Data sheet .............................................................................................................................................................3-6Approval Overview ...................................................................................................................................................7System description/variants/accessories/approvals ...........................................................................................8General technical data .............................................................................................................................................9Connection diagram...............................................................................................................................................10Technical data of outputs/inputs .....................................................................................................................11-12Flame monitoring/flame detector connection ............................................................................................... 13-14Installation MPA 411x .............................................................................................................................................15Dimensions MPA 411x ...........................................................................................................................................16Installation MPA412x .............................................................................................................................................17Dimensions MPA 412x ...........................................................................................................................................17Description of the functionsUnlocking functionExtended unlockingAccess level ............................................................................................................................................................18Description of the functionsGas valvesFlame detectorAir pressure switchGas pressure switchLimit switchParameter modeAutomatic/Parameter mode switch ......................................................................................................................19Flow chart ......................................................................................................................................................... 20-21State description .............................................................................................................................................. 22-24Parameters/Parameter change .............................................................................................................................25Parameters/Parameter description ................................................................................................................26-32Parameters/Factory settings ........................................................................................................................... 33-34Status information ................................................................................................................................................. 35MPA 4111/Version without display .................................................................................................................36-37MPA 41x2/Version with display ............................................................................................................................ 38MPA 41x2/Overview of the display modes ...........................................................................................................39MPA 41x2/Display .................................................................................................................................................. 40MPA 41x2/Operation display .................................................................................................................................41MPA 41x2/Additional display information ............................................................................................................42MPA 41x2/Display of parameterisation and service box ................................................................................... 43MPA 41x2/Information display ............................................................................................................................. 44MPA 41x2/Error display ........................................................................................................................................ 45MPA 41x2/Display of the error memory .............................................................................................................. 46MPA 41x2/Parameter display ........................................................................................................................... 47-54MPA 41x2/Reset display ..................................................................................................................................55-56Error overview for minimum indication................................................................................................................57MPA 41xx Errors without error ID ........................................................................................................................ 58MPA 41xx Error from the basic system ..........................................................................................................59-60MPA 41xx Error from the extended functions ................................................................................................ 61-63Annex .................................................................................................................................................................... 64Profibus Extension module MPA 41xx - EM 2/2 ............................................................................................... 65Profibus, Modbus, Shutter Extension module MPA 41xx - EM 2/4 ............................................................ 66-78Multifunctional modul MPA 41xx-EM 2/6 ..................................................................................................... 79-104Flame detector ............................................................................................................................................ 105-106 UV 41 ............................................................................................................................................................107-108UV 42 ............................................................................................................................................................109-110UV 4x EM 1/1 Shutter module ...................................................................................................................... 111-112FLW 20 UV ....................................................................................................................................................113-115FLW 10 IR .....................................................................................................................................................116-118FLW 41 I .........................................................................................................................................................119-120Ignition transformers DEZ ..........................................................................................................................121-123VisionBox ............................................................................................................................................................124
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
3 … 1262 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
µP Automatic Burner Control MPA 41xx
Automatic burner control for one-stage and modulating gas burners
DescriptionMicroprocessor-controlled automatic gas burner control for intermittent and continuous operation of one-stage at-mospheric burners or one-stage or modulating fanned burners.The program sequence and times can be customised by setting software pa-rameters.
Versions• MPA4111withoutdisplay• MPA4112withintegrateddisplay• MPA4122withmetalhousingand integrated display
ApplicationFor one-stage or modulating gas burn-ers with or without ignition gas. In particular for industrial thermoprocess-ing equipment to EN 746-2.
ApprovalsECtype-examinationcertificateaccord-ingtotheECGasAppliancesDirective:MPA41xx CE-0085BU0487
EC type-examination certificate ac-cordingtotheECPressureEquipmentDirective:MPA41xx CE0036
FMApprovedtoFM761ULRecognizedComponent perUL372,UL1998andCSAC22.2.GOST/Rostechnadzor
Suitable for applications up to SIL3.Meets the requirement according to IEC 61508(2ndEd.2011)CertifiedbyTÜVSüd
• Automatic gas burner control for one-stage burners with pilot burner or direct ignition
• Continuous operation
• Configurable program sequence
• Version with or without display
• Two independent flame detectors:Ionisation inputGate input
• Additional functions byextension modules
• Profibus
• AccessoriesFlame detectorIgnition transformersParameterisation and service box
5 … 1264 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA41xxautomaticgasburnersaresuitable for all types of one-stage or modulating gas burners with and with-out ignition gas.
Theflameismonitoredeitherbymeansofanionisationinput,gateinputorbothinputsforburnerswithtwoflamedetec-tor positions.
• For atmospheric burners and fan burners
• Suitableforcontinuousoperation• MPA4112/4122configurationwithoutlaptop/PCviadisplay
• Ionisationandgateinputsasflamedetectors
• ExtensionmoduleforProfibuscom-munication
Example for connection
Atmospheric burner with ignition gas output
V1 V2
Fan burner, direct ignition:V1 V2
Atmosphericburnerwith ignitiongasoutput.Aftertheheatrequestandanadjust-abledelay,theignitionisswitchedonandV1andVzareopened.After the flame has been detected, themaingasflowV2isopened.
Fanburner,directignitionofthemaingasflame.After the heat request, the fan isswitched on, and the air pressure ischeckedbythepressureswitch.Afterthe pre-aeration time has lapsed, the ignition is switched on, and the two valves V1 and V2 are opened together.
Wiring scheme
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
q
P
M
N G
qPGPE
NL1
6.3 A T(10 A F)
Ionisation
SupplyFlam
e detector
Safety chain
Operation
Fault
Ignition transform
er Flame detector 2 N
CFlam
e detector 2 NO
Air pressure switch
Heat request
Reset
Not used
V1
V2
Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).
5 … 1264 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error displayDisplay of the error memory
• Automaticactivationoferror messages
• Additionalinformationaboutfaults•Query of the last ten faults
Display modesOperation display
• Displayofthecurrentoperating state
• Displayoftheprogramstate• Displayofbusaddress
Info display
• Displayofflamequality• Displayof resettablecounters forstart-up,operatinghoursandop-erating cycles
Parameter display
• Password-protected functionallevels for serviceandOEMpa-rameter settings
• Settingofimportantparameterssuchas: Pre-purge timeSafety time for startup phasePost-purge timeBehaviour after flame lift-offOperating modes of V1 and V2Continuous or intermittent operation
Accessories
Flame detectorFLW 10 IRIRflamedetector for connection toionisationinput.Suitableforintermit-tent operation.
FLW 20 UVUVflamedetectorforconnectiontoionisationinput.Suitableforintermit-tent operation.
UV 41 (HE)/UV 42 UVflamedetectorforhighmechani-calload;metallicversion.Suitableforintermittent operation.
With shutter module suitable for con-tinuous operation
FLW 41 IFlame safeguard module for ionisation flamemonitoring.TheFLW41Iiscon-nected to the second flame guardinputoftheMPA41xx.When equipped with an extension module,forexampleEM2/4,suitablefor continuous operation.
The program sequence and times can bemodified on themounted display(MPA4112/MPA4122)tomatcheachapplication.AlaptoporPCisnotrequiredforthemodification.The automatic burners are protected by passwords against unauthorised access.
All settings for the MPA 41xx auto-matic gas burners can also be made bymeansofalaptop/PCviaMPAVisionBox.
Communication
MPA 41 extension module EM2/4AdditionalcircuitboardandconnectorsetforProfibusDPandModbuscom-munication.
MPA 41 extension module EM2/6 AdditionalcircuitboardforProfibusDPand Modbus communication.PWMoutput foropen loopcontrolofDC fans,voltage-/currentoutputalsoprogram state related relay outputs.
Parameter setting and serviceMPA 41 parameterisation and service boxUniversalsupportforcheckingdevicesin the field; for producing small andmedium series.
MPA Vision BoxInadditiontoMPA41parameterisationandserviceboxforsettingparametersviaaPC/laptop.
7 … 1266 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Subjecttotechnicalmodificationintheinterestoftechnicalprogress.
µP Automatic Burner ControlMPA 41xx
Automatic burner control for one-stage or modulating gas burners
Technical DataRatedvoltage 115VAC-15%...+10%(dependingonthemodel) 230VAC-15%...+10%Frequency 50Hz...60HzPowerconsumption max.10VAFuse max.6.3Aslow-blow or10Afast-blowReadysignal max.1AFaultsignal max.1AGasvalves max.2AFan max.1AIgnition max.1AFlamedetectorsupply 230VAC/10mAFlame detector lonisationlonisationcurrent/operation 10-20µAShutdownsensitivity 1,2µAShort-circuitcurrentlimit approx.280µAUnlockingduetofault PushbuttonsandremoteunlockingTypeofprotection MPA4111/IP42 MPA4112/IP54 MPA4122/IP65Ambienttemperature -40°C-+70°C -20°C-+60°C(ULapproval)Ordering dataMPA4111/230VAC OrderNo.259058MPA4111/115VAC OrderNo.259062MPA4112/230VAC OrderNo.259066MPA4112/115VAC OrderNo.259070MPA4122/230VAC OrderNo.260347MPA4122/115VAC OrderNo.260355
Extension module EM2/4MPA411x OrderNo.257960EM2/4MPA412x OrderNo.257961ProfibusDP,Modbus,ShutterEM2/6MPA411x OrderNo.260751EM2/6MPA412x OrderNo.260570ProfibusDP,Modbus,Shutter,PWM,analogIn/Out
Flame detectorFLW10IR OrderNo.255216FLW20UV OrderNo.250733FLW41I OrderNo.258396UV41 OrderNo.256692UV41HE OrderNo.260575UV42 OrderNo.258385UV4x-EM1/1(Shutter) Artikel-Nr.259361
Company addressKarl Dungs GmbH & Co. KGSiemensstraße 6-10D-73660 Urbach, GermanyPhone +49 (0)7181-804-0Fax +49 (0)7181-804-166
Postal addressKarl Dungs GmbH & Co. KGPostfach 12 29D-73602 Schorndorf, Germanye-mail: info@dungs.comInternet: www.dungs.com
77
148.5
152.5
152.5
77
151.5
240
80
160
Dimensions [mm]MPA 4111
MPA 4112
MPA 4122
7 … 1266 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA41xx from V1.1
UV4x UV4x-EM1/1 (Shutter)
Components SIL SFF PFH
X Ionisation input
3 99,48% 1,80E-09
XInputFLW2NO,FLW2NC,LDWandremote unlo-cking
3 99,38% 1,80E-09
X X UV41+ionisa-tion input
2 96,91% 1,50E-07
X XUV42+inputFLW2NO
2 96,87% 1,51E-07
X X XUV4x-EM1/1(shutter)+UV41+ionisa-tion input
3 99,35% 3,15E-08
X X XUV4x-EM1/1(Shutter)+UV42+inputFLW2NO
3 99,34% 3,15E-08
Safety Integrity Level (SIL)
Approval overview Order No.
CE FM ULrecog-nized
UL listed
CSA C22.2
Gost AGA
MPA4111/AC230V 259058 x x x x xMPA4111/AC115V 259062 x x x x x xMPA4112/AC230V 259066 x x x x xMPA4112/AC115V 259070 x x x x x xMPA4122/AC230V 260347 x x x x xMPA4122/AC115V 260355 x x -> x x x xExtension moduleEM2/2MPA41xx 256556 x x x x xEM2/3MPA41xx 257387 x xEM2/4MPA411x 257960 x x x x x (x)*EM2/4MPA412x 257961 x x (x)*EM2/5MPA412x 260743 x x x x x (x)*EM2/6MPA411x 260751 x x x x x (x)*EM2/6MPA412x 260570 x x x x x (x)*Flame detectorFLW10IR 255216 xFLW20UV 250733 xFLW41I 258396 x xUV41 256692 x x x x x xUV41HE 260575 x x x x x (x)*UV42 258385 x x x x x xUV4x-EM1/1(Shutter) 259361 x x x x x xIgnition TransformerDEZ1xx alle x (x)* xDEZ2xx alle x (x)* x
Approval overview
*onrequest
9 … 1268 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
1 MPA 41xx System description
The automatic gas burner control systemsMPA41xxaresuitableforintermittent or continuous operation of gas burners with or without fan.The system parameters may be set ontheintegrateddisplay(MPA4112/MPA4122)and/orusingtheDUNGSVisionBox.Theflameiseithermonitoredusinganionisationelectrode,aDUNGSFLWXXflamedetectororDUNGSUV41flamedetectorconnectedtotheionisationelectrodeinputoroverasecondflamedetectorinputforaflamedetectorwithpotential-freetwo-way contact or by means of the DUNGSUV42flamedetector.Bothflamedetectorinputsmaybeusedindividuallyorcombined.
TheMPA41xxparameterisationandserviceboxisavailablefortheproduction of small series and for checkingthesystemwhenserviceisrequired.
Foroperationinburnernetworks,aProfibus/ModbuscommunicationovertheextensionmoduleEM-2/4orEM2/6ispossible.
Accessories
Ignitiontransformers:-DEZxxx- Connection line- Ignition line
Flamedetector:-IR:FLW10-UV:FLW20,UV41,UV42-Ionisation:FLW41I
Designation Article no. Voltage DisplayMPA4111 259058 230VAC Minimum indicationMPA4111 259062 115VAC Minimum indicationMPA4112 259066 230VAC 3-digit7-segment
displayMPA4112 259070 115VAC 3-digit7-segment
displayMPA4122 260290 230VAC 3-digit7-segment
displayMPA4122 260355 115VAC 3-digit7-segment
display
System variants
Extension modules EM-EM2/4:Shutter,ProfibusDP,Modbus
-EM2/6:Shutter,ProfibusDP,Modus,PWManalogueIN/OUT.
9 … 1268 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4General MPA41XXProtectiontypeoftheplastichousing
MPA4111MPA4112
IP42IP54
Protectiontypeof metal housingMPA4122 IP65(Attention:usesuitablecablescrewconnectionsonly)AmbienttemperatureMPA41xx
-20°C...+60°C(ULApproval)-40°C...+70°C
Storageandtransport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleUsefullifeSwitchingoutputs
Minimum250,000switchingoperations
Mounting position as desiredDimensionsofMPA411xin mm
MPA4111(LxHxT):ca.152,5x148,5x77mmMPA4112(LxHxT):ca.152,5x151,5x77mm
WeightMPA411x 0,82kgDimensionsofMPA412xin mm
MPA4122(LxHxT):ca.160x240x80mm(excludingcablescrewconnection)
WeightMPA412x 2,2kg
Technical Data
Electrical dataRatedvoltage 230VAC -15%...+10%or
115VAC -15%...+10%,dependingontheversionFrequency 50Hz...60HzFuse 6.3Aslow-blowfuseor10Afast-blowfuse,integrated,exchangeableIsolation Nogalvanicisolationbetweenmainsand24VDCor5VDCElectrical connection Correct phase sequence(!)connectionandprotectiveearthconductoraccordingto
the wiring diagramThe contact protectionfortheUVsensormustbeguaranteedbymountingitintheoperating equipment
Powerconsumption(ownconsumption)
Maximum10W
Typically 115V 230VStandby 1.5W...1.8WOperation 3.4W...4.8W
WithextensioncardEM2/4Standby 3.3W...3.5WOperation 5.4W...6.3W
WithextensioncardEM2/6Standby xxW...6.3WOperation xxW...9.0W
Short-circuitcurrentIONagainstN115/230VAC
280µA
11 … 12610 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Connection diagramMPA411x
Attention:
Riks of fatal electric shocks!You must interrupt the power sup-ply before removing the hood.
After having removed the hood, you might get in contact with the electrical connections in the ter-minal socket.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
q
P
M
N G
qPGPE
NL1
6.3 A T(10 A F)
Ionisation
SupplyFlam
e detector
Safety chain
Operation
Fault
Ignition transform
er Flame detector 2 N
CFlam
e detector 2 NO
Air pressure switch
Heat request
Reset
Not used
V1
V2Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).
Do not remove the jumper be-tween terminals 1 and 2, which was mounted in the factory. It is required for the intended use of the automatic gas burner control system.
