2 HR SMOKE COMPARTMENT BARRIER
2 HR FIRE BARRIER
1 HR SMOKE COMPARTMENT BARRIER
1 HR FIRE BARRIER
NON-RATED SMOKE RESISTIVE PARTITION
NON-RATED PARTITION
3 HR SMOKE COMPARTMENT BARRIER
3 HR FIRE BARRIER
(FOR REFERENCE ONLY. SEE ARCH DRAWINGS FOR BARRIER DETAILS)
WALL & CEILING BARRIERS
DUCT SECTION - RISE / DROPMAKEUP AIR
DUCT SECTION - RISE / DROPRETURN
DUCT SECTION - RISE / DROPEXHAUST
DUCT SECTION - RISE / DROPOUTSIDE AIR
DUCT SECTION - RISE / DROPRELIEF
DUCT SECTION - RISE / DROPTRANSFER
DUCT SECTION - RISE / DROPSUPPLY HPS
DUCT SECTION - RISE / DROPSUPPLY LPS
DUCT SECTION - RISE / DROPSUPPLY MPS
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS AND APPLICABLE CODES AND REGULATIONS.
4. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS PRIOR TO FABRICATION.
5. WORK SHALL BE ACCURATELY LAID OUT WITH REFERENCE TO THE ARCHITECTURAL DRAWINGS AND IN COOPERATION WITH OTHER TRADES, WHICH SHALL AFFORD MAXIMUM ACCESSIBILITY FOR OPERATION, MAINTENANCE AND HEADROOM. FAILURE TO COORDINATE WORK WITH OTHER TRADES SHALL NOT BE CONSIDERED AS A BASIS FOR EXTRA COST CHANGES.
6. WHERE PLENUMS ARE USED FOR SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION SYSTEMS, MATERIALS WITHIN THE PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
7. DIMENSIONS SHOWN ON DRAWINGS FOR DUCTWORK ARE INSIDE CLEAR.8. ALL DUCTWORK, INCLUDING FIRE DAMPERS, SHALL BE SEALED AND TESTED FOR
LEAKS PRIOR TO COVERING WORK.9. PATCH ALL CUTTING OR DRILLING OF FINISHED WALLS, CEILINGS AND FLOORS.10. DIFFUSER AND GRILLE LOCATIONS TO BE COORDINATED WITH ARCHITECTURAL
CEILING PLAN. ANY CEILING MOUNTED DIFFUSERS OR GRILLES WHICH DO NOT MATCH CEILING TILE SIZES ARE TO BE MOUNTED IN CENTER OF TILE.
11. CONTRACTOR SHALL INSTALL ANY BALANCING DEVICE NECESSARY TO ACHIEVE PROPER ADJUSTING AND BALANCING OF MECHANICAL SYSTEMS.
12. REFRIGERANT PIPING SHALL BE SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
13. RUNOUTS TO DIFFUSERS / GRILLES SHALL BE THE SAME SIZE AS THE DIFFUSER / GRILLE NECK SIZE UNLESS OTHERWISE NOTED.
ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS, INCLUDING, BUT NOT LIMITED TO:• 21015 VIRGINIA CONSTRUCTION CODE• 21015 VIRGINIA EXISTING BUILDING CODE• 21015 VIRGINIA MECHANICAL CODE• 21015 VIRGINIA FUEL GAS CODE• 21015 VIRGINIA ENERGY CONSERVATION CODE• 2013 ASHRAE 90.1• 2013 ASHRAE 62.1• LATEST SMACNA STANDARDS
LEVEL / SHEET SEQUENCE
VIEW TYPE MODIFIER
0 = DEMOLITION PLANS (OPTIONAL)
1 = FLOOR PLANS
VIEW TYPE
0 = GENERAL / SCHEDULES1 = PLANS - HVAC / DUCT 2 = PLANS - PIPING3 = SECTIONS4 = ENLARGED PLANS5 = DETAILS6 = FLOW DIAGRAMS
& CONTROLS7 = SPECIFICATIONS
DISCIPLINE
M = MECHANICAL / HVAC
PHASE WORK - EXISTING DUCTWORK, PIPING OR EQUIPMENT MARKED FOR DEMOLITION. (DASHED LINE TYPE)
PHASE WORK - EXISTING DUCTWORK, PIPING OR EQUIPMENTTO REMAIN. (THIN, LIGHT)
PHASE WORK - NEW DUCTWORK, PIPING OR EQUIPMENT.
ACCESS DOOR
TURNING VANES
DUCT SECTION - RISE / DROPSUPPLY, MAKEUP AIR, OUTSIDE AIR
DUCT SECTION - RISE / DROPRETURN, TRANSFER
DAMPER, MOTORIZED
SENSOR, DUCT SMOKE DETECTOR
SENSOR, AIR FLOW MEASURING
DAMPER, FIRE - RECTANGULAR / ROUND
DUCT SECTION - RISE / DROPEXHAUST, RELIEF
F
S
CHECK VALVE
BUTTERFLY VALVE
STEAM PRESSURE REGULATING VALVE
STEAM DRIP TRAP ASSEMBLY
TEE OFF TOP
TEE OFF BOTTOM
FLOW CONTROL VALVE
DIRECTION OF FLOW
PITCH DOWN IN DIRECTION OF ARROW
MANUAL AIR VENT (SEE DETAIL)
AUTOMATIC AIR VENT (SEE DETAIL)
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ELBOW, TURNING DOWN
ELBOW, TURNING UP
DIFFERENTIAL PRESSURE SWITCH
GLOBE VALVE
GATE VALVE SCREWED OR SOLDERED
GATE VALVE FLANGED
HOSE BIBB DRAIN VALVE
BALL VALVE
UNION
BALANCING VALVE
AUTOMATIC VALVE, 3-WAY, PNUEMATIC
AUTOMATIC VALVE, 3-WAY, ELECTRIC/ELECTRONIC
FLEXIBLE PIPE CONNECTOR
AUTOMATIC VALVE, 2-WAY, PNUEMATIC
AUTOMATIC VALVE, 2-WAY, ELECTRIC/ELECTRONIC
RELIEF VALVE
WATER PRESSURE REDUCING VALVE
STRAINER
PIPE GUIDE
PIPE ANCHOR
FLOW METER
PIPE CAP
CARBON DIOXIDE SENSOR (MOUNT 4'-0" A.F.F.)
CARBON MONOXIDE SENSOR (MOUNT 4'-0" A.F.F.)
POINT OF CONNECTION, NEW TO EXISTING
REMOVE TO THIS POINT
DP
AAV
MAV
DUCTWORK WITH LINER
DAMPER, VOLUME (BALANCING)
TRANSITION, FLAT ON TOP
SPLITTER DAMPER
SUPPLY AIR DEVICE
DUCTWORK (SHOWING INSULATION)
TRANSITION, FLAT ON BOTTOM
FOT
FOB
FLEXIBLE DUCT CONNECTION
FLEXIBLE DUCT
12x12 S-1
300 CFM
RETURN AIR DEVICE12x12 R-1
300 CFM
EXHAUST AIR DEVICE12x12 E-1
300 CFM
HUMIDITY SENSOR (MOUNT 4'-0" A.F.F.)
THERMOSTAT (MOUNT 4'-0" A.F.F.)
TEMPERATURE SENSOR (MOUNT 4'-0" A.F.F.)
FD
VD
FD
DAMPER, SMOKE - RECTANGULAR / ROUND
SD SD
HUMIDISTAT (MOUNT 4'-0" A.F.F.)
DAMPER, BACK DRAFT
BDD
C
CO
H
H
TS
T
PHASE WORK - TEMPORARY DUCTWORK, PIPING OR EQUIPMENT.
SUPPLY DIFFUSER WITH BLANK-OFF
DOOR UNDERCUT
1. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
2. PATCH ALL CUTTING OR DRILLING OF FINISHED WALLS, CEILINGS AND FLOORS. 3. UNLESS SPECIFICALLY NOTED, REMOVE ALL HVAC SYSTEMS IN THEIR ENTIRETY.
THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT, THERMOSTATS, TERMINAL UNITS, DUCTWORK, PIPING, AIR DEVICES, AND ALL ASSOCIATED COMPONENTS AND SUPPORTS. PATCH AND REPAIR ALL AREAS THAT ARE TO REMAIN WHERE ITEMS WERE ATTACHED OR SUPPORTED.
4. COORDINATE EXTENT OF DEMOLITION WITH NEW WORK IN ALL LOCATIONS WHERE MECHANICAL COMPONENTS ARE TO REMAIN.
5. CONTRACTOR TO REMOVE ANY MECHANICAL COMPONENTS WITHIN WALLS INDICATED TO BE DEMOLISHED ON ARCHITECTURAL DEMOLITION PLANS.
