remote End Z magnitude 2.580

4 Remote End Z argument 80.000

5 Postive sequence resistance at local end in ohms(RISA) 2.370

6 Postive sequence reactance at local end in ohms(XISA) 12.090

7 Postive sequence resistance at remote end in ohms(R1SB) 1.675

8 Postive sequence reactance at remote end in ohms(X1SB) 8.544

O Phase Selection

1 X1Phs 49.488

2 X0Phs 185.428

3 Calculated RFPEphs 56.905

4 Calculated RFPPphs 49.701

5 104.544

6 RFPEphs 52.272

7 Conditions for 2nd Zone 35.158

8 Conditions for 4th Zone 5.003

9 Conditions for 3-ph fault 62.212

10 RFPPphs 49.701

11.288 16.746

Zloadmin =(KV)2\MVA

Page 38: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

48 OF 205

400/220 KV WARANGAL SUBSTATION

220kV yyyyyyyyyy FEEDER

ABB DISTANCE PROTECTION RELAY SETTING

Type : ABB make REL670

DESCRIPTION PARAMETER SETTING RECOMMENDED

Max. load current \ CT primary current lb (FLC \ CT Primary) 0.492

lminop 0.200

Distance Protection zone 1

operating mode and directionaity of zone I operation Forward

Settings of Phase to Phase measurement

Operation of distance protection zone I for Ph-I Operation PP On

Positive sequence reactance of zone 1 for ph-ph fault X1PP 9.672

Positive sequence reactance of zone 1 for ph-ph fault R1PP 1.896

Resisitive reach of distance protection for ph-ph faults RFPP 11.376

Timer t1PP On

t1PP 0.000

Settings of Phase to earth element

Operation of distance protection zone I for Ph-I Operation PE On

X1PE 9.672

Positive sequence resistive reach of distance zone 1 for ph-E fault R1PE 1.896

XOPE 36.240

ROPE 6.120

Resisitive reach for zone 1 Ph-E faults RFPE 8.532

Timer t1PP On

t1PE 0.000

Operating mode of time delayed trip for the distance protection zone 1 for ph-ph faults

Time delayed trip operation for the distance protection zone 1 for ph-ph faults

Zero sequence line reactance included in distance protection zone I for Ph-E faults

Zero sequence line reactance included in distance protection zone I for Ph-E faults

Operating mode of time delayed trip for the distance protection zone 1 for ph-E faults

Time delayed trip operation for the distance protection zone 1 for ph-ph faults

Page 39: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

49 OF 205

Distance Protection zone II ZONE II

operating mode and directionaity of distance zone II operation Forward

Settings of Phase to Phase measurement

Operation of distance protection zone 2 for Ph-Ph fault Operation PP On

Positive sequence reactance of zone 2 for ph-ph fault X1PP 16.362

Positive sequence reactance of zone 2 for ph-ph fault R1PP 3.207

Resisitive reach of distance protection for ph-ph faults RFPP 19.242

Timer t1PP On

t1PP 0.400

Settings of Phase to earth element

Operation of distance protection zone 2 for Ph-E faults Operation PE On

X1PE 16.362

Positive sequence resistive reach of distance zone 2 for ph-E fault R1PE 3.207

XOPE 61.306

ROPE 10.353

Resisitive reach for zone 2 Ph-E faults RFPE 14.432

Timer t1PP On

t1PE 0.400

Distance protection zone lll ZONEIII

Operating mode and directionality of zone 3 Operation Forward

SETTINGS OF PHASE TO PHASE MEASUREMENT

Operation of Distance protection Zone 3 for Ph fault Operation PP On

Positive sequence reactance of zone 3 for phase to phase faults X1PP 24.744

Positive sequence resistance of zone 3 for phase to phase faults R1PP 4.851

Positive reach of distance protectin for phase to phase faults RFPP 29.104

Operating mode of time delayed trip for the distance protection zone 2 for ph-ph faults

Time delayed trip operation for the distance protection zone 2 for ph-ph faults

Zero sequence line reactance included in distance protection zone 2 for Ph-E faults

Zero sequence line reactance included in distance protection zone 2 for Ph-E faults

Operating mode of time delayed trip for the distance protection zone 2 for ph-E faults

