SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS CUTOUTS AND ARRESTERS GENERAL 08.00-03 08.01-01 ARRESTERS, 10KV CUTOUTS AND BRACKETS 08.01-10 08.01-11 CUTOUTS AND ARRESTERS 2 OR 3 EACH ON TRIPLE MOUNTING BRACKET "L" BRACKET 08.01-13 08.01-12 CUTOUTS AND ARRESTERS SINGLE-PHASE TERMINATION ON POLE MOUNTED BRACKET HORIZONTAL CONSTRUCTION TO BRANCH LINE 08.01-36 08.01-37 HORIZONTAL CONSTRUCTION WITH LIGHTNING ARRESTER HORIZONTAL CONSTRUCTION TO HORIZONTAL DEADEND 08.01-32 08.01-33 HORIZONTAL CONSTRUCTION TO HORIZONTAL WITH CUTOUT (FLYING TAP) DOUBLE CIRCUIT CONSTRUCTION WITH LIGHTNING ARRESTER 08.01-29 08.01-28 VERTICAL CONSTRUCTION WITH LIGHTNING ARRESTER ELECTRONIC RESETTABLE SECTIONALIZERS 08.04-02 08.05-00 RECLOSERS, SECTIONALIZERS, TRANSFERS AND THREE-PHASE RECLOSER RECLOSER IDENTIFICATION 08.05-01 08.05-15A ABB RECLOSER ON VERTICAL DOUBLE CIRCUIT WITH VERTICAL BYPASS SWITCH 08.06-10 08.06-08B RECLOSER ASSEMBLY, THREE-PHASE, ABB WITH VERTICAL BYPASS SWITCH RECLOSER AND FRAME, THREE-PHASE, ABB WITH VERTICAL BYPASS SWITCH 08.06-08A RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH 08.06-22A 08.06-22B RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH CUTOUT AND ARRESTER, (2) OR (3)-PHASE TERMINATION ON TRIPLE MOUNTING RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION 08.00-01 DISTRIBUTION SURGE ARRESTERS 0 3 APPR. REVISED BY CK'D 08.05-02 TYPICAL SINGLE-PHASE RECLOSER DIMENSIONS, WEIGHTS AND OIL CAPACITIES 08.01-04 APPLICATION OF DIRECT CONNECTED ARRESTERS ON DISTRIBUTION TRANSFORMERS ELKINS GUINN CECCONI 11/30/10 08.05-15B OIL CIRCUIT RECLOSER - SINGLE-PHASE INSTALLATION BYPASS CUTOUT BRACKET LIGHTNING ARRESTER MOUNTING DETAIL 08.05-16A RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION, FEEDER 08.06 RECLOSERS - THREE-PHASE CONFIGURATIONS 08.05 RECLOSERS - SINGLE-PHASE CONFIGURATIONS 08.04 SECTIONALIZERS 08.01 CUTOUTS AND ARRESTERS 08.00 GENERAL RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH 08.06-11B 08.06-11A RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH RECLOSER ASSEMBLY, THREE-PHASE, VIPER ST WITH VERTICAL BYPASS SWITCH 08.06-11C 08.01-39 VERTICAL CONSTRUCTION - TANGENT FUSED TAP CONSTRUCTION 08.01-38 SINGLE-PHASE CONSTRUCTION - FUSED TAP 08.01-14 SLACKSPAN WITH FUSED CUTOUT ADCOCK GUINN KATIGBAK 12/19/14 RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12A RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12B ASSEMBLY, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12C 08.05-18B RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION SLACK SPAN TAP 08.05-18A RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION SLACK SPAN TAP WIRING DIAGRAM FOR PT CLUSTER FOR G&W VIPER 08.06-15A 08.06-15B 08.05-16B RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION, FEEDER 08.00-00A DEF X DEP DEM DEC 08.05-06 COOPER RECLOSERS OPERATING LEVERS ABB TO SEL 651-R2 CONTROL CONVERSION ON ABB RECLOSERS 08.06-16A ABB TO SEL 651-R2 CONTROL CONVERSION ON ABB RECLOSERS 08.06-16B WIRING DIAGRAM FOR PT CLUSTER ABB 1PT TO 3PT CONVERSION FUSE AND BATTERY FOR SEL 651-R2 CONTROLS (ABB & VIPER) 08.06-15C 08.06-15D FUSE AND BATTERY FOR SEL 651-R2 CONTROLS (ABB & VIPER) 4 ADCOCK BURLISON KATIGBAK 12/16/15 08.06-13A DOUBLE CIRCUIT, THREE-PHASE, VIPER ST 08.06-13B DOUBLE CIRCUIT, THREE-PHASE, VIPER ST 08.06-14A VIPER RECLOSER HORIZONTAL CONSTRUCTION 08.06-14B VIPER RECLOSER HORIZONTAL CONSTRUCTION 08.01-16 VERTICAL DOUBLE DEADEND WITH CUTOUTS 08.05-114B OIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION, HORIZONTAL CONSTRUCTION 08.05-114A OIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION, HORIZONTAL CONSTRUCTION SINGLE-PHASE UNITS SINGLE-PHASE UNITS 5 ADCOCK BURLISON KATIGBAK 4/18/16 08.06-15E SPECIAL PROVISIONS - G&W VIPER ST, IPP INTERCONNECTION

08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

Embed Size (px)

Citation preview

Page 1: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES

TABLE OF CONTENTS

CUTOUTS AND ARRESTERS GENERAL 08.00-03

08.01-01ARRESTERS, 10KV

CUTOUTS AND BRACKETS 08.01-1008.01-11CUTOUTS AND ARRESTERS 2 OR 3 EACH ON TRIPLE MOUNTING BRACKET

"L" BRACKET

08.01-13

08.01-12CUTOUTS AND ARRESTERS SINGLE-PHASE TERMINATION ON POLE MOUNTED

BRACKET

HORIZONTAL CONSTRUCTION TO BRANCH LINE 08.01-3608.01-37HORIZONTAL CONSTRUCTION WITH LIGHTNING ARRESTER

HORIZONTAL CONSTRUCTION TO HORIZONTAL DEADEND 08.01-3208.01-33HORIZONTAL CONSTRUCTION TO HORIZONTAL WITH CUTOUT (FLYING TAP)

DOUBLE CIRCUIT CONSTRUCTION WITH LIGHTNING ARRESTER 08.01-2908.01-28VERTICAL CONSTRUCTION WITH LIGHTNING ARRESTER

ELECTRONIC RESETTABLE SECTIONALIZERS 08.04-02

08.05-00RECLOSERS, SECTIONALIZERS, TRANSFERS AND THREE-PHASE RECLOSER

RECLOSER IDENTIFICATION 08.05-01

08.05-15A

ABB RECLOSER ON VERTICAL DOUBLE CIRCUIT WITH VERTICAL BYPASS SWITCH 08.06-1008.06-08BRECLOSER ASSEMBLY, THREE-PHASE, ABB WITH VERTICAL BYPASS SWITCH

RECLOSER AND FRAME, THREE-PHASE, ABB WITH VERTICAL BYPASS SWITCH 08.06-08A

RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH 08.06-22A08.06-22BRECLOSER ASSEMBLY, THREE-PHASE, VERTICAL, 600 AMP SWITCH

CUTOUT AND ARRESTER, (2) OR (3)-PHASE TERMINATION ON TRIPLE MOUNTING

RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION

08.00-01DISTRIBUTION SURGE ARRESTERS

0

3

APPR.REVISED BY CK'D

08.05-02TYPICAL SINGLE-PHASE RECLOSER DIMENSIONS, WEIGHTS AND OIL CAPACITIES

08.01-04APPLICATION OF DIRECT CONNECTED ARRESTERS ON DISTRIBUTION TRANSFORMERS

ELKINSGUINNCECCONI11/30/10

08.05-15BOIL CIRCUIT RECLOSER - SINGLE-PHASE INSTALLATION BYPASS CUTOUT BRACKET

LIGHTNING ARRESTER MOUNTING DETAIL

08.05-16ARECLOSER ASSEMBLY, VERTICAL CONSTRUCTION, FEEDER

08.06 RECLOSERS - THREE-PHASE CONFIGURATIONS

08.05 RECLOSERS - SINGLE-PHASE CONFIGURATIONS

08.04 SECTIONALIZERS

08.01 CUTOUTS AND ARRESTERS

08.00 GENERAL

RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH 08.06-11B08.06-11ARECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH

RECLOSER ASSEMBLY, THREE-PHASE, VIPER ST WITH VERTICAL BYPASS SWITCH 08.06-11C

08.01-39VERTICAL CONSTRUCTION - TANGENT FUSED TAP CONSTRUCTION08.01-38SINGLE-PHASE CONSTRUCTION - FUSED TAP

08.01-14SLACKSPAN WITH FUSED CUTOUT

ADCOCKGUINNKATIGBAK12/19/14

RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12A

RECLOSER AND FRAME, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12B

ASSEMBLY, THREE-PHASE, VIPER ST, WITH VERTICAL BYPASS SWITCH - 25KV CONSTRUCTION 08.06-12C

08.05-18BRECLOSER ASSEMBLY, VERTICAL CONSTRUCTION SLACK SPAN TAP08.05-18ARECLOSER ASSEMBLY, VERTICAL CONSTRUCTION SLACK SPAN TAP

WIRING DIAGRAM FOR PT CLUSTER FOR G&W VIPER 08.06-15A08.06-15B

08.05-16BRECLOSER ASSEMBLY, VERTICAL CONSTRUCTION, FEEDER

08.00-00A

DEF

X

DEPDEMDEC

08.05-06COOPER RECLOSERS OPERATING LEVERS

ABB TO SEL 651-R2 CONTROL CONVERSION ON ABB RECLOSERS 08.06-16AABB TO SEL 651-R2 CONTROL CONVERSION ON ABB RECLOSERS 08.06-16B

WIRING DIAGRAM FOR PT CLUSTER ABB 1PT TO 3PT CONVERSIONFUSE AND BATTERY FOR SEL 651-R2 CONTROLS (ABB & VIPER) 08.06-15C

08.06-15DFUSE AND BATTERY FOR SEL 651-R2 CONTROLS (ABB & VIPER)

4 ADCOCKBURLISONKATIGBAK12/16/15

08.06-13ADOUBLE CIRCUIT, THREE-PHASE, VIPER ST08.06-13BDOUBLE CIRCUIT, THREE-PHASE, VIPER ST08.06-14AVIPER RECLOSER HORIZONTAL CONSTRUCTION08.06-14BVIPER RECLOSER HORIZONTAL CONSTRUCTION

08.01-16VERTICAL DOUBLE DEADEND WITH CUTOUTS

08.05-114BOIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION, HORIZONTAL CONSTRUCTION

08.05-114AOIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION, HORIZONTAL CONSTRUCTION

SINGLE-PHASE UNITS

SINGLE-PHASE UNITS

5 ADCOCKBURLISONKATIGBAK4/18/16

08.06-15ESPECIAL PROVISIONS - G&W VIPER ST, IPP INTERCONNECTION

Page 2: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES

TABLE OF CONTENTS0

3

2

APPR.REVISED BY CK'D

ELKINS12/1/10 CECCONI GUINN

08.10 SWITCHES - MANUAL08.10-10BYPASS SWITCHES

SWITCH MOUNTING IN VERTICAL DOUBLE CIRCUIT 08.10-12A

600 AMP DOUBLE CIRCUIT TIE SWITCH 08.10-14A600 AMP DOUBLE CIRCUIT TIE SWITCH 08.10-14B

08.10-20SWITCH ASSEMBLY, 300 AMP, SOLID BLADE HORIZONTAL08.10-18BSWITCH ASSEMBLY, 600 AMP, SOLID BLADE, VERTICAL08.10-18ASWITCH ASSEMBLY, 600 AMP, SOLID BLADE, VERTICAL

SWITCH ASSEMBLY, 300 AMP, SOLID BLADE, VERTICAL 08.10-16

SWITCH ASSEMBLY, 600 AMP, SOLID BLADE HORIZONTAL 08.10-22

VLR LOAD CONTROL SWITCH 08.12-02BVLR LOAD CONTROL SWITCH 08.12-02A08.12 SWITCHES - LOAD CONTROL

08.13-01OVERHEAD AUTOMATIC TRANSFER SCHEME08.13 SWITCHES - AUTOMATED

08.13-03VLR TYPE S TRANSFER CONTROL

SWITCH MOUNTING IN VERTICAL DOUBLE CIRCUIT 08.10-12B

600 AMP INLINE DISCONNECT 08.10-24

08.13-10D08.13-10E

OMNI-RUPTER SWITCH CONTROL FACEPLATEANTENNA INSTALLATION FOR VERTICAL OMNI-RUPTER SWITCH

08.13-05AUTOMATIC TRANSFER SWITCH ASSEMBLY, (VLR), CONTROL WIRING DETAIL

SCADA MATE CX SWITCH STANDARD MOUNTING ARRANGEMENT 08.13-08CSCADA MATE CX SWITCH STANDARD MOUNTING ARRANGEMENT 08.13-08BSCADA MATE CX SWITCH STANDARD MOUNTING ARRANGEMENT 08.13-08A

OMNI-RUPTER SWITCH STANDARD MOUNTING ARRANGEMENT (FMO) 08.13-10A08.13-10B08.13-10C

08.13-11A

08.13-11B

08.13-13B08.13-13A

OMNI-RUPTER SWITCH STANDARD MOUNTING ARRANGEMENT (FMO)OMNI-RUPTER SWITCH STANDARD MOUNTING ARRANGEMENT (FMO)OMNI-RUPTER SWITCH STANDARD STACKED

OMNI-RUPTER SWITCH HORIZONTAL MOUNTING ARRANGEMENT (FMO)OMNI-RUPTER SWITCH HORIZONTAL MOUNTING ARRANGEMENT (FMO)OMNI-RUPTER SWITCH HORIZONTAL MOUNTING ARRANGEMENT (FMO) 08.13-13C

DOUBLE-CIRCUIT POLE ARRANGEMENT (FMO)OMNI-RUPTER SWITCH STANDARD STACKED

DOUBLE-CIRCUIT POLE ARRANGEMENT (FMO)

INTELLITEAM RADIO TRANSCEIVERS (FMO) 08.13-15

THE FOR MAINTENANCE ONLY DRAWINGS LISTED BELOW ARE NOT CONTAINEDIN THE PRINTED SPEC BOOK, BUT ARE AVAILABLE ONLINE

FOR MAINTENANCE ONLY DRAWINGS

08.04-12HORIZONTAL CONSTRUCTION TO HORIZONTAL CONSTRUCTION WITH

SECTIONALIZER ASSEMBLY, OIL TYPE, VERTICAL (FMO) 08.04-08

VERTICAL CONSTRUCTION TO VERTICAL CONSTRUCTION WITH

08.06-12RECLOSER ASSEMBLY, THREE-PHASE, HORIZONTAL 600 AMP SWITCH (FMO)OIL SECTIONALIZER (FMO)

08.04-06WITH OIL SECTIONALIZER (FMO)

08.12-06LOAD CONTROL SWITCH ASSEMBLY, (VLR), THREE-PHASE HORIZONTAL

WITH 600 AMP BYPASS (FMO)

VERTICAL TANGENT CROSSING WITH 600 AMP DISCONNECTS 08.10-26

ADCOCK9/26/14 KATIGBAK GUINN

08.00-00B

DEF

X

DEPDEMDEC

VERSAVAC LOAD CONTROL 08.12-04AVERSAVAC LOAD CONTROL 08.12-04BCONNECTION DIAGRAM FOR VERSAVAC SWITCH 08.12-04C

ADCOCK8/27/15 KATIGBAK BURLISON

LOAD CONTROL SWITCH 600 AMP 08.12-06ALOAD CONTROL SWITCH 600 AMP 08.12-06B

4 ADCOCK1/6/16 KATIGBAK BURLISON

RECLOSER ASSEMBLY, HORIZONTAL CONSTRUCTION (FMO) 08.05-17ARECLOSER ASSEMBLY, HORIZONTAL CONSTRUCTION (FMO) 08.05-17B

Page 3: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

STANDARD PROCEDURES BULLETIN

STANDARD DISTRIBUTION ARRESTERS:

THE STANDARD DISTRIBUTION ARRESTER IS A DIRECT-CONNECTED METAL OXIDE ARRESTER WITH A GROUND

INSTALLATION PRACTICES:

1. ARRESTER LEAD LENGTHS (BOTH LINE AND GROUND LEADS) SHALL BE AS SHORT AND AS STRAIGHT AS POSSIBLE. THIS PROVIDES THE BEST PROTECTION BY MINIMIZING THE SURGE VOLTAGE DURING ARRESTEROPERATION. DO NOT COIL TRANSFORMER RISERS.

2. GROUND RODS SHALL BE INSTALLED AT ALL POLES CONTAINING ARRESTERS ACCORDING TO THE STANDARD

ARRESTER APPLICATIONS

TRANSFORMERS, RECLOSERS, CAPACITOR BANKS, VOLTAGE REGULATORS, AND OTHER EQUIPMENT SHALL HAVE ARRESTERS INSTALLED AS SHOWN ON THE APPROPRIATE SPECIFICATION DRAWINGS CONTAINEDHEREIN.

2. LINE PROTECTION

A. ALL NORMAL OPEN POINTS SHALL HAVE ARRESTERS INSTALLED ON EACH PHASE ON BOTH SIDES(NORMAL SOURCE AND LOAD). ARRESTERS MAY BE MOUNTED ON POLE ADJACENT TO SWITCHES.

B. INSTALL ARRESTERS AT DEADENDS UNLESS PROTECTED BY EQUIPMENT ARRESTER.

C. INSTALL ARRESTERS EVERY 1400' TO 1600' UNLESS THERE ARE ARRESTERS PRESENT. ALSO, AREAS WITH TALL TREES AND/OR BUILDINGS ALONG SIDE THE LINE ARE SHIELDED AND MIGHT REQUIRE LESS REQUIRE LESS ARRESTERS AS PER ENGINEER'S JUDGMENT.

LEAD DISCONNECTOR (DWG. 08.01-04 FOR DISCONNECTOR PROCEDURES).

1. EQUIPMENT PROTECTION (GROUND PER DWGS. 01.01-01A, 01.01-01B, 01.01-01C AND 01.01-05) ALL

DISTRIBUTION SURGE ARRESTERS

PROCEDURES OUTLINED ON DWGS. 01.01-01A, 01.01-01B, 01.01-01C AND 01.01-05.

METAL OXIDE ARRESTERS (MOV) HAVE BEEN PURCHASED SINCE 1984 AND OFFER THE BEST AVAILABLEPROTECTION AGAINST LIGHTNING AND SWITCHING SURGES. BY DESIGN, THE MOV ARRESTER CONDUCTS ASMALL LEAKAGE CURRENT (MILLIAMPS) TO GROUND UNDER NORMAL VOLTAGE CONDITIONS. SINCE 1990, ALLOF OUR MOV ARRESTERS HAVE BEEN PURCHASED WITH POLYMER HOUSINGS. THE ADVANTAGE OF THE POLYMERHOUSING IS THAT IT IS DESIGNED TO RETAIN THE BLOCKS DURING A CATASTROPHIC FAILURE MODE. THESEMOV ARRESTERS ARE AVAILABLE IN THREE DIFFERENT CLASSIFICATIONS AS FOLLOWS:

RISER POLE ARRESTERS ARE USED ON PRIMARY UNDERGROUND CABLE RISERS. THESE ARRESTERS NORMALLYCONTAIN LARGER BLOCKS THAN STANDARD DISTRIBUTION ARRESTERS TO PROVIDE ADDITIONAL PROTECTIONFOR THIS APPLICATION. THESE ARRESTERS ARE LABELED WITH THE WORDS "RP" AND THE VOLTAGE CLASS.

STANDARD DISTRIBUTION ARRESTERS ARE USED FOR OVERHEAD LINE AND EQUIPMENT PROTECTION. WHILETHEY DO NOT HAVE A SPARK OVER VOLTAGE AS LOW AS THE RISER POLE ARRESTER, THEY PROVIDE ANECONOMICAL BIL MARGIN OF PROTECTION EXCEEDING THE OLD SILICONE CARBIDE ARRESTER.

TRANSFORMER ARRESTERS ARE IDENTICAL TO THE STANDARD DISTRIBUTION ARRESTER. THEY ARE CATALOGED DIFFERENTLY TO INCLUDE A CONNECTION LEAD AND A GROUND STRAP TO CONNECT IT TO ATRANSFORMER.

SILICONE CARBIDE ARRESTERS HAVE NOT BEEN PURCHASED SINCE 1984. THESE ARRESTERS CAN BE FOUND ONTHE SYSTEM WITH INTERNAL OR EXTERNAL GAP STRUCTURES. ALL SILICONE CARBIDE ARRESTERS HAVEPORCELAIN HOUSINGS.

INTERNAL GAP ARRESTERS CONTINUE TO PROVIDE GOOD SURGE PROTECTION FOR THE SYSTEM AND SHALL

EXTERNAL GAP ARRESTERS THAT ARE REMOVED SHALL BE SCRAPPED.

CONTINUE TO BE USED UNTIL THEY ARE REMOVED FOR ANY REASON. ONCE REMOVED, THEY SHALL BESCRAPPED.

0

3

2

1

APPR.REVISED BY CK'D

ELKINSGUINNHOFFMAN8/16/10

08.00-01

DEF

X

DEPDEMDEC

ADCOCKWHITELOOSIER3/31/15

Page 4: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

8. AN ARRESTER SHOULD BE USED TO PROTECT ANY PHASE THAT HAS A GROUND WIRE EXTENDING PAST IT, EXCEPT ON CONCRETE OR STEEL POLES.

CUTOUTS AND ARRESTERS GENERALGUINNHOFFMAN11/29/10 ELKINS0

3

2

1

APPR.REVISED BY CK'D

GENERAL

ON WOOD POLE CONSTRUCTION USE SINGLE COIL LOCKWASHER AND SQUARE WASHERS WITH CUTOUT,ARRESTER AND SWITCH BRACKETS.

1. BYPASS FUSE HOLDERS OR NORMALLY OPEN CUTOUT DOORS SHOULD BE HUNG BY THEIR OPERATING RINGS SO THE BARRELS WILL NOT FILL UP WITH WATER.

2. A TRANSFORMER STEM CONNECTOR MAY BE USED WHEN 1/0 OR SMALLER ALUMINUM WIRE IS RUN DIRECTLY INTO THE CUTOUT.

3. WHEN ADDING CUTOUTS TO EXISTING VERTICAL CONSTRUCTION, THE PHASE TO PHASE SPACING SHOULDBE 42 INCHES FOR 23KV.

1. ARRESTERS SHALL BE INSTALLED ON BOTH SIDES OF ANY NORMAL OPEN PRIMARY SWITCH DEVICE WHICHCAN BE SOURCE FED FROM BOTH DIRECTIONS.

2. THE PRIMARY ARRESTER TAP SHOULD BE #6 BARE SOFT DRAWN SOLID COPPER WIRE.

3. ARRESTERS SHALL BE POSITIONED SUCH THAT A BLOWN DISCONNECTOR/ISOLATOR WILL NOT AFFECT OTHER ENERGIZED EQUIPMENT.

4. ARRESTERS SHALL BE INSTALLED ON THE SOURCE AND LOAD SIDE OF RECLOSERS AND REGULATORS.

6. THE PRIMARY ARRESTER TAP CONNECTION CAN BE MADE WITH ALUMINUM HOT LINE ARRESTER CLAMPS. STIRRUPS ARE NOT REQUIRED FOR ARRESTERS.

7. KEEP ARRESTER TAP AND GROUND LEADS AS SHORT AS POSSIBLE. THIS PROVIDES GREATER EQUIPMENT PROTECTION.

5. AT VOLTAGE REGULATOR INSTALLATIONS, INSTALL THE LIGHTNING ARRESTERS ON THE REGULATOR, IFPOSSIBLE. IF NOT POSSIBLE, MOUNT THE ARRESTERS AS CLOSE TO THE SOURCE AND LOAD BUSHINGS ASPOSSIBLE.

ON THE TERMINAL POLE OUTSIDE THE SUBSTATION AND ON THE TERMINAL POLE IN THE SUBSTATION.

CUTOUTS

ARRESTERS

11. INSTALL ARRESTERS EVERY 1400' TO 1600' UNLESS THERE ARE ARRESTERS PRESENT. ALSO, AREAS WITHTALL TREES AND/OR BUILDINGS ALONG SIDE THE LINE ARE SHIELDED AND MIGHT REQUIRE LESS ARRESTERS AS PER ENGINEER'S JUDGMENT.

12. CONCRETE OR METAL TRANSMISSION AND DISTRIBUTION POLES: INSULATE WITH 35KV INSULATORS ANDAPPLY LIGHTNING ARRESTERS ON ALL PHASES EVERY 550'.

10. RISER POLE ARRESTERS SHALL BE USED ON ALL OVERHEAD TO UNDERGROUND DIP POLES.

9. ON UNDERGROUND SUBSTATION EXITS, DISTRIBUTION CLASS RISER POLE ARRESTERS SHALL BE LOCATED

08.00-03

DEF

X

DEP

X

DEM

X

DEC

XWHITELOOSIER3/31/15 ADCOCK

Page 5: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-01DWG.

1

2

3

4

ARRESTERS, 10 KVELKINSGUINNHOFFMAN8/31/10

R

BRACKET, ARRESTER AND CUTOUTARRESTER, LIGHTNING, 10KV, HD MOV

1

BOLT, MACHINE, 5/8" X 10"BRACKET, SINGLE MOUNT

BRACKET, DOUBLE LIGHTNING ARR & COWASHER, 2-1/4" SQUAREWASHER, SPRING COIL, 5/8"

21

21

2

220202070101311263152106013264013308070106

WASHER, 2-1/4" SQUAREWASHER, SPRING COIL, 5/8"2

2

152106013264013308

BOLT, MACHINE, 5/8" X 10"2

BKTCOLASTLXARMF

BKTCOLASNGSTLF

BKTCOLADBLSTLF

0

3

2

1

APPR.REVISED BY CK'D

OVER-TORQUING CAN EASILY OCCUR USING THESE WRENCHES RESULTING IN A BROKEN CONTACTINSIDE THE ARRESTER HOUSING.

1. CAUTION: DO NOT TIGHTEN TOP NUT ON ARRESTERS WITH AN AIR OR HYDRAULIC SPEED WRENCH.

4

3

2

BILL OF MATERIALS

CATALOGDESCRIPTION

1

1

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

NOTES:

CABLE, 600V #6 SOLID SD CU193511AREQOH10F1 1

2

Page 6: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.01-04

ISOLATOR

PRIMARY RISER

GROUND STRAP

GROUNDED

NOTES:

1. DIRECT CONNECTED ARRESTER LEADS ARE FURNISHED WITH AN EYE TERMINAL. THE LEAD IS TO BE CONNECTEDBETWEEN THE ARRESTER AND THE PRIMARY BUSHING TERMINAL WITH THE EYE TERMINAL BETWEEN THE NUTAND THE TERMINAL, AND ARRANGED SO AS NOT TO INTERFERE WITH THE PRIMARY RISER

2. IN THE EVENT OF AN ARRESTER FAILURE, THE ISOLATOR WILL OPERATE AND DISCONNECT THE GROUND LEAD,THUS PREVENTING AN INTERRUPTION TO THE CIRCUIT. ALL FAILED ARRESTERS ARE TO BE REPORTED TO THELOCAL OPERATIONS CENTER. THE ARRESTER IS TO BE CHANGED OUT AS SOON AS POSSIBLE AFTER BEINGREPORTED.

