2nd pageprint

  • Upload
    sunzala

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

  • 8/7/2019 2nd pageprint

    1/52

    1

    OPERATIONAL FAULTS IN SYNCHRONOUS GENERATORS

    Major Project Report(Part-I)

    Submitted in Partial Fulfillment of the Requirements for Semester-III of

    Master of Engineering

    In

    Electrical Engineering

    (Electrical Power System)

    By

    Suryadeep D. Zala

    090070707006

    GUJARAT TECHNOLOGICAL UNIVERSITY

  • 8/7/2019 2nd pageprint

    2/52

    2

    Certificate

    This is to certify that the Major Project Report (Part-I) entitled OPERATIONALFAULTS OF SYNCHRONOUS GENERATORS submitted by Mr.Suryadeep D. zala

    (090070707006), towards the partial fulfillment of the requirements for Semester-III ofMasterof Engineering (Electrical Engineering) in the field of (Electrical PowerSystem) of Gujarat Technological University is the record of work carried out by himunder our supervision and guidance. The work submitted has reached a level requiredfor being accepted for examination. The results embodied in this major project, to thebest of my knowledge, have not been submitted to any other University or Institution foraward of any degree or diploma. Date:

    Prof. R.P.Mehta Prof.B.A.Oza

    (Project Guide) (PG Co-ordinator)Department of Electrical Engineering Department of Electrical Engineering

    Birla Vishvakarma Mahavidyalaya Birla Vishvakarma Mahavidyalaya

    Vallabh Vidyanagar Vallabh Vidyanagar

    Head-EE

    Department of Electrical Engineering

    Birla Vishvakarma Mahavidyalaya

    Vallabh Vidyanagar

  • 8/7/2019 2nd pageprint

    3/52

    3

    Acknowledgements

    With immense pleasure, I would like to present this report on the dissertation work related toOPEARATIONAL FAULTS OF SYNCHRONOUS GENERATORS. I am very thankful to all those whohelped me for the successful completion of the first phase of the dissertation and for providing valuableguidance throughout the project work.

    I would first of all like to offer thanks to Prof.R.P.Mehta, Guide, whose keen interest and excellentknowledge base helped me to finalize the topic of the dissertation work. He has shown keen interest inthis dissertation work right from beginning and has been a great motivating factor in outlining the flow ofmy work. I would also like to thank to Mr.N.B.Shah & Mr.S.H.Kahar(Ex.Engineers,Gsecl) who hascreated interest for finding ways to improve continuity of generators in me. Also I would like to extend my

    thanks to Prof. B.A.Oza PG Co-ordinator, BVM, Vallabh Vidyanagar.

    My sincere thanks and gratitude to Dr.B.R.Parekh, Head, Electrical Engineering Department, BirlaVishvakarma Mahavidyalaya for his continual kind words of encouragement and motivation throughoutthe Dissertation work. I am thankful to Birla Vishvakarma Mahavidyalaya ,Vallabh Vidyanagar forproviding all kind of required resources. I would like to thank The Almighty, my family, for supporting andencouraging me in all possible ways. I would also like to thank all my friends who have directly orindirectly helped in making this dissertation work successful.

    - Suryadeep D. Zala090070707006

  • 8/7/2019 2nd pageprint

    4/52

    4

    Contents

    Certificate

    Acknowledgements

    1 Scope of thesis work 5

    2 Work plan for various stages including Dissertation Phase-1 and Phase-2 6

    3 Introduction 8

    4 Faults in synchronous generators 12

    5 Literature Review 40

    6 Conclusion & Future Work 50

    7 References 51

  • 8/7/2019 2nd pageprint

    5/52

    5

    Scope of thesis work

    Today's societies are critically dependent on the reliable supply of electricity. The

    reliable operation of large synchronous generators in power stations is therefore

    of paramount importance. Thus, power utilities are most keenly concerned in

    taking measures to avoid catastrophic failures and to minimize the impact of

    generator outages due to faults. Each generator constitutes one of the most

    expensive single pieces of equipment in the power station. Although they are

    mostly reliable and generally require minimal maintenance, faults can and do

    occur with varying degrees of consequences ranging from minor outages to

    catastrophic failures. When faults occur, cause-effect relationships need to be

    identified systematically. This is necessary for having a better understanding of

    the fault formation mechanisms so that preventive measures can be taken,

    although sometimes the immediate pressures for returning a generator to servicemay impede a thorough investigation. The purpose of this thesis is to report on

    practical problems in the operation of large synchronous generators and offer

    advice on remedy & try to improve the performance.

  • 8/7/2019 2nd pageprint

    6/52

    6

    Work plan for various stages

    Including Dissertation Phase-1

    and phase-2

    Work plan for dissertation Phase-1

    Sr. no. Month Work

    1 August-2010 (1)searching for the topic and requested Prof.R.P.Mehta to guide for the

    dissertation work

    (2)Confirmation from Prof. R.P.Mehta for the guidance

    2 September-2010 Collection of relevant materials including books & IEEE papers

    3 October-2010 (1)Study of Generator operation, factors affecting its performance &

    Occurrence of Faults

    (2)Literature Review

    4 November-2010 (1)Problem identification and deciding the methodology for the work

    (2)First Presentation in front of guide

  • 8/7/2019 2nd pageprint

    7/52

  • 8/7/2019 2nd pageprint

    8/52

    8

    CHAPTER:1

    INTRODUCTION

    Over the last half century much advancement has been made in the field of large

    synchronous generators. The need for larger unit sizes has driven the

    development of better and more innovative designs. Manufacturing processes

    have steadily improved.

    The advent of new insulation materials has contributed to increased

    reliability in operation at lower cost. The so-called Class F fiber-glass epoxy

    insulation system, now recognized worldwide as the best modern insulation

    system for commercial high voltage Generators, has all but replaced the hot dip

    varnish insulation systems known as Class B insulation. Sophisticated designoptimization, clever use of modern materials and more efficient cooling systems

    have been some of the key achievements in the field of design and manufacturing

    of large synchronous generators. For example, the emergence of new technology

    in internal water-cooled conductors within hydrogen cooled generators in the

    1960s was, for the power generation industry, a quantum leap in building higher

    capacity generators to answer the quest of the rapid growth in power generation

    demands with improved generation efficiency.

    Toward the end of the 20th century, privatization reforms swept through the

    electricity industry in many developed countries. It is now widely observed that,

    especially during the transition period, there have been shortfalls of capital

    investment in upgrading and replacing aged equipment in the electricity supply

    industry in all areas of generation, Transmission and Distribution.

  • 8/7/2019 2nd pageprint

    9/52

    9

    Major investment decisions have been heavily influenced by economic

    drivers, which predominantly focus on short term interests, causing a serious

    decline in support for load growth and difficulties in maintaining a satisfactory

    Level of reliability for electricity supply. This is reflected in the reduction of

    spinning reserve in the national electricity power systems. Due to the economic

    realities of the electricity market, there is also a tendency that many old

    generators built in the 1950's and 1960's are still kept in service or even recalled

    from retirement. This has caused major concerns for power generation

    companies for whom the reliability of operation of large synchronous generators

    is of critical importance. Hence, innovative measures need to be taken so as to

    avoid the risk of catastrophic failures, minimize the impact of generator outages

    and ultimately making the best use of existing generating assets.

    As participants in the modern electricity market, generating units, inevitably,

    are required to be more flexible and responsive. No different from turbines and

    power station auxiliaries, large synchronous generators have been operated

    under increasingly tough conditions with significantly greater numbers of start-up

    and shut-down, faster loading rates and a wider range of output fluctuation.

