Melowind 50 MW Wind Farm 150 kV UTE SUBSTATION 00 04-06-2012 MAB RP HLS FOR INQUIRY Index Date Issued Checked Released Details of Revision EPC Contractor Project MELOWIND Client ESTRELLADA Status (Stamp) Project KKS Code MELOWIND ___ Date Name Format A4 Scale n/a Handling Instr. CONFIDENTIAL Issued 04-06-2012 MAB Title Checked 04-06-2012 RP Released 04-06-2012 HLS 150 kV UTE SUBSTATION Ref.No. 000 Originator SSO Document Code Doc. Part No. of Appendix Rev Sheet(s) 214486-EL-DS-0-00037 0 n/a 00 31 The reproduction, transmission or use of this document or his contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights by patented grant or registration of a utility model or design, are reserved. [Only to use in case of supplier information]

150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

  • Upload
    others

  • View
    33

  • Download
    2

Embed Size (px)

Citation preview

Page 1: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

Melowind

50 MW Wind Farm

150 kV UTE SUBSTATION

00 04-06-2012 MAB RP HLS FOR INQUIRY

Index Date Issued Checked Released Details of Revision

EPC Contractor

Project

MELOWIND

Client

ESTRELLADA

Status (Stamp)

Project KKS Code

MELOWIND ___

Date Name Format A4 Scale n/a Handling Instr. CONFIDENTIAL

Issued 04-06-2012 MAB Title

Checked 04-06-2012 RP

Released 04-06-2012 HLS 150 kV UTE SUBSTATION

Ref.No. 000

Originator SSO

Document Code Doc. Part No. of Appendix Rev Sheet(s)

214486-EL-DS-0-00037 0 n/a 00 31

The reproduction, transmission or use of this document or his contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights by patented grant or registration of a utility model or design, are reserved.

[Only to use in case of supplier information]

Page 2: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 2 / 32 Melowind

150 kV UTE SUBSTATION

Index

Page 3: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 3 / 32 Melowind

150 kV UTE SUBSTATION

1. OBJECT ...................................................................................................................5

2. BASIC DESIGN DATA .............................................................................................6

2.1. Site Conditions .....................................................................................................6

2.2. Operation Voltages...............................................................................................6

3. SCOPE OF SUPPLY ................................................................................................7

3.1. Basic and Detailed Engineering..........................................................................7

3.1.1. Equipment .........................................................................................................7

3.1.1.1. Melowind Position...........................................................................................7

3.1.1.2. Melo Position ...................................................................................................8

3.1.1.3. Treinta y Tres Position....................................................................................8

3.1.1.4. Tie Breaker.......................................................................................................9

3.1.1.5. 150 kV Busbar Voltage Metering....................................................................9

3.1.1.6. UPS, DC System and Diesel Generator .........................................................9

3.1.1.7. Control, Protection and Communication.......................................................9

3.1.1.8. Hardware ........................................................................................................10

3.2. Services...............................................................................................................11

3.2.1. Erection............................................................................................................11

3.2.2. Auxiliary Services Feeding ............................................................................11

3.2.3. Earthing ...........................................................................................................12

3.2.4. Lighting............................................................................................................12

3.2.5. Civil Works.......................................................................................................12

3.2.6. Commissioning ...............................................................................................12

3.2.7. Spare parts for the Commissioning ..............................................................13

3.2.8. Substation Legalization Project.....................................................................13

3.2.9. Tests and Inspections ....................................................................................13

3.2.10. Transport and Intermediate Storage .............................................................13

Page 4: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 4 / 32 Melowind

150 kV UTE SUBSTATION

3.2.11. Documentation ................................................................................................13

3.3. Limits of Supply..................................................................................................13

3.4. Exclusions ..........................................................................................................14

4. TENDER PROCESS...............................................................................................15

5. APPLICABLE CODES AND STANDARDS ...........................................................16

5.1. General ................................................................................................................16

5.2. Codes & Standards ............................................................................................16

6. DESCRIPTION AND SUPPLY SPECIFICATION...................................................17

6.1. Equipment Characteristics ................................................................................17

6.2. Circuit Breaker (52L) ..........................................................................................17

6.3. Line Disconnecting Switch & Earthing Switch (89L and 89T)) .......................17

6.4. Current Transformers (CTs) ..............................................................................18

6.5. Voltage Transformers (VTs) ..............................................................................18

6.6. Surge Arresters ..................................................................................................18

6.7. Protection System..............................................................................................19

6.8. Control System...................................................................................................19

6.9. Communication System.....................................................................................20

6.10. Metering System.................................................................................................20

6.11. Signals.................................................................................................................22

6.12. Painting and Surface coatings ..........................................................................22

7. TEST AND INSPECTIONS.....................................................................................23

8. TECHNICAL GUARANTIES...................................................................................24

9. TECHNICAL DOCUMENTATION ..........................................................................25

10. 150kV UTE SUBSTATION DATA SHEET .............................................................26

11. REFERENCE DOCUMENTS..................................................................................32

Page 5: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 5 / 32 Melowind

150 kV UTE SUBSTATION

1. OBJECT As part of the Melowind project, the UTE grid in 150 kV needs to be upgraded in order to be able to evacuate the generated power without affecting the electric system and service quality for the grid and other users. UTE has described in the document “Procedimiento de Compra No. K43037, Anteproyecto de Conexión”, that it is required to build a new substation at the Melowind site, to be connected in the existing 150 kV overhead line Treinta y Tres – Melo. This new substation will provide the connection point for Melowind and will complete the interconnection with the UTE grid. This specification defines the conditions and requirements for the basic and detailed engineering, design, manufacturing, supply, testing and inspection, transporting, unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier shall comply with all requirements stated in this Technical Specification and fill in the information requested in this document as well as in the attached Data Sheet.

