80
1. NASLOVNA STRAN NAČRTA ŠTEVILČNA OZNAKA NAČRTA IN VRSTA NAČRTA: NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi d.o.o. Cesta Ljubljanske brigade 11b, 1000 LJUBLJANA OBJEKT: VGRADNJA ENOTE SPTE V KOTLOVNICO MRP, na parc. št. 772, 773, k.o. BOHOVA pri VZDRŽEVALNEM CENTRU MARIBOR, Bohova 19 B, 2311 HOČE VRSTA PROJEKTNE DOKUMENTACIJE: PZR – PROJEKT ZA RAZPIS ZA GRADNJO: INVESTICIJSKO VZDRŽEVANJE PROJEKTANT: PRO-MARK Marko KAMENŠEK s.p. M.P. Ceste 8, 3250 ROGAŠKA SLATINA gsm: 031 603 930 e-mail: [email protected] ODGOVORNI PROJEKTANT: Marko KAMENŠEK, u.d.i.s. S-1147 M.P. ŠTEVILKA NAČRTA, KRAJ IN DATUM IZDELAVE NAČRTA: 25/16-S, ROGAŠKA SLATINA, OKTOBER 2016 IZVOD: 1 2 3 4 5 6

1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

1. NASLOVNA STRAN NAČRTA

ŠTEVILČNA OZNAKA NAČRTA IN VRSTA NAČRTA:

NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5

INVESTITOR:

Plinovodi d.o.o.

Cesta Ljubljanske brigade 11b, 1000 LJUBLJANA

OBJEKT:

VGRADNJA ENOTE SPTE V KOTLOVNICO MRP, na parc. št. 772, 773, k.o. BOHOVA

pri VZDRŽEVALNEM CENTRU MARIBOR, Bohova 19 B, 2311 HOČE

VRSTA PROJEKTNE DOKUMENTACIJE:

PZR – PROJEKT ZA RAZPIS

ZA GRADNJO:

INVESTICIJSKO VZDRŽEVANJE

PROJEKTANT:

PRO-MARK Marko KAMENŠEK s.p. M.P. Ceste 8, 3250 ROGAŠKA SLATINA

gsm: 031 603 930 e-mail: [email protected]

ODGOVORNI PROJEKTANT:

Marko KAMENŠEK, u.d.i.s. S-1147 M.P. ŠTEVILKA NAČRTA, KRAJ IN DATUM IZDELAVE NAČRTA: 25/16-S, ROGAŠKA SLATINA, OKTOBER 2016 IZVOD: 1 2 3 4 5 6

Page 2: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 2 od 16

2. KAZALO VSEBINE NAČRTA STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

1. NASLOVNA STRAN NAČRTA .......................................................................................... 1

2. KAZALO VSEBINE NAČRTA STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S ......................................................................................................................... 2

3. TEHNIČNO POROČILO .................................................................................................... 3

3.1. Projektna naloga ......................................................................................................... 3

3.2. Tehnični opis .............................................................................................................. 4

3.2.1. SPLOŠNO ........................................................................................................... 4

3.2.2. Enota SPTE - kogeneracija .................................................................................. 4

3.2.3. Prostor, kjer bo postavljena enota SPTE – kotlovnica .......................................... 5

3.2.4. Cevi in izolacija .................................................................................................... 7

3.2.5. Tlačni preizkus ogrevalnega razvoda ................................................................... 8

3.2.6. Preizkusno obratovanje ....................................................................................... 8

3.2.7. Potrebna dokumentacija za prevzem sistema ...................................................... 8

3.2.8. PLIN .................................................................................................................... 9

4. TEHNIČNE RISBE ...........................................................................................................15

5. PRILOGE .........................................................................................................................16

Page 3: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 3 od 16

3. TEHNIČNO POROČILO

3.1. Projektna naloga

Za objekt: VGRADNJA ENOTE SPTE V KOTLOVNICO MRP, na parc. št. 772, 773, k.o.

BOHOVA, pri VZDRŽEVALNEM CENTRU MARIBOR, Bohova 19 B, 2311 HOČE, je

potrebno izdelati projekt za razpis PZR za fazo strojnih inštalacij in strojne opreme in sicer za

priključitev ENOTE ZA SOPROIZVODNJO TOPLOTNE IN ELEKTRIČNE ENERGIJE (enote

SPTE oz. kogeneracije) na obstoječo kotlovnico. Variantno je potrebno obdelati postavitev

najprej ene enote SPTE in nato še dodatne druge enote SPTE.

Enota SPTE z elektro omaro in toplotnim izmenjevalcem se postavi v kotlovnico poleg

talnih plinskih kotlov. Enota SPTE se poveže na obstoječi ogrevalni sistem - z dovodom na

skupni dovod do toplotnih menjalnikov za ogrevanje plina in povratkom na skupni povratek iz

toplotnih menjalnikov za ogrevanje plina.

Enota SPTE se poveže na plinsko inštalacijo pred glavnim plinomerom v kotlovnici pri kotlih. Naročnik mora odobriti PZI projekt pred pričetkom izvedbe.

Projektna naloga predvideva tudi naslednje:

- zamenjava glavnih obtočnih črpalk z novimi varčnimi, komplet z ventili, čistilnimi kosi in

povratnimi loputami,

- izvedba varovanja kotlov proti prenizki temperaturi povratka preko mešalnega ventila, ki

bo hkrati reguliral dovod tople vode iz kotlov v sistem in omogočal, da bo SPTE enota delala

optimalno,

- ureditev kaskadne regulacije kotlov,

- prevezava dveh toplotnih menjalnikov za ogrevanje zemeljskega plina iz vzporedne

vezave na zaporedno vezavo,

- uvedba energetskega monitoringa oz. toplotnih števcev posebej za SPTE enoto in

posebej za kotla

- izvedba toplotne izolacije toplovodnega razvoda v kotlovnici in redukcijskem prostoru

Page 4: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 4 od 16

3.2. Tehnični opis

3.2.1. SPLOŠNO

OBSTOJEČE STANJE - KOTLOVNICA V MRP Maribor se koristi za potrebe ogrevanja zemeljskega plina pri prehodu iz višjega na nižje tlačno stanje zemeljski plin kar iz MRP same. Upravljavec in lastnik so Plinovodi d.o.o. Objekt je razdeljen na kotlovnico z dvema pomožnima prostoroma ter redukcijski prostor, kjer je EX cona 2 in je strogo ločen od ostalih prostorov objekta. V kotlovnici sta inštalirana dva talna plinska kotla Viessmann Vitoplex 100 – moči 170kW in sta povezana v kaskado, nimata pa kaskadne regulacije. Kotla delujeta izmenično in je eden kot rezerva za zanesljivost delovanja. Kotla sta povezana direktno na toplotni menjalnik za ogrevanje zemeljskega plina v redukcijskem prostoru. Cirkulacijo omogočata stari obtočni črpalki s fiksno hitrostjo, kjer je ena prav tako rezervna in delujeta izmenično. Temperaturni režim je 80/60°C.

Ogrevalni sistem ima izvedeno zaprto ekspanzijo. Odvod dimnih plinov je preko sestavljivih dimniških cevi direktno na streho od vsakega kotla posebej. Dovod zraka je urejen preko precej velikih rešetk pri tleh prostora kotlovnice, odvod pa preko rešetk pod stropom. Kotlovnica je zelo dobro prezračena, zato se pozimi v njej lahko pojavijo zelo nizke temperature. Kot varovanje ogrevalnega sistema pred zamrznitvijo je v sistemu namesto čiste vode mešanica glikola, ki zdrži vsaj do -20°C. Plin V redukcijskem prostoru je narejen odcep za dobavo plina v kotlovnico. Narejena je redukcija tlaka iz 10 bar na 50mbar in cev DN40 povezana v kotlovnico, kjer je mehovni plinomer BK-G16 (Qmax=25m3/h), potem pa dovod do obeh kotlov. V kotlovnici je inštaliran še manjši mehovni plinomer in odcep za sosednji objekt. Oprema v kotlovnici:

- mehovni plinomer G16 Qmax=25m3/h DN40 in - plinski ventil s termičnim varovalom na vsakem kotlu.

3.2.2. Enota SPTE - kogeneracija

Soproizvodnja toplotne in električne energije, krajše enota SPTE, imenovana tudi kogeneracija, je proces sočasnega pretvarjanja energije goriva – v našem primeru zemeljskega plina - v toploto in električno energijo. Pri tem se uporablja električni generator, ki ga poganja mehanska energija vrtečih se delov motorjev oziroma turbin. Pri pretvorbi notranje energije goriv v mehansko se sprosti velika količina toplote, ki se pri tem načinu koristno uporabi. O mikro soproizvodnji električne in toplotne energije govorimo takrat, ko generatorjeva moč ne preseže 50 kW. Soproizvodnja prinaša občutne prihranke primarne energije in zmanjšuje emisije CO2 v ozračje. Zaradi uporabe preostale toplote imajo soproizvodni sistemi celotni izkoristek približno 90 %. Izbor velikosti SPTE je opravljen na podlagi diagramov prikaza potrebne toplote v MRP Maribor (v prilogi) podanih s strani investitorja Plinovodi d.o.o., ob upoštevanju predhodnega soglasja elektro distributerja Elektro Maribor. Izbor velikosti in tipa SPTE je na podlagi razpoložljivih podatkov ter znanja in izkušen opravil ponudnik SPTE Butan plin d.d.

Page 5: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 5 od 16

Predvideva se postavitev naslednje SPTE enote – I. faza: Podatki o enoti SPTE: Enota SPTE: ECE POWER - XRGI 9G-TO

- Qtopl = 20kW, - Pel = 9kW, - Psk = 31kW, - gorivo: zemeljski plin, - tlak plina 20-50mbar, - poraba zemeljskega plina 3,3 Sm³/h, - plinski priključek DN20.

Možnost je postavitve kasneje še naslednje SPTE enote – II. faza: Podatki o enoti SPTE: Enota SPTE: ECE POWER - XRGI 20G-TO

- Qtopl = 40kW, - Pel = 20kW, - Psk = 65kW, - gorivo: zemeljski plin, - tlak plina 20-50mbar, - poraba zemeljskega plina 6,8 Sm³/h, - plinski priključek DN20.

3.2.3. Prostor, kjer bo postavljena enota SPTE – kotlovnica

Enota SPTE bo postavljena poleg plinskih kotlov v kotlovnici, elektro omara in izmenjevalec pa na steno zraven enote. Kotlovnica ustreza predpisom za plinske kotlovnice in ni potrebno uvajati novih ukrepov, prezračevalne odprtine so zadostne in ni potrebno dodatnih, ker potrebuje enota SPTE zrak za zgorevanje. Predvidena je izvedba kondenzacijske naprave na izpušnem sistemu, kar še poveča skupno toplotno moč enote. Od kondenzacijske naprave je speljana izpušna cev iz nerjavečega kislinsko odpornega jekla fi80 vertikalno pod strop in potem horizontalno skozi sprednjo steno in zunaj po steni vertikalo 1 m nad streho. Kondenz od izpušnega sistema se od kondenzacijske naprave spelje v zunanji meteorni jašek ob objektu. Kompletno cev za odvod kondenza je potrebno varovati z grelnimi kabli proti zmrzali in termostatom. Enota SPTE se naveže z dovodom na dovod za toplotna menjalnika za ogrevanje plina, s povratkom pa na glavni povratek DN80 med kotloma in toplotnima menjalnikoma. Vsa izvedba se v I. fazi zaradi morebitne vgradnje še ene SPTE enote kasneje izvede tako, da so vse glavne cevi in prostorska postavitev narejeni tako, da se druga enota inštalira z minimalnimi predelavami inštalacij. Izpuh enot SPTE Izpuh se projektira iz kislinsko odpornih nerjaveči cevi varjene izvedbe DN80. SPTE je nadtlačni odvodnik izpušnih plinov in mora zadostovati pogojem DVGW G600 TRGI za plinska trošila skupine B, ki so odvisna od zraka v prostoru. Cevi morajo biti nepropustne in tlačno odporne do tlaka 5000 Pa (Tip H1 ali H2) in temperaturne odpornosti razreda T160.

Page 6: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 6 od 16

Od izpušne cevi je potrebno izvesti odvod kondenza. Kondenz se spelje od vseh mest zbiranja kondenza najprej iz nerjavečih kislinsko odpornih cevi preko sifonov ter naprej po PVC ceveh DN50 in se naveže v odtok zunaj objekta.

Izvesti je potrebno tudi naslednje (razvidno iz risb):

- zamenjava glavnih obtočnih črpalk z varčnimi frekvenčno vodenimi, komplet z ventili,

čistilnimi kosi in povratnimi loputami,

- izvedba varovanja kotlov proti prenizki temperaturi povratka preko mešalnega ventila, ki

bo hkrati reguliral dovod tople vode iz kotlov v sistem in omogočal, da bo SPTE enota delala

optimalno,

- ureditev kaskadne regulacije kotlov,

- prevezava dveh toplotnih menjalnikov za ogrevanje zemeljskega plina iz vzporedne

vezave na zaporedno vezavo,

- uvedba energetskega monitoringa oz. toplotnih števcev posebej za SPTE enoto in

posebej za kotla

- izvedba toplotne izolacije toplovodnega razvoda v kotlovnici in redukcijskem prostoru

Izbrana nova oprema:

1. Obtočna črpalka s tremi hitrostmi regulacije vrtljajev GRUNDFOS UPS 65-30F,

15m3/h, h=1,5m PN6/10, 0,2kW, s prirobničnimi priključki – glavna obtočna

črpalka

2. Obtočna črpalka s tremi hitrostmi regulacije vrtljajev GRUNDFOS UPS 25-40,

130, 2m3/h, h=1,5m PN6/10, 0,06kW, s navojnimi priključki – vmesna obtočna

črpalka

3. Obtočna črpalka IMP PUMPS EGHN 32-180 s prigrajenim frekvenčnim

pretvornikom (0-10V), 96kW, dT=30°C, 2,8m3/h, h=1,5m PN6, 0,06kW, s

navojnimi priključki - obtočna črpalka SPTE enot

4. Tripotna mešalna pipa s prirobničnimi priključki DANFOSS tip HFE 3 - DN80 / 150

Page 7: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 7 od 16

Prezračevanje kotlovnice

Za prezračevanje kotlovnice sta dovolj obstoječe dovodne in odvodne rešetke. POŽARNA VARNOST Kotlovnica SPTE, kjer bo postavljena enota SPTE mora biti opremljena tako, da ustreza pravilniku o plinskih kotlarnah. Upoštevajo se naslednji zakonski akti: Plinska kotlovnica se projektira po DVGW TRGI G 600 april 2008. Upošteva jo se:

- Zakon o varstvu pred požarom (Ur.l. RS 71/93, 87/01) - Pravilnik o požarni varnosti v stavbah ( Ur.l. RS, št. 31/2004) - Tehnična smernica TSG-1-001:2010 Požarna varnost v stavbah in v njej predpisani

podporni dokumenti. - Nemška smernica Muster-Feuerungsverordnung (MFeuV), - Smernica SZVP 407: Požarna varnost pri načrtovanju, vgradnji in rabi kurilnih in

dimovodnih naprav - Pravilnik o tehničnih pogojih za graditev, obratovanje in vzdrževanje plinovodov z

najvišjim delovnim tlakom do vključno 16 bar (Uradni list RS št. 26/2, 54/02), - Tehnične zahteve za graditev glavnih in priključnih plinovodov in notranje plinske

napeljave Potrebno je upoštevati tudi naslednje:

� Prostor mora biti dobro osvetljen. � Prehodi med drugimi napravami oz. elementi v prostoru in enoto SPTE oziroma med

štrlečimi deli na napravah in steno ne smejo biti manjši kot 0,8m.

3.2.4. Cevi in izolacija

Vsa toplovodna inštalacija je izdelana iz jeklenih cevi, material St 33 in potekajo vidno pod stropom. Cevovodi so pobarvani z dvakratnim slojem temeljne barve, primerne za temperature do 150 °C. lzolirani so s penasto izolacijo ustrezne debeline, odvisno od debeline cevi. Neizolirani deli so pobarvani s temperaturno odporno pokrivno barvo. Barvno skalo za označevanje cevnih napeljav določa DlN 2403, barvne oznake RAL pa so združene v registru barv RAL 840 HR. Polnjenje ogrevalnega sistema se izvede z mešanico glikol – voda (40% GLIKOLA). Horizontalni in vertikalni cevni razvod je razviden iz situacij ogrevanja, kjer je prikazano: • dimenzije cevi • prehodi med gradbenimi konstrukcijami • razporeditev cevovodov • način polaganja (v tleh, pod stropom, vidno) Odzračevanje sistema se izvede z avtomatskimi odzračevalci na najvišjih mestih razvoda. Vsak element sistema ogrevanja je možno ločiti od ostalega omrežja s predvidenimi zapornimi ventili.