6. PROTECT ALL EQUIPMENT TO REMAIN FROM DAMAGE DURING DEMOLITION. PROVIDE TEMPORARY COVERS AND CAP ENDS OF ALL PIPING AND DUCTWORK AT COMPLETION OF PARTIAL DEMOLITION.
7. COORDINATE WITH ELECTRICAL DEMOLITION BEFORE REMOVING DUCTWORK CONTAINING SMOKE DETECTORS OR EQUIPMENT, DEVICES, AND SYSTEMS HAVING ELECTRICAL CONNECTIONS.
LEGEND - RATED WALLS
LEGEND - MECHANICAL SYMBOLS
GENERAL NOTES - MECHANICAL
APPLICABLE CODES
MECHANICAL SHEET LISTSHEET NUMBER NAME
M001 LEGEND, ABBREVIATIONS AND GENERAL NOTES
M002 SCHEDULES
M101 FIRST FLOOR PLAN - DEMOLITION
M111 FIRST FLOOR AND LOW ROOF PLANS - NEW WORK
M501 DETAILS
M601 CONTROLS
N
S
W
E160.00°
TRUE NORTH
PROJECT (PLAN) NORTH
ANGLE BETWEEN TRUE & PROJECT NORTH
SHEET NUMBERING
LEGEND - MECHANICAL SYMBOLS
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:07 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
LEGEND, ABBREVIATIONSAND GENERAL NOTES
06/23/2021 -CONSTRUCTION DOCUMENTS
M001
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
0' 4' 8' 24'20'16'12'
1/8" =1'-0"
0' 2' 4' 12'10'8'6'
1/4" =1'-0"
GRAPHIC SCALES
GENERAL NOTES - DEMOLITION
MECHANICAL ABBREVIATIONSAbbrev Definition
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFMS AIRFLOW MEASURING STATION
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING ANDAIR-CONDITIONING ENGINEERS
BDD (COUNTERBALANCED) BACKDRAFT DAMPER
BFW BOILER FEEDWATER
CD CONDENSATE DRAIN
CFM CUBIC FEET (AIR) PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CVD (REMOTE) CABLE-CONTROLLED VOLUME DAMPER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DSD DUCT SMOKE DETECTOR
EXH EXHAUST (AIR SYSTEM)
FD FIRE DAMPER
FM FLOW METER
FOB FLAT ON BOTTOM
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FLAT ON TOP
GPM GALLONS PER MINUTE
GR GLYCOL RETURN
GS GLYCOL SUPPLY
HPS HIGH PRESSURE STEAM / HIGH PRESSURE SUPPLY (AIR SYSTEM)
HR HOUR
HRR HEAT RECOVERY RETURN
HRS HEAT RECOVERY SUPPLY
HVAC HEATING, VENTILATING AND AIR-CONDITIONING
HWR (HEATING) HOT WATER RETURN
HWS (HEATING) HOT WATER SUPPLY
LPS LOW PRESSURE STEAM / LOW PRESSURE SUPPLY (AIR SYSTEM)
MPS MEDIUM PRESSURE STEAM / MEDIUM PRESSURE SUPPLY (AIRSYSTEM)
NA or N/A NOT APPLICABLE
OA OUTSIDE AIR (SYSTEM)
PCR PUMPED CONDENSATE RETURN
PRV PRESSURE REDUCING VALVE
RA RETURN AIR (SYSTEM)
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RV RELIEF VALVE
SA SUPPLY AIR (SYSTEM)
SD SMOKE DAMPER
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTOR'S NATIONALASSOCIATION
TYP. TYPICAL
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
06/23/2021
SPECIFICATION SECTIONS:233416 - CENTRIFUGAL HVAC FANS
REMARKS:1. PROVIDE SINGLE POINT POWER CONNECTION.2. EC MOTOR IS FOR BALANCING ONLY; FAN SHALL OPERATE AS CONSTANT VOLUME FAN AT AIRFLOW SHOWN ABOVE.3. PROVIDE SPEED CONTROLLER.
SPECIFICATION SECTIONS:233713 - DIFFUSERS, REGISTERS, AND GRILLES
REMARKS:1. FINAL COLOR SELECTION BY ARCHITECT. VENDOR TO SUBMIT FULL COLOR CHART. 2. LINEAR DEVICE DATA INTENTIONALLY LEFT BLANK FOR NON-LINEAR TYPE DEVICES.
SPECIFICATION SECTION:233600 - AIR TERMINAL UNITS
REMARKS:1. PROVIDE DISCONNECT. COORDINATE WITH ELECTRICAL FOR CIRCUITING.2. PROVIDE SCR CONTROL FOR REHEAT COILS.
SPECIFICATION SECTION:237213 - HEAT WHEEL AIR-TO-AIR ENERGY-RECOVERY EQUIPMENT
REMARKS:1. ENERGY RECOVERY WHEEL AND ASSOCIATED CONTROLS SHALL BE PROVIDED BY RTU-1 MANUFACTURER AS PART OF RTU-1.2. WHEEL SHALL BE BALANCED TO 1885 CFM OF OUTSIDE AIR AND 1185 CFM OF EXHAUST AIR.
SPECIFICATION SECTION:237416.11 - PACKAGED SMALL-CAPACITY ROOFTOP AIR-CONDITIONING UNITS
REMARKS:1. MECHANICAL CONTRACTOR SHALL PROVIDE DISCONNECTS.2. UNIT SHALL BE INSTALLED ON EXISTING STRUCTURAL STEEL FRAME; SEE STRUCTURAL DRAWINGS FOR MORE INFORMATION. DUCTS SHALL DROP DOWN FROM UNIT AND PENETRATE THROUGH ROOF.3. UNIT SHALL BE PROVIDED WITH ENERGY RECOVERY WHEEL AND 5 HP EXHAUST FAN (208 VOLT, 3 PHASE, 16.7 FLA). SEE ENERGY RECOVERY WHEEL SCHEDULE FOR PERFORMANCE DATA.4. PROVIDE RETURN DUCT SMOKE DETECTOR.5. GAS HEATING COIL IS SIZED TO PROVIDE A LAT OF 60F IN CASE OF ENERGY RECOVERY WHEEL MALFUNCTION. REFERENCE SHEET M601 FOR REQUIRED CONTROLS AND SMOKE DETECTOR FUNCTIONALITY.
GENERAL NOTES1. ASSOCIATED SPECIFICATION SECTION: 238239.2. PROVIDE SINGLE POINT POWER CONNECTION.3. PROVIDE FACEPLATE THERMOSTAT; SET TO 70F.
