    AI DI AO DO Soft Type Runs Tag From To

    PLANT ROOM

    A CHILLED WATER PUMPS SECONDARY 4

    On/Off Command 4 2 Core 4 PUMPx-ONOF-CMD DDC Pump PaneBMS DDC sh

    potential fr

    Run Status 4 2 Core 4 PUMPx-RUN-STS Pump Panel DDC BMS DDC sh

    potential fr

    High current Alarm 0 4 - - - Pump VFD - BMS DDC sh

    Bypass Line Valve Control 0 4 Core 1 VLV-CTRL DDC Valve

    Actuator

    BMS DDC sh

    VFD Integration 4

    Secondary Pump's VFD Speed Feedback 4

    Secondary Pump's VFD Frequency 4

    Secondary Pump's VFD Current 4

    0 Secondary Pump's VFD Voltage 4

    1 Secondary Pump's VFD Power 4

    2 Secondary Pump's VFD Run Time 4

    3 BTU Meter (400mm) 1

    4 Su l Tem erature 15 Return Tem erature 16 Delta Tem erature 17 Flow Rate 18 Total Flow 19 Power 10 Ener 11 Chilled water common supply temp 1 1 2 Core 1 CHWS-TEMP Imm.Temp

    Sensor

    DDC Supply, Inst

    2 Chilled watercommon return Temp 1 1 2 Core 1 CHWR-TEMP Imm.Temp

    Sensor

    DDC Supply, Inst

    3 Outside Air Temperature Monitoring 1 2 Core 1 OD-TEMP

    -5 Integration of the Sec pump Controller 1 0 2 Core25 PUMP-CTRL-COMM DDC Pump

    Controller

    1) Supply, I

    Testing & C

    Modbus RS4

    2) Commun

    laying from

    integrator t

    6 Sec Pump Controller Common fault

    monitoring

    1 2 Core 1 SCHW-CTLR-FAULT SCHW Control DDC BMS DDC sh

    7 Sec Pump Controller Common On/Off

    Command

    1 2 Core 1 SCHW-CTLR-CMD DDC SCHW Cont BMS DDC sh

    PRESSURIZATION UNIT 2

    Unit run status 0 PU-RUN-STS Panel DDC BMS DDC sh

    potential fr

    l.

    1 AHU-VLV-STS Valve

    Actuator

    DDC BMS DDC sh

    Vdc signal

    for 0-

    HAIL'S Scop

    Bypass Line Valve Feedback 0 2 Core

    PARTICULARS QTY

    2 Core1

    (Daisy

    Chain)

    BTU-COMM DDC BTU

    2 Core1

    (Daisy

    Chain)

    VFD-COMM DDC Pump VFD 1) Supply, I

    Testing & C

    Modbus RS4Integrator.

    2) Commun

    laying from

    VFDs in dais

    3) VFD poin

    I/O DETAILS CABLE DETAILS

    1 OD T+RH Sens DDC Supply, Inst

    Supply, Inst

    and Commi

    Ultrasonic B

    4 Core 2

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    2/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Unit trip alarm 0 PU-TRIP-STS Panel DDC BMS DDC sh

    potential fr

    System pressure 0 4 Core 2 PU-PRES Water Pressur DDC Supply, Inst

    & Commiss

    Water Press

    AHU 99

    10

    On/Off Command 107 2 Core 107 AHU-ONOF-CMD DDC AHU Panel BMS DDC sh

    potential fr

    (N.O.)

    contact to A

    Run Status 107 2 Core 107 AHU-RUN-STS Air DPS DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    Auto Manual status 107 AHU-A/M-STS AHU Panel DDC BMS DDC sh

    potential fr

    Trip Status 107 AHU-TRIP-STS AHU Panel DDC BMS DDC sh

    potential fr

    Filter status 107 2 Core 107 AHU-FLTR-STS Air DPS DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    Supply Air Temperature Monitoring 107 2 Core 107 AHU-SA-TEMP Duct Temp