Page 8: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 8 od 16

3.2.5. Tlačni preizkus ogrevalnega razvoda

Izvajalec po končani montaži grobe inštalacije in pred izoliranjem cevi izvede tlačni preizkus cevovodov. Pri hladnem preizkusu se napolni instalacijo z mrzlo vodo in poveča tlak na 1.3x vrednost najvišjega možnega tlaka, a najmanj 100 kPa nad najvišjim možnim tlakom. Meri se na najnižjem delu instalacije. Tlak v instalaciji ne sme pasti v 10 min pri nespremenjeni temperaturi vode v ceveh. Hladni tlačni preizkus je mogoče pri večjih instalacijah izvesti po delih, vendar se morajo preizkušeni odseki med seboj prekrivati. Toplotni preizkus se izvede po možnosti neposredno po hladnem preizkusu. Če celotna instalacija še ni končana, se izvede po končani montaži za celotno omrežje. Gorivo ali toplotno energijo zagotovi investitor. Pri tem ogrejemo vodo na najvišjo obratovalno temperaturo. Instalacija ne sme puščati, cevi se pri toplotnem raztezanju ne smejo trajno deformirati. O izvršenih preizkusih je potrebno izdelati zapisnik, ki naj vsebuje:

− podatke o instalaciji (situacija, moč, najvišji obratovalni tlak/temperatura), − podatke o izvajalcu, − preizkusni tlak, − čas obremenitve s preizkusnim tlakom, − potrdilo, da je omrežje tesno in da na nobenem delu instalacije niso nastale trajne

deformacije.

3.2.6. Preizkusno obratovanje

Med preizkusnim obratovanjem izvedemo sledeča dela: − preizkusimo delovanje varnostnih naprav, − nastavimo regulacijske elemente v omrežju.

3.2.7. Potrebna dokumentacija za prevzem sistema

o Zapisnik o hladnem tlačnem preizkusu, o Zapisnik o toplotnem preizkusu, o Atesti in garancijski listi za vgrajene elemente o Navodila za obratovanje in vzdrževanje o Shema vezave enot SPTE v okvirju zaščitenim s steklom o PID dokumentacija

Page 9: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 9 od 16

3.2.8. PLIN

Obstoječa plinska inštalacija Upravljalec in lastnik so Plinovodi d.o.o. Glavna plinska cev v kotlovnico je DN40 in zadostuje za priklop enote SPTE s cevjo DN25. Nadaljni cevovod se izvede iz jeklenih brezšivnih cevi po SIST EN 10220. Spoji cevi so praviloma čelno varjeni. Elemente, ki so medsebojno spojeni z varjenjem lahko varijo le za to usposobljeni varilci z veljavnim atestom. Vsi spoji so varjeni razen na mestih, kjer je vgrajena armatura. Na teh mestih je uporabljena prirobnična ali navojna zveza. Odcep za enoti SPTE je preko zapornega plinskega ventila DN25. Plinska inštalacija za navezavo enote SPTE na obstoječo plinsko inštalacijo v kotlovnici pred glavnim plinomerom kotlov. Izdelavo, predelave in vzdrževalna dela na plinski napeljavi lahko razen Plinovodi d.o.o. opravljajo tudi ostala instalacijska podjetja v soglasju s Plinovodi d.o.o. Plinska napeljava in njeni posamezni deli morajo biti takšni, da so varni pri pravilni uporabi. Uporabljeni materiali morajo imeti ustrezne ateste za uporabo zemeljskega plina. Cevi se antikorozijsko zaščitijo in prebarvajo z rumeno barvo z dvakratnim premazom. Lokacija cevi in podrobnosti so razvidne iz načrta. CEVI IN ARMATURE Medsebojno spajanje armature ali armature in cevi je dovoljeno s prirobničnimi ali z navojnimi zvezami. Navojne zveze se uporabljajo do vključno DN 50. Max. dolžina navoja po SIST EN 10241 in SIST EN 10242 je: DN (mm) 15 20 25 32 40 50 dolžina navoja (mm) 15 16.3 19.1 21.4 21.4 25.7 V skladu s predpisom SIST HD 60364-5-51:2009 - Nizkonapetostne električne inštalacije je potrebno upoštevati sledeče:

• notranji plinovodi v vsaki zgradbi morajo biti ločeno priključeni na spojno letev za izenačitev električnega potenciala. Letev mora biti povezana z ozemljitveno instalacijo objekta. El. upornost te mora biti manjša od 2 ohma.

• obvezno je treba premostiti vse navojne in prirobnične spoje armatur • o izenačitvah potencialov in ozemljitvah plinovoda mora izvajalec izdati pisno izjavo in

rezultate meritev galvanskih povezav in ozemljitev Plinovod mora potekati tako, da ni možnosti nastanka mehanskih poškodb. Ne sme biti pritrjeni na druge napeljave in ne sme služiti kot podpora za druge napeljave. Prav tako mora biti položen tako, da nanj ne more kapljati kondenz ali voda z drugih napeljav. Pritrditev cevi mora biti izdelana ognjevarno, nosilni deli cevnih podpor pa morajo biti iz negorljivih materialov in ne smejo biti privarjeni na plinovod. Poleg navedenega pa je pri izvajanju plinske inštalacije potrebno upoštevati še sledeče:

• spajajo se izključno z zvari, armatura na cevovodih pa mora biti v posebnih, lahko dostopnih mestih,

• cevovodi, ki so izvedeni vidno, so položeni ali pritrjeni na konzole oz. nosilce; na strop ali zid so lahko pritrjeni z ustreznimi obešali

Page 10: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 10 od 16

• pri razmiku med oporami in oddaljenosti cevovoda od stene je potrebno upoštevati min razdalje

• plinski cevovodi ne smejo biti pod nobenim pogojem pod cevmi z agresivnimi fluidi ali pod cevmi, na katerih utegne nastati kondenzat

• prehodi skozi stene morajo biti izvedeni z zaščitno cevjo večjega premera, zatesnjeni s trajno elastičnim kitom, vmesni prostor pa zapolnjen z bituminizirano vrvjo

• instrumenti, oprema in priključki plinskega trošila se spajajo s plinskim vodom s cevno navojno zvezo ali prirobnico

• cevovodi v kletnih prostorih morajo biti spojeni izključno z zvari in vidni • če vodi potekajo v skupnem jašku vzporedno, morajo biti ostali vodi

odmaknjeni za najmanj 40 cm • cevovodi morajo biti zavarovani pred korozijo • vidni del cevovodov mora biti opleskan z rumeni barvo • na stabilnem cevovodu mora biti pred zvezo z zvijavim cevovodom ventil za zapiranje • na zvijavem cevovodu ne sme biti zapornega organa • varjenje cevovodov smejo vršiti atestirani varilci • izvajanje plinske instalacije smejo vršiti pooblaščeni plinski instalaterji

Padec plinovoda je proti trošilu. Kovinskih plinovodov se ne sme uporabiti kot zaščitna ali delovna ozemljila niti kot zaščitne odvodnike v jakotočnih napeljavah. Prav tako se jih ne sme uporabiti za odvodnike ali ozemljila v strelovodnih napeljavah. Plinovod mora potekati tako, da ni možnosti nastanka mehanskih poškodb. Ne sme biti pritrjeni na druge napeljave in ne sme služiti kot podpora za druge napeljave. Prav tako mora biti položen tako, da nanj ne more kapljati kondenz ali voda z drugih napeljav. Pritrditev cevi mora biti izdelana ognjevarno, nosilni deli cevnih podpor pa morajo biti iz negorljivih materialov in ne smejo biti privarjeni na plinovod. Pri montaži je potrebno upoštevati največje razdalje med dvema podporama, ki za različne premere veljajo za jeklene cevi (podano v tabeli).

Page 11: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 11 od 16

Pri vodenju cevovodov skozi dilatacije, ki ločujejo dva dela zgradbe, je potrebno poskrbeti za to, da premikanje ne vpliva škodljivo na plinovod. Pri preboju dvižnih in razdelilnih vodov skozi stene in strope morajo biti vgrajene zaščitne cevi, ki gledajo na vsaki strani 4cm iz zidu. Zaščitne cevi morajo biti iz materiala odpornega proti koroziji ali zaščitene proti koroziji. Notranji cevovod mora dopuščati malenkostne aksialne pomike hišnega priključka oziroma zunanjega cevovoda ne da bi to povzročilo mehanske poškodbe notranjega cevovoda ali njegove netesnost. Ta zahteva je izpolnjena, če je vstop v zgradbo tak, da je na prvih 2m notranjega cevovoda najmanj ena sprememba smeri za 90° in nobene fiksne točke. Plinovodi morajo biti pred korozijo zaščiteni v skladu z SIST EN 12068. Prostor,v katerem je nameščen plinomer, ne sme biti pretopel, biti mora lahko dostopen in suh. Prostor, v katerem je nameščen plinomer in vrsto plinomera odobri Plinovodi d.o.o. Namestitev plinomera mora biti v skladu s (DVGW TRGI G 600 2008). Izgotovljeni in še ne priključeni, mirujoči ali iz obratovanja vzeti notranji plinovodi, morajo imeti vse odprtine tesno zaprte s čepi, kapami, pokrovi ali s slepimi prirobnicami iz kovinskih materialov. Zaprti zaporni elementi (npr. pipe, zasuni, lopute) ne veljajo kot tesne zapore, razen varnostnih zaključnih armatur po SIST EN 13774. Pred ločevanjem ali spajanjem, pred demontažo ali vgradnjo delov napeljave, armatur, plinomerov, regulatorjev tlaka itd., kot tudi pri nameščanju ali odstranjevanju čepov, je treba

Page 12: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 12 od 16

kovinske plinovode zaščititi pred napetostjo pri dotiku in pred iskrenjem, s premostitvijo ločenih delov. Za premostitev se uporabi gibko, izolirano bakreno pletenico s presekom najmanj 16mm2 in ne daljše od 3m. Priključne spojke morajo biti prirejene premeru cevi. Pri priključevanju je treba paziti na dober električni stik. Stična mesta je treba pred uporabo prižemnih spojk očistiti do kovinskega sijaja. Vmesno vlaganje kovinskih folij ni dovoljeno. Pri delih na plinovodih pod plinom je treba upoštevati DVGW TRGI G 600 2008. MONTAŽA Cevi so med seboj spojene z varjenjem s čelnim V-zvarom. Varijo lahko samo varilci z veljavnim atestom. Napeljava mora potekati po predpisih DVGW - TRGI G 600 2008, točka 3.3. Notranja napeljava mora biti ozemljena v skladu s predpisi. ZAŠČITA NAPELJAVE Vidna oz. nadometno vodena napeljava mora biti po predhodnem čiščenju do kovinskega sijaja in oplesku s temeljno barvo popleskana z rumeno barvo. Preizkus trdnosti in tesnosti notranje instalacije po DVGW TRGI G 600 april 2008 Varnostni ukrepi med izvajanjem preizkusov: Zaradi stisljivosti plinov je treba pri izvajanju preizkusa trdnosti poskrbeti za ustrezne varnostne ukrepe. Maksimalni preizkusni tlak je 1 bar (pri testu napeljave do 100mbar) in 3bare (pri testu napeljave do 1bar) ter ne sme biti prekoračen. Preprečiti je potrebno vsako nenadno zvišanje tlaka v preskušanem delu plinske napeljave. Preskusi se v skladu z G600-2008 izvajajo bodisi z zrakom ali z inertnim plinom (npr. dušik). Preskusi se v skladu s 'sposobnostjo za obratovanje' praviloma izvajajo z distribuiranim plinom. Uporaba kisika je prepovedana. Preizkus plinske napeljave do vključno 100mbar (točka 5.6.4.) Za plinske napeljave z delovnimi tlaki do vključno 100mbar so predpisani naslednji preskusi:

a) Preskus trdnosti; b) Preskus tesnosti

Vsa armatura in cevi morajo imeti atest. Celotno instalacijo preizkušamo brez armature preden je prekrita, ometana ali prepleskana. Preizkus se vrši z inertnim plinom (npr. dušik). Uporaba kisika je prepovedana. Preskus trdnosti Preskus trdnosti je treba izvesti pred preskusom tesnosti in zajema samo napeljavo, to pomeni brez armatur, regulatorjev tlaka plina, plinomerov ter plinskih trošil in pripadajočih varnostnih naprav. Armature so lahko vključene v preskus, če je njihov maksimalni dovoljeni delovni tlak najmanj enak preskusnemu tlaku. Preskusni tlak znaša 1 bar in se med časom preskušanja 10 minut ne sme znižati. Ločljivost uporabljene merilne naprave mora biti najmanj 0,1 bar. Po izvedenem preskusu trdnosti je treba preskusni tlak sprostiti iz plinske napeljave na varen način. Pri tem je treba iz vseh delov napeljave izpihati morebitno neizogibno umazanijo, ki je ostala v ceveh po montažnih delih.

Page 13: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 13 od 16

Preskus tesnosti Preskus tesnosti je treba izvesti po preskusu trdnosti in obsega plinsko napeljavo vključno z armaturami, vendar brez plinskih trošil ter pripadajočih regulacijskih in varnostnih armatur. Preskus tesnosti lahko zajema tudi regulatorje tlaka in / ali plinomere, v kolikor so le-ti dimenzionirani za preizkusni tlak. Preskusni tlak mora biti najmanj 150 mbar in se med časom preskušanja ne sme znižati. Upoštevati je potrebno ustrezen čas prilagoditve za izravnavo temperature v odvisnosti od volumna plinske napeljave: Volumen plinske napeljave Čas prilagajanja Min. trajanje preskusa < 100 l 10 min 10 min ≥ 100 l < 200 l 30 min 20 min ≥ 200 l 60 min 30 min Ločljivost uporabljene merilne naprave mora biti najmanj 0,1 bar. Po izvedenem preskusu trdnosti je treba preskusni tlak sprostiti iz plinske napeljave na varen način. Varnostni ukrepi med izvajanjem preskusov: Preskus in spuščanje plina v instalacijo bodo izvedli Plinovodi d.o.o. ali njihov pooblaščen izvajalec, ki je opremljen z vsemi potrebnimi dovoljenji in certifikati za tovrstne posege na plinskih instalacijah. Spuščanje plina v plinsko instalacijo se mora izvesti po predpisih, ki izvirajo iz standarda DVGW TRGI in iz odredb iz standarda DIN 3381. NASTAVITEV IN PREIZKUS DELOVANJA TROŠIL Pri nastavitvi in preizkusu delovanja trošil je potrebno upoštevati proizvajalčeva navodila za vgradnjo in obratovanje. Na osnovi oznake trošil je pred zagonom potrebno ugotoviti, če so trošila primerna za območje Wobbe indeksa, ki ga ima plin, ki je predviden za oskrbo. Ugotoviti je tudi potrebno, če so trošila primerna za predvideni priključni tlak. Trošilo je potrebno nastaviti na nazivno toplotno obremenitev. PODUK UPORABNIKOM Uporabnike napeljave je potrebno podučiti, še posebej pa jim je potrebno predati navodila za uporabo trošil. Opozoriti jih je potrebno na nujnost rednega vzdrževanja plinskih trošil. Poučiti jih je potrebno o ukrepih, ki so bili uporabljeni za dovod zgorevalnega zraka in odvod dimnih plinov in jih opozoriti, da se jih ne sme naknadno spreminjati. Posebej varnostne ukrepe pri uporabi in servisiranju plinskih trošil ni potrebno posebej poudarjati, ker se v MRP gibljejo samo usposobljene osebe Plinovodi d.o.o., ki zelo dobro poznajo ukrepe za varno delo v MRP.