ROTATE ARRESTER TOBE STRAIGHT OUT FROMTANK

3. ON NEW POLE MOUNTED SINGLE-PHASE TRANSFORMERS, THE TRANSFORMER IS SHIPPED WITH THE LIGHTNING ARRESTER ROTATED UP AGAINST THE TANK. THIS IS DONE TO PREVENT BREAKAGE OF THE ARRESTER DURINGSHIPPING. BEFORE THE TRANSFORMER IS INSTALLED, THE ARRESTER MOUNTING BOLT SHOULD BE LOOSENEDAND THE ARRESTER ROTATED UNTIL IT IS STRAIGHT OUT FROM THE TANK. IF THIS IS NOT DONE AND THEARRESTER IS LEFT UP AGAINST THE TANK, IT WILL EVENTUALLY CAUSE MOMENTARY FEEDER OPERATIONS OROUTAGES.

CAUTION:

VOLTAGE

MAY BE ENERGIZEDAT PRIMARY

FAILED ARRESTERPROPERLY INSTALLED ARRESTER

APPLICATION OF DIRECT CONNECTED ARRESTERS

ON DISTRIBUTION TRANSFORMERSELKINSGUINNGUINN7/11/100

3

2

1

APPR.REVISED BY CK'D

TORQUING CAN EASILY OCCUR USING THESE WRENCHES RESULTING IN A BROKEN CONTACT INSIDE THEARRESTER HOUSING.

4. CAUTION: DO NOT TIGHTEN TOP NUT ON ARRESTERS WITH AN AIR OR HYDRAULIC SPEED WRENCH. OVER-

Page 7: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-10DWG.

23

4

CUTOUTS AND BRACKETSELKINSGUINNHOFFMAN10/12/10

R

C

AH

CE

N

0

3

2

1

APPR.REVISED BY CK'D

3

111

BILL OF MATERIALS

CATALOGDESCRIPTION

1

111

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

CUTOUT, NONLOADBREAK, 15KV, 100A, 16KA, 110KV BIL CUTOUT, NONLOADBREAK, 15KV, 100A, 16KA, 110KV BILCUTOUT, NONLOADBREAK, CUTOUT, 27KV, 100A, 12KA, 150KV BIL

BRACKET, .., SGL MTWASHER, .., SPRING,COIL,STEEL,FOR,5/8",BOLT,GALV.WASHER, SQUARE, 2-1/4",SQUARE,FLAT,13/16",HOLE,GALV. BOLT, MACHINE, 5/8 IN, 10 IN, STEEL, A-ASTM A307, GLV, MACH,

NOTES:

FUSE15CO100FTFUSE15CO100FFUSE27CO100F

BKTCOLASNGSTLF

221112

221139

013308152106

311263

11

1222

1

ELKINSBURLISONBURLISON2/6/12

FOR MAINTENANCE ONLY

5

FOR TRANSFORMER AND CAPACITOR BANKS. THIS ENSURES PROPER ACCOUNTING IN WMIS.

2. 27KV CUTOUTS ARE REQUIRED ON THE 25KV SYSTEM IN HOLOPAW, ON ALL CONCRETE POLES AND INCOASTAL/CONTAMINATED AREAS.

3. USE 100 AMP CUTOUT DOORS WITH 103 FUSE LINKS AND SMALLER. USE 200 AMP CUTOUT DOORS WITH125, 150, AND 200 AMP FUSE LINKS. DO NOT USE 200 AMP CUTOUT DOORS WITH 103 OR SMALLER FUSES.

111

111 1 CUTOUT, SILICONE, 27KV, 100A, 12KA, 150KV BIL, SILICON

CUTOUT, NONLOADBREAK, CUTOUT, 27KV, 100A, 12KA, 150KV BILCUTOUT, SILICONE, 27KV, 100A, 12KA, 150KV BIL, SILICON

FUSE27CO100PFTFUSE27CO100FTFUSE27CO100PF

922009006311

11

11 1 CUTOUT, NONLOADBREAK, CUTOUT, 27KV, 200A, 10KA, 150KV BIL

CUTOUT, BLADE, BLADE,SLD,NONLOADBREAK,300A,15 KVFUSE27CO200FSW153COSBDF

2211439220210916 1

2

1

1

1 1 CUTOUT, BLADE, SLD, NONLOADBREAK BLADE,300A,25 KV, 150 KV BILBRACKET, LA & CO TY ABOLT, CARRIAGE, 3/8 IN, 6 IN, CARBON STEEL, ASTM A153, CRG 3

SW253COSBDF

BKTCOLASTLXARMF

9220210993070101011213

12

4 1

BRACKET, .., ARSTR & CO,DBL MNTGWASHER, .., SPRING,COIL,STEEL,FOR,5/8",BOLT,GALV.WASHER, SQUARE, 2-1/4",SQUARE,FLAT,13/16",HOLE,GALV. BOLT, MACHINE, 5/8 IN, 10 IN, STEEL, A-ASTM A307, GLV, MACH,

BKTCOLADBLSTLF

070106

55

11 1 BLADE, CUTOUT, BLADE SOLID, CUTOUT, 15KV, 300A

BLADE, CUTOUT, BLADE, SOLID, CUTOUT, 27KV, 300ASW153COSBDBOFSW253COSBDBOF

269046269043 1

22

12

221112

221139 1192200900631

013264

013308152106

013264

POLE MOUNTED CUTOUTCROSSARM MOUNTED CIRCUIT

1. USE FUSE (FUSE____F) FOR OVERHEAD AND UNDERGROUND LINE CUTOUTS. USE TFUSE ( TFUSE____F)

Page 8: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-11DWG.

CUTOUTS AND ARRESTERS2 OR 3 EACH ON TRIPLE

MOUNTING BRACKETELKINSGUINNGUINN8/30/10

WASHER, SPRING COIL, 5/8"

CUTOUT, 15 KV 100A, 16KA ASYMMETRICALBRACKET, LA, CUTOUT, 48"

1

21

BOLT, MACHINE, SQ, NUT, 5/8" X 12"WASHER, 2-1/4" SQUARE2

2

221112070104013264013308152107

0

3

2

1

APPR.REVISED BY CK'D

BILL OF MATERIALS

CATALOGDESCRIPTION

1

QTYPERCU

NUMBERCOMPATIBLE

UNITQTY

REQ'D

FUSE15CO100F 2 OR 3

BKTCOLATRISTLF2

1

CUITEMNO.

1

2

ADCOCKDANNAMcCONNELL4/9/13

Page 9: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-12DWG.

1

CUTOUTS AND ARRESTERSSINGLE-PHASE TERMINATION

ON POLE MOUNTED "L" BRACKETELKINSGUINNHOFFMAN11/5/100

3

2

1

APPR.REVISED BY CK'D

OVER-TORQUING CAN EASILY OCCUR USING THESE WRENCHES RESULTING IN A BROKEN CONTACTINSIDE THE ARRESTER HOUSING.

1. CAUTION: DO NOT TIGHTEN TOP NUT ON ARRESTERS WITH AN AIR OR HYDRAULIC SPEED WRENCH.

NOTES:

4

3

2

1 FUSE15CO100F

BILL OF MATERIALS

CATALOGDESCRIPTION

ARUGTP10F

BKTCOLASNGSTLF

KHLC40N6F 1

1

1

1

QTY

21

22

1111

PERCU

NUMBERMACRO UNIT

CA2T15FM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

CUTOUT, LOADBREAK, 15KV, 100A, 16KA, 110KV BILARRESTER, LIGHTNING, RP, 10KV, FOR TRANSITION POLES, HDCONNECTOR, STEM, ARRESTERBRACKET, SGL MTWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/16" HOLE, GALV.BOLT, MACHINE, 5/8" X 10", STEEL, A-ASTM A307, GALV.CLAMP, HOT LINE, ALUM, SMALL, 4/0

221112220208153534311263013264013308152106

9220184790

CA1T15FMOR

2

3

4

(TWO-PHASE)

ADCOCKDANNA6/7/13

CONNECTOR STEMINCLUDED WITHTERMINATOR KIT

Page 10: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-13DWG.

3

CUTOUT AND ARRESTER,(2) OR (3) PHASE TERMINATIONON TRIPLE MOUNTING BRACKETELKINSGUINNHOFFMAN11/5/100

3

2

1

APPR.REVISED BY CK'D

OVER-TORQUING CAN EASILY OCCUR USING THESE WRENCHES RESULTING IN A BROKEN CONTACTINSIDE THE ARRESTER HOUSING.

1. CAUTION: DO NOT TIGHTEN TOP NUT ON ARRESTERS WITH AN AIR OR HYDRAULIC SPEED WRENCH.

NOTES:

BKTCOLATR1STLF

4

3

2

1 FUSE15CO100F

BILL OF MATERIALS

CATALOGDESCRIPTION

ARUGTP10F

1

3

3

QTY

2

22

1111

PERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

CUTOUT, LOADBREAK, 15KV, 100A, 16KA, 110KV BILARRESTER, LIGHTNING, RP, 10KV, FOR TRANSITION POLES, HDCONNECTOR, STEM, ARRESTERBRACKET, LA AND CO TRI MNTGWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/16" HOLE, GALV.BOLT, MACHINE, 5/8" X 10", STEEL, A-ASTM A307, GALV.

221112220208153534070104013264013308152106

CA3T15FM

1

2

4

KHLC40N6F 3 1 CLAMP, HOT LINE, ALUM, SMALL, 4/09220184790

ADCOCKDANNA6/7/13

Page 11: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

11/9/12 HOFFMAN DANNA ADCOCK

SLACKSPAN WITH FUSED CUTOUT

3

REVISED CK'DBY APPR.

1

0

2

FRONT VIEW

72"

5"

36"

36"

KHLC40N6F

KHLC7933FOR

NOTES:

1. SEE DWG 03.06-04 FOR POST TYPE INSULATORS.

2. SEE DWG. 03.06-08 FOR PIN TYPE INSULATORS.

3. SEE DWG. 03.03-04 FOR SLACK SPAN CLAMPS.

4. SEE DWG. 03.16-00 FOR SLACK SPAN GRIPS.

NEUTRAL

6"

4"

14"

14"

14"

4"

8/7/14 SALAS

4"

#2 WP COPPERCU RCRISERN2CUF

08.01-14

DEF

X

DEPDEMDEC

DANNA ADCOCK

Page 12: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

1. THIS DESIGN SPECIFICATION CAN ALSO BE APPLIED TO A SINGLE-PHASE CONFIGURATION.

NOTES:

VERTICAL DOUBLE DEADEND WITH CUTOUTS

PLAN VIEW

4"

FRONT VIEW

0

2

1

APPR.REVISED BY CK'D

NEUTRAL

#6 SD BC

3

8/10/15 LOOSIER BURLISON ADCOCK

1

4 3

2

08.01-16

DEF

X

DEPDEMDEC

SOURCE LOAD

6"

C TOP BOLT OF BRACKET

72"

36"

5"

L

36"

5432

1 ISEYEBOLT5812F

BILL OF MATERIALS

ITEM

11709

BRACKET, STANDOFF, 1.5" RND X 18" LG IN, FIBERGLASSINSULATOR DEADEND SUSPENSION (KV) POLYMERDEADEND CLAMP (WIRE)

BOLT, OVAL EYE, 5/8" X 12"

INSULATOR SUPPORT EYENUT

DESCRIPTION

13346ISEYENUT58F 12210

DECLMP(WIRE)F -IDES(KV)F -

922027581763

63

3

QTY

11

1111

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

WASHER, 3" SQ., CURVED, 13/16" HOLE

5

BKTCO18FGF

Page 13: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NEUTRAL

VERTICAL CONSTRUCTION

WITH LIGHTNING ARRESTERELKINSGUINNROBESON8/11/10

FRONT VIEW FRONT VIEW

PLAN VIEW

PLAN VIEW

TANGENT CONSTRUCTION

0

2

1

APPR.REVISED BY CK'D

5"

36"

36"

72"

36"

36"

72"

8"

8"

8"

DEADEND CONSTRUCTION

NEUTRAL

CN 220202

CN 080212

8" TYP.

4" TYP. TO

#6 SD BC#6 SD BC

NOTES:

#6 SD BC

3

GUY ATTACHMENT

ELKINSBURLISONBURLISON3/2/11

SEE NOTE 1

1. INSTALL GROUND AWAY FROM INSULATOR.

SEE NOTE 1

ADCOCKDANNAMcCONNELL5/24/13

LOOSIER6/6/14

#6 WP COPPERCU ARRRISERN6CUF

08.01-28

DEF

X

DEPDEMDEC

CN 9220218856

CN 9220184794CN 9220184790 OR

ADCOCKDANNA

Page 14: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.01-29

DOUBLE CIRCUIT CONSTRUCTION

WITH LIGHTNING ARRESTER

FRONT VIEW

NOTES:

R

ELKINS11/29/10 HOFFMAN GUINN0

3

2

1

APPR.REVISED BY CK'D

1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

NEUTRAL

36" MIN.36"

64"

5"

PLAN VIEW

4" TYP.

TOP BRACKET BOLT

10"

36"

Page 15: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

1. CUTOUTS WILL NORMALLY BE INSTALLED ON THE TAP POLE.

HORIZONTAL CONSTRUCTION TO

HORIZONTAL DEADENDELKINSGUINNROBESON8/11/10

FRONT VIEW FRONT VIEW

PLAN VIEW

PLAN VIEW

78" GUY

STIC

K

NEUTRAL

72"

36"

4"

6"72"

4"

6"

8"18"16"34"8"

6"

6"

18"

16"

34"

8"

0

3

2

1

APPR.REVISED BY CK'D

8"

6"

4"

#6 SD BC

#6 SD BC

ELKINSBURLISONBURLISON8/31/11

KHLC40N6F

KHLC7933FOR

ADCOCKDANNASALAS8/7/14

#2 WP COPPERCU RCRISERN2CUF

08.01-32

DEF

X

DEPDEMDEC

Page 16: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

GUY

ATTA

CHM

ENT

HORIZONTAL CONSTRUCTION TOHORIZONTAL WITH CUTOUT

(FLYING TAP)ELKINSGUINNROBESON8/11/10

NEUTRAL

FRONT VIEW

PLAN VIEW

6"

16"

16"

42"

0

3

2

1

APPR.REVISED BY CK'D

36"

62"

4"

6"

6"

6"

NEUTRAL

NEUTRAL

#6 SD BC

KHLC40N6F

KHLC7933FOR

ELKINSBURLISONBURLISON8/31/11

ADCOCKDANNASALAS8/7/14

#2 WP COPPERCU RCRISERN2CUF

08.01-33

DEF

X

DEPDEMDEC

Page 17: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

HORIZONTAL CONSTRUCTION TO

BRANCH LINEELKINSGUINNROBESON8/11/10

78" GUY

STIC

K

NEUTRAL

TANGENT CONSTRUCTION

PLAN VIEW

FRONT VIEW

GUY ATTACHMENTAND 78" GUY STICK

FRONT VIEW

NEUTRAL

SOURCE

LOAD

DEADEND TO DEADEND

PLAN VIEW

36"

72"

4"

4"

2"

TOP BOLT OF'L' BKT

6"

0

3

2

1

APPR.REVISED BY CK'D

ELKINSBURLISONBURLISON8/31/11

KHLC40N6F

KHLC7933FOR

ADCOCKDANNASALAS8/7/14

72"

#2 WP COPPERCU RCRISERN2CUF

08.01-36

DEF

X

DEPDEMDEC

Page 18: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.01-37DWG.

GUY ATTACHMENT

GUYATTACHMENT

DETAIL 'A'

HORIZONTAL CONSTRUCTION WITH

LIGHTNING ARRESTERELKINSGUINNHOFFMAN11/29/10

IN-LINE CONSTRUCTION DEADEND CONSTRUCTION

FRONT VIEW

R

0

3

2

1

APPR.REVISED BY CK'D

PLAN VIEW

FRONT VIEW

PLAN VIEW

4"

9"

35"

9"

15" 20"

9"

4"

62"

6"

9"

24"

9"

33"

9"

6"

72"

6"

SEEDETAIL 'A'

1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

NOTES:

#6 SD BC#6 SD BC

#6 SD BC

5"

Page 19: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

11/8/12 HOFFMAN DANNA ADCOCK

SINGLE-PHASE CONSTRUCTION - FUSED TAP

0° - 5° ANGLE

12KV

5"

12"

4"

0

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW

#6 SD BC

4. SEE DWG. 08.01-10 FOR BILL OF MATERIALS FOR CUTOUTS.

3. TYPICAL INSTALLATION: SEE SECTION 02 FOR GUYING DETAILS.

2. TYPICAL INSTALLATION: SEE SECTION 04 FOR NEUTRAL/SECONDARY DETAILS.

72"

4"

5. 72" NEUTRAL SPACING IS PREFERRED TO ACCOMMODATE MAINTENANCE AND SHOULD BE OBTAINED ONNEW CONSTRUCTION OR UPGRADE INVOLVING POLE REPLACEMENT. UPGRADES AND ADDITIONS ONEXISTING POLES MAY UTILIZE 60" NEUTRAL SPACING IF 72" SPACING CANNOT BE OBTAINED WITHOUTREPLACING THE POLE OR CAUSING CONFLICT WITH COMMUNICATION CABLES.

(SEE NOTE 5)

C OF BOLT HOLEL

3"

6"

4"

BOLTBRACKETTOP

BOLTBRACKETBOTTOM

3"

IDES25PF

6. SEE DWG. 03.06-02 FOR BOLTS AND LINE CLAMPS.

KHLC40N6F

KHLC7933FOR

3/21/13 McCONNELL DANNA ADCOCK

FOR POST INSULATOR INSTALLATIONS ON WOOD POLES WHEN THE POLE DOES NOT HAVE A SLAB GAIN FOR ALL CONDUCTOR SIZES.WHEN THE CONDUCTOR IS 336.4 KCMIL OR LARGER, USE POLE GAIN EVEN IF SLAB GAIN EXISTS. POLE GAINS ARE NOT REQUIRED FOR INSULATORS USED FOR JUMPERS. SLACK SPANS WITH 336 AND

1. POLE GAINS (ISGAINGRIDF FOR 15/25KV INSULATORS OR ISGAINGRID55F FOR 35KV INSULATORS) ARE REQUIRED

795 CONDUCTORS REQUIRE A POLE GAIN.

8/7/14 SALAS

#2 WP COPPERCU RCRISERN2CUF

DANNA ADCOCK

08.01-38

DEF

X

DEPDEMDEC

Page 20: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

VERTICAL CONSTRUCTION - TANGENT

FUSED TAP CONSTRUCTIONADCOCKHOFFMAN11/8/12 DANNA

12 KV

2. FOR FEEDER TAPS, THE CUTOUTS ARE OMITTED, BUT THE SPACING FOR THE TAP IS THE SAME.

72"

3RD PHASEPOSITION

2ND PHASEPOSITION

78" GUY

INSU

LATO

R

78" GUY

INSU

LATO

R

120"

GUY

INSU

LATO

R

1. MIDDLE CUTOUT CAN BE PLACED ON SAME SIDE OF POLE AS OTHER CUTOUTS.

0

3

2

1

REVISED BY CK'D APPR.

4"

5"

36"

36"

4"

1ST PHASEPOSITION

12"

3"

6"

4"

BOLTBRACKETTOP

BOLTBRACKETBOTTOM

3"

IDES25PF

FUSE15CO100F

3. SEE DWG. 03.06-02 FOR BOLTS AND LINE CLAMPS.

KHLC40N6F

KHLC7933FOR

SALAS8/7/14

#2 WP COPPERCU RCRISERN2CUF

08.01-39

DEF

X

DEPDEMDEC

ADCOCKDANNA

Page 21: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.04-02

TRADITIONAL NON-LOADBREAK SECTIONALIZER

RESETTING TRADITIONAL SECTIONALIZERS

INSERT THE OPENING OF AN ADJUSTABLE WRENCH INTO THE HOLEON THE BACK OF THE TRUNION. ROTATE THE TRUNION WITH THEWRENCH UNTIL TRUNION DOOR IS COMPLETELY SHUT. SLOWLY,REMOVE THE WRENCH FROM THE TRUNION. THE TRUNION WILLSNAP OPEN IF IT IS NOT FULLY CLOSED.

TRUNIONLOWER

CAP

RESETTABLE SECTIONALIZER

ELECTRONICS

ELECTRONIC RESETTABLE SECTIONALIZERSELKINSGUINNHOFFMAN9/20/10

SECT15E100S3FSECT15E100S2F

9220108582300601 SECTIONALIZER, 15KV, NLBK, 1-PH, 100A, 2-SHOT, NO CUTOUT

SECTIONALIZER, 15KV, NLBK, 1-PH, 100A, 3-SHOT, NO CUTOUT9220108583SECT15E200S2F

9220086479SECT27E100S2F

R

COLOR CODED BANDS

TOP

NO BAND = 2 COUNTGREEN BAND = 3 COUNT

BOTTOM

BROWN BAND = 100 AMPNO BAND = 200 AMP

SECTIONALIZER, 15KV, NLBK, 1-PH, 200A, 2-SHOT, NO CUTOUT

SECTIONALIZER, 25KV, NLBK, 1-PH, 100A, 2-SHOT, NO CUTOUTSECTIONALIZER, 15KV, NLBK, 1-PH, 200A, 3-SHOT, NO CUTOUT9220109650SECT15E200S3F

0

2

1

APPR.REVISED BY CK'D

3

54321

BILL OF MATERIALS

CATALOGDESCRIPTION

11111

QTY

11111

PERCU

NUMBER

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

MACROUNIT

NOTES:

2. SECTIONALIZERS HAVE NO FAULT CURRENT INTERRUPTING CAPABILITY. THEY RELY ON THE SOURCE SIDEBREAKER OR RECLOSER TO OPEN DURING THE FAULT. THE SECTIONALIZER OPENS WHILE THE BREAKER/RECLOSER IS OPEN. THEY DO NOT RELY ON FAULT CURRENT FOR COORDINATION; THEREFORE THEY ARE

3. SECTIONALIZER COUNTS WHEN LINE CURRENT DROPS BELOW 300 mA.

1. SECTIONALIZERS WILL FIT IN A STANDARD NLB INTERCHANGEABLE CUTOUT.

USEFUL WHERE COORDINATION PROBLEMS EXIST.

4. CONTACT YOUR SYSTEM ENGINEER PRIOR TO INSTALLATION ON MULTI-PHASE LOCATIONS.

ELKINSBURLISONHOFFMAN6/16/11

5. ITEM 6 - SEE QUICK REFERENCE MANUAL FOR OPERATING INSTRUCTIONS.

9220181861SECT15EABBF SECTIONALIZER, 15KV, NLBK, 1-PH, USER SETABLE, NO CUTOUT6 1 1

USER SETABLE NON-LOADBREAK SECTIONALIZER

SEE QUICK REFERENCE MANUAL FOR USER OPERATING INSTRUCTIONS.

*

Page 22: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.05-00

GENERAL

1. USE THE SUPPLIED GROUNDING CONNECTOR ON THE OIL SECTIONALIZER TANK AND RECLOSER TANK TOGROUND THE UNIT TO THE ARRESTER DOWN LEAD.

AND ADJACENT RECLOSER BUSHINGS IS TO BE 13 INCHES.3. FOR VERTICAL CONSTRUCTION THE MINIMUM TANK CLEARANCE BETWEEN SINGLE-PHASE RECLOSER TANKS

2. A LOAD BREAK TOOL SHOULD BE USED TO OPEN DRY TYPE SECTIONALIZERS AND RECLOSER BYPASSSWITCHES.

4. FOR THREE-PHASE RECLOSERS, THE GROUND TRIP SHORTING SWITCH OPERATES AS FOLLOWS:

A. SWITCH-UP - THE GROUND TRIP IS CUT OUTB. SWITCH DOWN - THE GROUND TRIP IS CUT IN

SOURCE TO LOAD DIRECTION OF FEED THROUGH THE RECLOSER.5. THE THREE-PHASE RECLOSER MAY BE REVERSED IN THE MOUNTING BRACKET TO ACCOMMODATE THE

RECLOSERS, SECTIONALIZERS, TRANSFERS

RECLOSERS, SECTIONALIZERS, TRANSFERS ANDTHREE-PHASE RECLOSER LIGHTNING ARRESTER

MOUNTING DETAILELKINSGUINNHOFFMAN11/29/10

R

0

3

2

1

APPR.REVISED BY CK'D

Page 23: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.05-01

RECLOSER IDENTIFICATIONHOYTGUINNGUINN11/29/10

R

TWO FAST FOLLOWED BY TWO RETARDEDTWO FAST FOLLOWED BY TWO EXTRA RETARDEDTWO FAST FOLLOWED BY TWO STEEP RETARDED

ONE FAST FOLLOWED BY THREE EXTRA RETARDEDONE FAST FOLLOWED BY THREE STEEP RETARDEDONE FAST FOLLOWED BY TWO RETARDED

ONE FAST FOLLOWED BY THREE RETARDED

A AND B

A AND DA AND C

A AND C

A AND BA AND D

A AND B

CURVE(S)SINGLE-PHASE RECLOSERS

A AND CONE FAST FOLLOWED BY TWO EXTRA RETARDED

SEQUENCE2A2B2A2C2A2D1A3B1A3C1A3D1A2B1A2C

OPERATING SEQUENCE

CATALOG NUMBER,

OPERATING CURVES,

MFG. SERIAL

2" UP TO 10 DIGITS

NUMBER, 2"

RATING, 2"TYPE - AMPS

SINGLE-PHASE RECLOSERS

THREE-PHASE HYDRAULIC RECLOSERSALL HYDRAULICS - NOT VACUUM UNITS

INCLUDED RECLOSERS:H, 4H, L, V4L AND E

3"

CERTIFICATION, 2"NON-PCB

6

400-2A2D7 - GROUND TRIP SOLENOID CONNECTION: 1 (SERIES) 2 (PARALLEL)6 - GROUND TRIP FAST OPEN OPERATIONS: 1 2 3 45 - GROUND TRIP TIME DELAY CURVE: 2 3

100 (100:5) 200(200:5) 300(300:5)4 - BUSHING CT RATIO:

B. NUMBER OF OPERATIONS ON DELAYED B, C, D OR E-CURVEA. NUMBER OF OPERATIONS ON A-CURVE

3 - PHASE TRIP OPERATING SEQUENCE:

1 - PHASE TRIP COIL SIZE: 100, 160, 185, 225, 280, 400, 400X, 560, 560X

9 - MANUFACTURER'S SERIAL NUMBER10 - MAINTENANCE DATE

8 - CATALOG NUMBER (UP TO 10 DIGITS)

8

VW AND WVINCLUDED RECLOSERS:

XX-XX9

10

1 - CATALOG NUMBER (UP TO 10 DIGITS)2 - MANUFACTURER'S SERIAL NUMBER3 - MANUFACTURER'S TYPE RECLOSER: VWE, VR3S AND OVR

THREE-PHASE ELECTRONIC CONTROLLED RECLOSERS

5 - MAINTENANCE DATE4 - FULL-LOAD CURRENT RATING (560, 630, 800)

SNSNSNSNVR3S-560

CNCNCNCN

4 - CATALOG NUMBER, 2"3 - MAINTENANCE DATE2 - COUNTS TO OPEN OR SHOTS TO LOCKOUT1 - AMPERE RATING

HYDRAULIC SECTIONALIZERS

CNCN

HANGER ON BACK SIDEOF SECTIONALIZER

21

3 4

MAINTENANCE DATE, 1"

754

1 3A

400 (400:5) 500(500:5) 600(600:5)

2 - PHASE TRIP TIME DELAY CURVE: B, C, D OR E-CURVE

3"

3B

CNCNCNCNCN

2

3 4

1

11 - NON-PCB CERTIFICATION (ON END WITH OPERATING HANDLE)

11

5

NOTES:

1. SEE DWG. 08.04-02 FOR ELECTRONIC SECTIONALIZERS.

NOTES:

1. STENCIL THE CATALOG NUMBER ON THE OUTSIDE, PADLOCKSIDE OF THE RECLOSER ELECTRONIC CONTROL CABINET.

3"

0

2

1

APPR.REVISED BY CK'D

3

A AND DONE FAST FOLLOWED BY TWO STEEP RETARDED1A2D

Page 24: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

TYPICAL SINGLE-PHASE RECLOSER

DIMENSIONS, WEIGHTS AND OIL CAPACITIESELKINSGUINNHOFFMAN11/29/100

2

1

APPR.REVISED BY CK'D

3

DIMENSIONS DIMENSIONS

A

B

C

RECLOSER TYPE

4H

36

17

7

L

37

19

6

V4L

45

19

15

E

42

20

9

4E

49

23

15

H

30

16

14

WEIGHT WITH OIL

OIL CAPACITY

114

5

159

7

205

9.5

169

8.2

205

9.5

85

4

(LBS.)