Page 6: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 6 / 32 Melowind

150 kV UTE SUBSTATION

2. BASIC DESIGN DATA

2.1. Site Conditions

See document 214486-EN-SP-0-00066

2.2. Operation Voltages

Equipment and materials to be used on the Project shall be designed, manufactured and tested according the following values: Rated voltage: 150 kV ± 10% Service AC power voltage 400/230 ± 15% Protection and metering voltage 110 V +10% -15% DC power voltage 110 V +10% -15% Frequency margin 47 – 52 Hz.

Page 7: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 7 / 32 Melowind

150 kV UTE SUBSTATION

3. SCOPE OF SUPPLY The Scope of Supply will be an EPC Turnkey that includes all of the necessary works for the design, supply, erection, tests, commissioning, start-up and legalization. As minimum shall include: a) Basis and Detailed Engineering b) Supply of the equipment and materials. c) Civil works d) Erection. e) Earthing. f) Commissioning (including a final Dossier of the commissioning tests). g) Start-up. h) Commissioning spare parts. i) Substation legalization project.

3.1. Basic and Detailed Engineering Basic and detailed engineering necessary to define the UTE substation, shall be part of the scope of supply (electrical, mechanical, I&C and civil engineering). It shall include calculation reports, drawings, O&M Manuals, Commissioning Manuals, trip matrix and protection settings, insulation coordination report and as-built documentation. Once purchase order settled, the supplier will submit all engineering documentation according with the annex 1 VRDL.

3.1.1. Equipment The substation shall be Air Insulated Substation type (AIS), designed in double bus bar, for two (02) positions for overhead lines and one position for a generator plant (Melowind). Each position will be formed by the following equipment. The characteristics of the equipment and values are given for reference. Supplier shall perform the basic and detailed engineering to properly define all equipment and components of the substation.

3.1.1.1. Melowind Position a) Three (3) surge arresters, metal oxide, 150kV, class 2, 10kA with discharge

counter. b) Three (3) voltage transformers, capacitive type. Three (3) secondary windings,

two for metering class 0.2 and one for protections class 0.5-3P.

Page 8: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 8 / 32 Melowind

150 kV UTE SUBSTATION

c) Three (3) current transformers with one (1) secondary winding for tariff metering 0,2S FS≤5.

d) Three (3) current transformers with three (3) secondary windings, two (2) for protections class 5P20, and one (1) for metering class 0,5S FS≤5.

e) Three (3) three-phase line disconnecting switch (89L). One for outgoing circuit, one for Main Bus Bar and one for Transfer Bus Bar.

f) One (01) earthing switch (57L). The line disconnecting switch shall be equipped with a mechanical interlocking system for safety reasons. The mechanical interlock foreseen shall be able to extract a key when the earthing switch is closed. The interlocking shall be performed when there is no voltage in the grid.

g) One (1) three-phase circuit breaker (52L), SF6 type.

3.1.1.2. Melo Position a) Three (3) surge arresters, metal oxide, 150kV, class 2, 10kA with discharge

counter. b) Three (3) voltage transformers, capacitive type. Two (2) secondary windings for

protections class 0.5-3P. c) Three (3) current transformers with three (3) secondary windings, two (2) for

protections class 5P20, and one (1) for metering class 0,5S FS≤5. d) Three (3) three-phase line disconnecting switch (89L). One for outgoing circuit,

one for Main Bus Bar and one for Transfer Bus Bar. e) One (01) earthing switch (57L). The line disconnecting switch shall be equipped

with a mechanical interlocking system for safety reasons. The mechanical interlock foreseen shall be able to extract a key when the earthing switch is closed. The interlocking shall be performed when there is no voltage in the grid.

f) One (1) three-phase circuit breaker (52L), SF6 type. g) One (01) Line trap system, composed by main coil, surge arrester and tuning unit.

3.1.1.3. Treinta y Tres Position a) Three (3) surge arresters, metal oxide, 150kV, class 2, 10kA with discharge

counter b) Three (3) voltage transformers, capacitive type. Two (2) secondary windings for

protections class 0.5-3P. c) Three (3) current transformers with three (3) secondary windings, two (2) for

protections class 5P20, and one (1) for metering class 0,5S FS≤5. d) Three (3) three-phase line disconnecting switch (89L). One for outgoing circuit,

one for Main Bus Bar and one for Transfer Bus Bar.

Page 9: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 9 / 32 Melowind

150 kV UTE SUBSTATION

e) One (01) earthing switch (57L). The line disconnecting switch shall be equipped with a mechanical interlocking system for safety reasons. The mechanical interlock foreseen shall be able to extract a key when the earthing switch is closed. The interlocking shall be performed when there is no voltage in the grid.

f) One (1) three-phase circuit breaker (52L), SF6 type. g) One (01) Line trap system, composed by main coil, surge arrester and tuning unit.

3.1.1.4. Tie Breaker a) Two (2) three-phase line disconnecting switch (89L). One for Main Bus Bar and

one for Auxiliary Bus Bar. b) One (1) three-phase circuit breaker (52L), SF6 type. c) Three (3) current transformers with three (3) secondary windings, two (2) for

protections class 5P20, and one (1) for metering class 0,5S FS≤5.