MECHANICAL EQUIPMENT SCHEDULE - FANS
DESIGNATION SERVICE TO TYPE
FAN DATA MOTOR DATA
EMERGENCYPOWER MANUFACTURER MODEL REMARKSAIR FLOW BLADE TYPE
STATIC PRESSURE -TOTAL SPEED (RPM) POWER SPEED (RPM) VOLTS PHASE VFD OR ECM
STARTER /DISCONNECT
AFT/STARTERPROVIDED BY
EF-1 LAB (124) DIRECT DRIVE INLINE 650 CFM BI CENTIRIFUGAL 0.36 in-wg 1583 0.17 hp 1725 208 V 1 ECM YES MECHANICAL NO GREENHECK SQ-95-VG 1, 2
EF-2 NTWRK (132) CEILING EXHAUST 250 CFM FORWARDCURVED
CENTRIFUGAL
0.25 in-wg 1000 0.10 hp 1000 115 V 1 NO YES MECHANICAL NO GREENHECK SP-A 250 1, 3
MECHANICAL EQUIPMENT SCHEDULE - GRILLES, REGISTERS AND DIFFUSERS
UNIT TAG
TYPE SERVICE TO MOUNTING DATA CONSTRUCTION DATA LINEAR DEVICE DATA SELECTION BASED ON
REMARKSG R D SA RA EA TA CEILING DUCT WALL SHAPE MATERIAL COLOR
ACCESSORIES PATTERN
# SLOTS SLOT SIZE ACTIVE LENGTH CONTINUOUS MANUFACTURER MODELVOLUME DAMPER REMOTE CABLE OPERATOR 1-W 2-W 3-W 4-W E/R
E-1 X X X SQUARE STEEL PER ARCH. X TUTTLE & BAILEY T75D-LT 1, 2
E-2 X X X RECTANGULAR STEEL PER ARCH. X TUTTLE & BAILEY T75D 1, 2
R-1 X X X SQUARE STEEL PER ARCH. X TUTTLE & BAILEY T75D-LT 1, 2
R-T75D X X X RECTANGULAR STEEL PER ARCH. X TUTTLE & BAILEY T75D 1, 2
S-1A X X X SQUARE, 6" NECK STEEL PER ARCH. X TUTTLE & BAILEY T1100 1, 2
S-1B X X X SQUARE, 8" NECK STEEL PER ARCH. X TUTTLE & BAILEY T1100 1, 2
S-1C X X X SQUARE, 10" NECK STEEL PER ARCH. X TUTTLE & BAILEY T1100 1, 2
S-1D X X X SQUARE, 12" NECK STEEL PER ARCH. X TUTTLE & BAILEY T1100 1, 2
S-2 X X X RECTANGULAR STEEL PER ARCH. X TUTTLE & BAILEY MA 1, 2
S-3 X X X RECTANGULAR ALUMINUM PER ARCH. X TUTTLE & BAILEY AMA 1, 2
S-4 X X X LINEAR ALUMINUM PER ARCH. X 4 1/2" 48" TUTTLE & BAILEY 6000-S-050-4-60 1
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:07 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
SCHEDULES
06/23/2021 -CONSTRUCTION DOCUMENTS
M002
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
INSULATION SCHEDULEAPPLICATION LOCATION THICKNESS (IN.) INSULATION TYPE REMARKS
SUPPLY AIR SYSTEMS (ALL)
AHU TO VAV TERMINAL ALL OUTDOORS 2" EXTERNAL RIGID FIBERGLASS WITH ALUMAGUARD JACKET SPECIFIED IN SECTION 230713
AHU TO VAV TERMINAL CONCEALED: RTU TO TERMINAL BOX 1-1/2" 1 LB/CF. DENSITY BLANKET SPECIFIED IN SECTION 230713
AHU TO VAV TERMINAL EXPOSED: RTU TO TERMINAL BOX 1-1/2" 1 LB/CF. DENSITY BLANKET SPECIFIED IN SECTION 230713
VAV TERMINAL TO SUPPLY GRILLE ALL 1-1/2" 1 LB/CF. DENSITY BLANKET SPECIFIED IN SECTION 230713
RETURN SYSTEMS (ALL)
GRILLE TO RTU CONCEALED 1-1/2" 1 LB/CF. DENSITY BLANKET (NONE IF PLENUM RETURN SYSTEM) SPECIFIED IN SECTION 230713
GRILLE TO RTU ALL OUTDOORS 2" EXTERNAL RIGID FIBERGLASS WITH ALUMAGUARD JACKET SPECIFIED IN SECTION 23071
SPECIFICATION SECTIONS: 230713 - DUCT INSULATION
SCHEDULE - AIR VOLUME CONTROL VALVE SCHEDULEIDENTITY DATA COOLING AIRFLOW REHEAT DATA - AIRSIDE ELECTRICAL DATA SELECTION BASED ON
REMARKSDESIGNATION SERVICE TYPE INLET SIZE MAXIMUM MINIMUM
MAXIMUMHEATINGAIRFLOW EAT LAT
AIRSIDEPRESSURE
DROP
ELECTRICREHEAT COIL
VOLTAGE PHASE FREQUENCY MANUFACTURER MODELCAPACITY
TB-01 101 CONFERENCE SINGLE DUCT - ELEC. REHEAT 8" 300 CFM 100 CFM 300 CFM 55.0 °F 86.5 °F 0.30 in-wg 3.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-2a 110 OPEN OFFICE SINGLE DUCT - ELEC. REHEAT 10" 665 CFM 150 CFM 335 CFM 55.0 °F 92.5 °F 0.30 in-wg 4.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-2b 110 OPEN OFFICE SINGLE DUCT - ELEC. REHEAT 10" 665 CFM 150 CFM 335 CFM 55.0 °F 92.5 °F 0.30 in-wg 4.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-2c 110 OPEN OFFICE SINGLE DUCT - ELEC. REHEAT 10" 665 CFM 150 CFM 335 CFM 55.0 °F 92.5 °F 0.30 in-wg 4.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-2d 110 OPEN OFFICE SINGLE DUCT - ELEC. REHEAT 10" 665 CFM 150 CFM 335 CFM 55.0 °F 92.5 °F 0.30 in-wg 4.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-03 HR OFFICES SINGLE DUCT - ELEC. REHEAT 6" 200 CFM 65 CFM 130 CFM 55.0 °F 91.3 °F 0.30 in-wg 2.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-04 MARKETING OFFICES SINGLE DUCT - ELEC. REHEAT 6" 200 CFM 65 CFM 160 CFM 55.0 °F 94.3 °F 0.30 in-wg 2.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-05 108 COLLAB SINGLE DUCT - ELEC. REHEAT 10" 515 CFM 170 CFM 485 CFM 55.0 °F 90.7 °F 0.30 in-wg 5.5 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-06 ENVIRONMENTAL OFFICES SINGLE DUCT - ELEC. REHEAT 6" 155 CFM 50 CFM 155 CFM 55.0 °F 95.6 °F 0.30 in-wg 2.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-07 121 OPEN OFFICE SINGLE DUCT - ELEC. REHEAT 8" 425 CFM 140 CFM 240 CFM 55.0 °F 94.3 °F 0.30 in-wg 3.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-08 122 BREAK/ALL HANDS SINGLE DUCT - ELEC. REHEAT 10" 690 CFM 230 CFM 560 CFM 55.0 °F 91.5 °F 0.30 in-wg 6.5 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-09 123 PLOT ROOM SINGLE DUCT - ELEC. REHEAT 6" 315 CFM 65 CFM 160 CFM 55.0 °F 94.3 °F 0.30 in-wg 2.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
TB-10 124 LAB SINGLE DUCT - ELEC. REHEAT 8" 680 CFM 125 CFM 450 CFM 55.0 °F 89.9 °F 0.30 in-wg 5.0 kW 208 V 3 60 Hz TITUS DESV ER 1, 2
SCHEDULE - ENERGY RECOVERY WHEEL
DESIGNATION SERVICE TO
OUTDOOR AIR SUPPLY AIR EXHAUST AIR (FROM BUILDING) EXHAUST AIR (TO BUILDING DISCHARGE) MOTOR DATA SELECTION BASED ON
REMARKSEAT SUMMER
(DB)EAT SUMMER
(WB)EAT WINTER
(DB)EAT WINTER
(WB)SUMMER LAT
(DB)SUMMER LAT
(WB)WINTER LAT
(DB)WINTER LAT
(WB)SUMMER EAT
(DB)SUMMER EAT
(WB)WINTER EAT
(DB)WINTER EAT
(WB)SUMMER LAT
(DB)SUMMER LAT
(WB)WINTER LAT
(DB)WINTER LAT
(WB) RPMMOTORPOWER MANUFACTURER MODEL
ERW-1 RTU-1 91.0 °F 74.0 °F 10.0 °F 9.0 °F 81.6 °F 68.2 °F 60.5 °F 47.5 °F 80.0 °F 67.0 °F 70.0 °F 53.0 °F 90.6 °F 73.6 °F 12.1 °F 12.0 °F 1075 0.167 hp AAON EERC-5262C 1, 2
SCHEDULE - PACKAGED DX AIR HANDLING UNIT
DESIGNATION LOCATION SERVICE
SUPPLY FAN DATA DX COOLING COIL DATA HEATING DATA
FILTER MERVRATING
ELECTRICAL DATA SELECTION BASED ON
REMARKS
AIRFLOW STATIC PRESSURE FAN MOTOR
AIRFLOW
EAT LAT CAPACITY
EERPRESSURE
DROP
NATURAL GAS
AIRFLOW EAT LAT VOLTAGE PHASE MCA MOCPSTARTER /
DISCONNECT PROVIDED BY MANUFACTURER MODELMAX MIN OA MIN EXTERNAL TOTAL QUANTITY POWER RPM VOLTAGE PHASE FLA VFD DB WB DB WB TOTAL SENSIBLEINPUT
CAPACITYOUTPUT
CAPACITY
RTU-1 LOW ROOF 1ST FLOOR 5000 CFM 1760 CFM 1450 CFM 3.500 in-wg 4.560 in-wg 1 7.5 hp 1760 208 V 3 24.2 A YES 5000 CFM 81.6 °F 68.2 °F 53.5 °F 53.4 °F 218400 Btu/h 148600 Btu/h 12.4 0.100 in-wg 270000 Btu/h 218700 Btu/h 4400 CFM 60.5 °F 106.5 °F 13 208 V 3 111.0 A 125.0 A DISCONNECT MECH AAON RN-018 1, 2, 3, 4, 5
MECHANICAL EQUIPMENT SCHEDULE - ELECTRIC HEATERS
DESIGNATION TYPE TOTAL CAPACITY
AIR DATA ELECTRICAL DATA SELECTION BASED ON
REMARKSAIR FLOWLEAVING AIR
TEMPERATURE KW VOLTAGE PHASE FREQUENCY MANUFACTURER MODEL
UH-1 WALL (RECESSED) 6800 Btu/h 160 CFM 130 °F 2.0 kW 208 V 1 60 Hz MARKEL H3052T2DWB 1, 2, 3
06/23/2021
1 2 3 4
5 6 7 8 9
10
23.002
(E) UH
(E) RTU(ON ROOF)
(E) RTU(ON ROOF)
(E) RTU(ON ROOF)
23.003
23.004
23.004
23.004
2D
M111
23.007
(E) CU
23.001
23.008
1 2 3 4
5 6 7 8 9
10
23.005
23.006
1. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
2. PATCH ALL CUTTING OR DRILLING OF FINISHED WALLS, CEILINGS AND FLOORS. 3. UNLESS SPECIFICALLY NOTED, REMOVE ALL HVAC SYSTEMS IN THEIR ENTIRETY.
