Upload
independent
View
0
Download
0
Embed Size (px)
Citation preview
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 1 of 17
PROJECT INFORMATION
Project Reference #: 1305DEO1
Project Name: VITAS HEALTH CENTER (PROPOSED 2-STOREYBUILDING)
Project Location: VIB COMPOUND, VITAS, TONDO, MANILA
Client: DPWH NORTH MANILA ENGINEERING DISTRICT
Client’s Address: DPWH NAGTAHAN, STA. MESA, MANILA
Consultant: -
Contact Number: -
1.0 INTRODUCTION
The DPWH North Manila Engineering District, henceforth known as the Client, acquires
the services of A.M. Geoconsult& Associates to conduct a subsurface investigation of a
Proposed Two (2) Storey Building (Vitas Health Center) located at VIB Compound,
Vitas, Tondo, Manila, Philippines.
The objectives of this report is to provide geotechnical assessments based on the
results of laboratory tests using soil samples obtained underlying the site.
Recommendations on the following are then provided for the foundation scheme of the
structures:
1. Screening for potential problems such as expansive or liquefiable soils
2. Allowable bearing capacities of possible foundations
3. General guidelines in construction execution
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 2 of 17
2.0 SCOPE OF WORK SUMMARY
Two boreholes are drilled within the vicinity of the proposed building. Standard
Penetration Testing (SPT) is performed at every 1.50 meter interval and core samples
are taken when hard strata or rock material is encountered. Both boreholes are
advanced to a depth of 15.00 meters for good measure of the underlying material.
The samples are subjected to routine laboratory tests to determine the classification of
the materials using the Unified Soil Classification System (USCS) and their
corresponding engineering properties.
2.1 DETAILS OF FIELD WORKS
Table 1. Summary of field works
Borehole No. Drilling Depth (m) No. of Samples
SPT Coring
1 15.00 10 0
2 15.00 10 0
2.2 DETAILS OF LABORATORY WORKS
Table 2. Summary of laboratory works
Laboratory Test No. of Samples
Particle Size Distribution 20
Moisture Content 20
Atterberg Limits 20
Unified Soil Classification System 20
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 3 of 17
3.0 GEOLOGY AND SITE CONDITIONS
3.1 GENERAL AREA
The site is located in Tondo, Manila; an area that is near the coast of Manila Bay. The
project location is undoubtedly underlain by alluvial soils. Erosion from high plateau
cities (such as Quezon City) and mountains from the north east are brought to Pasig
River and are eventually deposited to Manila Bay (refer to Figure 1).
Figure 1. General location (Google Earth)
3.2 SITE SPECIFIC
The proposed two storey building is located within a compound with existing
surrounding structures.
Flood is a normal occurrence in the area. This prompts a worst case scenario in
foundation analysis, wherein ground water level is assumed to be at grade elevation.
3.3 SEISMICITY
The nearest seismic source for the project would be the Valley Fault System. The site is
approximately located at a distance of 10 km from an active segment of the West Valley
Fault. A study by Punongbayan et al (1997) predicted that Metro Manila is likely to
experience a magnitude 7.5 earthquake centred along the Valley Fault.
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 4 of 17
Although some segments of Valley Fault System are considered active, it has yet to
move. Historically, four (4) seismic sources have been identified as the cause of major
earthquakes in Metro Manila. These are the Philippine Fault Zone, Lubang Fault,
Casiguran Fault, and Manila Trench.
4.0 METHODOLOGY OF THE INVESTIGATION
4.1 FIELD SAMPLING & TESTING
The boreholes are advanced by rotary drilling and wash boring method. Alternately with
these methods, SPT is conducted at every 1.5 meter depth interval on soil layer, while
rotary drilling on hard materials down to the bottom of the hole. Protective casings are
inserted around the hole with a drop hammer to prevent materials from collapsing. The
boring operation entails the following phases:
a) Rotary Drilling
A method employed when hard materials are encountered or where the N-value
exceeds fifty (50). Under rotary action, the 46 mm diameter core bit is advanced into
the rock with core runs between 1.00 to 1.50 meters.
b) Wash Boring
A process in advancing the borehole by applying an up and down twisting motion of
a drill or chopping bit attached to the ends of drill rods while simultaneously allowing
a stream of water pumped through the rods to the soil. The combined action of the
water jet and chopping loosens the soil and is flushed to the surface.
c) Standard Penetration Test (ASTM-D1586)
The main sampling procedure conducted at every 1.50 meter depth interval using a
Donut free fall type of hammer. It involves placing a 50.80 mm (O.D.) diameter split
spoon sampler with the drilling rod into the ground at the bottom of the borehole. The
hammer weighs 63.50 kg and is dropped a distance of 762 mm to produce a
theoretical input driving energy (Ein) of 473.28 Nm. The number of blows to penetrate
every 150 mm interval is recorded successively until the third interval is penetrated.