Page 14: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 14 od 16

PRERAČUN PLINSKE INŠTALACIJE OD PLINOMERA NAPREJ ZA OBE SPTE 50mbar

PODATKI ZA TROŠILA:

I. FAZA: Tip enote SPTE Priključna moč plinskih

trošil (kW) Poraba plina

(Sm³/h) Električna moč

(kW) Plinska kotla 2 x 170kW

(eden rezerva) 170 19 /

ECE POWER - XRGI 9G-TO – I.faza 31 3,3 9

SKUPAJ 201 22,3 9

II. FAZA:

Tip enote SPTE Priključna moč plinskih

trošil (kW) Poraba plina

(Sm³/h) Električna moč

(kW)

Plinska kotla 170kW x 2 170 19 /

ECE POWER - XRGI 9G-TO – I.faza 31 3,3 9

ECE POWER - XRGI 20G-TO – II.faza 65 6,8 20

SKUPAJ 266 29,1 29

Max. inštalirana plinska moč 96 kW

Spodnja kurilna vrednost plina 9,5 kWh/Nm3

Max. normna poraba plina 10,86 Nm3/h

IZRAČUN POGONSKEGA STANJA PLINA

Temperatura plina 15 °C

Tlak plina 50 mbar

Zunanji barometrski tlak 980 mbar

Faktor redukcije 0,97

Pogonsko stanje plina 11,16 Sm3/h

Absolutna srednja višina hrapavosti k 0,99

Izračun temelji na priporočenih max. hitrostih plina v cevovodu vodvisnosti od tlaka plina (po Rombahu)

Priporočena max. hitrost plina 6 m/s

Potreben presek cevi 516,6 mm2

Potreben notranji presek cevi 25,65 mm

Ustreza cev DN32 z notranjim premerom 37,2 mm

Dejanska hitrost v cevi 2,85 m/s

Page 15: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 15 od 16

4. TEHNIČNE RISBE

► OGREVANJE SPTE – I. faza - tloris kotlovnice M 1:50 S1

► OGREVANJE SPTE – II. faza - tloris kotlovnice M 1:50 S2

► OGREVANJE SPTE – I. faza – tehnološka shema kotlovnice M 1:X S3

► OGREVANJE SPTE – II. faza – tehnološka shema kotlovnice M 1:X S4

► PLINSKA INŠTALACIJA SPTE – I. faza – tloris kotlovnice M 1:50 S5

► PLINSKA INŠTALACIJA SPTE – II. faza – tloris kotlovnice M 1:50 S6

► PLINSKA INŠTALACIJA SPTE – I. faza – plinska shema kotlovnice M 1:X S7

► PLINSKA INŠTALACIJA SPTE – II. faza – plinska shema kotlovnice M 1:X S8

Page 16: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 PZR 25/16-S

Vzdrževalni center Maribor - PZR - strojne inštalacije - 20.10.2016.doc Stran 16 od 16

5. PRILOGE

- diagrami potrebne toplote v MRP

- podatki o izbranih obtočnih črpalkah

Page 17: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Št. Opis materiala in del EM Kol. Cena/EM ZNESEKEUR EUR

REKAPITULACIJA :

01 MRP Maribor SPTE - I. faza kpl 1,00 0,00

02 Predelava obstoječega sistema kpl 1,00 0,00

01 MRP Maribor SPTE - II. faza kpl 1,00 0,00

SKUPAJ BREZ DDV: 0,0DDV 22% 0,00

SKUPAJ Z DDV: 0,0

Stran 1 od 11

Page 18: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

20.10.2016

Cena/enota Cena1. Enota SPTE: EC POWER - XRGI 9G-TO Qtopl=20kW,

Pel=9kW, Psk=31kW, z izmenjevalnikom izpušnih plinov, v toplotno in zvočno izoliranem ohišju, dimniškim setom, dušilcem, skupaj s priključnímí kosi, odvodno tuljavo ustrezne višine, koleni oz, ustreznim setom za priklop na dimniški sistem, skupaj s pritrdilnim in montažnim materialom. Dobavljeno skupaj z navodili v slovenskem jeziku, postavitvijo, priključitvijo, poučevanjem osebja ter zagonom - ali odgovarjajoče

kpl 1 0,00

2. Toplotni izmenjevalec EC POWER Q20 - ali odgovarjajoče kpl 1 0,00

3. Krmilna omara EC POWER iQ10 - ali odgovarjajoče kpl 1 0,00

4. Fleksibilne cevi DN32 za povezavo SPTE enote in izmenjevalca EC POWER - ali odgovarjajoče

kos 2 0,00

5. Nadzor zalogovnika (Storage control) EC POWER komplet s štirimi potopnimi tipali za zalogovnik - 4x PT 100 sensor, 3m kabla za senzor, 10m mrežnega kabla, montaža potopnih tipal, 4 potopne tulke

kpl 1 0,00

6. Kondenzacijska enota izpušnih plinov EC POWER - ali odgovarjajoče

kos 1 0,00

7. Polnilni ventil 1/2'' z notranjim navojem (montaža na toplotni izmenjevalec)

kos 2 0,00

8. Hranilnik tople vode 1000 l (po skici): iz jeklene pločevine ST37/2, s toplotno izolacijo, s štirimi tulkami za potopna tipala in 6. navojnimi priključki DN50 (2'')

kpl 1 0,00

9. Raztezna posoda ZILMET CAL PRO V150L, vključno z varnostnim ventilom DN20, 3 bar in zapornim ventilom DN20 varovanim proti nepooblaščenemu zaprtju ventila - ali odgovarjajoče

kpl 1 0,00

10. Obtočna črpalka s s prigrajenim frekvenčnim pretvornikom, s navojnimi priključki, navojnimi holandci, izolacijo, skupaj s tesnilnim in vijačnim materialom

0,00

Za opremo in material, ki se vgrajuje v objekt mora izvajalec del predložiti ustreznadokazila kvalitete ( ves vgrajeni material mora biti najboljše kakovosti in izdelan poSIST, EN, DIN standardih in mora imeti ustrezni certifikat oz. atest proizvajalca ) inostale spremne dokumente. Montažna dela se lahko izvajajo pod vodstvom strokovnousposobljenega vodje del in v soglasju z nadzorom. Kot opcija se dovoljuje izbira ustrezne druge opreme kot je projektirana ter se navedezraven predvidene opreme; ustrezati mora predvidenim projektnim in tehničnimparametrom, kar morata pisno potrditi investitor in projektant. Pred izvedbo je potrebno preveriti ali nabavljena oprema ustreza projektnim zahtevamin gradbenemu stanju objekta. Če ni posebej navedeno, se pri vsaki poziciji upoštevatudi montaža.VSI ELEMENTI, KI SO V STIKU Z OGREVALNO VODO MORAJO BITI ODPORNI NA40% GLIKOL!

POPISI STROJNE INŠTALACIJE

Inštalacija enote SPTE EC POWER 9kWe -

MRP MARIBOR - I. faza

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 2 od 11

Page 19: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

IMP PUMPS EGHN 32-180 s prigrajenim frekvenčnim pretvornikom (0-10V)0, 96kW, dT=30°C, 2,8m3/h, h=1,5m PN6, 0,06kW - ali odgovarjajoče

kpl 1 0,00

11. Ultrazvočni merilnik pretoka za SPTE s toplotnim števcem ALLMESS ENERKON - CF ECHO II 10 - 300, PN 16, navojni, 10m3/h DN40 + M-bus kartica (dajalnik impulzov), -za vgradnjo v horizontalni ali vertikalni položaj, primeren za dvižne in padajoče vode - računska enote za temp. območje 0…180°C z optičnim vmesnikom ZVEI - merilnik pretoka do Qn 20m3/h ter tem. območja do 130°C - 2 x temperaturno tipalo Pt 100 do 130°C s potopnimi tulkami - impulzna vrednost računske enote in merilnika pretoka odvisna od nazivnega pretoka - standardna dol. kabla temp. tipal: 3m, dol. kabla merilnika pretoka: 10m - ves pritrdilni in montažni material - ali odgovarjajoče

kpl 1 0,00

IZPUŠNI SISTEM

12. Izolirana cev fi84 x 2 iz kislinsko odpornega nerjavečega jekla AISI 316 (W.Nr. 1.4404) varjene izvedbe za navezavo iz SPTE do dimne tuljave z vsemi fazonskimi, priključnimi kosi in pritrdilnimi elementi. Izpušna cev iz kislinsko odpornega nerjavečega jekla je nadtlačni odvodnik izpušnih plinov in mora zadostovati pogojem DVGW G600 TRGI za plinska trošila skupine B, ki so odvisna od zraka v prostoru. Cevi morajo biti nepropustne in tlačno odporne do tlaka 5000 Pa (Tip H1 ali H2) in temperaturne odpornosti razreda T160, montaža z vsem pritdilnim materialom.

m 8 0,00

13. Cev fi84 x 2 iz kislinsko odpornega nerjavečega jekla AISI 316 (W.Nr. 1.4404) varjene izvedbe za navezavo iz SPTE vertikalno skozi streho z vsemi fazonskimi, priključnimi kosi in pritrdilnimi elementi. Izpušna cev iz kislinsko odpornega nerjavečega jekla je nadtlačni odvodnik izpušnih plinov in mora zadostovati pogojem DVGW G600 TRGI za plinska trošila skupine B, ki so odvisna od zraka v prostoru. Cevi morajo biti nepropustne in tlačno odporne do tlaka 5000 Pa (Tip H1 ali H2) in temperaturne odpornosti razreda T160, montaža z vsem pritdilnim materialom.

m 4 0,00

14. Projekt za dimnikarsko soglasje z dimnikarskim soglasjem kpl 1 0,00

15. Črna jeklena brezšivna cev izdelana po EN 10216-2 ter DIN 2448, iz materiala St35.8, atestirana po EN 10204, skupaj s fitingi (T kosi, kolena, spojke, redukcije…), fazonskimi kosi, varilnim in obešalnim materialom ter dvakratnim popleskom z antikorozijsko barvo po predhodnem čiščenju ter odstranitvi korozije, ( + 5 % za razrez)

f 33,7 x 2,6 mm (DN25) m 6 0,00

f 42,4 x 2,6 mm (DN32) m 6 0,00

f 60,3 x 2,9 mm (DN50) m 20 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 3 od 11

Page 20: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

16. Izolacijski cevaki za izolacijo ogrevalnih cevi - Tubolit/armacell, material negorljiv, razreda B1 po DIN 4102

f 33,7 x 2,6 mm (DN25) - (19mm izolacije) m 6 0,00

f 42,4 x 2,6 mm (DN32) - (19mm izolacije) m 6 0,00

f 60,3 x 2,9 mm (DN50) - (25mm izolacije) m 20 0,00

17. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom temeljne barve

m2 4,5 0,00

18. Krogelni ventil / navojni

DN32 kos 6 0,00

DN50 kos 8 0,00

19. Ravni lovilec nečistoč s fino mrežico iz nerjavečega materialaza vodo 90°C in tlak 6 bar, pritrdilni in tesnilni material, DN50 /PN6-navojni

kos 1 0,00

20. Protipovratni ventil z notranjim navojnim priključkom, okrov iz medi, z ročico za odpiranje, PN 6, tesnilni material DN50 / PN6-navojni

kos 1 0,00

21. Poševnosedežni ventil za hidravlično uravnovešanje z navojnim priključkom PN 20 namenjen za delovno temperaturo od –20°C do 120°C. Ventil ima proporcionalno karakteristiko dušenja, merilne priključke za instrument za nastavljanje pretoka, ročno nastavitveno kolo z numerično skalo, funkcijo zapornega elementa, (s priključkom za izpust vode oz. signalni vod). Postavka vključuje nastavitev pretoka s pomočjo merilnega instrumenta in izdelavo zapisnika o doseženih pretokih, tesnilni material, kot npr. proizvod TA– IMI International, tip STAD ali enakovredno - DN 25

kos 1 0,00

22. Termo-manometer, premer okrova 80 mm, priključni nastavek R ¼, na hrbtni strani, vključno s protipovratnim elementom R ½ , merilno območje za temp. 0-120°C, za tlak 0-4 bar

kos 4 0,00

23. Cev PP fi32 za odvod kondenza z armaflex izolacijo m 6 0,00

24. Izdelava preboja skozi steno za kondenčno cev fi32 in ureditev zatesnitve stene, navezava na zunanji jašek

kpl 1 0,00

25. Avtomatski odzračevalni lonček, vključno s pritrdilnim in tesnilnim materialom

kos 2 0,00

26. Polnilno-praznilna pipa DN 15 z nastavkom za gumi cev kos 3 0,00

27. Izdelava preboja skozi steno za izpušno cev fi80 in ureditev zatesnitve stene

kpl 1 0,00

28. Navezava na obstoječ ogrevalni sistem kpl 1 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 4 od 11

Page 21: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

29. Polnjenje sistema z mešanico 40% glikol - cca. 1200l kpl 1 0,00

30. Pripravljalna dela, pregled dokumentacije, zarisovanje, transportni in manipulativni stroški, montaža, tesnostni in tlačni preizkus, funkcionalni zagon, ureguliranje sistema, preizkusno obratovanje, zaključna dela, čiščenje in ostala dela

kpl 1 0,00

31. Navodila za obratovanje in vzdrževanje v slovenskem jeziku kpl 1 0,00

32. Označitev smeri pretokov, napisne ploščice kpl 1 0,00

33. Shema vezave enot SPTE v okvirju zaščitenim s steklom kpl 1 0,00

34. Izdelava PZI dokumentacije kpl 1 0,00

35. Projektantski nadzor kpl 1 0,00

36. Vris vseh sprememb glede na PZI strojnih inštalacij s strani izvajalca del ter predaja izdelovalcu prikaza izvedenih del (PID)

kpl 1 0,00

37. Izdelava PID dokumentacije kpl 1 0,00

38. Nepredvidena dela v višini 5% investicijske vrednosti kpl 1 0,00

PLINSKA INŠTALACIJA

39. Jeklena brezšivna cev za plinsko napeljavo po DIN 2440, St35.8, skupaj z varilnimi loki in pritrdilnim materialom

DN25 (33,7 x 2,6) m 3 0,00

DN32 (42,4 x 2,6) m 10 0,00

40. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom temeljne barve

m2 1,8 0,00

41. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom končne rumene barve za plin

m2 1,8 0,00

42. Plinski zaporni ventil DN32 kos 2 0,00

43. MEHOVNI PLINOMER BK-G10, max. 16m3/h, DN32 1 0,00

44. Fleksibilna plinska cev DN20 dolžine 800mm za povezavo SPTE enote z fiksno cevjo EC POWER - ali odgovarjajoče

kos 1 0,00

45. Plinski filter DUNGS GF 507/1 - 1'' navojni kos 1 0,00

46. R kos DN25/DN20 kos 1 0,00

47. Manometer (0-60mbar) kos 1 0,00

48. Termični zaporni element s 60 minutnim tesnjenjem pri 925°C tip TAS proizvajalca TECO DN20

kos 1 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 5 od 11

Page 22: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

49. Navezava na obstoječ plinski razvod kpl 1 0,00

50. Preizkušanje plinske inštalacije, spuščanje plina iz in po končanju v inštalacijo, montaža, zaključna dela, regulacija, preizkusno obratovanje, zagon

kpl 1 0,00

51. Nepredvidena dela v višini 5% investicijske vrednosti kpl 1 0,00

Skupaj 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 6 od 11

Page 23: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

20.10.2016

Cena/enota Cena1. Obtočna črpalka s tremi hitrostmi regulacije vrtljajev, s

prirobničnimi priključki, proti prirobnicami, izolacijo, skupaj s tesnilnim in vijačnim materialom

GRUNDFOS UPS 65-30F, 15m3/h, h=1,5m PN6/10, 0,2kW kpl 2 0,00

2. Obtočna črpalka s tremi hitrostmi regulacije vrtljajev, s navojnimi priključki, navojnimi holandci, izolacijo, skupaj s tesnilnim in vijačnim materialom

GRUNDFOS UPS 25-40, 130, 2m3/h, h=1,5m PN6/10, 0,06kW

kpl 1 0,00

3. Tripotna mešalna pipa s prirobničnimi priključki, skupaj s tesnilnim materialom, proti prirobnicami, vijačnim materialom, tesnili ter elektromotornim pogonom s tritočkovnim regulacijskim signalom

kpl 1

DANFOSS tip HFE 3 - DN80 / 150 kpl 1 0,00

4. Ultrazvočni merilnik pretoka s toplotnim števcem ALLMESS ENERKON - CF ECHO II 15 - 270, PN 16, prirobnični, 15m3/h DN50 + M-bus kartica (dajalnik impulzov), -za vgradnjo v horizontalni ali vertikalni položaj, primeren za dvižne in padajoče vode - računska enote za temp. območje 0…180°C z optičnim vmesnikom ZVEI - merilnik pretoka do Qn 15m3/h ter tem. območja do 130°C - 2 x temperaturno tipalo Pt 100 do 130°C s potopnimi tulkami - impulzna vrednost računske enote in merilnika pretoka odvisna od nazivnega pretoka - standardna dol. kabla temp. tipal: 3m, dol. kabla merilnika pretoka: 10m - ves pritrdilni in montažni material

kpl 1 0,00

5. Strojna predelava, vgradnja mešalne pipe, obtočnih črpalk, toplotnega števca

kpl 1 0,00

POPISI STROJNE INŠTALACIJE

Predelava obstoječe inštalacije - MRP MARIBOR

Za opremo in material, ki se vgrajuje v objekt mora izvajalec del predložiti ustreznadokazila kvalitete ( ves vgrajeni material mora biti najboljše kakovosti in izdelan poSIST, EN, DIN standardih in mora imeti ustrezni certifikat oz. atest proizvajalca ) inostale spremne dokumente. Montažna dela se lahko izvajajo pod vodstvom strokovnousposobljenega vodje del in v soglasju z nadzorom. Kot opcija se dovoljuje izbira ustrezne druge opreme kot je projektirana ter se navedezraven predvidene opreme; ustrezati mora predvidenim projektnim in tehničnimparametrom, kar morata pisno potrditi investitor in projektant. Pred izvedbo je potrebno preveriti ali nabavljena oprema ustreza projektnim zahtevamin gradbenemu stanju objekta. Če ni posebej navedeno, se pri vsaki poziciji upoštevatudi montaža.VSI ELEMENTI, KI SO V STIKU Z OGREVALNO VODO MORAJO BITI ODPORNI NA40% GLIKOL!