3.1.1.5. 150 kV Busbar Voltage Metering a) Three (3) voltage transformers, capacitive type for main bus bar. Two (2)

secondary windings, one for metering class 0.2 and one for protections class 0.5-3P.

3.1.1.6. UPS, DC System and Diesel Generator a) UPS system, composed by rectifier, inverter, by pass transformer, static switch

and batteries. UPS and its by pass transformer will be fed from the Auxiliary Service Panel.

b) DC system, double system in parallel configuration, composed by charger/rectifiers, batteries and accessories for connection. Both rectifiers shall be fed from the Auxiliary Service Panel.

c) Emergency Diesel Generator (EDG) with automatic transfer Switch panel (ATS), 60 KVA as minimum, 400/230 VAC, for back up feeding to Auxiliary Service Panel.

3.1.1.7. Control, Protection and Communication a) The control system will be composed by Control Units cabinets, Substation

SCADA cabinet, HMIs touch screen for local operation, alarms panel, fiber optic panel and grid analyzer device.

b) All protection relays for each position of the substation and for the substation itself will be composed by a main relay and another for backup in which several protection functions, events recorder and oscillographic will be implemented.

Page 10: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 10 / 32 Melowind

150 kV UTE SUBSTATION

c) Ethernet connection for relays communication. d) Time synchronization GPS (IRIG B000). e) Communication system will be composed by fiber optic OPGW type as main

communication channel and radio link connection as back up communication channel. The associated equipment and accessories for these systems shall be foreseen, (tuning device, switches, converters, 18 mts tower, antenna), etc. the Destination will be the closer point of the future overhead line of 500 kV San Carlos – Melo (by others), to be defined later. It is assumed a distance of 30 km of fiber optic OPGW installed on the existing line supports.

f) At generator position (Melowind), a fiber optic OPGW type will be used as main communication channel, (by others).

g) At Treinta y Tres and Melo positions, Power Line Carrier will be used as the main communication channel.

h) Energy production metering System for Melowind position (SMEG, UREE 14/002).

3.1.1.8. Hardware a) Steel hot dip galvanized support structure for equipments, cables trays and

gantries for the overhead lines to Melowind, Treinta y Tres and Melo substations. b) Supports, structures, isolators, aerial cable and hardware necessary to cut the

existing line Melo-Treinta y Tres and make the deviation to gantries of UTE Substation.

c) Complete 150 kV bus bar for substation, main bus bar and auxiliary bus bar, included copper tubes, cables, isolators, all the connections clamps and derivations.

d) All power, control, protection, communication and fiber optic cables for interconnections. Cables for power and control shall be 0.6/1kV, armored cable. The rest shall be adequate for each voltage level, armored and /or shielded. All cables shall be low smoke, no fire propagation and zero halogen.

e) Full equipment for security, operation, maintenance and for fire fighting system, (to be quoted as an option).

f) The Supplier shall to design, supply and install the distribution panels required to serve the substation equipment. These panels should be:

• Auxiliary Services Panel 400/230 VAC. (lighting, receptacles, heaters, UPS, DC, etc.).

• Panel for equipment that requires uninterruptible electrical supply, 400/230 VAC. (metering, protection devices), fed from the UPS.

• Panel for equipment that require DC feeding, 110 VDC. (circuit breaker, disconnecting switches, protection relays, etc.) fed from the DC system.

Page 11: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 11 / 32 Melowind

150 kV UTE SUBSTATION

3.2. Services

3.2.1. Erection It shall be part of the scope of supply the erection of the equipment stated in section 3.1 of this Technical Specification. Besides, electrical interconnection between equipment and the Limits of Supply defined in this Technical Specification will be part of the scope of supply, including electrical power cables, interconnection cables (metering, interlocks and trips), control wiring and earthing. Main erection activities will be:

a) Civil Works described in 3.2.5. b) Erection of all equipment described in 3.1.1. into the building and in switchyard. c) To cut the existing line Melo-Treinta y Tres and to make the deviation until the

gantries of UTE Substation. d) To perform the connection in 150 kV of the cables coming from Melowind to its

gantry. e) Protections, communication and control systems inside substation and the

connections required for trips, commands or signals at the substations involved (Treinta y Tres, Melo, and Melowind).

Erection works shall comply with the codes and standards herein specified.

3.2.2. Auxiliary Services Feeding Auxiliary services of UTE substation will be fed from an existing MV distribution line. An overhead line shall be included in the scope of supply from the connection point to the new UTE substation. Due the data of the connection point is not known yet, the following conditions must be assumed:

• Feeder type: overhead line.

• Rated voltage: 15 kV

• Length: 5 km.

• Support type: Hot dip galvanized steel, single circuit.

• Conductor type: Steel - Aluminum. The following supply and erection activities must be included on the Scope of Supply:

• The necessary modifications in the existing line to make the derivation to the new UTE substation. It shall include the supply and erection of surge arresters, disconnectors, isolators, supports, etc.

• 300 kVA, 15/0.42 kV, three phase transformer and all accessories for its correct operation, to be placed at the last support close to the new UTE substation.

• Low voltage feeder, 4 wires + earth, 0.6/1 kV, from the secondary terminals of the transformer to the LV switchgear BFA, including underground conduits for its correct installation across the route. The length assumed is 20 meters.