    Sensor

    DDC Supply, Inst

    & Commissi

    Duct Temp

    Return Air Temperature Monitoring 107 2 Core 107 AHU-RA-TEMP Duct Temp

    Sensor

    DDC Supply, Inst

    & Commissi

    Duct Temp

    Valve Modulation 107 4 Core 107 AHU-VLV-MOD DDC Valve

    Actuator

    BMS DDC sh

    VFD control Signal 107 2 Core 107 AHU-VFD-CTR DDC AHU VFD BMS DDC sh

    0 VFD modulation using diff press

    transmitter

    107 4 Core 107 AHU-DP Air DPT DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    1 VFD soft integration 107

    3 AHU's VFD S eed Feedback 1074 AHU's VFD Fre uenc 1075 AHU's VFD Current 107

    6 AHU's VFD Volta e 1077 AHU's VFD Power 1078 AHU's VFD Run Time 107

    FAHU 6

    Supply Air Temperature Monitoring 6 2 Core 6 FAHU-SA-TEMP Duct Temp DDC Supply, Inst

    Temperature After Heat Recovery 6 2 Core 6 FAHU-AHR-TEMP Duct Temp DDC Supply, Inst

    Exhaust Temperature before heat recovery 6 2 Core 6 FAHU-BHR-TEMP Duct Temp DDC Supply, Inst

    Ambient temperature Monitoring 6 2 Core 6 FAHU-AMB-TEMP Duct Temp DDC Supply, Inst

    Temperature After Heat wheel 6 2 Core 6 FAHU-AHW-TEMP Duct Temp DDC Supply, Inst

    4 Core 107

    2 Core1

    (Daisy

    Chain)

    VFD-COMM DDC AHU VFD 1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.

    2 Commun

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    3/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Supply Fan Run Status 6 2 Core 6 FAHU-SF-RUN Air DPS DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    Supply Fan Trip Status 6 2 Core 6 FAHU-SF-TRIP FAHU Panel DDC BMS DDC sh

    Exhaust Fan Run Status 6 2 Core 6 FAHU-EF-RUN Air DPS DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    Exhaust Fan Trip Status 6 2 Core 6 FAHU-EF-TRIP FAHU Panel DDC BMS DDC sh

    potential fr

    0 HW Motor Run Status 6 2 Core 6 FAHU-HW-RUN FAHU Panel DDC BMS DDC sh

    potential fr

    1 HW Motor Trip Status 6 2 Core 6 FAHU-HW-TRIP FAHU Panel DDC BMS DDC sh

    potential fr

    2 Filter before HW on Exhaust 6 2 Core 6 FAHU-HW-FLTR Air DPS DDC Supply, Inst

    3 Pre Filter Fresh Air 6 2 Core 6 FAHU-PR-FLTR Air DPS DDC Supply, Inst

    4 Bag Filter Fresh Air 6 2 Core 6 FAHU-BG-FLTR Air DPS DDC Supply, Inst

    5 VFAU Start/Stop 6 2 Core 6 FAHU-ONOF-CMD DDC FAHU Pane BMS DDC sh

    potential fr

    (N.O.)

    contact to A

    6 HOA Switch 6 2 Core 6 FAHU-A/M-STS FAHU Panel DDC BMS DDC sh

    potential fr

    7 AHU Trip on Fire Mode 0 FAHU-TRIP-STS FAHU Panel DDC BMS DDC sh

    potential fr

    contact fro

    8 Valve Modulation 6 4 Core 6 FAHU-VLV-MOD DDC Valve

    Actuator

    BMS DDC sh

    9 VFD control Signal 6 2 Core 6 FAHU-VFD-CTR DDC FAHU VFD BMS DDC sh

    0 VFD modulation using diff press

    transmitter

    6 4 Core 6 FAHU-DP Air DPT DDC Supply, Inst

    & Commissi

    Air Diff. Pre

    1 VFD soft integration 6

    7

    2 AHU's VFD Speed Feedback 73 AHU's VFD Frequency 74 AHU's VFD Current 75 AHU's VFD Voltage 76 AHU's VFD Power 77 AHU's VFD Run Time 7

    FANS

    A SMOKE EXTRACT FAN 1

    Common Damper open/close command 0 SEF-DMPR-CMD DDC Damper

    Actuator

    BMS DDC sh

    potential fr

    1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.