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 7 od 11

Page 24: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

6. LŽ medprirobnična zaporna loputa, skupaj z EPDM tesnili, ročico za posluževanje, protiprirobnicama ter tesnilnim in vijačnim materialom DN80, PN 6

kos 4 0,00

7. Medprirobnična protipovratna loputa, skupaj s protiprirobnicama, tesnilnim in vijačnim materialom DN80, PN 6

kos 2 0,00

8. Lovilec nesnage s prirobničnima priključkoma, z drobno zankastim sitom (velikost zank 0,4 mm) ter magnetnim vložkom, skupaj s protiprirobnicama, tesnilnim in vijačnim materialom DN80, PN 6

kos 2 0,00

9. Črna jeklena brezšivna cev izdelana po EN 10216-2 ter DIN 2448, iz materiala St35.8, atestirana po EN 10204, skupaj s fitingi (T kosi, kolena, spojke, redukcije…), fazonskimi kosi, varilnim in obešalnim materialom ter dvakratnim popleskom z antikorozijsko barvo po predhodnem čiščenju ter odstranitvi korozije, ( + 5 % za razrez)

f 88,9 x 3,2 mm (DN80) m 12 0,00

10. Izolacijski cevaki za izolacijo ogrevalnih cevi - Tubolit/armacell, material negorljiv, razreda B1 po DIN 4102 - izolirajo se tudi obstoječe cevi

f 88,9 x 3,2 mm (DN80) - 32mm izolacije m 16 0,00

11. Prevezava dveh grelnikov plina v zaporedno vezavo, zdaj sta povezana vzporedno - potrebna izredna pazljivost, ker se dela izvajajo v ex coni plinske postaje, prostor mora biti dobro prezračevan, stalno spremljanje koncentracije plina

kpl 1 0,00

12. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom temeljne barve

m2 2,0 0,00

13. Navodila za obratovanje in vzdrževanje v slovenskem jeziku kpl 1 0,00

14. Označitev smeri pretokov, napisne ploščice kpl 1 0,00

15. Nepredvidena dela v višini 5% investicijske vrednosti kpl 1 0,00

Skupaj 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 8 od 11

Page 25: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

20.10.2016

Cena/enota Cena1. Enota SPTE: EC POWER - XRGI 20G-TO Qtopl=40kW,

Pel=20kW, Psk=65kW, z izmenjevalnikom izpušnih plinov, v toplotno in zvočno izoliranem ohišju, dimniškim setom, dušilcem, skupaj s priključnímí kosi, odvodno tuljavo ustrezne višine, koleni oz, ustreznim setom za priklop na dimniški sistem, skupaj s pritrdilnim in montažnim materialom. Dobavljeno skupaj z navodili v slovenskem jeziku, postavitvijo, priključitvijo, poučevanjem osebja ter zagonom - ali odgovarjajoče

kpl 1 0,00

2. Toplotni izmenjevalec EC POWER Q80 - ali odgovarjajoče kpl 1 0,00

3. Krmilna omara EC POWER iQ20 - ali odgovarjajoče kpl 1 0,00

4. Fleksibilne cevi DN32 za povezavo SPTE enote in izmenjevalca EC POWER - ali odgovarjajoče

kos 2 0,00

5. Kondenzacijska enota izpušnega sistema - ali odgovarjajoče kos 1 0,00

6. Load sharer EC POWER - ali odgovarjajoče kos 1 0,00

7. Polnilni ventil 1/2'' z notranjim navojem (montaža na toplotni izmenjevalec)

kos 2 0,00

IZPUŠNI SISTEM

8. Izolirana cev fi84 x 2 iz kislinsko odpornega nerjavečega jekla AISI 316 (W.Nr. 1.4404) varjene izvedbe za navezavo iz SPTE do dimne tuljave z vsemi fazonskimi, priključnimi kosi in pritrdilnimi elementi. Izpušna cev iz kislinsko odpornega nerjavečega jekla je nadtlačni odvodnik izpušnih plinov in mora zadostovati pogojem DVGW G600 TRGI za plinska trošila skupine B, ki so odvisna od zraka v prostoru. Cevi morajo biti nepropustne in tlačno odporne do tlaka 5000 Pa (Tip H1 ali H2) in temperaturne odpornosti razreda T160, montaža z vsem pritdilnim materialom.

m 6 0,00

POPISI STROJNE INŠTALACIJE

Inštalacija enote SPTE EC POWER 20kWe -

MRP MARIBOR - II. faza

Za opremo in material, ki se vgrajuje v objekt mora izvajalec del predložiti ustreznadokazila kvalitete ( ves vgrajeni material mora biti najboljše kakovosti in izdelan poSIST, EN, DIN standardih in mora imeti ustrezni certifikat oz. atest proizvajalca ) inostale spremne dokumente. Montažna dela se lahko izvajajo pod vodstvom strokovnousposobljenega vodje del in v soglasju z nadzorom. Kot opcija se dovoljuje izbira ustrezne druge opreme kot je projektirana ter se navedezraven predvidene opreme; ustrezati mora predvidenim projektnim in tehničnimparametrom, kar morata pisno potrditi investitor in projektant. Pred izvedbo je potrebno preveriti ali nabavljena oprema ustreza projektnim zahtevamin gradbenemu stanju objekta. Če ni posebej navedeno, se pri vsaki poziciji upoštevatudi montaža.VSI ELEMENTI, KI SO V STIKU Z OGREVALNO VODO MORAJO BITI ODPORNI NA40% GLIKOL!

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 9 od 11

Page 26: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

9. Cev fi84 x 2 iz kislinsko odpornega nerjavečega jekla AISI 316 (W.Nr. 1.4404) varjene izvedbe za navezavo iz SPTE vertikalno skozi streho z vsemi fazonskimi, priključnimi kosi in pritrdilnimi elementi. Izpušna cev iz kislinsko odpornega nerjavečega jekla je nadtlačni odvodnik izpušnih plinov in mora zadostovati pogojem DVGW G600 TRGI za plinska trošila skupine B, ki so odvisna od zraka v prostoru. Cevi morajo biti nepropustne in tlačno odporne do tlaka 5000 Pa (Tip H1 ali H2) in temperaturne odpornosti razreda T160, montaža z vsem pritdilnim materialom.

m 4 0,00

10. Projekt za dimnikarsko soglasje z dimnikarskim soglasjem kpl 1 0,00

11. Črna jeklena brezšivna cev izdelana po EN 10216-2 ter DIN 2448, iz materiala St35.8, atestirana po EN 10204, skupaj s fitingi (T kosi, kolena, spojke, redukcije…), fazonskimi kosi, varilnim in obešalnim materialom ter dvakratnim popleskom z antikorozijsko barvo po predhodnem čiščenju ter odstranitvi korozije, ( + 5 % za razrez)

f 42,4 x 2,6 mm (DN32) m 8 0,00

12. Izolacijski cevaki za izolacijo ogrevalnih cevi - Tubolit/armacell, material negorljiv, razreda B1 po DIN 4102

f 42,4 x 2,6 mm (DN32) - (19mm izolacije) m 8 0,00

13. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom temeljne barve

m2 2,0 0,00

14. Krogelni ventil / navojni

DN32 kos 4 0,00

15. Termo-manometer, premer okrova 80 mm, priključni nastavek R ¼, na hrbtni strani, vključno s protipovratnim elementom R ½ , merilno območje za temp. 0-120°C, za tlak 0-4 bar

kos 2 0,00

16. Cev PP fi32 za odvod kondenza z armaflex izolacijo m 2 0,00

17. Avtomatski odzračevalni lonček, vključno s pritrdilnim in tesnilnim materialom

kos 2 0,00

18. Polnilno-praznilna pipa DN 15 z nastavkom za gumi cev kos 1 0,00

19. Izdelava preboja skozi steno za izpušno cev fi80 in ureditev zatesnitve stene

kpl 1 0,00

20. Navezava na obstoječ ogrevalni sistem kpl 1 0,00

21. Polnjenje sistema z mešanico 40% glikol - cca. 100l kpl 1 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 10 od 11

Page 27: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

22. Pripravljalna dela, pregled dokumentacije, zarisovanje, transportni in manipulativni stroški, montaža, tesnostni in tlačni preizkus, funkcionalni zagon, ureguliranje sistema, preizkusno obratovanje, zaključna dela, čiščenje in ostala dela

kpl 1 0,00

23. Navodila za obratovanje in vzdrževanje v slovenskem jeziku kpl 1 0,00

24. Označitev smeri pretokov, napisne ploščice kpl 1 0,00

25. Shema vezave enot SPTE v lesenem okvirju zaščitenim s steklom

kpl 1 0,00

26. Izdelava PZI dokumentacije kpl 1 0,00

27. Projektantski nadzor kpl 1 0,00

28. Vris vseh sprememb glede na PZI strojnih inštalacij s strani izvajalca del ter predaja izdelovalcu prikaza izvedenih del (PID)

kpl 1 0,00

29. Izdelava PID dokumentacije kpl 1 0,00

30. Nepredvidena dela v višini 5% investicijske vrednosti kpl 1 0,00

PLINSKA INŠTALACIJA

31. Jeklena brezšivna cev za plinsko napeljavo po DIN 2440, St35.8, skupaj z varilnimi loki in pritrdilnim materialom

DN25 (33,7 x 2,6) m 3 0,00

32. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom temeljne barve

m2 0,4 0,00

33. Antikorozijska zaščita cevovodov, obešalnega in pritrdilnega materiala, vključno s čiščenjem in dvakratnim premazom končne rumene barve za plin

m2 0,4 0,00

34. Fleksibilna plinska cev DN20 dolžine 800mm za povezavo SPTE enote z fiksno cevjo EC POWER - ali odgovarjajoče

kos 1

35. Plinski filter DUNGS GF 507/1 - 1'' navojni kos 1 0,00

36. R kos DN25/DN20 kos 1 0,00

37. Manometer (0-60mbar) kos 1 0,00

38. Termični zaporni element s 60 minutnim tesnjenjem pri 925°C tip TAS proizvajalca TECO DN20

kos 1 0,00

39. Navezava na obstoječ plinski razvod kpl 1 0,00

40. Preizkušanje plinske inštalacije, spuščanje plina iz in po končanju v inštalacijo, montaža, zaključna dela, regulacija, preizkusno obratovanje, zagon

kpl 1 0,00

41. Nepredvidena dela v višini 5% investicijske vrednosti kpl 1 0,00

Skupaj 0,00

MRP Maribor - SPTE_PZR_strojne_instalacije-20.10.2016.xls 11 od 11

Page 28: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 29: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 30: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 31: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 32: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 33: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 34: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 35: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 36: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

1. NASLOVNA STRAN NAČRTA

ŠTEVILČNA OZNAKA NAČRTA IN VRSTA NAČRTA:

NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4

INVESTITOR:

Plinovodi d.o.o. Cesta Ljubljanske brigade 11b, 1000 LJUBLJANA

OBJEKT:

VGRADNJA ENOTE SPTE V KOTLOVNICO MRP, na parc. št. 772, 773, k.o. BOHOVA

PRI VZDRŽEVALNEM CENTRU MARIBOR, Bohova 19b, 2311 HOČE

VRSTA PROJEKTNE DOKUMENTACIJE:

PZR- PROJEKT ZA RAZPIS

ZA GRADNJO:

INVESTICIJSKO VZDRŽEVANJE

PROJEKTANT: EL PART

Bogdan Lepan s.p. Cesta na Bellevue 3 3250 Rogaška Slatina M.P. Tel. 03 819 0668 GSM 041 389 070

e-mail [email protected] ODGOVORNA OSEBA PROJEKTANTA:

Bogdan LEPAN, dipl.inž.el. M.P. E-0963 ŠTEVILKA NAČRTA, KRAJ IN DATUM IZDELAVE NAČRTA: PZR 69/16-E, Rogaška Slatina, oktober 2016 ŠTEVILKA IZVODA:

1 2 3 4 5 6

Page 37: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 2

2. KAZALO VSEBINE NAČRTA ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

1. NASLOVNA STRAN NAČRTA .......................................................................................... 1

2. KAZALO VSEBINE NAČRTA ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E .................................................................................................... 2

3. TEHNIČNO POROČILO ...................................................................................................... 3

3.1. Projektna naloga .............................................................................................................. 3

3.2. Lokacija objekta .............................................................................................................. 3

3.3. SPTE- kogeneracija splošno............................................................................................ 3

3.4. Zaščita na ločilnem mestu ............................................................................................... 4

4. SPTE VZDRŽEVALNI CENTER MARIBOR- VARIANTA 1 ........................................... 5

4.1. Izvedba priklopa SPTE enote .......................................................................................... 5

4.2. Tehnični podatki enote SPTE XRGI 9G-TO .................................................................. 5

4.3. Priključno mesto enote SPTE .......................................................................................... 6

4.4. Merilno mesto enote SPTE ............................................................................................. 6

4.5. Podatki o planirani proizvodnji ....................................................................................... 6

4.6. Ostale električne povezave .............................................................................................. 7

4.7. Izenačitev potenciala ....................................................................................................... 7

4.8. Opozorilo dvojnega napajanja ......................................................................................... 7

4.9. Tehnične risbe ................................................................................................................. 8

5. PRILOGA 1 ............................................................................................................................ 9

6. PRILOGA 2 .......................................................................................................................... 10

7. SPTE VZDRŽEVALNI CENTER MARIBOR- VARIANTA 2 ......................................... 11

7.1. Izvedba priklopa SPTE enote ........................................................................................ 11

7.2. Tehnični podatki enote SPTE XRGI 20G- TO ............................................................. 12

7.3. Podatki o planirani proizvodnji ..................................................................................... 12

7.4. Ostale električne povezave ............................................................................................ 12

7.5. Izenačitev potenciala ..................................................................................................... 13

7.6. Opozorilo dvojnega napajanja ....................................................................................... 13

7.7. Tehnične risbe ............................................................................................................... 13

8. PRILOGA 3 .......................................................................................................................... 14

Page 38: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 3

3. TEHNIČNO POROČILO

3.1. Projektna naloga

Za objekt VGRADNJA ENOTE SPTE V KOTLOVNICO MRP, na parc. št. 772, 773, k.o. BOHOVA, je potrebno izdelati projekt za razpis električnih inštalacij in sicer za priključitev ene in dveh enot za soproizvodnjo toplotne in električne energije v prostor kotlovnica, ki bosta priključeni na interno napeljavo (porabniško proizvodni priklop po Navodilih za

priključevanje in obratovanje elektrarn inštalirane moči do 10 MW). Enoti SPTE se bosta priključili na distribucijsko omrežje po tipski shemi P1.3.

3.2. Lokacija objekta

Objekt se nahaja na parc. št. 772, 773, k.o. Bohova. Lastnik parcel je Plinovodi d.o.o., Cesta Ljubljanske brigade 11b, 1000 Ljubljana.

3.3. SPTE- kogeneracija splošno

Soproizvodnja toplotne in električne energije, krajše soproizvodnja (SPTE), imenovana tudi kogeneracija, je proces sočasnega pretvarjanja energije goriva v toploto in električno energijo. Pri tem se uporablja električni generator, ki ga poganja mehanska energija vrtečih se delov motorjev oziroma turbin. Pri pretvorbi notranje energije goriv v mehansko se sprosti velika količina toplote, ki se pri tem načinu koristno uporabi.

O mikro soproizvodnji električne in toplotne energije govorimo takrat, ko generatorjeva moč ne preseže 50 kW. Soproizvodnja prinaša občutne prihranke primarne energije in

Page 39: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 4

zmanjšuje emisije CO2 v ozračje. Zaradi uporabe preostale toplote imajo soproizvodni sistemi celotni izkoristek med 80 in 90 %.

3.4. Zaščita na ločilnem mestu

Krmiljenje naprave vsebuje napetostno frekvenčne zaščite in meritev električne energije, ki so vgrajene v samo enoto SPTE. Po Sistemskih obratovalnih navodilih za distribucijsko omrežje električne energije (Uradni list RS št. 41/2011) se le te lahko smatrajo kot ločitev od omrežja (str. 5503).

Zaščito na ločilnem mestu je potrebno nastaviti tako, da ustreza zahtevam v Sistemskih obratovalnih navodilh za distribucijsko omrežje, kot je navedeno v nadaljevanju.

Parameter Največji dovoljen

čas delovanja (s)

Nastavitve

Prenapetostna zaščita (stopnja 2) 0,2 Un + 11 % ... + 15 %

Prenapetostna zaščita (stopnja 1) a 1,5 Un + 11 %

Podnapetostna zaščita (stopnja 1) b 1,5 Un – 15 %

Podnapetostna zaščita (stopnja 2) 0,2 Un – 15 % ... – 30 %

Nadfrekvenčna c 0,2 51 Hz

Podfrekvenčna c 0,2 47 Hz

Izpad omrežja d d d

a Prvo stopnjo prenapetostne zaščite se lahko opusti, če je druga stopnja prenapetostne zaščite nastavljena na Un + 11 %.

b Prvo stopnjo podnapetostne zaščite se lahko opusti, če je druga stopnja podnapetostne zaščite nastavljena na Un – 15 %.

c Podfrekvenčna zaščita mora biti sposobna delovati vsaj v območju, ki ga določajo maksimalne nastavitve delovanja napetostnih zaščit.

d Zaščito pred izpadom omrežja (kot so na primer skok kolesnega kota, df/dt, sprememba impedance omrežja) lahko zahteva SODO. V praksi je to dokaj zahtevna zaščita. Za njeno pravilno nastavitev potrebujemo natančne podatke omrežja, v katero je generator vključen. Težavo povzročajo vse spremembe v omrežju, ki spreminjajo pogoje za delovanje te zaščite (trenutna poraba, morebitno prenapajanje,…). Posledično slabo izračunana meja delovanja zaščite povzroči izpadanje generatorja po nepotrebnem ali pa nedelovanje zaščite ob izpadu omrežja. Zaradi tega ta zaščita načelno ni potrebna, razen če jo SODO v posameznih primerih posebej ne zahteva.