(GAL.)

A

B

C

NOTES:

1. THE DIMENSIONS, WEIGHTS AND CAPACITIES LISTED ABOVE ARE APPROXIMATE.

DIMENSION(IN.)

TYPE 4H, L, V4L, E AND 4E RECLOSERS TYPE H RECLOSER

B

12"

C

A

ADCOCKBURLISONLOOSIER11/17/15

08.05-02

DEF

X

DEPDEMDEC

Page 25: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

COOPER RECLOSERS

OPERATING LEVERSADCOCKGUINNGUINN7/31/140

3

2

1

APPR.REVISED BY CK'D

RETURN TO"UP" POSITION

AFTER USE

CLOSED

OPEN

VIEW OF LEVERCONTROL MECHANISM

NON-AUTOMATIC RECLOSING LEVER

SET LEVER IN THISPOSITION FOR

NONRECLOSING

NOTES:

1. NON-AUTOMATIC RECLOSING LEVER FOR COOPER RECLOSERS PROVIDES ONE-SHOT LOCKOUT OF THE RECLOSER WHEN TRIPPED ELECTRICALLY. IT IS CONTROLLED BY AN ADDITIONAL LEVER UNDER THE OPERATING HANDLEHOOD WHICH, WHEN PULLED DOWN, ENGAGES THE LOCKOUT AND PLUNGER MECHANISMS, BYPASSING THEHYDRAULIC LOCKOUT IN SUCH A MANNER THAT WHEN THE SOLENOID PLUNGER IS PULLED DOWN, THELOCKOUT MECHANISM IS TRIPPED. IN ORDER FOR THE RECLOSER TO RESUME NORMAL, FULL-AUTOMATICOPERATION, THE LEVER IS MOVED BACK TO THE "UP" POSITION. THE LEVER OPERATES ON A TOGGLE SO THATIT IS POSITIVELY IN THE NON-AUTOMATIC OR AUTOMATIC POSITION.

2. AFTER USE, THE NON-AUTOMATIC RECLOSING LEVER MUST BE RETURNED TO NORMAL "UP" POSITION TOPROVIDE AUTOMATIC RECLOSING

TO CLOSE, PLACE HOTSTICK TIPAGAINST MANUAL OPERATINGHANDLE AND PUSH UPWARD TO OPEN, INSERT HOTSTICK

TIP INTO EYELET OF MANUALOPERATING HANDLE AND PULLDOWNWARD.

08.05-06

DEFDEP

X

DEMDEC

RECLOSING

NON

XXX

Page 26: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

FUSESSTORED WITHBARRELS DOWN

SOURCELOAD

BE COVERED TO

ALL ENERGIZEDPARTS SHOULD

GUARD AGAINSTDAMAGE CAUSEDBY ANIMALS

1

RECLOSER ASSEMBLY,

VERTICAL CONSTRUCTION

FRONT VIEW SIDE VIEW

PLAN VIEW

0

APPR.REVISED BY CK'D

#6 SD BC

#2 SD BC

#2 SD BC

#2 SD BC

5"

54"

54"

72"

6"

26"

28"

6"

26"

28"

6"

26"

46"

4321

BILL OF MATERIALS

ITEM

WIRE, COPPER, #2, SOLID, 600V, SD COPPERCLAMP, HOT LINE, ALUMINUM, SMALLCUTOUT, BLADE, SLDCUTOUT, LB, 15KV, 100A, 16KA, 110KV BIL

DESCRIPTION

FUSE15CO100F 2211129220210916SW153COSBDF

KHLC40N6F 92201847909220218857

QTY

112 FT.

11

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTY. REQ'D.

1Ø 2Ø 3Ø

2442

1221

3663

1

2

10/6/10 HOFFMAN ELKINSGUINN

3

2

SEE DWG. 08.05-15B

4

3

ON 3" STAPLE

NOTES:

1. ISSUE RECLOSER SEPARATELY. RECLOSER WILL COME WITH ARRESTERS PRE-MOUNTED.2. FOR ALL V4L RECLOSER INSTALLATIONS ON VERTICAL CONSTRUCTION, INCREASE THE PHASE SPACING BETWEEN THE PRIMARY

CONDUCTORS FROM 54" TO 64" AND INCREASE THE 28" DIMENSIONS TO 38".*

3. SEE DWG 08.05-15B FOR BRACKET DETAILS AND BILL OF MATERIALS.4. FOR SINGLE-PHASE AND TWO-PHASE INSTALLATIONS, USE SPACING REQUIREMENTS FROM BOTTOM UNIT CLOSEST TO NEUTRAL

TOWARDS THE TOP OF THE POLE.5. EQUIPMENT CASE GROUND TO NEUTRAL TO BE #2 SD BC.

CUTOUTS WITH SOLID BLADES.6. IF RECLOSERS ARE USED IN MAINLINE FEEDER (336 OR 795), USE 600 AMP RECLOSER BYPASS (SEE DWG. 08.10-10) INSTEAD OF

7. DISCONNECT CONNECTIONS MAY BE MADE WITH SOLID CONNECTION IN LIEU OF HOT LINE CLAMP AND STIRRUP.

RCRISERN2CUF

3/29/11 HOFFMAN ELKINSBURLISON

08.05-15A

DEF

X

DEPDEMDEC4/21/15 LOOSIER ADCOCKBURLISON

11/17/15 LOOSIER ADCOCKBURLISON

Page 27: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.05-15B

OIL CIRCUIT RECLOSER -SINGLE-PHASE INSTALLATION

BYPASS CUTOUT BRACKETELKINSGUINNHOFFMAN10/11/10

R

0

APPR.REVISED BY CK'D

1

2

3

18"

12"

12"

TOP VIEW

SIDE VIEW

NOTES:

1. SEE DWG 08.05-15A FOR RECLOSER INSTALLATION DETAILS.

1

1 BKTEQ1824FGF

BILL OF MATERIALS

CATALOG

9220201401

DESCRIPTION

1

QTY

1

PERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

1326413308152107

222

BRACKET, FG, CUTOUT MTG BKT, 3 HOLEWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, 2-1/4", SQUARE, FLAT, 13/16", HOLE, GALV.BOLT, MACH, SQ. NUT, 5/8" X 12"

8"

-

2. USE ONE CU PER RECLOSER INSTALLED.

Page 28: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY,

VERTICAL CONSTRUCTION, FEEDER0

APPR.REVISED BY CK'D

9/28/11 BURLISON ELKINSBURLISON

3

60"

60"

72"

16"

5"

4"

11"

NOTES:

1. SEE DWG. 08.05-16B FOR BILL OF MATERIALS.

08.05-16A

DEF

X

DEPDEMDEC

4

13

2

2. FOR ALL V4L RECLOSER INSTALLATIONS ON VERTICAL CONSTRUCTION, INCREASE THE

PHASE SPACING BETWEEN THE PRIMARY CONDUCTORS FROM 60" TO 64".

(SEE NOTE 2)

4/21/15 LOOSIER ADCOCKBURLISON

SEE NOTE 3

3. RISER SIZE SHOULD MATCH PRIMARY CONDUCTOR SIZE.

4 8/27/15 LOOSIER ADCOCKBURLISON

5 11/17/15 LOOSIER ADCOCKBURLISON

Page 29: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY,

VERTICAL CONSTRUCTION, FEEDER0

APPR.REVISED BY CK'D

1

2

3

5/28/14 LOOSIER ADCOCKDANNA

NOTES:

2. SEE DWG. 08.05-16A FOR DESIGN SPECIFICATIONS.

08.05-16B

DEF

X

DEPDEMDEC

1

BILL OF MATERIALS

CATALOGDESCRIPTION

3

QTYPERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTY REQ'D

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, 304, ALLOY, COARSE THRD.WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, 304, ALLOY, COARSE THRD.WASHER, FLAT, 1/2 IN, SILICON BRONZE, FLAT, ROUNDLUG, COMPRESSIN, 2H-795ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODBOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

CABLE, XLP UG AL 500

2

4

3

6

6

6

0109280012277013128

010928012277013163155326

10542504

202112

SW156BYPF

KLC2H50ALF

KLC2H50AL90DF

RCRISER500ALF

888

224122

12

WASHER, ROUND, FLAT, STAINLESS, STEEL, 304, ALLOY, FOR, 1/2"BOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISC, 15KV, LBK, HOOKS, 600A, LEFT

013407152107260123

1621

SPRING, DOUBLE COIL, STEEL, FOR, 5/8", BOLT, GALV.013264 2WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.013308 2

NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, 304, ALLOY, COARSE THRD.012277 2WASHER, FLAT, 1/2 IN, SILICON BRONZE, FLAT, ROUND013163 4WASHER, ROUND, 1/2, SS, 1.375" OD10542504 2LUG, 2-HOLE, TIN-PLATED, NEMA9220068102 1

010928

1. ISSUE RECLOSER SEPARATELY. RECLOSER WILL COME WITH ARRESTERS PREMOUNTED.

2Ø1Ø 3Ø

2

4

4

4

1

2

2

2

Page 30: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

BE COVERED TO

ALL ENERGIZEDPARTS SHOULD

GUARD AGAINSTDAMAGE CAUSEDBY ANIMALS

RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION

SLACK SPAN TAP0

APPR.REVISED BY CK'D

1

2

12/6/13 SALAS ADCOCKDANNA

3

SIDE VIEW FRONT VIEW

5"

6"

26"

54"

28"

6"

26"

54"

28"

6"

26"

72"

FUSESSTORED WITHBARRELS DOWN #6 SD BC

ON 3" STAPLE

46"

#2 SD BC

#2 SD BC

NOTES:

1. SEE DWG. 08.05-18B FOR PLAN VIEW, BILL OF MATERIALS AND NOTES.

1

2

3

4

SEE DWG. 08.05-15B

08.05-18A

DEF

X

DEPDEMDEC

4/21/15 LOOSIER ADCOCKBURLISON

11/17/15 LOOSIER ADCOCKBURLISON

Page 31: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY, VERTICAL CONSTRUCTION

SLACK SPAN TAP0

APPR.REVISED BY CK'D

1

2

12/6/13 SALAS ADCOCKDANNA

3

PLAN VIEW

NOTES:

5. SEE DWG. 08.05-18A FOR DESIGN SPECIFICATIONS.

SOURCE

LOAD

5

8

6

7

87654321 FUSE15CO100F

BILL OF MATERIALS

ITEM

0000221112

CLAMP, DEADEND, DE,SO,6-4/0 ACSR,6-4/0 CU, 4-4/0 ALLINK, CHAIN,TWISTED,90,25M,3-3/8",LONG

INSULATOR, POLYMER, 25KV, DE, SI, RATED 15KVCLAMP, ANGLE, SUSPENSION,ANGLE,ALUMINUM,0.25-0.75"WIRE, COPPER, #2 SOLID, COPPER, 600V, SD COPPERCLAMP, HOT LINE, ALUMINUM, SMALL

CUTOUT, LB, 15KV, 100A, 16KA,100KV BILLCUTOUT, BLADE, BLADE,SLD,NONLOADBREAK,300A,15 KV

DESCRIPTION

SW153COSBDF 9220210916KHLC40N6F 9220184790

RCRISERN2CUF 9220218857SCLMP10AAACF 0000090306

IDES25PF 080577DECLMP10AAACF 0000100708

MIDSPANTAPF 000011542811

11

1321

QTY

11

11

12FT.111

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTY REQ'D

1. ISSUE RECLOSER SEPARATELY. RECLOSER WILL COME WITH ARRESTERS PRE-MOUNTED.

2. FOR ALL V4L RECLOSER INSTALLATIONS ON VERTICAL CONSTRUCTION, INCREASE THE PHASE SPACING

6. FOR SINGLE-PHASE AND TWO-PHASE INSTALLATIONS, USE SPACING REQUIREMENTS FROM BOTTOM UNIT

7. EQUIPMENT CASE GROUND TO NEUTRAL TO BE #2 SD BC.

8. IF RECLOSERS ARE USED IN MAIN LINE FEEDER (336 OR 795), USE 600 AMP RECLOSER BYPASS (SEE

9.DISCONNECT CONNECTIONS MAY BE MADE WITH SOLID CONNECTION IN LIEU OF HOT LINE CLAMP AND STIRRUP.

BETWEEN THE PRIMARY CONDUCTORS FROM 54" TO 64" AND INCREASE THE 28" DIMENSIONS TO 38".

3. SEE DWG 08.05-15B FOR BRACKET DETAILS AND BILL OF MATERIALS.

4. SEE DWG 03.18-03 FOR ALTERNATE SLACK SPAN CONSTRUCTION DETAILS.

CLOSEST TO NEUTRAL TOWARDS THE TOP OF THE POLE.

DWG. 08.10-10) INSTEAD OF CUTOUTS WITH SOLID BLADES.

1Ø 3Ø

22

22

2642

33

33

3963

11/17/15 LOOSIER ADCOCKBURLISON

08.05-18B

DEF

X

DEPDEMDEC

Page 32: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

OIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION,

HORIZONTAL CONSTRUCTIONSINGLE-PHASE UNITS0

APPR.REVISED BY CK'D

2

3

RECLOSER BRACKET DIRECTLY BEHIND THE RECLOSER BUSHING AS SHOWN.3. ARRESTERS ARE TO BE CONNECTED TO BOTH SOURCE AND LOAD SIDE BUSHINGS AND INSTALLED ON THE

BARRELS BY THE PULL RING SO WATER AND DEBRIS CANNOT COLLECT INSIDE BARREL.2. HANG FUSE BARRELS FROM BY-PASS CUTOUTS ON A DRIVE HOOK OR LAG SCREW NEAR THE NEUTRAL. HANG

1. ALL SWITCHING SHALL BE DONE WITH TELESCOPIC STICK AS PER WORK STANDARDS. SOURCE AND LOAD

NOTES:

5. BOND RECLOSERS TO THE RECLOSER MOUNTING BRACKET WITH #2 CU AND CONNECT TO SYSTEM NEUTRAL.

4. SOURCE BUSHING IS LOCATED OVER THE MANUAL (YELLOW) HANDLE. ROTATE HEAD TO HAVE THE HANDLEVISIBLE FROM NORMAL APPROACH (TYPICALLY ROAD SIDE).

6. SINGLE-PHASE RECLOSERS HAVE DIFFERENT OPERATING CURVES: 2A2B, 2A2C, ETC. WHEN INSTALLING OR

7. SEE DWG. 08.05-114B FOR TABLES FOR RECLOSER TAP CONDUCTOR AND SWITCH SIZING AND BILL OF

REPLACING A RECLOSER, BE SURE THE UNIT HAS THE CORRECT OPERATING CURVES AS WELL AS THE CORRECT

08.05-114A

DEFDEPDEMDEC

1 XX

#2 CU TANKGROUND

SIDE VIEW

#6 CU POLE

#2 CU FRAME GROUND

10-1/4"

2

16

14

LOAD SOURCE

FRONT VIEW

SOURCE

LOAD

5

SOURCE

LOAD

SOURCE

LOAD

SEENOTE 9

12"

3" 30" 30" 3"

9"

5"

12"

SLEET HOOD

6" 9"

8. SEE SYSTEM PROTECTION FOR BY-PASS SWITCH DETAILS.

SOURCE

LOAD

CUTOUTS ARE TO HAVE SOLID BLADES.

AMPERE RATING TYPE.

MATERIALS.

GROUND BYPASS FUSEBARRELS

12

13

15" 12" 12" 15"

1

113

2

4

15

BYPASSCUTOUTS

8

6

7 10

7 10

3 9

10' ARM

5"

12"

12"

12"

6"9"

4" MIN.

9. SEE DWG. 08.05-02 FOR RECLOSER HEIGHT MEASUREMENT.

20"

17

ADCOCKBURLISONBRUINS11/17/15

XXLOOSIER12/16/15 ADCOCKBURLISON

Page 33: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

11/17/15 BURLISON EANES ADCOCK

REVISED CK'DBY APPR.

1

0

3

2

NOTES:

08.05-114B

DEFDEPDEMDEC

XOIL CIRCUIT RECLOSERS, THREE-PHASE INSTALLATION,

HORIZONTAL CONSTRUCTIONSINGLE-PHASE UNITS

3

5

3

2

ARMSDE120HFF

CUTOUT, BLADE, BLADE,SLD,NONLOADBREAK,300A,15 KV

BOLT, MACHINE, 5/8 IN, 2 IN, ASTM A307, A, GALVANIZED, SQWASHER, LOCK, 3/4 IN DBL COILWASHER SQUARE, RB, CRV, 3"X3"BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNC

RECLOSER TYPE L (VARIABLE AMP AND CURVE)

BILL OF MATERIALS

ITEM

9220272389

CUTOUT, NON LOADBREAK, 15KV,100ACABLE, XLP UG AL 4/0

WASHER, LOCK, 3/4 IN DBL COILWASHER SQUARE, RB, CRV, 3"X3"

CROSSARM, DEADEND, HD, FIBERGLASSBOLT, HEX, 3/4 IN, 10"X12 STEEL, A307

DESCRIPTION

1521221334613265

RCRISER10ALF202111

FUSE15CO100F 202112SW153COSBDF 9220210916

BKTTFMRSMALF

-

1521221334613265152104

6

1

3

6

1

1

6222

3

ITEM

112

2221

QTY/CU

NUMBERBUBBLENUMBER

COMPATIBLEUNIT

CUQTY

7

6

INSULATOR, POST, LINE, 35KV ROUND BASE TIE TOPGUARD, ANIMAL, 5 1/2 INCH HTGUARD, ANIMAL, 9 INCH HTWGEQBUSHSNAPF 470114

IHPTT35F9220284709

802173

6

111

WASHER, LOCK, 5/8 IN, STEEL, GLV, LK,5/8,COIL,DBL,GLV13264 1STUD, LINE POST, LP 5/8 INCH X 12 INCH72367 1

11

10

BOLT, CARRIAGE, 1/2 IN, 6 IN, STEEL, GLV BRACKET, MOUNTING, 8 7/8 IN X 2 1/2 IN IN, GALVANIZED STEELTIE, COMPOSITE FOR #2/0 TO #4/0- 9220284740

BKTCOLASTLXARMF7010111213

6

1

211

10 TIE, COMPOSITE FOR #2 TO #2/0 - 92202847391 1

8BOLT, MACHINE, 5/8 IN, 11 INX 12 IN, STEELCROSSARM, TANGENT, 10 FT, FIBERGLASS, BRACELESS, TANGENT

ARMS120FF

9220201451152107

121

WASHER, LOCK, 5/8 IN, STEEL, GLV, LK,5/8,COIL,DBL,GLV13264 2WASHER SQUARE, RB, CRV, 3"X3"13346 2

1

1. SEE DWG. 08.05-114A FOR DESIGN SPECIFICATIONS AND NOTES.

2CONDUCTOR, AAAC, 1/0, AAAC, 7-STR, 6201-T81 ALUMINUM ALLOY

RCRISERN2CUF 922021885754008800

61212 CONDUCTOR, COPPER, WP #2 AWG

4 RCL(VARIES) 3

ISSTUDBOLT5812F 3

9BOLT, CARRIAGE, 1/2 IN, 6 IN, STEEL, GLVBRACKET, MOUNTING, 8 7/8 IN X 2 1/2 IN IN, GALVANIZED STEEL

BKTCOLASTLXARMF7010111213

321

SCREW, LAG, 1/4 IN X 2 IN, STEEL, GLV, LAG,HX,1/4-INCH O.D.14114 112 - 1

STAPLE, DIAMOND POINT, GALV STL 2X5/8X3/16CONDUCTOR, COPPER, #2 SOLID, SOFT DRAWN, BARE

GOWE2F

922016222115280

14040

13

ROD, GROUND, 5/8 X 60 IN, COPPER CLAD, THREADLESS 5/8" X 5'CLAMP, GROUND, GRD,BRN,5/8 CAST BRONZE GROUND ROD CLAMP

GRODFRF160123

92201923191

11

ROD, GROUND, 5/8 X 60 IN, COPPER CLAD, THREADLESS 5/8" X 5'COUPLING, ROD, 5/8 IN, COPPER PLATED STEEL, ROD,GRD,5/8

GAR1F 60136

92201923193

11

ARRESTER, METAL OXIDE, 10KV,METOX DIST CLASS, METAL OXIDE220202 1

15DEADEND CLAMP (VARIES WITH WIRE SIZE)INSULATOR, DEADEND, POLYMER,28KV,DEADEND,SILICONEIDES25PF 80577

-6

11

DECLMP(VARIES) 6BLADES COME WITH SW253COSBDC- 116 - 6

2 RCRISER40ALF 6

BRACKET, MOUNTING, MTG,RACK,TF,SM THREE POS, 5-50KVA12912507 1

CONNECTOR, GROUND, TF,GND,EYEBOLTCONNECTOR, COMPRESSION, COMP, AL153111

160182 21

CONNECTOR, VISE TYPE 2 CU162205 2

14 AREQOH10F 6

- 6

12/16/15 LOOSIER BURLISON ADCOCK

Page 34: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

1. SWITCHES TO BE ON ROAD SIDE.

4. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.5. TOTAL WEIGHT OF THE RECLOSER AND FRAME IS 850 LBS.6. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.

RECLOSER AND FRAME, THREE-PHASE, ABB

WITH VERTICAL BYPASS SWITCHELKINSGUINNHOFFMAN10/12/10

8. SEE DWG. 08.06-08B FOR BILL OF MATERIALS.

6

12

1

11

8

5

4

L1

L2

BLACK

GREEN - GROUND

SECONDARYARRESTER

TERMINAL L1

BLACK

SECONDARY ARRESTER CONNECTION

3

0

2

APPR.REVISED BY CK'D

2. PT TO BE LOCATED ON SOURCE SIDE. RELOCATE ON RECLOSER FRAME IF NECESSARY.3. SIX ARRESTERS REQUIRED: 3 ON EACH SIDE. CONNECT TO TERMINALS OF RECLOSER WITH CONNECTOR UNDER WILDLIFE PROTECTORS.

7. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS. DO NOT EXCEED!

3

2

7

1/2" SS

ROUNDWASHER

DETAIL "B"

BOLT

4 HOLESPADE ONRECLOSER

#6 BC

ROUNDBOLT

#6 BC

NUT

LOCKWASHER

9

10

PT

#2 SD BC

LOAD SOURCE6"

48"48"

48"

76"

35"

#6 SD BC

48" MIN. GUARD FORBOLT ON TAMPER

CONTROL CABLE

FRONT VIEW SIDE VIEW

38"

#6 SD BC 37"

4"

4"

PLUG

ADCOCKDANNAHOFFMAN11/8/12

ADCOCKGUINNGUINN5/28/14

08.06-08A

DEF

X

DEPDEMDEC4 BURLISON12/19/14 ADCOCKGUINN

Page 35: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY, THREE-PHASE, ABB

WITH VERTICAL BYPASS SWITCHELKINSGUINNHOFFMAN11/9/10

NOTES:

5. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS: DO NOT EXCEED!

1. GROUND RESISTANCE TO BE 15 OHMS OR LESS.2. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.

4. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.3. TOTAL WEIGHT OF RECLOSER ASSEMBLY IS 850 LBS.

92200852319220087168

EXTERNAL PT FOR ABB OVR RECL, 13.8V, 110BIL, VOG-11, 60:1COASTAL EXT. PT- ABB OVR RECL, 13.8 KV, 125 KV BIL, W/60:1 RATIO

9220102215 CABLE LOCKING SLEEVE - ABB RECL. CTRL CABLE CONNECTOR9220087542 BATTERY, RECLOSER, PCD CNTRL, 48VDC (SET OF 4-12VDC)9220100256 CABLE-PT, ABB RECLOSER, 8 FOOT, W/2-5-PRONG CONNECTORS9220085226 ABB PCD SINGLE-PHASE TRIP CARD9220102547 COM5 MODULE/CARD FOR ABB PCD CONTROL (SLOT-E)9220127574 ABB PCD UPS CARD TYPE 3, 48VDC (SLOT-A)9220127570 ABB PCD UPS CARD TYPE 2, 48VDC (SLOT-A)9220127579 ABB PCD DIO-2B I/O CARD (SLOT-B)9220127587 ABB PCD DIO-1 I/O CARD (SLOT-C)9220127588 ABB PCE CPU-2 CARD (SLOT-D)9220127589 ABB PCD COM-2A CARD (SLOT-E)9220127564 ABB PCD PT/CT 600:1 CARD (SLOT-F)

6. SEE DWG. 08.06-08A DESIGN SPECIFICATIONS.

0

3

2

APPR.REVISED BY CK'D

3

8765

4

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

1

6444

3

1

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

RECLOSER TYPE OVR 630 AMP ELEC. 15KV VRT MNTG W/1PTBOLT, MACHINE, SQ, NUT, 5/8" X 12"WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304 ALLOYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWIRE, TIE, #4 SD BC, SLDRECLOSER CONTROL PCD 2000 FOR ABB RECLRECLOSER CONTROL CABLE FOR ABB VR3 AND OVR, 40FTWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.BOLT, MACHINE, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISCONNECT, 15KV, LBKBRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREADINSULATOR, 25 KV POLYMER, 1-3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATORARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODLUG, 2-HOLE, TIN-PLATED, NEMA, 90 DEGREECABLE, XLP UG AL 500GUARD, PVC, CABLE, 2-1/4" X 10'BANDING, STAINLESS STEEL, 316, 3/4" WIDE, .030 THBANDING, BUCKLE, SS, 3/4", FOR BANDINGARRESTER, LIGHTNING, SEC 120-240 3 WIRE

9

13

12

1110

6

1

2

66

9220090147152107013308013264013128013407010928012277

922006924492200875509220100429

013264013308152107260123

922008786892200910189220068094

220202010928012277013163155326

105425049220068102

202112323422434122434142220139

RCOVR630E15V1F

RCCNTLPCDABBFRCOVRCAB40F

SW156BYPF

BKTFBGPIN15138FIPIN25PF

TTIEF500COVALPFAREQOH10F

KLC2H50ALF

KLC2H50AL90DFRCRISER500ALF

CRIS1UGPVC225CF

AREQSC120F

ADDITIONAL PARTS FOR REPLACEMENT

24

333231302928272625

23222120191817

CATALOGDESCRIPTION

--------------

-

---------

-

--

-

11111

1

111111111

QTY

1

11

1

11111

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

RECLOSER, ABB OVR-630 AMP, 12KA, 27KV-HV EDGEMOUNT COASTALRECLOSER, PCD,CONTROL,LV,MODULE,WITHOUT,SINGLE-PHASE,TRIRECLOSER, CONTROL, PCD 2000 COOPER RETROFITTRANSFORMER, POTENTIAL, 15KV,7200VMODULE, LOOP CONTROL, RECLOSER, ABB, FOR PCD CONTROL.