    2) Commun

    4 Core 1

    2 Core1

    (Daisy

    Chain)

    VFD-COMM DDC FAHU VFD

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    4/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Damper open status 0 SEF-DMPR-STS Fan Panel DDC BMS DDC sh

    potential fr

    `Auto' position of H/O/A switch 1 SEF-A/M-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan trip alarm 1 SEF-TRIP-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan Start/Stop Command 1 SEF-ONOF-CMD DDC Fan Panel BMS DDC sh

    potential fr

    (N.O.)

    contact to F

    Fan run status 1 SEF-RUN-STS Fan Panel DDC BMS DDC sh

    potential fr

    FA signal 1 2 Core 1 SEF-FIRE-STS Fan Panel

    FAS CR

    DDC BMS DDC sh

    potential fr

    STAIRCASE PRESSURIZATION FAN + PASS2+1

    Common Damper open/close command 0 SPFx-DMPR-CMD DDC Damper

    Actuator

    BMS DDC sh

    potential fr

    Damper open status 0 SPFx-DMPR-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan trip alarm 3 SPFx- Fan P DDC BMS DDC shall

    accept potential

    free (N.O.)

    contact from Fan

    Fan Panel sha Confirmed.Ok

    5 Fan Start/Stop Command (N.O.)

    contact to BMS DDC.

    Fan run status 3 SPFx- Fan P DDC BMS DDC shall

    accept potential

    Fan Panel

    shall provide

    VFD Control Signal 3 4 SPFx- DDC Fan VF BMS DDC shall

    provide 0-10 Vdc

    signal output for 0-

    Fan VFD shall

    accept 0-

    10Vdc signal

    -`Auto' position of H/O/A switch for Fire + Normal Sta 6 EXFx-A/M-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan trip alarm

    Fire Mode + Normal Mode

    6 EXFx-TRIP-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan Start/Stop CommandFire Mode + Normal Mode

    0 2 Core 6 EXFx-ONOF-CMD DDC Fan Panel BMS DDC shpotential fr

    Fan run status

    Fire Mode + Normal Mode

    12 2 Core 12 EXFx-RUN-STS Fan Panel DDC BMS DDC sh

    potential fr

    FA signal 0 2 Core 6 EXFx-FIRE-STS Fan Panel DDC BMS DDC sh

    potential fr

    (N.O.)

    EXTRACT FAN (SINGLE SPEED) 6

    2 Core Confirmed.

    Confirmed. To be

    4 Core 1

    4 Core 1

    4 Core 4

    4 Core 6

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    5/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Common Damper open/close sommand 0 EXFx-DMPR-CMD DDC Damper

    Actuator

    BMS DDC sh

    potential fr

    Damper open status 0 EXFx-DMPR-STS Fan Panel DDC BMS DDC sh

    potential fr

    `Auto' position of H/O/A switch 6 EXFx-A/M-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan trip alarm 6 EXFx-TRIP-STS Fan Panel DDC BMS DDC sh

    potential fr

    Fan Start/Stop Command 0 2 Core 6 EXFx-ONOF-CMD DDC Fan Panel BMS DDC sh

    potential fr

    Fan run status 3 2 Core 6 EXFx-RUN-STS Fan Panel DDC BMS DDC sh

    potential fr

    FA signal 0 2 Core 4 EXFx-FIRE-STS Fan Panel DDC BMS DDC sh

    potential fr

    contact from

    I LIFT 14

    Floor Position 14

    Door fully Closed Signal 14

    Status of Landing Floor (Open/Close) 14

    Inspection Status (Normal/Maintenance) 14

    Emergency Stop Status 14

    Fault Indication 14

    Fireman Switch Status 14

    Lift Auto/Manual Status 14

    Lift Run Status 14

    V FCU FOR COMMON AREAS (Max. 10

    Points per FCU)

    100 1000 - - - - - FCUs Points

    into BMS

    software.

    V BTU METER VIA M-BUS 98

    Supply Temperature 98

    Return Temperature 98

    Delta Temperature 98

    Flow Rate 98

    Total Flow 98

    Power 98

    Energy 98

    VI PUBLIC HEALTH ENGG.