    Cyclic operation in peak load or Load following modes is more suitable to fast

    response gas turbine driven and hydro-electric generating units, whereas the

    traditional large base load machines are designed for large volume, steady output

    generation. Changing the operational mode of older machines from base load to

    peak load or load following poses significant risks to large Generators, make harsh

    problems related to ageing and, ultimately, reducing their Remanent (remaining

    after the magnetizing field has been removed) service life.

    As a matter of fact, a number of problems have emerged over time in

    generators, especially in those manufactured during the transition period of the

    1960s and 1970s. These problems have varied from fractures of stator endwinding conductors, causing hydrogen to leak into the stator coolant, to fretting

    damage of the high voltage insulation system, causing partial discharge and, in

    some severe cases, electrical short circuits. Such problems are observed

    particularly in machines of the type known as waterbox generator, discussed in

  • 8/7/2019 2nd pageprint

    10/52

    10

    further detail in further chapters, where relevant constructional features are

    described along with a number of internal faults.

    The faults described in detail cover stator core localized overheating, fractured

    stator conductors, rotor retaining ring cracking, rotor coil deterioration and inter-turn short circuits. One highlight of these problems is the failures of stator end

    windings, which originate in one way or another, from mechanical deterioration

    of the end-winding support structures. Observations on symptoms are given

    which include evidence of insulation fretting dust found in stator conductor

    interspace and on support structures. Fractures in conductors have been

    attributed to copper work hardening due to uncontrolled movement of

    conductors. Effects such as hydrogen gas leaking into the stator coolant water,

    posing an increased risk for failure.

    Also a range of test and investigation techniques commonly employed to

    detect faults in large synchronous generators discussed in it. An inspection and

    test plan is proposed, providing broad guidelines for monitoring the service

    condition of generators.

    The plan includes routine inspection, condition monitoring strategies and

    appropriate test techniques. Early detection of failure in machines is absolutely

    critical in avoiding major damage. Condition Monitoring (CM) is one of the most

    effective means of failure prevention by early fault detection in modern asset

    management practice.

    In order to optimize the maintenance strategies, the traditional time-based

    maintenance routines have been replaced with condition-based activities.

    Although capital investment is required to setup appropriate CM systems, such

    early fault detection can prevent major failures, downtime and repay their

    investment many times over. Offline diagnostics, on the other hand, play animportant role in 'health spot checks' for synchronous generators. They can be

    carried out routinely or as required and are great complement to the online

    systems.

  • 8/7/2019 2nd pageprint

    11/52

    11

    A range of offline inspections and test techniques is suggested for detection of

    specific faults of stator and rotor components. In general, it is observed that visual

    inspection by an experienced inspector, who is familiar with a particular type of

    generator, does not require sophisticated equipment and can be by far the most

    beneficial in discovering many faults and the early beginning of faults.

    Most problems within large generators can be traced back to two main original

    sources: machine design and operating regime. The former may explain why

    fracturing of some components is more common in some topologies than in

    others, whereas the latter may have to do with the temptation in meeting the

    raised generation requirements due to market demands. The thesis presents

    examples of both types, with detailed accounts being given in each case.

    Particular attention is paid to condition monitoring, both online and off-line, as abasis for developing preventive maintenance strategies to achieve reliable

    operation with extended service life.

  • 8/7/2019 2nd pageprint

    12/52

    12

    CHAPTER : 2

    FAULTS IN SYNCHRONOUS GENERATORS

    Large synchronous generators are critically important to the reliability ofpower systems. Any fault, no matter how insignificant it may be perceived to be,

    is a potential thread to its operation. Unchecked faults may ultimately lead to

    catastrophic failure with dire consequences.

    The majority of internal faults of large synchronous generators are in one way

    or the other, related to mechanical related origins, of which the mechanical wear

    and tear including structural deterioration are amongst the most common causes.

    Electrical components such as the stator conductors are designed with generoussafety margins and rarely develop faults from within themselves, provided that

    they are operated under the specified operational conditions. Some faults

    originate from inherent weaknesses in generator design or in manufacturing

    techniques and are often difficult to be remedied. On the other hand, operating

    conditions constitute the other significant contributor to the development of

    faults in large synchronous generators. Particularly, excesses in operation beyond

    the original design capabilities can cause major damage or exacerbate existing

    problems within the generators.

  • 8/7/2019 2nd pageprint

    13/52

    13

    2.1 FAULTS OF THE STATOR CORE

    2.1.1 Constructional Features of Stator Core

    Stator core of a large generator is made up of a large number of stamped thin

    segmental magnetic steel laminations. Depending on the design and size of the

    generator, there could be from 4 to 12 segments of laminations per layer. The

    lamination material usually has high magnetic permeability and low electrical

    losses. Each segment of lamination is coated with a thin layer of insulating varnish

    so that when the core laminations are compressed together, each lamination is

    electrically insulated from one another minimizing eddy current losses when the

    core is excited.

    Key bars of trapezoidal cross section are anchored axially along the internal

    bore of stator frame to form a robust support structure for the core laminations.

    Each lamination segment has dovetail shaped slots stamped on its outer

    periphery and parallel radial slots stamped on its inner periphery to

    accommodate the conductors. When the core is built up, each lamination

    segment is sequentially located and locked into the appropriate key bars at the

    dovetail slots. This allows the lamination segments to be accurately located,

    aligned and supported at the key bars. The lamination stacks are then tightlycompressed at stages under pressure to form a rigid core, providing a strong

    foundation for stator windings to be housed at the same time completing the

    stator magnetic circuits.

  • 8/7/2019 2nd pageprint

    14/52

    14

    Figure 1. Typical arrangement in the back of stator core of a 210 MW

    synchronous generator.

    Longitudinally, the core is divided into sections. Each section is sandwiched

    between two rings of thicker core plates and I-section spacers. Once built with the

    adjacent sections, they form a network of radial cooling ducts. These ducts

    provide essential cooling for the deeper parts of core laminations and passage for

    control of hydrogen flow. In most generator cores, these cooling ducts are built at

    short intervals of few centimeters along the entire length of the core while othersare built in a portion of the core only, depending on the design of cooling gas flow

    control. Core lamination intervals are called core packet.

    At both ends of the core, where magnetic flux density is the greatest due to the

    high concentration of magnetic fringing flux, additional cooling provisions are

  • 8/7/2019 2nd pageprint

    15/52

  • 8/7/2019 2nd pageprint

    16/52

    16

    problems are difficult and expensive to rectify. In large generators, stator cores

    are inevitably of complex design and, if not constructed correctly, major problems

    can and do occur after a few years in service. Some problems can escalate to

    damaging stator windings. It is also important to follow the correct procedures

    when the stator core is constructed, in addition to having the correct design and

    materials. Each core lamination must be adequately insulated, pressed tightly

    together and remain tight for the life of the generator. Loose core laminations can

    lead to major core damage and catastrophic failures.Figure 3 illustrates such a

    core fault. Following the discovery of a core fault during a routine inspection, a

    thorough investigation was carried out on a 210 MW generator that had been in

    service for 15 years. This particular generator suffered a core relaxation problem.

