Six core activities in the commissioning of the earthing system
Six core activities in the commissioning of the earthing system (photo credit: SouthCityElectrical via Youtube)
Testing of the earthing system
Commissioning of new earthing system is essential as a validation step for the design and installation process and
for the design inputs. In most cases commissioning should measure the outputs of the earthing system in terms of
produced voltages and current distributions rather than solely resistance.
The commissioning should consider closely the key performance criteria identified in the hazard identification and
treatment analysis phases.
Commissioning will determine the earthing system initial compliance and set a benchmark or
baseline for ongoing supervision.
As it is not always possible to foresee all hazard mechanisms at the design stage commissioning testing should also
determine the need for any localised secondary mitigation and any additional requirements for telecommunication
coordination and pipeline interference coordination or mitigation.
The earthing system commissioning procedure normally consists of six core activities. In some instances, not all
1
http://electrical-engineering-portal.com/guidelines-for-installing-power-transformershttp://electrical-engineering-portal.com/commissioning-earthing-systemhttp://electrical-engineering-portal.com/
8/17/2019 Six Core Activities in the Commissioning of the Earthing System
2/5
activities are required //
1. Visual inspection
2. Continuity testing
3. Earth resistivity testing
4. Injection testing
1. Earth potential rise (EPR) measurement
2. Current distribution measurement
5. Transfer, touch and step voltage testing
6. To be aware of
1. Visual inspection
The visual inspection typically involves checks of //
Design compliance and as-built drawing accuracy
Condition of earthing conductors and connections
Condition of earthing electrodes
Presence and condition of earthing bonds to equipment
Condition of surface layer materials if required
Condition of access fences if required
Presence of transfer hazards.
2. Continuity testing
Continuity testing is used to measure the resistance between items of plant within the main earth grid and to
components that should be effectively bonded to the grid. This test is especially important in large earthing systems
where visual inspection of all conductors and connections is more difficult.
Adequate bonding is essential to ensure that personnel are working only on equipment that is
effectively connected to the earthing system.
Go back to Commissioning Activities ↑
3. Earth resistivity testing
It is often necessary to carry out earth resistivity tests in conjunction with performance assessments to allow accurate
error corrections and safety criteria determination.
2
8/17/2019 Six Core Activities in the Commissioning of the Earthing System
3/5
Even where resistivity testing was undertaken at the design stage, additional testing (however brief )
may help to define measurement errors and periodic variations.
Go back to Commissioning Activities ↑
4. Injection testing
The remaining tests require the presence of a simulated power system line to ground fault. To achieve this, a circuit is
established between the earthing system under test and a remote injection point.
Ideally this circuit should reflect the actual fault return point. Where this is not possible post testing analysis is
necessary to reflect the actual fault scenario or scenarios. This may include multiple points of return.
The simulated fault is typically made sustainable by injecting a small current, commonly between 2 and 20 amps .
The effects are made measurable, even on live systems, by injecting at a frequency away from power system
frequency and using frequency tuneable measuring equipment.
The test is referred to as a Low Current, Off Power Frequency Injection Test .
Go back to Commissioning Activities ↑
4.1 Earth potential rise (EPR) measurement
With test current flowing through the simulated fault circuit, voltages will be present in the same locations and in
proportion to those generated during a real earth fault . The earthing system’s EPR is measured by performing afall of potential test.
This test requires a test lead to be run out from the earthing system to allow a series of voltage measurements to
be made between the earthing system under test and the ground. The route and distance is chosen to minimise
measurement errors.
The measurements taken from the fall of potential test must be processed for the difference between test and power
system frequency and for distance to remote earth. They can then be used to determine the earth system impedance
and the EPR under actual fault conditions. Adjustments should also be made for mutual earth resistance and for
mutual inductance as required.
Direct remote earth measurements, such as voltage measurements to remotely earthed communications or pilot
wires, can also supply supplementary test data. However, with single point measurement alone it is very difficult to
correctly assess and correct the many error sources that can be part of any measurement taken.
Go back to Commissioning Activities ↑
4.2 Current distribution
3
8/17/2019 Six Core Activities in the Commissioning of the Earthing System
4/5
In the situation where fault current may leave the earthing system through paths alternate to the earth grid (such as
cable sheaths or overhead earth wires), the current through those alternate paths should also be measured.
This allows analysis of how fault energy is dissipated, its effect on the alternate paths (for example, cable sheath
capacity) and calculation of the earth grid impedance from the total system impedance.
In complex systems the results are particularly important in modelling alternate fault scenarios and
in-feeds not simulated during testing .
Go back to Commissioning Activities ↑
5. Transfer, touch and step voltage testing
While test current is flowing in the fault circuit, measurements are made of actual transfer, touch and step
voltages. The purpose of such measurements is to directly measure the earthing system’s outputs and the
compliance with the determined safety criteria.
When measuring touch and step voltages it is important to measure the prospective touch and step voltages using a
high impedance voltmeter and to measure the effective or loaded touch and step voltages appearing across an
appropriate resistance that represents the human body.
Care should be taken not to confuse the prospective step and touch voltages (i.e. open circuit case) with the effective
step and touch voltages criteria. The loaded touch and step voltage cases are more variable due to variations in
contact resistance.
Therefore, the loaded case is only used when necessary and precautions taken (for example, take
multiple measurements, use electrode contact initially, and only use a weighted plate on moistened soil
if necessary).
Go back to Commissioning Activities ↑
To be aware of //
Telecommunications coordination
Where telecommunications equipment is installed within the area of influence of a high voltage earthing systemconsideration is required of the hazards that may be created. In such cases notification must be given to the
appropriate telecommunications group.
Pipeline interference / coordination
Where pipelines are installed within the area of influence of a high voltage earthing system consideration is require
of the hazards that may be created. These hazards must be reviewed during commissioning. In such cases
notification must be given to owner / operator of the pipeline.
Go back to Commissioning Activities ↑
4
8/17/2019 Six Core Activities in the Commissioning of the Earthing System
5/5
Reference // Power System Earthing Guide—part 1: management principles by ENA