THIS INCLUDES BUT IS NOT LIMITED TO EQUIPMENT, THERMOSTATS, TERMINAL UNITS, DUCTWORK, PIPING, AIR DEVICES, AND ALL ASSOCIATED COMPONENTS AND SUPPORTS. PATCH AND REPAIR ALL AREAS THAT ARE TO REMAIN WHERE ITEMS WERE ATTACHED OR SUPPORTED.
4. COORDINATE EXTENT OF DEMOLITION WITH NEW WORK IN ALL LOCATIONS WHERE MECHANICAL COMPONENTS ARE TO REMAIN.
5. CONTRACTOR TO REMOVE ANY MECHANICAL COMPONENTS WITHIN WALLS INDICATED TO BE DEMOLISHED ON ARCHITECTURAL DEMOLITION PLANS.
6. PROTECT ALL EQUIPMENT TO REMAIN FROM DAMAGE DURING DEMOLITION. PROVIDE TEMPORARY COVERS AND CAP ENDS OF ALL PIPING AND DUCTWORK AT COMPLETION OF PARTIAL DEMOLITION.
7. COORDINATE WITH ELECTRICAL DEMOLITION BEFORE REMOVING DUCTWORK CONTAINING SMOKE DETECTORS OR EQUIPMENT, DEVICES, AND SYSTEMS HAVING ELECTRICAL CONNECTIONS.
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:09 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
FIRST FLOOR PLAN -DEMOLITION
06/23/2021 -CONSTRUCTION DOCUMENTS
M101
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
N
S
W
E160.00°
0' 4' 8' 24'20'16'12'
1/8" =1'-0"
SCALE: 1/8" = 1'-0"6A FIRST FLOOR HVAC PLAN - DEMOLITION
KEY NOTE LEGEND
23.001 ALL DUCTWORK AND DIFFUSERS IN THIS AREA ARE EXISTING TO REMAIN.
23.002 REMOVE AND RETAIN EXISTING WAREHOUSE HEATER. EXISTING EXHAUST FLUEAND FUEL SUPPLY PIPING SHALL REMAIN. CLEAN AND REFURBISH HEATER TOLIKE-NEW CONDITION. RELOCATE TO LOADING AREA (114), AS INDICATED IN NEWWORK PLAN. RECONNECT TO EXISTING EXHAUST FLUE AND FUEL PIPING.
23.003 EXISTING EXHAUST DUCT UP TO EXISTING EXHAUST FAN. TO REMAIN.
23.004 EXISTING SUPPLY AND RETURN DUCTS UP TO EXISTING ROOFTOP UNIT TOREMAIN. CONTRACTOR SHALL VERIFY EXACT SIZE/LOCATIONS.
23.005 DISCONNECT AND REMOVE EXISTING ROOFTOP UNIT AND ALL CONNECTEDDUCTWORK, CONTROLS, AND ACCESSORIES. STRUCTURAL DUNNAGE SHALLREMAIN FOR REUSE DURING NEW CONSTRUCTION.
23.006 DISCONNECT AND REMOVE EXISTING UTILITY SET EXHAUST FAN AND ALLCONNECTED DUCTWORK, CONTROLS, AND ACCESSORIES. PATCH AND SEALROOF OPENING.
23.007 RECOVER REFRIGERANT, THEN DISCONNECT EXISTING CONDENSING UNIT ANDSTORE FOR REUSE IN NEW CONSTRUCTION.
23.008 REMOVE EXISTING RETURN GRILLE AND REINSTALL IN NEW CEILING GRID INNEW CONSTRUCTION PHASE.
SCALE: 1/16" = 1'-0"6D ROOF HVAC PLAN - DEMOLITION
GENERAL NOTES - DEMOLITION
06/23/2021
1 2 3 45 6 7
8 9
10
T
SPRINKLER
103A
CONFERENCE
101
RECEPTION
100
OPENOFFICE
110
LOADINGAREA
114
LAB
124
HR - J.GILBERT
105
HR - H.GODSEY
120
ACCT - L.DAVIS
106
SDI - C.HOWARD
119
MARKETING -BD MGR
107
UTILITIESFUTURE
118
MARKETING -BD MGR
108
TEAM ROOM
117
STORAGE
115
SPRINKLERCLOSET
103
WELLNESS
139
STORAGE
140
PANELROOM
142
WOMEN'S RR
137
EXISTINGMEN'S RR
141
IT
130
FUTUREOFFICE
135
IT STORAGE
133
FUTUREOFFICE
134
SURVEY
127
GEOTECH
126
JANITOR
131NTWRK
132UNISEX RR
136
NOT INCONTRACT,
VIF
500
OPENOFFICE
125
OPENOFFICE
121
ENVIR - S.NATHELLA
112
ENVIR - M.LAWLESS
116
PLOT ROOM
123
COLLAB
109
BREAK / ALLHANDS
122
CLOSET
129
CLOSET
128
CORRIDOR
138(w)
CORRIDOR
102
CORRIDOR
111
23.101
23.10123.101
6x6 S-2
60 CFM
6x6 S-2
30 CFM
6ø S-1A
70 CFM
6ø S-1A
55 CFM
8ø S-1B
140 CFM
8ø S-1B
215 CFM
8ø S-1B
105 CFM
(TYP. 4)
6ø S-1A
50 CFM
6ø S-1A
100 CFM
6ø S-1A
100 CFM
8ø S-1B
200 CFM
6ø S-1A
90 CFM
6ø S-1A
50 CFM
6x6 S-3
50 CFM
TB-01
6ø S-1A
55 CFM6ø S-1A
55 CFM
6ø S-1A
55 CFM
6ø S-1A
55 CFM
TB
-2a
TB
-2b
TB
-2c
TB
-2d
10ø S-1C
295 CFM10ø S-1C
295 CFM
10ø S-1C
295 CFM
10ø S-1C
295 CFM
23.105
23.10523.10523.105
10ø SA
14x14 SA
(E) UH
(E) RTU(ON ROOF)
(E) RTU(ON ROOF)
(E) RTU(ON ROOF)
23.108
23.109
6x6 E-2
70 CFM
8x8 EXH
14x14 SA12x10 SA
14x14 SA
10x10 SA
6ø S-4
150 CFM
6ø S-4
150 CFM
6ø S-1A
105 CFM
8ø S-1B
170 CFM
8ø S-1B
150 CFM
10ø S-1C
340 CFM
6ø S-1A
50 CFM
6ø S-1A
60 CFM
6ø S-1A
55 CFM
10ø S-1C
260 CFM
10ø S-1C
260 CFM6ø S-1A
55 CFM
6ø S-1A
85 CFM6ø S-1A
55 CFM
6ø S-1A
55 CFM
8x8 SA
14x14
8x8 SA 6x6 R-1
45 CFM
23.102
23.102
23.102
15x15 R-1
750 CFM
6x6 R-1
45 CFM6x6 R-1
80 CFM6x6 R-1
90 CFM
6x6 R-1
90 CFM
12ø SA14x14 SA16x16 SA12ø SA
12x12 SA
12x14 SA
8x8 SA
EF-1
14x14 E-1
175 CFM
18x12 EXHAUST LOUVERBASED ON GREENHECK ESD-435MINIMUM 1.0 SQ. FT. FREE AREA.PROVIDE BACKDRAFT DAMPER.
BDD
TB
-06
TB
-03
TB
-04
TB
-05
8x8 S
A
12x10 S
A
10x12 S
A
TB
-09
TB-10
TB-07
10x8 SA
6ø SA
8ø SA
10ø SA
6ø SA 10ø SA
6ø SA
10ø SA
10ø SA
12ø SA
8ø SA
10ø S-1C
295 CFM
10ø S-1C
295 CFM
10ø S-1C
295 CFM
10ø S-1C
295 CFM
8x10 SA
6x6 RA14x14 RA
8x8 SA8x8 SA
8x8 SA
10x10 SA
12x12 SA
10ø SA
10ø SA6ø SA
6ø SA
6ø SA
6ø SA
6ø SA
6ø SA6ø SA
10ø SA 10ø SA
14x14 SA14x14 SA
14x14 SA
10ø SA 10ø SA
TB-08
10x10 SA
TB-08
T
T
TB-04
TB-03
T
TTB-01
TB-2a
T T T T
TB-2b TB-2c TB-2d
TB-05 T
T
TB-06
TB-10TB-07 T T TB-09
T
T
T
T
T
(TYP. 2)
14x14 SA
8x8 SA
6x8 RA 6x6 RA
2D
M111
22x16 SA
EF-2
UH-112ø S-1D
390 CFM
UH-1
23.107
23.107
(TYP. 2)
DISCHARGE TO PLENUM.