Connection diagramMPA 412x
1LL 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
q
P
M
N G
qPGPE
NL1
6.3 A T(10 A F)
Ionisation
SupplyFlam
e detector
Safety chain
Operation
Fault
Ignition transform
er
Flame detector 2 N
CFlam
e detector 2 NO
Air pressure switch
Heat request
Reset
Not used
V1
V2
11 … 12610 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4Outputs*Designation Safety-
relatedType of output Line length Electrical data
V1Maingasvalve
● Relaycontact Max.100m 115/230VAC/2Acosϕ=1Minimumload0.5W
V2Safetygasvalve
● Relaycontact Max.100m 115/230VAC/2Acosϕ=1Minimumload0.5W
Ignition ● Relaycontact Max.100m 115/230VAC/1Acosϕ=0.4correspondsto115/230VAC/2.5Acosϕ=1
Fan Relaycontact Max.100m 115/230VAC/1Acosϕ=0.4correspondsto115/230VAC/2.5Acosϕ=1
Operation Relaycontact Max.100m 115/230VAC/1Acosϕ=1
Fault Relaycontact Max.100m 115/230VAC/1Acosϕ=1
Flame detector supply
ForUV41(HE),42FLW10,FLW20
Max.100m 230VAC/10mA*1
Technical Data
*1:Theflamedetectorisalwayssuppliedwith230VAC,eventhe115VACversion,viatheMPA41xxpowersupplyflamedetector,pin7
Thesumofthecurrentsofallsafety-relatedconsumersmustnotexceed5A!Thesumofthecurrentsofallconsumersmustnotexceed6.3A(10A),notefusevalue
Inputs*Designation Type of input Line length Electrical dataSafetychain Potential-freecontact Max.100m 115/230VAC/max.10AFlamedetector1(Ionisation)
Ionisation for one or two-probe operation
Max.10m** Thresholdvalue:approx.1.2µA
Flame detector 2 NO Switchingcontact Max.100m 115/230VAC“normally open”
Flame detector 2 NC Switchingcontact Max.100m 115/230VAC“normally closed”
Heatrequest Switchingcontact Max.100m 115/230VACAirpressureswitch Switchingcontact Max.100m 115/230VACRemoteunlocking Switchingcontact Max.100m 115/230VAC
*Thewireswhichareusedfortheconnectionmustbeapprovedforambienttemperaturesofminimun75°C(167°F).
**Fordistances>10mflamedetector2shouldtakeplace.ForspecialapplicationsIonizationlinelengthupto50mispossibleonrequest.
13 … 12612 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
General informationDesignation Type of input Electrical data MPA 4111 MPA 41x2L1connectionoverex-changeable backup fuse
L1protectedbyintegratedfuse,6.3Aslow-blowor10Afast-blow
● ●
TWI interface TWI ConnectiononlyforVision-Box and parameterisation boxNOT galvanically iso-lated!
● ●
Switchforparametermode Bistable switch ON/OFFswitchinMPA(mayonlybeswitchedafterhavingremovedMPAfromthebase)
● ●
Displayunit"Multi-function switch"
In housing towards inte-grated multi-function switch
1pushbuttonwith2LED's ●
Display In housing towards inte-grated display
3x7segment+4keys ●
Spark generator connection MPA41xxdoesnothaveamountedspark generator. Suitable spark generators, see ac-cessory list.
Attention:Aspecialsparkgeneratoris required depending on the elec-trode arrangement (single-electrodeoperation).
Technical Data
13 … 12612 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Single-electrode operation ionisation
Flame detector connection
Flame detector UV41 (HE) / FLW 10 IR / 20 UV
Flame monitoring system and IgnitionFlame detector 1 connection
MPA connection
15:Ignition
3:N
4:PE
5:ION
7:FLWpower
16:FLW2NO
Flame
MPA connection
15:Ignition
3:N
4:PE
5:ION
7:FLWpower
16:FLW2NO
Flame
UV41(HE)
MPA connection
15:Ignition
3:N
4:PE
5:ION*
7:FLWpower
16:FLW2NO
Flame
*WhenusingaDUNGSDEZ1xxSEOignitiontransformerforsingle-electrodeoperation,thegreen/yellow cable must be connected to terminal 5.
Two-electrode operation ionisation
15 … 12614 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Flame detector connection and ignition
Flame detector 2 connection
Flame detector FLW 41I
15:Ignition
3:N
4:PE
5:ION
7:FLWpower
16:FLW2NO
Flame
Flame detector UV 42
15:Ignition
3:N
4:PE
5:ION
7:FLWpower
16:FLW2NO
Flame
15 … 12614 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Installation of the MPA 41xx
InstallationoptionsfortheMPA41xx:
- direct screw connection of the base on the mounting sur-faceBreakoutmountingholes,e.g.,withasuitablescrewdriveror drill them with a drill 4.2 mm (M4)or5.5mm(M5).
-Hatrailmounting(lockingthebaseintoplaceonahatrail)
Mounting bores
Hatrailmounting
ScrewM4
ScrewM5Attention! Use only plastic screws!
17 … 12616 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
148.5
77 152.5
151,5
77 152,5
Dimensions of the MPA 4111
Dimensions of the MPA 4112
ø15,7mmforProfibusconnection
ø16mmforScrewconnectionM16x1.5
17 … 12616 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Installation of the MPA 41xx
InstallationoptionsfortheMPA412x:
- direct screw connection of the housing on the installation surface usingM4screws,lengthmin.20mm
M4 M4
M4 M4
240
Dimensions of the MPA 412x
225
123
80
160
37,9 40,5 26 12
M32x1.5 - 6HM32x1.5 - 6H
M16x1.5 - 6H
M16x1.5 - 6H
M16x1.5 - 6H
32
15,5
18,5
14,6
19 … 12618 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Description of the functions
Unlocking functionIfMPAislocked(state0),itcanbeun-locked by pressing the unlock key. Keep thekeypressedminimum0.5s(max.5s)todistinguishthefunctionfrompos-sible EMC interfering impulses.Thesameistruefor230Vunlockingandunlockingviafieldbusmodules.
According toDINEN14459 (annexJ),the number of possible unlocking proc-essesislimitedto5in15minutes,thatmeans the automatic system denies fur-therunlockingiftheMPAhasbeenun-locked more than 5 times within a short time period. Only after a waiting time duringwhich theMPA isprovidedwithpower is itpossible tounlock theMPAagain.
The waiting time is 15 minutes or 3minutes for each unlocking.
Extended unlockingThe described limitation to 5 unlock-ing operations in 15 minutes can bereset by means of "Extended unlock-ing".Todothis,theunlockkeymustbepressedforatleast5s(max..10s)(af-ter5s,thedisplaybeginstoflash).
The"Extendedunlocking"isactiveinalloperationalstatesoftheMPA,thatmeansthatasafetycut-offwithrestartoftheMPAinoperationcanbecarriedoutviathe"Extendedunlocking"alsointhepresenceofaflame.
Extended unlocking is not possible viathe230Vunlockinginputandviafieldbusmodules!
Access levelWriteaccesstoMPAisdefinedondif-ferentaccesslevels.Each parameter is assigned to a cer-tain access level. In order to modifyaparameter,MPAmustbe in theas-signedorhigherlevel.If theaccess level isnotsufficient formodifyingaparameter,theVisionBoxreports it, or amessage ispromptedontheMPAdisplayrequestingtoen-terthevalidpassword.Inhigherlevels,theusersmustpressakeytoconfirmthat they are on site. The display is flashingfor30suntilakeyispressed;otherwise,theMPAremainsinthepre-viouslevel.In order to change the access level,enter the correct password either on thedisplay(MPA4112/MPA4122)orintheVisionBox→MPAsettings→Ac-cesslevel.
The access level is automatically re-set after 5 hours or after power failure. Exception:Iftheautomaticgasburnercontrol system makes a restart during these5hours, forexampleduetoanerror,these5hoursforthecurrentac-cesslevelarecountedagainfromthebeginning.
Note:Werecommendresettingtheac-cesslevelafterhavingconfiguredtheautomatic gas burner control system.
Level Designa-tion
Key con-firmation required
1 Dungs yes2 OEM
Expertyes
3 OEM yes4 Service yes5 Operator no
19 … 12618 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Gas valvesThevalveconnectionmaybeconfig-ured,seesection"Parameterde-scription"-P38.
Flame detectorSeeAnnex-Flamedetector.
Fortheconnectionofasecondflamedetector,seesection"Parameterdescription"-P18.
Air pressure switchSeesection"Parameterdescription"-P16
Gas pressure detectorSeesection"Parameterdescription"-P18
Limit switch / POC Proof of Clo-sureSeesection"Parameterdescription"-P18
Parameter mode (manual operation)Aswitchintheconnectionchamberis used for switching between param-eter and automatic mode.TheMPAregistersaswitchingopera-tion not before a restart.
MPA 4112/MPA 4122AfterconnectingthemainssupplyinParametermode,amessagesisprompted on the display requesting you to enter the code. Enter the pass-wordforserviceorOEMlevel.
Afterhavingchangedthelevel,theselectedparametersareactivatedoneafter the other. SeechapterMPA4112/MPA4122Parameterdisplayforparametersandsequence.Theparametervaluesmaybemodi-fiedbypressingthekeys+and-.Theunlockkeyisusedforsavingthedis-playedvalue.Pressthe←keytoreturntothepreviouspositionorparameter.
Asthedisplayhastwopositionsonly,somevaluesarerepresentedinanoptimisedresolution.Ifthesetvaluecannotbedisplayedinthisresolution,thedisplayshows"––".Thevaluemay be changed in a resolution that can be displayed.Ifallparametersareset,thereisanautomatic start for checking the pa-rametervalues.Theprogramstopsinpause states; press a key to proceed (Hxisdisplayed).Thesetparametervalueswillbeap-pliedwhenreachingtheH5state.Ifyoudonotpressanykeyfor30
minutesinparametermode,thepro-gram tries a restart.
Switch on "Auto"Withthisswitchposition,theMPAis working in normal operation. If a monitored parameter was changed andnotreleasedtheMPAindicatesanerrorwith0x60.
ParameterswitchLeft"Auto"positionRight"Para"position
21 … 12620 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Flow chart
The program sequence may be cus-tomised by changing the parameters.
Attention: All modifications must comply with the requirements of the valid standard.DUNGS shall not assume any liability for material or personal damage caused by improper use or parameter setting of the auto-matic gas burner control system.
*1ThemonitoringoftheLDWdependsontheoperatingmodesetinP16.*2V1canbedeactivatedviaparameterP38afterthesecondsafetytime(=interruptedstartgas)*3ThetwoinputsFlame1andFlame2canbeactivatedordeactivatedindependentlyofoneanotherperparameter
forphase1andphase2.*4Bothflameinputsmustbeoff!*5With"Flameon",itwillrunwith15minutesoffollow-upafteraregularswitch-off.After24hOFF,thesignalwillbe
activatedfor1minute.*6Theinput"Flame2NC"canalsobeconfiguredasGDW.TheGDWtoleratesfaultysignalsofupto1s.*7Thefollow-uptimealreadystartsduringthe"Post-purge"state.Ifthepost-purgeisgreaterthan/equaltothefollow-
uptime,the"Follow-uptime"statewillbeskipped.*8TheMPAcanalsorunintwo-stageoperation(P38=2).Theselectionofstage1/stage2willthenbemadevia
afieldbus(e.g.Profibus,Modbus,...).V1isalwaysopen(=stage1).V2willopenafterafieldbussetpointinput(=stage2).Intheoperatingmodes"interruptedstartgas"(P38=0)and"permanentstartgas"(P38=1),V2isalwaysON.
*9Theinput"Flame2NC"canalsobeconfiguredasProof-Of-Closure(POC)asafunctionofoutputV1orV2.ThePOCtoleratesfaultysignalsofupto1s.
*10IntheoperatingmodeP38=2(two-stageoperation),thesecondsafetytimeisskipped,andtheMPAgoesfrom"Pause3"directlytothe"Operation"state!
21 … 12620 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error
Break 1
- Man
ual opera
tion
Waiting fo
r hea
t req
uest
Idle sta
te co
ntrol a
ir pres
sure
switc
h
State c
ontrol s
afety
chain
Watchdog lo
ading phas
e
Waiting fo
r air p
ressu
re
Check f
alse f
lame
Pre-ae
ration
Break 2
- Man
ual opera
tion
Pre-ignitio
nFirs
t safe
ty tim
e (SZA) -
Ignition
First s
afety
time (
SZA) - Flam
e dete
ction
Stabilis
ation fla
me A
Break 3
- Man
ual opera
tion
Second sa
fety t
ime (
SZB) *10
Second sa
fety t
ime (
SZB) - Flam
e dete
ction *1
0
Stabilis
ation fla
me B *1
0
Operatio
n Break 4
- Man
ual opera
tion
Post-ae
ration
Follow-up tim
e *7
Restar
t pro
tectio
n
Break 5
- Man
ual opera
tion
Waiting fo
r gas
presss
ure
Safety
chain
inter
rupted
Stat
enum
ber
01
23
45
67
89
1011
1213
1415
1617
1819
2021
2223
2425
Dis
play
Info
rmat
ion
Fxx
H1
01
11
11
1H
21
11
2H
32
23
3H
44
44
H5
D2
D1
P30
P31
P34
P37
P51
P52
P20
0..
0..
0..
max
.2m
inm
ax.
1min
3sm
ax.
1min
max
.1m
in0.
.1h
0..
0..1
h0,
5..
59,5
s0,
5s0.
.1h
0..
0..
29,5
s0,
5s0.
.1h
0..
0..
0..1
h0.
.1h
0..1
h0.
.0.
.0.
.1h
Safe
ty C
hain
Hea
t Req
uest
Wat
chdo
gA
larm
Ope
ratio
n"W
aitin
g fo
r Hea
t Req
uest
""F
lam
e S
tabi
l""M
ain
Flam
e O
N"
"Fla
me
ON
""F
lam
e O
N +
bac
klas
hf"
*5V1
*2V2
*10
*8*8
Igni
tion
Fan
Rel
ayPh
ase
1Ph
ase
2
Flam
e 1
and
/ or 2
*3*4
*4*4
Air
Pres
sure
Sw
itch
*1
Gas
Pre
ssur
e Sw
itch
*6
Proo
f-Of-C
losu
re*9
*9*9
*9*9
*9*9
*9*9
*9Io
nisa
tion
Inpu
t act
ive
Out
put s
igna
lO
utpu
t sig
nal a
ny o
r con
stan
t
Inpu
t sig
nal
Inpu
t sig
nal a
ny o
r con
stan
t
P32
P35
Tim
eP
50 *
7
Capt
ion
see
page
20
23 … 12622 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
State descriptionMPA 41xxState xx Designation Description
00 Error Iftheautomaticgasburnercontrolsystemisinthisstate,there is an error. The display automatically shows an error message and indicatesthecurrenterror(e.g."F11")insteadofthestatenumber.
01 Manual operation - Pause 1 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).
02 Waiting for heat request The automatic control system is ready for operation but there is not any heat request.
03 Idle state control LDW (air pressure switch)
Depending on the operating mode of LDW (P16), it ischecked whether LDW reports "no air pressure". Max.waitingtime2min.→Restart.
04 Safety chain monitoring Inthisstate,itischeckedwhetherthesafetychainispo-tential-free.Thefanrelay isstillopen,andthewatchdogrelay has not yet picked up. If the safety chain is not po-tential-free,thesystemwaitsmaximumoneminutebeforetrying to restart.
05 Watchdog loading phase The safety-related watchdog -circuit is activated. If thesafetychainisinterrupted→State25.
06 Waiting for air pressure The air pressure must be applied within a state time of max.1min.,otherwise,thesystemtriestorestart.
07 External light monitoring The flamemay not be detected within the state time ofmax.1min.Otherwise,thesystemtriestorestart.
08 Pre-purge Thisstateprovidessufficientpre-purge.Bothflameinputsmustbeswitchedoffforthedurationdefinedinparameter"Pre-purge"(P30).
09 Manual operation - Pause 2 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).
10 Pre-ignition The ignition isactivated for thedurationspecified inpa-rameterP31withoutopeningvalveV1.
11 First safety time - ignition ThegasvalveV1isopenedinthisstate.ThedurationofthisstateisP32-0.5s.
23 … 12622 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
State descriptionMPA 41xxState xx Designation Description
12 First safety time - flame detection Afterdeactivatingtheignition,theprocessforflamedetec-tion is started. If an ionisation current flowsor the230Vinputisswitchedon-dependingontheconfiguration-,theMPAreportsaflame.Thedurationofthisstateis0.5s.
13 Flame A stabilisation Theflamecanstabilise in thisstate.Thedurationof thestabilisationphase(P34)canbeconfigured.
14 Manual operation - Pause 3 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).
15 Second safety time ThegasvalveV2isopenedinthisstate.ThedurationofthisstateisP35-0.5s.
16 Second safety time - flame detec-tion
Theprocessfordetectingthesecondflameisstarted.Ifanionisationcurrentflowsorthe230Vinputisswitchedon-dependingontheconfiguration-,theMPAreportsflame2.Thedurationofthisstateis0.5s.
17 Flame B stabilisation Theflame2canstabiliseinthisstate.Thedurationofthestabilisationphase(P37)canbeconfigured.
18 Operation The automatic gas burner control system is now operating. Avoluntaryswitch-offafteradefinedtimecanbeactivated(P40).Ifthistimeissettoamaximumof23hoursand59minutes,theMPAisinintermittentmode.
19 Manual mode - Pause 4 Iftheswitchison"Para"fortheparametermode,theMPAstops in this state. Press the "Next" key (unlock key) tocontinue with the next state. If you do not press any key during30minutes,theautomaticgasburnercontrolsys-tem restarts or indicates an error.The manual mode may only be cancelled after havingrun completely through all states and after having resetthe parameter switch to automatic mode. If you reset the parameterswitchbeforereachingstateH5andyouhavemodifiedparameters,theyarenotyetapplied,andtheau-tomaticgasburnercontrolsystemindicatesanerror(seealsoP10).