    A TRANSFER PUMP 4

    H/O/A Switch in auto position 4 TX-Px-A/M-STS Pump Panel DDC BMS DDC sh

    potential fr

    4 Core 6

    4 Core 6

    1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.

    2) Commun

    laying from

    Lifts in dais

    3) Lift point

    into BMS So

    2 Core1

    (Daisy

    Chain)

    LIFT-COMM DDC LIFT

    4 Core 4

    Supply, Inst

    and Commi

    Ultrasonic B

    2 Core1

    (Daisy

    Chain)

    BTU-COMM DDC BTU

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    6/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Run Status 4 TX-Px-RUN-STS Pump Panel DDC BMS DDC sh

    potential fr

    Trip Status 4 TX-Px-TRIP-STS Pump Panel DDC BMS DDC sh

    potential fr

    On/Off Command 4 TX-Px-ONOF-CMD DDC Pump PaneBMS DDC sh

    potential fr(N.O.)

    contact to P

    SUMP PUMP 6

    Unit Fault status 6 SUMP-Px-FAULT Pump Panel DDC BMS DDC sh

    potential fr

    Run Status 6 SUMP-Px-RUN-STS Pump Panel DDC BMS DDC sh

    potential fr

    Auto Manual Status 6 2 Core 6 SUMP-Px-A/M-STS Pump Panel DDC BMS DDC sh

    potential fr

    BOOSTER PUMP 6

    H/O/A Switch in auto position 6 BSTR-Px-A/M-STS Pump Panel DDC BMS DDC sh

    potential fr

    Trip 6 BSTR-Px-TRIP-STS Pump Panel DDC BMS DDC sh

    potential fr

    Run Status 0 BSTR-Px-RUN-STS Pump Panel DDC BMS DDC sh

    potential fr

    On/Off Command 0 BSTR-Px-ONOF-CM DDC Pump PaneBMS DDC sh

    potential fr

    contact to P

    VFD soft integration 6Pump VFD Speed Feedback 6Pump VFD Frequency 6Pump VFD Current 6Pump VFD Voltage 6

    0 Pump VFD Power 61 Pump VFD Run Time 6

    WATER TANK 1

    6

    Tank Level 6

    High/Low Level Alarm 12

    Water meter 13 13 2 Core1 daisy MTRx-FLOW Flow Meter DDC BMS DDC sh

    Vdc signal

    VII FIRE FIGHTING SYSTEM

    A FIRE FIGHTING PUMP 1

    Pump auto-manual status 1 FFP-A/M-STS Pump Panel DDC BMS DDC sh

    potential fr

    6

    4 Core 6

    4 Core 6

    1

    (Daisy

    Chain)

    4 Core 4

    4 Core

    2 Core 1 FIRE-TANK-LVL Level Sensor DDC Supply and

    Level

    VFD-COMM DDC Pump VFD 1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.

    2) Commun

    2 Core

    4 Core 1

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    7/11

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    8/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    ON/OFF Status of each main outgoing breaker 4 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh

    potential fr

    Trip alarm indication of main outgoing breaker 1 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh

    potential fr

    Breaker Trip Command 1 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh

    potential fr

    Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh

    potential fr

    LV PANEL 2 1

    Incoming breaker

    ON/OFF Status of each main incoming breaker 1 LV-P2-IC-ONOF-STS Panel DDC BMS DDC sh

    potential fr

    Trip alarm indication of main incoming breaker 1 LV-P2-IC-TRIP-STS Panel DDC BMS DDC sh

    potential fr

    Breaker Trip Command 1 2 Core 1 LV-P2-IC-TRIP-CMD DDC Panel BMS DDC sh

    potential fr

    Outgoing breaker 4

    ON/OFF Status of each main outgoing breaker 4 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh

    potential fr

    Trip alarm indication of main outgoing breaker 1 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh

    potential fr

    Breaker Trip Command 1 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh

    potential fr

    Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh

    potential fr

    LV PANEL 3 1

    Incoming breaker

    ON/OFF Status of each main incoming breaker 1 LV-P2-IC-ONOF-STS Panel DDC BMS DDC sh

    Trip alarm indication of main incoming breaker 1 LV-P2-IC-TRIP-STS Panel DDC BMS DDC sh