    The condition deteriorates over time due to cyclic thermal and electromagnetic

    forces acting on the laminations. In this case, the core was built with a thin layer

    of compressed paper base material at approximately 100 mm intervals repeated

    for the entire core length. Over time, the paper layers had been slowly

    compressed further in service causing the relaxation. As the retaining pressure in

    axial direction reduces, core 15 lamination vibration increases allowing the thicker

    protective end plates on both sides of the lamination packets to rattle against the

    'I' section gas duct spacer and eventually braking away. At the time of the repair,

    many similar areas were found to have looseness and electrical arcing similar tothat shown in Figure 3.

    Evidently, the broken away pieces of the core lamination material, bouncing

    around in the air gap when the rotor is in motion cause mechanical impact

    damage to both the stator and rotor surfaces. Lamination short circuits were

    found in many places on the stator core. The stator and rotor windings were

    contaminated with steel debris and carbon from the areas of coreburning.

  • 8/7/2019 2nd pageprint

    17/52

  • 8/7/2019 2nd pageprint

    18/52

    18

    2.1.3 Stator Core End Plates Hot Spots

    For optimum performance, generator stator core designs incorporate many

    special features. Of these, core efficiency is the main design feature measured by

    core losses. Other features such as cooling, rigidity, durability against thermal

    cycling, and ease of construction are also very important. Magnetic field

    distributions within the generator during normal and abnormal operating

    conditions are also carefully considered in generator core designs. Improper

    design or construction can lead to irreparable damage. Dreaded problems such as

    core end plate burning are amongst those consequences. Some older stator cores

    built in the 1960's and 1970's have been known to suffer a chronic problem of

    local overheating at the end regions, labelled core end plate burning. After the

    problem was experienced in several generators, it was found that the core end

    plates of these generators were made of magnetic materials which are unsuitable

    and highly susceptible to induced eddy currents.

    When generators operate in leading power factor mode the air gap flux

    density increases excessively. This leads to a significant increase in the fringingflux density in the end winding region, inducing eddy currents in the core end

    plates, resulting in local overheating and burning. As the burning activities occur

    on and behind the core end plate, usually in inaccessible locations, it is difficult to

    detect. Figure 4 illustrates a typical magnetic field distribution in the end winding

    region.

  • 8/7/2019 2nd pageprint

    19/52

    19

    Figure 4. Typical magnetic field distribution in the end winding region of a

    synchronous generator

    Once the core burning starts, it forms a so called 'hot spot" and gradually

    grows. The heat generated from the hot spots can cause damage to the

    surrounding lamination insulation, encouraging further burning. In at least three

    severe cases, the hot spots were found to have spread through the conductor

    insulation causing stator winding-to-earth faults. In other cases, the damage was

    found to have extended to the generator air gap and stator core teeth where the

    magnetic flux density is high, causing rapid core deterioration.

    2.1.4 Back-of-Core Burning Fault

    Back-of-core burning fault, as its name suggests, occurs in the back of the core

    between the stator core laminations and their support key bars. The burning is a

    result of electrical arcing from the current transfer between core laminations and

    the key bars through poor electrical contacts. The key bars have an important

  • 8/7/2019 2nd pageprint

    20/52

    20

    function to provide accurate alignment and mechanical support for individual

    laminations through a dovetail arrangement, as described previously in Section

    2.1.1. Generally, there are about 20 to 30 key bars in a stator core of a 210 MW

    generator.

    There are two main types of stator core commonly known as (1) insulated

    core and (2) non-insulated core. As their names suggest, the insulated cores are

    electrically insulated from the stator frame whereas the non-insulated cores have

    their laminations directly built on the dovetail shape key bars, which are

    electrically earthed to the stator frame.

    The key bars are electrically short circuited at the ends to form a squirrel

    cage, designed to carry the induced currents caused by the stator leakage flux in

    the back of the core. The induced currents flow between the network of key bars,

    core laminations and core end plates and are highly complex in orientation,

    fluctuating in magnitude depending on the operating condition and the degree of

    magnetic saturation in the stator core. Especially during high leading power factor

    generation, the saturation of magnetic field

    can cause the induced currents in the back of the core to intensify near the core

    ends. Back-of-core burning faults have been found on the top, sides and bottom

    of turbo-generator stator cores.

    Even though the back-of-core burning fault does not threaten an immediate

    outage to the affected generator, it poses a major concern. As the electrical arcing

    activity occurs, it produces metal globules at the fault location as a result of high

    temperature burning of core lamination and key bar metals. Eventually, the

    globules dislodge themselves from their 'birth place' and find their way into the

    generator air gap causing serious contamination to the generator internal

    components with thousands of small broken metal globules. This ramifies tosecondary problems such as degrading the high voltage winding insulation,

    creating magnetic termites on stator conductors, promoting interturn short

    circuits on rotor windings, causing interlaminar short circuits to stator core and

    other mechanical impact damage to rotor components such as slot wedges and

    rotor retaining rings.

  • 8/7/2019 2nd pageprint

    21/52

    21

    2.2FAULTS OF THE STATOR WINDINGS

    Stator winding faults can have devastating consequences in terms of generating

    plant availability. Although they can occur in any types of generator, some are

    more prone to developing stator winding faults due to inherent design

    weaknesses. One such type is known as the waterbox generator, which made its

    debut halfway through the 20th

    centuiy. Figure 7 depicts the end view of a typical

    waterbox generator. Although reasonably reliable when new, its inherent

    weaknesses became evident after about 10 years of operation. The design proved

    to be maintenance intensive and hazardous due to occurrences of hydrogen

    leaking into the stator coolant.

    2.2.1 Constructional Features of Stator Windings

    2.2.1.1 Conductors

    There are two layers of coil side within each stator slot. Each coil side consists

    of a bundle of insulated prismatic hollow copper strands, referred to as sub-

    conductors. The sub-conductors are individually insulated from each other to

    minimize internal eddy currents, and are transposed along the stator core to

    minimize internal circulating currents in between the strands, referred to as

    Roebel transposition, further improving machine efficiency. These hollow sub-

    conductors are designed to carry the stator currents as well as to reticulate the

    cooling water. At each end of the half coils, the strands are pneumatically and

    electrically connected together and soldered to a hollow termination nozzle

    making it a gas tight joint. This nozzle is mounted onto the back of waterbox. Each

    termination nozzle takes cooling water from the waterbox for conductor cooling

    at the same time carries electrical current. Each pair of corresponding termination

  • 8/7/2019 2nd pageprint

    22/52

    22

    nozzles is connected together via copper links to complete the electrical circuits

    of the windings.

    Due to the physical arrangement of the waterboxes, there is a larger gap in

    between the adjacent waterboxes; the space in between the conductors ofadjacent phase groups is much greater than that of others in the same phase

    group. Since the stator core slots are made with equal spacing, there are subtle

    differences in coil pitch lengths and shape variations of conductors in the same

    phase group at the end winding regions

    This unique feature makes stock-holding of spare conductors difficult and

    expensive. Most waterbox generators utilize so called, semi-flexible coils; that is

    the middle section of the coil in the core region is more solid. In contrast, the

    overhang sections are more flexible. Following the insulation wrapping process,

    the middle straight section of the coils in the core section is pressed in formers to

    exact dimensions and heated to cure the resin enriched insulation simultaneously.

    The overhang end sections are, however, not pressed but insulated differently to

    the core section in such a way that they are more flexible making coil installation

    process easier. The insulation materials and coil construction methodologies have

    varied with time and technologies available. The early generators utilized resin

    rich mica-bituminous hot dip varnish insulation whereas the more recentgenerators have been equipped with resin rich fiber-glass epoxy insulation

    system.