20 Post-purge In this state, the post-purgeof the combustion chamberis carried out (P51). The gas valves remain closed fromthis state on. The fan continues running in this state; it is switchedoffinthenextstate.
Post-purge (P51) may be interrupted by a repeated heat request if the restart protection (P52) has been set to 0 and the follow-up time (P50) has already lapsed.
25 … 12624 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
State descriptionMPA 41xxState xx Designation Description
21 Follow-up time Duringthistime(P50-P51>0),aflamesignalmaybepre-sent from thepreviousmodecausedbye.g.existing re-sidual gas in the combustion chamber. The external light monitoring is only started in the following state.The follow-up time starts in the post-purge state if the post-purge is equal to or greater than the follow-up time; then the follow-up time state is skipped.
22 Restart protection In thisstate, thesystemwaitsuntilparameterP52 isfin-ished;thispreventsanimmediaterestartoftheautomaticgasburnercontrolsystemifaheatrequestisactive.Theflamemaynolongerbedetectedinthisstate;otherwise,MPAreportsanexternallighterror.
23 Manual mode - Pause 5 If theswitch ison"Para" for theparametermode,allpa-rameters are set, and the system has run through theentireprocess, theautomaticgasburner control systemstopsinthisstate.Thesetparametervaluesarenowap-plied automatically. You may reset the parameter switch to the"Auto"mode.Alternatively,youmaypressthe"Next"key(unlockkey)torestart parameter setting from the beginning. If you do not pressanykeyduring30minutes,theautomaticgasburnercontrol system restarts or indicates an error.
24 Waiting for gas pressure IftheautomaticgasburnercontrolsystemisconfiguredforuseofaGaspressureswitch,itchangestostate24whendetectingmissinggasinstates1to10.Itleavesitinstate1aftersufficientgaspressurehasbeenbuiltup.TheMPAruns through the post-purge, follow-up time and restartprotection states before changing to state 24.
25 Safety chain open The automatic gas burner control system remains in this stateduringthetimesetinparameterP20ifthesystemdoesnotdetectaclosedsafetychain.Afterthetimehaslapsed,itdecidesbasedonP15whetheritlocksimmedi-ately or tries to restart. IfthesafetychainisclosedbeforethetimeofP20haslapsed,MPAchangestostate1tocheckthesafetychainagain.Inthisstate,thefanrelayisactive,thefanisrun-ning.
25 … 12624 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter changeParametertypes:1-bitparameter(U1)-setting0and1(displayedasON/OFF),nolimits8-bitparameter(U8)-valuesettingwithinvariablelimits16-bitparameter(U16)-valuesettingwithinvariablelimits.
AparametermaybemodifiedonthedisplayofMPA4112/MPA4122orviatheVisionBoxsoftwareonaPC.
Inordertochangeaparameter,youneedtosettheaccesslevelassignedto the parameter.
Thevaluemustbewithinthevariablelimits;avalueoutsidetheselimitsisnot possible. Inaccesslevel2(OEMexpert),itispossibletochangethevariableupperandlowerlimits.Thevariablelimitsmay only be changed by means of VisionBox,notontheMPAdisplay.Thevariablelimitsarerestrictedbymeansoffixedlimits.Thesefixedlimits cannot be changed.
To change a parameter that cannot bechangedduringnormaloperation,it is necessary to change to state "Waiting for heat request".Most of the parameters are moni-toredinautomaticmode(switchontheboardon"Auto").TheMPAdetectschangesofthevaluesandimmediately changes to lockout (error0x60).Anychangesmustbereleased in parameter mode incl. a manualprogramrun(seealsopa-rametertable).
27 … 12626 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P11 Fieldbus address configuration
Setting the bus slave address ofMPA.Ifaninvalidaddressfortheconnect-edbusmoduleissetandtheMPAisinautomaticmode,itrestarts(er-ror0x18).
IfaninvalidvaluefortheconnectedbusmoduleissetandtheMPAisinparametermode,anerrormessageis generated. Furthermore, the set-ting "o" for the bus address is en-tered when setting the parameters.
Duringoperationanderrormessag-es,thecurrentbusaddressmaybeseenbypressingthe←key.
Valuerange:OFF(noFieldbus)0to254(e.g. Profibus adjustment rangefrom1to126)
Note:Amodifiedvaluefor thispa-rameter is not applied before a re-start or extended unlocking.
P12 Number of restart attempts or anti-os-cillation counter
Number of restart attempts of the MPA.Afterafailedlaststart,theMPAlocksandchangestolockout(faultstate0).The anti-oscillation counter is reset when returning to operating state or whenunlockingtheMPA.
Valuerange:0-5attempts
P13 Number of restart attempts when flame is missing after the start-gas flame prov-ing period
The number of restart attempts af-ter creating a flame (P12) can belimitedforthecasethattheflameisstillmissingafterthefirststart-gasflameprovingperiod.The restart counter and the anti-oscillation counter are reset when changing to the operating state or after unlocking.
Valuerange:0-5attempts
Example:P12=5,P13=1Duringthefirststartphase,noflameisgenerated→1.Restartattempt→Error idle state control LDW → 2.Restart attempt → Error idle statecontrolLDW 3.RestartattemptAfterthethirdrestartattemptLDWOK,thereisstillnoflameAutomatic gas burner control sys-tem is locked although the number ofrestartattempts(P12)hasnotyetbeen reached but the number of re-start attempts after missing flamehas been reached.
P14 Number of restart attempts after flame lift-off or missing flame after the sec-ond start-gas flame proving period
The number of restart attempts (P12) can be limited for the casethat there is a flame lift-off or thatthe flame is still missing after thesecondstart-gasflameprovingpe-riod.The restart counter and the anti-oscillation counter are reset when changing to the operating state or after unlocking.
Valuerange:0-5attempts
Example:P12=5,P14=1Flamelift-offduringoperation→ 1.Restartattempt→ Error Idle state controlLDW→ 2.Restartattempt→ Error Idle state control LDW→ 3.Restartattempt→ Aflameisnot created after the third restart at-tempt LDW OK→ Automatic gasburner control system is locked.
27 … 12626 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P15 Locking with open safety chain
Ifthesafetychainisnotclosed,theMPAwaitsinstate25(safetychainopen).If the adjustable time (P20) haslapsed and the safety chain is still open, the system changes tolockout due to an error or restarts (depending on the anti-oscillationcounter).
Thissettingisalsovalidifthesafetychain is opened after state 4.
Setting:0: Restart attempt depending onthe anti-oscillation counter1:Immediatelockout
P16 Air pressure switch operating mode
Monitoring of the air pressure may beactivatedforstart-up(states6to10)and/oroperation(states13,14and 17 to 20) and/or during post-purge(state20).Alsoforidlestatecontrol(state3).
Air pressure switch operating modeSetting Air pressure moni-
toring during post-purge
Air pressuremonitoring during startup
Air pressuremonitoring during operation
Idle statecontrol
0 OFF OFF OFF OFF1 OFF OFF OFF ON2 OFF OFF ON OFF3 OFF OFF ON ON4 OFF ON OFF OFF5 OFF ON OFF ON6 OFF ON ON OFF7 OFF ON ON ON8 ON OFF OFF OFF9 ON OFF OFF ON10 ON OFF ON OFF11 ON OFF ON ON12 ON ON OFF OFF13 ON ON OFF ON14 ON ON ON OFF15 ON ON ON ON
29 … 12628 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P17 Temperature control-ler operating mode
- Internal parame-ter Value will be set automatically by the MPA.
The temperature controller can be operated in the following operating modes:
Setting0:The heat request is always swit-ched OFF, independently of thehard-ware inputSetting1:The heat request is always swit-ched ON, independently of thehardware inputSetting2:TheheatrequestisOFF,however,this operating mode must be de-fned again within one minute. Oth-erwise the automatic gas burner control system switches to the set-ting3.Thiscanhappen,forexam-ple,ifthefildbuscommunicationisinterrupted.Setting3:The heat request is determined by hardware input "temperature con-troller".Setting4:The heat request isON, however,this operating mode must be de-fned again within one minute. Oth-erwise the automatic gas burner control system switches to the set-ting3.Thiscanhappen,forexam-ple,ifthefildbuscommunicationisinterrupted.
29 … 12628 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P18 Flame detector 2 or gas pressure detec-tor
This parameter defineswhether asecondflamedetector,agaspres-sure detector or a limit switch for valvemonitoringisconnected.
Setting0:The inputs NO and NC are moni-toredfortheflamesignal.Thesig-nalsmustbeinverse.Setting1:Only input NO is monitored for the flamesignal.Setting2:Only input NO is monitored for the flame signal. In addition, the Gaspressure switch signal is read out on input NC.Setting3:Only input NO is monitored for the flame signal. In addition, the limitswitchsignalforvalve1isreadouton input NC.Setting4:Only input NO is monitored for the flame signal. In addition, the limitswitchsignalforvalve2isreadouton input NC.
P19 Configuration of the output operating mode
The output may be switched to dif-ferent states by means of the follow-ing parameter settings. ON means 115VACor230VAC,forallothers,OFF,i.e.0V.
Setting0:"Wait":OutputisONinstate2(wait-ingforheatrequest).Setting1:"Stable":OutputisONinstates18(operation)and19(pause4).Setting2:"Main flame ON" output is ON instates17 (flameB stabilisation) to19(pause4).Setting3:"Flame ON" Output is ON from states13 (flameAstabilisation) to19(pause4).Setting4:"Follow-up": Output is ON fromstates13 (flameAstabilisation) to19(pause4).
Whenthisstateswillbeleft,theout-putremainsforanother15minutes. This follow-up information remains activatedbeyondarestartattemptof the automatic gas burner control system,butnotifthemainssupplyisswitchedoffandonagain.In addition, the output is switchedon for one minute after 24 hours as pump blocking protection. Note:After a restartwithin 24 hours the24 hour cycle of the pump blocking protection starts new.
31 … 12630 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P20 Duration of safety chain open
This parameter defines the dura-tionofstate25(safetychainopen).Time until the system restarts or changes to lockout, depending ontheanti-oscillationcounterandP15(lockingwithopensafetychain).
Valuerange:0to65535(resolutionin1/16s).
P21 Shutter test for flame detector
Theshuttertestoftheflamedetec-torisactivatedbymeansofthispa-rameter. Makesure toobserve the settingsfor parameter P33 (active FLW inphase 1) and P36 (active FLW inphase2).
Example: If P33=1 and P36=1,there is not any shutter flame testforflamedetector2.Thetestisonlyactiveinstateswith"flameON"(states12-19).Setting0:Shutterflametestinactive.Setting1:Shutterflametest forflamedetec-tor1.Setting2:Shutterflametest forflamedetec-tor 2.Setting3:Shutterflametest forflamedetec-tors 1 and2 (expert setting).Withthis setting, the test starts only ifboth flame signals report ON; itendswithsuccessifbothflamesig-nals report OFF
P22 FM mode Setting0:notactiveSetting1:Lockoutwithmissinggasandfaultof limit switch for main gas.
P30 Duration of pre-purge Thisparameterdefinesthedurationofstate8(pre-purge).
Valuerange:0to65534(resolutionin1/16s).
P31 Duration of pre-igni-tion time
Thisparameterdefinesthedurationofstate10(pre-ignition).Duringthistime, the ignition is already active,thegasvalveisclosed.
Valuerange:2to65534(resolutionin1/16s).
P32 Start-gas flame proving period / first safety time
Definesthedurationofthestart-gasflameprovingperiod.Maximum time from opening the gasvalvestodetectingaflame.
Note:This duration is divided intostates11and12.State12isalways0.5seconds.
Valuerange:16to960(resolutionin1/16s).
Attention: For FM applications thefollowingvaluesshouldnotex-ceeded.Burnerwithpilotflame:10sBurnerwithdirectignition:<2,500,000Btu/hr≤15s>2,500,000Btu/hr≤10s
31 … 12630 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P33 Active flame detector(s) for start-gas flame proving period
Theparametercontrolswhichflamedetector(s) (states11 to16) is/areactivefordetectingaflame.
Note: If flame signal 2 is used,please make sure to observe thesettingforP18(flamedetector2orgaspressuredetector).
Setting:1:Onlyflamesignal1relevant2:Onlyflamesignal2relevant3:Flame1ANDflame24:Flame1ORflame2
P34 Stabilisation time A Durationofstate13"FlameAstabilisation"
Valuerange:0to65534(resolutionin1/16s).
P35 Second start-gas flame proving period
Durationofthesecondsafetytime;the time between detecting the flamesignalofthefirstsafetytimeand the maximum time is set. Maxi-mum time from opening the gas valvestodetectingaflame.
Note: This duration is divided intostates15and16.State16isalways0.5seconds.Valuerange:16to480(resolutionin1/16s).
Attention: For FM applications thefollowingvaluesshouldnotex-ceeded.Burnerwithpilotflame:10s(Settingvaluemax.160)Burnerwithdirectignition:<2,500,000Btu/hr≤15s(Settingvaluemax.240)>2,500,000Btu/hr≤10s(Settingvaluemax.160)
P36 Active flame detector(s) for phase 2
The parameter controls which flamedetector(s)(states17"FlameBstabilisation"to19"Pause4")is/areactiveinphase2fordetectingaflame.Note:Ifflamesignal2isused,pleasemakesuretoobservethesettingforP18(flamedetector2orgaspressuredetector).
Setting:1:Onlyflamesignal1relevant2:Onlyflamesignal2relevant3:Flame1ANDflame24:Flame1ORflame2
P37 Stabilisation time B Durationofstate17"FlameBstabilisation"
Valuerange:0to65534(resolutionin1/16s).
P38 Operating mode V1 V2 DefinestheoperatingmodesforgasvalvesV1andV2duringoperation.Onlyvalidforstates18(operation)and19(pause4).
0:Interruptedstartgas.V1OFF,V2ON 1:Permanentstartgas.V1andV2ON2:Two-leveloperation.V1ON,V2ON/OFF during operation; deter-mined by bus. V2 does not openduring the second start-gas flameprovingperiod!
Note: If you use setting 2, a bus con-nection isrequired. If it ismissing,restart is tried because the bus connection is monitored in the op-erating states.
33 … 12632 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParametersParameter description
Parameter Designation Description Setting / Examples
P40 Standard mode dura-tion
IftheMPAisoperating,itchangesto state 2 after this time has lapsed and restarts. Aself-testduringstart-upisrequiredevery24hoursinintermittentopera-tion.Iftheheatrequestisactiveuntilthese24hourshavepassed,anautomatic restart is tried.
NOTE(ifcontinuousoperationisnotset):ThestabilisationtimesA(P34)andB(P37)areaddedtotheoperatingtime;therefore,thesetimes are deducted from the dura-tion of the normal operation if they exceed1minute.If the total of stabilisation times is longer than the duration of the normaloperation,thedurationofthenormaloperationissetto0,andMPAswitchesoffimmediatelywhenstartingoperation(state18).
Valuerange1to65534:Timeuntilrestart(reso-lutioninminutes)65535:Continuousoperation1439:Intermittentoperation
P41 Operation safety time FLW1
DefinesthedurationofthesafetytimeforMPA41xxduringoperationforflame1.Timeuntilgasvalvesclosewhenthereisnotanyflame.
Valuerange:12to48(resolutionin1/16s).
ATTENTION: The entire reaction time after there is not any flame during operationis combined of P41 and possiblereaction times of external flamedetectors,seechapter14Annex -flamedetector.
P42 Operation safety time FLW2
Definesthedurationofthesafetytimeduringoperationforflame2.Maximumtimeuntilgasvalvesclosewhenthereisnotanyflame.
Valuerange:3to48(resolutionin1/16s).
ATTENTION: The entire reaction time after there is not any flame during operationis combined of P42 and possiblereaction times of external flamedetectors,seechapter14Annex -flamedetector.
P50 Follow-up time Definesthedurationofthefollow-uptime(state21).However,thetime measurement is already start-edduringpost-purge(state20),i.e.if the follow-up time is smaller than orequaltothepost-purgetime,thefollow-up state is skipped.
Valuerange:9to65534(resolutionin1/16s).
P51 Post-purge time Definesthedurationofthepost-purgetime(state20).
Valuerange:0to65534(resolutionin1/16s).
P52 Restart protection Definesthedurationoftherestartprotection(state22).
Valuerange:0to65534(resolutionin1/16s).
Notes regard-ing P50, P51
and P52
Post-purge (P51) may be interrupted by a repeated heat request if the restart protection (P52) has been set to 0 and the follow-up time (P50) has already lapsed.
P260 and following
Internal parameters Pleasedonotchange!