92200871779220085219922008763392200852319220087552

RCOVR630E27V1FRCCNTLPCDABBNSF

RCCNTLPCDRFF-

RCPCDLCMF

161715757236364112221

111224121121

0.231

1

161514

333

111 GUARD, ANIMAL, TERMINAL GUARD, STRAIGHT

GUARD, ANIMAL, L-SHAPED, GUARDGUARD, ANIMAL, PT OR VOLTAGE TRANSFORMER

922010221292201022139220102214

3534

WGRCTERMGSFWGRCLSHPFWGRCPTTRF

HOFFMAN3/28/12 ELKINSBURLISON

HOFFMAN11/14/12 ADCOCKDANNA

4 BURLISON12/19/14 ADCOCKGUINN

08.06-08B

DEF

X

DEPDEMDEC

Page 36: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

1. SEE DWG. 08.06-08B FOR BILL OF MATERIALS AND REPLACEMENT PARTS FOR RECLOSER INSTALLATION.

DETAIL "A" DETAIL "B"

SEE DETAIL "A"

#2 SD BC

USE WILDLIFE GUARDS

ELKINSGUINNHOFFMAN10/12/10

EXTRA CAUTION SHOULD BE TAKEN WHEN BOLTING CONNECTIONS OR TRAINING LEADS TO BUSHINGS. SEE NOTE 4ON DWG. 08.06-08B.

ABB RECLOSER ON VERTICAL DOUBLE CIRCUIT W/

VERTICAL BYPASS SWITCH0

3

2

1

APPR.REVISED BY CK'D

CN 153109

NOTES:

2. A 55' CLASS 3 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.3. SEE DWG. 08.06-08A FOR MORE DETAILS ON RECLOSER INSTALLATION, INCLUDING SECONDARY AND PRIMARY

ADCOCKDANNAHOFFMAN11/8/12

LOAD SOURCE

5"

36"

36"

36"

6"

48"48"

48"

76"

35"

#6 SD BC

48" MIN. GUARD FOR CONTROLBOLT ON TAMPER

CABLE PLUG

FRONT VIEW SIDE VIEW

38"

CN 9220102213

CN 9220102212

CN 9220102214

#6 SD BC

SEE DETAIL "B"

37"

4"4"

08.06-10

DEF

X

DEPDEMDECADCOCKGUINNBURLISON12/19/14

ARRESTER CONNECTIONS.

Page 37: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

RECLOSER AND FRAME, THREE-PHASE, VIPER ST,

WITH VERTICAL BYPASS SWITCHADCOCKBURLISONHOFFMAN10/12/12

1. SEE DWG. 08.06-11C FOR BILL OF MATERIALS AND NOTES.

10

2

BØAØ

L1

L2

BLACK

GREEN - GROUND

SECONDARYARRESTER

TERMINAL L1

BLACK

SECONDARY ARRESTER CONNECTION

0

APPR.REVISED BY CK'D

1/2" SS

ROUNDWASHER

DETAIL "C"

BOLT

4 HOLESPADE ONRECLOSER

#6 WP

ROUNDBOLT

#6 WP

NUT

LOCKWASHER

USE WILDLIFE GUARDS

DETAIL "A"

1

16

SEE DETAIL "B"

DETAIL "B"VIPER ST JUNCTION

BOX PANEL; SEE NOTE 4ON 08.06-11C

5"

6"

24"

24"

FRONT VIEW

38"

BOLT ON TAMPERGUARD FORCONTROL CABLEPLUG

SIDE VIEW

13

11

SEE DETAIL "A"

12

SOURCE

LOAD

(4) 9220102213(2) 9220252997

17

IN CONTROL BOX

3

14

#6 SD BC

4

9

6

SEE

108"

48"

48" MIN.

DETAIL "C"

5

15

SOURCE LOAD

NEUTRAL

8

48"

#2 CU

756"

2. BRACKET IS REVERSIBLE AND CAN BE INSTALLED ON EITHER SIDE OF POLE TO SUIT FIELD CONDITIONS.

56"

3. IN COASTAL AREAS, USE DWG. 08.06-12A FOR 25KV CONSTRUCTION.

4 McCONNELL2/17/14 ADCOCKDANNA

5 LOOSIER7/1/15 ADCOCKBURLISON

08.06-11A

DEF

X

DEPDEMDEC6 LOOSIER8/10/15 ADCOCKBURLISON

Page 38: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

RECLOSER AND FRAME, THREE-PHASE, VIPER ST,

WITH VERTICAL BYPASS SWITCH

1. SEE DWG. 08.06-11A FOR DESIGN SPECIFICATIONS.

0

2

1

APPR.REVISED BY CK'D

3

ADCOCKDANNAMcCONNELL6/7/13

2. SEE DWG. 08.06-11C FOR BILL OF MATERIALS AND NOTES.

16.5"

29.74"

47.7"

LOWER SUPPORTSSHIPPED UNATTACHED

52.06"

27.66"

59.62"

55.76"

44.75"6

19

6

BACK VIEW

3.02"

1.27"

20"

INTERNAL CURRENTTRANSFORMER

SHIPPED WITH UNITALUMINUM POLEMOUNTING FRAME

MODULE CABLEACCESS IN THEJ-BOX

JUNCTION BOXRECLOSER CONTROLCABLE AND HARDWARE

LEFT VIEW

RIGHT VIEW

ATTACH GROUNDSTIRRUP TO FRAME

LOAD SIDE

1

SOURCE SIDE

(ANIMAL GUARD NOT SHOWN FOR CLARITY)

(ANIMAL GUARD NOT SHOWN FOR CLARITY)

16

17

PT JUNCTIONBOX

BØ CØAØ

#6 CU WP SEE DETAIL C

ON DWG. 08.06-11A

2.13"

#6 CU WP

McCONNELL2/17/14

3. BRACKET IS REVERSIBLE. DEPENDING ON HOW UNIT IS INSTALLED IN FIELD, DIAGRAMS

ADCOCKDANNA

SPACING AVAILABLEFOR 3 ADDITIONALPTS IF NECESSARY

08.06-11B

DEF

X

DEPDEMDECLOOSIER7/21/14

ABOVE MAY BE REVERSED.

ADCOCKDANNA

LOOSIER7/1/15 ADCOCKBURLISON

Page 39: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY, THREE-PHASE, VIPER ST

WITH VERTICAL BYPASS SWITCH

NOTES:

7. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS: DO NOT EXCEED!

5. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION. IF JOINT USE ON POLE, CLEARANCES MAY REQUIRE 50' POLE.6. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.

0

3

2

APPR.REVISED BY CK'D

654

3

2

1

BILL OF MATERIALS

ITEMDESCRIPTION

-44

4

3

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

RECLOSER TYPE VST 800 AMP ELEC. 27KV VRT MNTGBOLT, MACHINE, SQ, NUT, 5/8" X 12"WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304 ALLOYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWIRE, TIE, #4 SD BC, SLDBOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEXWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING, DOUBLE COIL, F

INSULATOR, 25 KV POLYMER, 1-3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATORARRESTER (INCLUDED FROM MANUFACTURER)BOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODBOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

CABLE, XLP UG AL 500SCREW, LAG, HX, 1/4" X 2", STEEL, GALV.GUARD, PVC, CABLE, 2-1/4" X 10"

7

11

10

8

5

2

6

7

9220244274152107013308013264013128013407010928012277

92200692440109280012277013128

013264

92200910189220068094

220202010928012277013163155326

10542504

202112014111323422

RCVST800E27V1F

SW156BYPF

BKTFBGPIN15138F

IPIN25PFTTIEF500COVALPF

AREQOH10F

KLC2H50ALF

KLC2H50AL90DF

RCRISER500ALF

CRIS1UGPVC225WF

19 - 3 TRANF, POTENTIAL (INCLUDED FROM MANUFACTURER)9220085231-

161715757236364888

111224122

12151

2

11. TOTAL WEIGHT OF THE RECLOSER AND FRAME IS 750 LBS DOES NOT INCLUDE PT'S OR LA'S.12. NEUTRAL MAY BE DOUBLE DEADENDED OR STRAIGHT THROUGH ON SPOOL AS NEEDED.

8. PT'S TO BE LOCATED ON SOURCE SIDE. POWER SOURCE FOR PT'S FROM UNIT 1.

VIPER ST CONTROL CABLE12 1 9220244739RCVIPCAB40F 1SEL 651 CONTROL13 1 9220244823RCCNTL651GWF 1CONTROL CABLE, 40' ARMORED 8 PIN FOR PT

14 - 9220267667- 1

1" CONDUIT, FLEX, AND FITTING15 - PRECHARGE- -GUARD, ANIMAL, SOLID COVER, STRAIGHT, VERTICAL16 2 9220252997WGRCSLDSVF 1

ADCOCKDANNA6/7/13

GUARD, ANIMAL, L-SHAPED17 4 9220102213WGRCLSHPF 1GUARD, ANIMAL, PT OR VOLTAGE TRANSFORMER18 3 9220102214WGRCPTTRF 1

2. GROUND RESISTANCE TO BE 15 OHMS OR LESS.3. CONNECT ENDS OF POWER AND CONTROL CABLES WITH PROTECTIVE ARMORED FLEX TO CONTROL.4. WHEN INSTALLING UNIT, OPEN JUNCTION BOX PANEL BY REMOVING SCREWS, RECORD 3 PT CORRECTION FACTORS LISTED AND PLACE

ON INSIDE DOOR OF CONTROL. CLOSE JUNCTION BOX PANEL.

10. USE #6 CU WP FOR ARRESTER SECONDARY CONNECTIONS.

WASHER, ROUND, FLAT, STAINLESS, STEEL, 304, ALLOY, FOR, 1/2"BOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISC, 15KV, LBK, HOOKS, 600A, LEFT

013407152107260123

1621

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING, DOUBLE COIL, F013264 2WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.013308 2

WASHER,3", SQUARE, CURVED, 13/16", HOLE013346 2BOLT, MACH, SQ, NUT, 5/8" X 12"152107 2BRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREAD9220087868 1

NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEX012277 2WASHER, FLAT, ROUND, SILICON, BRONZE, FOR, 1/2", BOLT013163 4WASHER, ROUND, 1/2, SS, 1.375" OD10542504 2LUG, 2-HOLE, TIN-PLATED, NEMA9220068102 1

010928

1. SEE DWG. 08.06-11A FOR DESIGN SPECIFICATIONS.

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

9 6KLC2H79ALF

2NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEX012277 2WASHER, FLAT, ROUND, SILICON, BRONZE, FOR, 1/2", BOLT013163 4WASHER, ROUND, 1/2, SS, 1.375" OD10542504 2LUG, COMPRESSION, 2H-795AL155331 1

010928

9. SIX ARRESTERS REQUIRED: 3 ON EACH SIDE. CONNECT TO TERMINALS OF RECLOSER AS SHOWN ON DETAIL C ON DWG. 08.06-11A.

13. ARRESTORS, PT'S and 8 PIN PT CONTROL CABLE COME WITH RECLOSER FROM MANUFACTURER.

5/2/14 LOOSIER

08.06-11C

DEF

X

DEPDEMDEC

(INCLUDED FROM MANUFACTURER)

ADCOCKDANNA

10/17/14 LOOSIER ADCOCKDANNA

4 7/1/15 LOOSIER ADCOCKBURLISON

Page 40: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

RECLOSER AND FRAME, THREE-PHASE, VIPER ST,WITH VERTICAL BYPASS SWITCH

- 25KV CONSTRUCTION -ADCOCKDANNASALAS10/7/13

1. SEE DWG. 08.06-12C FOR BILL OF MATERIALS AND NOTES.

10

2

BØAØ

L1

L2

BLACK

GREEN - GROUND

SECONDARYARRESTER

TERMINAL L1

BLACK

SECONDARY ARRESTER CONNECTION

0

2

1

APPR.REVISED BY CK'D

3

1/2" SS

ROUNDWASHER

DETAIL "C"

BOLT

4 HOLESPADE ONRECLOSER

#6 WP

ROUNDBOLT

#6 WP

NUT

LOCKWASHER

USE WILDLIFE GUARDS

DETAIL "A"

1

16

SEE DETAIL "B"

DETAIL "B"VIPER ST JUNCTION

BOX PANEL; SEE NOTE 4ON 08.06-12C

5"

6"

24"

24"

FRONT VIEW

38"

BOLT ON TAMPERGUARD FORCONTROL CABLEPLUG

SIDE VIEW

13

11

SEE DETAIL "A"

12

SOURCE

LOAD

(4) 9220102213(2) 9220252997

17

IN CONTROL BOX

3

14

#6 SD BC

4

9

6

SEE

108"

48"

48" MIN.

DETAIL "C"

5

15

SOURCE LOAD

NEUTRAL

8

48"

#2 CU

756"

2. BRACKET IS NOT REVERSIBLE. WILL NEED TO MOUNT UNIT ROAD SIDE OR FIELD SIDE DEPENDING ON

56"

08.06-12A

DEF

X

DEPDEMDEC

DIRECTION OF SOURCE.

ADCOCKBURLISONLOOSIER7/17/15

ADCOCKDANNASALAS11/6/13

LOOSIER8/10/15 ADCOCKBURLISON

Page 41: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

RECLOSER AND FRAME, THREE-PHASE, VIPER ST,WITH VERTICAL BYPASS SWITCH

- 25KV CONSTRUCTION -

1. SEE DWG. 08.06-12A FOR DESIGN SPECIFICATIONS.

0

2

1

APPR.REVISED BY CK'D

3

ADCOCKDANNA10/7/13

2. SEE DWG. 08.06-12C FOR BILL OF MATERIALS AND NOTES.

16.5"

29.74"

47.7"

LOWER SUPPORTSSHIPPED UNATTACHED

52.06"

27.66"

59.62"

55.76"

44.75"6

19

6

3.02"

1.27"

20"

INTERNAL CURRENTTRANSFORMER

SHIPPED WITH UNITALUMINUM POLEMOUNTING FRAME

MODULE CABLEACCESS IN THEJ-BOX

JUNCTION BOXRECLOSER CONTROLCABLE AND HARDWARE

LEFT VIEW

RIGHT VIEW BACK VIEW

ATTACH GROUNDSTIRRUP TO FRAME

LOAD SIDE

SOURCE SIDE

1

(ANIMAL GUARD NOT SHOWN FOR CLARITY)

(ANIMAL GUARD NOT SHOWN FOR CLARITY)

16

17

PT JUNCTIONBOX

BØ CØAØ

#6 CU WP SEE DETAIL C

ON DWG. 08.06-12A

2.13"

#6 CU WP

SALAS

08.06-12B

DEF

X

DEPDEMDEC

SPACING AVAILABLE FOR 3 ADDITIONALPTS IF NECESSARY

ADCOCKBURLISON7/17/15 LOOSIER

ADCOCKDANNA7/21/14 LOOSIER

Page 42: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY, THREE-PHASE, VIPER STWITH VERTICAL BYPASS SWITCH

- 25KV CONSTRUCTION -

NOTES:

7. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS: DO NOT EXCEED!

5. A 45' CLASS 4 POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION. IF JOINT USE ON POLE, CLEARANCES MAY REQUIRE 50' POLE.6. ISSUE TAPS TO SWITCHES SEPARATELY (WIRE, CONNECTORS, AND LUGS). BOLTS WILL BE ON SWITCH.

0

3

2

1

APPR.REVISED BY CK'D

654

3

2

1

BILL OF MATERIALS

ITEMDESCRIPTION

644

4

3

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

RECLOSER TYPE VST 800 AMP ELEC. 27KV VRT MNTGBOLT, MACHINE, SQ, NUT, 5/8" X 12"WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304 ALLOYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWIRE, TIE, #4 SD BC, SLDBOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEXWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING, DOUBLE COIL, F

INSULATOR, 25 KV POLYMER, 1-3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATORARRESTER, LIGHTNING, 18KV HD MOV W/SILICONE RUBBER POLYBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODBOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

CABLE, XLP UG AL 500GUARD, PVC, CABLE, 2-1/4" X 10'BANDING, STAINLESS STEEL, 316, 3/4" WIDE, .030 THBANDING, BUCKLE, SS, 3/4", FOR BANDING

7

11

10

8

5

2

6

7

9220244274152107013308013264013128013407010928012277

92200692440109280012277013128

013264

92200910189220068094

220207010928012277013163155326

10542504

202112323422434122434142

RCVST800E27V1F

SW256BYPF

BKTFBGPIN15138F

IPIN25PFTTIEF500COVALPF

AREQOH18F

KLC2H50ALF

KLC2H50AL90DF

RCRISER500ALF

CRIS1UGPVC225CF

19 - 3 TRANF, POTENTIAL, 25KV, 14400V0020800983-

161715757236364888

111224122

121

0.23

2

11. TOTAL WEIGHT OF THE RECLOSER AND FRAME IS 750 LBS DOES NOT INCLUDE PT'S OR LA'S.12. NEUTRAL MAY BE DOUBLE DEADENDED OR STRAIGHT THROUGH ON SPOOL AS NEEDED.

8. PT'S TO BE LOCATED ON SOURCE SIDE. POWER SOURCE FOR PT'S FROM UNIT 1.

VIPER ST CONTROL CABLE12 1 9220244739RCVIPCAB40F 1SEL 651 CONTROL13 1 9220244823RCCNTL651GWF 1CABLE, CONTROL, #10, 4 WIRE14 40 192324- 11" CONDUIT, FLEX, AND FITTING15 - PRECHARGE- -GUARD, ANIMAL, SOLID COVER, STRAIGHT, VERTICAL16 2 9220252997WGRCSLDSVF 1GUARD, ANIMAL, L-SHAPED17 4 9220102213WGRCLSHPF 1GUARD, ANIMAL, PT OR VOLTAGE TRANSFORMER18 3 9220102214WGRCPTTRF 1

2. GROUND RESISTANCE TO BE 15 OHMS OR LESS.3. CONNECT ENDS OF POWER AND CONTROL CABLES WITH PROTECTIVE ARMORED FLEX TO CONTROL.4. WHEN INSTALLING UNIT, OPEN JUNCTION BOX PANEL BY REMOVING SCREWS, RECORD 3 PT CORRECTION FACTORS LISTED AND PLACE

ON INSIDE DOOR OF CONTROL. CLOSE JUNCTION BOX PANEL.

10. USE #6 CU WP FOR ARRESTER SECONDARY CONNECTIONS.

WASHER, ROUND, FLAT, STAINLESS, STEEL, 304, ALLOY, FOR, 1/2"BOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISC, 25KV, LBK HOOKS, 600A, LEFT OPENING

013407152107260552

1621

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING, DOUBLE COIL, F013264 2WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.013308 2

WASHER,3", SQUARE, CURVED, 13/16", HOLE013346 2BOLT, MACH, SQ, NUT, 5/8" X 12"152107 2BRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREAD9220087868 1

NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEX012277 2WASHER, FLAT, ROUND, SILICON, BRONZE, FOR, 1/2", BOLT013163 4WASHER, ROUND, 1/2, SS, 1.375" OD10542504 2LUG, 2-HOLE, TIN-PLATED, NEMA9220068102 1

010928

1. SEE DWG. 08.06-12A FOR DESIGN SPECIFICATIONS.

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

9 6KLC2H79ALF

2NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEX012277 2WASHER, FLAT, ROUND, SILICON, BRONZE, FOR, 1/2", BOLT013163 4WASHER, ROUND, 1/2, SS, 1.375" OD10542504 2LUG, COMPRESSION, 2H-795AL155331 1

010928

9. SIX ARRESTERS REQUIRED: 3 ON EACH SIDE. CONNECT TO TERMINALS OF RECLOSER AS SHOWN ON DETAIL C ON DWG. 08.06-12A.

ADCOCKDANNA10/7/13 SALAS

13. RECLOSER COMES WITH 10KV ARRESTERS AND 7200 PT'S, REPLACE WITH 18KV ARRESTERS AND 14400 PT'S

AS SHOWN IN THE BILL OF MATERIALS.

08.06-12C

DEF

X

DEPDEMDECADCOCKBURLISON7/17/15 LOOSIER

ADCOCKDANNA2/10/14 McCONNELL

10/26/15 LOOSIER ADCOCKBURLISON

Page 43: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

DOUBLE CIRCUIT, THREE-PHASE, VIPER STADCOCKGUINNLOOSIER2/13/15

1. SEE DWG. 08.06-13B FOR BILL OF MATERIALS AND NOTES.

0

1

APPR.REVISED BY CK'D

2

3

08.06-13A

DEF

X

DEPDEMDEC

2. LEADS TO RECLOSER MUST BE A MINIMUM OF 14 INCHES CLEARANCE FROM THROUGH CIRCUIT.

L1

L2

BLACK

GREEN - GROUND

SECONDARYARRESTER

TERMINAL L1

BLACK

SECONDARY ARRESTER CONNECTION

USE WILDLIFE GUARDS

DETAIL "A"

DETAIL "B"VIPER ST JUNCTION

BOX PANEL; SEE NOTE 2ON DWG. 08.06-13B

(4) 9220102213(2) 9220252997

IN CONTROL BOX19

14"

290°

27-3/4"

72"

6"

1

#6 SD BC

#2 SD BC TANKGROUND TOSYSTEM NEUTRAL

SEEDETAIL "C"

6

4" MIN.

21

17

7

15 16

2423

SEE DETAIL 'A'

20

13

11

12

FRONT VIEWSIDE VIEW

SOURCE LOAD

(TANGENT PHASE OMITTED FOR CLARITY)

48"

48"

24"

60"

24"

5"

24"

24"

48"

48"

14

3 4 5

8 9 10

22

18

SEE NOTE 3

3. USE COLA CROSSARM BRACKET FOR OUTER TWO SOURCE SIDE ARRESTERS. THIS WILL SHORTEN JUMPER LENGTH.4. MOUNT PT JUNCTION BOX (INCLUDED WITH RECLOSER UNIT) ON PT BRACKET. WHOLE PT ASSEMBLY CAN BE BUILT

ON GROUND PRIOR TO INSTALLATION.

SEE NOTE 4

48" MIN.

4" MIN. (TYP.)

1/2" SS

ROUNDWASHER

DETAIL "C"

4 HOLESPADE ONRECLOSER

#6 WP

ROUNDBOLT

#6 WP

NUT

LOCKWASHER

ADCOCKBURLISONLOOSIER4/10/15

LOOSIER8/10/15 ADCOCKBURLISON

Page 44: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DOUBLE CIRCUIT, THREE-PHASE, VIPER ST

NOTES:

4. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED TO 40 FT-LBS: DO NOT EXCEED!

3. MINIMUM 55' POLE REQUIRED. WHEN DESIGNING, CONSIDER VERTICAL TENSION ON ADJACENT POLES.

0

3

2

1

APPR.REVISED BY CK'D

6. NEUTRAL MAY BE DOUBLE DEADENDED OR STRAIGHT THROUGH ON SPOOL AS NEEDED.

5. PT'S TO BE LOCATED ON SOURCE SIDE. POWER SOURCE FOR PT'S FROM UNIT 1.

ADCOCKGUINN2/13/15

2. WHEN INSTALLING UNIT, OPEN JUNCTION BOX PANEL BY REMOVING SCREWS, RECORD 3 PT CORRECTION FACTORS LISTED AND PLACE ON INSIDE DOOR OF CONTROL. CLOSE JUNCTION BOX PANEL.

1. SEE DWG. 08.06-13A FOR DESIGN SPECIFICATIONS.

08.06-13B

DEF

X

DEPDEMDEC

LOOSIER

5

6

8

4

3

2

1

BILL OF MATERIALS

ITEMDESCRIPTION

1

ITEMQTY/CU

NUMBERMACRO UNIT

-

BUBBLENUMBER

COMPATIBLEUNIT

CUQTY

16151413

10

9

12

11

7

RECLOSER, ELECTRONIC, G&W VIPER-ST, HORIZ MOUNT, 27 KV, 800BOLT, MACHINE, SQ, NUT, 5/8"X12"WASHER, SQUARE, 2-1/4",SQUARE,FLAT,13/16",HOLE,GALV.WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COILSWITCH, RECLOSER BY-PASS, THREE-PHASE HORIZONTALWASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COILWASHER, 3",SQUARE, CURVED, 13/16" HOLEBOLT, MACHINE, SQ, NUT, 5/8"X12"BRACKET, STANDOFF, FIBERGLASS STAND-OFF, 1-3/8" THREADINSULATOR, 25 KV POLYMER, 1 3/8" THREADTIE, PLASTIC, 2-7/8",F-NECK,INSULATOR

INSULATOR, POST, TIE, TOP, 25KV

BOLT, MACHINE, 1/2 IN X 2 IN, STAINLESS STEEL, HEX HEADNUT, HEX, 1/2 IN, STAINLESS STEELWASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUNDLUG, COMPRESSION, 2H 500 ALWASHER, ROUND, 1/2", SS,1.375" ODBOLT, MACHINE, 1/2 IN X 2 IN, STAINLESS STEEL, HEX HEADNUT, HEX, 1/2 IN, STAINLESS STEELWASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUNDWASHER, ROUND, 1/2", SS,1.375" ODLUG, COMPRESSION, 4HOLE,795,AAC

ARRESTER, LIGHTNING, 10KV HD MOV W/SI RUBBER POLY HOUSINGBOLT, CARRIAGE, 3/8 IN, 6 IN, CARBON STEELBRACKET, ARRESTOR, LIGHTNING AND CUTOUT TYPE A

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COILWASHER, 3",SQUARE, CURVED, 13/16" HOLEBRACKET, STANDOFF, 30 IN, FIBERGLASSSTUD, LINE POST, 5/8"X1-3/4"BOLT, MACHINE, SQ, NUT, 5/8"X12"TIE, E-Z, SIDE, F-NECK, 795,AAC

CABLE, XLP UG AL 500CONDUCTOR, ALUMINUM, AACPT CONTROL CABLE (INCLUDED FROM MANUFACTURER)VIPER ST CONTROL CABLEGUARD, PVC, CABLE, 2-1/4" X 1-'SCREW, LAG, HX, 1/4' X 2', GALVSEL 651 CONTROLARRESTER, LIGHTNING, SEC 120-240 3 WIRETRANSFORMER, POTENTIAL, 15KV, 7200VBRACKET, MOUNTING, 42 IN, GALVANIZED STEEL, 3 PT MOUNTINGBOLT, MACHINE, SQ, NUT, 5/8"X12"WASHER, SQUARE, 5/8 INCH SS, 2-1/4 INCH X 2-1/4 INCHWASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COILGUARD, ANIMAL, SOLID COVER, STRAIGHT, VERTICALGUARD, ANIMAL, L-SHAPED,GUARDGUARD, ANIMAL, PT OR VOLTAGE TRANSFORMER

18

2322

21

2019

17

24

12221222111

1

2241222421

121

221121

128-11151111222111

92202482951521071330813264

92202482881326413346152107

922008786892200910189220068094

80212

109281227713163155326

10542504109281227713163

10542504155464

2202021121370101

13264133467043172361152107121434

202112922021886192202676679220244739

32342214111

9220244823220139

92200852319220224674

1521079220132411

13264922025299792201022139220102214

RCVST800E27HF

SW256RECBYPF

BKTFBGPIN15138F

IPIN25PFTTIEF500COVALPF

IHPTT15F

KLC2H50ALF

KLC4H79ALF

AREQOH10F

BKTCOLASTLXARMF

BKTFPIS30F

STIE795ALF

RCRISER500ALFJUMP795ALF

RCVIPCAB40F

CRIS1UGPVC225WF

RCCNTL651GWFAREQSC120FRCPTREC15F

BKT3PTRCTRISTLF

WGRCSLDSVFWGRCLSHPFWGRCPTTRF

-

6

6

6

6

6

1

1-

126

6

6

2

6

6

1

33

1

31

2

3

ADCOCKBURLISON4/10/15 LOOSIER

Page 45: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

3/31/15 LOOSIER BURLISON ADCOCK

VIPER RECLOSER HORIZONTAL CONSTRUCTION0

APPR.REVISED BY CK'D

1

2

3

NOTES:

1. SEE DWG. 08.06-14B FOR BILL OF MATERIALS AND NOTES.

08.06-14A

DEF

X

DEPDEMDEC

2. POSITION JUMPERS TO ENSURE MINIMUM OF 10" CLEARANCE BETWEEN THEM.

3. MOUNT PT JUNCTION BOX (INCLUDED WITH RECLOSER UNIT) ON PT BRACKET. WHOLE PTASSEMBLY CAN BE BUILT ON GROUND PRIOR TO INSTALLATION.