Page 12: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 12 / 32 Melowind

150 kV UTE SUBSTATION

3.2.3. Earthing It shall be designed and erected the necessary earthing grid to meet the current regulations, with the soil resistivity value given in Design Basis document. The earthing grid shall include necessary cooper bare conductors with the appropriate section, copper bonded ground rod with ground inspection wells, cadweld welding, test bridges, clamps and accessories.

3.2.4. Lighting Normal and Emergency lighting shall be foreseen for switchyard area, access roads and fences, as well as, service receptacles for maintenance. Lighting shall be designed to maintain and operate all substation equipment in night shift hours.

3.2.5. Civil Works The scope of supply in Civil shall include the following works:

a) Site preparation, earth works for a plot of 200 x 200 meters, leveling and compacting.

b) Urbanization, it must include access road, internal roads, and plots for the foreseen positions plus space for future positions, fencing, surface finishing and drainage.

c) Concrete works, foundations for equipments, currents transformers, voltage transformers, surge arresters, circuit breaker, etc.

d) Control Building, composed by protection & control panels’ room, communication room, batteries room, diesel generator room, warehouse/workshop and toilets. Also, the proper services as HVAC, fire fighting system, normal and emergency lighting, receptacles, voice & data, plumbing & sewage, etc. shall be part of the scope of the building.

e) Will be part of the scope of supply the following security systems: 1) Access control 2) Intruder detection in perimeter fence and building. 3) Electrified perimeter fence. 4) Fire detection system in building, cabinets and panels.

f) Aboveground / underground electrical raceways necessary to interconnect the AIS equipment.

3.2.6. Commissioning Commissioning works shall be part of the scope of supply of this technical specification. The Supplier shall be responsible to plan and coordinate commissioning tests between

Page 13: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 13 / 32 Melowind

150 kV UTE SUBSTATION

the Client and the Electrical Company (UTE). Therefore, UTE standards and commissioning procedures shall apply. The Supplier shall include along with the offer an equipment list, catalogues and tests to be considered. Moreover, it shall also include a list including the foreseen equipment for the commissioning works.

3.2.7. Spare parts for the Commissioning Spare parts that the Supplier considers necessary to execute the commissioning phase without any delay shall be included. The guarantee tests shall be also consider in the scope. The Supplier shall bear in mind that he is the responsible for the commissioning works. The proposal shall consist of a list including the catalog numbers, quantity and price, manufacturer data, model, type, etc.

3.2.8. Substation Legalization Project The Supplier shall legalize the installation, issuing the necessary documentation required by the Official Organizations and managing all activities requested to obtain permits, licenses, authorizations that apply in Uruguay and UTE, etc.

3.2.9. Tests and Inspections Before energizing any equipment, the tests and inspections required for this Scope of Supply is shown in the Annex IDS, “Inspection Data Sheet”.

3.2.10. Transport and Intermediate Storage To be in accordance with commercial terms and PO.

3.2.11. Documentation The supplier shall submit the documentation for engineering, quality and shipping according with the annex 1 VRDL.

3.3. Limits of Supply The following limits of supply are established:

a) The battery limits in high voltage will be the point where the existing line between Melo and Treinta y Tres will be cut and diverted to the new UTE substation. The other side of the battery limit in high voltage will be the entry gantry isolator terminals of the overhead line to Melowind. The connection of the overhead lines to terminals is included.

b) In low voltage, UTE substation will cover the entire internal distribution system. For Auxiliary Services, the battery limit will be the connection point in a MV UTE distribution line, covering the scope described in section 3.2.2 of this Technical Specification.

c) For communications and protection, the battery limits will be those points at Melo, Treinta y Tres and Melowind substations, as well as UTE dispatch, etc. requested for external trips, remote metering, remote commands, etc. At the engineering development, a detailed list of signals exchanged between the new UTE substation and substations mentioned shall be provided.

Page 14: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 14 / 32 Melowind

150 kV UTE SUBSTATION

3.4. Exclusions a) The overhead lines in 150 kV to Melo and to Treinta y Tres. Only the works related with the

deviation to the gantry of new substation is included.

b) The overhead line to Melowind is part of another contract but the connection at the gantry is included for the line and fiber optic.

c) Maneuvers for overhead lines discharge.

d) Operations at UTE substations for start up maneuvers or any other electrical operations in UTE grid. Only the coordination and management of this operations and the presentation of tests, permits, etc. are part of the Scope of Supply.

Page 15: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 15 / 32 Melowind

150 kV UTE SUBSTATION

4. TENDER PROCESS The offer will be divided in two separate documents: the Technical offer and the Commercial offer.

The address, due date of the offers and any other data related to the tender process, will be described in the quotation request.

The Parts included in the Commercial Offer that are relevant for the technical bid evaluation such as scope of supply, limits of supply, exclusions, technical guarantees, and delivery date shall be included also in the Technical Offer or make a clear reference to the chapter where they are describe in the commercial documents.

Page 16: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 16 / 32 Melowind

150 kV UTE SUBSTATION

5. APPLICABLE CODES AND STANDARDS

5.1. General Design, engineering, materials, manufacturing, construction, erection, inspection, and tests of the equipment to be supplied must be in accordance with the basis established in the standards indicated on the Design Basis. In addition, UTE and Uruguayan Standards shall be taken into account.

The Supplier will apply, whenever possible, the same set of standards to the design, manufacturing, inspection, and tests of the equipment to be supplied.