Page 40: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 5

4. SPTE VZDRŽEVALNI CENTER MARIBOR- VARIANTA 1

4.1. Izvedba priklopa SPTE enote

Investitor bo postavil mikro SPTE enoto tipa XRGI 9G- TO proizvajalca EC POWER A/S v smislu izboljšave, ki sledi napredku tehnike in omogoča učinkovito rabo primarne energije. Vgradnja soproizvodne enote je po Zakonu o graditvi objektov opredeljena kot investicijsko vzdrževalno delo.

Podatki za enoto SPTE: XRGI 9G- TO- Qtopl = 20 kW, Pel = 9 kW, proizvajalec EC POWER A/S.

Celotna proizvodna naprava SPTE je električno povezana. Iz enote SPTE se izvede povezava do njene komandne omare na zidu kotlovnice s kablom FG7OR 5G6 mm². Od tu dalje izvedemo povezavo do prostostoječe priključno-merilne omarice PS-PMO 1, ki je locirana ob ograji na stalno dostopnem mestu na zemljišču v lasti investitorja. Tu bo zmontiran nov števec za neto proizvedeno električno energijo (P2).

Iz omarice PS-PMO 1 poteka povezava naprej do glavnega razdelilnika objekta MRP, kjer se preko rezervnega varovalčnega podnožja priključimo na distribucijsko omrežje za obstoječim prevzemno predajnim mestom. Povezave od komandne omare proizvodne naprave SPTE do PS-PMO 1 in naprej do razdelilnika MRP se izvedejo s kabli FG7OR 5G25 mm².

Za merjenje prevzete električne energije iz distribucijskega omrežja je v obstoječi priključno-merilni omarici PMO zmontiran trifazni števec električne energije za odjem objekta. Z istim števcem se bo merila tudi proizvedena električna energija nove naprave SPTE, ki bo oddana v distribucijsko omrežje. Obstoječi števec za odjem se bo zamenjal s števcem za dvosmerne meritve.

4.2. Tehnični podatki enote SPTE XRGI 9G-TO

Osnovni podatki: Tip: SPTE XRGI 9G-TO Gorivo: Zemeljski plin Električna nazivna moč: 9 kW Toplotna nazivna moč: 20 kW Električni izkoristek: 30,6 % Toplotni izkoristek: 72,7 % Skupni izkoristek: 103,3 % Napetost/frekvenca: 3x230V/400V/50Hz Generator: Asinhronski trifazni generator

Page 41: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 6

4.3. Priključno mesto enote SPTE

Priključno mesto je točka porabniško proizvodnega priklopa enote SPTE v kateri so naprave uporabnika priključene na distribucijsko omrežje. V našem primeru je to razdelilnik MRP, kjer se bo izvršil priklop na interno omrežje za obstoječim merilno- predajnim mestom.

4.4. Merilno mesto enote SPTE

Meritve električne energije za neto proizvedeno energijo (merilno mesto št. 8012586 proizvodnja) bodo izvedene na napetostnem nivoju 0,4 kV za obstoječim prevzemno predajnim mestom za objekt. Lokacija merilnega mesta PS-PMO 1 je prikazana na risbi E1, zunanji izgled in razporeditev opreme pa na risbah E3 in E4 projekta. Iz kogeneracijske naprave s kablom FG7OR 5 x 25 mm² povežemo enoto SPTE do razdelilnika PS-PMO 1. Nato poteka vezava preko kontaktorja, direktnega trifaznega števca in 160 A 3-polnega varovalčnega ločilnika z varovalkami 3 x 16 A v razdelilnik MRP, kjer se priklopimo na interno omrežje preko varovalk C 20A za obstoječim prevzemno predajnim mestom. Za povezavo iz PS-PMO 1 v razdelilnik MRP se uporabi kabel FG7OR 5G25 mm². Novi števec neto proizvedene električne energije je direktni trifazni števec LANDIS GYR ZMD310CT44 s komunikacijskim modulom CU-P42. Delovanje kontaktorja je pogojeno s preklopko 0-1 in z varnostnim relejem DOLD v razdelilniku RL (ločilno mesto), ki blokirata njegov vklop. Shema vezave merilnega mesta je razvidna iz risb E5 in E6 projekta. Na merilnem mestu se zmontirajo prenapetostni odvodniki razreda I. in ključavnica elektrodistribucije.

Za merjenje prevzete električne energije iz distribucijskega omrežja je v priključno-merilni omarici PMO zmontiran trifazni števec električne energije. Meritve električne energije za prevzemno predajno mesto ostanejo izvedene na obstoječem odjemnem mestu za odjem (merilno mesto št. 4-1306- odjem) in za proizvedeno električno energijo, ki bo oddana v distribucijsko omrežje (merilno mesto 4-8012586- oddaja) z obstoječimi merilnimi napravami. Obstoječ števec za odjem se zamenja z direktnim trifaznim števec LANDIS GYR ZMD310CT44 s komunikacijskim modulom CU-P42. 4.5. Podatki o planirani proizvodnji

Za varianto 1 se planira 8.500 ur letnega obratovanje naprave. Letna proizvodnja ........................................................................................... 51.000 kWh Za lastne potrebe ............................................................................................ 40.800 kWh Za oddajo v DO .............................................................................................. 10.200 kWh

Proizvedena električna energija bo v večjem delu namenjena za lastne potrebe, višek

pa za oddajanje v javno distribucijsko omrežje.

Page 42: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 7

4.6. Ostale električne povezave

Razen močnostnih povezav je potrebno nekatere elemente povezati še s signalnimi kabli. Z opletenimi kabli se izvede povezava med enoto SPTE in njeno komandno omaro Komunikacijske povezave s kabli SFTP cat. 6 se izvedejo med enoto SPTE in njeno komandno omaro ter naprej do toplotnega izmenjevalca. Prosta komunikacijska vhoda se terminirata z 150 Ohm-skima uporoma.

Do toplotnega izmenjevalca (vtičnica 230 VAC pri izmenjevalcu) je potrebno pripeljati še napajanje 230 VAC. To se izvede s kablom OEL110 3x1,5 mm² iz razdelilnika MRP.

V kotlovnico se vgradi nov razdelilnik RR, ki bo napajan iz razdelilnika MRP. V njem bo vgrajen krmilnik Siemens vrste LOGO, ki bo na podlagi izstopne temperature zemeljskega plina in temperature rosišča zunanjega zraka reguliral gretje plina oz. krmilil mešalni ventil. V kotlovnici MRP sta vgrajena nizkotemperaturna kotla podjetja Viessmann, ki nista povezana v skupno regulacijo, zato se le- ta dogradi. Skupna kaskadna regulacija bo imela možnost krmiljenja izstopne temperature s signalom 0 ÷ 10 V.

Odvodna cev kondenza bo proti zmrzali varovana z grelnim elektro kablom. Dotrajan razdelilnik MRP se zamenja s tipskim razdelilnikom MRP Plinovodi.

4.7. Izenačitev potenciala

Za preprečevanje pojavljanja potencialnih razlik med različnimi kovinskimi deli se v objektu izvede izenačenje potencialov. Instalacija za izenačenje potenciala se izvede z vodnikom rumeno-zelene barve.

Z ozemljitveno žico HO7VK-Y 16 mm2 povežemo ohišje enote SPTE na obstoječe ozemljilo. Ozemljitvena upornost ozemljitve prenapetostnih odvodnikov mora biti manjša od 5 Ohmov. Za izvedbo ozemljitve PS-PMO 1 se uporabi pocinkani valjanec 25x4 mm. Položi se v jarek in spelje v priključno merilno omarico.

4.8. Opozorilo dvojnega napajanja

Opozorilni napis dvojnega napajanja objekta se prilepi: - na vrata obstoječega prevzemno predajnega mesta objekta, - v notranjost obstoječega prevzemno predajnega mesta, - ob števec neto proizvedene električne energije in - na enoto SPTE.

Opozorilo je v skladu s standardom Zahteve za vzporedno vezavo mikro generatorjev z javnim

nizkonapetostnim razdelilnim omrežjem (SIST EN 50438:2007). Primer opozorilne nalepke:

Page 43: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 8

4.9. Tehnične risbe

► Delni tloris objekta- dispozicija opreme- varianta 1 M 1:50 E1

► Delni tloris objekta- shema ogrevanja- varianta 1 M 1:50 E2

► Zunanji izgled razdelilnika PS PMO 1 M 1:10 E3

► Razpored opreme v razdelilniku PS PMO 1- varianta 1 M 1:5 E4

► Tripolna shema vezave razdelilnika PS PMO 1- varianta 1 M 1:X E5

► Enopolna shema vezave razdelilnika PS PMO 1- varianta 1 M 1:X E6 ► Zunanji izgled in razporeditev opreme v razdelilniku RL- ločilno mesto

M 1:X E7

► Tehnološka shema kotlovnice- varianta 1 M 1:X E8

Page 44: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 45: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 46: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 47: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 48: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

0 1 7 8 965432

FAZA DATUM IZDELAVE

PODPIS

PODPIS

ŠT.NAČRTA

ŠT. RISBE

Š t e v i l k a l i s t a 1

ELEKTROINŠTALACIJE

VRSTA NAČRTA:

SPREMEMBA:

l i s t o v

INVESTITOR NAROČNIK

od 1

VSEBINA RISBE

E5

PROJEKTANT:

EL PART, Bogdan LEPAN s.p.ODGOVORNI PROJEKTANT

Bogdan.LEPAN,dipl.inž.el.OBDELOVALEC

IZS E-0963IDENT.ŠT.PLINOVODI d.o.o.

Cesta Ljubljanske brigade 11b1000 LJUBLJANA

OBJEKT LOKACIJA

VGRADNJA ENOTE SPTE V KOTLOVNICOMRP, Bohova 19b, 2311 HOČEna parc. št. 733, k.o. BOHOVA

PZR 69/16-E

TRIPOLNA SHEMA VEZAVERAZDELILNIKA PS PMO 1

VARIANTA 1

KONTAKTORSIEMENS

C2A

* DRŽALO SVETILKE Z INTEGRIRANOLED DIODO:

SIEMENS3SB34-201RB- rdeča3SB34-201RE- bela

*RDEČA

KONTAKTOR JEVKLOPLJEN

NAPETOST JEPRISOTNA

BELA

*

LOČILNOMESTORL

PRENAPETOSTNIODVODNIKI RAZRED I

ZA OBJEKTNOTRANJI RAZVODI

MERILNO MESTOZA OBJEKT

PMO

LANDIS GYRRAZDELILNIK PS PMO 1

TP BOHOVA VODOVOD(t-117)NN IZVOD I-04 ŽELEZNICA

M.M. odjem...4-1306M.M. oddaja...4-8012586

LANDIS+ GYR ZMD310CT44+CU-P42 GSM/GPRS

MRP

M.M. proizvodnja...8012586ZMD310CT44+ CU-P42

-P33RT1045-1AP04

1

2

3

4

5

6

-F2

1 2

3 4

5 6

1.1

13 141.3

13

14

-K1

A1

A2

-K1X1

X2

-H1X1

X2

X1

X2

X1

X2

-H2-4

1

2

3

4

5

6

-K1

L1

.

-X1

ČR

L2

.

SI

L3

.

MO

N

.

RZ

PE

.

5

.

-X1

5

.

-X2

1

.

1

.

2

.

2

.

3

.

3

.

4

.

4

.

5OEL1105x1,5 mm2

-W31 2 3 4

ČR

SI

MO

RZ

-B1

-F1

IZKLOP

VKLOP

1

2

-S1

U

f

L1 L2 L3 21

24

1114

N

X1 B1 X2 B2

DOLDRP9800

-U1

3x230/400V

10-120A

1 2 3 4 5 6 7 8 9 10 11 12

-P2

/1.2

/1.2

KOGENERACIJSKA NAPRAVA

KOTLOVNICA- 9 kW

RJFG7OR5G25 mm2

-W1

RJ

FG7OR

5G25 mm2

-W2

-F1-Fx

-Fx

NV 160A16A

NV 160A20A

X.2016

Page 49: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

0 1 2 3 4 5 6 7 8 9

FAZA DATUM IZDELAVE

PODPIS

PODPIS

ŠT.NAČRTA

ŠT. RISBE

Š t e v i l k a l i s t a 1

ELEKTROINŠTALACIJE

VRSTA NAČRTA:

SPREMEMBA:

l i s t o v

INVESTITOR NAROČNIK

od 1

VSEBINA RISBE PROJEKTANT:

EL PART, Bogdan LEPAN s.p.ODGOVORNI PROJEKTANT

Bogdan.LEPAN,dipl.inž.el.OBDELOVALEC

IZS E-0963IDENT.ŠT.PLINOVODI d.o.o.

Cesta Ljubljanske brigade 11b1000 LJUBLJANA

OBJEKT LOKACIJA

VGRADNJA ENOTE SPTE V KOTLOVNICOMRP, Bohova 19b, 2311 HOČEna parc. št. 733, k.o. BOHOVA

PZR 69/16-E

ENOPOLNA SHEMA VEZAVERAZDELILNIKA PS PMO 1VARIANTA 1

E6

KONTAKTOR JEVKLOPLJEN

0-1

RDEČA

NV 160

VAROVALČNILOČILNIK

RAZRED I

PRENAPETOSTNIODVODNIKI

KONTAKTORSIEMENS

KOTLOVNICA

NAPETOST JEPRISOTNA

C2A

BELA

ZASEBNO OMREŽJE

JAVNO OMREŽJE

DOLDRP9800 -U1

RL- LOČILNO MESTOLASTNA RABA

MERILNO MESTOZA OBJEKT

PMO

ZA OBJEKTNOTRANJI RAZVODI

NV 160

VAROVALČNILOČILNIK

LANDIS GYR

M.M. proizvodnja...8012586ZMD310CT44+ CU-P42P2

PS PMO 1

LANDIS+ GYR ZMD310CT44+CU-P42 GSM/GPRS

M.M. odjem...4-1306M.M. oddaja...4-8012586

TP BOHOVA VODOVOD(t-117)NN IZVOD I-04 ŽELEZNICA

MRP

3RT1045-1AP04

-Flr

. .

-S1

-H1

-F1

-B1-H2-H4

2

1

-F2

OEL1105x1,5 mm2

-W3

GGENERATOR 1

16A

20A

-Fx

-F1-Fx

FG7OR5G25 mm2

-W1FG7OR5G25 mm2

-W2

-K1

-K1

KOGENERACIJSKA NAPRAVA

X.2016

Page 50: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 51: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 52: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 9

5. PRILOGA 1

Soglasje za priključitev št.: 1063924-O (3805-89/2016-23805-89/2016-2) Elektro Maribor, d.d.

Pogoji za priključitev elektrarne/proizvodne naprave v interno omrežje št.: 1063919-O/1063919-P (3805-89/2016-2) Elektro Maribor, d.d.

Page 53: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

' Slim ISO 9001 a348 ISO 14001 £-128

BSOHSAS 18001 H-(m

E F Q M I prijwno Recognised for excellem P16005475

Flioovodi Ć.O. 17=08=2016 PRiSPELO

E L E K T R O mARIBDR podjetje za distribucijo električne energije, d.d.

ELEKTRO MARIBOR d.d. , Vetrinjska ulica 2, p.p. 1244, 2000 Maribor na osnovi pooblastila SODO d.o.o. In na osnovi 147. člena Energetskega zakona (Ur.l. RS, št. 17/14, 81/15), Splošnih pogojev za dobavo In odjem električne energije Iz distribucijskega omrežja električne energije (Ur.l. RS, št. 126/07 In 1/08 - popr., 37/11 -odl. US In 17/14 - EZ-1), Sistemskih obratovalnih navodil za distribucijsko omrežje električne energije (Ur.l. RS, št. 41/11), Zakona o splošnem upravnem postopku (Ur.l. RS, št. 24/06 - uradno prečiščeno besedilo, 105/06, 126/07, 65/08, 8/10, 82/13) ter na osnovi vloge za objekt SP7E - VC Maribor, kl jo je podal vložnik PLINOVODI d.o.o.. Cesta Ljubljanske brigade 11 B, 1000 Ljubljana, izdaja naslednje

SOGLASJE ZA PRIKLJUČITEV št.: 1063924-O (3805-89/2016-23805-89/2016-2)

Vložniku PLINOVODI d.o.o., Cesta Ljubljanske brigadell B, 1000 Ljubljana se Izda soglasje za priključitev za objekt SPTE - VC Maribor na parceli št. 773 (k.o. 695 - BOHOVA) na naslovu BOHOVA 19 B v kraju BOHOVA pod navedenimi pogoji.

Tipska shema

Oznaka merilno-krmilne naprave

Številka merilnega mesta

Priključna moč (kW)

Vsota moči elektrarn (kW)

Lastnik proizvodne naprave/elektrarne

P1.3 P3 4-1306 35 10 /

P1.3 P2 4-8012586 10 10 PLINOVODI d.o.o.

