8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
1/11
AI DI AO DO Soft Type Runs Tag From To
PLANT ROOM
A CHILLED WATER PUMPS SECONDARY 4
On/Off Command 4 2 Core 4 PUMPx-ONOF-CMD DDC Pump PaneBMS DDC sh
potential fr
Run Status 4 2 Core 4 PUMPx-RUN-STS Pump Panel DDC BMS DDC sh
potential fr
High current Alarm 0 4 - - - Pump VFD - BMS DDC sh
Bypass Line Valve Control 0 4 Core 1 VLV-CTRL DDC Valve
Actuator
BMS DDC sh
VFD Integration 4
Secondary Pump's VFD Speed Feedback 4
Secondary Pump's VFD Frequency 4
Secondary Pump's VFD Current 4
0 Secondary Pump's VFD Voltage 4
1 Secondary Pump's VFD Power 4
2 Secondary Pump's VFD Run Time 4
3 BTU Meter (400mm) 1
4 Su l Tem erature 15 Return Tem erature 16 Delta Tem erature 17 Flow Rate 18 Total Flow 19 Power 10 Ener 11 Chilled water common supply temp 1 1 2 Core 1 CHWS-TEMP Imm.Temp
Sensor
DDC Supply, Inst
2 Chilled watercommon return Temp 1 1 2 Core 1 CHWR-TEMP Imm.Temp
Sensor
DDC Supply, Inst
3 Outside Air Temperature Monitoring 1 2 Core 1 OD-TEMP
-5 Integration of the Sec pump Controller 1 0 2 Core25 PUMP-CTRL-COMM DDC Pump
Controller
1) Supply, I
Testing & C
Modbus RS4
2) Commun
laying from
integrator t
6 Sec Pump Controller Common fault
monitoring
1 2 Core 1 SCHW-CTLR-FAULT SCHW Control DDC BMS DDC sh
7 Sec Pump Controller Common On/Off
Command
1 2 Core 1 SCHW-CTLR-CMD DDC SCHW Cont BMS DDC sh
PRESSURIZATION UNIT 2
Unit run status 0 PU-RUN-STS Panel DDC BMS DDC sh
potential fr
l.
1 AHU-VLV-STS Valve
Actuator
DDC BMS DDC sh
Vdc signal
for 0-
HAIL'S Scop
Bypass Line Valve Feedback 0 2 Core
PARTICULARS QTY
2 Core1
(Daisy
Chain)
BTU-COMM DDC BTU
2 Core1
(Daisy
Chain)
VFD-COMM DDC Pump VFD 1) Supply, I
Testing & C
Modbus RS4Integrator.
2) Commun
laying from
VFDs in dais
3) VFD poin
I/O DETAILS CABLE DETAILS
1 OD T+RH Sens DDC Supply, Inst
Supply, Inst
and Commi
Ultrasonic B
4 Core 2
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
2/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Unit trip alarm 0 PU-TRIP-STS Panel DDC BMS DDC sh
potential fr
System pressure 0 4 Core 2 PU-PRES Water Pressur DDC Supply, Inst
& Commiss
Water Press
AHU 99
10
On/Off Command 107 2 Core 107 AHU-ONOF-CMD DDC AHU Panel BMS DDC sh
potential fr
(N.O.)