    Breaker Trip Command 1 2 Core 1 LV-P2-IC-TRIP-CMD DDC Panel BMS DDC sh

    Outgoing breaker 5

    ON/OFF Status of each main outgoing breaker 5 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh

    Trip alarm indication of main outgoing breaker 0 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh

    Breaker Trip Command 0 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh

    Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh

    ESMDB 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    Outgoing breaker 6

    ON/OFF Status of each main incoming breaker 6 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC - B 1

    4 Core 4

    4 Core 4

    4 Core 1

    4 Core 4

    4 Core 1

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    9/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    EMCC - B 1

    Incoming breaker 1ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB - B 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC - PUMP 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC SUMP PUMP 2

    Incoming breaker 2

    ON/OFF Status of each main incoming breaker 2 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC ETS 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB - G 1Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC - R1 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC - R2 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC shpotential fr

    SMDB UR 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB RT 1

    Incoming breaker 1

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    10/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    EMCC - R 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC shpotential fr

    SMDB UPS 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB UPS II 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB GYM 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB F & B 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    SMDB CF1 & CF2 2Incoming breaker 2

    ON/OFF Status of each main incoming breaker 2 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    MCC FF 1

    Incoming breaker 1

    ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    FLOOR SMDBs 28

    Incoming breaker 28

    ON/OFF Status of each main incoming breaker 28 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    TENANT SMDBs 73

    Incoming breaker 73

    ON/OFF Status of each main incoming breaker 73 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh

    potential fr

    TRANSFORMERS 3

  • 8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013

    11/11

    AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS

    Signals for monitoring 3 2 Core 3 TX-SINGx-MTR Panel DDC BMS DDC sh

    Signals for monitoring 16 4 Core 8 TX-SINGx-STS Panel DDC BMS DDC sh

    potential fr

    O HT PANELS/BREAKERS 4Signals for monitoring 3 2 Core 3 HT-SINGx-MTR Panel DDC BMS DDC sh

    Signals for monitoring 32 4 Core 16 HT-SINGx-STS Panel DDC BMS DDC sh

    potential fr

    LOAD MANAGERS INTEGRATION ENERGY 91

    Average Current 91Voltage 91Kilowatt 91Run hour 91

    Power Factor 91Forward Active Energy 91Power Factor Average 91Line to Line Voltage Average 91Line to Line Neutral Average 91

    0 Frequency 91

    Q LIGHTING CONTROL 64

    Circuit open/close status 64 LP-CKT-ONOF-STS Panel DDC BMS DDC sh

    Circuit open/close command 64 LP-CKT-ONOF-CMD DDC Panel BMS DDC sh

    R AIRCRAFT WARNING LIGHT 1

    Circuit on/off status 1 AL-CKT-ONOF-STS Panel DDC BMS DDC sh

    Circuit trip alarm 1 AL-CKT-TRIP-STS Panel DDC BMS DDC sh

    PA/BGM SYSTEM 1

    Panel power ON status 1 BMG-CKT-ONOF-ST Panel DDC BMS DDC sh

    Panel fault status 1 BMG-CKT-FLT-STS Panel DDC BMS DDC sh

    UPS 2

    O/P Voltage - R 2O/P Voltage - Y 2O/P Voltage - B 2O/P Current - R 2O/P Current - Y 2O/P Current - Y 2

    Battery Voltage 2Battery Charge Remaining 2Frequency 2

    0 Alarm Status 2

    X CCTV SYSTEM INTEGRATION DVM Interfa

    FIRE ALARM SYSTEM INTEGRATION 3200 Modbus Int

    I ACCESS CONTROL SYSTEM Tema Inter

    TOTAL 382 1092 229 205 6740

    4 Core 1

    4 Core 1

    1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.2) Commun

    laying from

    EMs in daisy

    3) EM point

    into BMS So

    4 Core 64

    2 Core1

    (Daisy

    Chain)

    EM-COMM DDC Load

    Manager

    2 Core1

    (Daisy

    Chain)

    UPS-COMM DDC UPS 1) Supply, I

    Testing & C

    Modbus RS4

    Integrator.

    2) Commun

    laying fromUPSs in dais

    3) UPS poin

    into BMS So