TP 1 4̂1

1 P2

LO

LR

ELEKTRARNA

ELEKTROENERGETSKI POGOJI ODJEM

1. Številka merilnega mesta: 4-1306 2. Številka obstoječega soglasja za priključitev: 537031 3. Skupina končnih odjemalcev: Ostali odjem na nizki napetosti od 0,4 kV do 1 kV brez merjenja moči 4. Število razpoložljivih merilnih mest: 1 5. Nova priključna moč pri odjemu Iz distribucijskega sistema: 1 x 35 kW 6. Predviden letni odjem Iz distribucijskega sistema: 15000 kWh 7. Predvideno leto priključitve: 2016 8. Jakost omejevalca toka: 1 x 3 x 50 A 9. Jalova energija mora biti kompenzirana na cos(p = 0.95

TEHNIČNI POGOJI ODJEM

1. Priključno mesto (mesto vključitve priključka na distribucijski sistem) - Lokacija oz. mesto priključitve:

Mesto priključitve obstoječe

NN izvod 1-04 ŽELEZNICA

TP T-117 BOHOVA VODOVOD Nazivna napetost: 400 V Vrsta priključka: Trifazni priključek

Izvedba priključka Dolžina priključka Prerez priključka

podzemni vod 0,00 m Al 4x70+2,5 mm2 - Napajanje z električno energijo bo izvedeno iz:

stran 1 / 3

Page 54: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

E L E K T R O mARIBOR podjetje za distribucijo električne energije, d.d.

TP T-117 BOHOVA VODOVOD SN Izvod J 09 DV 20 KV ROGOZA SKOKE RTP RTP-20 DOBRAVA 110/20/10 KV

Kratkostična moč: 236,5 MW - Enopolni tok zemeljskega stika Iz strani distribucijskega sistema: 300 A - Avtomatski ponovni vklop - prva stopnja: 0,3 s - Avtomatski ponovni vklop - druga stopnja: 30 s

2. Prevzemno predajno mesto (mesto sprejema električne energije iz distribucijskega sistema) -pogoji za vložnika

- Lokacija: - Nazivna napetost: 400 V - Merilne naprave:

Merilne naprave morajo ustrezati naboru merilnih naprav (SONDO verzija 5 veljavna od 1. 2. 2015), kl se nahaja na spletni strani Sodo, d.o.o.: (http://www.sodo.sl/) In obsegajo:

Direktni trifazni dvosmerni števec s 15-minutno registracijo energije r.l (lEC) ali B (MID) in jalove energije r.2, (3x230/400V, 10-120A) ter komunikacijskim vmesnikom - za odjemalce:

- števec tip Iskraemeco MT880-D2A42R56, 3x230/400V, 10-120A s komunikacijskim modulom tip CM-v-3 GSM/GPRS ali

- števec tip Landls+Gyr ZMD310CT44, 3x230/400V 10-120A s komunikacijskim modulom tip Landis+Gyr CU-P42 GSM/GPRS ali

- števec tip Itron SL761 Y070, 3x230/400V, 10-120A s komunikacijskim modulom tip Sparklet GSM/GPRS.

Merilna oprema na dovodu mora biti zaščitena z zaščitnimi napravami (prenapetostni odvodniki razreda B po VDE) z osnovnimi tehničnimi zahtevami: maksimalna dovoljena delovna napetost med 320 VAC in 400 VAC, maksimalnim odvodni tok; (8/20|us) > 50 kA (10/350 |as) > 5 kA In odzivni čas < od 25 ns. V primeru zahteve po nadzoru se uporabljajo moduli z daljinsko signalizacijo.

OSTALI POGOJI - Uporabnik mora upravljalcu zagotoviti stalen dostop do vseh delov priključka in do vseh naprav, ki so

vgrajene na prevzemno predajnem mestu. - Z deli na priključku sme uporabnik pričeti tedaj, ko na svoje stroške uredi s pristojnim nadzorništvom

prestavitev obstoječih elektroenergetskih vodov oz. naprav na varno oddaljenost. O nameravanem začetku kakršnihkoli del na priključku mora biti upravljalec pisno obveščen najmanj osem dni pred začetkom del.

- Upravljalec daje izjavo, da bo kakovost električne napetosti ob izvedbi vseh tehničnih pogojev navedenih v tem soglasju za priključitev in odjemalčevi uporabi naprav, ki imajo certifikat o elektromagnetni združljivosti (EMC), skladna s Splošnimi pogoji za dobavo in odjem električne energije iz distribucijskega omrežja električne energije (Ur.l. RS, št. 126/07 In 1/08 popr.) In standardom SIST 50160.

- V primeru pomanjkanja električne energije se je odjemalec dolžan ravnati po določilih uredbe o omejevanju obtežb in porabe električne energije v elektroenergetskem sistemu (Ur.l. RS, št. 42/95 in 64/95).

- V primeru, ko upravljalec ugotovi, da uporabnik s svojim odjemom električne energije povzroča motnje (nemiren odjem električne energije) ostalim uporabnikom električne energije, sl upravljalec pridržuje pravico naknadno predpisati dodatne pogoje, v katerih od uporabnika zahteva odpravo teh motenj.

- Uporabnik mora po dokončnosti tega soglasja in pred priključitvijo skleniti z upravljalcem pogodbo o priključitvi, v kateri bodo urejeni odnosi v zvezi s priključkom, omrežnino za priključno moč in plačilom za priključitev na omrežje.

- Uporabnik si mora v primeru izgradnje novega priključka ali spremembe obstoječega pred pričetkom izvajanja del pridobiti ustrezno projektno dokumentacijo za priključek in od upravljalca pridobiti izjavo o ustreznosti projektne rešitve. Projektna dokumentacija mora biti izvedena skladno s Pravilnikom o projektni in tehnični dokumentaciji ter v skladu s tipizacijo omrežnih priključkov, tipizacijo merilnih mest in naborom merilne opreme.

stran 2 / 3

Page 55: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

ELEKTRO mARIBOR podjetje za distribucijo električne energije, d.d.

- Imetnik soglasja mora pred začetkom odjema električne energije z Izbranim dobaviteljem električne energije skleniti pogodbo o dobavi električne energije (seznam dobaviteljev je dostopen na spletni strani Javne agencije RS za energijo) in z upravljalcem pogodbo o uporabi distribucijskega sistema.

- V skladu z 2. 3. in 4. točko 147. člena Energetskega zakona (EZ-1 Ur.l. RS št. 17/14, 81/15) dokončno soglasje za priključitev velja dve leti. V tem roku mora imetnik soglasja za priključitev objekta izpolniti vse pogoje, predpisane v soglasju za priključitev in izvesti priključitev. Če imetnik soglasja za priključitev gradi nov objekt, mora v roku iz prejšnjega odstavka predložiti dokončno gradbeno dovoljenje, s čimer se izdanemu soglasju za priključitev veljavnost podaljša za obdobje veljavnosti predloženega gradbenega dovoljenja. Veljavnost soglasja za priključitev lahko elektrooperater na zahtevo imetnika soglasja za priključitev podaljša največ dvakrat, vendar vsakič največ za eno leto. Zahtevo za podaljšanje mora imetnik soglasja za priključitev podati 30 dni pred iztekom veljavnosti soglasja za priključitev.

- N a uporabnikove elektroenergetske naprave ni dovoljeno brez soglasja upravljalca priključevati elektroenergetskih naprav drugih uporabnikov.

-Zaradi priključitve uporabnikovega objekta na distribucijski sistem ne smejo biti prizadete pravice In pravne koristi tretjih oseb. Škodo, kl bi nastala zaradi kršitev pravic in pravnih koristi teh oseb, nosi uporabnik.

- S pravnomočnostjo In izpolnitvijo pogojev tega soglasja za priključitev preneha veljati soglasje za priključitev št. 537031 za merilno mesto št. 4-1306.

O b r a z l o ž i t e v

Vložnik PLINOVODI d.o.o., Cesta Ljubljanske brigade 11 B, 1000 Ljubljana je dne 12.7.2016 z vlogo, ki smo jo zavedli pod zaporedno št. V00792314 zaprosil ELEKTRO MARIBOR d.d. za izdajo soglasja za priključitev za objekt SPTE - VC Maribor na parceli št. 773 (k.o. 695 - Bohova) na naslovu Bohova 19 B v kraju Bohova.

ELEKTRO MARIBOR d.d. ugotavlja, da je vložnik vlogi za izdajo soglasja za priključitev priložil vso potrebno dokumentacijo in dokazila, ki so pogoj za izdajo soglasja za priključitev.

Upravljalec je na podlagi dejstev, ugotovljenih v postopku, in v skladu s 147. členom Energetskega zakona (Ur.l. RS, št 17/14), Splošnimi pogoji za dobavo in odjem električne energije iz distribucijskega omrežja električne energije (Ur.l. RS, št. 126/07 in 1/08 popr.). Sistemskimi obratovalnimi navodili za distribucijsko omrežje električne energije (Ur.l. RS, št. 41/11) ter Zakonom o splošnem upravnem postopku (Ur.l. RS, št. 24/06 - uradno prečiščeno besedilo, 105/06, 126/07, 65/08 in 8/10) odločil, kot ie navedeno v izreku tega soglasia. Stroškov v postopku ni bilo.

PRAVNI POUK: Zoper to odločbo je dovoljena pritožba v 15 dneh od dneva vročitve na Agencijo za energijo, Strossmayerjeva ulica 30, 2000 Maribor. Pritožbo je potrebno vložiti na ELEKTRO MARIBOR d.d. , Vetrinjska ulica 2, p.p. 1244, 2000 Maribor, pisno ali ustno na zapisnik oziroma poslati priporočeno po pošti.

Datum: 10. 8. 2016

Postopek vodil: Dejan PEKLIČ, dipl. inž. el.

DEJAN PEKLIČ Eiektro Maribor d.d.

S O D O - 3 1 4 / 2 0 1 6 - D V

Vročiti osebno po ZUP: - PtlNOVODI:d:o:O7reesta:Ljubljanske^gadeJJ_B,J.0.00_Ljubljaria_

Vročiti: - OE Maribor z okolico

Predsednik uprave ELEKTRO MARIBOR d.d. : mag. Boris SOVIČ, univ. dipl. inž. el.

po pooblastilu: Peter KAUBE, univ.dipl.inž.el.

E L E K ; H ; R O M A R I B C ^ R , p-S^M.n, za disf.rlbucijo

6 eleKtrične energije d d -MARIBOR, Vetrinjska ulica 2

stran 3 / 3

Page 56: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

ISO 9001 Q-ios ISO wool E-128

BS OHSAS 18001 H-(W6

Oiulni E F Q M • r Jpi l jazno Recognised for excellence ^ Mm podjelje 4 siai - 2016

E L E K T R O m A R I B O R

podjetje za distribucijo električne energije, d.d.

ELEKTRO MARIBOR d.d. , Vetrinjska ulica 2, p.p. 1244, 2000 Maribor na osnovi Sistemskih obratovalnih navodil za distribucijsko omrežje električne energije (Ur.l. RS, št. 41/11) in na osnovi vioge za izdajo pogojev za priključitev elektrarne/proizvodne naprave v interno električno omrežje za objekt SPTE-VC Maribor, SPTE - VS Maribor, ki jo je podal vložnik PLINOVODI d.o.o., Cesta Ljubljanske brigade 11 B, 1000 Ljubljana, izdaja naslednje

POGOJE ZA PRIKLJUČITEV ELEKTRARNE/PROIZVODNE NAPRAVE V INTERNO OMREŽJE št: 1063919-O / 1063919-P (3805-89/2016-2)

Vložniku PLINOVODI d.o.o.. Cesta Ljubljanske brigade 11 B, 1000 Ljubljana se izdajo pogoji za priključitev elektrarne/proizvodne naprave v interno električno omrežje za objekt SPTE-VC Maribor, SPTE - VS Maribor na parceli št. 773 (k.o. 695 - BOHOVA) v kraju Bohova pod navedenimi pogoji.

Oznaka merilno-krmilne naprave Številka merilnega mesta Enotni identifikator merilnega mesta P3 4001306 4-1306 P2 8012586 4-8012586

TP

LO

LR

ELEKTRARNA

ELEKTROENERGETSKI POGOJI

A.) PROIZVODNJA

1. 2. 3. 4. 5. 6. 7.

Številka merilnega mesta: 4-8012586 Elektrarna bo priključena po vezalni shemi: P1.3 Nova priključna moč: 10 kW Jakost omejevalca toka: 3 x 16 A Karakteristika jalove moči: razred A Način obratovanja: paralelno - delno porabijo sami, viške oddajo v omrežje Podatki elektrarne: - Število generatorjev/razsmernikov: 1

Vrsta generatorja Nazivna moč Nazivna napetost Nazivna frekvenca sinhronski 10,00 kVA 400 V 50 Hz

8. 9. 10. 11.

Predvidena letna proizvodnja za lastne potrebe: 5.000 kWh Predvidena letna proizvodnja za oddajo v distribucijski sistem: 3.000 kWhi Predvideno leto priključitve: 2016 Instalirana celotna nazivna moč elektrarne: 10,00 kVA

TEHNIČNI POGOJI

A.) PROIZVODNJA

1. Priključno mesto (mesto vključitve priključka na distribucijski sistem) - Lokacija oz. mesto priključitve:

stran 1 / 3

Page 57: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

E L E K T R O mARIBOR podjetje za distribucijo električne energije, d.d.

Mesto priključitve Za merilnim mestom št,: 1306 NN izvod 1-04 ŽELEZNICA TP T-117 BOHOVA VODOVOD

- Nazivna napetost: 400 V - Vrsta priključka: Trifazni priključek - Distribucijski sistem v točki priključitve omogoča TN sistem zaščite sistem ozemljitve. - Kratkostična moč: 236,5 MW - Enopolni tok zemeljskega stika iz strani distribucijskega sistema: 300 A

2. Ločilno mesto Lokacija: NN priključno merilna omarica Nazivna napetost: 400 V Elektrarna mora ustrezati zahtevam delovanja hitrega avtom, ponovnega vklopa v distribucijski sistem. Vsak izpad nap. v javnem omrežju EES mora povzročiti zanesljiv izklop odklopnika na ločilnem mestu. Če se je odklopnik ločilnega mesta izključil zaradi delovanja zaščitnih naprav na ločilnem mestu, mora ostati izključen, dokler niso izpolnjeni pogoji za ponovni vklop. Elektrarna/proizvodna naprava se lahko samodejno priključi na distribucijski sistem, ko so parametri napetosti na omrežni strani ločilnega mesta znotraj mej zaščite na ločilnem mestu dovolj časa, kar znaša za elektronske pretvomiške generatorje najmanj 20 s oz. za rotirajoče generatorje najmanj 3 min. Ločilno mesto z ročnim izklopom mora biti opremljeno s ključavnico ELEKTRO MARIBOR d.d. Na ločilnem mestu mora biti vgrajen odklopnik z izklopno tuljavo, ki je vključena v izklopni tokokrog zaščitnih naprav na ločilnem mestu. Za elektrarne do 16 A na fazo je za nastavitve zaščit ločilnega mesta potrebno upoštevat standard SIST EN 50438. Za vse ostale elektrarne so nastavitve zaščit ločilnega mesta navedene v razpredelnici 4.1. Navodil za priključevanje in obratovanje elektrarn inštalirane električne moči do 10 MW (SONDO - Ur l. RS, št. 20/11). Zaščita na ločilnem mestu in generatorska zaščita ne smeta omejevati vgradnje oziroma delovanja shunt-stikala, ki ob zemeljskem stiku v SNO za trenutek v RTP ozemlji fazo, na kateri je zemeljski stik. Odklopnik ločilnega mesta mora biti dimenzioniran za predvideni kratkostični tok na priključnem mestu. Omogočen mora biti ročni izklop z blokado ponovnega vklopa. Vse zaščitne naprave na ločilnem mestu morajo biti plombirane in pod ključem Elektro Maribor d.d. Umerjanje, nastavitev in preskuse delovanja zaščitnih naprav ločilnega mesta lahko izvede upravljalec ali za ta dela registrirana organizacija, vendar le ob prisotnosti predstavnika Elektro Maribor d.d. Spremembe nastavitve zaščitnih naprav na ločilnem mestu lahko določa samo pooblaščena oseba distribucijskega operaterja.

3. Prevzemno predajno mesto - pogoji za vložnika

Merilne naprave morajo ustrezati naboru merilnih naprav (SONDO verzija 5 veljavna od 1. 2. 2015), kl se nahaja na spletni strani Sodo, d.o.o.: (http://www.sodo.si/) in obsegajo:

Direktni trifazni dvosmerni števec s 15-minutno registracijo energije r.l (lEC) ali B (MID) in jalove energije r.2, (3x230/400V, 10-120A) ter komunikacijskim vmesnikom - za odjemalce:

- števec tip Iskraemeco MT880-D2A42R56, 3x230/400V, 10-120A s komunikacijskim modulom tip CM-v-3 GSM/GPRS ali

- števec tip Landis+Gyr ZMD310CT44, 3x230/400V 10-120A s - komunikacijskim modulom tip Landis+Gyr CU-P42 GSM/GPRS ali - števec tip Itron SL761 Y070, 3x230/400V, 10-120A s

komunikacijskim modulom tip Sparklet GSM/GPRS.