contact to A
Run Status 107 2 Core 107 AHU-RUN-STS Air DPS DDC Supply, Inst
& Commissi
Air Diff. Pre
Auto Manual status 107 AHU-A/M-STS AHU Panel DDC BMS DDC sh
potential fr
Trip Status 107 AHU-TRIP-STS AHU Panel DDC BMS DDC sh
potential fr
Filter status 107 2 Core 107 AHU-FLTR-STS Air DPS DDC Supply, Inst
& Commissi
Air Diff. Pre
Supply Air Temperature Monitoring 107 2 Core 107 AHU-SA-TEMP Duct Temp
Sensor
DDC Supply, Inst
& Commissi
Duct Temp
Return Air Temperature Monitoring 107 2 Core 107 AHU-RA-TEMP Duct Temp
Sensor
DDC Supply, Inst
& Commissi
Duct Temp
Valve Modulation 107 4 Core 107 AHU-VLV-MOD DDC Valve
Actuator
BMS DDC sh
VFD control Signal 107 2 Core 107 AHU-VFD-CTR DDC AHU VFD BMS DDC sh
0 VFD modulation using diff press
transmitter
107 4 Core 107 AHU-DP Air DPT DDC Supply, Inst
& Commissi
Air Diff. Pre
1 VFD soft integration 107
3 AHU's VFD S eed Feedback 1074 AHU's VFD Fre uenc 1075 AHU's VFD Current 107
6 AHU's VFD Volta e 1077 AHU's VFD Power 1078 AHU's VFD Run Time 107
FAHU 6
Supply Air Temperature Monitoring 6 2 Core 6 FAHU-SA-TEMP Duct Temp DDC Supply, Inst
Temperature After Heat Recovery 6 2 Core 6 FAHU-AHR-TEMP Duct Temp DDC Supply, Inst
Exhaust Temperature before heat recovery 6 2 Core 6 FAHU-BHR-TEMP Duct Temp DDC Supply, Inst
Ambient temperature Monitoring 6 2 Core 6 FAHU-AMB-TEMP Duct Temp DDC Supply, Inst
Temperature After Heat wheel 6 2 Core 6 FAHU-AHW-TEMP Duct Temp DDC Supply, Inst
4 Core 107
2 Core1
(Daisy
Chain)
VFD-COMM DDC AHU VFD 1) Supply, I
Testing & C
Modbus RS4
Integrator.
2 Commun
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
3/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Supply Fan Run Status 6 2 Core 6 FAHU-SF-RUN Air DPS DDC Supply, Inst
& Commissi
Air Diff. Pre
Supply Fan Trip Status 6 2 Core 6 FAHU-SF-TRIP FAHU Panel DDC BMS DDC sh
Exhaust Fan Run Status 6 2 Core 6 FAHU-EF-RUN Air DPS DDC Supply, Inst
& Commissi
Air Diff. Pre
Exhaust Fan Trip Status 6 2 Core 6 FAHU-EF-TRIP FAHU Panel DDC BMS DDC sh
potential fr
0 HW Motor Run Status 6 2 Core 6 FAHU-HW-RUN FAHU Panel DDC BMS DDC sh
potential fr
1 HW Motor Trip Status 6 2 Core 6 FAHU-HW-TRIP FAHU Panel DDC BMS DDC sh
potential fr
2 Filter before HW on Exhaust 6 2 Core 6 FAHU-HW-FLTR Air DPS DDC Supply, Inst
3 Pre Filter Fresh Air 6 2 Core 6 FAHU-PR-FLTR Air DPS DDC Supply, Inst
4 Bag Filter Fresh Air 6 2 Core 6 FAHU-BG-FLTR Air DPS DDC Supply, Inst
5 VFAU Start/Stop 6 2 Core 6 FAHU-ONOF-CMD DDC FAHU Pane BMS DDC sh
potential fr
(N.O.)
contact to A
6 HOA Switch 6 2 Core 6 FAHU-A/M-STS FAHU Panel DDC BMS DDC sh
potential fr
7 AHU Trip on Fire Mode 0 FAHU-TRIP-STS FAHU Panel DDC BMS DDC sh
potential fr
contact fro
8 Valve Modulation 6 4 Core 6 FAHU-VLV-MOD DDC Valve
Actuator
BMS DDC sh
9 VFD control Signal 6 2 Core 6 FAHU-VFD-CTR DDC FAHU VFD BMS DDC sh
0 VFD modulation using diff press
transmitter
6 4 Core 6 FAHU-DP Air DPT DDC Supply, Inst
& Commissi
Air Diff. Pre
1 VFD soft integration 6
7
2 AHU's VFD Speed Feedback 73 AHU's VFD Frequency 74 AHU's VFD Current 75 AHU's VFD Voltage 76 AHU's VFD Power 77 AHU's VFD Run Time 7
FANS
A SMOKE EXTRACT FAN 1
Common Damper open/close command 0 SEF-DMPR-CMD DDC Damper
Actuator
BMS DDC sh
potential fr
1) Supply, I
Testing & C
Modbus RS4
Integrator.