    2.2.1.2End-Winding Support System

    In the case of waterbox generators, a unique end winding support

    system is utilized in order to restrain the stator conductors in the correct position

    against electromagnetic forces. The stator end winding support system at each

    end of the generator consists of one support comb to restrain the conductor ends

    and support the resin waterboxes, nonmetallic support brackets to provide back

    bone support for the end windings and to connect the support comb to the stator

    frame structure at core end, a frustum cone on the involute side and a network of

  • 8/7/2019 2nd pageprint

    23/52

    23

    nylon tie rods. Each end-winding support comb consists of six matching segments

    fabricated from resin-bonded fabric laminate material. It is mounted on the end

    of the support brackets in parallel with stator core laminations to form a locating

    platform for the ends of the

    stator conductors. The stator conductors are further secured in position with a

    resin-bonded fabric laminate ring fitted to the inner periphery of the support

    comb by a series of radial nylon studs through the comb width. For additional

    stiffness, the comb is secured to the stator core compression plate via a set of

    long brass studs in parallel with the support brackets.

    [End winding support system looking from behind the end winding involute

    showing radial support brackets.]

    2.2.1.3 Waterbox

    A waterbox assembly consists of a cast resin epoxy base with conductor mounting

    holes and securing studs, a cover and a carbon free rubber gasket . Waterboxes

    are installed at both ends of the stator winding for the purpose of reticulating the

  • 8/7/2019 2nd pageprint

    24/52

    24

    cooling water into the hollow stator conductors. They also serve as an additional

    barrier of electrical insulation between the high voltage conductors and the

    nearby outer casing at earth potential. Once installed correctly with all

    conductors in position, the waterbox assembly becomes gastight to an operating

    hydrogen pressure of about 300 kPa. Stator conductors of the same phase group

    are mounted through the back of a waterbox in two rows corresponding to the

    inner and outer layers of the stator windings. Electrical connections between the

    inner conductors and outer conductors are made with copper clamps called

    'conductor links' forming stator windings.

    Stator coolant water is pumped into each waterbox through hollow

    terminal leads at one end of the generator. The cooling water is then forced

    through the conductors to the corresponding waterbox at the opposite endbefore returning to the external cooling, filtering and pumping system.

    [A typical end winding arrangement in a 210 MW generator, showing

    waterbox base, coil links, coil end nozzles and spacing between conductor

    ends.]

  • 8/7/2019 2nd pageprint

    25/52

    25

    2.2.2Sub-ConductorCracking Problem

    In normal operation, the generator is filled with hydrogen gas at 300 kPapressure and the stator coolant system is charged with demineralised water at

    200 kPa. The purpose for the differential in the pressure is to prevent water

    leakage into the stator insulation system. Should any small leaks occur in the

    stator coolant system due to faults such as cracks in conductors or leak gaskets,

    hydrogen gas escapes into the stator coolant water and is collected in a gas

    catchment chamber. An alarm is triggered and hydrogen gas is vented safely into

    the atmosphere. Usually, hydrogen leaks are small and the loss of hydrogen

    pressure is insignificant. However, if the cracks were allowed to grow, excessivehydrogen gas in stator coolant water could seriously reduce cooling capacity of

    the sub-conductors leading to local overheating, eventually, deformation of the

    subconductors and severe damage to the stator conductor. Even though most

    stator designs incorporate thermal protection features with thermocouples

    embedded in the core and various stator slots, overheating of this nature tends to

    be localising around the affected conductor and have minute impact on the

    average thermal distribution of the stator. If the fault location is away from a

    thermocouple, its temperature is less likely to be registered. In the extreme cases,

    the stator windings could suffer catastrophic failure.Such a gas leakage into the

    stator coolant water is commonly called 'gas-in-statorcoolant leak'.

    2.2.3End Winding Looseness Problem

    Investigation of the end winding structure of many generators have found

    that in most cases where cracked subconductors are found there is evidence of

    excessive interconductor movement within the end-winding and relative to their

    support structures. As the conductors vibrate in service, they rub against one

    another and their support system, thus generating the so-called insulation fretting

    dust, as exemplified in Figure. The fretting dust is relatively harmless to the

  • 8/7/2019 2nd pageprint

    26/52

    26

    generator and is a useful indicator for visual inspection of looseness. However,

    excessive amount of insulation fretting dust is a cause for alarm as it is indicative

    of a significant loss of insulation material; a sign of dangerous degradation of

    conductor insulation system, thus increased risk of discharge and electrical faults.

    Visual inspection is arguably the most practical and effective method for

    detecting insulation fretting and deterioration of end winding insulation related

    to conductor vibration. The relaxation of the conductors and their support

    systems invariably leads to the loosening of the support comb and the involute

    frustum support cone, which then vibrates in sympathy with the conductors,

    causing insulation fretting, as illustrated in Figure 18. This accelerates the rate of

    deterioration of the end winding support system.

    [End winding relaxation causing abrasion wear on conductor insulation

    indicated by insulation fretting dust.]

  • 8/7/2019 2nd pageprint

    27/52

    27

    [Stretched and unlocked nylon tie rods further promoting end winding

    relaxation.]

    2.2.4.1 A Case Study of stator winding fault

    2.3ROTOR FAULTS

    2.3.1 Constructional Features of Synchronous Generator Rotor

    Only high speed turbo cylindrical generator rotor is discussed in this

    thesis. Large turbo generator rotor is manufactured from one-piece alloy steel

  • 8/7/2019 2nd pageprint

    28/52

    28

    forging with winding slots and ventilation slots machined in the forging. The rotor

    shafts are usually hollow and supported at both ends by white metal journal

    bearings. Most high speed turbo generators of significant size would normally be

    hydrogen cooled and their rotor shafts provide a good sealing collar for the

    hydrogen seal to perform satisfactorily. Some rotor designs utilise sliprings as

    means of connecting the rotor windings to the main excitation DC source, either

    from a static excitation system or a DC main exciter. Other designs utilise a

    brushless excitation system involving an AC main exciter and rotating rectifiers

    eliminating the need for rotor sliprings. In both cases, the physical connections

    from the rotor winding to its external DC supply are made through axial leads

    placed in the centre bore of the shaft at the exciter end called 'up-shaft leads'.

    Radial connections,also called 'radial pins' complete the electrical connection

    between the up-shaft leads and the rotor windings. Design considerations of the

    rotor insulation system are not only to satisfy the electrical requirements for the

    windings but more importantly, to withstand the enormous centrifugal forces

    acting on the windings

    The rotor end windings are robustly built with strong insulation packing

    blocks in between each coil groups in both radial and axial directions to prevent

    coil distortion that could result from mechanical forces under steady state and

    transient conditions. Each end winding is held in position by a retaining ring and a

    balance ring.The rotor end windings are insulated from their retaining rings with

    a strong insulation wrapping that allows sufficient electrical insulation property

    but also withstands the mechanical pressure between the end winding coils and

    the retaining rings. Furthermore, it is also critical that the design of insulation

    system, rotor winding coils and their retaining systems have careful

    considerations for thermal expansion for the winding coils to avoid distortions of

    the copper coils.

  • 8/7/2019 2nd pageprint

    29/52

    29

    2.3.1.1 Rotor End Winding Retaining Rings

    As the name suggests, retaining rings are of cylindrical shape that

    manufactured from extremely high yield strength steel alloy, designed to

    withstand enormous centrifugal forces from the weight of rotor copper end

    windings. The retaining rings' main function is to retain the rotor end windings.