T EF-2
23.110
(E) CU
6ø S-1A
100 CFM
8x8 S
A
(TYP. 2)
10x8 SA
6x6 S-2
30 CFM
(E) AHU
23.112
23.10923.109
23.11723.117
6x6 E-2
30 CFM
8x8 EXH
8ø S-1B
200 CFM
14x12 RA
14x14 RA
23.1186x6 R-1
100 CFM
15x15 R-1
905 CFM
23.103
28x20 RA
23.119
1 2 3 4
5 67
8 9
10
RTU-1
(E) FAN
(E)RTU
(E)RTU(E)RTU
23.104
2D
M111
23.113 23.114
23.116 23.116
23.115
UNDERSIDE OF ROOF
18' - 1"LOADING DOCK SIDES
15' - 11"
UNDERSIDE OF
STRUCTURE
11' - 6"
RTU-1
20x50 RA
20x38 SA
23.111
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS AND APPLICABLE CODES AND REGULATIONS.
4. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING DIMENSIONS PRIOR TO FABRICATION.
5. WORK SHALL BE ACCURATELY LAID OUT WITH REFERENCE TO THE ARCHITECTURAL DRAWINGS AND IN COOPERATION WITH OTHER TRADES, WHICH SHALL AFFORD MAXIMUM ACCESSIBILITY FOR OPERATION, MAINTENANCE AND HEADROOM. FAILURE TO COORDINATE WORK WITH OTHER TRADES SHALL NOT BE CONSIDERED AS A BASIS FOR EXTRA COST CHANGES.
6. WHERE PLENUMS ARE USED FOR SUPPLY, RETURN, EXHAUST, RELIEF OR VENTILATION SYSTEMS, MATERIALS WITHIN THE PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
7. DIMENSIONS SHOWN ON DRAWINGS FOR DUCTWORK ARE INSIDE CLEAR.8. ALL DUCTWORK, INCLUDING FIRE DAMPERS, SHALL BE SEALED AND TESTED FOR
LEAKS PRIOR TO COVERING WORK.9. PATCH ALL CUTTING OR DRILLING OF FINISHED WALLS, CEILINGS AND FLOORS.10. DIFFUSER AND GRILLE LOCATIONS TO BE COORDINATED WITH ARCHITECTURAL
CEILING PLAN. ANY CEILING MOUNTED DIFFUSERS OR GRILLES WHICH DO NOT MATCH CEILING TILE SIZES ARE TO BE MOUNTED IN CENTER OF TILE.
11. CONTRACTOR SHALL INSTALL ANY BALANCING DEVICE NECESSARY TO ACHIEVE PROPER ADJUSTING AND BALANCING OF MECHANICAL SYSTEMS.
12. REFRIGERANT PIPING SHALL BE SIZED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
13. RUNOUTS TO DIFFUSERS / GRILLES SHALL BE THE SAME SIZE AS THE DIFFUSER / GRILLE NECK SIZE UNLESS OTHERWISE NOTED.
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:13 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
FIRST FLOOR AND LOWROOF PLANS - NEW WORK
06/23/2021 -CONSTRUCTION DOCUMENTS
M111
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
SCALE: 1/8" = 1'-0"6A FIRST FLOOR HVAC PLAN - NEW WORK
KEY NOTE LEGEND
23.101 CONNECT TO EXISTING SPLIT SYSTEM AIR HANDLING UNIT SERVINGRECEPTION AREA.
23.102 CONNECT TO EXISTING ROOFTOP UNIT SUPPLY/RETURN DUCT RISERS.CONTRACTOR SHALL VERIFY EXACT SIZE/LOCATION AND MAY BE REQUIREDTO ADJUST ROUTING ACCORDINGLY.
23.103 CAP FOR FUTURE VAV BOX IN LOADING AREA.
23.104 SET RTU-1 ON EXISTING STRUCTURAL DUNNAGE. CONTRACTOR TO REUSEEXISTING ROOF PENETRATION TO ROUTE SUPPLY AND RETURN DUCTDOWN INTO BUILDING (SEE DETAIL ON M501). SET UNIT TO MAINTAINMINIMUM 10'-0" CLEARANCE FROM EXISTING EXHAUST FAN.
23.105 SLOPE DUCT DOWN TO FOLLOW SLOPE OF ROOF.
23.107 PROVIDE 2KW, 208V MARKEL ELECTRIC UNIT HEATER. MODEL NUMBER:H3052T2DWB. ELECTRIC HEATER TO BE WALL RECESSED.
23.108 EXISTING UNIT HEATER. REINSTALL IN LOADING AREA (114). RECONNECTTO EXISTING EXHAUST FLUE AND FUEL SUPPLY PIPING. MATCH EXISTINGDUCT / PIPE MATERIALS AND SIZES.
23.109 BALANCE EXISTING EXHAUST GRILLES SO THAT EACH RESTROOM HAS 150CFM OF EXHAUST AIRFLOW.
23.110 RECONNECT CONDENSING UNIT STORED DURING DEMOLITION PHASE.EXTEND REFRIGERANT PIPING INTO BUILDING AND RECONNECT TOEXISTING AIR HANDLER. RECHARGE REFRIGERANT AND PROVIDE NEW LINEDRIER FILTER PER MANUFACTURER RECOMMENDATIONS.
23.111 ROUTE NEW SUPPLY AND RETURN DUCT WITHIN EXISTING ROOF OPENING.COORDINATE FINAL DUCT SIZE WITH EXISTING ROOF OPENING. SEALAROUND DUCTS AND INSULATION PER DETAIL ON M501.
23.112 BALANCE UNIT TO 1000 CFM SUPPLY AIR, 100 CFM OUTSIDE AIR, AND 900CFM RETURN AIR.
23.113 BALANCE ROOFTOP UNIT TO 1200 CFM SUPPLY AIR, 150 CFM OUTSIDE AIR,AND 1050 CFM RETURN AIR.
23.114 BALANCE ROOFTOP UNIT TO 1105 CFM SUPPLY AIR, 100 CFM OUTSIDE AIR,AND 1005 CFM RETURN AIR.
23.115 BALANCE ROOFTOP UNIT TO 1200 CFM SUPPLY AIR, 245 CFM OUTSIDE AIR,AND 955 CFM RETURN AIR.
23.116 CONTRACTOR TO PROVIDE OUTSIDE AIR INTAKE HOOD AND DAMPERCOMPATIBLE WITH TRANE 4YCC4036 ROOFTOP UNIT.
23.117 CONNECT 8" DUCT TO EXISTING SUPPLY DIFFUSER IN RESTROOM. BALANCEEACH DIFFUSER TO TO 100 CFM.
23.118 BALANCE EXISTING DIFFUSERS IN THIS AREA TO A TOTAL OF 1075 CFM.
23.119 REINSTALL EXISTING RETURN GRILLE REMOVED DURING DEMO PHASE.
SCALE: 1/8" = 1'-0"6D ROOF PLAN - NEW WORK
N
S
W
E160.00°
0' 4' 8' 24'20'16'12'
1/8" =1'-0"
SCALE: 1/8" = 1'-0"2D RTU DUCT SECTION
GENERAL NOTES - MECHANICAL
06/23/2021
FLEXIBLE DUCT - SAME DIAMETER AS DIFFUSER INLET. 5'-0" MAXIMUM LENGTH,FULLY SUPPORTED TO PREVENT COLLAPSE.
45° TAKEOFF WITH MANUAL VOLUME DAMPER.
DUCT STRAP HANGER, ATTACHED TO STRUCTURE. PROVIDE ENOUGH
HANGERS TO ENSURE PROPER SUPPORT TO PREVENT FLEXIBLE
DUCT COLLAPSE.
CEILING
CEILING DIFFUSER
SUPPLY DUCT
R = 1.5 x DUCT DIAMETER
VD
90° TEE
NOTE: TEE APPLIES TO BOTH SUPPLY AND RETURN
(PREFERED OFFSET)
90° RADIUS ELBOWS
DUCT OFFSETS
NOTE: USE WITH DUCTS WITH WIDTH (W) LESS THAN OR EQUAL TO 12". FOR WIDTH (W) GREATER THAN 12", USE MITERED ELBOW WITH VANES.