5.2. Codes & Standards See document “Design Basis” 214486-EN-SP-0-00066.

Page 17: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 17 / 32 Melowind

150 kV UTE SUBSTATION

6. DESCRIPTION AND SUPPLY SPECIFICATION

6.1. Equipment Characteristics a) Rated voltage: .............................................................................................. 150kV b) Insulation voltage: ........................................................................................ 170kV c) Rated power frequency withstand voltage:................................................... 325kV d) Rated lightning impulse withstand voltage: .................................................. 750kV e) Max three-phase fault current: .................................................................40kA / 1s f) Creepage distance: ............................................................................... 25 mm/kV1

6.2. Circuit Breaker (52L) a) Circuit breaker (52L) shall be three-phase, single pole. It shall be capable of

extinguishing the arc generated amongst the contacts.

b) The operation mechanism shall be of spring type motor loaded. It shall be foreseen local and remote control of the breaker.

c) Circuit breaker shall be SF6 type, motorized and formed by three main sections. In the lower part there is the spring charge mechanism. Over this mechanism the insulators are laid. And in the upper part there is a gas chamber for current interruption.

d) Circuit breaker shall be equipped with a spring charge mechanism, lock magnet devices for opening and closing, limit switch with SPDT auxiliary contacts, heater resistance, SF6 control system, etc.

e) Circuit breaker shall have one (1) closing coil and two (2) opening coils.

6.3. Line Disconnecting Switch & Earthing Switch (89L and 89T)) a) Line disconnecting switches, high speed earth switches and hand-operated maintenance

earth switches shall be complete with all parts that are necessary for efficient operation. Line switch shall be rotating type, three columns per pole and double side opening, with the following main features

b) Line disconnecting switches shall meet the following requirements:

• They shall meet the rated short circuit withstand current.

• They shall be equipped with electric motor drive operable from main control room as well as local control cubicle.

c) The earthing switch shall have the following features:

• They shall be equipped with electric motor drive and an energy storing mechanism so that closing is possible even if the power supply fails.

Page 18: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 18 / 32 Melowind

150 kV UTE SUBSTATION

• They shall be equipped with manual closing facility. The power drive shall be blocked during manual operation.

• Disconnecting switches shall be equipped with an interlocking system for safety reasons. The mechanical interlock foreseen shall be able to extract a key when the earthing switch is closed. The interlocking shall be performed when there is no voltage in the grid.

6.4. Current Transformers (CTs) a) The current transformers are used for metering and protection. The ratio, burden,

accuracy class of different cores shall be as per AIS Single Line Diagram and Data Sheet.

b) Terminal and polarity marks shall be indelibly marked on CTs and shall be as per relevant standard. Installation orientation to be identical for all CTs. Facility shall be provided for shorting and earthing in the terminal box.

6.5. Voltage Transformers (VTs) a) Voltage transformers are used for system monitoring and protection. The burden and

accuracy class shall according to the use. They shall be capacitive type. Please refer to SLD and Data Sheet.

b) Terminal and polarity marks shall be indelibly marked on VTs and shall be as per relevant standard. Facility shall be provided to isolate the device.

6.6. Surge Arresters a) The surge arresters shall be installed close to the gantries of the incoming overhead

lines. Surge counters shall be foreseen for each phase and shall be assembled at a visible height to facilitate the reading of the meter.

b) The surge arresters shall be of metallic oxide type (ZnO), hermetically tight with self-supporting structure.

c) The insulators shall be made of porcelain or polymer and must have an adequate mechanical rigidity for a satisfactory operation.

d) A detector of leakage current shall be part of the surge counter. An isolated copper conductor shall be used for the connection between the surge counter terminal and the surge arrester earth terminal.

e) If the Supplier considers any technical requirements stated in this specification to be detrimental to the performance or quality of the equipment specified, he shall indicate this to the Purchaser and shall obtain written directive on how to proceed. Otherwise he will be held fully responsible for any consequence of not following such procedure.

Page 19: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 19 / 32 Melowind

150 kV UTE SUBSTATION

6.7. Protection System a) Is under the scope of the supplier to perform the necessary protection study and offer

those that are best adapt to the substation in accordance with the requirements of the client. Table I shows the basic scheme for protections, function described in the points b) and c) below are mandatory. During the development of the detailed engineering, the protection scheme will be finally defined with UTE.

b) The position for Generator (Melowind) shall have differential and overvoltage protection. Trip circuit verification system for circuit breaker shall be provided also.

c) For Treinta y Tres and Melo positions, both protection relays shall be identical and shall be provided of Line Differential protection, Distance protection with re-closing functions as minimum.

d) All protection relays for each position of the substation and for the substation itself will be composed by a main relay and another for backup in which several protection functions, events recorder and oscillographic will be implemented.

e) Protection relays shall be of digital type featuring multi-functionality according to IEC 60255. They shall be housed in the control and protection cabinets.

f) The Supplier shall readily configure and parameterize all protection relays including settings and internal protection relay logics for the communication with DCS ready to be tested during FAT.

g) The relays will be communicated between them and with the UTE general protection system through an Ethernet connection or fiber optic with an industrial type switch. The communication protocol to be used will be IEC 61850 and IEC 60870-5.

h) Time synchronization for all relays shall be made through GPS (IRIG B000) or IEC 1588v2 protocol. Relays shall be suitable for remote operation, (settings adjustment, viewing of electrical data, status, oscillographic records and events), and their interconnection with the SCADA system.