    The design details of retaining rings can vary between manufacturers. However,

    they commonly have one end of their cylinder interference fitted to the rotor

    body and the other to a so called balance ring. On installation, the end rings are

    heated to a designed temperature usually about 250C. As the thermal expansion

    overcomes the interferential fit, the retaining ring is slid over the insulated end

    winding onto the rotor shrink landing while being hot. It is extremely important

    that the interference fit it designed and manufactured correctly so that the end

    rings stay tight in position to at least 120% of the rotor rated speed. To further

    secure the retaining rings in position and to prevent the retaining rings to move

    away from the shrink landing, a locking mechanism is built into the nose section in

    the form of a bayonet, step, clip ring or screw thread as shown in figure.

    [Common types of retaining ring designs.]

  • 8/7/2019 2nd pageprint

    30/52

    30

    2.3.1.2Rotor Windings

    In the case of a high speed, 3000 rpm, large turbo generators, the rotor has a two

    pole winding made up from serial connected double helical bare copper coils

    forming North South magnetic poles. Each turn of the rotor winding is

    insulated from each other with thin insulation strips, called 'inter-turn insulation'

    forming rotor coil stacks. The coil stacks are then insulated from the rotor body

    with strong fibre-glass insulation troughs call 'slot liners'. The coils are retained in

    the slots by strong metallic slot wedges that are keyed in the rotor slots by their

    inverted-T shape and the retaining ring at each end. Cooling circuits are formed in

    the windings by using a network of hollow conductors and carefully designed

    radial cooling ducts made up by cut-out slots or perforated holes along each coil

    turn.

    In most rotors, the cooling gas is forced through the coils in both axial and

    radial directions. Carefully designed ventilation features are incorporated in the

    coil stack in each rotor slot and in the slot wedges to maximize the gas flow

    through the rotor. The bulk of exhaust gas from the rotor flows into the air-gap

    and then through stator core cooling ducts to further remove heat from the

    stator. As the rotor windings normally carry thousands of Amperes, a properly

    designed cooling system for rotor coils is

    extremely important.

    2.3.1.3Rotor Radial Connectors

    Rotor radial connectors constitute another one of the critical components of

    the generator rotor. The connectors provide electrical connections from rotor

    windings to a DC supply via sliprings or rotating rectifiers. The main components

    of the connectors are made of high conductivity hard drawn copper, fitted to and

    electrically insulated from the rotor shaft. As the connectors rotate with the rotor,

  • 8/7/2019 2nd pageprint

    31/52

    31

    their design must have robust mechanical construction and must have a locking

    mechanism to ensure that their components are secured in position. hi hydrogen

    cooled generators, they are also required to be gas tight to prevent gas leakage to

    the atmosphere. A typical arrangement of a radial connector assembly.

    2.3.2 RotorRetaining Ring Faults

    2.3.2.1 Stress Corrosion Cracking

    In addition to the centrifugal forces produced by the rotor end windings, the

    retaining rings' own mass and the shrink fit forces contribute a

    significant radial loading on the rings. Iii fact, studies have found that only

    approximately 25% of the force is contributed by the end windings' mass and 75%

    from the retaining ring itself. These forces stress the retaining rings to over 50%

    yield strength at the normal operating speed. In-service failure of rotor retaining

    rings is catastrophic. Many studies and failure investigations on generator rotor

    retaining rings have been undertaken in the70

    's and80

    's by large powergeneration utilities and technical organisations such as EPRL They all come to the

    same conclusion, namely that the intergranular stress corrosion cracking of

    nonmagnetic materials such as 1 8Mn4Cr steel is responsible for most failures of

    rotor retaining rings.Statistically, while the failure rate of rotor retaining rings is

    less than 0.01 percent, the consequence of this type of failure is enormous. In

    most cases where a retaining ring contained cracks greater than the critical crack

    size, its failure leads to a total destruction of the generator.

    The majority of retaining ring replacements is due to crack discovery below

    critical crack size by routine Non Destructive Testing (NDT), risk management or

    preventative asset management initiatives. For example, according to the

    experience of one OEM, about 80% of non-magnetic 1 8Mn4Cr retaining rings

    inspected had indications of stress corrosion defects either requires replacement

  • 8/7/2019 2nd pageprint

    32/52

    32

    or remedial work, of which, approximately 5 percents requires immediate

    replacement because of critical size defects, and the rest was refurbished and

    returned to service for later replacement. To date there is still a considerably

    large number of 1 8Mn4Cr retaining rings remaining in service with strict control

    of generator internal environment

    and regular NDT programs.

    2.3.2.2 Electrical Arcing on Rotor Retaining Rings

    This fault, while considered minor and often overlooked, is quite common

    especially in older generator rotors. Electrical arcing damage is often found at the

    interface between the retaining rings and rotor body or balance rings or rotor slot

    wedges. The arcing spots are a result of electrical arcing across the components

    driven by negative phase sequence currents generated on the rotor surface

    during generator's abnormal operations such as motoring, pole slipping or lost of

    excitation. Such arcing spots could alter the material properties locally, especially

    hardness. In the worst case, an arcing spot could lead to initiation of cracks and

    eventually cause catastrophic failure to the retaining ring.

  • 8/7/2019 2nd pageprint

    33/52

    33

    2.3.3Copper Dusting Problem in Rotor Windings

    The radial cooled rotor design utilises channels underneath each winding slot,called sub slot, to deliver the cooling gas to the centre of the rotor from both

    ends. The cooling gas is forced under the rotor end windings to pressurise the sub

    slots, then bleeding radially outward through perforations along the rotor coils as

    depicted in Figure. The cooling gas continues its travel past the air gap and

    exhausts through stator core cooling ducts before transfer its heat to Hydrogen

    coolers typically placed horizontally behind the stator core or vertically at each

    end of the stator. In order to maximize heat exchange efficiency between the

    copper coils and the cooling gas, each coil turn in the slot section of the rotorwinding is made up of two layers, so called half coil, of bare copper strips

    uninsulated from each other. The half turns are brazed to the curved sections in

    the end windings to complete the coil. Each copper strip has elongated slots cut-

    out for its entire

    straight length. The slots are slightly offset from the centre in opposite direction

    so that when stacked up together they form a zigzag path for cooling gas to flow

    through as shown in Figure. In radial cooled rotors, a significant proportion ofcopper dust is generated in between the pairs of half turns. The rest is generated

    by the rubbing action at the interfaces between the copper coils and the fiber

    glass insulation surrounding them such as slot liner, top insulation pads and inter-

    turn insulation.

  • 8/7/2019 2nd pageprint

    34/52

    34

    [Cross sectional view of rotor winding (a) radial cooling, (b) axial cooling.]

    Copper dusting is generated both when generator is on-line and off-line with

    a different dynamic mechanism. When the generator rotor is rotating at full

    speed, all rotor coils are pushed outward against the rotor slot retaining wedges

    by enormous centrifugal forces. This causes the rotor coils and their insulationsystem to lock up together.