4. USE COLA CROSSARM BRACKET FOR OUTER TWO SOURCE SIDE ARRESTERS. THIS WILLSHORTEN JUMPER LENGTH.

FRONT VIEW

14"

38"

5'-0"BOLT ON TAMPERGUARDS FOR CONTROLCABLE PLUG AND

MOUNT CONTROLON OPPOSITESIDE OF POLEFROM RECLOSER

POWER CABLE

4"

SOURCE LOAD

11L1

L2

BLACK

GREEN - GROUND

SECONDARYARRESTER

TERMINAL L1

BLACK

SECONDARY ARRESTER CONNECTION

1/2" SS

ROUNDWASHER

DETAIL "A"

BOLT

4 HOLESPADE ONRECLOSER

#6 WP

ROUNDBOLT

#6 WP

NUT

LOCKWASHER

IN CONTROL BOX

9

#6 SD BC POLEGROUND

SIDE VIEW

27-3/4"

72"

6"

1

#6 SD BC

#2 SD BC TANKGROUND TOSYSTEM NEUTRAL

SEEDETAIL "A"

5

4" MIN.

16

8

6

12 10

141317

7

C BOLT HOLEL

3

SEE NOTE 3

SEE NOTE 2

4

15

SEE NOTE 4

5'-0" MAX.

4/10/15 LOOSIER

2

BURLISON ADCOCK

Page 46: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

VIPER RECLOSER HORIZONTAL CONSTRUCTION0

3

2

1

APPR.REVISED BY CK'D

3

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

6

1

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

RECLOSER, ELECTRONIC, G&W VIPER-ST, HORIZ MOUNT, 27 KV, 800 AWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.BOLT, MACHINE, SQ, NUT, 5/8" X 12"SWITCH, RECLOSER, RECLOSER BY-PASS, THREE-PHASE HORIZONTAL

BOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2" X 2"

CABLE, XLP UG AL 500GUARD, PVC, CABLE, 2-1/4" X 10'SCREW, LAG, HX, 1/4" X 2", GALV.ARRESTER, LIGHTNING, SEC 120-240 3 WIRE

5

9

8

7

6

6

1

2

6

6

9220248295013264013308152107

9220248288220202

010928012277013163155326

10542504010928

202112323422014111220139

RCVST800E27HF

SW256RECBYPF

AREQOH10F

KLC2H50ALF

KLC4H79ALF

RCRISER500ALF

CRIS1UGPVC225WF

AREQSC120F

22211

224122

121151

ADCOCKBURLISONLOOSIER3/31/15

VIPER ST CONTROL CABLE10 1 9220244739RCVIPCAB40F 1SEL 651 CONTROL11 1 9220244823RCCNTL651GWF 1PT CONTROL CABLE (INCLUDED FROM MANUFACTURER)WILDLIFE GUARD RECL SOLID STRAIGHT VERTICAL COVER

BRACKET, MOUNTING, 42 IN, GALVANIZED STEEL, 3 PT MOUNTINGBOLT, MACHINE, 5/8", 11" X 12", STEEL, ANSI C135.1., MWASHER, SQUARE, 2-1/4 X 2-1/4 X 3/16, GALVWASHER, LOCK, 5/8", STEEL, GLV, LK, 5/8, COIL, DBL

WILDLIFE GUARD RECL L-SHAPED COVER

TRANSFORMER, POTENTIAL, 15KV, 7200V

-1

1222

1

1

92202676679220252997

9220224674152107

9220132411013264

9220102213

9220085231

WGRCSLDSVFWGRCLSHPF

121314

17

16

--

RCPTREC15F

33

1

3

3. A 45' CLASS POLE IS THE MINIMUM TO BE USED FOR THIS INSTALLATION.

5. PT TO BE LOCATED ON THE SOURCE SIDE.

6. USE GROUNDING LUGS ON RECLOSER AND FRAME TO PROPERLY GROUND RECLOSER.

NOTES:

1. SEE DWG. 08.06-14A FOR RECLOSER DESIGN SPECIFICATIONS.

4. ALL BOLTS ON PRIMARY CONNECTIONS ARE TO BE TORQUED AT 40 FT-LBS: DO NOT EXCEED!

7. NEUTRAL MAY BE DOUBLE DEADEND OR STRAIGHT THROUGH ON SPOOL AS NEEDED.

2. WHEN INSTALLING UNIT, OPEN JUNCTION BOX PANEL BY REMOVING SCREWS, RECORD 3 PT CORRECTIONFACTORS LISTED AND PLACE ON INSIDE DOOR OF CONTROL. CLOSE JUNCTION BOX PANEL.

08.06-14B

DEF

X

DEPDEMDEC

NUT, STAINLESS STEEL, HEX, 304 ALLOY, COARSE THREAD012277 2WASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLT013163 4WASHER, ROUND, 1/2", SS, BRONZE, FOR 1/2" BOLT10542504 2LUG, COMP. 4H, 795 AL155464 1

BKT3PTRCTRISTLF

BOLT, CARRIAGE, 3/8 IN, 6 IN, CARBON STEELBRACKET, ARRESTOR, LIGHTNING AND CUTOUT TYPE A

2011213070101

BKTCOLASTLXARMF21

4

ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLY

GUARD, ANIMAL, PT OR VOLTAGE TRANSFORMER19220102214WGRCPTTRF15 3

Page 47: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

WIRING DIAGRAM FOR PT CLUSTER

FOR G&W VIPER0

3

2

1

APPR.REVISED BY CK'D

SOURCE

X1 X2

GND

7.2 OR 14.4 KVSOURCE

7.2 OR 14.4 KVSOURCE

7.2 OR 14.4 KV

AØ BØ CØ

PT1

PT2

PT3

PT JUNCTION BOX

TO CONTROL BOX

BLK

GRN

WHT

X1 X2

GND

BLK

GRN

WHT

X1 X2

GND

BLK

GRN

WHT

NOTES: 1. X1 WIRE IS BLACK, X2 WIRE IS WHITE, GROUND WIRE IS GREEN.

08.06-15A

DEF

X

DEPDEMDEC

12/19/14 BURLISON GUINN ADCOCK

Page 48: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

WIRING DIAGRAM FOR PT CLUSTER

ABB 1PT TO 3PT CONVERSION0

3

2

1

APPR.REVISED BY CK'D

SOURCE

X1 X2

GND

C PHASESOURCEB PHASE

SOURCEA PHASE

X1 X2

GND

X1 X2

GND

NOTES:

12/19/14 BURLISON GUINN ADCOCK

POLE

TO ANPHONAL CONNECTORAT BOTTOM OF RECLOSER

GRNGRNGRN

GRN GRN

BLKBLKBLK

WIRE NUTWIRE NUTBLK

RED

WHTWHT

BLK

WHT

1. THE DIAGRAM ABOVE SHOWS THE POLE TO THE LEFT; HOWEVER, THE PT’S MAY BE ON THE OTHER SIDE.

WIRING DIAGRAM WOULD BE REVERSED IF POLE IS TO THE RIGHT. FOLLOW THIS CONVENTION:C PHASE X1 – RED

B PHASE X1 – WHITE

A PHASE X1 – BLACK

X2 ON ALL PHASES IS GREEN

2. WHEN CONVERTING A RECLOSER FROM 1PT ATTACHED TO THE B PHASE TO 3 PT’S, THE FIRST STEP IS TO

CAREFULLY REMOVE THE SECONDARY CABLE FROM THE B PHASE. THIS CABLE WILL NEED TO BE REINSTALLEDON THE C PHASE PT.

3. PT’S MAY BE GROUNDED IN ONE OF TWO WAYS. 1) WITH OLDER PT’S, THE GROUNDING LUG ON THE BACK

OF THE PT IS ATTACHED TO A COPPER GROUNDING BAR. 2) ON NEWER PT’S, THE GROUNDING LUG ON THE BACK

OF THE PT IS BONDED TO THE FRAME THROUGH THE MOUNTING BOLT AND A PRE-INSTALLED STRAP. PT’S MUST

BE GROUNDED TO THE LUG ON THE BACK OF THE PT IN ONE OF THESE TWO METHODS.

4. PT CONVERSION KITS HAVE BEEN CREATED AND INCLUDE: 4 STRESS RELIEF CONNECTORS, WIRE NUTS,TWO PRE-CUT AND PRE-STRIPPED PIECES OF CONTROL CABLE AND 3/8” STAINLESS STEEL NUTS, BOLTS AND

WASHERS FOR MOUNTING AND WIRING THE THREE PT’S.

5. INSTALL JUMPER FROM THE X2 BUSHING TO THE GROUND BUSHING IN THE "A" PHASE PT.

SEE NOTE 5

ORANGE

BLUE

BLACK

RED

YELLOW NOT USEDALTERNATE COLOR SCHEME FORCONTROL CABLE WITH BLUE,BLACK, RED, ORANGE ANDYELLOW CONDUCTORS

08.06-15B

DEF

X

DEPDEMDEC

Page 49: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

FUSE AND BATTERY FOR SEL 651-R2 CONTROLS

(ABB & VIPER)0

3

2

1

APPR.REVISED BY CK'D

12/19/14 BURLISON GUINN ADCOCK

08.06-15C

DEF

X

DEPDEMDEC

321 -

BILL OF MATERIALS

ITEMDESCRIPTION

-- -

--

ITEM

111

QTY/CU

NUMBERMACRO UNIT

-

BUBBLENUMBER

COMPATIBLEUNIT

CUQTY

F201 - 30ABATTERY/ BATTERYCHARGER CIRCUIT

F202 - 5A12 VDC AUX

SUPPLY

F412 - 10A120 VAC POWER

MODULE PROTECTION

9220273322 CONTROL, BATTERY CHARGER CKT, SEL 651 RECLOSER CONTROL - F201-30A9220237204 CONTROL, 12VDC AUX SUPPLY, SEL 651 RECLOSER CONTROL - F202-5A9220273356 CONTROL, 120VAC POWER MODULE, SEL 651 RECLOSER CONTROL - F412-10A

3

2

1

Page 50: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

FUSE AND BATTERY FOR SEL 651-R2 CONTROLS

(ABB & VIPER)0

3

2

1

APPR.REVISED BY CK'D

12/19/14 BURLISON GUINN ADCOCK

08.06-15D

DEF

X

DEPDEMDEC

321 -

BILL OF MATERIALS

ITEMDESCRIPTION

-- -

--

ITEM

111

QTY/CU

NUMBERMACRO UNIT

-

BUBBLENUMBER

COMPATIBLEUNIT

CUQTY

F401 - F403 6ALOAD SIDE PT FUSES

1028160 CONTROL, PT VOLTAGE, SEL 651 RECLOSER CONTROL - F401-F406-6A9220226465 CONTROL, AC POWER SUPPLY & HEATER, SEL 651 RECLOSER CONTROL - F407-F410-30A9220237208 CONTROL, GFCI OUTLET, SEL 651 RECLOSER CONTROL - F411-15A

F404 - F406 6ASOURCE SIDE COPPER PLUG

DUMMY FUSES INPT FUSES

F-408 AND F410

NEUTRAL CIRCUITS

F407 - 30A120 VAC POWER

MODULE PROTECTION

F411 15A120 VAC GFCIPROTECTION

4 - - 19220284497 BATTERY, LEAD ACID SEALED, 16 A H, SEL 651R CONTROL

7/17/15 LOOSIER BURLISON ADCOCK

2/19/16 LOOSIER BURLISON ADCOCK

Page 51: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SPECIAL PROVISIONS -

G&W VIPER ST, IPP INTERCONNECTION0

1

APPR.REVISED BY CK'D

2

3

4/18/16 BRAVO BURLISON ADCOCK

SPECIAL PROVISIONS FOR G&W VIPER ST INSTALLATIONS AT INTERCONNECTIONS WITH IPPS (INDEPENDENT

IS TO BE CONNECTED TO THE “UTILITY” SIDE OF THE RECLOSER (TOWARDS THE UTILITY SUBSTATION).

SIDE IS THE “IPP/GENERATOR” SIDE OF THE RECLOSER (TOWARDS THE GENERATING FACILITY).

UNBOLTED AND REMOVED FROM THE SWITCH BEFORE IT IS MOUNTED. (EACH PHASE HAS SOURCE ANDLOAD DISCONNECT BLADES THAT ARE PARALLEL TO EACH OTHER, AND THESE ARE LEFT ALONE. ONLYTHE BYPASS BLADE, HORIZONTAL TO THE OTHERS, IS TO BE REMOVED. WHEN READY, THE SWITCHESWILL HAVE 6 BLADES INSTEAD OF 9. THIS IS DONE BECAUSE AN IPP INTERTIE RECLOSER MUST NEVER BE

4. SEL 651R RELAYS AT IPP INTERCONNECTIONS HAVE SETTINGS, DISPLAY PANELS, AND BUTTONS THATARE NOT THE SAME AS A REGULAR LINE RECLOSER. THE PROPER SETTINGS AND FACEPLATE LABELS AREAVAILABLE FROM THE COMPANY PROTECTION ENGINEER AND ARE TO BE APPLIED AT TIME OF RELAY

LOCATED ONE SPAN AWAY, CLOSER TO THE IPP.

POWER PRODUCERS):

BYPASSED, SINCE THERE IS NO BACKUP PROTECTION TO ASSURE PROPER OPERATION OF THE IPP WITHOPERATION OF THE IPP WITH THE UTILITY.)

PROVISIONING.

2. IN DWG. 08.06-11A, THE SIDE OF THE RECLOSER REFERENCED AS THE LOAD HORIZONTAL BUSHING

1. IN DWG. 08.06-11A, THE SIDE OF THE RECLOSER REFERENCED AS THE SOURCE VERTICAL BUSHING SIDE

5. SEE DWGS. 11.09-10 OR 11.09-20 FOR CONSTRUCTION DETAILS FOR THE IPP PRIMARY METERING POLE

08.06-15E

DEFDEP

X

DEMDEC

3. FOR IPP INTERTIE APPLICATIONS, THE BYPASS BLADE ON THE “SWITCH” ( ITEM # 260123) MUST BE

Page 52: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

ABB TO SEL 651-R2 CONTROL CONVERSION ON

ABB RECLOSERS0

3

2

1

APPR.REVISED BY CK'D

ADCOCKGUINNBURLISON12/19/14

1. FOLLOWING STANDARD OPERATING PROCEDURES AND SAFETY MEASURES, BYPASS THE ABB RECLOSER AND

2. DISCONNECT THE BATTERY IN THE EXISTING CONTROL.

3. UNPLUG THE CONTROL CABLE AND SAFELY MOVE IT OUT OF THE WAY.

4. DISCONNECT THE GROUNDING CONNECTION TO THE EXISTING CONTROL.

5. LOOSEN BOLTS AND REMOVE CONTROL FROM POLE.

6. MOUNT THE NEW CONTROL. USE THE SAME TOP BOLT, THE BOTTOM BOLT WILL NEED TO BE REDRILLED.

7. CONNECT GROUND TO CONTROL BOX.

8. PLUG THE CONTROL CABLE INTO THE NEW CONTROL. INSTALL PLUG GUARD OVER THE PLUG

9. 9” ABOVE THE TOP THROUGH BOLT OF THE CONTROL, DRILL HOLE FOR 5/8” THROUGH BOLT. INSTALL ANTENNA

10. INSTALL ANTENNA AND CONDUIT WITH ANTENNA WIRE INSIDE. SECURE CONDUIT TO POLE WITH STRAPS.

13. CLOSE THE SOURCE SIDE DISCONNECTS. CONTROL AND MODEM SHOULD COME TO LIFE.

14. FOLLOW INSTRUCTIONS FOR COMMISSIONING CONTROL.

15. WHEN GIVEN OK - CLOSE LOAD SIDE DISCONNECTS AND FOLLOW STANDARD PROCEDURES TO RESTORE

OPEN ALL THREE SOURCE AND LOAD SIDE DISCONNECTS TO COMPLETELY DE-ENERGIZE THE RECLOSER.

BRACKET WITH A STANDARD INSULATOR POLE GAIN WITH A 5/8” THROUGH BOLT AND TIGHTEN.

RECLOSER TO SERVICE.

INSTALLATION NOTES:

11. REMOVE COVER FROM 1" PREDRILLED HOLE IN BOTTOM OF CONTROL. FEED CABLE THROUGH 1" HOLE ANDATTACH CONDUIT.

12. CONNECT THE 3 ANTENNA WIRES TO THE MODEM INSIDE CONTROL. SEE DWG. 08.06-16B FOR DETAIL.

08.06-16A

DEF

X

DEPDEMDEC

BRACKET - CN 9220272934ANTENNA - CN 9220272935

16. WHEN RELOCATING THE CONTROL BOX, IF IT REMAINS ON THE SAME FEEDER, IT WILL

RETAIN THE SAME EQUIPMENT ID. IF THE DEVICE IS RELOCATED TO A DIFFERENT FEEDER,THEN THE DEVICE WILL REQUIRE A NEW EQUIPMENT ID AND WILL REQUIRE NEWSETTINGS TO BE UPLOADED.

Page 53: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

ABB TO SEL 651-R2 CONTROL CONVERSION ON

ABB RECLOSERS0

3

2

1

APPR.REVISED BY CK'D

12/19/14 BURLISON GUINN ADCOCK

THERE ARE THREE CABLES COMING FROM THE ANTENNA. THE SMALL CABLE IS THE GPS AND MUST BE SCREWEDINTO THE MIDDLE SPOT ON THE BACK OF THE MODEM. THE TWO LARGER CABLES ARE INTERCHANGEABLE.SCREW THEM INTO THE OTHER TWO SPOTS.

08.06-16B

DEF

X

DEPDEMDEC

MODEM - CN 9220272933MODEM MUST BE CONFIGURED BY TELECOM

Page 54: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.06-22ADWG.

NOTES:

2. CONTROL BOX AND SECONDARY REQUIRED FOR ELECTRONIC RECLOSER ONLY.3. ISSUE RECLOSER AND ELECTRONIC CONTROL SEPARATELY.4. RECLOSER MAY BE REVERSED IN HANGER TO ACCOMMODATE SOURCE AND LOAD POSITION.5. WHEN END MOUNTING THREE-PHASE RECLOSER, USE A MINIMUM OF A 45 FT. CLASS 4 WOOD POLE.

RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL

600 AMP SWITCHELKINSGUINNHOFFMAN10/19/10

1. SEE DWG. 08.06-22B FOR BILL OF MATERIALS.

0

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW

12"

35"

48" MIN.

72"

48"

48"

5"

6"

38"

6"

CØBØAØ

#6 SD BC

BOLT ON TAMPERGUARD FORCONTROL CABLEPLUG

SIDE VIEW

11" 2"

31"

4

3

1

9

5

6

8

SECONDARYARRESTER

SECONDARY ARRESTER CONNECTION

2

1/2" SS

ROUNDWASHER

DETAIL "B"

BOLT

4 HOLESPADE ONRECLOSER

#6 BC

ROUNDBOLT

#6 BC

NUT

LOCKWASHER

L1

L2

BLACK

GREEN - GROUND

TERMINAL L1

BLACK

SECONDARY

NEUTRAL

ADCOCKDANNASALAS11/6/13

Page 55: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.06-22BDWG.

RECLOSER ASSEMBLY, THREE-PHASE, VERTICAL,

600 AMP SWITCHELKINSGUINNHOFFMAN10/19/10

NOTES:

1. SEE DWG 08.06-22A FOR DESIGN SPECIFICATIONS.

R

372102381674372172373379323422220133

1

11

1

CONTROL, ELECTRONIC (ISSUE SEPARATELY)

ADAPTER, PVC, MALE, SCH 40NUT, 1", STEEL CONDUITCONDUIT, 1", PVC, SCH 40

22

1CABLE GUARD, PLASTIC, 2-1/4" X 10"ARRESTER, SECONDARY, 650V

CONDUIT, 90°, 1" PVC

2. SEE DWG 03.06-04 FOR PIN INSULATOR DETAILS.

0

3

2

1

APPR.REVISED BY CK'D

181716 -

ADDITIONAL MATERIALS FOR ELECTRONIC RECLOSER ONLY

CATALOGDESCRIPTION

------ -

--

----

QTYPERCU

NUMBERMACRO UNIT

CU/CNITEMNO.

COMPATIBLE UNIT

QTYREQ'D

-

- 19202122

11

10

9

87

6

5432

1

BILL OF MATERIALS

CATALOGDESCRIPTION

1

1

2

66

4

6

6

44

3

QTYPERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

013264013308152107260123

922008786892200910189220068094

220202010928012277013163155326

105425049220068102

202112323422434122434142220139013264013308152107153111160123190404

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.BOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 3-SLD BLADE DISC,, 15KV, LBKBRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREADINSULATOR, 25 KV POLYMER, 1 3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATORARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLYBOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD, 1/2" X 2"NUT, STAINLESS, STEEL, HEX, 304, ALLOY, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTLUG, COMP 2H 500 ALWASHER, ROUND, RD, 1/2, SS, 1.375" ODLUG, 2-HOLE, TIN-PLATED, NEMA, 90 DEGREECABLE, XLP UG AL 500GUARD, PVC, CABLE, 2-1/4" X 10'BANDING, STAINLESS STEEL, 316, SS, 3/4" WIDE, .030 THBANDING, BUCKLE, SS, 3/4", FOR BANDINGARRESTER, LIGHTNING, SEC 120-240 3 WIREWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.BOLT, MACH, SQ, NUT, 5/8" X 12"CONNECTOR, COMP, AL, A=2/0STR-2SOL, B=2STR-6SOLCONNECTOR, GND, 5/8, ROD, 2, CUWIRE, COPPER, #6, SOFT DRAWN, CU, BR, SDW, SLD, #6

2221

111224121121

0.231221114

1

SW156BYPF

BKTFBGPIN15138FIPIN25PF

TTIEF500COVALPFAREQOH10F

KLC2H50ALF

KLC2H50AL90DFRCRISER500ALF

CRIS1UGPVC225CF

AREQSC120F

GOCE6F

Page 56: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.10-10DWG.

SWITCH, BYPASS, SINGLE-PHASE

NOTES:

1. THE FACE OF POLE SHOULD BE LEFT CLEAR FOR OPERATION OF VERTICAL MOUNTED SOLID BLADE SWITCHES.AVOID MOUNTING STREET LIGHT BRACKETS AND OTHER SIMILAR EQUIPMENT ON THESE POLES.

BYPASS SWITCHES R

15 KV SWITCH, BYPASS, SINGLE-PHASE 25 KV SWITCH, BYPASS, SINGLE-PHASE

1

BRACKET IS INCLUDED WITH SWITCHBRACKET IS INCLUDED WITH SWITCH

0

2

1

APPR.REVISED BY CK'D

ELKINS8/23/10 GUINN GUINN

3

SW156BYPF

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", SQUARE, FLATBOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 600A, 15KV, W/ BRACKET

SW256BYPF

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", SQUARE, FLATBOLT, MACH, SQ, NUT, 5/8" X 12"SWITCH, BYPASS, 600A, 25KV, W/ BRACKET

013264013308152107260123013264013308152107260552

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

1

1

QTYPERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

22212221

2

Page 57: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

1. THIS POLE SHOULD BE OFFSET WHEN POSSIBLE SO THAT CONDUCTORS STAY IN LINE.

SWITCH MOUNTING IN VERTICAL DOUBLE CIRCUIT0

3

2

1

APPR.REVISED BY CK'D

HOFFMAN11/29/10 ELKINSGUINN

FRONT VIEW

PLAN VIEW

2

6

NEUTRAL

#6 SD BC

4

5

1

SEE NOTE 4

5"

28-3/4"

15-1/4"

28-3/4"

9"

72"

44"

44"

2. SEE DWG. 08.10-12B FOR BILL OF MATERIALS.

4"

4"

15-1/4"

28-3/4"

4"

4"

3

4"

4"

DANNA1/23/13 ADCOCKDANNA

08.10-12A

DEF

X

DEPDEMDECLOOSIER3/31/15 ADCOCKWHITE

3. ARRESTERS APPLIED ONLY IN NORMAL OPEN CONFIGURATION.

SEE NOTE 3

4. CAN USE EITHER 20" OR 30" STANDOFF BRACKET AS REQUIRED BY FIELD CONDITIONS.

LOOSIER7/1/15 ADCOCKBURLISON

Page 58: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.10-12BDWG.

NOTES:

SWITCH MOUNTING IN VERTICAL DOUBLE CIRCUIT0

3

2

1

APPR.REVISED BY CK'D

BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD, 1/2" X 2"NUT, STAINLESS, STEEL, HEX, 304, ALLOY, COARSE, THREADBRACKET, MNTG SWITCH ARSTRWASHER, RD, 1/2, SS, 1.375" OD

ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER P

WASHER, SPRING, COIL, STEEL, FOR 5/8", BOLT, GALV.WASHER, 2-1/4", SQUARE, FLAT, 13/16", HOLE, GALV.BOLT, MACH, SQ, NUT, 5/8" X 10"BRACKET, SGL MTCONNECTOR, HOT LINE CLAMP, 795 MCM TO 336 MCM

AREQOH10F

BKTLASWBKTSTLF

010928012277070283

10542504

220202

013264013308152106311263

9220184794

2212

1

22211

BKTCOLASNGSTLF

KHLC7933F

4

2

BILL OF MATERIALS

CATALOGDESCRIPTION

9

3

QTYPERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

5

6

3

6

CABLE, 600V, #6 SD BC193511 2

HOFFMAN11/29/10 ELKINSGUINN

1. SEE DWG. 08.10-12A FOR DESIGN SPECIFICATIONS.

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2

BKTSBDSWSTLF3 3

013264013308070282152107

WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/162BRACKET, MNTG WD/CNCR POLE1BOLT, MACH, SQ, NUT, 5/8" X 12"2

HOFFMAN1/6/12 ELKINSBURLISON

McCONNELL4/9/13 ADCOCKDANNA

BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD,1 /2"X2"NUT, HEX, 1/2 IN, A304, STAINLESS STEELWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304, ALLOY, FOR,1/2"BOLT, MACH, HEX, HD, 1/2"X2"SWITCH, DISCONNECT, SOLID BLADE, 15KV, 600A, 1PH, SWITCH

SW156SBDF

010928012277013128013407152074260136

444821

1 3

Page 59: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

NOTES:

2. THIS POLE SHOULD BE OFFSET WHEN POSSIBLE SO THAT CONDUCTORS STAY IN LINE.

3. MAINTAIN A MINIMUM CLEARANCE OF 16" BETWEEN JUMPERS AND PHASES.

4. CAN USE EITHER 20" OR 30" STANDOFF BRACKET AS REQUIRED BY FIELD CONDITIONS.

600 AMP DOUBLE CIRCUIT

TIE SWITCH

5"

44"

1. SEE DWG 08.10-14B FOR BILL OF MATERIALS.

DETAIL "A"

SEE DETAIL "A"

ELKINSGUINNGUINN8/23/100

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW SIDE VIEW

PLAN VIEW

22"28-3/4"

22"

22"15-1/4"

22"

NEUTRAL

44"

72"

8"

1

TO STRAIGHTTHROUGH

(FAR SIDECONDUCTOR NOT SHOWNFOR CLARITY)

CIRCUIT

16" MIN. TYP.