Merilna oprema na dovodu mora biti zaščitena z zaščitnimi napravami (prenapetostni odvodniki razreda B po VDE) z osnovnimi tehničnimi zahtevami: maksimalna dovoljena delovna napetost med 320 VAC in 400 VAC. maksimalnim odvodni tok; (8/20ns) > 50 kA (10/350 ns) > 5 kA in odzivni čas < od 25 ns. V primeru zahteve po nadzoru se uporabljajo moduli z daljinsko signalizacijo.

stran 2 / 3

Page 58: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

E L E K T R O IDARIBOR podjetje za distribucijo električne energije, d.d.

OSTALI POGOJI - Vgrajene naprave v elektrarni oziroma proizvodni napravi morajo izpolnjevati pogoje smemic

elektromagnetne združljivosti (EMC), za kar morajo imeti ustrezne certifikate. - Vložnik je pred izdajo tega soglasja za priključitev poskrbel za podpis Izjave lastnika objekta in Izjave

investitorja elektrarne na osnovi katerih se obvezuje zagotoviti ustrezno kratkostično trdnost interne električne inštalacije, od obstoječega merilnega mesta odjema P3 do točke priključitve elektrarne (proizvodne naprave) ter zgraditi ustrezen elektroenergetski vod od elektrarne (proizvodne naprave) do točke vključitve v interno električno inštalacijo objekta.

- Kakovost električne energije, ki jo elektrarna oddaja v distribucijski sistem mora biti v skladu s Splošnimi pogoji za dobavo in odjem električne energije iz distribucijskega omrežja električne energije (Ur.l. RS, št. 126/07), tako da obratovanje ostalih odjemalcev ali proizvajalcev na tem distribucijskemu sistemu v nobenem primeru ni moteno, v nasprotnem primeru lahko distribucijski operater predpiše dodatne pogoje.

- Vložnik mora po izdaji teh pogojev priključitve elektrarne/proizvodne naprave na interno omrežje skleniti z upravljavcem distribucijskega sistema Pogodbo o izvedbi priključitve na interno omrežje za prevzemno predajno mesto (merilno mesto s števcem P2) elektrarne (proizvodne naprave), v kateri bodo urejena vsa medsebojna razmerja v zvezi s priključitvijo.

- Pred priključitvijo objekta mora biti s strani upravljavca distribucijskega omrežja izvršen pregled priključka glede izpolnjevanja tehničnih ter drugih pogojev, določenih v soglasju za priključitev za prevzemno predajno mesto odjema (merilno mesto s števcem P3) in teh pogojev za priključitev ter predložen merilni protokol preizkusov zaščitnih naprav na ločilnem mestu in ustrezni dokumenti iz Uredbe o dopolnitvah Uredbe o energetski infrastrukturi (Ur.l. RS, 53/11).

- Sestavni del zaprosila za priključitev so tudi obratovalna navodila, sestavljena skladno s 14. členom SONDO.

- Za vsako spremembo elektroenergetskih ali tehničnih pogojev teh pogojev za priključitev elektrarne/proizvodne naprave v interno omrežje, mora uporabnik vložiti vlogo za spremembo in k vlogi priložiti potrebno dokumentacijo.

- V primeru, ko distribucijski operater ugotovi, da uporabnik s svojo proizvodnjo električne energije povzroča motnje (nemiren odjem električne energije) ostalim uporabnikom električne energije, si upravljavec pridržuje pravico naknadno predpisati dodatne pogoje, v katerih od uporabnika zahteva odpravo teh motenj.

- Ti pogoji za priključitev prenehajo veljati, če uporabnik v dveh letih ne izpolni vseh zahtev. Na predlog uporabnika, ki mora biti vložen najkasneje 30 dni pred potekom veljavnosti teh pogojev za priključitev elektrarne/proizvodne naprave v interno omrežje, se lahko veljavnost teh pogojev podaljša največ dvakrat, vendar vsakič največ za eno leto.

- Na elektroenergetske naprave uporabnika ni dovoljeno brez soglasja sistemskega operaterja priključevati elektroenergetskih naprav drugih odjemalcev.

Datum: 10. 8. 2016

Postopek vodil: Dejan PEKLIČ, dipl.inž.el.

DEJAN PEKLIČ Elektro Maribor d.d.

S O D O - 3 1 4 / 2 0 1 6 - D V

Vročiti osebno po ZUP: -J2l=IN0V0D"ra7o:oTeesta-tjubljanske-brigade-1i-BrlWO-LjuBljana^

Vročiti: - OE Maribor z okolico

Predsednik uprave ELEKTRO MARIBOR d.d. : mag. Boris SOVIČ, univ.dipl.inž.el.

po pooblastilu: Peter KAUBE, univ.dipl.inž.el.

E L E K T R t D M A R i B O R , fiodifsisz za aistribiicljo

6 eiei'trične oneigi;e, a d. M A R I B O R . Vetrinjska ulica 2

stran 3 / 3

Page 59: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

S l i ^ ^ ^ ^ i P • L l • ELEKTRO mARIBOR [SO90O1 0-343 V^r~~>V P^^P'it^'no ^ | 9 M ^ ^ 1

S'OHSAS%DO^~"M6^%8(^ kkflpodieiie ^ k ^ l ^ Z ^ B podjctje ZS dlstribucIjo električne energije, d.d.

PLINOVODI D.O.O.

(naziv stranke v postopku)

CESTA LJUBLJANSKE BRIGADE 11 B

(ulica in hišna številka)

1000 LJUBLJANA

(poštna številka in pošta)

IZJAVA O ODPOVEDI PRAVICI DO PRITOŽBE PO VROČITVI ODLOČBE

(prvi in drugi odstavek 229. a člena ZUP)

Na podlagi prvega in drugega odstavka 229. a člena Zakona o splošnem upravnem postopku (Uradni list RS, št. 24/06-UPB2, 105/06-ZUS-l, 126/07, 65/08 in 8/10) v zvezi z vlogo za

• izdajo soglasja za priključitev na distribucijski sistem

izjavljam,

da se nepreklicno odpovedujem pravici do pritožbe zoper odločbo elektrodistribucijskega podjetja ELEKTRO MARIBOR d.d. , številka 1063919, z dne , ki mi je bila vročena dne .

Odpoved pravici do pritožbe, predložena po vročitvi odločbe, se ne more več preklicati.

Kraj: Žig in podpis uporabnika

Datum:

Stran 1 /1

Page 60: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 10

6. PRILOGA 2

Popisi- varianta 1

Page 61: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

REKAPITULACIJA STROŠKOV

I. PRIPRAVLJALNA DELAII. GROBA INSTALACIJSKA DELAIII. OZEMLJITVE IV. RAZDELILNIK PMOV. RAZDELILNIK MRPVI. MERILNO MESTO- PS PMO 1VII. RL- LOČILNO MESTOVIII. REGULACIJA TEMPERATURE PLINAIX. KASKADNA REGULACIJA KOTLOVX. FINOMONTAŽNA DELAXI. ZAKLJUČNA DELA

SKUPAJ (€)DDV (22%)SKUPAJ (€)

POPISI SPTE KOTLOVNICA MRP MARIBOR- VARIANTA 1

0

0

000

0

0

0

00

00

0

0

Stran 1

Page 62: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

I. PRIPRAVLJALNA DELA

1 Izdelava projekta PZI kpl. 1 02 Priprava gradbišča kpl. 1 03 Transport materialov do objekta kpl. 1 04 Zavarovanje gradbišča kpl. 1 0

SKUPAJ 0

II. GROBA INSTALACIJSKA DELA

1Ročni- strojni izkop kabelskega jarka dimenzije 0,40 x 0,80 m; III.ktg m 15 0

2

Izdelava kabelske blazine iz mivke vključno s prevozom za jarek dim. 0,40 x 0,80 m, zasip in planiranje, vzpostavitev terena v prvotno stanje m 15 0

3 Dobava in polaganje plastičnih cevi Ø110 mm v kabelski jarek m 17 0

4 Opozorilni trak z napisom ELEKTRIKA m 15 0

5Perforirana pocinkana kabelska polica PK100, komplet z vsem spojnim in montažnim materialom - dobava in montaža m 18 0

6Perforirana pocinkana kabelska polica PK50, komplet z vsem spojnim in montažnim materialom - dobava in montaža m 10 0

7Dobava in polaganje kabla FG7OR 5G6 mm², položenega na kabelski polici m 5 0

8Dobava in polaganje kabla FG7OR 5G25 mm², položenega delno na kabelski polici, delno podzemno v zaščitni cevi m 70 0

9Dobava in polaganje kabla OEL110 5G1,5 mm², položenega delno na kabelski polici, delno podzemno v zaščitni cevi m 25 0

10 Kabel OEL110 3G1,5 mm² m 130 011 Kabel OEL110CY 12G0,75 mm² m 10 012 Kabel OEL110CY 3G0,75 mm² m 10 013 Kabel OEL110CY 4G0,75 mm² m 60 014 Kabel OEL110CY 2x0,75 mm² m 40 015 Kabel SFTP cat. 6 m 30 0

16Inštalacijska cev Ø13 mm, komplet z vsem spojnim in montažnim materialom m 100 0

17 Dobava in priklop 5-polnega vtikača, 63 A kom 118 Priklop kabla FG7OR kom 4 019 Vodnik HO7V-K rumeno-zelen, 1x16 mm² m 20 0

20

Dobava in montaža samoregulirnega grelnega kabla BARTEC 10W/m, l= m od SPTE do jaška, priključni kabel z vtičnico 5 m skupaj s spoji in zaključki IP65 m 10 0

21 Preboji sten kpl. 1 022 Razni drobni nespecificiran material kpl. 1 0

SKUPAJ 0

Stran 2

Page 63: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

III. OZEMLJITVE

1 Valjanec FeZn 25x4 mm, položen v kabelski jarek m 20 02 Kabelski čevelj 16 mm² kom 1 03 Vijačni spoj na opremo kom 2 0

4

Izvedba meritev ponikalne upornosti temeljnega ozemljila, pregled in izdaja zapisnika o opravljenih meritvah in pregledu kpl. 1 0

SKUPAJ 0

IV. RAZDELILNIK PMO

1Direktni števec električne energije LANDYS+ GYR tip: ZMD310CT44 s CU-P42 komunikacijskim modulom kom 1 0

2 Varovalni vložek NH00/80A kpl. 1 03 Drobni material kpl. 1 0

SKUPAJ 0

V. RAZDELILNIK MRP

1 Demontaža obstoječega razdelilnika MRP kom 1 0

2

Strošek odvoza razdelilnika na deponijo investitorja oziroma deponijo predvideno za odpadno električno in elektronsko opremo skladno z zakonskimi določili kom 1 0

3Izdelava razdelilnika MRP po načrtih in dokumentaciji Plinovodi d.o.o.- ocenjena vrednost 3000 € kpl. 1 0

4 Montaža razdelilnika kom 1 05 Drobni material kpl. 1 0

SKUPAJ 0

Stran 3

Page 64: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

Dobava in montaža

1

Dobava in montaža certificiranega razdelilnika prostostoječe izvedbe dimenzij 460 x 900 x 190 mm s podstavkom dimenzij 450 x 1000 x 180 mm, s trotočkovnim zapiranjem, opremljen z napisi z vgrajeno opremo kom 1 0

2

Števčna plošča z direktnim števcem električne energije LANDYS+ GYR tip: ZMD310CT44 s CU-P42 komunikacijskim modulom kom 1 0

3 Varovalčni ločilnik HVL 00-3p M8 M8-P kom 1 04 Varovalni vložek NH00/50A kom 3 05 Kontaktor Siemens 3RT 1045- 1AP04 kom 1 06 Prenapetostni odvodniki RAZREDA I. kom 3 0

7Držalo svetilke z integrirano LED diodo kot npr. SIEMENS 3SB34 20.1RE bela kom 3 0

8Držalo svetilke z integrirano LED diodo kot npr. SIEMENS 3SB34 20.1RB rdeča kom 1 0

9 Inštalacijski odklopnik C2A, tripolni kom 1 010 Stikalo 0-1, 1p, n/o, 6 A kom 1 011 Ključavnica elektrodistribucije kom 1 012 PEN zbiralnica, Cu 30x5 mm, l= 250 mm kom 1 013 Sponke, drobni material kpl. 1 0

SKUPAJ 0

VI. MERILNO MESTO- PS PMO 1

Stran 4

Page 65: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

VII. RL- LOČILNO MESTO

1

Dobava in montaža atestiranega razdelilnika nadometne izvedbe dimenzij 300 x300 x 190 mm, prebarvan s temeljno in zaščitno barvo, RAL 7032, opremljen z napisi z vgrajeno opremo kom 1 0

2 Dobava in montaža varnostnega releja DOLD RP 9800 kom 1 03 Dobava in montaža kabla OEL110 5x1,5 mm² m 15 04 Sponke, drobni material kpl. 1 0

SKUPAJ 0

1Izdelava in montaža razdelilnika RR po načrtih in dokumentaciji Plinovodi d.o.o. kpl. 1 0

2Zidna kovinska omarica dimenzij (vxšxg) 400x500x210 mm tip SCHRACK WSM4050210, komplet z montažno ploščo kom 1 0

3Krmilnik Siemens LOGO 12/24RC tip 6ED1052-1MD00-0BA8 (8xDI, 4xDO rele) kom 1 0

4Napajalnik Siemens LOGO Power tip 6EP1331-1SH03

(230VAC/24VDC, 1,3A) kom 1 0

5

Analogni vhodni Pt100 modul Siemens LOGO tip 6ED1055-

1MD00-0BA2 (2xAI) kom 2 0

6

Analogni izhodni modul Siemens LOGO tip 6ED1055-1MM00-

0BA2 (2xAO) kom 2 0

7

Analogni vhodni modul Siemens LOGO tip 6ED1055-1MA00-

0BA2 (2xAI) kom 2 0

8 Sponka Weidmuller VDU 2,5 1020000000 kom 30 0

9 Sponka Weidmuller VDU 2,5 BL 1020080000 kom 1 0

10 Sponka Weidmuller VPE 2,5 1010000000 kom 10 0

11 Sponka Weidmuller WAP 2,5-10 1050000000 kom 2 0

12 Sponka Weidmuller WSI 4/2 1880430000 kom 2 0

13 Sponka Weidmuller WEW 35/2 1061200000 kom 2 0

14 DIN letev m 1 0

15 Cevna varovalka F1A kom 3 0

16 Kabelski kanal POK (vxš) 40x25 mm m 1 0

17 Kabelski kanal POK (vxš) 40x40 mm m 1 0

18 D-Link 4G LTE brezžični usmerjevalnik DWR-921 kom 1 0

19 Vsesmerna LTE, UMTS, GSM antena 9 dBi- SMA kom 1 0

20

AC/DC pretvornik 230VAC/12 VDC, 30W, DIN-RAIL DRB30-

12 kom 1 0

21 Pt100 sonda BARTEC-Ex3WIRE-300mm tip 27-7125-1333 kom 1 0

22 Tipalo tlaka Wika TP-A10-1/2-A-0/10bar-0/10V kom 1 0

23

Kombinirano zunanje tipalo vlaga, temperatura- Siemens senzor

vlage QFA3160+ Siemens senzor temperature AQF3100 kom 1 0

24 Razvodnica BARTEC Ex-e 2x PG9 kom 1 0

25

Elektromotorni pogon Danfos AMB 182/24V, 0.10V (ventil je v

strojnem popisu) kom 1 0

26 Temperaturno Pt100 tipalo Siemens QAD2010 kom 2 0

27 Drobni material, uvodnice kpl. 1 0

SKUPAJ 0

VIII. REGULACIJA TEMPERATURE PLINA

Stran 5

Page 66: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

1

Dobava in montaža avtomatike Viessmann Vitotronic 300-K

MW1B, komplet z zunanim in naležnim temperaturnim tipalom,

naročniška številka 7151941 kpl. 1 0

2

Dobava in montaža stenske konzole za avtomatiko, naročniška

številka 7151941 kom 1 0

SKUPAJ 0

X. FINOMONTAŽNA DELA

1

Montaža dislociranih enot SPTE (izmenjevalec, nadzor

zalogovnika...) kom 2 0

2 Dobava in montaža vtičnice 230 VAC, 16A, n/o kom 1 0

3 Montaža kontrolnih omar enot SPTE kom 1 0

4 Priklop temperaturnih tipal kom 7 0

5 Priklop avtomatike Vitotronic 300 K MW1B, komplet s tipali kom 1 0

6 Priklop črpalk in mešalnega ventila kom 4 0

7

Dobava in montaža sobnega termostata za vklop grelnega kabla

T<5°C Conrad FS20 kom 1 0

8 Drobni material kpl. 1 0

SKUPAJ 0

XI. ZAKLJUČNA DELA

1

Meritve, preizkusi in spuščanje v pogon posameznih sklopov

elektro opreme kpl. 1 0

2

Poučitev predstavnika investitorja o rokovanju z elektro

instalacijskimi sistemi na objektu kpl. 1 0

3

Priprava in izdaja "POTRDILA O ZANESLJIVOSTI

OBJEKTA" kot ločena mapa za el. instalacije kpl. 1 0

4 Primopredaja objekta investitorju kpl. 1 0

5 Izdelava načrtov izvedenega stanja- PID kpl. 1 0

SKUPAJ 0

IX. KASKADNA REGULACIJA KOTLOV

Stran 6

Page 67: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 11

7. SPTE VZDRŽEVALNI CENTER MARIBOR- VARIANTA 2

7.1. Izvedba priklopa SPTE enote

Investitor bo postavil še eno mikro SPTE enoto tipa XRGI 20G- TO, obe proizvajalca EC POWER A/S v smislu izboljšave, ki sledi napredku tehnike in omogoča učinkovito rabo primarne energije. Vgradnja soproizvodne enote je po Zakonu o graditvi objektov opredeljena kot investicijsko vzdrževalno delo.

