Danyal KUBİN, Bahadır ŞADAN, Aydan ÖZMEN,Joseph KUBİN, Elif EROĞLU

Prota Engineering Inc., Turkey

Hakan HAKALMAZ, Mustafa ŞENCANTürk Telekomünikasyon Inc., Turkey

Presented by: Dr. Bahadır ŞADAN

SE‐50EEEInternational Conference on Earthquake Engineering

29 to 31 May 2013 ‐ Skopje / Macedonia

Türk Telekomünikasyon A.Ş.                   (Turkish Telecommunication Inc.)

Güllük / Antalya – Turkey

8 Storey R/C Building

(Basement + Ground + 5 Floors + Steel Roof)

Built in late 90’s

Basement Floor (4.00m)

Ground Floor (4.40m)

1st Floor (3.60m)

2nd Floor (5.00m)

3rd Floor (5.00m)

4th Floor (5.00m)

5th Floor (2.60m)

Roof Floor (2.60m)

TOTAL HEIGHT = 32.20m

CR

CM

650cm 650cm620cm 620cm 620cm620cm54

0cm

540c

m550c

m550c

m

Field Studies

StoreyConcrete Strength (MPa)

Young Modulus

(MPa)

Roof 8 14,1425th 8 14,1424th 15 19,3653rd 13 18,0282nd 11 16,5831st 21 22,913

Ground 18 21,213Basement 19 21,794Average 12 17,321

2nd Seismic Zone

A0 = 0.3 g (Immediate Occupancy –475 years return period)

A0 = 0.45 g (Life Safety– 2475 yearsreturn period)

Importance Factor I= 1.0

Behaviour Factor R= 1.0

Cracked Section Stiffness Properties

(Columns 60%EI, ShearWalls & Beams 40%EI)

Immediate Occupancy

All Columns & Shearwalls in Minimal Damage Zone

10% of Beams in Moderate Damage Zone

No Brittle Failure Allowed

Life Safety

Shear Force Carried by Columns & Shearwalls in Severe Damage Zone

< 20% Vtotal  (All Floors)

< 40% Vtotal  (Top Floor)

30% of Beams in Severe Damage Zone

No Brittle Failure Allowed

Mode 1 Tz= 1.07 secM% = 41%

Mode 2 Ty= 0.89 sec M% = 56%

Mode 3 Tx= 0.66 secM% = 44%

MAJORITY OF BEAMS AND COLUMNS FAIL TO SATISFY LIFE SAFETY PERFORMANCE LEVEL CRITERIA

NO NEED TO CHECK IMMEDIATE OCCUPANCY PERFORMANCE LEVEL

BUILDING IS UNSAFE

SEISMIC RETROFIT NEEDED!

PERFORMANCE CRITERIA

• The building service shall not be interrupted during construction works

• Minimum obstruction to architectural usage

• Shall meet Immediate Occupancy & Life Safety Performance Levels

• Shall be cost effective

Seismic Base Isolation

There are adjacent buildings which makes base isolation impossible

Conventional Retrofitting (Addition of R/C ShearWalls)

The building service would be interrupted

Creates much dust and dirt

Architectural usagewould be obstructed. Overhangs would create problem.

PERFORMANCE CRITERIA

• The building service shall not be interrupted during construction works

• Minimum obstruction to architectural usage

• Shall meet Immediate Occupancy & Life Safety Performance Levels

• Shall be cost effective

Retrofitting by Steel Braces

Steel braces can be pre‐manufactured

Installation can be completed during night time

Building Service would not be interrupted

Less obstruction to architectural usage

Overhangs will be accessible

Aesthetic design

Cost effective with performance based design

PERFORMANCE BASED DESIGN

• Each storeymodelled with its ownspecific concrete compressive strength

• Moment‐Curvature and Axial Force‐Moment interaction diagrams of 

Columns, beams and walls have beenderived considering existing

reinforcements

• Rotational plastic hinges are assigned toeachmemberwhile

tension/compression hinges areassigned to steel braces

PERFORMANCE BASED DESIGN

• Seismic demand has been calculatedas described in Turkish Earthquake

Code (2007)

• Singlemode pushover analysis havebeen prformed for 4 orthogonal

directions

• Plastic rotation andtension/compression deformation of eachmember are compared with the

Life Safety and ImmediateOccupancy performance limits of 

FEMA356

PERFORMANCE BASED DESIGN

• The steel profiles are chosen as HA200 themost available steel

profile in themarket to speed up theretrofit process

• Several iterations resulted in themost optimal steel sections withvarying thickness at each storey

Ground Floor – 10mm1st Floor – 10mm2nd Floor – 8mm3rd Floor – 8mm4th Floor – 6mm5th Floor – 6mm