4

2

3

C BOLT HOLE (TYP.)L3" TYP.

3" TYP.

28-3/4"

15-1/4"

28-3/4"

ADCOCKDANNASALAS11/6/13

ADCOCKBURLISONLOOSIER6/17/15

08.10-14A

DEF

X

DEPDEMDEC

SEE NOTE 4

Page 60: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.10-14BDWG.

600 AMP DOUBLE CIRCUIT

TIE SWITCH

070282013264152107013308

9220068328 SIGN, CAUTION FEEDER TIE SWITCH

WASHER, 2-1/4", SQUARE FLAT, 13/16" HOLEBOLT, MACHINE, SQ, 5/8" X 12"WASHER, SPRING, COIL, FOR 5/8", STL, GALV.BRACKET, MOUNTING WD/CONCRETE POLE

NOTES:

1. SEE DWG 08.10-14A FOR DESIGN SPECIFICATIONS.

ELKINSGUINNGUINN8/23/100

3

2

1

APPR.REVISED BY CK'D

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

SW156SBDF 3

QTY

2

48

441

PERCU

NUMBERMACRO UNIT

-

CU/CNITEMNO.

COMPATIBLE UNIT

QTYREQ'D

260136 SWITCH, SOLID BLADE 600 AMP012277 NUT, SS, HEX013128 WASHER, ROUND, BELLEVILLE, SPRING010928 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"013407 WASHER, ROUND, FLAT, SS152074 BOLT, MACHINE, HEX HEAD, 1/2" X 2"

BKTSBDSWSTLF22

1

2

2

3

4 --165288 CONNECTOR, WEDGE, 4-HOLE, 795 AAC13 3KWP4H79F

ADCOCKDANNAMcCONNELL4/9/13

Page 61: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

LOAD

SWITCH ASSEMBLY, 300 AMP,

SOLID BLADE, VERTICALELKINSGUINNGUINN8/23/10

NOTES:

0

3

APPR.REVISED BY CK'D

1

BILL OF MATERIALS

CATALOG

9220210916

ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLYBRACKET, SINGLE MOUNTBOLT, MACHINE, 5/8" X 10", STEEL, A-ASTM A307, GALVWASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8", BOLT, GALV.

15KV CUTOUT WITH 300A SOLID DOOR25KV CUTOUT WITH 300A SOLID DOOR

DESCRIPTION

9220210993SW153COSBDF

2202026

3

33

QTY

1

21

22

11

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

#6 SD BC

#6 SD BC

NEUTRAL

36"

36"

72"

LINE

2

5"

2" TYP.

1

4

1. 300 AMP DISCONNECT IS AVAILABLE 15KV AND 25KV (COASTAL AND HOLOPAW).

1 SW253COSBDF

3 BKTCOLASNGSTLF

013264013308152106311263

4 AREQOH10F

BKTCOLADBLSTLF

013264013308070106152107

WASHER, LOCK, 5/8", STEEL, GLV, SPRING, DOUBLE COIL, STEEL, F2WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLD, GLV2BRACKET, ARRESTER AND CUTOUT, DBL MNTG1BOLT, MACHINE, SQUARE, NUT, 5/8" X 12"2

32

3

SIDE VIEW FRONT VIEW

KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0KHLC7933F 9220184794 CLAMP, HOT LINE, ALUM, LARGE, 336-795

6 15

6 1

5

-

ADCOCKDANNA4/15/13

4 5/31/13 ADCOCKDANNA

08.10-16

DEF

X

DEPDEMDEC5 3/31/15 LOOSIER ADCOCKWHITE

2. ARRESTERS APPLIED ONLY IN NORMAL OPEN CONFIGURATION.

SEE NOTE 2

Page 62: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SWITCH ASSEMBLY, 600 AMP,

SOLID BLADE, VERTICALELKINSGUINNHOFFMAN11/29/10

NOTES:

1. SEE DWG. 08.10-18B FOR BILL OF MATERIALS.

FRONT VIEW

0

3

APPR.REVISED BY CK'D

SIDE VIEW

PLAN VIEW

8"

44"

44"

72"

NEUTRAL

5"

28-3/4"

15-1/4"

28-3/4"

15-1/4"

28-3/4"

5

1

3

#6 SD BC

C BOLT HOLE (TYP.)L

1

08.10-18A

DEF

X

DEPDEMDEC

LOOSIER10/29/14

2

4

ADCOCKDANNA

4 LOOSIER3/31/15 ADCOCKWHITE

2. ARRESTERS APPLIED ONLY IN NORMAL OPEN CONFIGURATION.

SEE NOTE 2

6

5 LOOSIER6/17/15 ADCOCKBURLISON

Page 63: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SWITCH BRACKETDETAIL

SWITCH ASSEMBLY, 600 AMP,

SOLID BLADE, VERTICALELKINSGUINNHOFFMAN11/29/10

1. SEE DWG. 08.10-18A FOR DESIGN SPECIFICATIONS.

NOTES:

0

3

APPR.REVISED BY CK'D

BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD,1 /2"X2"NUT, HEX, 1/2 IN, A304, STAINLESS STEELWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304, ALLOY, FOR,1/2"BOLT, MACH, HEX, HD, 1/2"X2"SWITCH, DISCONNECT, SOLID BLADE, 15KV, 600A, 1PH, SWITCHBOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD, 1/2" X 2"NUT, STAINLESS, STEEL, HEX, 304, ALLOY, COARSE, THREADBRACKET, MNTG SWITCH ARSTRWASHER, RD, 1/2, SS, 1.375" OD

ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER PAREQOH10F

BKTLASWBKTSTLF

SW156SBDF

010928012277013128013407152074260136010928012277070283

10542504

2202029220184794

4448212212

11KHLC7933F

4

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

6

3

3

QTYPERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

5 6

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2

BKTSBDSWSTLF3 3

013264013308070282152107

WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/162BRACKET, MNTG WD/CNCR POLE1BOLT, MACH, SQ, NUT, 5/8" X 12"2

CONNECTOR, HOT LINE CLAMP, 795 MCM TO 336 MCM

08.10-18B

DEF

X

DEPDEMDEC

LOOSIER7/16/14 ADCOCKDANNA

2

3

4 LOOSIER3/31/15 ADCOCKWHITE

5 LOOSIER6/17/15 ADCOCKBURLISON

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD4

KLC4H79ALF6 6

109281227713163155464

NUT, HEX, 1/2 IN, A304, STAINLESS STEEL, 304, ALLOY, COARSE4WASHER, FLAT, 1/2 IN, SILICON BRONZE, FLAT, ROUND, SILICON8LUG, COMPRESSION, 4 HOLE, 795, AAC1

10542504 WASHER, ROUND, 1/2, SS, 1.375" OD4

Page 64: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.10-20DWG.

SWITCH ASSEMBLY, 300 AMP, SOLID BLADE

HORIZONTALELKINSGUINNHOFFMAN11/5/100

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW SIDE VIEW

PLAN VIEW

24"

60"

6"

6" TYP.

NOTES:

1. IN LOCATIONS WHERE THE SWITCH COULD BE USED TO TRANSFER LOAD AND COULD BE LEFT IN THEOPEN POSITION FOR AN EXTENDED PERIOD OF TIME, ENGINEERING SHOULD CALL FOR LIGHTNINGARRESTERS ON BOTH SIDES OF THE SWITCH.

6"

KHLC40N6F

KHLC7933FOR

ELKINSBURLISONBURLISON8/31/11

Page 65: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

SWITCH ASSEMBLY, 600 AMP, SOLID BLADE

HORIZONTALELKINSGUINNGUINN8/23/10

FRONT VIEW

#6 SD BC

0

3

2

1

APPR.REVISED BY CK'D

NOTES:

SIDE VIEW

14" 20" 34"14" 14"

10" 20" 18" 38" 10"

72"

1

2

3

3

2

1

1 SW156UHSBDF

BILL OF MATERIALS

CATALOG

BOLT, CARRIAGE, 3/8" X 4-1/2"ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLY

SWITCH, DISCONNECT, SOLID BLADE, 15KV, 600A, SINGLE-PHASE

SWITCH, DISCONNECT, SOLID BLADE, 25KV, 600A, SINGLE-PHASE

DESCRIPTION

SW256UHSBDF260547

AREQOH10F 220202

ARMD8LW36FSF 1

6

3

3

QTY

41

1

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

PLATE, SW BACKING1260136070793

PLATE, SW BACKING070793 1

1. 600 AMP SWITCH IS AVAILABLE FOR 15KV AND 25KV (COASTAL AND HOLOPAW).

011209011313013264013308014114031113071306

BOLT, DOUBLE ARMING, 5/8", 20", STEEL, WITH 4 NUTS3WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.1WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.10SCREW, LAG, 1/2" X 4", STEEL, GALV.2CROSSARM, WOOD, 8', MS-121-F, LIGHT2BRACE, FLAT, GALV, STEEL, 36"4

5"

ADCOCKDANNA5/31/13

4 CONNECTOR, HOT LINE CLAMP, 795 MCM TO 336 MCMKHLC7933F 92201847946 1

4

SEE NOTE 3

2. SEE DWG. 03.11-01B FOR REQUIRED CROSSARM.

3. ARRESTERS APPLIED ONLY IN NORMAL OPEN CONFIGURATION.

ADCOCKWHITELOOSIER3/31/15

08.10-22

DEF

X

DEPDEMDEC

Page 66: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

11/5/10 HOFFMAN GUINN ELKINS

600 AMP INLINE DISCONNECT

REVISED CK'DBY APPR.

1

0

3

2

NOTES:

BLADE STOP PIN

DEAD-ENDINGHOLE

11/16" DIA.PULL-OFF-HOLE

1-1/4" DIA.

PLATED TERMINALPADS

LOADBREAK HOOK

TO FACILITATE CONSTRUCTION, RESTORATION OR REPAIR. WHEN USED FOR THESE PURPOSES, THEY SHOULDBE REMOVED AT THE COMPLETION OF WORK. INLINE SWITCHES MAY BE USED FOR A PERMANENT INSTALLATIONWHEN THE PREFERRED INSTALLATION IS IMPRACTICAL OR IMPOSSIBLE.

1. SEE DWG. 08.10-18A FOR THE PREFERRED 600 AMP SWITCH INSTALLATION. INLINE SWITCHES MAY BE USED

25"

17" 4"4"

15-13/16"

2-3/8"

11/21/11 ROBESON BURLISON ELKINS

1

BILL OF MATERIALS

CATALOG

0000010928

WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT

BOLT, MACHINE, 1/2 IN, 2 IN, SS, 304, HEX HEADNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, HEX

DESCRIPTION

0000012277SW156ILSBDF 00000131281

QTY

444

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

SWITCH, DISCONNECT TEMPWASHER, ROUND, ROUND,FLAT,SS,304,ALLOY,FOR,1/2"0000013407

0000434241 18

2 DEADEND CLAMPDECLMP(WIRE)F -2 13 INSULATOR, DEADEND, POLYMER,25KV,DE,SILICONE, 15KVIDES25PF 00000805772 1

08.10-24

DEF

X

DEPDEMDEC

4 LUG, COMPRESSION, 2 HOLEKLC2H(WIRE)ALF -2 1

23 1

4

9/4/14 LOOSIER DANNA ADCOCK

Page 67: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.10-26DWG.

LINE

LOAD

1/23/13 ROBESON GUINN ADCOCK

VERTICAL TANGENT CROSSING

WITH 600 AMP DISCONNECTS

FRONT VIEW

PLAN VIEW

NEUTRAL

TANGENT CONSTRUCTION

CONFIGURATION MAY VARY.1. THE INTENT OF THIS DRAWING IS TO SHOW PHASE SPACING AND CIRCUIT ARRANGEMENT. PRIMARY SUPPORT

NOTES:

0

2

1

APPR.REVISED BY CK'D

3. SEE SPECIFIC CONFIGURATION DRAWINGS FOR ADDITIONAL DETAILS.

3

5"

28-3/4"

12"

44"

4"

15-1/4"

44"

44" 44"

72"

070282013264152107013308 WASHER, 2-1/4", SQUARE FLAT, 13/16" HOLE

BOLT, MACHINE, SQ, 5/8" X 12"WASHER, SPRING, COIL, FOR 5/8", STL, GALV.BRACKET, MOUNTING WD/CONCRETE POLE

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

SW156SBDF 3

QTY

2

48

441

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

260136 SWITCH, SOLID BLADE 600 AMP012277 NUT, SS, HEX013128 WASHER, ROUND, BELLEVILLE, SPRING010928 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"013407 WASHER, ROUND, FLAT, SS152074 BOLT, MACHINE, HEX HEAD, 1/2" X 2"

BKTSBDSWSTLF22

1

2

3

165288 CONNECTOR, WEDGE, 4-HOLE, 795 AAC13 3KWP4H79F

4"

1

3

2

3/21/13 McCONNELL DANNA ADCOCK

FOR POST INSULATOR INSTALLATIONS ON WOOD POLES WHEN THE POLE DOES NOT HAVE A SLAB GAIN FOR ALL CONDUCTOR SIZES.WHEN THE CONDUCTOR IS 336.4 KCMIL OR LARGER, USE POLE GAIN EVEN IF SLAB GAIN EXISTS. POLE GAINS ARE NOT REQUIRED FOR INSULATORS USED FOR JUMPERS. SLACK SPANS WITH 336 AND

2. POLE GAINS (ISGAINGRIDF FOR 15/25KV INSULATORS OR ISGAINGRID55F FOR 35KV INSULATORS) ARE REQUIRED

795 CONDUCTORS REQUIRE A POLE GAIN.

4/9/13 McCONNELL DANNA ADCOCK

Page 68: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.12-02ADWG.

VLR LOAD CONTROL AND

AUTO TRANSFER CONTROL SWITCHELKINSGUINNHOFFMAN11/29/10

FRONT VIEW

#2 SD BC

35"

48" MIN.

72"

48"

48"

5"

6"

20-1/8"

24"

24"

6"

#6 SD BC

0

2

1

APPR.REVISED BY CK'D

SIDE VIEW

3

#6 SD BC#6 SD BC

120/208VPT SOURCE

2. REFER TO DWG. 08.12-01 FOR WIRING DIAGRAM.

1. ENGINEER MUST SPECIFY JUMPER AND PRIMARY CONNECTOR SIZE.

NOTES:

4. BOND TANK AND FRAME WITH #2 SD BC TO SYSTEM NEUTRAL.

3. SEE DWG. 08.12-02B FOR BILL OF MATERIALS.

13

11

32

1

21

22

14

LASH 200' CT & SWCABLE TO AERIALQUADRUPLEX(COIL EXCESS)

171615 18 19 20

12

4

9

10

87

76 8

ADCOCKDANNA5/24/13

ADCOCKDANNA11/11/13 DANNA

5. WHEN USING AS LOAD CONTROL ON A PRIMARY METERED CUSTOMER, PLACE THE VLR SWITCH ON THE LOAD

SIDE OF THE PRIMARY METERING INSTALLATION.

Page 69: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.12-02BDWG.

VLR LOAD CONTROL AND

AUTO TRANSFER CONTROL SWITCHELKINSGUINNHOFFMAN11/29/100

2

1

APPR.REVISED BY CK'D

3

1. SEE DWG. 08.12-02A FOR DESIGN SPECIFICATIONS.

NOTES:

987

6

5

432

1

BILL OF MATERIALS

CATALOGDESCRIPTION

666

2

4

6

66

1

QTY

1

PERCU

NUMBERMACRO UNIT

SWOVLRFRMFM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

BRACKET, RCLSR 3PH TY 3H E-PWASHER, ROUND, FLAT, 1/2", BOLTWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, 3", SQUARE, CURVED, 13/16", HOLEBOLT, MACHINE, 1/2" X 3-1/2"BOLT, MACH, SQ, NUT, 5/8" X 12"ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLYBRACKET, LA & CO TY ACLAMP, HOT LINE, ALUMINUMBRACKET, FIBERGLASS, STAND-OFF, 20"STUD, LINE POST, 5/8" X 1-3/4"- 3/4 X 1BOLT, MACH, SQ, NUT, 5/8" X 12"WASHER, 3", SQUARE, CURVED, 13/16", HOLEWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.STUD, LINE POST, 5/8" X 14"INSULATOR, POST, TIE TOP, 15/25KV, WITHOUT STUDWIRE, AL, SLD, BR, SDW, #4, TIEWIRECABLE, XLP UG AL 4/0SWITCH, BY-PASS, 3-SLD BLADE DISC, 15KV, LBK HOOKS, 600AWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16", HOLE, GALV.BOLT, MACH, SQ, NUT, 5/8" X 12"BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD, 1/2" X 2"WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, STAINLESS STEEL, 304 ALLOY, FOR 1/2" BOLTNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, COARSE, THREAD, 1ARRESTER, LIGHTNING, SEC 120-240 3 WIRE*RISER, KIT-SCADA CONTROLFUSE, SEC INS 30 AMP

1211

10

11

3

13 1

1222621111122211158122288168111

BKTOSVLREPF

AREQOH10FBKTCOLASTLXARMF

KHLC40N6F

BKTFPIS20F

ISSTUDBOLT5814F

IHPTT15FHTIEN4AACF

RCRISER40ALF

SW156BYPF

AREQSC120FSWOSCADACNTKITF

FUSESEC30F

070467013229013264013346152094152107220202070101

9220184790070430072361152107013346013264013264072368080212200306202111260123013264013308152107010928013128013407012277220139263165230464

19

21

20

1817161514

14

SWITCH, AUTO, XFER FAULT BL

SW154VLRF

SW154VLRFBF 263136

1

1

1

1

11

1

1

1

1

30.211

1

11

1

6

1

53011

-

SWITCH, OIL 15KV 3 RC 400A8CABLE, IS1 VLR SW CNTRL 35CABLE, CONTROL, #10, 2 - CONDUCTORWIRE, AL, SLD, BR, SDW, #4, TIEWIREGUARD, TRANSFORMER, WILDLIFE, ROUND, GRAY MIN. 9"

263138264219192281200306470114

CABLE, IS1 VLR SW CNTRL 35'CABLE, CNTL, TYPE S, 45' SWCABLE, CNTL, TYPE S, 45' CTCABLE, CNTL, TYPE S, 200' CTCABLE, CNTL, TYPE S, 200' SWCABLE, CNTL, TYPE S, 45' FBGUARD, PVC, CABLE, 2-1/4"X10'BANDING, STAINLESS STEEL, 316, SS, 3/4", WIDE, .030, THBANDING, BUCKLE, SS, 3/4", FOR BANDING

-

264219264210264208264211264212264209323422434122434142

22 CONTROL, OILSW TYPE S 3PHSWOHASTCNTLSF 2642071 1

SWOS1CAB35FSWOS1CAB45SWFSWOS1CAB45CTFSWOS1CAB200CTFSWOS1CAB200SWFSWOS1CAB45FBF

CRIS1UGPVC225CF-

-

VLR VERTICAL FRAMING - ORDER SWITCH, CONTROL AND CABLES SEPARATELY

VLR SWITCH USED FOR LOAD CONTROL - SWITCH AND CONTROL CABLE

VLR SWITCH USED FOR AUTO SOURCE TRANSFER SCHEME - SWITCH ONLY - ORDER CABLES SEPARATELY

TYPE S CONTROL - SPECIAL ORDER

2. SEE DWG. 08.13-05 FOR AUTO TRANSFER WIRING DETAIL.

ADCOCKDANNA5/24/13

Page 70: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

VERSAVAC LOAD CONTROLADCOCKBURLISONDANNA5/1/150

2

1

APPR.REVISED BY CK'D

3

2. REFER TO DWG. 08.12-04C FOR WIRING DIAGRAM.

1. ENGINEER MUST SPECIFY JUMPER AND PRIMARY CONNECTOR SIZE.

NOTES:

4. BOND TANK AND FRAME WITH #2 SD BC TO SYSTEM NEUTRAL.

3. SEE DWG. 08.12-04B FOR BILL OF MATERIALS.

5. ON A PRIMARY METERED CUSTOMER, PLACE THE VERSAVAC SWITCH ON THE LOAD SIDE

OF THE PRIMARY METERING INSTALLATION.

08.12-04A

DEF

X

DEPDEMDEC

FRONT VIEW

#2 SD BC

42"

48" MIN.

72"

48"

48"

5"

6"

20-1/8"

24"

24"

6"

#6 SD BC

SIDE VIEW

9

8

1

9

6

7

54

11

43 5

2

24"

6"

4"

Page 71: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

VERSAVAC LOAD CONTROLADCOCKBURLISONDANNA5/1/150

2

1

APPR.REVISED BY CK'D

3

1. SEE DWG. 08.12-04A FOR DESIGN SPECIFICATIONS.

NOTES:

654

3

2

1

BILL OF MATERIALS

ITEMDESCRIPTION

644

8

4

1

QTY

1

PERCU

NUMBERMACRO UNIT

SWOVLRFRMFM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

BRACKET, VERSAVAC, 3PH TY 3H E-P

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.STUD, LINE POST, 5/8" X 14"

CABLE, XLP UG AL 4/0SWITCH, BY-PASS, 3-SLD BLADE DISC, 15KV, LBK HOOKS, 600AWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.WASHER, SQUARE, 2-1/4", FLAT, 13/16", HOLE, GALV.BOLT, MACH, SQ, NUT, 5/8" X 12"BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD, 1/2" X 2"WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, STAINLESS STEEL, 304 ALLOY, FOR 1/2" BOLTNUT, HEX, 1/2 IN, A304, STAINLESS STEEL, COARSE, THREAD, 1ARRESTER, LIGHTNING, SEC 120-240 3 WIRE*RISER, KIT-SCADA CONTROLFUSE, SEC INS 30 AMP

98

7

11

3

10 1

11158122288168111

BKTFBFGPIN15138F

ISSTUDBOLT5814F

IPIN25PFTTIEF500COVALPF

RCRISER40ALF

SW156BYPF

AREQSC120FSWOSCADACNTKITF

FUSESEC30F

9220278631

013264072368

202111260123013264013308152107010928013128013407012277220139263165230464

11 SW152VVACF 1

653011

-

SWITCH, VACUUM, 15KV 200ACABLE, IS1 VLR SW CNTRL 35CABLE, CONTROL, #10, 2 - CONDUCTORWIRE, TIE, #4 ALUMINUM, SLDGUARD, TRANSFORMER, WILDLIFE, ROUND, GRAY MIN. 9"

9220278629264219192281

0011060100470114

VERSAVAC SWITCH USED FOR LOAD CONTROL - SWITCH AND CONTROL CABLE

08.12-04B

DEF

X

DEPDEMDEC

INSULATOR, 25 KV POLYMER, 1-3/8" THREADPLASTIC TIE WRAP FOR 2-7/8" F-NECK INSULATOR

92200910189220068094

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING, DOUBLE COIL, F013264 2WASHER,3", SQUARE, CURVED, 13/16", HOLE013346 2BOLT, MACH, SQ, NUT, 5/8" X 12"152107 2BRACKET, FIBERGLASS STAND-OFF, 1-3/8" THREAD9220087868 1

ARRESTER, LIGHTNING, 10KV, HD MOV12 6 1AREQOH10F 220202CLAMP, HOT LINE, ALUM, SMALL, 4/013 6 1KHLC40N6F 9220184790

LOOSIER12/2/15

BKTLCVVACEPF

VLR SWITCH - FOR REMOVAL ONLY

-- SWITCH, OH, 15KV, 400A, COOPER VLR, LD BRKSW154VLRF 2631381 1- SWITCH, OH, 15KV, 400A, COOPER VLR, W/FAULT BLOCK, LD BRKSWOHASTCNTLAKF 2631361 1

ADCOCKBURLISON

Page 72: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

TERMINAL WIRE FUNCTION

120V BLACK

N WHITE

1 GREEN

G WHITE

2 RED

3 BLACK

NEUTRAL FROM SOURCE

TIP

CLOSE

NEUTRAL TO SWITCH

POWER TO SWITCH

120V FROM SOURCE

SECONDARY ARRESTER

BLA

CK

WH

ITE

120V

GREEN

WHITE

RED

BLACK

GREEN

WH

ITE

RED

BLA

CK

0 1 G 2 3 4

VLRSWITCH

6 PINPLUG

SECONDARY INDICATING FUSE

SECONDARYSERVICE

TWO WIRECABLE

GREEN

BLACK

RED

WHITE

3

2

G

N

1

TERMINAL STRIP INRADIO SWITCHALTERNATE CONSTRUCTION

TERMINAL STRIP IN VLRSWITCH CONTROL CABINET

CONNECTION DIAGRAM FOR

VERSAVAC SWITCH

120V

N

ADCOCKBURLISONDANNA5/1/15

FOURWIRECABLE

0

3

2

1

APPR.REVISED BY CK'D 08.12-04C

DEF

X

DEPDEMDEC

Page 73: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

LOAD CONTROL SWITCH

600 AMPADCOCKBURLISONLOOSIER8/27/15

NOTES:

1. SEE DWG. 08.12-06B FOR PLAN VIEW, NOTES AND

0

3

2

1

APPR.REVISED BY CK'D 08.12-06A

DEF

X

DEPDEMDEC

FRONT VIEW

SIDE VIEW

9"

40"

72"

1

#6 SD BC

C BOLT HOLEL

40"

5"

117-7/8"

5

3

4

8

48" MIN.

BILL OF MATERIALS.

7

2

5"

(TYP.)