33 … 12632 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParameterFactory settings
Pa-ram-eter
Designation Factory setting
Unit Accesslevel
Comfortparameter setting
Min. value Max. value
P11 Field bus ad-dress configura-tion
255 SERVICE x 0 255
P12 Number of re-start attempts or anti-oscillation counter
5 OEM 0 5
P13 Number of restart attempts when flame is missing after the start-gas flame proving period
0 OEM x 0 5
P14 Number of restart attempts after a flameout or missing flame after the second start-gas flame proving period
0 OEM x 0 5
P15 Locking with open safety chain
ON OEM x
P16 Air pressure switch operating mode
15 OEM x 0 15
P18 Flame detector 2 or gas pres-sure switch
0 OEM x 0 4
P19 Configuration of the output oper-ating mode
1 SERVICE x 0 255
P20 Duration of safety chain open
960 1/16s OEM 0 65535
P21 Shutter test for flame detector
0 OEM x 0 3
P22 FM mode OFF OEMP30 Duration of pre-
purge32 1/16s OEM x 0 65534
P31 Duration of pre-ignition time
16 1/16s OEM x 0 65534
P32 Start-gas flame proving period / first safety time
16 1/16s OEM x 16 960
P33 Active flame detector(s) for start-gas flame proving period
1 OEM x 1 4
P34 Stabilisation time A
48 1/16s OEM 0 65534
35 … 12634 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParameterFactory settings
Pa-ram-eter
Designation Factory setting
Unit Accesslevel
Comfortparameter setting
Min. value Max. value
P35 Second start-gas flame prov-ing period
16 1/16s OEM x 16 480
P36 Active flame detector(s) for phase 2
1 OEM x 1 4
P37 Stabilisation time B
48 1/16s OEM 0 65534
P38 Operating mode V1 V2
1 OEM x 0 2
P40 Standard mode duration
1439 min. OEM x 0 65535
P41 Operation safe-ty time FLW1
16 1/16s OEM x 12 48
P42 Operation safe-ty time FLW2
16 1/16s OEM x 3 48
P50 Follow-up time 80 1/16s OEM 16 65534P51 Post-purge time 80 1/16s x 0 65534P52 Restart protec-
tion80 1/16s SERVICE x 0 65534
35 … 12634 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Status InformationMPA 41xxDesignation Description Display
via Vision-Box
Display viadisplay
General informationLockout Systemislocked ● LED
Statenumber Currentstateofthesystem,keycombination+and-
● 7-segment
Currentaccesslevel ●Flame Flame detected ● LEDManual mode Systeminmanualmode ● 7-segmentFlame quality Value>49goodflame(forionisation) ● InfoHardwareinputfortemperaturecontroller Signalfortemperaturecontrollerinput ●
Bus connection present ● 7-segmentHeatrequest Signalcombinationfrombussetpointinputandhardwareinput ● LEDInputsLDW ●Flame1 Signalfromflame1input ●Flame 2 NO Signalfromflame2_NOinput ●Flame2NC/GDW/POC Signalfromflame2_NCinputorGDWorPOC ●OutputsGasvalveV1 ●GasvalveV2 ●Ignition ●Fan ●CounterTimecounter/Lifetime counter
Time since switching on the automatic gas burner control system
●
Runtimemeter Fixed runtime ● InfoRuntimemeterResettable ResettableviaVisionBoxanddisplay ●
Startcounter Fixed start counter ● InfoResettablestartcounter ResettableviaVisionBoxanddisplay ●SwitchingcyclescounterV2 ● InfoInternal informationStatetimerinminutes Displayedstatetimerrunsinminutes,otherwisein1/16sec. ●Initialisation phase The automatic gas burner control system is being initialised ●Multi-function switch Is "ON" when unlock key is pressed ●Accesslevelchange CCCorvalueflashesondisplay,↵keyexpected ● 7-segmentSafetyswitch-offflag Systemislocked ●Error index Internal error counter ●Remainingstatetime is65535ifunlimitedremainingtime ●Cycl. state counter Countsin1/128scycle ●Processorload ●Nominal modulation degree No function ●Actualmodulationdegree No function ●
LED:Indicatedbyoneofthe3LEDsonthedisplay7-segment:Indicatedbyoneorseveralcharactersofthe7-segmentdisplayInfo:Displayedininformativedisplaymode
37 … 12636 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA 4111Version without displayTheMPA4111versionmaybeusedifthedialogviathedisplayisnotrequired or limited information is enough.
The parameters of the system are eithersetbymeansofVisionBoxorby means of the parameterisation andservicebox.
The system status is indicated by meansoftwoLEDs.
Displayunit
Yellow LED- Operation
Red LED- Fault- Flashing signal for error code-Pausestateduringparametersetting
RESET key-Unlocking- Extended unlocking-Confirmationofaccesslevelchange
Yellow LED information
LEDOFF:Fault(state0)
LEDpermanentlyON:Waitingforheatrequest(state2)untilsecondsafetytimeforflamedetec-tion(state17)andfromstatespost-purge(20)topause5(23).
FlashingLED(0.5Hz):Operation(states18and19).
FastflashingLED(2Hz):Waiting for gas pressure if gas is missing(state24)andsafetychainopen(state25).
Red LED information
FaultThedifferentflashingfrequenciesindicate the most important error codes.The remaining error codes are indi-catedbyapermanentlylitLED.
Both LED information:PasswordentryexpectedBothLEDflashingalternating
MPA4111inParametermodeAfterenteringofthepasswordbothLEDareflashingsimultariousParametercouldbechanged
37 … 12636 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
...
4s Pause4s Pause
... ...LED ein
LED aus
Anzahl der LED aus, je nach Fehler-Blink-Code
1s 1s
Blink code Minimum indication
Error ID Error designation
Pleaseseethetablesaboveformoreinformationabouttheindividualerrors.1 0xA2 ERROR_SAFETY_CHAIN_OPEN2 0x60 ERROR_PARAMETERCHANGE_NOTRELEASED3 0xA7 ERROR_NOFLAME_DURING_FIRSTSAFETYTIME3 0xBC ERROR_NOFLAME_DURING_SECONDSAFETYTIME3 0xA9 ERROR_FLAME_GONE_OUT_DURING_STABILISATION4 0xA8 ERROR_FLAME_GONE_OUT_DURING_OPERATION5 0xAA ERROR_IDLESTATECONTROL_LDW5 0xAB ERROR_NO_AIR_PRESSURE6 0xA6 ERROR_EXTERNAL_LIGHT7 0x18 ERROR_EXTERNAL_APPLICATION8 0x16 ERROR_TWI_COMMUNICATIONANDLOWVOLTAGE
Parameter setting
Tochangeparameters,settheswitchintheconnectionchamberto"Para"and supply the system with power; bothLEDsareflashingalternately.EnterthepasswordandconfirmitbypressingtheRESETbutton.BothLEDsareflashingsimultaneously.The parameters may now be changed.Inparametermode,theMPAstopsinpausestates;presstheRESETbuttontocontinuetothenextstate(seestatedescription).
Attention: The changed parameters areappliedafterpause5(state23).TheflashingfrequencyoftheLEDshows the pause state and that it is requiredtopresstheRESETbutton.
Example: The pause 4 state has beenreached:theredLEDflashes4timesandisthenswitchedoffduring4 seconds.
...4s Pause4s Pause
... ...
LED ein
LED aus
Anzahl der LED ein, je nach Pausenstate
1s 1s
Information about both LEDs:
BothLEDsarelightedtwicetochecktheirfunctionalitywhenlivevoltageisapplied.
BothLEDflash(1Hz)ifyouarere-quested to press a button to change aleveloriftheautomaticgasburnercontrol system is ready for the ex-tendedunlocking(pressingabuttonafter5s,until10s).
BothLEDsflashalternatelyifthesys-tem is started in parameter mode and the password for changing the pa-rametershasnotbeenenteredyet(inVisionBoxonPC).TheRESETbuttonand the manual mode are locked.
Error code - flashing frequency
Numberofswitched-offLEDs, dependingonerrorflashcode
Numberofswitched-offLEDs, dependingonerrorflashcode
LEDON
LEDON
4s pause
4s pause
4s pause
4s pause
LEDOFF
LEDOFF
39 … 12638 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA 4112/MPA 4122Version with displayThecustomermaycustomizetheMPA4112/MPA4122versiononthe integrated display to match the desired burner.Allimportantparametersmaybesetby means of the four operating keys.
Theparametersofthedeviceareei-thersetbymeansofVisionBoxorbymeans of the parameterisation and servicebox.
3x7segmentdisplay
LED:Blue:HeatrequestYellow:Flamequality(flashesiftheflamequalityispoor)Red:Fault
Release buttonRESETfunctionandconfirmationofthe entry
Back
PlusIncreasesthedisplayedvalue
MinusReducesthedisplayedvalue
Dependingontheoperatingstateof the automatic gas burner control system,differentinformationisdis-played:
39 … 12638 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Overview of the display modes for MPA 4112/MPA 4122
Mode:
Operation display
Error display
Info display
Displayoftheerrormemory
Parameterdisplay
Resetdisplay
Flashing display
Active:
innormaloperationifnoerrorisactive
if the automatic gas burner control system is in lockout
From operation display by pressing a shortcut
and
From operation display by pressing a shortcut
From operation display by pressing a shortcut
From operation display by pressing a shortcut
Dependingonthedisplaymode:
1.Requesttoconfirmtheaccesslevelchange2. Keeptheunlockkeydepressedformorethan5storestarttheMPA ("Extendedunlocking")
3.Processor2error,seeerrorlist4. New password after password change5. Restartofthesystem,allsegmentsandLEDsareflashing
41 … 12640 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA41x2 display
MPA41x2 display
▶ Displayed operating state for setting parameters and troubleshooting
Heatrequestblue
Flameyellow
Faultred
Characterblue
AttentionIllustrationin7-Segmentdisplay
1.Digits
6=
8=
0=
2. Characters
Bor.b=
Dor.d=
Ooro=
41 … 12640 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
MPA 4112 display
▶ Shows the operating state of the system
11.7 Operating state
Post-purgeFollow-up timeRestartprotection
Waiting for safety chain
with open safety chain from watchdog loading phase state
Waiting for gas pressure
withinsufficientgaspressure
Flame B stabilisationOperation
SecondsafetytimeSecondsafetytime-Flame detection
FlameAstabilisation
Pre-ignitionFirst safety time - ignition First safety time -Flame detection
IdlestatecontrolLDW(airpres-sureswitch)SafetychaincheckWatchdog loading phaseWaiting for air pressure External light controlPre-purge
Waiting for heat request
Parameterswitchto"Auto",pow-er supply "On"
43 … 12642 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Operation display
Additional display information
▶ Display of state number▶ Display of bus address
Displayofstatenumber
Press the keys simultaneously to changethe state display
DisplayofbusaddressorOFF
Displayofbusaddresswhilepress-ing a key
Operation display
43 … 12642 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parametersareloadedfromtheparameterisation and serviceboxintoMPA
Operation display
Display / Parameterisation and service box
▶ Display of the state of the automatic gas burner control system for parameterisation or check in the service box
TheMPAisintestmodeinitialisedbytheparam-eterisationandservicebox.Note:Theparameterandresetdisplayislockedduring the test
45 … 12644 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Information display
▶ The information display is activated from the operation display (not during automatic parameter setting).
▶ The information display allows to see the flame quality, the resettable runtime meter, the resetta-ble start counter and the switching cycles counter.
▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.
Info display
DisplayofflamequalityMax58<50flashingseealso:Appendix-Flamesafeguard
Displayofresettableruntimemeter Tens of thousands digit
Displayofresettableruntimemeter Hundredsdigit
Displayofresettableruntimemeter Unit
Displayofresettablestartcounter Tens of thousands digit
Displayofresettablestartcounter Hundredsdigit
Displayofresettablestartcounter Unit
DisplayofswitchingcyclecounterV2Tens of thousands digit
DisplayofswitchingcyclecounterV2Hundredsdigit
DisplayofswitchingcyclecounterV2Unit
Back to operation display
from each info display state
Back to operation display
45 … 12644 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error display
▶ The error display is automatically activated if the automatic gas burner control system signalises an error.
▶ The last occurred error is displayed.
Error display
The state number is displayed as long as the plus button is pressed
The additional error note is displayed as long as the minus key is pressed
Automaticactivationifafaultisactive
The current bus address is displayed as long as the back key is pressed
Unlock
47 … 12646 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Display of the error memory
▶ The error memory shows the last 10 errors.▶ The error that has occurred last is displayed.
▶ The error memory display is activated out of the operation display (not during automatic param-eter setting).
▶ The error code is displayed on the two-digit seven-segment display.
▶ This error memory display is quit after 60 s due to a timeout if you do not press any key within this time period.
▶ If there is not any error for the error position, -- is displayed.
Display of the error memory
The state number is displayed as long as the plus button is pressed
The additional error note is displayed as long as the minus key is pressed
Back to operation display
Lasterroroccurred
Ifthekeyispressed,thepreviouserrorisdisplayedalways.
From each error display state
The state number is displayed as long as the plus button is pressed
The additional error note is displayed as long as the minus key is pressed
Back to operation display
Tenth to last error
...
47 … 12646 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
DisplayNumber
Parameter Valuerange
Unit
0 P30-pre-purgetime 0...99 1s1 P31-durationofpre-ignition 0...99 1s2 P32-Firststart-gasflameprovingperiod 1...60 1s3 P33-Activeflamemonitoringphase1 1...44 P35-Secondstart-gasflameprovingperiod 1...30 1s5 P36-Activeflamemonitoringphase2 1...46 P41-Operationsafetytimeforflamedetector1 06...30(=0.6...3s) 0.1s*1
7 P42-Operationsafetytimeforflamedetector2 05...30(=0.5...3s) 0.1s*1
8 P51-post-purgetime 0...99 1s9 P14-Numberofpermittedrestartsafterflamelift-offduringoperation 0...5A P13-Numberofpermittedrestartsaftermissingflame 0...5b P15-Lockingafteropeningthesafetychain 0=OFF/1=ONC P16-Operatingmodeoftheairpressuredetector 0...15d P38-OperatingmodeV1V2 0...2E P18-Flamedetector2NCmonitoring/Gaspressureswitch/POC 0...4F P40-Continuousoperation(noswitch-offafter24h) 0=OFF/1=ONh *3 P21-Shuttertestforflamedetector 0...3L P19-Outputoperatingmode"Operation" 0...4o P52-Durationofrestartprotection 0...99 1sn *2 P11-Fieldbusaddress 0...99*2
*1Adjustableinsteps: 05=0.5s 8/16 (onlypossibleforFLW2forFLW41Iwith0,19sreactiontime) 08=0.75s 12/16 (onlypossibleforFLW1,smallestpossibleadjustment) 09=0.875s 14/16 (forUV41/UV42with0.125sreactiontime) 10=1s 16/16 15=1.5s 24/16 (forFLW41Iwith0,19sreactiontime) 19=1.875s 30/16 (forUV41/UV42with0.125sreactiontime) 20=2s 32/16 25=2.5s 40/16 (forFLW41Iwith0,19sreactiontime) 29=2.875s 46/16 (forUV41/UV42with0.125sreactiontime) 30=3s 48/16
*2Usetheshortcut-and+toswitchbetweenOFF(display=oF)andtheaddress.Thesetting"o"isonlydisplayedifabusmoduleisconnected.Addressesover99mustbesetbymeansofVisionBox.
*3Thesetting"h"isonlydisplayedifcontinuousoperationisactiveorhasbeenactivatedinsettingF.
Parameter display
Parameter display
▶ After activating the automatic parameter setting, 19 parameter values must be defined; see param-eter list.
▶ This parameter setting is not quit by means of a timeout. ▶ A password is required for changing the parameters.
▶Attention: Some parameter values are displayed in another resolution than in the parameter mode using VisionBox. If it is not possible to display the parameter value in this resolution, -- is dis-played; nevertheless, the value may be changed in the resolution that can be displayed.
▶ To change service or OEM parameters, the required password or a higher-level password must be entered (e.g. all service parameters may also be changed using the OEM password).
49 … 12648 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
flashing(30stimeout)
Passwordentry1stcharacter
Passwordentry2nd character
flashing(30stimeout)
Parameterswitchto"Para",power supply "On"Passwordentry
Parameter display
▶ Attention: Press the "Back" button to return to previous steps in parameter mode.If you have reached the first entry field again, press the key again to quit the parameter mode.