6.8. Control System The control system will be composed by Control Units cabinets, Substation SCADA cabinet, HMIs touch screen for local operation, alarms panel, fiber optic panel and grid analyzer device.

The Control Units consist on an integrated system where the main component will be the Substation Control Unit (SCU), which shall manage the overall whole of substation operation.

The main functions of the substation control system will be:

a) Control and signaling of all positions of the substation through the Positions Control Units (PCU).

b) Control and interlocking positions, as well as logical functions.

c) Presentation and management of alarms of the system.

d) Management of communications with the tele-control and the UCP. Management with the peripheral hardware such as monitor, local workstation, printer, modem, etc.

e) Fails and events reports.

Page 20: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 20 / 32 Melowind

150 kV UTE SUBSTATION

f) Time synchronization though GPS.

g) The main functions of the substation control system will be:

The Position Control Units (PCU) will manage the following activities in each position:

a) Measurement of current, voltage (single-phase, three-phase), power, frequency and power factor of the corresponding voltage transformers and current.

b) Control and signals of the associated equipment of the substation: circuit breakers, disconnecting switches, earthing switches, etc.

c) Gathering of signals from the equipment mentioned above.

d) Internal alarms management of the PCU.

6.9. Communication System Main functions of the telecommunication system are:

a) Remote trips (both directions) to the Circuit Breakers installed in UTE Substation and Wind Farm Substation.

b) Communication between line differential protections.

c) Integration of Melowind Wind Farm into the communications network of UTE substation and communication with UTE or “Delegated Dispatch”.

The communication system for the overhead lines position will be Power Line Carrier and for Generator (Melowind) will be fiber optic. All equipment, accessories, auxiliary devices, etc. for these communications links shall be implemented.

For the Integration of new substation into the UTE communication network or with UTE or “Delegated Dispatch”, a fiber optic will be implemented between the new substation and the closer point of the future overhead line of 500 kV San Carlos – Melo (by others), this location will be defined later. A distance of 30 km is assumed for this connection. As back up communication channel a radio link will be used, the supplier shall foreseen all devices

6.10. Metering System The requirements for the energy metering shall be those settled at Reglamento del Sistema de Medición Comercial (SMEC).

Page 21: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 21 / 32 Melowind

150 kV UTE SUBSTATION

Table I

PROTECTION RELAY SCHEME FUNCTIONS

EQUIPMENT ANSI FUNCTION DESCRIPTION

21 Distance Relay

87L Line Differential Relay

79 Reclosing Relay

3 Coil Supervision / Coil Monitoring relay

(50/51)

(50N/51N)

(67N)

Over current protection of phases with instantaneous relay

Neutral directional overcurrent

2 Phase Discrepancy Relays

Ove

rhea

d Li

nes

Pos

ition

s

1st P

rote

ctio

n &

Bac

k up

Pro

tect

ion

Mod

el b

y ve

ndor

87L Line Differential Relay

50S-62 Breaker Failure Relay

25 Synchronism

3 Coil Supervision / Coil Monitoring relay

(50/51)

(50N/51N)

(67N)

Over current protection of phases with instantaneous relay

Neutral directional overcurrent

(27/59) Under/overvoltage relay

2 Phase Discrepancy Relays

Gen

erat

or P

ositi

on

1st P

rote

ctio

n &

Bac

k up

Pro

tect

ion

Mod

el b

y ve

ndor

Page 22: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 22 / 32 Melowind

150 kV UTE SUBSTATION

6.11. Signals Auxiliary contacts for the circuit breaker, disconnecting switches and earthing switches status shall be hard-wired to the Wind Farm SCADA. All auxiliary contacts for the status of this equipment shall be hard-wired to the “Formation Frontier Box”.

Analog signals concerning electrical measurements (current, voltage, energy, power factor, etc.) will be hard-wired to the Wind Farm SCADA.

Three (3) signal lists will be issued during the project.

a) Hard-wired signal list. It will include the hard-wired signals to be exchanged between the Power Plant and the AIS substation. It will include not only the hard-wired signals to the Scada, but also the interconnection signals for metering, trips, control, equipment status etc.

b) Bus signal list. It will include the communicated signal list from the Substation Control Panel to the Scada of the plant.

c) Signals to be exchanged to the “UTE / Delegated Dispatch”. Any other signal foreseen by the Supplier considers as necessary.

6.12. Painting and Surface coatings All structures and metallic parts of the substation components like circuit breaker, disconnecting switches, CT´s, VT´s, overhead lines supports, gantries, etc. shall be hot dip galvanized.

For cabinets, and any painted housing equipment, finishing color will be industrial grey (RAL 7032).

Page 23: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 23 / 32 Melowind

150 kV UTE SUBSTATION

7. TEST AND INSPECTIONS Test and inspections required for this scope of supply is shown in the annex IDS “Inspection Data Sheet”.

Page 24: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 24 / 32 Melowind

150 kV UTE SUBSTATION

8. TECHNICAL GUARANTIES The Supplier shall guarantee compliance with the values and quantities according to the Data Sheet of the present Technical Specification for DC SYSTEM and its accessories according to applicable codes and standards.

Tolerances shall be according to IEC Standards.

Page 25: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 25 / 32 Melowind

150 kV UTE SUBSTATION

9. TECHNICAL DOCUMENTATION The supplier shall submit the documentation for engineering, quality and shipping according to the annex VRDL.