9

10

4"

LOOSIER1/26/16 ADCOCKBURLISON

Page 74: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

LOAD CONTROL SWITCH

600 AMPADCOCKBURLISONLOOSIER8/27/15

NOTES:

1. SEE DWG. 08.12-06A FOR DESIGN SPECIFICATIONS.

0

3

2

1

APPR.REVISED BY CK'D 08.12-06B

DEF

X

DEPDEMDEC

876

5

43

2

1

BILL OF MATERIALS

ITEM

9220270022

CABLE GRIP, SINGLE EYE

#6 CU GND#6 DPX 600V SL CABLE

1" X 10 FT U GUARDSCREW, LAG, 1/2" X 2"LUG, COMPRESSION, 2H - 795 ALBOLT, MACHINE, SQ NUT, 5/8" X 12"

SWITCH, OVERHEAD, 15KV 1200A, 3PH, ALDUTI-RUPTER, FBGLASS

SWITCH, CONTROL, OPERATOR, ALDUTI-RUPTER SWITCH, KIRK KEY

DESCRIPTION

9220269976

- 152107- 155331

CRIS1UGPVC10WF014111323421

CABGRP1X125F 320452WUSNGDPXRF 202107

- -

1

-1

15

--

1

1

ITEM

1

-30

151

62

1

1

QTY/CU

NUMBERMACRO UNIT

-

BUBBLENUMBER

COMPATIBLEUNIT

CUQTY

2. JUMPERS SHALL MATCH CONDUCTOR SIZE.

3. USE AS A LOAD CONTROL SWITCH WHERE A KIRK KEY SYSTEM IS IN PLACE.

4. PLACE SWITCH ON LOAD SIDE OF PRIMARY METERED CUSTOMERS.

PLAN VIEW(CONTROL OPERATOR REMOVED FOR CLARITY)

4

1

9

BOLT, MACHINE, STAINLESS, STEEL, HEX, HEAD,1 /2"X2"NUT, HEX, 1/2 IN, A304, STAINLESS STEELWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTWASHER, ROUND, FLAT, STAINLESS STEEL, 304, ALLOY, FOR,1/2"BOLT, MACH, HEX, HD, 1/2"X2"SWITCH, DISCONNECT, SOLID BLADE, 15KV, 600A, 1PH, SWITCH

SW156SBDF

010928012277013128013407152074260136

444821

9 3

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2

BKTSBDSWSTLF10 3

013264013308070282152107

WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/162BRACKET, MNTG WD/CNCR POLE1BOLT, MACH, SQ, NUT, 5/8" X 12"2

10

5. FOR SWITCH OPERATOR WITHOUT KIRK KEY, USE ITEM # 9220279778.

LOOSIER12/2/15

2

SWITCH, CONTROL, OPERATOR, ADULTI-RUPTER, W/O KIRK KEY9220279778

1

1

WASHER, 2-1/4",SQUARE,FLAT,11/16",HOLE13307 2SWOHASTCNTLAF

SWOHASTCNTLAKF

SW2512ALDF

BOLT, MACHINE, SQ NUT, 5/8" X 12"152107 2

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2013264

WASHER, 2-1/4",SQUARE,FLAT,11/16",HOLE13307 2BOLT, MACHINE, SQ NUT, 5/8" X 12"152107 2

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2013264

WASHER, 2-1/4",SQUARE,FLAT,11/16",HOLE13307 2BOLT, MACHINE, SQ NUT, 5/8" X 12"152107 2

WASHER, SPRING, COIL, STEEL, 5/8", BOLT, GALV2013264

ADCOCKBURLISON

Page 75: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.13-01DWG.

TYPE"S"

CONTROL

TAP CUSTOMERTO THIS POLE

400A VLR SWITCH

120/208V

NSW CT CT SW

PT

PT

OVERHEAD AUTOMATIC TRANSFER SCHEME

AN OVERHEAD AUTOMATIC TRANSFER SCHEME IS SHOWN IN THE ABOVE DRAWING. A MINIMUM OF FIVE POLES ARE REQUIRED FOR THE INSTALLATION. THE TWO OUTSIDE POLES EACH HAVE A THREE-PHASE WYE-WYE 120/208V TRANSFORMER STATION. THESE STATIONS ARE CONSTRUCTED WITH SMALL KVA TRANSFERS ANDARE CONNECTED TO A SMALL QUADRUPLEX CABLE WHICH RUNS TO THE NEUTRAL POSITION OF THE POLE WITHTHE TYPE "S" AUTOMATIC TRANSFER CONTROL. THE QUADRUPLEX CABLE IS OPENED AT THIS POLE AND SPLICEDTO THE TWO 45' PT CABLES WHICH CONNECT TO THE TYPE "S" CONTROL. THE 45' CT AND 45' SW CABLES ARE CONNECTED TO THE 400A VLR SWITCH ON THE SAME POLE AS THE TYPE "S" CONTROL. THE 200' CT AND THE 200' SW CABLE ARE INSTALLED UP THE POLE WITH THE TYPE "S" CONTROL AND THEN LASHED TO THE QUADRUPLEX CABLE GOING TO THE OTHER 400A VLR SWITCH. THE LOAD IS CONNECTED TO THE CIRCUIT BETWEEN THE TWO VLR SWITCHES. THE TRANSFER SWITCHES WILL MAKE AN OPEN TRANSFER (OPEN & THEN CLOSE) UPON LOSS OF ONE OR MORE PHASE VOLTAGES (THREE-PHASE SENSING) ON THE PREFERRED SOURCEPROVIDED THE FAULT IS NOT ON THE TRANSFERRED CIRCUIT (FAULT BLOCK FEATURE). EITHER SOURCE CAN BECHOSEN AS THE PREFERRED SOURCE FROM THE CONTROL SELECTIONS. THE RETRANSFER TIME AND OPEN ORCLOSE TRANSITION IS SELECTABLE. IT IS ALSO POSSIBLE TO SELECT NO PREFERRED SOURCE IN WHICH CASENO RETRANSFER OCCURS.

ELKINSGUINNHOFFMAN8/25/10

R

0

3

2

1

APPR.REVISED BY CK'D

120/208V

PRIMARY

SECONDARY

Page 76: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.13-03DWG.

VLR TYPE S TRANSFER CONTROLELKINSGUINNGUINN9/7/10

R

0

2

1

APPR.REVISED BY CK'D

3

22-5/32"

12-13/16"

11"

13-1/2"

8"

16"

1-1/2"

17-7/8"

20-1/8"

LAMP TEST SWITCH (S6)

SWITCH I OPEN ANDCLOSED LAMPS

PREFERRED-TO-ALTERNATE TIMER

OPERATION SELECTORSWITCH (S3)

SOURCE I ENERGIZEDLAMP

SOURCE-PREFERENCEAND RETURN MODESELECTOR SWITCH (S4)

LOCKING TAB

STOP SCREW

INSTRUCTION TAG

FUSES

CONTROL MODE SWITCH (S5)

MANUAL OPERATION SOURCE I AND SOURCE IISWITCHES (S1, S2)

SOURCE II ENERGIZEDLAMP

ALTERNATE-TO-PREFERRED TIMER

SWITCH II OPEN ANDCLOSED LAMPS

LATCH RELAY STATUSTEST TERMINALS (T-1, T-2,T-3)

(2) MTG HOLES FOR5/8" MAX BOLT DIA.

5/8" HOLE PROVIDEDFOR CUSTOMER LOCK

GROUNDING TERMINAL LUG(14 TO 4 STRANDED)

5-1/4"

2-1/2" 2-1/2"3"

2-1/2"2-1/2"

STD CONTROL

CONTROL WITH FAULT BLOCK

Page 77: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.13-05DWG.

CTPTSWSWPTCT

SOURCE IISOURCE I

DETAIL "A"

AUTOMATIC TRANSFER SWITCH ASSEMBLY, (VLR),

CONTROL WIRING DETAILELKINSGUINNGUINN11/29/10

R

0

1

APPR.REVISED BY CK'D

NOTES:

1. SEE DWG. 08.13-01 FOR OVERVIEW OF ENTIRE OVERHEAD AUTOMATIC TRANSFER SCHEME.

2. SEE DWG. 08.12-02B FOR BILL OF MATERIALS.

FRONT VIEW SIDE VIEW

2

SEE DETAIL 'A'

4. THE OTHER POLE IN TRANSFER SCHEME WILL BE IDENTICAL, EXCEPT NO S TRANSFER CONTROL.

3

#2 SD BC

35"

72"

48"

48"

5"

6"

24"

24"

6"

CØBØ

#6 SD BC

#6 SD BC

#6 SD BC

LASH 200' CT & SWCABLE TO AERIALQUADRUPLEX(COIL EXCESS)

PT SOURCE I120/208V

3. BOND TANK AND FRAME WITH #2 SD BC TO SYSTEM NEUTRAL.

48" MIN.48" MIN.

PT SOURCE II120/208V

Page 78: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.13-08ADWG.

SCADA MATE CX SWITCH

STANDARD MOUNTING ARRANGEMENTELKINSGUINNHOFFMAN11/29/100

3

2

1

APPR.REVISED BY CK'D

10"

64"

42"

42"

5"11"

72"

12"

SIDE VIEWFRONT VIEW(LOOKING FROM LOAD SIDE)

SOURCE LOAD

30"

4' ABOVEGROUND

FOR CONTROL31'-8" MAX.

CABLE

#6 SD BC 4

12

35"

2

1

9

NOTES:

10"

4"SEE NOTE 1

1. ROTATE B PHASE STANDOFF AS NECESSARY TO CLEAR THE CONTROL BOX.

2. SEE DWG. 08.13-08B FOR PLAN VIEW.

11

#2 SD BC

19

13 14

3. SEE DWG. 08.13-08C FOR BILL OF MATERIALS.

ADCOCKDANNA5/24/13

Page 79: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-08B11/29/10 HOFFMAN GUINN ELKINS

SCADA MATE CX SWITCH

STANDARD MOUNTING ARRANGEMENT

NOTES:

1. SEE DWG. 08.13-08A FOR DESIGN SPECIFICATIONS.

PLAN VIEW

34-3/8"

23-1/16"

SOURCE LOAD

3

15 8

0

1

APPR.REVISED BY CK'D

2

3

2. SEE DWG. 08.13-08C FOR BILL OF MATERIALS.

5/24/13 DANNA ADCOCK

Page 80: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-08C11/29/10 HOFFMAN GUINN ELKINS

SCADA MATE CX SWITCH

STANDARD MOUNTING ARRANGEMENT

NOTES:

2. SEE DWGS. 08.13-08A AND 08.13-08B FOR DESIGN SPECIFICATIONS.

0

1

APPR.REVISED BY CK'D

2

3

12

5

1

LUG, COMP 2H-795AL1

1 TAPE, ELECTRICAL, ELEC, 3/4X66'X.007

2 WASHER, ROUND, RD, 1/2, SS, 1.375" OD

013265

1

2

2

1

46

BOLT, MACH, SQ, NUT, 5/8"X12"

BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNCWASHER, ROUND, FLAT, STAINLESS STEEL, 304, ALLOY, FOR 1/2"

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.

WASHER, SPRING, COIL, STEEL, FOR 3/4" BOLT

15

462

WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.

WASHER, SPRING, COIL, STEEL, FOR 3/4" BOLTWASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.

DESCRIPTION

SW15S6VRTSATSF

013308

152107

SW15S9VRTSATSF152123011708013128

152122

KLC2H79ALF155331

10542504

SWOSANTKITF 390122

SWOSANTBRKF

013264 2 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.

6

152123 2 BOLT, SQUAREHEAD, 3/4 IN, 14 IN, S, A307, GALV., 10, UNCBOLT, 5/8 IN, 10 IN, STEEL, GALV., OVAL EYE3011708

013407

AREQSC120F434142 BANDING, BUCKLE, SS, 3/4", FOR BANDING3

WOCN6CU1CF 190204 1 WIRE, COPPER, #6, HARD DRAWN, BR9220109491 1 KIT, ANTENNA, UTILI-NET

402179 COMPOUND, INSUL, SEAL, PAD, 3-3/4"1

013308 WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.152106 BOLT, MACHINE, 5/8 IN, 10 IN, STEEL, A-ASTM A307, GALV., MACH, 240306 BRACKET, STREET LIGHT, 6 ',W/30", RISE, GALV-STL 013264 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.

22

11

WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT1013128WASHER, ROUND, FLAT, STAINLESS STEEL, 304, ALLOY, FOR 1/2"1013407BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNC2152122

266178 1 SWITCH, SCADAMATE UPRIGHT MTG

152122 2 BOLT, SQUAREHEAD, 3/4 IN, 12 IN, S, A307, GLV, 10, UNC19220179952 SWITCH, VRT, AUTO, 14.4KV, 630A, SCADA-MATE CX21013264

1

10

21

CATALOGNUMBER

MACRO UNIT

-

QTYPERCU

1

1

1

QTYREQ'D

12

6

1

1

COMPATIBLE UNIT

2WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.

013265

BOLT, MACH, SQ, NUT, 5/8"X12"BOLT, SQUAREHEAD, 3/4 IN, 14 IN, S, A307, GLAV., 10, UNCBOLT, EYE, 5/8 IN, 10 IN, STEEL, GALV., OVAL EYEWASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLT

013308013264152107

211523

CLAMP, HOT LINE, ALUMINUM, EXTRA LARGE 795121418 TIE, TOP F NECK 795 AL

11

WASHER, 3", SQUARE, CURVED, 13/16" HOLE013346 2

260123 SWITCH, BY-PASS, SWITCH, BYPASS, 3-SLD BLADE DISC, 15KV, LBK H220202 ARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE RUBBER POLY323422 GUARD, PVC, CABLE, 2-1/4"X10'434122 BANDING, STAINLESS STEEL, 316, SS, 3/4", WIDE, .030, TH

111

0.2

ARRESTER, LIGHTNING, SEC 120-240 3 WIREBOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2"X2"NUT, 1/2 IN, A304, STAINLESS STEEL, HEX HEADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLT

220139010928012277013163

1224

CUITEMNO

BOLT, MACH, SQ, NUT, 5/8"X12"

SW156BYPF

013264 2 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.

2 32 WASHER, SQUARE, 2-1/4", SQUARE, FLAT, 13/16" HOLE, GALV.

152107013308

AREQOH10F3 6

4 CRIS1UGPVC225CF 2

LUG, COMP 4HOLE 795 AAC12 WASHER, ROUND, 1/2, SS, 1.375" OD

KLC4H79ALF155464

10542504

7 6

BOLT, MACHINE, STAINLESS STEEL, HEX HEAD, 1/2"X2"NUT, HEX, 1/2 IN, A304, STAINLESS STEELWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLT

010928012277013163

224

9220184794TTIEF795ALF9 6KHLC7933F8 6

13 BKTFPIS20F 3 BRACKET, FIBERGLASS, STAND-OFF, 20"070430 1STUD, LINE POST, 5/8"X1-3/4", INSULATOR STUD072361 1BOLT, MACH, SQ, NUT, 5/8"X12"152107 2

IHPTT15F 080212 1 INSULATOR, POST, TIE, TOP, 15/25KV, WITHOUT STUD14 3IDES25PF 080577 1 INSULATOR, DEADEND, POLYMER, 25KV, SILICONE, RATED 15K15 12

ISEYEBOLT5810F011708 1 BOLT, EYE, 5/8 IN, 10 IN, STEEL, GALV, OVAL EYE

16 61 WASHER, 3", SQUARE, CURVED, 13/16",HOLE013346

DECLMP795AACF 101125 1 CLAMP, DE, SO, 336.4-954 ACSR, 397.5-1000 AL, COND RANGE17 6WOP795AACF 200238 1 WIRE, AAC, AAC 37STR 795 66 REE18 60

19 SWOS5201CTRF

9220109490 1 SWITCH, CTRL, AUTOMATED, INTELLI-TEAM-II013264 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.013308 WASHER, SQUARE, 2-1/4", FLAT, 13/16" HOLE, GALV.152107 BOLT, MACH, SQ, NUT, 5/8"X12"

112

1

1. CHOOSE EITHER THE 900A OR 600A SCADA-MATE VERTICAL LOAD BREAK SWITCH.

(SEE NOTE 1)

(SEE NOTE 1)

BILL OF MATERIALS

5/24/13 DANNA ADCOCK

Page 81: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-10D8/11/10 GUINN GUINN ELKINS

OMNI-RUPTER SWITCH

CONTROL FACEPLATER

NOTES:

1. TO EXTEND BATTERY CARRYOVER TIME, THE SWITCH TURNS OFF POWER TO THE LEDS AND LCD ON THE FACEPLATE WHEN THECONTROL CABINET DOOR IS CLOSED.

OVERCURRENT FAULT - COMES ON WHEN A, B OR C PHASE HAS AN OVERCURRENT CONDITION.

A. IF OMNI-RUPTER IS CLOSED, LED TURNS OFF WHEN THREE-PHASE LINE VOLTAGE IS SENSED AND AFTER 45 MINUTES.B. IF OMNI-RUPTER SWITCH IS OPEN, LED TURNS OFF WHEN THE SWITCH IS CLOSED AND REMOTE/LOCAL IS TOGGLED MANUALLY

OR VIA SCADA.C. IF OMNI-RUPTER SWITCH IS NORMALLY OPEN, LED TURNS OFF WHEN REMOTE/LOCAL IS TOGGLED MANUALLY OR VIA SCADA OR

WHEN THE SWITCH IS CLOSED.

REMOTE COMMUNICATIONS RCV/XMIT - BLINK WHEN COMMUNICATION SIGNALS ARE RECEIVED OR SENT.ERROR DETECTED - COMES ON FOR ANY OF THE FOLLOWING CONDITIONS:

A. BATTERY CHARGER OVER-VOLTAGE.B. OPEN/CLOSE CONTACTS ARE BOTH OPEN OR BOTH CLOSED.C. TEMPERATURE SENSOR FAILURE.D. SWITCH ERROR SUCH AS BYPASS SWITCHES OPEN AND OMNI-RUPTER SWITCH IS BYPASSED.

PROCESSOR STATUS - BLINKS ONCE PER SECOND WHEN CONTROL HAS POWER AND SOFTWARE IS RUNNING NORMALLY.

BATTERY LOW - OFF WHEN BATTERY CHARGER WORKING NORMAL. ON WHEN BATTERY VOLTAGE DROPS BELOW A PRESET LIMIT. IF ON WITH AC POWER ON TO CONTROL, BATTERY MAY BE DEFECTIVE. BLINKS DURING ANY BATTERY TEST.

LEDS

0

3

2

1

APPR.REVISED BY CK'D

Page 82: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-10E11/29/10 HOFFMAN GUINN ELKINS

ANTENNA INSTALLATION

FOR VERTICAL OMNI-RUPTER SWITCHR

NOTES:

1. SEE DWG. 08.13-10A FOR DESIGN SPECIFICATIONS.

1. SCREW THE ANTENNA COAX CONNECTOR TOGETHER SO THAT IT IS TIGHT.

2. WRAP ELECTRICAL TAPE AROUND THE COAX CONNECTOR COVERING ONE INCH EITHER SIDE OF THE CONNECTION.

HOW TO WATERPROOF THE ANTENNA COAX CONNECTION:

AROUND TO WATERPROOF THE CONNECTION.

4. WRAP ELECTRICAL TAPE AROUND THE AQUA SEAL WATERPROOFING PAD TO COVER THE ENTIRE AREA OF AQUASEAL PLUS ONE INCH ABOVE AND BELOW THE SEAL.

3. PLACE THE AQUA SEAL PAD ( CN 402179) SQUARELY OVER THE COAX CONNECTION AND WRAP IT SECURELY

COAX CONNECTIONAREA MUST BEWATERPROOF

2. SEE DWG. 08.13-10C FOR BILL OF MATERIALS.

0

3

2

1

APPR.REVISED BY CK'D

Page 83: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.04-06DWG.

TANGENT TO DEADEND

DEADEND TO DEADEND

VERTICAL CONSTRUCTION TOVERTICAL CONSTRUCTION

WITH OIL SECTIONALIZER (FMO)ELKINSGUINNHOFFMAN10/13/10

FRONT VIEW

R

SIDE VIEW

GUY

ATTA

CHM

ENT

NEUTRAL

FRONT VIEW SIDE VIEW

5"

12"

36"

36"

72"

4"

18"

18"

18"

4" TYP.

0

2

1

APPR.REVISED BY CK'D

2"

18"

2"

2"

18"

2"

18"

2"

2"

36"

36"

72"

4"

#6 SD BC

1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

NOTES:

#2 SD BC

#6 SD BC

#2 SD BC

#2 SD BC TANK GROUND TOSYSTEM NEUTRAL

#6 SD BC

#6 SD BC

#2 SD BC

#2 SD BC TANK GROUNDTO SYSTEMNEUTRAL

4"

4"

2"

2"

3

2"

Page 84: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.04-08DWG.

NEUTRAL

1

2

SECTIONALIZER ASSEMBLY,

OIL TYPE, VERTICAL (FMO)ELKINSGUINNHOFFMAN10/13/10

FRONT VIEW SIDE VIEW

R

SECTIONALIZERCABLE, 600V #6 SOLID SD CU

BRACKET, LA AND CO TY A

220202

-070101

AREQOH10FARRESTER, LIGHTNING, 10KV HD MOV W/SILICONE

O

2

1

APPR.REVISED BY CK'D

1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

NOTES:

32

1

BILL OF MATERIALS

CATALOGDESCRIPTION

21

2

QTY

1121

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

3

#6 SD BC

SECT_BKTCOLASTLXARMF

193511

30"

#6 SD BC

2. ARRESTERS TO BE MOUNTED ON SOURCE AND LOAD SIDE.

8"

3

#6 SD BC

Page 85: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.04-12DWG.

DEADEND TO DEADEND

TANGENT TO DEADEND

BOND CASE GROUNDWITH CONNECTORSUPPLIED ON BRACKET

HORIZONTAL CONSTRUCTION TOHORIZONTAL CONSTRUCTION

WITH OIL SECTIONALIZER (FMO)

LOAD

SOURCE

LOAD

ELKINSGUINNHOFFMAN10/13/10

SIDE VIEW FRONT VIEW

R

0

3

2

1

APPR.REVISED BY CK'D

#6 SD BC

NOTES:

1. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

#6 SD BC

#2 SD BC

#2 SD BC

#6 SD BC

#2 SD BC

#2 SD BC

2. RUN #2 SD BC UNDER CROSSARM TO B0ND SECTIONALIZERS TO SYSTEM NEUTRAL.

#2 SD BC

72"

6"

2"

10"24" 20"

6" 10"

6"10"

2"

14" 23"

9"

16"34"

4"

6" 12"18" 22"

14"12" 12"

4" 16" 4"

6"8"

10"4"

72"

SIDE VIEW FRONT VIEW

Page 86: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

LOAD

NOTES:

1. ISSUE RECLOSER SEPARATELY. RECLOSER WILL COME ARRESTERS PRE-MOUNTED.

RECLOSER ASSEMBLY,

HORIZONTAL CONSTRUCTION (FMO)

2. SEE DWG. 08.01-11 FOR CUTOUT MOUNTING DETAILS

0

3

2

1

APPR.REVISED BY CK'D

SEE NOTE 3

#6 SD BC

3. EQUIPMENT CASE GROUND TO NEUTRAL TO BE #2 SD BC.

SOURCE

4. SEE DWG. 08.05-17B FOR BILL OF MATERIALS AND DETAILS ON ALUMINUM CROSSARM.

NEUTRAL

#2 SD BC

1

2

3

4

5

FRONT VIEW SIDE VIEW

24"

33"

27"

6"

5. FOR TWO-PHASE HORIZONTAL INSTALLATIONS, ONLY INSTALL RECLOSERS AND SWITCHES ON OUTSIDE TWOPHASES.

FUSESSTORED WITHBARRELS DOWNON 3" STAPLE

HOFFMAN10/6/10 ELKINSGUINN

SALAS8/7/14

#2 WP COPPERCU RCRISERN2CUF

ADCOCKGUINN

08.05-17A

DEF

X

DEPDEMDECLOOSIER11/17/15 ADCOCKBURLISON

LOOSIER1/6/16 ADCOCKBURLISON

Page 87: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

RECLOSER ASSEMBLY,

HORIZONTAL CONSTRUCTION (FMO)ELKINSGUINNHOFFMAN10/6/100

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW

1

5

3

4

3

2

1 BKTCOLA8AALF

BILL OF MATERIALS

ITEM

9220205263

CLAMP, HOT LINE, ALUMINUM, SMALL

BRACKET, CUTOUT, BYPASS CUTOUT, 9 POSITION, AL, 97-1/2"

CUTOUT, LB, 15KV, 100A, 16KA, 110KV BIL

DESCRIPTION

FUSE15CO100F

SW153COSBDF

KHLC40N6F 92201847906

6

3

1

QTY

1

11

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

100349081054010210544005

222

BOLT, MCH, SQ, GLV, 5/8" X 12"WASHER, SQ., RB, CRV, 3" X 3"WASHER, LK, 5/8", COIL, DBL, GLV.

221112

NOTES:

1. SEE DWG. 08.05-17A FOR DESIGN SPECIFICATIONS AND NOTES.

2

5 CABLE, 600V, #2 SD CU, 7 STR. RCRISERN2CUF 1935133 1

3Ø2Ø

QTYREQ'D

4

4

2

1

2

BLADE, SOLID, CUTOUT, 15KV, 300A1269046CUTOUT, LB, 15KV, 100A, 16KA, 110KV BIL221112

08.05-17B

DEF

X

DEPDEMDEC

ADCOCKBURLISONLOOSIER1/6/16

Page 88: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.06-12DWG.

NOTES:

1. CONTROL BOX AND SECONDARY REQUIRED FOR ELECTRONIC RECLOSER ONLY.

2. ISSUE RECLOSER AND ELECTRONIC CONTROL SEPARATELY.

3. RECLOSER MAY BE REVERSED IN HANGER TO ACCOMMODATE SOURCE AND LOAD POSITION.

RECLOSER ASSEMBLY, THREE-PHASE,

HORIZONTAL, 600 AMP SWITCH (FMO)ELKINSGUINNHOFFMAN10/11/10

FRONT VIEW SIDE VIEW

R

0

3

2

1

APPR.REVISED BY CK'D

4. SEE SECTION 01 FOR ADDITIONAL GROUNDING DETAILS.

#2 SD BC BONDTANK AND FRAMETO SYSTEM NEUTRAL

60"

44"

12"

12"

12"

NEUTRAL

SECONDARY

SECONDARY

10" 20" 18" 38" 10"

#6 SD BC

42"

#6 SD BC

5"

Page 89: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

08.12-06DWG.

LOAD CONTROL SWITCH ASSEMBLY, (VLR),THREE-PHASE

HORIZONTAL WITH 600 AMP BYPASS (FMO)ELKINSGUINNHOFFMAN11/29/10

R

0

2

1

APPR.REVISED BY CK'D

3

NOTES:

1. ENGINEER MUST SPECIFY JUMPER AND PRIMARY CONNECTOR SIZE.

3. RADIO SWITCH MUST BE SET FOR PURCHASE BY INSTALLING JUMPER PINS AS SPECIFIED IN CONTROL BOX.

NEUTRAL

SEE NOTES 2 & 3

10"

2. REFER TO DWG. 08.12-01 FOR WIRING DIAGRAM.

10"18"20" 38"

55"

SIDE VIEW FRONT VIEW

Page 90: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

OMNI-RUPTER SWITCH

STANDARD MOUNTING ARRANGEMENT (FMO)

RADIUS ON CABLE4' ABOVE

30"

FOR CONTROL31'-8" MAX.

NOTES:

1. SEE DWG. 08.13-10B FOR PLAN VIEW AND BILL OF MATERIALS. SEE DWG. 08.13-10C FOR OPTIONAL CONSTRUCTION BILL OF

SIDE VIEW

CABLE

#6 SD BC

GROUND

9" MINIMUM

29-1/8"

34"

43"

41"

5"

6"

5"

72"

6"

26"

26"

11"

97"

18-3/4"

21"

42"

42"

13

4

3

1

2

14

3. SEE DWG. 08.13-10E FOR ANTENNA INSTALLATION.2. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE.

MATERIALS AND ADDITIONAL NOTES.