The first interval blow count is considered as the seating drive and is discarded. The
last two blow counts from the second and third intervals are added to give what is
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 5 of 17
known as the N-value. Disturbed soil samples obtained by the split spoon were
collected for visual inspection and laboratory testing.
d) Ground Water Level
This measurement is done by lowering a weighted tape down the hole until water
contact is made. Readings are made after water is allowed to stand for a minimum
period of 12 hours following completion of the drilling. The observation made during
this period is assumed as the ground water level.
4.2 DETAILS OF LABORATORY WORKS
The following laboratory tests are performed in accordance with the specified
procedures from the American Society for Testing and Materials (ASTM). Appropriate
test procedures are referenced in ASTM Manuals for the soil tests discussed in the
following sections:
a) Natural Moisture Content (ASTM-D2216)
This test is also known as water content. It is the ratio expressed as a percentage of
the weight of water in a given mass of soil to the weight of the solid particles.
b) Grain Size Analysis of Soils (ASTM-D422)
A process wherein the proportion of each grain size present in a given soil sample
(grain-size distribution) is determined. The grain- size distribution of coarse –grained
soils is determined directly by sieve analysis, while that of fine-grained soils is
determined indirectly by hydrometer analysis. The grain-size distribution of mixed
soils is determined by combined sieve and hydrometer analyses.
c) Atterberg Limits of Soils (ASTM-D4318)
A procedure that consists of several parameters that are primarily water contents
which define the limits of various stages of consistency for fine-grained soils. The
liquid limit (LL) and the plastic limit (PL) define the upper and lower limits,
respectively, of the plastic range of a soil; the numerical difference between these
two limits expresses the plasticity of a soil and is termed the plasticity index (PI).
d) Classification of Soils for Engineering Purposes (ASTM-D2487)
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 6 of 17
In general, soils are classified based on the Unified Soil Classification System
(USCS). In this system, soil falls within one of the three major categories: coarse-
grained, fine- grained, and highly- organic soils.
5.0 RESULTS OF INVESTIGATION
Below is a summary of the results of each borehole. The profiles of the index properties
and in-situ moisture content of each borehole are also illustrated. The green line
represents the magnitude of the plasticity index, with the left boundary as the plastic
limit and the right boundary as the liquid limit. The blue line corresponds to the in-situ
moisture content. Lastly, the red dashed line shows the measured groundwater level at
the site.
Table 3. Summary of results, BH-1
BOREHOLE 1
DEPTH (m) N-Value USCS DESCRIPTION CONSISTENCY
INDEX PROPERTIES
0.0 – 1.5 8 SC-SM Silty clayey SAND w. gravel Loose
1.5 – 3.0 12 SC Clayey SAND Medium Dense
3.0 – 4.5 31 SC Clayey SAND w/ gravel Dense
4.5 – 6.0 24 SC Clayey SAND Medium Dense
6.0 – 7.5 8 ML SILT w/ sand Medium Stiff
7.5 – 9.0 45 SC-SM Silty clayey SAND Dense
9.0 – 10.5 45 SC Clayey SAND w/ gravel Dense
10.5 – 12.0 53 SM Silty SAND w/ gravel Very Dense
12.0 – 13.5 63 SM Silty SAND w/ gravel Very Dense
13.5 – 15.0 66 SM Silty SAND w/ gravel Very Dense
END OF DRILLING
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 7 of 17
Table 4. Summary of results, BH-2
BOREHOLE 2
DEPTH (m) N-Value USCS DESCRIPTION CONSISTENCY
INDEX PROPERTIES
0.0 – 1.5 7 SC-SM Silty clayey SAND w. gravel Loose
1.5 – 3.0 17 SC-SM Silty clayey SAND Medium Dense
3.0 – 4.5 34 SM Silty SAND Dense
4.5 – 6.0 16 SM Silty SAND Medium Dense
6.0 – 7.5 27 ML Sandy SILT Very Stiff
7.5 – 9.0 43 SM Silty SAND Dense
9.0 – 10.5 45 SP-SM Well-graded SAND Dense
10.5 – 12.0 58 SC Clayey SAND w/ gravel Very Dense
12.0 – 13.5 65 SC-SM Silty clayey SAND w/ gravel Very Dense
13.5 – 15.0 65 GC Clayey GRAVEL w/ sand Very Dense
END OF DRILLING
6.0 ENGINEERING ANALYSIS AND CONSIDERATIONS
6.1 SITE CONDITIONS
The boreholes consistently reveal that the surface layer comprises of alluvial soils
characterized by predominantly sands in varying proportions of fine-grained materials.