49 … 12648 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parameter0(P30)Pre-purgetime(0-99s/1s)
Parameter1(P31)Pre-ignition(0-99s/1s)
Parameter2(P32)Firststart-gasflameprovingperiod (0-60s/1s)
Parameter3(P33)Activeflamemonitoringphase1(1-4)
51 … 12650 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parameter4(P35)Secondstart-gasflameprovingperiod (1-30s/1s)
Parameter5(P36)Activeflamemonitoringphase2(1-4)
Parameter6(P41)Operationsafetytimeforflamedetector1(0,8-3s/0,1s)
Parameter7(P42)Operationsafetytimeforflamedetector2(0,5-3s/0,1s)
51 … 12650 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parameter8(P51)Post-purgetime(0-99s/1s)
Parameter9(P14)Numberofpermittedrestartsafterflamelift-offduringoperation(0-5)
ParameterA(P13)Numberofpermittedrestartsafternoflameatstartup(0-5)
Parameterb(P15)Lockingafteropeningthesafetychain0=NO(OFF)1=YES(ON)
53 … 12652 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parameter[(P16)Operating mode of the air pressure detector (0-15)
Parameterd(P38)OperatingmodeV1;V2(0-2)
ParameterE(P18)Flamedetector2NCmonitoring/GDW/POC(0-4)Attention:Setparameterto01ifFLW2inputisunused
ParameterF(P40)Continuous operation0=NO(OFF)1=YES(ON)
ON
OFF
Parameterh(P21)Shuttertestforflamedetector(0-3)
53 … 12652 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Back to parameter0
ParameterL(P19)Outputoperatingmode(0-4)
Restartprotectionparameter(P52)Durationoftherestartprotection(0-99s/1s).
Parametern(P11)Fieldbus address (0-99)
Manual modefor checking the settings
(press+and-to-gether to switch fieldbusOn/orOff
55 … 12654 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Post-purgeFollow-up timeRestartprotection
Waiting for safety chain
with open safety chain from watchdog loading phase
Waiting for gas pressure
withinsufficientgas
Flame B stabilisationOperation
SecondsafetytimeSecondsafetytime-Flame detection
FlameAstabilisation
Pre-ignitionFirst safety time - ignition First safety time -Flame detection
IdlestatecontrolLDW (airpressureswitch)SafetychaincheckWatchdog loading phaseWaiting for air pressure External light controlPre-purge
Waiting for heat request Manualoperation-Pause1
in manual mode
"Next" key
"Next" key
Manualoperation-Pause2
Manualoperation-Pause3
in manual mode
"Next" key
Manualoperation-Pause4
in manual mode
"Next" key
Manualoperation-Pause5
in manual mode
Startparameter0
ParametersettingfinishedInterruptvoltagesupplySwitchfrom"Para"to"Auto"
Manual mode for checking settings
55 … 12654 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Reset display
Reset display
▶ The reset display is activated out of the operation display (not during automatic parameter set-ting).
▶ The reset display allows deleting error memory, access level, resettable runtime meter or start counter and changing the passwords for service and OEM level.
▶ This mode is quit after 60 seconds due to a timeout if you do not press any key within this time period.
▶ If the test mode of the programm- and service box is active the reset display is locked.
Activationoftheresetdisplaybysimultaneous pressing of the keys
Previousaction
Next action
Cancel the action
Action0,1,2,3
Actiontobecarriedout:0 deletestheerrormemory1 resetstheaccesslevel2 deletes the resettable
runtime meter3 deletesresettablestartcounter4 Change password forservicelevel
5 ChangepasswordforOEMlevel
Action4,5
Back to operation display
57 … 12656 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Correct password
Entry1stcharacter
Incorrect password
Back to operation display
Entry2nd character
Entryofthepreviouspassword1stcharacter
Entryofthepreviouspassword2nd character
Displayofnewpassword
Displayofnewpassword
Operation display
57 … 12656 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xx error table for minimum indication (MPA4111) ordered by flash codeErrorID
Internalerror
Error descriptionPlease see the tables above for more information about the individual errors.
1 0xA2 ERROR_SAFETY_CHAIN_OPEN2 0x60 ERROR_PARAMETERCHANGE_NOTRELEASED3 0xA7 ERROR_NOFLAME_DURING_FIRSTSAFETYTIME3 0xBC ERROR_NOFLAME_DURING_SECONDSAFETYTIME3 0xA9 ERROR_FLAME_GONE_OUT_DURING_STABILISATION4 0xA8 ERROR_FLAME_GONE_OUT_DURING_OPERATION5 0xAA ERROR_IDLESTATECONTROL_LDW5 0xAB ERROR_NO_AIR_PRESSURE6 0xA6 ERROR_EXTERNAL_LIGHT7 0x18 ERROR_EXTERNAL_APPLICATION8 0x16 ERROR_TWI_COMMUNICATIONANDLOWVOLTAGE
59 … 12658 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xx error without error IDErrorID
Internalerror
Error description
F1flashing
LowvoltageBus connection interruptedInternal error
F2flashing x Theconnecteddisplayisinvalid
F3flashing
The password has been entered incorrectly when trying to change it or has not been con-firmedbymeansoftheunlockkey
F4flashing
Thesignaloftheremoteunlockingviabusisactivetoolong
F5 to F8 not usedF9
flashingConnection to bus missing. The bus module has been connected but there is not any con-nection to the master.
FAflashing x Failedtoreadparameter"Outputoperatingmode",theoutputfortheoperatingmodeisnot
switched
59 … 12658 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xxError from the basic system (0x01 to 0x3F)ErrorID
Flash code
minimum indica-
tion
Internalerror
Error description
0x01 0 X ERROR_INTERRUPT_CYCL_STATEFRAME0x02 0 X ERROR_WD_TRIGGERING
0x03 0
ERROR_WD_HARDWAREPossiblecauseoftheerror:Too high ambient temperatureOvervoltage
0x04 0
ERROR_UNLOCKING_DENIEDPossiblecauseoftheerror:Morethan5unlockingoperationsinthelast15minutes. Remedy:Waitorextendedunlocking
0x05 0 x ERROR_ROM_TEST0x06 0 x ERROR_RAM_TEST0x07 0 x ERROR_PINSHORTCIRCUIT0x08 0 x ERROR_STACK_OVERFLOW0x09 0 x ERROR_PROGRAMMING0x0A 0 x ERROR_DI_VARIABLE0x0B 0 x ERROR_IN_TABCONTROLERROR0x0C 0 x ERROR_CONFIGURATION0x0D 0 x ERROR_CPU_TEST0x0E 0 x ERROR_EEPROM_PARAMETER0x0F 0 x ERROR_ADDRESS_TEST0x10 0 x ERROR_FUNCTION_ERRORID
0x11 0ERROR_UNDERVOLTAGEPossiblecauseoftheerror:Theadmissiblelowervoltagelimitwasnotreachedatleastforashorttime
0x12 0ERROR_POWERFAILUREPossiblecauseoftheerror:Thesupplyvoltagewasinterruptedduringstartup,operationorregularswitch-off
0x13 0
x ERROR_WD_STATUSSafetychainnotpotential-free.Possiblecauseoftheerror:The fan continues running too long. Remedy:Increasethetimefortherestartprotection
0x14 0 x ERROR_DI_SEGMENT_TEST0x15 0 x ERROR_SFRREGISTER_TEST
0x16 0
ERROR_TWI_COMMUNICATIONPossiblecauseoftheerror:ATWIbususerwasconnectedtothebusorseparatedfromthebuswhiletheMPAwasnotdisconnectedfromthemains.Remedy:ConnectorseparateauseroftheTWIbusonlyiftheMPAisdisconnectedfromthemains.Too many users are connected to the TWI bus or EMC faults occur on the TWI line. Remedy:Useshorterlinesorreducethenumberofusers
0x17 0 x ERROR_STATEFRAME_OVERLOAD
61 … 12660 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xxError from the basic system (0x01 to 0x3F)ErrorID
Flash code
minimum indica-
tion
Internalerror
Error description
0x18 7
ERROR_EXTERNAL_APPLICATIONPossiblecauseoftheerror:Aswitch-offhasbeenactivatedbyanexternaluser,forexamplebyselectingthefunction"Switch-off"inthePCsoftwareoftheVisionBoxTimeoutofparametermode/manualmode(0.5hwithoutpressingakey)-de-tailerror4thbyte=0xA0An invalid fieldbusaddresshasbeenentered inP11 for the connectedbusmodule.Detailerror4thbyte=0xA1and6thbyte=setaddressP11
0x19 0 not used0x1A 0 x ERROR_SWWD_DURING_INITIALISATION0x1B 0 x ERROR_BUFFEROVERFLOW0x1C 0 x ERROR_SYNCHRONISATION_DURING_INITIALISATION
0x1D 0ERROR_PROCESSORFAILUREPossiblecauseoftheerror:ThereisstrongEMCinterferenceonMPA
0x1E 0 x ERROR_SFRREGISTER_STATEBLOCK
61 … 12660 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID
Flash code
minimum indica-
tion
Internalerror
Error description
0x40 - 0x42
reserved
0x43 0 x ERROR_TEST_IONISATIONINPUT0x44 - 0x5F
reserved
0x59
ERROR_MONITORING_INTERFACEP2Internal failureFieldbusnotconnectedorinterruptedwhileP38setting=2(externaldetarmin-ationV2)
0x60 2 ERROR_PARAMETERCHANGE_NOTRELEASEDAmonitoredparameterhasbeenchanged
0x61 ERROR_SHUTTERTEST
63 … 12662 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID
Flash code
minimum indica-
tion
Internalerror
Error description
0xA0 0 x ERROR_STATE_DURATION_TOO_LONG0xA1 reserved
0xA2 1
ERROR_SAFETY_CHAIN_OPENPossiblecauseoftheerror: The safety chain has been opened or is not closedThe wires of the safety chain are interrupted
0xA3 not used0xA4 0 x ERROR_FEEDBACK_V1_INCORRECT0xA5 0 x ERROR_FEEDBACK_V2_INCORRECT
0xA6 6
ERROR_EXTERNAL_LIGHTPossiblecauseoftheerror:Earth connection to an ionisation electrodeGasflowsoutandisburnedforexamplebyneighbouringburnersWrongconfigurationofP46andP47(totalmustbegreaterthan0.5s)DefectiveUVtubeConnectedflamedetector(UV,...)detectslightorisdefective
0xA7 3
ERROR_NOFLAME_DURING_FIRSTSAFETYTIMEAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:Ionisation electrode incorrectly setIgnition electrodes incorrectly setInsulatedlinesoftheignitionelectrodesordefectiveionisationelectrodeGasvalvesdonotopenthegasflowConnectedflamedetector(UV,...)doesnotdetectlightorisdefectiveLinesofmainsconnectionontheMPAexchanged("N"and"L1")
0xA8 4
ERROR_FLAME_GONE_OUT_DURING_OPERATIONAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1Possiblecauseoftheerror:FlamebodydefectiveConnectedflamedetector(UV,...)doesnotdetectlightorisdefective
0xA9 3ERROR_FLAME_GONE_OUT_DURING_STABILISATIONAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1
0xAA 5
ERROR_IDLESTATECONTROL_LDWPossiblecauseoftheerror:TheairpressuredetectorisdefectiveThereisairpressureduringtheidlestatecontrol,forexampleduetoanairflowfromtheexhaustline,...Thethresholdvalueoftheairpressuredetectorissetincorrectly
0xAB 5 ERROR_NO_AIR_PRESSURE0xAC 0 x ERROR_FEEDBACK_IGNITION_INCORRECT0xAD 0 ERROR_LACKOFGAS_GDWMIN0xAE–0xAF
reserved
0xB0 0 x ERROR_TESTCIRCUIT_EXTENSION0xB1-2 reserved
0xB3 ERROR_GASVALVEFEEDBACK_FALSEAdditionalinformationbyte0:1=V1,2=V2
0xB4-5 reserved0xB6 0 ERROR_LIMITSWITCH_MAINGAS(POC)
63 … 12662 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewMPA 41xxError from the extended functions (0x40 to 0x9F)ErrorID
Flash code
minimum indica-
tion
Internalerror
Error description
0xB7–0xBB reserved
0xBA ERROR_FALSEFLAME_STARTFalseflame>1min.afterheatrequest
0xBC 3ERROR_NOFLAME_DURING_SECONDSAFETYTIMEAdditionalinformationbyte0:Bit0=FlametoFLW1;Bit1=FlametoFLW2Additionalinformationbyte1:FlamequalityforFLW1
0xBD 0 ERROR_FLAMEDETECTOR_NOTSWITCHED_INVERSE0xBF 0 ERROR_SAFETY_CHAIN_NOT_POTENTIAL-FREE
65 … 12664 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Annex
Setting bus adress, bus termination ................................................................................................................. 65Profibus, Modbus, Shutter Extension module MPA 41xx - EM 2/4 ............................................................ 66-78Multifunctional modul MPA 41xx-EM 2/6 ..................................................................................................... 79-104Flame detector ............................................................................................................................................ 105-106 UV 41 ............................................................................................................................................................107-108UV 42 ............................................................................................................................................................109-110UV 4x EM 1/1 Shutter module ...................................................................................................................... 111-112FLW 20 UV ....................................................................................................................................................113-115FLW 10 IR .....................................................................................................................................................116-118FLW 41 I .........................................................................................................................................................119-120Ignition transformers DEZ ..........................................................................................................................121-123VisionBox ............................................................................................................................................................124
65 … 12664 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Setting the Profibus addressIf you want to connect the automatic gas burner control system to the bus,avalidProfibusaddressmustbeenteredinparameterP11.Thedisplay shows OFF during param-etersettingifyouhavenotsetanyaddress.Pressthekeys-and+toswitch to the change mode. Now set the desired address in the range from1to126.If you want to change the address lateron,itispossibleduringopera-tion.Important:Anymodificationsare applied after a restart or an extended unlocking of the automatic gas burner control system.
AbusconnectionisnotrequiredforoperatingtheMPA.Ifabusisnotconnected,theMPAcanonlyreceiveaheatrequestviathehardwareinput"Temperature controller".Ifthereisabusconnection,whichcanberecognisedbyaflashingdigitonthedisplay,theheatrequestisgivenbymeansofbit0andbit6inAB0.Ifthesystemisagainsepa-ratedfromthebus,itautomaticallychanges to reading the hardware input "Temperature controller" after one minute.
Duringoperationanderrormes-sages,thecurrentbusaddressmaybeseenbypressingthe←key.
Bus terminationAterminatorisrequiredonthefirstandlastdeviceonthebus.
The shielding of the bus cable should be placed onto PEtoavoidelectromagneticradia-tion.
Pinassignment(M12-5B-coded)
Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not usedThread Shielding(earthconnection)recom-
mended
Pin Socket
1
2
3
4
3
1
2 4
5 5
67 … 12666 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Extension module MPA 41xx EM 2/4 Profibus DP interface,Modbus RTU / ASCII and shut-ter activation for flame detector device suitable for continuous operation
UniversalextensionmoduleforintegratingtheMPA41xxinfieldbussystemswithupto32slaves.
Integratedfunctions:-ProfibusDPinterface-ModbusRTU/ASCII-Activationforshuttermodule UV4x/Shutter
The bus protocol can be selected by meansofDIPswitch.Viathebus,commandscanbetrans-mittedtotheMPAandstatusinforma-tion can be queried.Inaddition,anoutputforactivatingthe shutter module to continuously operatetheUV4xprobesisinte-grated.
BUS protocol presettings
The4-pinDIPswitchisusedtoselectthebusprotocolandtoactivatetherespectivelinetermination.The bus protocol must be selected onlywithdeadvoltage.Modificationsare impossible during operation.
Bus protocol selection
DIP switch No. 4:
OFFposition=ProfibusONposition=Modbus
ON 1 2 3 4
Bus termination
IftheterminationisactivatedviatheDIPswitch,externalterminationresistors must not be plugged into the output connectors.
Ifaterminationisactivated,thetermi-nationofthealternativebusprotocolhastobedeactivatedinanycase.Modbus termination
DIP switch No. 1:
ONposition=Modbusterminationresistor120Ohm
Profibus termination
DIP switches No. 2 and 3:
ONposition=Profibusterminationresistor220Ohm
Setting the bus address
ThebusaddressisenteredintheP11parameter(displayindication"n").OFF is displayed if no address has been entered. Anaddressbetween1and99(upto126viaVisionBox)canbeenteredintheparametermode.Anymodi-ficationswilltakeeffectonlyafterarestart or an extended unlocking.
Duringoperationanderrormessag-es,thecurrentbusaddressmaybeseenbypressingthe←key.
Bus interruption
ModbusThe bus module requires at least one queryperminute.Ifthereisnoquery:
-safetyswitch-offifV2isactivatedviathebus
or-afteranotherminute,switchoverto
the hardware input "heat request" is done
ProfibusIf the cyclic data stream is interrupt-ed,afteraProfibusWatchdogperioddefinedbythemaster(e.g.2.5s):-safetyswitch-offifV2isactivatedviathebus
or-afteranotherminute,switchoverto
the hardware input "heat request"
Profibus data
The amount of the input and output dataisdefinedbythemodulesintheenclosedGSDfileforProfibus.
Profibus output data master to MPA
Theoutputdatahave8bits,seetable
Commandcontentsofassignedbits:
Bit 0(heatrequest)setto1bymas-ter=heatrequest.
Bit 1(highpower)setto1bymaster=V2isopenedinthestates18(opera-tion)and19(pause4)(parameter38issettovalue2).
Bit 2(remoteunlocking)setto1bymaster(atleast0.5smax.5s)=MPAisunlocked.