ROUND DUCT TAKEOFF
BRANCH DUCT OR DIFFUSER RUNOUT DUCT
MAIN TRUNK
CONNECTION LENGTH EQUAL TO 25% BRANCH DUCT WIDTH.
SUPPLY
RETURN / EXHAUST
D
D
1.5 x D
X Y
YX
20° MAX
W
W WW
WW
R=
W
R=
Wx2
W
W
R=WR=
Xx2
(MINIMUM 4")
RECTANGULAR DUCT TAKEOFF
(ACCEPTABLE WHERE ROOM IS NOT AVAILABLE FOR FULL RADIUS BENDS)
DUCT TAKEOFF FROM RECTANGULAR MAIN
ALL THREADED GALVANIZED
HANGER RODS
TOP VIEW
SIDE VIEW
VAV BOX
SHEET METAL DUCT RUN-OUT, SIZE AS SHOWN ON DRAWINGS.
45° LOW LOSS TAP
INSTALL A MINIMUM OF 3 DIAMETERS OF STRAIGHT RUN
OF DUCT AT INLET OF BOX.
LOW PRESSURE DUCT TO DIFFUSERS. SIZE AS
SHOWN ON DRAWINGS.
VAV BOX
NOTE:THIS DETAIL APPLIES TO ALL TYPES OF TERMINAL BOXES.
SHEET METAL CLOSURE BETWEEN DUCTS
ROOF CURB BASE
ROOFING SYSTEM
DUCT INSUL.
FULLY ADHERED ROOFING MEMBRANE
DUCT WATERPROOFING OVERLAPPED AND SEALED TO
ROOFING BASE FLASH.
DUCT WATERPROOFING MEMBRANE
DUCT WALL
NOTE: DUCT INSULATION AND WATERPROOFING REMOVED FOR CLARITY.
PRE-FAB INSULATED ROOF CURB
ROOF DECK
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:14 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
DETAILS
06/23/2021 -CONSTRUCTION DOCUMENTS
M501
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
NOT TO SCALE
2D CEILING DIFFUSER DUCT CONNECTION DETAIL
NOT TO SCALE
2B LOW VELOCITY DUCT FITTINGS DETAIL
NOT TO SCALE
2A TERMINAL BOX DETAILNOT TO SCALE
4A DUCT PENETRATION DETAIL - MULTIPLE DUCTS THROUGH ROOF
06/23/2021
NC
ENERGY RECOVERY WHEEL
NC
CC
NO
GAS REFRIGERANT
LIQUID REFRIGERANT
OUTSIDE AIR
OA ENTHALPYGLOBAL
EXHAUST AIR
PRE-CONDITIONED OUTDOOR AIR
ENERGYRECOVERY
WHEELMOTOR
EXHAUST FAN
PF-MERV 8
PF-MERV 8
RETURN AIR DAMPER
OUTSIDE AIR UNITISOLATION DAMPER
EXHAUST AIR UNITISOLATION DAMPER
HEAT WHEELBYPASSDAMPER
T
AI
DP
AI
SUPPLY FAN
VFD
AO
V
AO
FZ
DI
T
AI
DP
AI
D
AO
X SD
DI
T/H
AI
T/H
AI
CFM
AI
D
AO
T/H
AI
S/S
DO
CS
DI
ALM
DI
MAGNEHELICS(TYP)
MAGNEHELICS (TYP)
D
AO
D
DO
VFD
AO
RETURN AIR
SUPPLY AIR
NATURAL GAS SUPPLY
V
AO
NATURAL GASHEATEXCHANGER
RTU-1 SEQUENCE OF OPERATIONS:VARIABLE VOLUME ROOFTOP UNIT WITH TOTAL ENERGY WHEEL AND TERMINAL BOXES
NOTE: UNITS SHALL BE EQUIPED WITH UNITARY CONTROLS. NO BAS INTEGRATION REQUIRED. PROVIDE CONTROL POINTS AS SHOWN IN FLOW DIAGRAM TO INTEGRATE WITH UNITARY CONTROLS.
A. GENERAL1. THE UNIT IS DESIGNED TO CONDITION AND VENTILATE THE BUILDING AND
SUPPORTING SPACES. WHEN THE UNIT IS NO SUPPLYING AIR TO THE SPACE, THE UNIT ISOLATION DAMPERS SHALL BE CLOSED.
2. THE SEQUENCE DESCRIBED BELOW CONSISTS OF THREE MODES: SHUTDOWN, OCCUPIED COOLING OR HEATING, AND UNOCCUPIED COOLING OR HEATING.
3. SHUTDOWN MODE IS INTENDED TO DESCRIBE STOPPING THE RTU FANS IN AN ORDERLY MANNER, CLOSING DAMPERS, AND INITIATING SHUTDOWN STATUS AT THE CONTROLLER.
4. OCCUPIED COOLING OR HEATING MODE IS DETERMINED BY THE OCCUPANCY SCHEDULE AND ADJUSTED BY THE OPTIMAL START PROGRAM FROM THE CONTROLLER.
5. EACH FAN SHALL HAVE AN INDEPENDENT VFD.6. IT IS THE INTENT FOR ALL VFD'S TO OPERATE VIA COMMON COMMUNICATION
PROTOCOL. PARAMETERS SHALL BE AVAILABLE AT THE CONTROLLER. 7. ALL SAFETIES OPERATE REGARDLESS OF VFD BYPASS SELECTION, IF PROVIDED.
G. SEQUENCE OF OPERATION - ENTHALPY WHEEL1. THE CONTROLLER SHALL START/STOP WHEEL AND PROVIDE STATUS AND ALARMS
FOR ALL OPERATING FUNCTIONS.2. THE CONTROLLER SHALL SEND A START SIGNAL AND A SUPPLY TEMPERATURE
SETPOINT. 3. WHEEL SHALL STOP AND WHEEL BYPASS DAMPER SHALL OPEN WHEN IN THE
ECONOMIZER SEQUENCE (WHEN OUTDOOR AIR ENTHALPY IS LESS THAN EXHAUST AIR ENTHALPY) OR WHEN FREEZING CONDITIONS ARE DETECTED.
4. ALARMS:a. NO ROTATION ALARMb. REVERSE ROTATION ALARMc. EACH ALARM CAN BE SEPARATELY SET AS A CRITICAL OR A STATUS ALARM.
F. NOTIFICATIONS1. IF THE TEMPERATURE AFTER NATURAL GAS BURNER (LAT) FALLS BELOW 42F (ADJ.),
PROVIDE WARNING TO THE CONTROLLER.2. IF AN ALARM CONDITION IS REGISTERED BY THE UNIT FREEZESTAT (SETPOINT 37F),
THE UNIT SHALL REVERT TO SHUTDOWN MODE.3. IF THE PRODUCTS OF COMBUSTION ARE SENSED BY THE UNIT SMOKE DETECTOR,
THE SYSTEM SHALL REVERT TO SHUTDOWN MODE.4. THE CONTROL PROGRAM SHALL BE CONFIGURED TO PROHIBIT SIMULTANEOUS
OPERATION OF THE GAS BURNER AND COOLING COILS.5. IF RETURN AIR HUMIDITY LEVELS RISE ABOVE 60% (ADJ.), THE UNIT HIGH HUMIDITY
SENSOR SHALL ISSUE AN ALARM TO THE CONTROLLER BUT THE UNIT WILL NOT SHUT DOWN.
6. IF FAN DISCHARGE PRESSURE IN THE UNIT EXCEEDS THE PRESSURE RATING OF THE DUCTWORK, THE FAN SHALL SHUTDOWN.
7. IF FILTER DIFFERENTIAL PRESSURE RISES ABOVE SETPOINT, A DIRTY FILTER INDICATION WILL BE GENERATED AT THE CONTROLLER.
E. SMOKE SHUTDOWN1. IN THE EVENT THAT SMOKE IS PRESENT IN THE RETURN AIR DUCT:
a. AN AUXILIARY CONTACT IN THE RETURN AIR DUCT SMOKE DETECTOR SHALL OPEN DE-ENERGIZING THE AUTO-MAINTAINED POWER SUPPLY TO THE FAN'S STARTER OR VFD OF THE RTU CAUSING THE FAN TO SHUT OFF.
b. THE CONTROLLER SHALL SHUT DOWN THE RELIEF AIR FAN UPON SHUTDOWN OF THE SUPPLY AIR FAN IN THE UNIT.
c. SMOKE DETECTOR CONTACTS SHALL BE WIRED IN SERIES IN THE FAN MOTOR STARTER CIRCUIT.
d. THE MECHANICAL CONTRACTOR SHALL PROVIDE AND TERMINATE THE HARD-WIRED CONNECTIONS FROM ANY DETECTOR RELAY (FURNISHED BY FIRE ALARM CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR) TO THE ASSOCIATED FAN TO BE SHUT DOWN.