There is irregularity with increasing depth; a deeper soil layer may be less dense
compared to shallower layers. This just confirms the predicted geology of a dynamic
alluvial depository area.
With the inconsistencies of the surface soils, it is highly likely that the site will
experience differential settlement.
After the first 9.0 meters, the soils encountered are considered to be competent layers.
The presence of alluvial soils at the surface is also a cause for immediate concern
since these soil types are potentially liquefiable. These layers warrant a closer
inspection prior to recommending foundation schemes.
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 8 of 17
6.2 LIQUEFACTION POTENTIAL
In evaluating the potential of the soil for liquefaction, the simple criteria provided by the
National Structural Code of the Philippines, (NSCP) 2010, Section 303.4 is used. Soils
meeting all three of the following provisions will be considered liquefiable:
1) Shallow ground water, two meters or less
2) Unconsolidated saturated alluvium (N<15)
3) Seismic Zone 4
The project site is clearly located in a Seismic Zone 4. The upper 9.0 meters of soil is
also considered to be unconsolidated alluvium as derived from the index properties.
Finally, the same upper layers show samples having N-values less than or close to 15.
The hazard map provided by the Philippine Institute of Volcanology & Seismology (refer
to Figure 2) further calls for attention. It shows that the project area is questionably at
the boundary of the said liquefiable soils. This, however, serves only as a guide and
detailed calculations of engineering properties is needed for confirmation.
Figure 2. Liquefaction hazards in Metro Manila (Philvocs)
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 9 of 17
The loose to medium dense layers classified as predominantly cohesionless soils are
the primary target. Due to lack of testing specific to liquefaction, analysis is done by
correlating to SPT N-values. The Factor of Safety (FS) for liquefaction potential is
calculated as the ratio of the Cyclic Resistance Ratio (CRR) to the Cyclic Tress Ratio
(CSR).
FS=CRR / CSR
Where
Table 5. Summary of potentially liquefiable cohesionless soils
BH No. Depth (m) CRR CSR FS
1
0.0 – 1.5 0.088682 0.508893 0.174264
1.5 – 3.0 0.129916 0.494567 0.262687
3.0 – 4.5 0.341792 0.479559 0.712721
4.5 – 6.0 0.267222 0.471611 0.566615
2
0.0 – 1.5 0.079845 0.511437 0.15612
1.5 – 3.0 0.183471 0.492265 0.372708
3.0 – 4.5 0.509445 0.476764 1.068548
4.5 – 6.0 0.172844 0.470587 0.367294
*amax = 0.4g **the factor of safety is at earthquake magnitude 7.5
These data show that the project area is susceptible to liquefaction. The distribution of
potentially liquefiable soils within the project area is not fully known since the boreholes
show variations in consistencies. What is consistent is the fact that the hazardous
layers are encountered only up to depths of 9.0 meters.
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 10 of 17
But, as mentioned, this general analysis is based only on SPT correlations. It is
recommended that further testing should be conducted specific to liquefaction.
6.3 FOUNDATION DESIGN RECOMMENDATION
The exact structural details for the proposed school building are not known during the
making of this report. The following are generalized recommendations.
Considering the soil profile from the borehole results and the potential for problems, the
proposed building is recommended to be fitted with the following foundation schemes:
Shallow Foundation:
Mat Foundation
Deep Foundation:
Driven piles
Bored piles
Options are provided for the discretion of the structural designer, however, it is strongly
recommended to incorporate BORED PILES in the design.
It is important to verify, during construction, if the soil profile is consistent throughout the
project area. Discrepancies such as varying soil properties or presence of
discontinuities must be taken into account for the design of the foundation.
6.4 SHALLOW FOUNDATION
The maximum load that the underlying soil may carry from the structure is estimated
using Terzaghi’s (1943) bearing capacity equation below.