    2.3.3.1 Consequences of Rotor Copper Dusting

    The generation of copper dusting can have a devastating impact on the

    operation and reliability of generators. The copper dust is highly conductive andcan cause short circuits between rotor turns, commonly called rotor shorted turn,

    or to ground, commonly called rotor earth fault. In relative terms, the rotor

    shorted turn problem is relatively less serious. The voltage between two adjacent

    coils is in the order of only a few volts. However, the inter-turn insulation is very

    thin: once a sufficient amount of copper dust is deposited across two adjacent

  • 8/7/2019 2nd pageprint

    35/52

    35

    coils, the rotor current would partially by-pass the rest of the winding causing

    imbalance in the magnetic field, resulting in an increase in shaft vibration. Sudden

    step changes in shaft vibration with the fundamental component at the exact

    generating frequency is usually the tell tail of a rotor winding inter-turn short

    circuit fault. The rotor earth fault, on the other hand, is much more serious and

    usually leads to extensive secondary damage to the rotor. Due to the massive

    inductance of the rotor windings, an earth fault could produce devastating arcs

    leading to burning damage to rotor components surrounding the fault.

    Fortunately, earth faults in rotor windings, directly caused by copper dusting

    alone, are relatively uncommon. They normally occur in cohort with other

    problems within the rotor or its protection systems. In addition to continuous

    online vibration monitoring systems, most of large turbo generators have a rotor

    earth fault protection system that continuously monitors the rotor impedance.

    2.3.4Rotor Coil Overheating

    Distortion damage of rotor coils is commonly found amongst large turbo

    generator rotors. In comparison to salient pole rotors, large high speeddistributed winding rotors have a relatively complicated system of rotor coils,

    insulation, separator blocks, retaining rings and so on. In addition, all components

    in the rotor windings are designed to move in harmony with each other, within

    certain design limits, to cope with the inevitable thermal expansion and

    contraction of rotor coils. The ventilation systems in these rotors are complex and

    play a very important role in their operation. Deterioration or misalignment of

    insulation components in the rotor windings often cause blockages to the

    ventilation system and coil overheating.

  • 8/7/2019 2nd pageprint

    36/52

  • 8/7/2019 2nd pageprint

    37/52

  • 8/7/2019 2nd pageprint

    38/52

    38

    2.3.7 RotorUp-Shaft Lead Fault

    Up-shaft lead assembly provides electrical connection from the outboard

    radial connectors to the inboard radial connectors of large hydrogen cooled

    synchronous generator rotors. The up-shaft lead assembly is inserted in the rotor

    shaft bore and usually contains gas tight seals to prevent hydrogen leaks. The up-

    shaft lead assembly functions as an electrical conduit conducting DC current to

    energize the rotor windings. A typical up-shaft lead assembly comprises two

    heavy 'D' cross sectional copper bars, an insulation separator between the D-

    sections and an insulating tube that doubles up as a shell for the whole assembly.

    The outer end of the leads is connected to the outboard radial connectorassembly and the inner end is connected to the inboard radial connectors.

    The insulation tube is made from paper resin impregnated bakelite or fibre

    glass based insulation materials in modem rotors. Given that the rated

    [ A typical crack in up-shaft lead insulation tube in a 210 MW generator.]

  • 8/7/2019 2nd pageprint

    39/52

    39

    rotor voltage is usually around 400 volts, even with a crack the insulation tube

    should provide adequate electrical insulation grading. However, the concern is

    that when the crack is contaminated with moisture or conductive dust, it can

    develop a significant risk of electrical earth fault or across the windings within the

    rotor shaft bore. Such faults, whilst relatively rare, can cause considerable

    damage to the rotor.

  • 8/7/2019 2nd pageprint

    40/52

    40

    Part-I IntroductionToday's societies are critically dependent on the reliable supply of electricity. The reliable

    operation of large synchronous generators in power stations is therefore of paramount

    importance. Thus, power utilities are most keenly concerned in taking measures to avoid

    catastrophic failures and to minimize the impact of generator outages due to faults. Each

    generator constitutes one of the most expensive single pieces of equipment in the power

    station. Although they are mostly reliable and generally require minimal maintenance, faults

    can and do occur with varying degrees of consequences ranging from minor outages to severe

    failures.

    When faults occur, cause-effect relationships need to be identified systematically. This is

    necessary for having a better understanding of the fault formation mechanisms so that

    preventive measures can be taken, although sometimes the immediate pressures for returning

    a generator to service may impede a thorough investigation.

    Over the last half century much advancement has been made in the field of large Synchronous

    generators. The need for larger unit sizes has driven the development of better and more

    innovative designs. Manufacturing processes have steadily improved. The advent of new

    insulation materials has contributed to increased reliability in operation at lower cost.

    Sophisticated design optimization, clever use of modern materials and more efficient cooling

    systems have been some of the key achievements in the field of design and manufacturing of

    large synchronous generators

    Different ways to improve the continuity of supply of generator are shown below different

    researchers are working on this era by using different methods by publishing different paper

    over past years.

    Part-2 Different Techniques

    I have presented the different techniques to improve the continuity of generator. I mention

    the considerations which would be taken care of research papers.

    Chapter:3 Literature review on Operational Faults in Large Synchronous Generators

    Suryadeep D. Zala

    M.E. (EPS)

  • 8/7/2019 2nd pageprint

    41/52

    41

    (a) Recent problems experienced with motor and generator windings IEEE Paper No. PCIC-

    2009-6 by G.C. Stone, M. Sasic, D. Dunn, I. Culbert

    The problem of building more efficient machines which has less cost & time consuming as

    well as with higher continuity.

    Some of the methods employed to accomplish this include

    (1) Reducing the conductor cross section

    (2) Reducing the insulation thickness

    (3) Reducing the amount of steel core material

    (4) Developing manufacturing methods that result in less time to manufacture.

    Each of these methods tends to increase the operating temperature of the windings or put

    additional voltage stress on the electrical insulation. The author indicates different problems

    associated with the machine parts such as rotor & stator while applying one of the methods

    shown above to achieve more efficiency.

    Some suggestions are also given by him to avoid premature failure of stator & rotor of machine

    such as to reduce partial discharge level by proper dimensioning of it. Also to take failure into

    consideration while designing different machines. the parameters are selected as which makes

    system more stable

    Problems such as coil abrasion in the slot, electric stress relief coating deterioration and partialdischarges in the end winding have led to failures in as short as 5 years of operation. This

    anecdotal information is supported by the fact that PD for some manufacturers is higher for

    recently made machines than for similar machines made in excess of 10 years ago.

    To avoid premature failures, users of modern air-cooled machines should ensure they have a

    good purchase specification and ensure the manufacturer has an appropriate QA program in

    place.

    Different problems occur due to the reduction of material as well as time. The faults due to

    partial discharge and some of the other faults can be avoided by means of proper study of theeffects of one component on other while change in design quality assurance programs as well

    as condition monitoring helps in reducing faults proper maintenance would proper

    maintenance would also help in improving continuity of the machine and there by increase in

    efficiency

  • 8/7/2019 2nd pageprint

    42/52

    42

    (b)Effect of manufacturer winding age and insulation type on stator winding Partial discharge

    levels by G. C. Stone and V. Warren From DEIS, September/October 2004, Vol. 20, No. 5

    Partial discharges (PD) are a symptom and sometimes a cause of many types of motor and

    generator stator winding insulation system deterioration mechanisms in utility generators.

    Online PD measurement has been able to determine whether the electrical insulation is

    deteriorating because of loose coils in the slots, resulting in insulation abrasion; thermal

    deterioration or load cycling, which leads to insulation delamination and electrical tracking

    caused by partly conductive contamination of the end windings

    At the end of 2003, over 60,000 test results had been accumulated over 10 yr, and simple

    statistical analysis has been applied to the database to extract Information that can help test

    users to interpret PD results better. In addition, experience has accrued on what operating and

    environmental parameters may affect the PD readings as well as the deterioration in the stator

    insulation condition.