Page 26: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 26 / 32 Melowind

150 kV UTE SUBSTATION

10. 150kV UTE SUBSTATION DATA SHEET BIDDER: UNITS REQUEST OFFERED NOTES

POS 150 kV SUBSTATION (AIS TYPE)

1 GENERAL DATA

1.1 Numbers of units Pc 1

1.2 Manufacturer - *

1.3 Manufacture place - *

1.4 Standards of design - manufacture - IEC

IEC- 62271-203. High-voltage

switchgear and controlgear - Part

203: Gas-insulated metal-enclosed

switchgear for rated voltages above 52kV

2 GENERAL CHARACTERISTICS

2.1 Characteristics of the grid - -

2.1.1 Service Voltage kV 150

2.1.2 Insulation voltage kV 170

2.1.3 Short-circuit current kA Pending

2.1.4 Creepage distance mm/kV 25

2.1.5 Rated frequency Hz 50

2.1.6 Neutral system - Solidly earthed

2.2 Service conditions of the installation - *  See Design Basis

2.3 General conditions of the installation for all AIS equipment - *

2.3.1 Rated voltage kV 150

2.3.2 Rated Insulation Levels kV - 170

2.3.3 Rated power frequency withstand voltage - -

2.3.4 To earth and between poles kV (rms) -

2.3.5 Through the insulation distance kV (rms) 325

2.3.6 Rated lightning impulse withstand voltage (1,2/50 µs) - -

2.3.7 To earth and between poles kV (peak) 750

2.3.8 Through the insulation distance kV *

2.3.9 Withstand voltage with maneuver overvoltage - -

Page 27: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 27 / 32 Melowind

150 kV UTE SUBSTATION

POS BIDDER: UNITS REQUEST OFFERED NOTES

2.3.10 To earth and between poles kV N/A

2.3.11 Through the insulation distance kV N/A

2.3.12 Rated for continuous service at 40ºC A *

2.3.13 Admissible short circuit current kA 40

2.3.14 Dynamic current (peak) kA 100

2.3.15 Time duration of short circuit s 1

2.4 Limit conditions - -

2.4.1 Max. temperature rise in active parts with continuous rated current

ºC *

2.5 Rated voltage aux. feedings - -

2.5.1 Aux. Feeding Lighting & Heating V 400-230VAC

2.5.2 Aux. Feeding Motor Drive system V 2x110 VDC Diodes in the

positive pole

2.5.3 Aux. Feeding Metering, converters… V 400-230VAC UPS feeding

2.6 Rated voltage aux. circuits - -

2.6.1 Drive motors system - -

2.6.2 Of the circuit breakers VDC 110

2.6.3 Of the switching and earthing system VDC 110

2.6.4 AIS control system V *

3 CIRCUIT BREAKERS

3.1 Manufacturer / Model - *

3.2 Quantity Pc. 4

3.3 Fluid Type for insulation and breaking - SF6

3.4 Number of poles Pc. 3

3.5 Rated nominal current A 3150 Preliminary

3.6 Short circuit breaking capacity (1s) - -

3.6.1 RMS value of AC component kA 40

3.6.2 Percentage DC component % *

3.7 First-pole-to-clear factor - 1,5

3.8 Short circuit making current (peak) kA 100

3.9 Duration of short circuit s 1

3.10 Operation sequence - O-0,3s-CO-3min-CO

3.11 Auxiliary Switches - -

Page 28: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 28 / 32 Melowind

150 kV UTE SUBSTATION

POS BIDDER: UNITS REQUEST OFFERED NOTES

3.11.1 No. Of normally open contacts Pc. *

All aux.contacts to be wired to the

"Formation Frontier Box"

3.11.2 No. Of normally closed contacts Pc. *

All aux.contacts to be wired to the

"Formation Frontier Box"

3.12 Closing coil Pc. 1

3.12.1 Power consumption kW *

3.13 Opening coil Pc. 2

3.13.1 Power consumption kW *

4 LINE SWITCHES

4.1 Manufacturer / Model - *

4.2 Quantity Pc. 12

4.3 Rated short circuit current (1 s) kA 40

4.4 Rated making current (peak) kA 100

4.5 Auxiliary Contacts - -

4.5.1 No. Of normally open contacts Pc *

All aux.contacts shall be wired to

Formation Frontier Box

4.5.2 No. Of normally closed contacts Pc *

All aux.contacts shall be wired to

Formation Frontier Box

4.6 Main Drive System - Motorized-Manual

5 EARTHING SWITCHES

5.1 Manufacturer / Model - *

5.2 Quantity Pc. 4

5.3 Rated Current A 1600

5.4 Rated short circuit current (1 s) kA 40

5.5 Rated making current (peak) kA 100

5.6 Auxiliary Switches - -

5.6.1 No. Of normally open contacts Pc *

All aux.contacts to be wired to the

"Formation Frontier Box"

5.6.2 No. Of normally closed contacts Pc *

All aux.contacts to be wired to the

"Formation Frontier Box"