Podatki za drugo enoto SPTE: XRGI 20G- TO- Qtopl = 40 kW, Pel = 20 kW, proizvajalec EC POWER A/S.

Naprava SPTE je električno povezana. Iz enote SPTE se izvede povezava do njene komandne omare na zidu kotlovnice s kablom FG7OR 5G10 mm². Vodnik FG7OR 5G25 mm² od električnega razdelilnika enote R-SPTE do prostostoječe priključno-merilne omarice PS-PMO 1, ki je locirana ob ograji na stalno dostopnem mestu na zemljišču v lasti investitorja se iz razdelilnika R-SPTE 1 odklopi in prestavi v skupni električni razdelilnik obeh enot SPTE (R-SK), ki je zmontiran v istem prostoru v neposredni bližini elektro omar posameznih enot SPTE. Iz razdelilnika posamezne enote SPTE se izvede povezava do skupnega električnega razdelilnika obeh enot SPTE (R-SK). V njej se oba dovodna kabla, prvi varovan z varovalko 3 x 20 A, drugi pa z varovalko 3 x 40 A, združita.

V omarici PS-PMO 1 se obe enoti priključita preko 50 A varovalke, v razdelilniku na mestu priklopa na interno omrežje (razdelilnik objekta MRP) pa preko varovalke C63 A.

Glavni razdelilnik celotnega kompleksa GR-VC je napajan iz distribucijskega omrežja. Tarifne varovalke so velikosti 3 x 63 A. V primeru, da bi se investitor odločil za to varianto, bo potrebno povečati tarifne varovalke na 3 x 80 A. Odvod iz glavnega razdelilnika celotnega kompleksa GR-VC na glavni razdelilnik kotlovnice MRP bo potrebno varovati z 3 x 63 A talilnimi varovalkami. Kabel med razdelilnikoma GR-VC in MRP bo potrebno zamenjati s kablom ustreznega preseka, z elektro distribucijo pa doreči ukrepe za povečanje maksimalne možne priključne moči enot SPTE. Pri elektro distribuciji bo potrebno pridobiti Soglasje za povečanje priključne moči iz 43 kW na 55 kW.

Page 68: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 12

7.2. Tehnični podatki enote SPTE XRGI 20G- TO

Osnovni podatki: Tip: SPTE XRGI 20G- TO Gorivo: Zemeljski plin Električna nazivna moč: 20 kW Toplotna nazivna moč: 40 kW Električni izkoristek: 32 % Toplotni izkoristek: 64 % Skupni izkoristek: 96 % Napetost/frekvenca: 3x230V/400V/50Hz Generator: Asinhronski trifazni generator

7.3. Podatki o planirani proizvodnji

Za varianto 1 se planira 8.500 ur letnega obratovanje naprave. Letna proizvodnja ........................................................................................... 51.000 kWh Za lastne potrebe ............................................................................................ 40.800 kWh Za oddajo v DO .............................................................................................. 10.200 kWh

Za varianto 2 se planira še dodatnih 4.000 ur letnega obratovanje druge enote SPTE. Letna proizvodnja ........................................................................................... 80.000 kWh Za lastne potrebe ............................................................................................ 64.000 kWh Za oddajo v DO .............................................................................................. 16.000 kWh Skupno se za varianto 2 planira naslednja proizvodnja: Letna proizvodnja ......................................................................................... 131.000 kWh Za lastne potrebe .......................................................................................... 104.800 kWh Za oddajo v DO .............................................................................................. 26.200 kWh

Proizvedena električna energija bo v večjem delu namenjena za lastne potrebe, višek pa za oddajanje v javno distribucijsko omrežje.

7.4. Ostale električne povezave

Razen močnostnih povezav je potrebno nekatere elemente povezati še s signalnimi kabli. Z opletenimi kabli se izvede povezava med enoto SPTE in njeno komandno omaro. S kabli SFTP cat. 6 se povežeta še druga komandna omara in toplotni izmenjevalec.

Do toplotnega izmenjevalca (vtičnica 230 VAC pri izmenjevalcu) je potrebno pripeljati še napajanje 230 VAC. To se izvede s kablom OEL110 3x1,5 mm² iz razdelilnika MRP kot nadaljevanje iz obstoječe vtičnice izmenjevalca 1.

Page 69: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 13

7.5. Izenačitev potenciala

Za preprečevanje pojavljanja potencialnih razlik med različnimi kovinskimi deli se v objektu izvede izenačenje potencialov. Instalacija za izenačenje potenciala se izvede z vodnikom rumeno-zelene barve.

Z ozemljitveno žico HO7VK-Y 16 mm2 povežemo ohišje enote SPTE na obstoječe ozemljilo.

7.6. Opozorilo dvojnega napajanja

Opozorilni napis dvojnega napajanja objekta se prilepi: - na enoto SPTE.

Opozorilo je v skladu s standardom Zahteve za vzporedno vezavo mikro generatorjev z javnim

nizkonapetostnim razdelilnim omrežjem (SIST EN 50438:2007). Primer opozorilne nalepke:

7.7. Tehnične risbe

► Delni tloris objekta- dispozicija opreme- varianta 2 M 1:50 E1

► Delni tloris objekta- shema ogrevanja- varianta 2 M 1:50 E2

► Razpored opreme v razdelilniku PS PMO 1- varianta 2 M 1:5 E3

► Tripolna shema vezave razdelilnika PS PMO 1- varianta 2 M 1:X E4

► Enopolna shema vezave razdelilnika PS PMO 1- varianta 2 M 1:X E5

► Zunanji izgled in razporeditev opreme v razdelilniku R-SK M 1:X E6

► Tehnološka shema kotlovnice- varianta 2 M 1:X E7

Page 70: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 71: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 72: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 73: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

0 1 7 8 965432

KONTAKTORSIEMENS

C2A

1

2

3

4

5

6

-F2

1 2

3 4

5 6

1.1

13 141.3

13

14

-K11.2

* DRŽALO SVETILKE Z INTEGRIRANOLED DIODO:

SIEMENS3SB34-201RB- rdeča3SB34-201RE- bela

*

A1

A2

-K1X1

X2

-H1RDEČA

KONTAKTOR JEVKLOPLJEN

NAPETOST JEPRISOTNA

X1

X2

X1

X2BELA

*X1

X2

-H2-4

1

2

3

4

5

6

-K11.2

LOČILNOMESTORL

L1

.

-X1L2

.

L3

.

N

.

PE

.

5

.

-X1

5

.

-X2

1

.

1

.

2

.

2

.

3

.

3

.

4

.

4

.

5OEL1105x1,5 mm2

-W31 2 3 4

PRENAPETOSTNIODVODNIKI RAZRED I

-B1

-F1

ZA OBJEKTNOTRANJI RAZVODI

FAZA DATUM IZDELAVE

PODPIS

PODPIS

ŠT.NAČRTA

ŠT. RISBE

Š t e v i l k a l i s t a 1

ELEKTROINŠTALACIJE

VRSTA NAČRTA:

SPREMEMBA:

l i s t o v

INVESTITOR NAROČNIK

od 1

VSEBINA RISBE

MERILNO MESTOZA OBJEKT

PMO

LANDIS GYR

KOGENERACIJSKI NAPRAVIKOTLOVNICA (R-SK)

PROJEKTANT:

EL PART, Bogdan LEPAN s.p.ODGOVORNI PROJEKTANT

Bogdan.LEPAN,dipl.inž.el.OBDELOVALEC

IZS E-0963IDENT.ŠT.

IZKLOP

VKLOP

1

2

-S1

U

f

L1 L2 L3 21

24

1114

N

X1 B1 X2 B2

DOLDRP9800

-U1

PLINOVODI d.o.o.Cesta Ljubljanske brigade 11b1000 LJUBLJANA

OBJEKT LOKACIJA

VGRADNJA ENOTE SPTE V KOTLOVNICOMRP, Bohova 19b, 2311 HOČEna parc. št. 733, k.o. BOHOVA

RAZDELILNIK PS PMO 1

TP BOHOVA VODOVOD(t-117)NN IZVOD I-04 ŽELEZNICA

M.M. odjem...4-1306M.M. oddaja...4-8012586

LANDIS+ GYR ZMD310CT44+CU-P42 GSM/GPRS

MRP

PZR 69/16-E

M.M. proizvodnja...8012586ZMD310CT44+ CU-P42

3x230/400V

10-120A

1 2 3 4 5 6 7 8 9 10 11 12

-P2

-P3

TRIPOLNA SHEMA VEZAVERAZDELILNIKA PS PMO 1

NV 160A50A

NV 160A63A

3RT1045-1AP04ČR SI MO RZRJFG7OR5G25 mm2

-W1

ČR

SI

MO

RZ

RJ

FG7OR

5G25 mm2

-W2

-F1-Fx

E4

-Fx

VARIANTA 2

X.2016

Page 74: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

0 1 2 3 4 5 6 7 8 9

G-Flr

. .

-K1

KONTAKTOR JEVKLOPLJEN

0-1-S1 -K1

RDEČA-H1

NV 160

-F1VAROVALČNILOČILNIK

RAZRED I

PRENAPETOSTNIODVODNIKI

-B1KONTAKTORSIEMENS

KOTLOVNICA

NAPETOST JEPRISOTNA

C2A

BELA-H2-H4

2

1

-F2

ZASEBNO OMREŽJE

JAVNO OMREŽJE

OEL1105x1,5 mm2

-W3

DOLDRP9800 -U1

RL- LOČILNO MESTOLASTNA RABAG

GENERATOR 1 GENERATOR 2

FG7OR5x35 mm2

-W1

KOGENERACIJSKI NAPRAVI

MERILNO MESTOZA OBJEKT

PMO

FG7OR5x35 mm2

-W2

ZA OBJEKTNOTRANJI RAZVODI

NV 160

VAROVALČNILOČILNIK

FAZA DATUM IZDELAVE

PODPIS

PODPIS

ŠT.NAČRTA

ŠT. RISBE

Š t e v i l k a l i s t a 1

ELEKTROINŠTALACIJE

VRSTA NAČRTA:

SPREMEMBA:

l i s t o v

INVESTITOR NAROČNIK

od 1

VSEBINA RISBE

E5

PROJEKTANT:

EL PART, Bogdan LEPAN s.p.ODGOVORNI PROJEKTANT

Bogdan.LEPAN,dipl.inž.el.OBDELOVALEC

IZS E-0963IDENT.ŠT.PLINOVODI d.o.o.

Cesta Ljubljanske brigade 11b1000 LJUBLJANA

OBJEKT LOKACIJA

VGRADNJA ENOTE SPTE V KOTLOVNICOMRP, Bohova 19b, 2311 HOČEna parc. št. 733, k.o. BOHOVA

PZR 69/16-E

LANDIS GYR

M.M. proizvodnja...8012586ZMD310CT44+ CU-P42P2

PS PMO 1

LANDIS+ GYR ZMD310CT44+CU-P42 GSM/GPRS

M.M. odjem...4-1306M.M. oddaja...4-8012586

TP BOHOVA VODOVOD(t-117)NN IZVOD I-04 ŽELEZNICA

ENOPOLNA SHEMA VEZAVERAZDELILNIKA PS PMO 1

MRP

63A

50A

3RT1045-1AP04

-Fx

-F1-Fx

VARIANTA 2

X.2016

Page 75: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 76: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi
Page 77: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Plinovodi d.o.o. NAČRT ELEKTRIČNIH INŠTALACIJ IN ELEKTRIČNE OPREME ŠT. 4 PZR 69/16-E

VZDRZEVALNI CENTER MARIBOR- PZR 14

8. PRILOGA 3

Popisi- varianta 2

Page 78: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

REKAPITULACIJA STROŠKOV

I. PRIPRAVLJALNA DELAII. GROBA INSTALACIJSKA DELAIII. OZEMLJITVE IV. RAZDELILNIK PMOV. RAZDELILNIK R-SKVI. FINOMONTAŽNA DELAVII. ZAKLJUČNA DELAVIII. POSEBNI STROŠKI- ELEKTRODISTRIBUCIJA

SKUPAJ (€)DDV (22%)SKUPAJ (€)

0

00

0

0

00

POPISI SPTE KOTLOVNICA MRP MARIBOR- VARIANTA 2

0

000

Stran 1

Page 79: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

I. PRIPRAVLJALNA DELA

1 Priprava gradbišča kpl. 1 02 Transport materialov do objekta kpl. 1 03 Zavarovanje gradbišča kpl. 1 0

SKUPAJ 0

II. GROBA INSTALACIJSKA DELA

1Ročni- strojni izkop kabelskega jarka dimenzije 0,40 x 0,80 m; III.ktg m 15 0

2

Izdelava kabelske blazine iz mivke vključno s prevozom za jarek dim. 0,40 x 0,80 m, zasip in planiranje, vzpostavitev terena v prvotno stanje m 15 0

3 Dobava in polaganje plastičnih cevi Ø110 mm v kabelski jarek m 15 0

4Dobava in polaganje kabla FG7OR 5G35 mm², položenega delno na kabelski polici, delno podzemno v zaščitni cevi m 80 0

5Perforirana pocinkana kabelska polica PK50, komplet z vsem spojnim in montažnim materialom - dobava in montaža m 60 0

6Dobava in polaganje kabla FG7OR 5G10 mm², položenega na kabelski polici m 10 0

7 Kabel OEL110 3G1,5 mm² m 10 08 Kabel OEL110CY 12G0,75 mm² m 10 09 Kabel OEL110CY 7G0,75 mm² m 20 0

10 Kabel OEL110 2x0,5 mm² m 20 011 Kabel SFTP cat. 6 m 20 0

12Inštalacijska cev Ø13 mm, komplet z vsem spojnim in montažnim materialom m 50 0

13 Dobava in priklop 5-polnega vtikača, 63 A kom 114 Priklop kabla FG7OR kom 8 015 Vodnik HO7V-K rumeno-zelen, 1x16 mm² m 25 016 Preboji sten kpl. 2 017 Razni drobni nespecificiran material kpl. 1 0

SKUPAJ 0

III. OZEMLJITVE

1 Kabelski čevelj 16 mm² kom 1 02 Vijačni spoj na opremo kom 1 0

3

Izvedba meritev ponikalne upornosti temeljnega ozemljila, pregled in izdaja zapisnika o opravljenih meritvah in pregledu kpl. 1 0

SKUPAJ 0

Stran 2

Page 80: 1. NASLOVNA STRAN NA ČRTA · 1. NASLOVNA STRAN NA ČRTA ŠTEVIL ČNA OZNAKA NA ČRTA IN VRSTA NA ČRTA: NA ČRT STROJNIH INŠTALACIJ IN STROJNE OPREME ŠT. 5 INVESTITOR: Plinovodi

Opis opreme/del enota količina cena/enoto skupaj

IV. RAZDELILNIK PMO

1 Varovalni vložek NH00/80A kom 3 02 Drobni material kpl. 1 0

SKUPAJ 0

V. RAZDELILNIK R-SK

1

Dobava in montaža atestiranega razdelilnika nadometne izvedbe dimenzij 300 x300 x 190 mm, prebarvan s temeljno in zaščitno barvo, RAL 7032, s trotočkovnim zapiranjem, opremljen z napisi z vgrajeno opremo kom 1 0

2 Varovalčni ločilnik HVL 00-3p M8 M8-P kom 2 03 Varovalni vložek NH00/40A kom 3 04 Varovalni vložek NH00/16A kom 3 05 Sponke, drobni material kpl. 1 0

SKUPAJ 0

VI. FINOMONTAŽNA DELA

1 Montaža dislociranih enot SPTE (izmenjevalec) kom 1 02 Dobava in montaža vtičnice 230 VAC, 16A, n/o kom 1 03 Drobni material kpl. 1 0

SKUPAJ 0

VII. ZAKLJUČNA DELA

1Meritve, preizkusi in spuščanje v pogon posameznih sklopov elektro opreme kpl. 1 0

2Poučitev predstavnika investitorja o rokovanju z elektro instalacijskimi sistemi na objektu kpl. 1 0

3Priprava in izdaja "POTRDILA O ZANESLJIVOSTI OBJEKTA" kot ločena mapa za el. instalacije kpl. 1 0

4 Primopredaja objekta investitorju kpl. 1 05 Izdelava načrtov izvedenega stanja- PID kpl. 1 0

SKUPAJ 0

1Stroški za pridobitev Soglasja za povečanje konične moči objekta iz 43 kW na 55 kW kpl. 1 0

SKUPAJ 0

VIII. POSEBNI STROŠKI- ELEKTRODISTRIBUCIJA

Stran 3