Qu = cNcsc+ γ1DfNq + 0.5γ2BNysy
where: Qu = ultimate bearing capacity
c = cohesion
Nc,Ny,Nq = bearing capacity factors
B = width of footing
Df = footing depth (embedment depth)
γ1 = effective unit weight of soil above footing level
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 11 of 17
γ2 = effective unit weight of soil below footing level
sc = shape factor (strip=1.0, square=1.3)
sy = shape factor (strip=1.0, square=0.8)
Qa = Qu / FS
where: Qa = allowable bearing capacity
FS = factor of safety (standard practice=3.0)
Figure 3. Diagram of a typical footing
It is estimated that settlement will not exceed 25 mm due to the caution provided by the
factor of safety.
a) Mat Foundation
In terms of shallow foundations, mat foundations are the best approach in preventing
damages from differential settlement.
Listed below are the possible bearing capacities for a mat foundation. The building’s
shorter width corresponds to the listed footing widths. The trends of the capacities are
also presented and may be used for estimating values using other dimensions (refer to
Figure 4).
B = width of footing
Df = footing depth
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 12 of 17
Table 6. Summary of Allowable Bearing Capacities Mat Foundation
Footing Width (B), m Allowable Bearing Capacity (Qa), kPa
Df = 1.0 m Df =1.5 m Df = 2.0 m Df = 3.0m
5.0 175 204 233 291
8.0 246 275 304 362
12.0 341 370 399 456
15.0 412 441 470 527
Figure 4. Trendlines of allowable bearing capacities with varying mat foundation dimensions
b) Other Considerations
The embedment depth requirement of any of the foundation scheme should satisfy the
lateral stability and structural integrity of the proposed structure.
The bearing capacities can be increased by 33% for analysis involving transient loads
in combination with wind and seismic forces.
The pressure due to the excavated material must also be added to the recommended
values. An estimated unit weight of18 kN/m3 may be used.
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 13 of 17
6.5 DEEP FOUNDATION
The most favourable option for this project is to adopt a deep foundation scheme in a
form of driven or bored piles. With this system, problematic soils are bypassed by
transmitting the loads deeper into competent layers.
It is up to the designer on which pile type to use, but it is recommended to use bored
piles since the project is within an existing campus. Pile driving may cause not only
disturbance to students and civilians, but the vibrations from the force of the hammer
may also cause settlement on the surrounding structures.
Presented below are the recommended pile dimensions and its corresponding
allowable bearing capacities. The NAVFAC Design Manual 7.02 for vertical capacity
analysis is used for deriving the values.
Table 7. Summary of Allowable Bearing Capacities of DRIVEN Piles
Pile Width = 400 mm
Depth (m) *Allowable Bearing Capacity
(kPa)
0.0-1.5 11
1.5-3.0 60
3.0-4.5 189
4.5-6.0 173
6.0-7.5 121
7.5-9.0 453
9.0-10.5 564
10.5-12.0 796
12.0-13.5 944
13.5-15.0 1099
*Allowable bearing capacities are calculated using a Factor of Safety = 3.0
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 14 of 17
Table 8. Summary of Allowable Bearing Capacities of BORED Piles
Pile Diameter = 600 mm
Depth (m) *Allowable Bearing Capacity
(kPa)
0.0-1.5 11
1.5-3.0 56
3.0-4.5 175
4.5-6.0 168
6.0-7.5 131
7.5-9.0 433
9.0-10.5 545
10.5-12.0 768
12.0-13.5 917
13.5-15.0 1076
*Allowable bearing capacities are calculated using a Factor of Safety = 3.0
It is recommended that the pile foundations should at least penetrate to a depth of 10.0
meters in order to completely bypass any possible liquefiable soils.
For reasons wherein the given recommendations are insufficient, the unit resistances
per layer are listed below and may be used for estimating values using other
dimensions. To compute for the corresponding bearing capacity, the following
equations may be used:
Qu = Qb+∑Qs
where: Qu = ultimate bearing capacity
Qb = ultimate base resistance
Qs = ultimate side resistance
Qu = fbAb+∑fsAs
where: fb = unit base resistance for each layer
fs = unit side resistance for each layer
Ab = area of pile base
As = surface of pile shaft for specified layer
Qa = Qu / FS
where: Qa = allowable bearing capacity
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 15 of 17
FS = factor of safety (standard practice=3.0)
Table 9. List of pile unit resistances
Recommended Unit Resistances
Depth (m) DRIVEN PILE BORED PILE
fb (kPa) fs (kPa) fb (kPa) fs (kPa)
0.0-1.5 125 8 64 8
1.5-3.0 838 20 411 20
3.0-4.5 2891 37 1430 37
4.5-6.0 2150 45 1057 45
6.0-7.5 739 43 376 43
7.5-9.0 6188 78 3061 78
9.0-10.5 7335 93 3628 93
10.5-12.0 10588 111 5248 111
12.0-13.5 12081 127 5988 127
13.5-15.0 13573 143 6728 143
It must be emphasized that the presented values are derived solely from the borehole
results. Discrepancies are possible, especially around alluvial deposits. It is prudent to
confirm the pile capacities by performing static or dynamic load tests. Results of these
tests may be used to adjust the initial estimations.