5.7 Main Drive System - Manual

Page 29: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 29 / 32 Melowind

150 kV UTE SUBSTATION

POS BIDDER: UNITS REQUEST OFFERED NOTES

6 CURRENT TRANSFORMERS

6.1 T1 - -

6.1.1 Quantity Pc. 3 

6.1.2 Transformer ratio A XXX/5  by supplier

6.1.3 Rated thermal withstand current - 100 In 

6.1.4 Burden & Class VA / Cl XX/ Cl0,2s FS<5  by supplier

6.2 T2 - -

6.2.1 Quantity Pc. 3 

6.2.2 Transformer ratio A XXX‐XXXX/5‐5‐5  by supplier

6.2.3 Rated thermal withstand current - 100 In

6.2.4 1st winding burden & class VA / Cl XX/ Cl0,5 FS<5 by supplier

6.2.5 2nd winding burden & class VA / Cl XX / 5P20 by supplier

6.2.6 3rd winding burden & class VA / Cl XX / 5P20 by supplier

7 VOLTAGE TRANSFORMERS (INDUCTIVE TYPE)

Test terminals to be installed in the front

part of the panel

7.1 TT-1

7.1.1 Quantity Pc.

7.1.2 Manufacturer / Type - *

7.1.2.1 Transformer ratio kV 150:√3 / 0,11:√3 / 0,11:√3 / 0,11:√3

7.1.2.2 1st winding burden & class VA / Cl XX / Cl 0,2 by supplier

7.1.2.3 2nd winding burden & class VA / Cl XX / Cl 0.5 - 3P by supplier

7.1.2.4 3rd winding burden & class VA / Cl XX / Cl 0.5 - 3P by supplier

7.2 TT-2

7.2.1 Quantity Pc.

7.2.2 Manufacturer / Type - *

7.2.2.1 Transformer ratio kV 150:√3 / 0,11:√3 / 0,11:√3

7.2.2.2 2nd winding burden & class VA / Cl XX / Cl 0.5 - 3P by supplier

7.2.2.3 3rd winding burden & class VA / Cl XX / Cl 0.5 - 3P by supplier

8 SURGE ARRESTERS

8.1 Type - Metal Oxide (ZnO)

8.2 Number of units Pc 6

8.3 Rated Voltage kV 150

8.4 Continuous operation voltage kV *

8.5 Rated surge arrester voltage kV *

8.4 Line discharge class (acc.to IEC) - Class 3

8.5 Rated current A *

Page 30: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 30 / 32 Melowind

150 kV UTE SUBSTATION

POS BIDDER: UNITS REQUEST OFFERED NOTES

8.6 Rated discharge current kA *

9 OPERATING MECHANISMS/DRIVES   

9.1 Circuit Breakers - -

9.1.1 Type of operating mechanism - Spring type

9.1.2 Operating voltage VDC 110

9.1.3 Power consumption W *

9.1.4 Tripping and closing coil operating voltage range VDC 110

9.1.5 Operating times - -

9.1.6 Opening time maximum ms *

9.1.7 Total break time at rated short circuit breaking current ms *

9.1.8 Maximum closing time ms *

9.1.9 Maximum make time ms *

9.2 Line Switches - -

9.2.1 Type of operating mechanism - *

9.2.2 Operating voltage VDC 110

9.2.3 Power consumption W *

9.2.4 Operating times - -

9.2.4.1 To open s *

9.2.4.2 To close s *

9.2.4.3 Minimum electrical impulse time for completion of operation

ms *

9.3 Earthing switches - -

9.3.1 Type of operating mechanism - *

9.3.2 Operating voltage VDC Manual

9.3.3 Power consumption W *

9.3.4 Operating times - -

9.3.4.1 To close s *

9.3.4.2 Minimum electrical impulse time for completion of operation

ms *

10 CONNECTIONS

10.1 Connections between the AIS switchgear (CB, Line & earthing switches, CTs, VTs shall be carried out by the AIS Supplier

REQUIRED See Technical Specification

10.2 150 kV Treinta y Tres and Melo overhead lines deviation - REQUIRED See Technical

Specification

Page 31: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 31 / 32 Melowind

150 kV UTE SUBSTATION

POS BIDDER: UNITS REQUEST OFFERED NOTES

10.3 15kV feeder for auxiliary Services of the UTE substation. REQUIRED See Technical

Specification

10.4 Fiber optic connection for the integration of the new substation with the UTE network. REQUIRED See Technical

Specification

11 PROTECTION RELAYS

11.1 Manufacturer/Type - *

11.2 Number of digital inputs/outputs Pc. 8

11.3 Number of Analog inputs Pc. 8

11.4 Trip contacts Pc 3

11.5 Protection relay functions for main and back up for overhead lines positions - -

11.5.1 Model - *

11.5.2 Functions - 21, 87L, 79, 50/51, 50/51N, 67N, 2, 3

11.6 Protection relay functions for main and back up for generator position - -

11.6.1 Model - *

11.6.2 Functions - 87L, 50S-62, 25, 50/51, 50N/51N,

67N, 3, 2

11.7 Protection Frontier Point - -

11.7.1 Model - *

11.7.2 Functions - 3x27, 59, 64

12 NOTES

12.1 * This values shall be defined by manufacturer. - *

12.2

Those values marked as PRELIMINARY are given for reference. Supplier shall perform the basic and detailed engineering to define all equipment properly.

- *

Page 32: 150 kV UTE SUBSTATION · unloading, erection, commissioning, start-up, spare parts for commissioning and warranty of the Turnkey for the complete 150 kV UTE Substation. The supplier

214486-EL-DS-0-00037 R. 00 32 / 32 Melowind

150 kV UTE SUBSTATION

11. REFERENCE DOCUMENTS

• DESIGN BASIS - 214486-EN-SP-0-00066

• UTE SUBSTATION SINGLE LINE DIAGRAM – 214486-EL-DG-0-00035

• UTE SUBSTATION PLANT LAYOUT - 214486-EL-DR-0-00069