2) Commun
4 Core 1
2 Core1
(Daisy
Chain)
VFD-COMM DDC FAHU VFD
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
4/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Damper open status 0 SEF-DMPR-STS Fan Panel DDC BMS DDC sh
potential fr
`Auto' position of H/O/A switch 1 SEF-A/M-STS Fan Panel DDC BMS DDC sh
potential fr
Fan trip alarm 1 SEF-TRIP-STS Fan Panel DDC BMS DDC sh
potential fr
Fan Start/Stop Command 1 SEF-ONOF-CMD DDC Fan Panel BMS DDC sh
potential fr
(N.O.)
contact to F
Fan run status 1 SEF-RUN-STS Fan Panel DDC BMS DDC sh
potential fr
FA signal 1 2 Core 1 SEF-FIRE-STS Fan Panel
FAS CR
DDC BMS DDC sh
potential fr
STAIRCASE PRESSURIZATION FAN + PASS2+1
Common Damper open/close command 0 SPFx-DMPR-CMD DDC Damper
Actuator
BMS DDC sh
potential fr
Damper open status 0 SPFx-DMPR-STS Fan Panel DDC BMS DDC sh
potential fr
Fan trip alarm 3 SPFx- Fan P DDC BMS DDC shall
accept potential
free (N.O.)
contact from Fan
Fan Panel sha Confirmed.Ok
5 Fan Start/Stop Command (N.O.)
contact to BMS DDC.
Fan run status 3 SPFx- Fan P DDC BMS DDC shall
accept potential
Fan Panel
shall provide
VFD Control Signal 3 4 SPFx- DDC Fan VF BMS DDC shall
provide 0-10 Vdc
signal output for 0-
Fan VFD shall
accept 0-
10Vdc signal
-`Auto' position of H/O/A switch for Fire + Normal Sta 6 EXFx-A/M-STS Fan Panel DDC BMS DDC sh
potential fr
Fan trip alarm
Fire Mode + Normal Mode
6 EXFx-TRIP-STS Fan Panel DDC BMS DDC sh
potential fr
Fan Start/Stop CommandFire Mode + Normal Mode
0 2 Core 6 EXFx-ONOF-CMD DDC Fan Panel BMS DDC shpotential fr
Fan run status
Fire Mode + Normal Mode
12 2 Core 12 EXFx-RUN-STS Fan Panel DDC BMS DDC sh
potential fr
FA signal 0 2 Core 6 EXFx-FIRE-STS Fan Panel DDC BMS DDC sh
potential fr
(N.O.)
EXTRACT FAN (SINGLE SPEED) 6
2 Core Confirmed.
Confirmed. To be
4 Core 1
4 Core 1
4 Core 4
4 Core 6
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
5/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Common Damper open/close sommand 0 EXFx-DMPR-CMD DDC Damper
Actuator
BMS DDC sh
potential fr
Damper open status 0 EXFx-DMPR-STS Fan Panel DDC BMS DDC sh
potential fr
`Auto' position of H/O/A switch 6 EXFx-A/M-STS Fan Panel DDC BMS DDC sh
potential fr
Fan trip alarm 6 EXFx-TRIP-STS Fan Panel DDC BMS DDC sh
potential fr
Fan Start/Stop Command 0 2 Core 6 EXFx-ONOF-CMD DDC Fan Panel BMS DDC sh
potential fr
Fan run status 3 2 Core 6 EXFx-RUN-STS Fan Panel DDC BMS DDC sh
potential fr
FA signal 0 2 Core 4 EXFx-FIRE-STS Fan Panel DDC BMS DDC sh
potential fr
contact from
I LIFT 14
Floor Position 14
Door fully Closed Signal 14
Status of Landing Floor (Open/Close) 14
Inspection Status (Normal/Maintenance) 14
Emergency Stop Status 14
Fault Indication 14
Fireman Switch Status 14
Lift Auto/Manual Status 14
Lift Run Status 14
V FCU FOR COMMON AREAS (Max. 10
Points per FCU)
100 1000 - - - - - FCUs Points
into BMS
software.
V BTU METER VIA M-BUS 98
Supply Temperature 98
Return Temperature 98
Delta Temperature 98
Flow Rate 98
Total Flow 98
Power 98
Energy 98
VI PUBLIC HEALTH ENGG.
A TRANSFER PUMP 4
H/O/A Switch in auto position 4 TX-Px-A/M-STS Pump Panel DDC BMS DDC sh
potential fr
4 Core 6
4 Core 6
1) Supply, I
Testing & C
Modbus RS4
Integrator.