    Procedures used to indicate and analyze insulation condition

    (1) Data Presentation (2) Database to the End of2003 (3) Database Analysis Method

    With thousands of machines monitored for as long as 25 yr with the same method, on-line PD

    testing has become a recognized, proven tool to help maintenance engineers identify which

    stator windings need off-line testing, inspections, and/or repairs. Within the statistical accuracy

    possible with several thousands of independent results, it seems that critical PD levels only

    depend on operating voltage, hydrogen pressure, manufacturer, and the specific type of PDsensor and instrumentation used.

    The paper illustrates the important parameters which effect the partial discharge levels of

    winding. The study shows that this method helps in selection of parameters in new design

    development as well as in findings the areas which needed the maintenance and reduces the

    time & money

    (c) An Accurate Approach to Earth Fault Detection for Generator Stator Using

    Fuzzy Logic byH. Khorashadi Zadeh

    In this paper the use of fuzzy logic for stator earth fault detection is presented. A generator

    model is simulated using EMTDC. Earth faults are simulated between 0.1% to 100% distancepoints from the generator neutral. The combination of both EMTDC simulation and neural

    network presented in this paper is to introduce a new, complementary method that will

  • 8/7/2019 2nd pageprint

    43/52

    43

    perform better in instances where the interpretation of traditional methods is somewhat

    dubious.

    A lot of attention has been focused on generators single-phase to ground fault which is one of

    the main causes for shutting down a generator. The causes may be due to insulation

    degradation in the windings as well as environmental influence such as moisture or oil in

    combination with dirt settles on the coil surfaces outside the stator slots. This often leads to

    electrical tracking discharges in the end winding which eventually punctures the ground wall.

    Stators winding fault must be avoided since the amount of time wasted and the cost for

    repairing a generator is enormous.

    Hence, it is necessary to prevent such occurrences by incorporation reliable protection and

    monitoring schemes. The differential relay does not cover the entire stator winding of the

    generator. In addition some of the faults may well occur before the sensitivities of the

    protective relay operate, while some types of deterioration can progress rapidly with littleadvance warning of the failure; therefore it is critical to get frequent updates of the condition

    of components.

    Protection relaying is just as much a candidate for the application of pattern recognition. The

    majority of power system protection techniques are involved in defining the system state

    through identifying the pattern of the associated voltage and current waveforms measured at

    the relay location. This means that the development of adaptive protection can be essentially

    treated as a problem-pattern Recognition/classification.

    Artificial Intelligences (AIs) are powerful in pattern recognition and classification. They possessexcellent features such as generalization capability, noise immunity, robustness and fault

    tolerance. Consequently, the decision made by an AI-based relay will not be seriously affected

    by variations in system parameters. AI-based techniques have been used in power system

    protection and encouraging results are obtained

    A fuzzy logic scheme to identifications of generator stator windings fault is presented.

    Simulation studies are performed and the relays performance with different internal fault is

    investigated. The obtained results show that the proposed fuzzy logic-based fault detector

    represents a proper action.

    It can operate with proper sensitivity thus the use of fuzzy scheme can make it possible to

    extend reliability and sensitivity fault detectors for generators.

  • 8/7/2019 2nd pageprint

    44/52

    44

    The paper illustrates about the earth fault detection as well as the use of fuzzy logic for the

    relaying operation of the simulated model of small power system. It is being advantageous as

    operation does not affect other parameters of system. the only problem is to implement a fuzzy

    logic system requires proper definition as well as proper design of simulated model. Also it is

    being complex, time consuming and costly. it can be used for small systems.

    (d)Effects of Types of Faults on Generator Vibration Signatures by R. Oliquino, Jr., S. Islam,SMIEEEand H. Eren,

    Generators are frequently subjected to high currents and voltages caused by electrical

    disturbances in the power system. Faults in particular subject the generator to stresses beyond

    its design limits and cause high temperature increase, amplify and distort air gap torques, and

    create unbalanced flux densities. Even more stressful as a consequence of faults are sudden

    loss of load, fault clearance and reclosing. Mechanically, the abnormal forces that are

    generated excite the rotor and as a result, amplify the shafts normal mode of oscillation. Theobjective of this paper is to present the results on the experiment conducted regarding the

    effects of selected types of electrical faults on generators vibration signatures. It aims to

    examine the generated vibration frequencies, changes in rotor shaft orbits and increase in

    vibration magnitudes as a result of faults. In this paper, the results on the experiment

    conducted regarding the effects of selected types of electrical faults on generator vibration

    signatures are presented. It aims to examine the generated vibration frequencies, changes in

    rotor shaft orbits and increase in vibration magnitudes due to three-phase fault (3PF), line-to-

    line fault (LLF), line-to ground fault (LGF) and double-line-to-ground fault (LLGF). In the

    experiment, the above conditions were applied to the terminals of a loaded 5KVA three phase

    synchronous generator. The vibration responses for each condition were examined, analyzed

    and compared.

    It is evident from the plots that the vibration frequencies are random, which means that the

    generator motion is not periodic. Random motion is associated with severe mechanical or

    structural looseness.

    The effect of3-phase fault (3PF), line-to-line fault (LLF), line-to-ground fault (LLGF) and line-to-

    ground fault (LGF) on the 5KVA model generator vibration signature is evidently seen

    particularly on the time and XY plots. LGF appears to have caused the strongest magnitude gainfollowed by LLF. However, 3PF has the highest average gain. This reveals that although LGF and

    LLF could produce the strongest vibration magnitudes, a 3PF will most likely generate strong

    vibration responses.

    LGF also exhibited the greatest effect on the generator shaft deflection by a wide margin

    against 3PF, which came in second. Additionally, LGF fault has the highest average shaft

  • 8/7/2019 2nd pageprint

    45/52

  • 8/7/2019 2nd pageprint

    46/52

    46

    (4) Sub conductor cracking problem

    In normal operation, the generator is filled with hydrogen gas at 300 kPa pressure and the

    stator coolant system is charged with demineralised water at 200 kPa. The purpose for the

    differential in the pressure is to prevent water leakage into the stator insulation system.

    Any small leaks occur in the stator coolant system due to faults such as cracks in conductors or

    leak gaskets, hydrogen gas escapes into the stator coolant water and is collected in a gas

    catchments chamber. An alarm is triggered and hydrogen gas is vented safely into the

    atmosphere. Usually, hydrogen leaks are small and the loss of hydrogen pressure is

    insignificant. However, if the cracks were allowed to grow, excessive hydrogen gas in stator

    coolant water could seriously reduce cooling capacity of the sub-conductors leading to local

    overheating, eventually, deformation of the sub conductors and severe damage to the stator

    conductor.

    (5) End Winding Looseness Problem

    Investigation of the end winding structure of many generators have found that in most cases

    where cracked sub conductors are found there is evidence of excessive interconductor

    Movement within the end-winding and relative to their support structures. As the conductors

    vibrate in service, they rub against one another and their support system, thus generating the

    so-called insulation fretting dust.

    Excessive amount of insulation fretting dust is a cause for alarm as it is indicative of a significant

    loss of insulation material; a sign of dangerous degradation of conductor insulation system,

    thus increased risk of discharge and electrical faults.

    (6)Conductor Damage by Foreign Objects Magnetic Termites

    A small metallic object accidentally left in the generator during an overhaul or a fragment of

    lamination broken away from the core can cause major failures.