Bit 6(deactivateheatrequest)setto1bymaster=thebit0signal"heatrequest"isignored,theautomaticgas burner control system does not receiveaheatrequestviathebus.Theheatrequestisonlypossibleviathe hardware input.
Eight modules are integrated in the enclosedGSDfile.Fourofthem,amoduleforBasic,StandardandExtended,donotcontainanyoutputbytesbutonlyinputbytes(informa-tionaboutMPA).Thereforetheycan-notgiveanycommandstoMPA.
Bit Output byte AB00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia
bus)7 Reserve(pleaseset0)
67 … 12666 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Profibus input data MPA to master
Input data is information about the stateoftheMPA.Theinputdatacon-tainadifferentnumberofbytes,de-pending on the data transfer module used. The lower bytes are always the same,i.e.BasictransferisincludedinStandardtransfer,Standardtransferin Extended transfer.
Basic transfer 2 bytes EB0andEB1
Standardtransfer4bytesEB0toEB3
Extendedtransfer12bytesEB0toEB11
SpecialExtended-Transfer20bytesEB0bisEB19
ThebytesEB0andEB1containbitinformation.Ifthebitissetto1,theconditionisincluded in the description of the bits.Somebitsareactiveduringthefault(markedwith"X"),othersare0.
69 … 12668 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Basic transfer areaMPA 41xxBit Input byte EB0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X
5 Input for temperature controller
Signalofthehardwareinput"Temperaturecontroller" X
6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X
Bit Input byte EB1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 0
4 Temperature control-ler(hardware+bus)
Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
5 not used 0
6 not used 07 Fault There is a fault in the automatic gas burner control system X
69 … 12668 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Standard transfer areaMPA 41xxBit Input byte EB2 Description During fault
0-7 Statenumberorerrorcode
Current state number or error code if there is a fault X
Bit Input byte EB3 Description During fault0-7 Flame quality Qualityoftheflameoverionisationinput 0
Bit Input byte EB5 Description During fault
0-7 ResettableRuntimemeter
Byte1ofthe32-bitruntimemeter(Units)
X
Bit Input byte EB6 Description During fault
0-7 ResettableRuntimemeter
Byte2ofthe32-bitruntimemeter(Units)
X
Bit Input byte EB7 Description During fault
0-7 ResettableRuntimemeter
Highbyte(byte3)ofthe32-bitruntimemeter(Units)
X
Bit Input byte EB8 Description During fault
0-7 ResettableStartcounter
Lowbyte(byte0)ofthe32-bitstartcounter X
Bit Input byte EB9 Description During fault
0-7 ResettableStartcounter
Byte1ofthe32-bitstartcounter X
Bit Input byte EB10 Description During fault
0-7 ResettableStartcounter
Byte2ofthe32-bitstartcounter X
Bit Input byte EB11 Description During fault
0-7 ResettableStartcounter
Highbyte(byte3)ofthe32-bitstartcounter X
Extended transfer areaMPA 41xxBit Input byte EB4 Description During fault
0-7 ResettableRuntimemeter
Lowbyte(byte0)ofthe32-bitruntimemeter(Units)
X
71 … 12670 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Input byte EB13 Description During fault
0-7Resettable
SwitchingcyclescounterV2
Byte1des32–bitswitchingcyclescounterV2(Unit:s)
X
Bit Input byte EB14 Description During fault
0-7Resettable
SwitchingcyclescounterV2
Byte2des32–bitswitchingcyclescounterV2(Unit:s)
X
Bit Input byte EB15 Description During fault
0-7Resettable
SwitchingcyclescounterV2
Highbyte(Byte3)ofthe32–bitswitchingcyclescounterV2(Unit:s)
X
Bit Input byte EB16 Description During fault
0-7 ResettableRuntimemeterV2
Lowbyte(Byte0)ofthe32–bitruntimemeterV2(ins) X
Bit Input byte EB17 Description During fault
0-7 ResettableRuntimemeterV2
Byte1ofthe32–bitruntimemeterV2(ins) X
Bit Input byte EB18 Description During fault
0-7 ResettableRuntimemeterV2
Byte2ofthe32–bitruntimemeterV2(ins) X
Bit Input byte EB19 Description During fault
0-7 ResettableRuntimemeterV2
Highbyte(Byte3)ofthe32–bitruntimemeterV2(ins) X
Special extended transfer areaMPA 41xxBit Input byte EB12 Description During fault
0-7Resettable
SwitchingcyclescounterV2
Lowbyte(Byte0)des32–bitswitchingcyclescounterV2(Unit:s)
X
71 … 12670 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Declaration of the Profibus interfaceMPA 41xxManufactureridentification IDOXOCF1(KarlDungsGmbH&Co.KG)ASCICtype VPC3+C
SyncandfreezemodeIs supported(Synccommand:FreezealloutputsoftheaddressedslavesFreezecommand:Freezeallinputsoftheaddressedslaves)
Cycle time
Maximumtimeuntilthereisaresponsetoarequesttelegram,dependingonthebustransferrate:9.6kBit/sto500kBit/s→15bittimes1500kBit/s→20bittimes3000kBit/s→35bittimes6000kBit/s→50bittimes12000kBit/s→95bittimes
Diagnosis
TheProfibusmodulecreatesanexternaldiagnosisifitdetectsaninternaler-ror.ThediagnosisinformationoftheDPslaveconsistsofstandarddiagnosisinformation(6bytes)andauser-specificdiagnosisinformationerrornumber(2bytes).Octet1:Bit0=Diagnosisstationdoesnotexist(setsmaster)Bit1=Diagnosisstationnotready:Theslaveisnotreadyfordataexchange.Bit2=Diag.cfg_Fault:ConfigurationdatadonotmatchBit3=Diag.ext_diag:SlavehasexternaldiagnosisdataBit4=Diag.notsupported:RequestedfunctionisnotsupportedinslaveBit5=Diag.invalid_slave_response(setsslavefixedto0)Bit6=Diag.prm_fault:Wrongparameters(IDnumber,etc.)Bit7=Diag.master_lock(setsmaster):Parametersofslavearesetbyan-other masterOctet2:Bit0=Diag.Prm_req:SlaverequiresnewparametersBit1=Diag.Stat_diag:Staticaldiagnosis(bytediag-bits)Bit2=fixedto1Bit3=Diag.WD_ON:ReactionmonitoringactiveBit4=Diag.freeze_mode:FreezecommandreceivedBit5=Sync_mode:SynccommandreceivedBit6=reservedBit7=Diag.deactivated(setsmaster)Octet3:Bit0-Bit6=reservedBit7=Diag.ext_overflowOctet4:Diagmaster_add:Masteraddressaftersettingparameters(FFwith-outparametersetting)Octet5:HighbyteIDnumberOctet6:LowbyteIDnumber
Parameter Only cyclical communication supportedAutomaticbaudratedetection is supported
73 … 12672 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Registration address 00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia
bus)7 Not used8 Not used9 Not used10 Not used11 Not used12 Not used13 Not used14 Not used15 Not used
Modbus dataModbus RTU or ASCII mode
The modbus protocol can be switched overtoASCIImode(seeprotocol)us-ingtheFunctionCode0x41.Thesettingispermanentlysavedintheslave.Standardvalue(upondelivery)ismod-busRTU.
Modbus output data master to MPA
Theoutputdatahave16bits,seetable
Command contents of assigned bits:
Bit 0(heatrequest)setto1bymaster=heatrequest.
Bit 1(highpower)setto1bymaster=V2isopenedinthestates18(opera-tion)and19(pause4)(parameter38issettovalue2).
Bit 2 (remoteunlocking) set to1bymaster(atleast0.5smax.5s)=MPAis unlocked.
Bit 6 (deactivateheatrequest)setto1bymaster= thebit 0 signal "heatrequest"isignored,theautomaticgasburnercontrolsystemdoesnotreceiveaheat request via thebus.Theheatrequestisonlypossibleviathehard-ware input.Use the followingFunctionCodes towritethesespecifications.05(0x05)WriteSingleCoil(Coil=bitatbitaddressx)06 (0x06)WriteSingleRegister (toregisteraddress)
16(0x10)WriteSingleRegister(fromregisteraddress)
IfitisnotwrittenonAB0,theMPAfunc-tionsviathehardwareinputs.
Modbus input data MPA to master
Input data is information about the state of theMPA.The inputdatacontainadifferentnumberofbytes,dependingon the used data transfer module. The lowerbytesarealwaysthesame,i.e.BasictransferisincludedinStandardtransfer,StandardtransferinExtendedtransfer. AnEBxcontains16bits.
Basic transfer 4 bytesEB0andEB1
Standardtransfer8bytesEB0toEB3
Extended transfer 24 bytesEB0toEB11
Special Extended transfer 42 bytesEB0toEB20
Special Extended-Transfer kurz 21Bytes EB21-EB31Fulluseofthe16Bitregister,contai-ningtheinformationofEB0-EB20
Use the followingFunctionCodes toread this information. 03(0x03)ReadHoldingRegisters01(0x01)ReadCoils.
73 … 12672 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Basic transfer area
Bit Registration address 0 Description During Fault
0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X5 Input for temp. controller Signalofthehardwareinput"Temperaturecontroller" X6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X
8...15 Not used Not used 0
Bit Registration address 1 Description During Fault
0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 04 Temperaturecontroller(hard-
ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
5 not used 06 not used 07 Fault There is a fault in the automatic gas burner control system X
8...15 Not used Not used 0
Bit Registration address 2 Description During Fault
0-7 StatenumberorError code
Currentstatenumber,orincaseoffault,theerrorcodeisincludedhere
X
8...15 Not used Not used 0
Standard transfer area
Bit Registration address 3 Description During Fault
0-7 Flame quality QualityofFlameSignal 08...15 Not used Not used 0
Standard transfer area
Extended transfer area
Bit Registration address 4 Description During Fault
0-7 resettable runtime meter Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X8...15 Not used Not used 0
75 … 12674 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Registration address 5 Description During Fault
0-7 resettable runtime meter Byte1ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0
Bit Registration address 6 Description During Fault
0-7 resettable runtime meter Byte2ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0
Bit Registration address 7 Description During Fault
0-7 ResettableRuntimemeter
Highbyte(byte3)ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0
Bit Registration address 8 Description During Fault
0-7 ResettableStartcounter
Lowbyte(byte0)ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Registration address 9 Description During Fault
0-7 ResettableStartcounter
Byte1ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Registration address 10 Description During Fault
0-7 ResettableStartcounter
Byte2ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Registration address 11 Description During Fault
0-7 ResettableStartcounter
Highbyte(byte3)ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Registration address 12 Description During Fault
0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0
Bit Registration address 13 Description During Fault
0-7 SwitchingcyclescounterV2 Byte1ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0
Bit Registration address 14 Description During Fault
0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0
75 … 12674 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Registration address 15 Description During Fault
0-7 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2 X8...15 Not used Not used 0
Bit Registration address 16 Description During Fault
0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0
Bit Registration address 17 Description During Fault
0-7 RuntimemeterV2 Byte1ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0
Bit Registration address 18 Description During Fault
0-7 RuntimemeterV2 Byte2ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0
Bit Registration address 19 Description During Fault
0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2(ins) X8...15 Not used Not used 0
Bit Registration address 20 Description During Fault
0-7 Additionalerrorinformation First additional error information byte X8...15 Not used Not used 0
Inthefollowing,theinformationislinkedtoallowthecompleteuseofthe16bitsregister.Query if the bus load is to be reduced.
Bit Registration address 21 Description During Fault
0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressure X5 Input for temperature control-
lerSignalofthehardwareinput"Temperaturecontroller" X
6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X8 Sparkgenerator Ignitionactive X9 Manual mode Manualmodeactive X10 Fan Fan relay on X11 not used 012 Temperaturecontroller(hard-
ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
13 not used 014 not used 015 Fault There is a fault in the automatic gas burner control system X
77 … 12676 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Registration address 22 Description During Fault
0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8-15 Flame quality Qualityoftheflameoverionisationinput 0
Bit Registration address 23 Description During Fault
0-7 ResettableRuntimemeter
Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X
8-15 ResettableRuntimemeter
Byte1ofthe32-bitruntimemeter(ins) 0
Bit Registration address 24 Description During Fault
0-7 ResettableRuntimemeter
Byte2ofthe32-bitruntimemeter(ins) X
8-15 ResettableRuntimemeter
Highbyte(Byte3)ofthe32–bitruntime meter (ins) X
Bit Registration address 25 Description During Fault
0-7 ResettableStartupcounter
Lowbyte(byte0)ofthe32-bitstart counter X
8-15 ResettableStartupcounter
Byte1ofthe32-bitstartcounter X
Bit Registration address 26 Description During Fault
0-7 ResettableStartupcounter
Byte2ofthe32-bitstartcounter X
8-15 ResettableStartupcounter
Highbyte(Byte3)ofthe32-bitstartcounter X
Bit Registration address 27 Description During Fault
0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitcyclecounterV2 X8-15 SwitchingcyclescounterV2 Byte1ofthe32-bitcyclecounterV2 X
Bit Registration address 28 Description During Fault
0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitcyclecounterV2 X8-15 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitcyclecounterV2 X
Bit Registration address 29 Description During Fault
0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimecounterV2 X8-15 RuntimemeterV2 Byte1ofthe32-bitruntimecounterV2 X
Bit Registration address 30 Description During Fault
0-7 RuntimemeterV2 Byte2ofthe32-bitcounteroperatinghoursV2 X8-15 RuntimemeterV2 Highbyte(byte3)ofthe32-bitcounteroperatinghoursV2 X
Bit Registration address 31 Description During Fault
0-7 Additionalerrorinformation First additional error information byte X8-15 Not used Not used 0
77 … 12676 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Line lengths
Designation Line length Electrical dataProfibusDP Max.1200m,seeBMAMPA41xx Galvanicallyisolated4kV
Modbus Max.1000m Galvanicallyisolated4kV
Supported baud rates
Profibus
ThefollowingtableisonlyvalidforlinetypeAtoEN50170
Transfer speed kBit/s
9,6 19,2 45,45 93,75 187,5 500 1500 3000 6000 12000
max. line length in m
1200 1200 1200 1200 1000 400 200 100 100 100
Modbus
9600bauds,19200bauds,19200baudsand57600bauds
The baud rate can be changed during operation by means of the Function-Code0x41andispermanentlysavedintheslave.Therelativeparitybitcanalsobedefined.None,EvenandOddaresupported.Defaultvalues(upondelivery)are19200baudsandEvenParity.
1.1 Pin assignment (M12–5 B-coded)MPA 411x MPA 4122
Pin no. Signal1 +5Vsupplyforbustermination2 Datalineminus(Aconductor)3 Earth4 Datalineplus(Bconductor)5 not used
Thread Shielding(earthconnection)recommended
Pin Socket
1
2
3
4
3
1
2 4
5 5
Shutter
VCC A B 2 1
Bus�IN/OUT
Bus termination
Aterminationresistorisrequiredonthefirstandthelastdeviceofthebusstructure.Alternativelytointernaltermination(above),anexternalbusterminationresistor can be connected instead of another bus cable.
The bus cable shielding is to be con-nectedtoPEtoavoidelectromag-netic radiation.
79 … 12678 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Flame detector device test for UV4x EM shutterTheEM2/4moduleincludesanacti-vationfortheUV4x/shutter.TheuseoftheUV4X/shutterallowstouseanUVflamedetectordeviceUV41(HE)andUV42suitableforcontinuous operation.The shutter signal can also be used for continuous operation of one or moreFLW41Iflamedetectordevice(s).
The control signal is independent from the use of the bus interface.
Connection:
Supply voltage:
24VDC
Current:
Max.200mA
Shutter frequency:
1shuttersignal/10minutes,thefrequencyisnotadjustable.
Parameter setting:
Theshuttersignalisturnedon/offbymeansoftheP21parameter(param-eter„h“inthedisplay).
+-24VDC
79 … 12678 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Extension module MPA 41xx EM 2/6
The multifunctional extension module EM2/6includesthefollowingfunc-tions:
-Relayoutputsasafunctionofstate-PWMoutputforspeedcontrolofDCfanswithpowerinputbyaPWMsignal
-Voltageoutput0..10V-Currentoutput4..20mA-Profibusinterface- Modbus interface-OutputforactivationoftheEM1/1
shutter module or the continuous operationfunctionoftheFLW41l.
FortheEM2/6MPA411x,art.no.260751theseparatelyavailablemountingbaseMPA411xWB,art.no.261374isrequired.
TheEM2/6forMPA412x,art.no.260903ismountedinthemetalhousing.
Attention
ThemountingoftheEM2/6modulesmustonlytakeplacebyDUNGSorbythirdpartiesauthorisedbyDungs.
Functions
Relay outputs as a function of state:
Asafunctionoftheprogramstate,the relay contacts are closed or opened.Theexternallyappliedvolt-age is switched to random consum-ers.
Application-Signallingofoperationalstates-Activationofanalogueactuators
Byusinganalogueactuators,twoposition messages can be reported totheEM2/6.
PWM signal for activation, for ex-ample, of speed-controlled fans.