2) Commun
laying from
Lifts in dais
3) Lift point
into BMS So
2 Core1
(Daisy
Chain)
LIFT-COMM DDC LIFT
4 Core 4
Supply, Inst
and Commi
Ultrasonic B
2 Core1
(Daisy
Chain)
BTU-COMM DDC BTU
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
6/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Run Status 4 TX-Px-RUN-STS Pump Panel DDC BMS DDC sh
potential fr
Trip Status 4 TX-Px-TRIP-STS Pump Panel DDC BMS DDC sh
potential fr
On/Off Command 4 TX-Px-ONOF-CMD DDC Pump PaneBMS DDC sh
potential fr(N.O.)
contact to P
SUMP PUMP 6
Unit Fault status 6 SUMP-Px-FAULT Pump Panel DDC BMS DDC sh
potential fr
Run Status 6 SUMP-Px-RUN-STS Pump Panel DDC BMS DDC sh
potential fr
Auto Manual Status 6 2 Core 6 SUMP-Px-A/M-STS Pump Panel DDC BMS DDC sh
potential fr
BOOSTER PUMP 6
H/O/A Switch in auto position 6 BSTR-Px-A/M-STS Pump Panel DDC BMS DDC sh
potential fr
Trip 6 BSTR-Px-TRIP-STS Pump Panel DDC BMS DDC sh
potential fr
Run Status 0 BSTR-Px-RUN-STS Pump Panel DDC BMS DDC sh
potential fr
On/Off Command 0 BSTR-Px-ONOF-CM DDC Pump PaneBMS DDC sh
potential fr
contact to P
VFD soft integration 6Pump VFD Speed Feedback 6Pump VFD Frequency 6Pump VFD Current 6Pump VFD Voltage 6
0 Pump VFD Power 61 Pump VFD Run Time 6
WATER TANK 1
6
Tank Level 6
High/Low Level Alarm 12
Water meter 13 13 2 Core1 daisy MTRx-FLOW Flow Meter DDC BMS DDC sh
Vdc signal
VII FIRE FIGHTING SYSTEM
A FIRE FIGHTING PUMP 1
Pump auto-manual status 1 FFP-A/M-STS Pump Panel DDC BMS DDC sh
potential fr
6
4 Core 6
4 Core 6
1
(Daisy
Chain)
4 Core 4
4 Core
2 Core 1 FIRE-TANK-LVL Level Sensor DDC Supply and
Level
VFD-COMM DDC Pump VFD 1) Supply, I
Testing & C
Modbus RS4
Integrator.
2) Commun
2 Core
4 Core 1
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
7/11
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
8/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
ON/OFF Status of each main outgoing breaker 4 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh
potential fr
Trip alarm indication of main outgoing breaker 1 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh
potential fr
Breaker Trip Command 1 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh
potential fr
Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh
potential fr
LV PANEL 2 1
Incoming breaker
ON/OFF Status of each main incoming breaker 1 LV-P2-IC-ONOF-STS Panel DDC BMS DDC sh
potential fr
Trip alarm indication of main incoming breaker 1 LV-P2-IC-TRIP-STS Panel DDC BMS DDC sh
potential fr
Breaker Trip Command 1 2 Core 1 LV-P2-IC-TRIP-CMD DDC Panel BMS DDC sh
potential fr
Outgoing breaker 4
ON/OFF Status of each main outgoing breaker 4 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh
potential fr
Trip alarm indication of main outgoing breaker 1 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh
potential fr
Breaker Trip Command 1 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh
potential fr
Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh
potential fr
LV PANEL 3 1
Incoming breaker
ON/OFF Status of each main incoming breaker 1 LV-P2-IC-ONOF-STS Panel DDC BMS DDC sh
Trip alarm indication of main incoming breaker 1 LV-P2-IC-TRIP-STS Panel DDC BMS DDC sh
Breaker Trip Command 1 2 Core 1 LV-P2-IC-TRIP-CMD DDC Panel BMS DDC sh
Outgoing breaker 5
ON/OFF Status of each main outgoing breaker 5 LV-P1-OGx-ONOF-S Panel DDC BMS DDC sh
Trip alarm indication of main outgoing breaker 0 LV-P1-OGx-TRIP-S Panel DDC BMS DDC sh
Breaker Trip Command 0 2 Core 4 LV-P1-OGx-TRIP-C DDC Panel BMS DDC sh
Fire Suppression System 1 2 Core 1 FIRE-SUP-SYS1-STS Fire Panel DDC BMS DDC sh
ESMDB 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
Outgoing breaker 6