Time delayed trip operation for the distance protection zone 2 for ph-ph faults

Page 40: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

50 OF 205

Timer t3PP On

t3PP 1.000

SETTINGS OF PHASE TO EARTH MEASUREMENT

Operating mode of distance protection zone 3 for Ph-E faults Operation PE On

Positive sequence reactive reach of distance zone 3 for Ph-E faults X1PE 24.744

Positive sequence resistive reach of distance zone 3 for Ph-E faults R1PE 4.851

X0PE 92.714

R0PE 10.353

Resistive reach for zone 3 for Ph-E faults RFPE 20.000

Timer t3PE On

t3PE 1.000

Manual energising time T manenerg 0.200

PHASE SELECTION

operation of phase selection operation On

positive sequence reactive reach for ph-ph loop measurement X1PP 24.744

Resistive reach for ph-ph loop measurement RFPP 29.104

positive sequence reactive reach for ph-e loop measurement X1PE 24.744

Zero sequence reactive for ph-e loop measurement XOPE 92.714

Resistive reach for ph-e loop measurement RFPE 20.000

Power swing blocking PSB

power swing function on/off operation On

Operating mode of internal PSD function detection on

positive sequence reactive reach of the inner boundary X1IN 27.219

positive sequence reactive reach of the inner boundary R1IN 32.671

reach multiplication for the outer reactive boundary KX 1.250

reach multiplication for the outer reactive boundary KR 1.250

Initial PSD timer tp1 0.045

Fast PSD timer tp2 0.015

Operating mode of time delayed trip for the distance protection zone 3 for Ph-Ph faults

Time delaye trip operation for the distnce protection zone 3 for Ph-Ph faults

zero sequence line reactance included in distance protection zone 3 for Ph-E faultsZero sequence line reactance included in distance protection zone 3 for Ph-E faults

Operating mode of time delayed trip for the distance protection zone 3 for Ph-E faultsTime delayed trip operation of the distance protection zone 3 for Ph-E faults

Page 41: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

51 OF 205

Hold timer for activation of fast PSD timer tw 0.250

Hold timer for PSD detected th 0.5s

Timer over coming 1-phase reclosing dead time tEF 3 s

Timer to time delay block by the residual current tR1 0.300

On delay timer for blocking of output signal at very slow swings tR2 2.000

Scheme communication logic Zcom

Operation of zoom scheme communication logic Operation On

Operation mode Schemetype Permissive UR

Coordination timer T coord 0.050s

Minimum duration of a carrier send signal T sendmin 0.1s

Operation mode for an unblocking signal Unblock Off

Security timer T security 0.035s

Operation mode of current reversal function Currev Off

Pick up time of current reversal function T pickup NA

Time delay for current reversal T delay NA

Operation mode of WEI function WEI Off

Coordination time for WEI function Twei NA

Voltage detection for PH-E faults UPN< NA

voltage detection for Ph-Ph faults UPP< NA

Automatic SOTF SOTF

Operation of SOTF Operation On

FUSE FAILURE FUNCTION FFR

FFR zero sequence function On\Off Zeroseq On

Operating value of voltage U0 3U0> 0.100

Operating value of current I0 3Uo< 0.100

BROKEN CONDUCTOR SUPERISION SSUP

Broken conductor function On\Off Operation On

Operating phase current as a% IP> 0.100

Time delay T 0.200

Page 42: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

52 OF 205

Loss of voltage YU<

Loss of voltage function On\Off Operation On

Operating phase voltage as a% UPE< 0.700

overload I>

Overload function On\Off Operation On

operating value of phase current IP> 1.000

Time delay T 20s

FAULT LOCATOR

Unit for presentation of line length Length unit Km

Length of protected line Line length 75.000

Positive sequence reactance of line X1 30.225

Positive sequence resistance of line R1 5.925

zero sequence reactance of line X0 113.250

Zero sequence resistance of line R1 19.125

Positive sequence reactance of source at local end X1SA 30.225

Positive sequence resistance of source at local end R1SA 5.925

Positive source reactance at remote end X1SB 21.359

Positive source resistance at remote end R1SB 4.187

Zero sequence mutual reactance for double circuit line XM0

Zero sequence mutual resistance for double circuit line RM0

Selection of presentation mode for the distance to fault * Distance unit Km

Analogue signal name** Name

Primary phase-phase voltage VT prim 220.000

Primary rated current CT prim 800.000

NOTES: ALL parameters of fault locator are set in the menu-settings-functions-group n-line.reference

*Settings done in menu: settings - Distrbreport-faultlocator

**settings done in menu:configuration-analogue inputs-u1,u2 etc

SYNCRO CHECK AND ENERGISATION CHECK FUNCTIONS:

Operation of syncro check function Operation On

Page 43: 7SA522  arelay Setting Calculation

SIEMENS 400/220kV WARANGAL SUBSTATION

53 OF 205

Reference voltage either phase to ground or phase to phase Input phase L1

Phase shift between U bus & U line Phase shift 10.000

Voltage ratio between U bus & Uline U ratio 1.000

Bus arrangment for voltage selection U selection single bus

Autoenergisation check Autoenerg Off

Mannual energisation check Manenerg Off

Mannual energisation check ManDBDL Off

High voltage limit Uhigh 0.800

Low voltage limit Ulow 0.400

Frequency difference limit Freqdiff 0.200

Phase angle difference limit Phasediff 20.000

Voltage difference limit Udiff 0.200

Autoenergisation check T autoenerg 0.200

Manual energising time T manenerg 0.200