C. OCCUPIED MODE1. HEATING OR COOLING:
a. AT THE PREDETERMINED OPTIMUM START TIME, AS DETERMINED BY THE CONTROLLER (SCHEDULE), THE RTU WILL BE ENABLED. THE RTU RETURN DAMPER REMAIN OPEN FULLY. THE EXHAUST AIR AND OUTSIDE AIR DAMPERS SHALL REMAIN CLOSED. MORNING WARMUP OR COOLDOWN SEQUENCE TO BE INITIATED.
b. THE CONTROLLER SHALL NEXT COMMAND RTU TO RUN AFTER ISOLATION DAMPER END SWITCHES INDICATE ISOLATION DAMPERS ARE OPEN. THE UNIT ISOLATION DAMPERS SHALL REMAIN CLOSED WHEN THE UNIT IS NOT RUNNING.
c. THE SUPPLY FAN VFD SHALL MODULATE THE SUPPLY FAN SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT (ADJ, SEE SCHEDULE) AS SENSED BY A STATIC PRESSURE SENSOR LOCATED 2/3 WAY DOWN THE SUPPLY DUCT.
d. THE EXHAUST FAN SHALL FOLLOW THE SAME SCENARIO, MAINTAINING THE BUILDING STATIC PRESSURE. NEXT THE CONTROLLER WILL INITIATE EITHER AN OCCUPIED MORNING WARMUP OR OCCUPIED MORNING COOLDOWN.
e. DURING MORNING WARMUP, THE CONTROLLER SHALL MODULATE THE NATURAL GAS BURNER TO ACHIEVE DISCHARGE SETPOINT. AFTER THE DISCHARGE SETPOINT IS ACHIEVED AND RETURN AIR FROM THE TERMINAL ZONES REACHES THE PREDETERMINED ROOM SETPOINT (69oF, ADJ.), THE CONTROLLER SHALL COMMAND THE TWO POSITION, MINIMUM OA DAMPER OPEN.
f. DURING MORNING COOLDOWN, THE COMPRESSOR SHALL CYCLE ON AND OFF TO MAINTAIN DISCHARGE AIR TEMPERATURE AT DISCHARGE TEMPERATURE SETPOINT (STARTUP SETPOINT 63F, ADJ.). THE RTU CONTROLLER SHALL RESET THE SUPPLY AIR TEMPERATURE SETPOINT 1oF COLDER EVERY 10 MINUTES (ADJ.) UNTIL THE SUPPLY TEMPERATURE IS AT THE OPERATING SETPOINT TEMPERATURE (INITIAL SETPOINT 59F, ADJ.). IF THE RETURN AIR RELATIVE HUMIDITY RISES ABOVE 50%, THE 10-MINUTE CYCLE SHALL REPEAT AT THE SAME TEMPERATURE.
g. THE EXHAUST AIR FAN SHALL BE MODULATED TO MAINTAIN SPACE STATIC PRESSURE AS SENSED BY THE STATIC DIFFERENTIAL SENSOR (INITIAL SETPOINT +0.05" W.C., ADJ.). THE RETURN AIR DAMPER AND OUTSIDE AIR DAMPER SHALL OPERATE INVERSELY TO MAINTAIN A NEGATIVE AHU "MIXING BOX" SETPOINT (-0.02" W.C., ADJ.). DURING NORMAL OPERATION, THE EXHAUST AIR FAN SHALL OPERATE AT MINIMUM OA FLOWRATE.
h. THE DEFAULT MODE FOR OUTSIDE AIR IS THROUGH THE ENERGY RECOVERY WHEEL.
i. WHEN OUTSIDE AIR IS AVAILABLE FOR COOLING PURPOSES (ECONOMIZER CYCLE, BASED ON OUTDOOR AIR ENTHALPY COMPARED TO THE RETURN AIR ENTHALPY), THE OUTSIDE AIR DAMPER, EXHAUST DAMPER, AND ECONOMIZER ISOLATION DAMPER SHALL MODULATE OPEN. THE RETURN AIR DAMPER SHALL MODULATE CLOSED. IN ADDITION, THE ENERGY RECOVERY WHEEL SHALL STOP, THE ENERGY WHEEL BYPASS DAMPERS SHALL OPEN, THE EXHAUST AIR FAN SHALL ADJUST ITS AIRFLOW TO MAINTAIN BUILDING PRESSURE (SETPOINT +0.05" W.C., ADJ.). IF DISCHARGE TEMPERATURE CANNOT MEET DISCHARGE TEMPERATURE SETPOINT, AND THE OA DAMPER HAS REACHED 100% OPEN FOR AN APPROPRIATE TIME, THE DIRECT EXPANSION COIL (COMPRESSOR) WILL ASSIST IN ACHIEVING DISCHARGE SETPOINT. ECONOMIZER SHALL ONLY BE ENABLED WHEN THERE IS NOT A CALL FOR RTU HEATING.
j. ON A RISE IN SUPPLY AIR TEMPERATURE ABOVE SETPOINT AND THE NATURAL GAS BURNER OFF, THE COMPRESSOR SHALL CYCLE ON AND OFF TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT (INITIAL SETPOINT 55oF RESET THE DISCHARGE SETPOINT UPWARDS TO 60oF WHENEVER OA TEMP < 35F, BOTH ADJ.).
k. ON A FALL BELOW SUPPLY AIR TEMPERATURE SETPOINT, AND THE COMPRESSOR IS OFF AND THE OUTSIDE AIR DAMPER IS AT ITS MINIMUM, THE NATURAL GAS BURNER SHALL MODULATE BETWEEN ITS FULLY OPEN AND FULLY CLOSED POSITIONS TO MAINTAIN SUPPLY TEMPERATURE SETPOINT.
B. SHUTDOWN MODE1. WHEN THE UNIT IS INDEXED FOR SHUTDOWN MODE, THE UNIT'S SUPPLY AND
EXHAUST FANS SHALL STOP. THE UNIT'S RETURN AIR DAMPER SHALL OPEN FULLY. EXHAUST AIR AND OUTSIDE AIR ISOLATION DAMPERS SHALL CLOSE.
2. THE COMPRESSOR AND CONDENSER FAN MOTORS SHALL STOP AND THE NATURAL GAS VALVE SHALL CLOSE.
3. A SIGNAL SHALL BE SENT TO THE CONTROLLER INDICATING SHUTDOWN WITH AN ERROR MESSAGE IDENTIFYING THE CONDITION.
4. THE SYSTEM SHALL BE INDEXED TO SHUTDOWN MODE IF ANY ONE OR MORE OF THE FOLLOWING CONDITIONS ARE MET:a. A SHUTDOWN SIGNAL FROM THE CONTROLLER b. AN ALARM FROM THE RTU'S RETURN SMOKE DETECTOR.c. AN ALARM CONDITION FROM THE RTU FREEZESTAT, THE OA DAMPER CLOSES
COMPLETELY AND RETURN DAMPER OPENS COMPLETELY.5. AN ALARM CONDITION FROM THE HIGH DISCHARGE STATIC PRESSURE LIMIT (ADJ.)
DP
AI
BUILDING PRESSURE+0.05" (ADJ)
FF-MERV 13
MAGNEHELICS(TYP)
CFM
AI
D. UNOCCUPIED MODE1. HEATING OR COOLING:
a. WHEN THE CONTROLLER SCHEDULE INDICATES THAT THE BUILDING IS IN UNOCCUPIED MODE, THE SUPPLY AND EXHAUST FAN SHALL STOP, THE EXHAUST AIR AND OUTSIDE AIR DAMPERS SHALL CLOSE, AND THE RETURN DAMPER SHALL OPEN IN FULL RECIRCULATION POSITION.
b. THE SPACE TEMPERATURE SETPOINTS SHALL REVERT TO THEIR SETBACK SETPOINTS (80F COOLING AND 64F HEATING, ADJ.).
c. IF THERE IS A CALL FOR HEATING OR COOLING FROM A ZONE, THE UNIT SUPPLY FAN SHALL MODEULATE TO MAINTAIN THE STATIC PRESSURE SETPOINT. THE SUPPLY FAN SHALL SHUTDOWN ONCE THE ZONE TEMPERATURE IS SATISFIED.