FRONT VIEW

PULL-RINGMANUAL OPEN

OPEN POSITION

LOCKOUT/TAGOUTBRACKET FOR SWITCH

SOURCE

97"

BRACKETSMOUNTING

SURGEARRESTER

34"

26"

26"

LOAD 6

5

15

7

(LOOKING FROM LOAD SIDE)

GROUND CONNECTIONS MUST BE VERY SECURE, ESPECIALLY THE #2 BC CONNECTION AT THE BASE OF THE

4. ARRESTERS SHOULD BE INSTALLED ON MOUNTING PADS PROVIDED ON BOTH SIDES OF THE OMNI-RUPTER SWITCH. THE ARRESTERSOURCE LEAD SHOULD BE CONNECTED TO THE 795 JUMPER JUST BEYOND THE OMNI-RUPTER 2-HOLE HIGH-VOLTAGE TERMINAL ONEITHER SIDE OF THE OMN-RUPTER SWITCH TO KEEP THE LEADS AS SHORT AS POSSIBLE. THE GROUND LEAD SHOULD BE RUN FROMTHE GROUNDING CONNECTION ON THE ARRESTER INTERRUPTER TO THE OMNI-RUPTER SUPPORT FRAME. THIS LEAD MUST BE LONG ENOUGH FOR THE INTERRUPTER TO OPERATE, BUT SHORT ENOUGH TO CLEAR ADJACENT CONDUCTORS. ALL

0

APPR.REVISED BY CK'D

1

#2 SD BC

#6 SD BC

2

3

11/29/10 HOFFMAN ELKINSGUINN

25

5/24/13 ADCOCKDANNA

08.13-10A

DEF

X

DEPDEMDEC8/5/14 EANES ADCOCKEANES

OMNI-RUPTER SWITCH.

Page 91: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-10B11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH

STANDARD MOUNTING ARRANGEMENT (FMO)

NOTES:

1. SEE DWG. 08.13-10A FOR DESIGN SPECIFICATIONS AND DWG. 08.13-10C FOR OPTIONAL OPERATION/

PLAN VIEW

34-3/8"

23-1/16"

SOURCE LOAD

INSTALLATION BILL OF MATERIALS AND ADDITIONAL NOTES.

5

6

7

2

15

14

25

0

1

APPR.REVISED BY CK'D

2

3

10

2019

12

11

987

6

3

2

1 -

GUARD, CABLE, PVC 2-1/4" X 10'1

1 ARRESTER-SECONDARY, 120/240 3-WIRE

1

0.2

SWITCH, 600 AMP BYPASS TYPE

BANDING, 316, SS, 3/4" WIDE, .030 THICKNESS, 100', RL

BILL OF MATERIALS

9220109487

6

15

1

2

11

CLAMP, DE, SO, 336-1000 AL

LUG, COMPR, 795 AAC, 4-HOLE (BOTTOM OF PKR SW)

BOLT, MACHINE, 5/8" X 12"BOLT, MACHINE, 3/4" X 14"

INSULATOR, 25KV, DEADEND, POLYMERARRESTER, 10KV, HD-MOV, SILICONE/RUBBER/POLYMER

1

11

KIT, ANTENNA, UTILI-NET, MA-30-AB RADIO

SW, VRT, AUTO, 14.4KV, 900A, 35' CONTROL CABLESW, CONTROL, AUTO, INTELLI-TM-II, WITH RADIO

DESCRIPTION

-

9220109490

-9220109491

- 220202

-

080577

- 101125- 152123- 152107-

155464

-323422434122

-

260123

- 220139

2221

- 190312 1 WIRE, #2 CU, BR, SDW, 7, STR, #2 (FOR POLE GND)

13

390122 1 TAPE, ELECTRICAL, 3/4" X 66' X .007 MILCOMPOUND, INSUL, SEAL, PAD, 3-3/4"1402179

-

BOLT, OVAL EYE, 5/8" X 10"3011708

-

155331 LUG, COMPR, 795 AL, 2-HOLE1

2423

-

- 190204 1 #6 BC, HDW- 121418 6 TIE, PF, TOP F NECK 795 AL

- 190204 WIRE, CU, BR, HRD, DRN, #6 (FOR ARRESTER GND)2.4

- 013308 WASHER, SQUARE FLAT, 5/8"- 013264 WASHER, SPRING COIL, FOR 5/8"- 013128 WASHER, SPRING, BELLEVILLE- 013407 WASHER, STAINLESS STEEL, ROUND, FLAT, 1/2"

4221

18

4 -

WASHER, SPG, CO, S, FOR 5/8" BOLT1013264WASHER, 2-1/4", SQ, FLT, 13/16" HOLE1013308BOLT, MACHINE, 5/8" X 12"1152107

240306 1 BRACKET, ST. LIGHT, 6', WITH 30" RISE, GALV. STEEL

013264 1 WASHER, SPG, CO, S, FOR 5/8" BOLTWASHER, 2-1/4", SQ, FLT, 13/16" HOLE1013308BOLT, MACHINE, 5/8" X 12"2152107

5

15

16

11

14

17

25 -

CATALOGNUMBER

MACRO UNITQTYPERCU

12

6

----

6

6

1

1

1

1

QTYREQ'D

3

3

3

3-1-

35----6

COMPATIBLE UNIT

BOLT, OVAL EYE, 5/8" X 10"WASHER, 2-1/4" SQUARE, FLAT, 13/16" HOLEWASHER, 3" SQUARE, CURVED, 13/16" HOLEWASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT

011708013308013346013264

1111

080212 INSULATOR, POST, TIE-TOP, 15/25KV, W/O STUD072361 STUD, LINE POST, 5/8" X 1-3/4"070430 BRACKET, FIBERGLASS, STAND-OFF, 20"014114 SCREW, LAG, 1/2" X 4"152107 BOLT, MACHINE, SQ, NUT, 5/8" X 12"013264 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT

111111

HLC, 336 TO 7959220184794 1

012277 NUT, SS, HEX, COARSE THREAD013163 WASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLT010928 BOLT, MACHINE, SS, HEX, HEAD, 1/2" X 2"

10542504 WASHER, RD, 1/2", SS, 1-3/8" OD

4844

NUT, SS, HEX, COARSE THREADWASHER, FLAT, ROUND, SILICON, BRONZE, FOR 1/2" BOLTBOLT, MACHINE, SS, HEX, HEAD, 1/2" X 2"WASHER, RD, 1/2", SS, 1-3/8" OD

012277013163010928

10542504

2422

CN/CUITEMNO

3 BANDING, BUCKLE, SS, 3/4",FOR BANDING434142

2 BOLT, MACH, SQ, NUT, 5/8" X 12"1521072 WASHER, SQUARE, 2-1/4", FLAT, 13/16", HOLE, GALV.0133082 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.013264

5/24/13 DANNA ADCOCK

Page 92: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-10C11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH

STANDARD MOUNTING ARRANGEMENT (FMO)R

9220109493FOR MOUNTING INSIDE CONTROL PANELRADIO, REPLACEMENT, UTILI-NET, SERIES II WANGATE RADIO

-

WEATHERIZED, SELF-CONTAINEDRADIO, REPEATER/RELAY, UTILI-NET, WANGATE, AC/DC,

9220109494-

BOLT, MACHINE, SS, HX, HD, 1/2" X 2"2010928

-NUT, SS, HX, 304 ALLOY, COARSE, THREAD, 1/2"012277 2WASHER, FLT, RD SIL, BRN, FOR 1/2" BOLT013163 4WASHER, RD, 1/2", SS, 1-3/8" O.D.10542504 2

1 LUG, COMP 2H 336 AAC155408

-

-BOLT, MACHINE, SS, HX, HD, 1/2" X 2"010928 4

NUT, SS, HX, 304 ALLOY, COARSE, THREAD, 1/2"012277 4WASHER, FLT, RD SIL, BRN, FOR 1/2" BOLT8013163

WASHER, RD, FLT, SS, 304 ALLOY, FOR 1/2" BOLT10542504 4

LUG, COMP, 4 HOLE, 336.4 AAC1155457

14844

-

HLC, 336 TO 7959220184794 1-NUT, OVAL EYE, 5/8"012210- 1BOLT, OVAL EYE, 5/8" X 10"011708

-

1WASHER, SPG, CO, S, FOR, 5/8" BOLT013264 1WASHER, 2-1/4", SQ, FLT, 13/16" HOLE013308 1WASHER, 3", SQ, CRV, 13/16" HOLE013346 1INSULATOR, POLYMER, 25KV, DEADEND, SILICONE, RATED 15K080577 1CLAMP, DE, SO, 2/0-556.5 ACSR, 2/0-556.5 AL, COND RANG101119 1-

- 101125 1 CLAMP, DE, SO, 336.4-954 ACSR, 397.5-1000 AL, COND RANG

1. SEE DWG. 08.13-10A FOR DESIGN SPECIFICATIONS AND DWG. 08.13-10B FOR PLAN VIEW.

NOTES:

2. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE AND DWG. 08.13-10E FOR ANTENNA CONSTRUCTION.

MATERIALS NEEDED FOROPTIONAL OPERATION/INSTALLATION

0

3

2

1

APPR.REVISED BY CK'D

3. REPLACEMENT BATTERY FOR THE INTELLITEAM CONTROL IS CN 9220176380. THESE ARE NOT KEPT IN STORESDUE TO SHELF LIFE. CONTACT PURCHASING FOR ORDERING AND LEAD TIME.

4. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE AND DWG. 08.13-10E FOR ANTENNA INSTALLATION.

2

1

CATALOGDESCRIPTION

6

6

12

12

1

1

QTY

1

PERCU

NUMBERMACRO UNIT

-

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

1

3

4

5

6

78

9

1011

61

1

11

155331 LUG, COMP 2H-795AL

012277 NUT, SS, HEX, COARSE THREAD013163 WASHER, FLAT, ROUND, SILICONE, BRONZE, FOR 1/2" BOLT010928 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"

10542504 WASHER, RD, 1/2", SS, 1-3/8" OD

12422

LUG, COMP, 4 HOLE, 795 AACNUT, SS, HX, 304 ALLOY, COARSE, THREAD, 1/2"WASHER, FLT, RD SIL, BRN, FOR 1/2" BOLTBOLT, MACHINE, SS, HX, HD, 1/2" X 2"WASHER, RD, FLT, SS, 304 ALLOY, FOR 1/2" BOLT

155464012277013163010928

10542504

8. THE VT AND CT SENSORS SHOULD ALWAYS BE ORIENTED TOWARD THE SOURCE SIDE OF THE SWITCH.

THE PULL-RING 7 TO 9 TIMES TO EFFECT A CHANGE OF STATE.IF POWER IS LOST AND THE OPERATING SPRING IS FULLY DISCHARGED, USE A HOOK STICK TO PULL ON THE

7. IF OPERATING SPRING IS CHARGED, ONLY A SINGLE PULL ON THE MOTOR OPERATOR PULL-RING IS REQUIRED.

AND SAVE SHORTING BLOCKS TO ALLOW SENSOR CABLE CONNECTION.6. SHORTING BLOCKS FOR SENSOR SECONDARIES ARE SHIPPED INSTALLED IN SWITCH CONNECTOR. REMOVE

5. BLADE CONTACTS ARE GREASELESS AND SELF-LUBRICATING SO NO GREASE IS NEEDED.

Page 93: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

OMNI-RUPTER SWITCH STANDARD STACKED

DOUBLE-CIRCUIT POLE ARRANGEMENT (FMO)

NOTES:

1. SEE DWG. 08.13-11B FOR PLAN VIEW AND BILL OF MATERIALS. SEE DWG. 08.13-10A FOR OMNI-RUPTER CONTROLLER.

SIDE VIEW

#2 SD BC

29-1/8"

34"

43"

41"

6"

6"

5"

60"

6"

26"

26"

11"

97"

18-3/4"

21"

42"

42"

12

4

3

1

2

13

3. SEE DWG. 08.13-10E FOR ANTENNA INSTALLATION.2. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE.

FRONT VIEW

PULL-RINGMANUAL OPEN

OPEN POSITION

LOCKOUT/TAGOUTBRACKET FOR SWITCH

SOURCE

97"

BRACKETSMOUNTING

SURGEARRESTER

34"

26"

26"

LOAD 6

5

14

7

5"

(LOOKING FROM LOAD SIDE)

36"

36"

NOTE: IF YOU NEED AUTOMATEDOMNI-RUPTER IN FDR2,FDR1 MUST BE RAISEDTO POSITION OF DOTTEDSTACKED TOP CIRCUIT.

ONE-LINE

FDR1

AOR

FDR2

SUB

MUST BE VERY SECURE, ESPECIALLY THE #2 BC CONNECTION AT THE BASE OF THE OMNI-RUPTER SWITCH.

SOURCE LEAD SHOULD BE CONNECTED TO THE 795 JUMPER JUST BEYOND THE OMNI-RUPTER 2-HOLE HIGH-VOLTAGE TERMINAL ONEITHER SIDE OF THE OMN-RUPTER SWITCH TO KEEP THE LEADS AS SHORT AS POSSIBLE. THE GROUND LEAD SHOULD BE RUN FROM THE GROUNDING CONNECTION ON THE ARRESTER INTERRUPTER TO THE OMNI-RUPTER SUPPORT FRAME. THIS LEAD MUST BE LONG ENOUGH FOR THE INTERRUPTER TO OPERATE, BUT SHORT ENOUGH TO CLEAR ADJACENT CONDUCTORS. ALL GROUND CONNECTIONS

0

APPR.REVISED BY CK'D

#6 SD BC

#2 SD BC

#6 SD BC

#2 SD BC

#6 SD BC

#2 SD BC

1

25-1/4"

19

19

2

3

4/22/10 GUINN ELKINSGUINN

4. ARRESTERS SHOULD BE INSTALLED ON MOUNTING PADS PROVIDED ON BOTH SIDES OF THE OMNI-RUPTER SWITCH. THE ARRESTER

5/24/13 ADCOCKDANNA

19

08.13-11A

DEF

X

DEPDEMDEC8/5/14 EANES ADCOCKEANES

Page 94: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-11B11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH STANDARD STACKED

DOUBLE-CIRCUIT POLE ARRANGEMENT (FMO)

1918

11

10

987

6

3

2

-

GUARD, CABLE, PVC 2-1/4" X 10'1

1 ARRESTER-SECONDARY, 120/240 3-WIRE

115

SWITCH, 600 AMP BYPASS TYPESCREW, LAG, 1/4" X 2"

9220109487

1

11

1

11

CLAMP, DE, SO, 336-1000 AL

LUG, COMPR, 795 AAC, 4-HOLE (BOTTOM OF PKR SW)BOLT, MACHINE, 5/8" X 12"BOLT, MACHINE, 3/4" X 14"

INSULATOR, 25KV, DEADEND, POLYMERARRESTER, 10KV, HD-MOV, SILICONE/RUBBER/POLYMER

1

11

KIT, ANTENNA, UTILI-NET, MA-30-AB RADIO

SW, VRT, AUTO, 14.4KV, 900A, 35' CONTROL CABLESW, CONTROL, AUTO, INTELLI-TM-II, WITH RADIO

-

9220109490

-9220109491

- 220202

-

080577

101125152123152107155464

-323422014111260123

- 220139

2120

- 190312 1 WIRE, #2 CU, BR, SDW, 7, STR, #2 (FOR POLE GND)

NOTES:

1. SEE DWG. 08.13-11A FOR DESIGN SPECIFICATIONS AND DWG. 08.13-10A FOR OMNI-RUPTER CONTROLLER.

12

390122 1 TAPE, ELECTRICAL, 3/4" X 66' X .007 MILCOMPOUND, INSUL, SEAL, PAD, 3-3/4"2402179

-

-

155331 LUG, COMPR, 795 AL, 2-HOLE1

2322

-

- 190204 1 #6 BC, HDW121418 6 TIE, PF, TOP F NECK 795 AL

190204 WIRE, CU, BR, HRD, DRN, #6 (FOR ARRESTER GND)2.4

013308 WASHER, SQUARE FLAT, 5/8"013264 WASHER, SPRING COIL, FOR 5/8"013128 WASHER, SPRING, BELLEVILLE013407 WASHER, STAINLESS STEEL, ROUND, FLAT, 1/2"

PLAN VIEW

4221

1

17

4 -

WASHER, SPG, CO, S, FOR 5/8" BOLT2013264WASHER, 2-1/4", SQ, FLT, 13/16" HOLE4013308BOLT, MACHINE, 5/8" X 12"2152107

240306 1 BRACKET, ST. LIGHT, 6', WITH 30" RISE, GALV. STEEL

013264 2 WASHER, SPRING COIL, FOR 5/8"WASHER, SQUARE FLAT, 5/8"4013308BOLT, MACHINE, 5/8" X 12"2152107

5

14

15

--

13

16

SOURCE

6

5

14

23-1/16"

13

2

34-3/8"

7

LOAD

24

0

2

1

APPR.REVISED BY CK'D

013264 WASHER, SPRING COIL, FOR 5/8"014114 SCREW, LAG, 1/2" X 4"070431 BRACKET, FIBERGLASS, STAND-OFF, 30"072361 STUD, LINE, POST, 5/8" X 1-3/4"080212 INSULATOR, POST, TIE TOP, 15/25KV, W/O STUD152107 BOLT, MACHINE, SQ, NUT, 5/8"X12"

11111

1

BILL OF MATERIALS

CATALOGDESCRIPTION

12

6

1526

6

1

1

1

1

QTYPERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

-

---

35-1

3

6

3

3

--

6

NUT, SS, HEX, 304 ALLOY, COARSE THREADWASHER, FLAT, ROUND, SI, BRONZE, FOR 1/2" BOLTWASHER, RD, 1/2, SS

010928 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"012277 NUT, SS, HEX, 304 ALLOY, COARSE THREAD013163 WASHER, FLAT, ROUND, SI, BRONZE, FOR 1/2" BOLT

10542504 WASHER, RD, 1/2, SS

---

-

-

-

---

1 BOLT, OVAL EYE, 5/8" X 10"0117081 WASHER, SPRING COIL, FOR 5/8"0132641 WASHER, SQUARE FLAT, 5/8"0133081 WASHER, 3" SQUARE, CURVED, 13/16" HOLE013346

4 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"01092840122778013163410542504

2242

3

9220184794 HLC, 336 TO 7956-

-2 BOLT, MACH, SQ, NUT, 5/8" X 12"1521072 WASHER, SQUARE, 2-1/4", FLAT, 13/16", HOLE, GALV.0133082 WASHER, SPRING, COIL, STEEL, FOR 5/8" BOLT, GALV.013264

-

5/24/13 DANNA ADCOCK

Page 95: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH

HORIZONTAL MOUNTING ARRANGEMENT (FMO)

SIDE VIEWFRONT VIEW

1. SEE DWG. 08.13-13B FOR PLAN VIEW AND NOTES. SEE DWG. 08.13-13C FOR BILL OF MATERIALS.

NOTES:

MACROSSA90HS_M

18" MIN.

15"

24"

24"

9-7/8"

14" 4-1/2"

SOURCE LOAD LOAD

SOURCE

LOADSOURCE

GROUND4' ABOVE

30"

CABLERADIUS ON9" MINIMUM

#6 SD BC

MANUAL OPENPULL-RING

1

3

5

6

7

4

24"

11"

5'-0" MAX.30" MIN.

8

3. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE.

4. SEE DWG. 08.13-10E FOR ANTENNA INSTALLATION.

LOAD

9

SOURCE

18" MIN.

6"

13

2. SEE DWG. 08.13-10C FOR OPTIONAL CONSTRUCTION BILL OF MATERIALS.

12

0

3

2

1

APPR.REVISED BY CK'D

2

#2 SD BC#2 SD BC

#6 SD BC

NEUTRAL

08.13-13A

DEF

X

DEPDEMDEC

8/5/14 EANES EANES ADCOCK

Page 96: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH

HORIZONTAL MOUNTING ARRANGEMENT (FMO)

PLAN VIEW

NOTES:

1. SEE DWG. 08.13-13A FOR FRONT AND SIDE VIEWS.

LOAD

SOURCE

LOADSOURCESOURCE LOAD SOURCE LOAD

75

3

1

6

2

8

12

THE INTERRUPTER TO OPERATE, BUT SHORT ENOUGH TO CLEAR ADJACENT CONDUCTORS. ALL GROUND

5. ARRESTERS SHOULD BE INSTALLED ON MOUNTING PADS PROVIDED ON BOTH SIDES OF THE OMNI-RUPTERSWITCH. THE ARRESTER SOURCE LEAD SHOULD BE CONNECTED TO THE 795 JUMPER JUST BEYOND THE OMNI-RUPTER 2-HOLE HIGH-VOLTAGE TERMINAL ON EITHER SIDE OF THE OMNI-RUPTER SWITCH TO KEEP THELEADS AS SHORT AS POSSIBLE. THE GROUND LEAD SHOULD BE RUN FROM THE GROUNDING CONNECTION ONTHE ARRESTER INTERRUPTER TO THE OMNI-RUPTER SUPPORT FRAME. THIS LEAD MUST BE LONG ENOUGH FOR

2. SEE DWG. 08.13-13C FOR BILL OF MATERIALS. SEE DWG. 08.13-10C FOR OPTIONAL CONSTRUCTION BILL OF

CONNECTIONS MUST BE VERY SECURE, ESPECIALLY THE #2 BC CONNECTION AT THE BASE OF THE OMNI-RUPTER

4. SEE DWG. 08.13-10E FOR ANTENNA INSTALLATION.

3. SEE DWG. 08.13-10D FOR CONTROL FACEPLATE.

MATERIALS.

SWITCH.

0

3

2

1

APPR.REVISED BY CK'D

13

8/5/14 EANES EANES ADCOCK

08.13-13B

DEF

X

DEPDEMDEC

Page 97: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-13C11/29/10 HOFFMAN GUINN ELKINS

OMNI-RUPTER SWITCH

HORIZONTAL MOUNTING ARRANGEMENT (FMO)R

1. SEE DWG. 08.13-13A FOR FRONT AND SIDE VIEWS. SEE DWG. 08.13-13B FOR PLAN VIEW AND NOTES.

BOLT, MACH, SQ, 3/4" X 12"

WASHER, SPRING COIL, FOR 3/4" BOLTWASHER, SQUARE FLAT, 5/8"

2

22

INSULATOR, 27KV, POLYMER DEADENDCTRL CABLE IN LIQUIDTITE FLEXIBLE CONDUITSW, HORIZ, AUTO, 14.4KV, 900A, G35' SHIELDED

WASHER, SQUARE FLAT, 2-1/4"

CONNECTOR, WEDGE, 795-795 STR.

CLAMP, DEADEND, 795 AL3

1

1

426

013265013308152122

9220110451

080577101125

165277

013264013308

COMPOUND, INSUL, 3-3/4"TAPE, ELEC, 3/4"SWITCH, CTRL, AUTO

BOLT, MACH, SQ, 5/8" X 12"WASHER, SQUARE FLAT, 2-1/4"WASHER, SPRING COIL, FOR 5/8" BOLTKIT, ANTENNA, UTILI-NET

1

21

21

24

ARRESTER, LIGHTNING, 10KVBKT, STREET-LIGHT, 6' WITH 30" RISE, GALV STL1

1

1521079220109490

390122402179

9220109491013264013308152107240306220202

BOLT, MACH, SQ, 5/8" X 12"2

-

-

-

-

-

-

WASHER, SPRING COIL, FOR 5/8" BOLT

WASHER, SPRING COIL, FOR 5/8" BOLT

152107-

1

92200878689220091018

013264013308 WASHER, SQUARE FLAT, 2-1/4"1

11 BOLT, MACH, SQ, 5/8" X 12"

BKT, FBG, STAND-OFF1 INSUL, 25KV, POLYMER

#6 BC, HDW190204- 1SWITCH, BYPASS, 3 PHASE, 600A, 15KV, HORIZONTAL19220117302WASHER, SPRING COIL, FOR 5/8" BOLT2013264BOLT, MACHINE, SQ. NUT, 5/8" X 12"2152107WASHER, SQUARE FLAT, 5/8"2013308WASHER, SPRING, BELLEVILLE4013128NUT, SS, 1/2"12012277BOLT, MACHINE, SS, 1/2" X 2"12

013407 WASHER, SS, ROUND FLAT, 1/2"24010928 6

155331

-

LUG, 2 HOLE, 795 AL1

010928

HLC, 336 TO 7959220184794 1--

2. SEE DWG. 08.13-10C FOR OPTIONAL CONSTRUCTION BILL OF MATERIALS.

NOTES:

CABLE GUARD, 2-1/4" X 10"

GROUND WIRE, 7 STR, #2 CU, 1 LB.

ARR LIGHTNING SEC, 120/240V

LAG SCREWS, 1/4" X 2"451

1

1220139-323422014111

-

190312-

-

-

0

3

2

1

APPR.REVISED BY CK'D

BILL OF MATERIALS

CATALOGDESCRIPTION

1

QTYPERCU

NUMBERMACRO UNIT

SA90HS M

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

1

1

1

1

6

1

1

1

1

6

661

3

35

1

2

3

4

5

6

7

8

9

10

11

121314

15

16

WASHER, ROUND, BELLEVILLE, FOR 1/2" BOLT4013128

010928 BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"2012277 NUT, SS, HEX, COARSE2013163 WASHER, FLAT, ROUND, BRONZE, 1/2" BOLT4

10542504 WASHER, ROUND,1/2",SS 2

BOLT, MACHINE, SS, HEX HEAD, 1/2" X 2"NUT, SS, HEX, COARSEWASHER, FLAT, ROUND, BRONZE, 1/2" BOLT

WASHER, ROUND,1/2",SS

012277 6013163 6155464 LUG, COMPRESSION, 4 HOLE 795 AL6

10542504 6

Page 98: 08.01 CUTOUTS AND ARRESTERS - Progress Energy Inc · PDF file08.01 cutouts and arresters 08.00 general recloser and frame, ... solid blade horizontal 08.10-20 switch assembly, 600

DWG.

08.13-15

MOUNTING BRACKET DETAILNOTE: DIMENSIONS MAY VARY ±15% DEPENDING ON STYLE

POWER CABLE

MOUNTING BRACKETSEE ANTENNA

LEVELING WEDGE

ANTENNA

LEVELING WEDGE

MOUNTING BRACKETSSUPPLIED BY METRICOM

LIGHTINGBRACKETS PER

DETAIL BELOW

ANTENNA

DWG. 30.02-25

40" MIN.

43" MIN. TO

ALTERNATE NEUTRALLOCATION

LOCATIONPREFERRED NEUTRAL

CLOSEST PHASETO CLOSEST SECONDARY, SERVICE

OR NEUTRAL

40" MIN.TO CLOSEST SECONDARY,

SERVICE OR NEUTRAL

40" MIN.TO CLOSEST SECONDARY,

SERVICE OR NEUTRAL

SUPPLIED BY METRICOM

METRICOM RADIO TRANSCEIVERUSED TO SUPPORTWIRELESS MODEMS

NOTES:

1. METRICOM EQUIPMENT MOUNTED ABOVE THE NEUTRAL POSITION SHALL BE INSTALLED AND MAINTAINED ONLY BY PERSONS QUALIFIED TO WORK IN THE SUPPLY SPACE, PER SECTION 224 IN THE NESC.

2. INSTALL ONLY ON POLES LOCATEDON PUBLIC RIGHT OF WAY. DO NOTINSTALL ON PRIVATE AREA LIGHTS NORDECORATIVE POLES.

INTELLITEAM RADIO TRANSCEIVERS (FMO)

POLE TOPFRAMINGAS REQUIRED

6.8"

4"

3"

3"12"

R

0

3

2

1

APPR.REVISED BY CK'D

10"

POWER CABLE

4/22/10 GUINN GUINN ELKINS