ThePWMsignalcanbemodulatedduring the "operation" state by apply-ingamainsvoltagesignal.The speed is controlled with no speed feedback.
Analogue output for current / voltage
Thecurrentsignal(4-20mA)orthevoltagesignal(0-10VAC)canbemodulatedbyapplyingamainsvolt-age signal.
Fieldbus communication
ProfibusDPandmodbusinterfaceareintegratedintotheEM2/6exten-sion module.Forthedescription,seepage70ff.EM2/4modul
Flame safeguard, shutter activa-tion for continuous operation.
TheactivationoftheEM1/1shuttermodule,whichisnecessaryforthecontinuousoperationofDUNGSUV4xandFLW41Iflamesafeguards,isintegratedintotheEM2/6(forthedescription,seepage82).
81 … 12680 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Erro
rPau
se 1 W
aitin
g for h
eatin
g reques
t
Stat
ic sta
te co
ntrol L
DW
Safe
ty ch
ain ch
eck
Wat
chdog lo
adin
g phas
e
Wait
ing fo
r air
press
ure
Exte
rnal
light c
ontrol
Pre-v
entin
g
Pause
2 Pre-ig
nition
First
safe
ty ti
me (
SZA) -
Igniti
on
First
safe
ty ti
me (
SZA) -
Flam
e det
ectio
n
Stab
ilisat
ion fl
ame A
Pause
3 Seco
nd safe
ty ti
me (
SZB)
Seco
nd safe
ty ti
me (
SZB) -
Flam
e det
ectio
n *10
Stab
ilisat
ion fl
ame B
*10
Operat
ion
Pause
4
Post-ve
nting
After-b
urnin
g tim
e *7
Resta
rt pro
tecti
on
Pause
5 (e
nd of p
aram
eter
isatio
n sequen
ce)
Wait
ing fo
r gas
pre
ssure
Safe
ty ch
ain o
pen
820
Stat
e nu
mb
er0
12
34
56
79
1011
1213
1415
1617
1819
2122
2324
25D
isp
lay
Fxx
H1
01
11
11
H2
11
12
H3
22
33
H4
44
H5
D2
D1
P248
P248
P248
*101
*102
*101
"H
igh
Fire
" in
put
*10
3
"Lo
w F
ire"
inp
ut *
103
Inpu
tO
NO
ffEi
ther
"Off
" or
"C
oolin
g m
ode"
*104
"O
ther
" po
sitio
n
Ope
n or
"Oth
er"
posi
tion*
107
Ope
n or
"Oth
er"
posi
tion
*107
"V
entin
g"
or "
Oth
er"
posi
tion
*106
"Pos
t-ve
ntin
g sp
eed"
P243
"Ign
ition
pos
ition
spe
ed"
P241
"Sta
bilis
atio
n sp
eed"
P242
8 1 P30
0..1
h
"Ig
nitio
n" p
ositi
on
20 4 P51
Con
trol
m
ode
P50
*7
0..1
h
"Off
" or
"C
oolin
g m
ode"
*104
Tim
es
Spee
d(P
WM
)"P
re-v
entin
g sp
eed"
P240
"Sw
itch
mod
ulat
ion"
out
put
"
Ven
ting"
pos
ition
"Off
" or
"C
oolin
g m
ode"
*104
*105
"Off
"
Ope
n or
"O
ther
"po
sitio
n *1
07O
pen
*7) T
he a
fter
-bur
ning
tim
e st
arts
alr
eady
in t
he "
Post
-ven
ting"
sta
te. W
hen
the
post
-ven
ting
beco
mes
larg
er o
r eq
ual t
o th
e af
ter-
burn
ing
time,
the
"A
fter
-bur
ning
tim
e" w
ill b
e sk
ippe
d.
*101
) Mon
itori
ng o
f th
e "H
igh
Fire
" in
put
will
not
be
star
ted
until
the
tim
e de
fined
in P
248
has
expi
red.
. *1
02) T
he ig
nitio
n sp
eed
is a
lrea
dy s
et b
efor
e th
e en
d of
the
pre
-ven
ting
time,
thi
s tim
e be
ing
defin
ed in
P24
8. S
tart
ing
from
thi
s m
omen
t, th
e "
Hig
h Fi
re"
inpu
t w
ill n
o lo
nger
be
mon
itore
d.
*103
) Mon
itori
ng o
f th
e "H
igh
Fire
" an
d "L
ow F
ire"
inpu
ts c
an b
e ac
tivat
ed o
r de
activ
ated
via
par
amet
er P
249
. *1
04) P
249,
bits
2+
3 ca
n be
use
d to
def
ine
whe
ther
the
spe
ed is
"O
ffs"
or
whe
ther
the
fan
is w
orki
ng in
coo
ling
mod
e.
*105
) The
sta
rt v
alue
of
the
spee
d, f
ollo
win
g a
soft
war
e re
star
t, is
est
ablis
hed
via
P244
if t
he c
oolin
g m
ode
is a
ctiv
e.
*106
) P24
9 is
use
d to
est
ablis
h w
heth
er t
he "
Ven
ting"
pos
ition
is a
ctiv
ated
als
o du
ring
pos
t-ve
ntin
g.
*107
) P24
9 is
use
d to
est
ablis
h w
heth
er t
he "
Switc
h m
odul
atio
n" is
Ope
n or
con
nect
ed t
o th
e "
Oth
er"
inpu
t.
SCH
M /
TST,
09.
10.2
012
ce)
Flow
cha
rt "
EM 2
/6"
81 … 12680 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4Outputs*Designation Safety-
relatedType of output Line length Electrical data
Fanactivation PWM4kHz,wit-hout detection of speed feedback
Max.10m 24VDC,safetyextralowvoltage(3lines:GND,+24VDC,PWMcontrol signal
Frequency con-verteractivation
0...10V4...20mA
Max.10m 10VDC,safetyextralowvoltage
Activationofshutter
Switchingcontact
Max.100m 24VDC,safetyextralowvoltage
Technical data
Inputs*Designation Type of input Line length Electrical data"HighFire"feedback Switchingcontact Max.100m 115/230VAC"LowFire"feedback Switchingcontact Max.100m 115/230VACPower+ Switchingcontact Max.100m 115/230VACPower- Switchingcontact Max.100m 115/230VAC
Other functions*Designation Type of input Line length Electrical dataSwitchforoption:0...10V,4…20mAorPWMoutput
Switch Plastichousing:Canonlybeswitchedoverwiththeextensionmodule dismounted.Metalhousing:No dismounting requiredAttention:Switchoveronlyin de-energised state
MODBUSinterface MODBUSbasedonRS485 Max.1000m RS485galvanicallyisolated4kVDIPswitchterminatingresistorsMODBUS
DIPswitch Foractivationordeactivation ofRS485terminatingresistors(MODBUS)
ProfibusDP Max.1200m Galvanicallyisolated4kV
* The connection cables used must be suitable for an ambient temperature of at least 75 °C (167 °F)
83 … 12682 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Connector 1 (analogue On/Off 115 VAC / 230 VAC)
1:COM2:"HighFire"switchingposition3:"LowFire"switchingposition4:Automaticswitchingposition
Connector 2 (115 VAC / 230 VAC inputs)
6:N7:"LowFire"feedback8:"HighFire"feedback9:Power-10:Power+
Connector 3 (analogue out)
PWMoutput(connectorbottom)12:DGND13:PWM14:VCCout(10.5...24VDC)
Analogueoutput0...10V(switchcentre)12:DGND13:Analogueoutput0…10V14:10Vout
Analogueoutput4...20mA(switchtop)12:DGND13:Analogueoutput4...20mA14:VCCout(10.5...24VDC)
Connector 4 (bus und shutter):
16:GND/shutter-17:VCC5V(forboosterminimisation)18:B(red)19:A(green)20:GNDshutter+
Pin assignment
1 2 3
Switch position analogue output 4...20 mA switch top0...10 V switch centrePWM switch bottom
4
1 2 3 6 7 8 9 10 12 13 14 16 17 18 19 20
GN
D
A(grün/green)
VCC
N High Fire
Low Fire
4
260806
Comm
on
Pro�bus/Modbus
83 … 12682 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Parameters
All"speed"valuesorthelikerefertothePWMcontrolsignalandhavenosignificancefortheactualspeedofthe fan.
ThevaluesP240toP244canbechangedafterentryofapassword,dependingontheaccesslevel.Readingaccessispossibleforallparameters,independentlyoftheac-cesslevel.ParametersP245toP249canbechanged without password.
ParameterscanbechangedviatheVisionBoxorthedisplayoftheMPA41x2.
Changed parameters are applied to thefancontrolafternolaterthan10s.
Overview of the fan control parametersVisionBox No. Display No. Name Meaning240 Pr0 RESERVIERT_OEM_0 Pre-venting241 Pr1 RESERVIERT_OEM_1 Ignition position242 Pr2 RESERVIERT_OEM_2 Stabilisation243 Pr3 RESERVIERT_OEM_3 Post-venting244 Pr4 RESERVIERT_OEM_4 Startvalue245 Pr5 RESERVIERT_BETREIBER_0 Min. speed246 Pr6 RESERVIERT_BETREIBER_0 Max. speed247 Pr7 RESERVIERT_BETREIBER_2 Increment248 Pr8 RESERVIERT_BETREIBER_3 Transitiontime(whenstartingpre-and
post-ventingandbeforetheendofpre-venting)
249 Pr9 RESERVIERT_BETREIBER_4 Bit functions (seedescriptionP249)
85 … 12684 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParameterParameter description
Parameter Designation Description Setting / Examples
P240 Pre-venting / Activa-tion of the extension module
Theparametervalueisusedforstates5-8(starttopre-venting)oftheMPA41xx,itbeingpossibleforstate8(pre-venting)tobedivided,seeP248.RefersdirectlytothePWMcontrolsignal.
Settingfrom0.01%to100.00%*1Resolution:0.01%If the parameter has been set to >0,anextensionmodulemusthavebeenconnectedtothemainboard.Thispreventsoperationwithout an extension module by generatinganerror(0x18,seechapter10Erroroverview).Setting0:IftheEMisconnectedtotheMPA,anerrorwillbegener-ated(0x18,Erroroverview).
P241 Ignition position Theparametervalueisusedforstates8-14(ignitionandflamedetec-tion)oftheMPA41xx,itbeingpos-sibleforstate8(pre-venting)tobedivided,seeP248.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%*1Resolution:0,01%
P242 Stabilisation Theparametervalueisusedforstates15-17(secondsafetytime(SZB)andstabilisationB)oftheMPA41xx.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%*1Resolution:0.01%
P243 Post-venting Theparametervalueisusedforstate20(post-venting)oftheMPA41xx.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%*1Resolution:0.01%
P244 Start value IftheMPAisstartedbyMainsOn,thisvaluewillbeusedasstartvalue.IftheMPAchangestooneofstates21to25(after-burntimetosafetychainopen),andthecurrentspeedis0,itisstartedagainfromthestartvalue.IftheMPAchangestostate1or2(e.g.,duetocancellingtheheatrequest),andthecurrentspeedis0,itisstartedagainfromthestartvalue.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%*1Resolution:0.01%
P245 Minimum speed Minimumspeed,controlwillnotoutputasmallervalue.Allparam-etervaluesofthefancontrolmustbeaboveoratthislimit.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%Resolution:0.01%
P246 Maximum speed Maximumspeed,controlwillnotoutputalargervalue.Allparametervaluesofthefancontrolmustbebelow or at this limit.RefersdirectlytothePWMcontrolsignal.
Adjustablefrom0.00%to100.00%Resolution:0.01%
85 … 12684 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
ParameterParameter description
Parameter Designation Description Setting / Examples
P247 Increment of speed change
Indicatesthevaluebywhichthedesired speed of the fan is in-cremented or decremented. The calculationiscarriedout16timespersecond,i.e.,thevalueoftheparameter is added to or subtract-edfromthecurrentvalueinthe1/16scycle.Theincrementinthetables is used for certain positions oftheinputs,seeD+andD-.
Adjustablefrom0.01%to100.00%Resolution:0,01%Calculation of the time based on the incrementTime[in1/16]=(Max[in%]-Min[in%])/Increment[in%]
Calculationoftheincrement(con-tentsP247)P247[in0.01%]=((Max[in%]-Min[in%])/(Time[ins]*16))*100
Examples:IncrementP247=40(=0.4%per1/16s)requires12.5sofminspeed=20%tomaxspeed100%.Longesttimefrom0to100%atincrementP247=1is625s.
P248 Transition time to ignition speed
Theparametervalueisusedforstate8(pre-venting)oftheMPA41xx.Indicatesatwhichtimethefanismovedtotheignitionposition.Thevaluecorrespondsto the time before the end of pre-venting(remainingpre-ventingstatetime).NOTE:MustnotbegreaterthantheP30pre-ventingtime,otherwisefaultconfigurationwith restart will be carried out.State8(pre-venting)isdividedinto3partsP248+x+P248=P30(xmustbegreaterthan1ifmonitoringisactive).AfterthefirstHighFiretime(P248):State20(post-venting)P248+x=P51(xmustbegreaterthan1ifmonitoringisactive).ThecontrolofparametersP248,P30andP50takesplaceduringthewatchdogloadingphase.Dur-ingchangesinoperation(param-eternotmonitored),Low/HighFiremonitoringcanbedisabledifP248≤P50.
Adjustablefrom0to1h.Resolution:1/16s
87 … 12686 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
P249 bit functionsTheparameterincludesthePWM/analogueswitchover,theidlestatecontrol of both air pressure switches LDWLow/LDWHighandarampfunction(desiredvaluedelay).
The output of the correct signal depends on the switch position (centre=voltageoutputsignal),(bottom=PWMoutputsignal),whichmust be identical to the setting of this parameter.
The parameter is divided into 16 bits:Bit 0Setting0:PWMoutput.SetslideswitchtoPWMoutput(bot-tomposition).
Setting1:Analogueoutput.Setslideswitchtovoltage(centreposition)orcurrent(topposition).Allparametervaluesin%arenowconvertedtotheoutputoftheana-loguevalue.
Example:Apost-ventingparameterof6000gives6Vattheanalogueoutput,etc.
Bit 1Setting0:Voltageoutputactive0..10VSetting1:Currentoutputactive4..20mA
Bits 2+3:Setting0:DuringstandbyandfaultPWM=0Setting1:DuringstandbyandfaultPWM=power+/-Setting2:DuringstandbyandfaultPWM=power+/-Setting3:Errorconfiguration
Bit 4Setting0:Allrelayoutputsopen(WO)Setting1:Relay1(automaticclosed)
Bit 5Setting1:HighFireinputcontroldur-ingpre-ventingtime
Bit 6Setting1:LowFireinputcontroldur-ing ignition and stabilisation time
Bit 7 HighFireinputcontrolduringpost-ventingtime
Bit 8Setting1:HighFirerelay3closedBit 9Bit 10Bit 11Bit 12Bit 13
Theramp(desiredvaluedelay)oftheoutputsignalisactiveduringeachchangeinspeed.TheMoreHeat/LessHeatinputshavepriorityiftheyareactive.
Bit 14Reserved:Setting0
Bit 15Reserved:Setting0
} 5-bitvalue
87 … 12686 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
45-bit value Duration in s
Example: if change is from 0 % to 100 %0 Jump1 3,1252 6,2503 9,3754 12,55 15,6256 18,757 21,8758 259 28,12510 31,2511 34,37512 37,513 40,62514 43,7515 46,87516 5017 53,12518 56,2519 59,37520 62,521 65,62522 68,7523 71,87524 7525 78,12526 81,2527 84,37528 87,529 90,62530 93,7531 96,875
Formulaforrampcalculation:Duration=|(olddesiredvalue-newdesiredvalue)|*5-bitvalue*1s/16
Example:
Changefrom0to100%,5-bitvalue31100%/2%*31/16s=97s
Calculation as ramp
89 … 12688 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Fieldbus communicationProfibus DP
ForProfibussetting,termination,technicaldata,seepage70ff.EM2/4modul
Profibus input data MPA to master
Input data is information about the stateoftheMPA.Theinputdatacon-tainadifferentnumberofbytes,de-pending on the data transfer module used. The lower bytes are always the same,i.e.BasictransferisincludedinStandardtransfer,Standardtransferin Extended transfer.
Basic transfer 2 bytes EB0andEB1
Standardtransfer7bytesEB0toEB6
Extendedtransfer15bytesEB0toEB14
SpecialExtendedtransfer25bytesEB0toEB24
ThebytesEB0andEB1containbitinformation.Ifthebitissetto1,theconditionisincluded in the description of the bits.Somebitsareactiveduringthefault(markedwith"X"),othersare0.