ON/OFF Status of each main incoming breaker 6 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC - B 1
4 Core 4
4 Core 4
4 Core 1
4 Core 4
4 Core 1
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
9/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
EMCC - B 1
Incoming breaker 1ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB - B 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC - PUMP 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC SUMP PUMP 2
Incoming breaker 2
ON/OFF Status of each main incoming breaker 2 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC ETS 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB - G 1Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC - R1 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC - R2 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC shpotential fr
SMDB UR 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB RT 1
Incoming breaker 1
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
10/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
EMCC - R 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC shpotential fr
SMDB UPS 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB UPS II 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB GYM 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB F & B 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
SMDB CF1 & CF2 2Incoming breaker 2
ON/OFF Status of each main incoming breaker 2 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
MCC FF 1
Incoming breaker 1
ON/OFF Status of each main incoming breaker 1 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
FLOOR SMDBs 28
Incoming breaker 28
ON/OFF Status of each main incoming breaker 28 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
TENANT SMDBs 73
Incoming breaker 73
ON/OFF Status of each main incoming breaker 73 2 Core 1 ESMDB-IC-ONOF-ST Panel DDC BMS DDC sh
potential fr
TRANSFORMERS 3
8/13/2019 (209743174) Response2 to IO Summary -Site Meeting 06 02 2013
11/11
AI DI AO DO Soft Type Runs Tag From Tol. HAIL'S ScopPARTICULARS QTY I/O DETAILS CABLE DETAILS
Signals for monitoring 3 2 Core 3 TX-SINGx-MTR Panel DDC BMS DDC sh
Signals for monitoring 16 4 Core 8 TX-SINGx-STS Panel DDC BMS DDC sh
potential fr
O HT PANELS/BREAKERS 4Signals for monitoring 3 2 Core 3 HT-SINGx-MTR Panel DDC BMS DDC sh
Signals for monitoring 32 4 Core 16 HT-SINGx-STS Panel DDC BMS DDC sh
potential fr
LOAD MANAGERS INTEGRATION ENERGY 91
Average Current 91Voltage 91Kilowatt 91Run hour 91
Power Factor 91Forward Active Energy 91Power Factor Average 91Line to Line Voltage Average 91Line to Line Neutral Average 91
0 Frequency 91
Q LIGHTING CONTROL 64
Circuit open/close status 64 LP-CKT-ONOF-STS Panel DDC BMS DDC sh
Circuit open/close command 64 LP-CKT-ONOF-CMD DDC Panel BMS DDC sh
R AIRCRAFT WARNING LIGHT 1
Circuit on/off status 1 AL-CKT-ONOF-STS Panel DDC BMS DDC sh
Circuit trip alarm 1 AL-CKT-TRIP-STS Panel DDC BMS DDC sh
PA/BGM SYSTEM 1
Panel power ON status 1 BMG-CKT-ONOF-ST Panel DDC BMS DDC sh
Panel fault status 1 BMG-CKT-FLT-STS Panel DDC BMS DDC sh
UPS 2
O/P Voltage - R 2O/P Voltage - Y 2O/P Voltage - B 2O/P Current - R 2O/P Current - Y 2O/P Current - Y 2
Battery Voltage 2Battery Charge Remaining 2Frequency 2
0 Alarm Status 2
X CCTV SYSTEM INTEGRATION DVM Interfa
FIRE ALARM SYSTEM INTEGRATION 3200 Modbus Int
I ACCESS CONTROL SYSTEM Tema Inter
TOTAL 382 1092 229 205 6740
4 Core 1
4 Core 1
1) Supply, I
Testing & C
Modbus RS4
Integrator.2) Commun
laying from
EMs in daisy
3) EM point
into BMS So
4 Core 64
2 Core1
(Daisy
Chain)
EM-COMM DDC Load
Manager
2 Core1
(Daisy
Chain)
UPS-COMM DDC UPS 1) Supply, I
Testing & C
Modbus RS4
Integrator.
2) Commun
laying fromUPSs in dais
3) UPS poin
into BMS So