6.6 FILL CONSTRUCTION
A layer of crushed gravel should be placed under the footings prior to its construction.
The granular fill shall consist of free-draining granular materials with a minimum
thickness of 200 mm. It will be compacted to a minimum of 95% MDD based on ASTM
D1557. This layer will provide drainage under and around the slab and footings.
Any organic or deleterious material shall be removed and will not be permitted in fills.
No rock or similar irreducible material with a maximum dimension greater than 200mm
shall be buried or placed in fills.
6.7 HYDROLOGICAL FACTORS
The measured ground water levels are consistently encountered at around 2.5 meters.
Groundwater intrusion is definitely a problem during the construction of shallow and
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 16 of 17
deep foundations, especially since the area is prone to flooding. Proper mitigating
equipment such as water pumps must be prepared. At the least, an efficient drainage
system must be provided to release external sources of water by fitting drains or canal
lines.
6.8 EXCAVATION
The soils at the surface may be problematic during excavation due to the shallow
groundwater. Superficial damage may likely happen during heavy rainfall. It is therefore
prudent to provide temporary support systems during construction.
Excavating adjacent to existing structures will remove resisting lateral forces, resulting
in possible lateral failure. This loss of lateral resisting force may be calculated and be
replaced by corresponding support systems. An estimated unit weight of 18 kN/m3 may
be used.
6.9 PAVEMENT DESIGN
As previously mentioned, the site is susceptible to differential settlement. This may
cause problems for slab-on-grade pavements. Since the floor and the footings might
settle at a different rate, cracks may develop. This is far from a threat to structural
integrity, but the Client may opt to prevent superficial damage. The pavements may be
reinforced or suspended as preventive measures.
6.10 SEISMIC DESIGN CONSIDERATION
The nearest fault that can generate large-scale magnitude earthquake for this site is the
West Valley Fault. This fault is situated at an approximate distance of approximately 10
km east from the project site. To satisfy the NSCP code provisions (2010) for
earthquake design of buildings, the seismic response coefficients and near source
factors was determined. For this site having soil profile type SD, the near source factors
are Na = 1.2 and Nv = 1.6, and seismic response coefficients are Ca = 0.44Na and Cv =
0.64Nv. The site falls in the Seismic Zone 4, having Z=0.4.
A.M. Geoconsult & Associates DPWH North Manila Engineering District Geotechnical Investigation Report Vitas Health Center (Proposed 2 Storey Building)
1305DEO1_RGIR_DSR_0 Page 17 of 17
7.0 LIMITATIONS
The geotechnical evaluation and recommendation given above were based on the
results from the two (3) boreholes and has been prepared as a guide in the design of
the proposed structure. The analyses and recommendations submitted in this report
are based, in part, on information obtained from field borings and laboratory test in
accordance with the generally accepted engineering principles and practices. Its scope
is limited to the location and type of structure described herein. Variations of subsoil
conditions between the borings may occur, and the nature and extent of these
variations may not become evident until construction is underway. The owner/client
should be aware that unanticipated soil/rock conditions are commonly encountered.
Unforeseen soil/rock conditions, such as perched groundwater, soft deposits, hard
layers, or cavities, may occur in localized areas and may require probing or corrections
in the field to attain a properly constructed project.
In the event that this report is used in other projects for design purposes or
recommendations contained in this report are not followed, the Undersigned disclaim its
responsibility. If there is any difference in location and/or design features as we
understand them and as are defined by the test borings, the Undersigned should be
informed thru this office so that appropriate modification can be made.
Prepared by:
DAVID DENNIS V. STA. ROSA, MS CE (G)
Civil/Geotechnical Engineer
PRC No.: 0118783
June 3, 2013