    (B)Different Faults occur of Rotor

    (1) Rotor Retaining Ring Faults

    (a) Stress Corrosion Cracking

    When in service, rotor retaining rings endure extremely high levels of stresses . In addition to

    the centrifugal forces produced by the rotor End windings, the retaining rings' own mass and

    the shrink fit forces contribute a Significant radial loading on the rings. Excessive stress may

    damage the rings.

  • 8/7/2019 2nd pageprint

    47/52

  • 8/7/2019 2nd pageprint

    48/52

    48

    (3) Stator Core Ring Flux Test

    (4) Stator Core Lamination Tightness Test

    (5) Stator Slot Wedge Tightness Test

    (6) End Winding Vibration Testing

    (a) On-line Condition Monitoring

    (b) Off-line Evaluation

    (7) Stator Windings Pneumatic Tests

    (8) Stator Core End Plate Hot Spot Inspection

    (9) Generator Rotor Retaining Ring Inspection

    (a) Traditional Dye-Penetrant Inspection

    (b) In-Situ Inspection

    (10) Rotor RSO Test

    (11) Rotor Coil Volt-Drop Test

    (12)Thermo graphic Examination

    (13) Radiographic Examination

    Part 4 conclusion

    In this paper, the different faults occur in synchronous generator as well as their detecting

    methods are presented.

    Different methods are selected according to the surrounding environment & their compatibility

    towards desired condition.

    Database method gives the detailed study of effects on different parameters while in operating

    conditions. It is very useful where detailed study of machines needed but it has a limitation that

    it is very lengthy process as well as data that are used from the database may not fulfill the real

    time requirement. in real time data may differ according to the surrounding environment

    Vibration signatures are helpful to indicate the effect of rotor vibration because of different

    faults. It is a model base analysis & limited to provide efficiency above certain range.

  • 8/7/2019 2nd pageprint

    49/52

    49

    The use of fuzzy logic & artificial intelligence gives the accurate results but it is difficult in design

    as well as implementation. Also the programming of the network is very difficult & costly.

    The methods for detecting & diagnostic methods are described in the paper. The mixed

    approach of different methods are used according the accuracy required in given time period.

    References

    [1] O. Gl and T. V. Tran, 'Stator End Winding Problems in Large Synchronous Generators and Some

    Remedies', ICEM - International Conference on Electrical Machines, Bruges - Belgium, August 2002.

    [2] G. C. Stone, Edward A. Boulter, Ian Culbert and Hussein Dhirani, 'Electrical Insulation for Rotating

    Machines Design, Evaluation, Aging, Testing, and Repair'. IEEE Press series on Power Engineering,

    Institute of Electrical and Electronics Engineers, 2004.

    [3] ESIPC - Electricity Supply Industry Planning Council, 'The South Australian Annual Planning Report -

    2005', Executive Summary, June 2005.

    [4] EWBANK PREECE AUSTRALIA, 'Preliminary Study into Two-shifting Operation at Torrens Island Power

    Station', Consultancy report for SA Generation Corporation, March 1997.

    [5] 5. Denison ETSA Torrens Island Power Station, 'Ageing of Machines with Respect to Load or Field

    Current Cycling', CIGRE Working Group 11-01 Questionnaire 90-3, reply letter to the CIGRE Paimel 11

    convernor, December 1992.

    [6

    ] J. E. Timperley and J. R. Michalec, 'Estimating The Remaining Service Life of Asphalt-Mica StatorInsulation', IEEE Transactions on Energy Conversion, Vol. 9, No. 4, pp 686-694, December 1994.

    [7] D. J. Petty, 'Recent Experiences in the Refurbishment of Large Generators', Cigre APi 1 Conference

    1996 - Sydney, No. 15, September 1996.

    [8] M. Liese, J. Ber, R. Gem and W. Schier, 'Life Extension Methods and Experiences with Turbine

    Generator Rehabilitation and Uprating', Cigr APi 1 1990 Paris Session, No. 11-104, August 1990.

    [9] T. R. Blackburn, R. C. Sheehy and B. T. Phung, 'Deterioration of Stator Bar Insulation: use of Phase-

    Resolved Partial Discharge Monitoring During Accelerated Ageing Tests', Cigre APi 1 Conference 1996 -

    Sydney, No.8

    , September 1996

    .

  • 8/7/2019 2nd pageprint

    50/52

    50

    Chapter:4

    Conclusion and future work

    Conclusion: From above it is Proved that different types of faults are occur due to the fatigue of

    machine component. The avoidance of these faults are necessary to maintain continuity of

    operation also to increase performance. These can be avoid by focusing on maintenance

    procedures & condition monitoring. The advantages are come up with reduction in

    maintenance cost which can be used for further development also better continuity will give

    rise in revenue

    Future Work:After referring various work done in this area the different faults & their detecting,diagnosis techniques are studied and try to find remedial solutions & improve the performance of

    machine

  • 8/7/2019 2nd pageprint

    51/52

    51

    Chapter : 5

    References

    [1] O. Gl and T. V. Tran, 'Stator End Winding Problems in Large Synchronous Generators andSome Remedies', ICEM - International Conference on Electrical Machines, Bruges - Belgium,

    August 2002.

    [2] G. C. Stone, Edward A. Boulter, Ian Culbert and Hussein Dhirani, 'Electrical Insulation for

    Rotating Machines Design, Evaluation, Aging, Testing, and Repair'. IEEE Press series on

    Power Engineering, Institute of Electrical and Electronics Engineers, 2004.

    [3] ESIPC - Electricity Supply Industry Planning Council, 'The South Australian Annual

    Planning Report - 2005', Executive Summary, June 2005.

    [4] EWBANK PREECE AUSTRALIA, 'Preliminary Study into Two-shifting Operation at

    Torrens Island Power Station',Consultancy report for SA Generation Corporation, March 1997.[5] 5. Denison ETSA Torrens Island Power Station, 'Ageing of Machines with Respect to

    Load or Field Current Cycling', CIGRE Working Group 11-01 Questionair 90-3, reply letter to

    the CIGRE Paimel 11 convernor, December 1992.

    [6] J. E. Timperley and J. R. Michalec, 'Estimating The Remaining Service Life of Asphalt-Mica

    Stator Insulation', IEEE Transactions on Energy Conversion, Vol. 9, No. 4, pp 686-694,

    December 1994.

    [7] D. J. Petty, 'Recent Experiences in The Refurbishment of Large Generators', Cigre APi 1

    Conference 1996 - Sydney, No. 15, September 1996.

    [8] M. Liese, J. Ber, R. Gem and W. Schier, 'Life Extension Methods and Experiences with

    Turbine Generator Rehabilitation and Uprating', Cigr APi 11990 Paris Session, No. 11-104,

    August 1990.

    [9] T. R. Blackburn, R. C. Sheehy and B. T. Phung, 'Deterioration of Stator Bar Insulation: use

    of Phase-Resolved Partial Discharge Monitoring During Accelerated Ageing Tests', Cigre APi 1

    Conference 1996 - Sydney, No. 8, September 1996.

    [10] T. Tran Optima Energy Torrens Island Power Station, 'TIPS 'B4' Generator Stator

    Complete Rewind Option Torrens Island Power Station', Departmential Letter, ETSA,December 1997.

  • 8/7/2019 2nd pageprint

    52/52

    [11] A. Nuttall - The Electricity Trust of South Australia, 'Metallurgical examination of

    Torrens Island Power Station Unit B2 Generator Stator Subconductors', MetallurgicalInvestigtion Report, report number MET\94\041, December 1994.