PF-MERV 13
MAGNEHELICS (TYP)
BDD
EXHAUST
SEQUENCE OF OPERATION - GENERAL EXHAUST FANS1. FAN CONTROL (EXISTING RESTROOM FAN)
A. AFTER THE INITIAL START-UP TIME, EXHAUST FANS SHALL RUN CONTINUOUSLY.
B. THE FAN SHALL RUN DURING OCCUPIED TIMES AND SHUT DOWN DURING UNOCCUPIED TIMES.
2. FAN CONTROL (EF-1, LAB OVEN EXHAUST FAN)A. AFTER THE INITIAL START-UP TIME, EXHAUST FANS SHALL RUN
CONTINUOUSLY.B. THE FAN SHALL RUN UNLESS SHUT DOWN BY DISCONNECT SWITCH
SINCE OVENS MAY OPERATE 24/7.3. FAN CONTROL (EF-2)
A. FAN SHALL CYCLE ON/OFF WITH THERMOSTAT LOCATED IN ROOM.B. WHEN ROOM TEMPERATURE EXCEEDS 80F, THE FAN SHALL CYCLE ON.C. WHEN ROOM TEMPERATURE DROPS BELOW 80F, THE FAN SHALL CYCLE
OFF.
ALM ALARM
AFMS /FS AIR FLOW MONITORING STATION
AI ANALOG INPUT
AO ANALOG OUTPUT
VFD VARIABLE FREQUENCY DRIVE
CO2 CARBON DIOXIDE (PARTS PER MILLION)
CFM AIR FLOW (CUBIC FEET PER MINUTE)
CC COOLING COIL
D DAMPER CONTROL
DI DIGITAL INPUT
DO DIGITAL OUTPUT
DP DIFFERENTIAL PRESSURE
ES DAMPER END SWITCH
FS FLOW SWITCH
H HUMIDITY
HP HIGH PRESSURE
L HIGH LEVEL LIMIT
M MOTOR OPERATOR
SD SMOKE DETECTOR
S SPEED
SAP STATIC AIR PRESSURE SENSOR
SF SPEED FEEDBACK
SOAP STATIC OUTSIDE AIR PRESSURE SENSOR
SP STATIC PRESSURE
S/S START / STOP
ST STATUS
T TEMPERATURE
V VALVE
ABBREVIATIONS
ABBREVIATION DESCRIPTION
LEGEND
DESCRIPTIONSYMBOL
X
AI
DPANALOG INPUT - DIFFERENTIAL PRESSURE INDICATION
AI
TANALOG INPUT - TEMPERATURE INDICATION
AI
T/HANALOG INPUT - TEMPERATURE / HUMIDITY INDICATION
AI
CFMANALOG INPUT - UNIT AIRFLOW INDICATION
AO
DANALOG OUTPUT - DAMPER SIGNAL
AO
VANALOG OUTPUT - VALVE SIGNAL
AO
VFDANALOG OUTPUT - VFD SPEED SIGNAL
DI
AFDIGITAL INPUT - AIRFLOW PROOF INDICATION
DI
ESDIGITAL INPUT - END SWITCH INDICATION
DI
FLTDIGITAL INPUT - FILTER STATUS
DI
FZDIGITAL INPUT - FREEZE PROTECTION INDICATION
DI
HHDIGITAL INPUT - HIGH HUMIDITY INDICATION
DI
HPDIGITAL INPUT - HIGH PRESSURE INDICATION
DI
SDDIGITAL INPUT - SMOKE INDICATION
DI
CSDIGITAL INPUT - STATUS INDICATION
DO
DDIGITAL OUTPUT - DAMPER SIGNAL
DO
S/SDIGITAL OUTPUT - START/STOP SIGNAL
SENSOR PROVIDED BY FIRE DEVICE CONTRACTOR
AO
SCRANALOG OUTPUT - SILICON CONTROLLED RECTIFIER SIGNAL
HC HEATING COIL
RHC REHEAT COIL
SPACE THERMOSTAT
PRIMARY AIR
T
AI
CFM
AI
D
AO
T
AI
SUPPLY AIR
LIMITS OF TERMINAL UNIT
ELEC. REHEAT COIL
SEQUENCE OF OPERATIONSVAV TERMINAL UNITS, NO FAN, ELECTRIC REHEAT COIL. NO BAS INTEGRATION REQUIRED
1. UNOCCUPIED: WHEN THE ZONE SERVED BY THE VAV UNIT IS INDEXED FOR UNOCCUPIED OPERATION (AND OPTIMAL START IS NOT IN OPERATION), THE TERMINAL PRIMARY AIR DAMPER SHALL CLOSE.
a. OPTIMAL START WARM-UP: WHEN THE OPTIMAL START PROGRAM CALLS FOR HEAT, THE OUTSIDE AIR DAMPER IN THE MECHANICAL ROOM SHALL BE SHUT, THE PRIMARY AIR DAMPER SHALL OPEN TO ITS MAXIMUM HEATING POSITION, AND THE TERMINAL BOX ELECTRIC HEATER SHALL MODULATE TO HIGHEST OUTPUT SETTING UNTIL THE ZONE SETPOINT IS SATISFIED. THEN THE VAV TERMINAL UNIT SHALL OPERATE AS DESCRIBED UNDER OCCUPIED OPERATION.
b. OPTIMAL START COOL-DOWN: WHEN THE OPTIMAL START PROGRAM CALLS FOR COOL-DOWN OPERATION, THE PRIMARY AIR DAMPER SHALL OPEN TO ITS MAXIMUM COOL CFM SETPOINT UNTIL THE ZONE SETPOINT IS SATISFIED. THE VAV TERMINAL UNIT SHALL OPERATE AS DESCRIBED UNDER OCCUPIED OPERATION.
c. WHEN IN UNOCCUPIED MODE, THE UNIT SHALL CONTROL AT THE HEATING SETBACK SETPOINT OF 64oF (ADJ.), COOLING SETBACK SETPOINT OF 80oF (ADJ.). WHEN ONE OR MORE ZONE TEMPERATURE SENSOR FALLS OUTSIDE OF THE SETBACK SETPOINT, THE ROOFTOP UNIT FAN SHALL START AND ENGAGE HEATING OR COOLING AS REQUIRED.
2. OCCUPIED: WHEN THE UNIT IS INDEXED FOR OCCUPIED OPERATION, THE UNIT SHALL CONTROL AT THE HEATING SETPOINT OF 70oF (ADJ.), COOL SETPOINT OF 74oF (ADJ.). THE PRIMARY AIR DAMPER SHALL MODULATE BETWEEN THE MAXIMUM HEATING AIRFLOW, MINIMUM AIRFLOW, AND MAXIMUM COOLING AIRFLOW AS SHOWN ON DIAGRAM, THIS SHEET (SEE SCHEDULES FOR AIRFLOW NUMBERS). THE ELECTRIC HEATING COIL SHALL MODULATE TO CONTROL SUPPLY AIR TEMPERATURE SETPOINT.
a. HEATING SUPPLY AIR TEMPERATURE SHALL BE LIMITED TO NO MORE THAN 20 DEGREES HIGHER THAN THE SPACE SETPOINT. THIS SHALL NOT APPLY DURING OPTIMAL START WARM-UP MODE.
3. THE CONTROLS SHALL BE ARRANGED FOR PRESSURE INDEPENDENT OPERATION (I.E., THE DAMPER POSITION SHALL BE SET BY THE FLOW SENSOR, AND THE SPACE TEMPERATURE WILL RESET THE FLOW SENSOR SO THAT PRIMARY AIR CAN BE CONTROLLED INDEPENDENT OF CHANGES IN PRIMARY DUCT PRESSURE).
SCR
AO
MAXIMUM SUPPLY AIR TEMPERATURE (LIMIT TO ZONE SETPOINT +20F)
MAXIMUM HEATING AIRFLOW SETPOINT
MINIMUM AIRFLOW SETPOINT
MAXIMUM COOLING AIRFLOW SETPOINT
AIRFLOW SETPOINT
SCR ELECTRIC HEATER SUPPLY AIR TEMPERATURE SETPOINT (FROM DISCHARGE TEMPERATURE SENSOR)
HEATING LOOP
DEAD BAND
COOLING LOOP
ELECTRIC REHEAT
SINGLE DUCT TERMINAL BOX CONTROL METHODOLOGY(AS REQUIRED BY ASHRAE 90.1-2013 6.5.2.1)
COPYRIGHT 2021 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
ISSUE
PROJECT NUMBER
1
A
23456
AB
CD
E
13456 2
BC
DE
TEMPLATE 2020.C.1
BASKERVILL, P.O. BOX 400, RICHMOND, VA 23218-0400
6/23/2021 5:01:14 PM C:\Users\pmaccormac\Documents\2.200348.0 - DAA - Blacksburg Office - Renovation- Mech_pmaccormac.rvt
CONTROLS
06/23/2021 -CONSTRUCTION DOCUMENTS
M601
2.200348
2200 S. MAIN STREETBLACKSBURG, VA 24060
DRAPER ADENBLACKSBURGRENOVATION
VARIABLE AIR VOLUME UNIT CONTROL DIAGRAM - RTU-1
EXHAUST FAN CONTROL DIAGRAM
SINGLE DUCT TERMINAL UNIT CONTROL DIAGRAM