89 … 12688 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Basic transfer areaMPA 41xxBit Input byte EB0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X
5 Input for temperature controller
Signalofthehardwareinput"Temperaturecontroller" X
6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X
Bit Input byte EB4 Description During fault0 MoreHeat HWinputstate X1 LessHeat HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X
4Warningmessage:MoreandLessHeat
simultaneously
TheinputsforHeat+andHeat-aresimultaneouslyactive X
5 not used 0
6 not used 07 not used 0
Standard transfer areaBit Input byte EB2 Description During fault
0-7 Statenumberorerrorcode
Current state number or error code if there is a fault X
Bit Input byte EB3 Description During fault0-7 Flame quality Qualityoftheflameviaionisationinput 0
Bit Input byte EB1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 0
4 Temperature control-ler(HW+BUS)
Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
5 not used 0
6 not used 07 Fault There is a fault in the automatic gas burner control system X
91 … 12690 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Input byte EB8 Description During fault
0-7 Resettableruntime meter
Byte1ofthe32-bitruntimemeter(Unit:s)
X
Bit Input byte EB9 Description During fault
0-7 Resettableruntime meter
Byte2ofthe32-bitruntimemeter(Unit:s)
X
Bit Input byte EB10 Description During fault
0-7 Resettableruntime meter
Highbyte(byte3)ofthe32-bitruntimemeter(Unit:s)
X
Bit Input byte EB11 Description During fault
0-7 Resettablestart counter
Lowbyte(byte0)ofthe32-bitstartcounter X
Bit Input byte EB12 Description During fault
0-7 Resettablestart counter
Byte1ofthe32-bitstartcounter X
Bit Input byte EB13 Description During fault
0-7 Resettablestart counter
Byte2ofthe32-bitstartcounter X
Bit Input byte EB14 Description During fault
0-7 Resettablestart counter
Highbyte(byte3)ofthe32-bitstartcounter X
Extended transfer areaMPA 41xxBit Input byte EB7 Description During fault
0-7 Resettableruntime meter
Lowbyte(byte0)ofthe32-bitruntimemeter(Unit:s)
X
Bit Input byte EB5 Description During fault0 Relaymatrixoutput
(2-bit)00=Off
01=Relay110=Relay211=Relay3
X
1
X
2Warning:Low/HighFire simultaneously
on
X
3 not used 04 not used 05 not used 0
6 not used 07 not used 0
Bit Input byte EB6 Description During faultDegreeofmodulation
in%
91 … 12690 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Input byte EB16 Description During fault
0-7 SwitchingcyclescounterV2
Byte1ofthe32-bitswitchingcyclescounterV2 X
Bit Input byte EB17 Description During fault
0-7 SwitchingcyclescounterV2
Byte2ofthe32-bitswitchingcyclescounterV2 X
Bit Input byte EB18 Description During fault
0-7 SwitchingcyclescounterV2
Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X
Bit Input byte EB19 Description During fault
0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(Unit:s)
X
Bit Input byte EB20 Description During fault
0-7 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(Unit:s)
X
Bit Input byte EB21 Description During fault
0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(Unit:s)
X
Bit Input byte EB22 Description During fault
0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(Unit:s)
X
Special Extended transfer areaMPA 41xxBit Input byte EB15 Description During fault
0-7 SwitchingcyclescounterV2
Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X
Bit Input byte EB23 Description During fault0-7 Erroradditionalinfo1 First additional error info byte X
Bit Input byte EB24 Description During fault0-7 Error additional info 4 Fourth additional error info byte X
93 … 12692 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Byte0Bit OutputbyteAB00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestviabus)7 Reserve(pleasesetto0)
Output data of the master to MPA
Byte10 ControlbitbusinputsActivateMore/LessHeat1 MoreHeat2 LessHeat3 Not used4 Not used5 Not used6 Not used7 Not used
Byte 20 Not used1 Not used2 Not used3 Not used4 Not used5 Not used6 Not used7 Not used
Transfer areas:A:nobytes
B:1byte
C:3bytes
93 … 12692 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
FieldbusModbusForModbussetting,termination,technicaldata,seepage70ff.EM2/4modul
Modbus input dataUsethefollowingFunctionCodestoreadthisinformation:03(0x03)ReadHoldingRegisters01(0x01)ReadCoils
95 … 12694 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Basic transfer area
Bit Register address 0 Description During fault0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X5 Input for temperature control-
lerSignalofthehardwareinput"Temperaturecontroller" X
6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X
8...15 Not used Not used 0Bit Register address 1 Description During fault0 Sparkgenerator Ignitionactive X1 Manual mode Manualmodeactive X2 Fan Fan relay on X3 not used 04 Temperaturecontroller(hard-
ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
5 not used 06 not used 07 Fault There is a fault in the automatic gas burner control system X
8...15 Not used Not used 0
Bit Register address 2 Description During fault0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8...15 Not used Not used 0
Standard transfer area
Bit Register address 3 Description During fault0-7 Flame quality 08...15 Not used Not used 0
Standard transfer area
Bit Register address 4 Description During fault0 MoreHeat HWinputstate X1 LessHeat HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X4 Warningmessage:MoreHeat/
LessHeatsimultaneouslyonX
5 Not used 06 Not used 07 Not used 0
8...15 Not used 0
95 … 12694 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Extended transfer area
Bit Registration address 7 Description During fault
0-7 Resettableruntimemeter Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X8...15 Not used Not used 0
Bit Register address 5 Description During fault
0 0..1or8..9:outputstateswitchmodulation(2-bit):0=Off,01=Relay1,10=Relay2,11=Relay3
X1 X
2 Warningmessage:LowFire/HighFiresimultaneouslyon
X
3 Not used 04 Not used 05 Not used 06 Not used 07 Not used 0
8...15 Not used 0
Bit Register address 6 Description During fault
0-15 Degreeofmodulationin% X
Bit Register address 8 Description During fault
0-7 Resettableruntimemeter Byte1ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0Bit Register address 9 Description During
fault0-7 Resettableruntimemeter Byte2ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0Bit Register address 10 Description During
fault0-7 Resettable
runtime meterHighbyte(byte3)ofthe32-bitruntimemeter(ins) X
8...15 Not used Not used 0
97 … 12696 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 11 Description During fault
0-7 Resettablestart counter
Lowbyte(byte0)ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Register address 12 Description During fault
0-7 Resettablestart counter
Byte1ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Register address 13 Description During fault
0-7 Resettablestart counter
Byte2ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Register address 14 Description During fault
0-7 Resettablestart counter
Highbyte(byte3)ofthe32-bitstartcounter X
8...15 Not used Not used 0
Bit Register address 15 Description During fault
0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X8...15 Not used Not used 0
Bit Register address 16 Description During fault
0-7 SwitchingcyclescounterV2 Byte1ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0
Bit Register address 17 Description During fault
0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0
Bit Register address 18 Description During fault
0-7 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X8...15 Not used Not used 0
Extended transfer area
97 … 12696 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 19 Description During fault
0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0
Bit Register address 20 Description During fault
0-7 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0
Bit Register address 21 Description During fault
0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0
Bit Register address 22 Description During fault
0-7 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(ins) X8...15 Not used Not used 0
Bit Register address 23 Description During fault
0-7 Additionalerrorinfo1 First additional error information byte X8...15 Not used Not used 0
Inthefollowing,theinformationislinkedtoallowcompleteuseofthe16-bitregister.Query if the bus load is to be reduced.
Bit Register address 25 Description During fault
0 Flame1 Thereisasignalforflame1 01 Flame 2 Thereisasignalforflame2 X2 Flame2NC/GDW Thereisasignalforflame2NCorGDW X3 Flame detection Theresultingflamesignalhasbeendetected X4 LDW Sufficientairpressureavailable X5 Input for temperature control-
lerSignalofthehardwareinput"Temperaturecontroller" X
6 Valve1 ThegasvalveV1isopen X7 Valve2 ThegasvalveV2isopen X8 Sparkgenerator Ignitionactive X9 Manual mode Manualmodeactive X10 Fan Fan relay on X11 not used 012 Temperaturecontroller(hard-
ware+bus)Evaluationbetweentemperaturecontrollerhardwareinputandbusspecification
X
13 not used 014 not used 015 Fault There is a fault in the automatic gas burner control system X
Bit Register address 24 Description During fault
0-7 Additionalerrorinfo4 Fourth additional error info byte X8...15 Not used Not used 0
99 … 12698 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 26 Description During fault
0-7 Statenumberorerrorcode CurrentstatenumberORerrorcodeifthereisafault X8-15 Flame quality Qualityoftheflameviaionisationinput 0
Bit Register address 27 Description During fault
0 Heatplus HWinputstate X1 Heatminus HWinputstate X2 HighFire HWinputstate X3 LowFire HWinputstate X4 Warningmessage:Powerplus
and minus simultaneously onX
5 Not used X6 Not used X7 Not used X
8..9 Output state switch modulati-on(2-bit):0=Off,01=Relay1,10=Relay2,11=Relay3
X
10 Warningmessage:LowandHighFiresimultaneouslyon
X
11 Not used 012 Not used 013 Not used 014 Not used 015 Not used 0
Bit Register address 28 Description During fault
0-15 Degreeofmodulationin% X
99 … 12698 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 29 Description During fault
0-7 Resettableruntime meter
Lowbyte(byte0)ofthe32-bitruntimemeter(ins) X
8-15 Resettableruntime meter
Byte1ofthe32-bitruntimemeter(ins) X
Bit Register address 30 Description During fault
0-7 Resettableruntime meter
Byte2ofthe32-bitruntimemeter(ins) X
8-15 Resettableruntime meter
Highbyte(byte3)ofthe32-bitruntimemeter(ins) X
Bit Register address 31 Description During fault
0-7 Resettablestart counter
Lowbyte(byte0)ofthe32-bitstartcounter X
8-15 Resettablestart counter
Byte1ofthe32-bitstartcounter X
Bit Register address 32 Description During fault
0-7 Resettablestart counter
Byte2ofthe32-bitstartcounter X
8-15 Resettablestart counter
Byte3ofthe32-bitstartcounter X
Bit Register address 33 Description During fault
0-7 SwitchingcyclescounterV2 Lowbyte(byte0)ofthe32-bitswitchingcyclecounterV2 X8-15 SwitchingcyclescounterV2 Byte1ofthe32-bitswitchingcyclescounterV2 X
Bit Register address 34 Description During fault
0-7 SwitchingcyclescounterV2 Byte2ofthe32-bitswitchingcyclescounterV2 X8-15 SwitchingcyclescounterV2 Highbyte(byte3)ofthe32-bitswitchingcyclescounterV2 X
Bit Register address 35 Description During fault
0-7 RuntimemeterV2 Lowbyte(byte0)ofthe32-bitruntimemeterV2(ins) X8-15 RuntimemeterV2 Byte1ofthe32-bitruntimemeterV2(ins) X
Bit Register address 36 Description During fault
0-7 RuntimemeterV2 Byte2ofthe32-bitruntimemeterV2(ins) X8-15 RuntimemeterV2 Highbyte(byte3)ofthe32-bitruntimemeterV2(ins) X
Bit Register address 37 Description During fault
0-7 Additionalerrorinfo1 First additional error info byte X8-15 Additionalerrorinfo4 Fourth additional error info byte X
101 … 126100 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 38 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberSWP1 X8-15 Highbyte:u24articlenumberSWP1 X
Bit Register address 39 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberSWP1
X
8-15 Highbyte:indexarticlenumberSWP1 XBit Register address 40 Description During
fault0-7 Lowbyte:dayproductionMPA X8-15 Highbyte:monthproductionMPA X
Bit Register address 41 Description During fault
0-7 Lowbyte:yearproductionMPA X8-15 Highbyte:notused X
Bit Register address 42 Description During fault
0-7 Lowbyte:LSByteoftheu32devicenumberMPA X8-15 Highbyte:u32devicenumberMPA X
Bit Register address 43 Description During fault
0-7 Lowbyte:u32devicenumberMPA X8-15 Highbyte:MSByteoftheu32devicenumberMPA X
Bit Register address 44 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberHW X8-15 Highbyte:u24articlenumberHW X
Bit Register address 45 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberHW X8-15 Highbyte:indexarticlenumberHW X
Bit Register address 46 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberdevice X8-15 Highbyte:u24articlenumberdevice X
Bit Register address 47 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberdevice X8-15 Highbyte:indexarticlenumberdevice X
Bit Register address 48 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberSWEM X8-15 Highbyte:u24articlenumberSWEM X
101 … 126100 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 49 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberSWEM X8-15 Highbyte:indexarticlenumberSWEM X
Bit Register address 50 Description During fault
0-7 Lowbyte:dayofEMproduction X8-15 Highbyte:monthproductionEM X
Bit Register address 51 Description During fault
0-7 Lowbyte:yearproductionEM X8-15 Highbyte:notusednotused X
Bit Register address 52 Description During fault
0-7 Lowbyte:LSByteoftheu32devicenumberEM X8-15 Highbyte:u32devicenumberEM X
Bit Register address 53 Description During fault
0-7 Lowbyte:u32devicenumberEM X8-15 Highbyte:MSByteoftheu32devicenumberEM 0
Bit Register address 54 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberHW-EM X8-15 Highbyte:u24articlenumberHW-EM X
Bit Register address 55 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberHW-EM X8-15 Highbyte:indexarticlenumberHW-EM X
Bit Register address 56 Description During fault
0-7 Lowbyte:LSByteoftheu24articlenumberdeviceEM X8-15 Highbyte:u24articlenumberdeviceEM X
Bit Register address 57 Description During fault
0-7 Lowbyte:MSByteoftheu24articlenumberdeviceEM X8-15 Highbyte:indexarticlenumberdeviceEM X
103 … 126102 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Bit Register address 00 Heatrequest1 Highpower/level22 Remoteunlocking3 Not used4 Not used5 Not used6 Ignorebit0(heatrequestvia
bus)7 Not used8 ActivateBusControlHeat+/-9 Heat+10 Heat-11 Not used12 Not used13 Not used14 Not used15 Not used
Bit Register address 10-15 Not used
Bit Register address 00 HWinputstatemoreheat1 HWinputstatelessheat2 HWinputstateHighFire3 HWinputstateLowFire4 Not used5 Not used6 Not used7 Not used8 Bits8..15:notused
Output dataUsethefollowingFunctionCodestowritethesespecifications.
05(0x05)WriteSingleCoil(Coil=bitatbitaddressx)06(0x06)WriteSingleRegister(toregisteraddress)16(0x10)WriteSingleRegister(fromregisteraddress)
Digital inputsUsethefollowingFunctionCodestoread this information. 04(x04)ReadInputRegisters02(0x02)ReadDiscreteInputsThis information is contained in the inputdata(seeabove).
103 … 126102 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Error overviewErrorID
Internalerror
Error description
0x18
Error in external applicationCausesoftheerror:• Additional byte 1: 0xB4 (error in VisionBox) Switch-offwascausedexternally,forexamplebyselectingthe "switch-off"functioninthePCsoftwareoftheVisionBox
• Additional byte 1: 0x90 (internal MPA error P2) Additionalbyte4:0xA0timeoutparameterizationmode Additionalbyte4:0xA1invalidbusaddress Additionalbyte4:0xA2parameteradjustmenterroroftheservicecase Additionalbyte4:0xA3anti-oscillationfunctionshuttererror Additionalbyte4:0xA4extensionmoduletest(P240>0andnoEMconnected)
• Additional byte 1 0xC2 (extension module error) Additionalbyte4:0xE0parametererror(parameteroutsidethelimits) Additionalbyte4:0xE1/0xE2calibrationvaluenotsetinEEPROMornotOK Additionalbyte4:0xE3reserved Additionalbyte4:0xE4HighFireSignalmissingduringpre-venting Additionalbyte4:error0xE5configuration: -ParameterP249oneormorebitswithoutfunction -Pre-orpost-ventingtimetooshortforP248 Additionalbyte4:0xE6errorconfiguration: -P248<16(1s) -P30-2*P248<16(1s) -P51-P248<16(1s) Additionalbyte4:0xE7reserved Additionalbyte4:0xE8EM2/6notrecognized(P240=0,EM2/6connected) Additionalbyte4:0xE9wrongsignalLowFireduringignitionandstabilisation Additionalbyte4:0xEAwrongsignalHighFireduringpost-ventingtime Additionalbyte4:0xEFadditionalmodulenotcompatiblewithMPAversion
xx Forothererrors,seepage56ff.
Error displayThe error information can be displa-yedviatheMPAdisplay,theDUNGSvisionboxorviathefieldbus.
Errordisplayondisplay:seepage44
105 … 126104 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Dimensions of plug-in base
190
165
151,
5
170
122
4,5 mm
x1MPA
x2EM2/6
105 … 126104 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Flame detector
RequestsforoperationbyseparateflamedetectorsonMPA41xx:
Theflamedetectorsmustbetestedandapprovedformonitoringgasburners.
The reaction times must be ob-served!
Totalreactiontime=reactiontimeMPA+reactiontimeflamedetectorAproofaboutthecompliancewiththerequirementsofEN298isre-quired.
Thereactiontimeafteraflamelift-offofanexternalflamedetectormaynotbelongerthanthefirstorsecondstart-gasflameprovingperiod.WhenconnectedtoFLW1,theioni-sationbehaviourofaflamemustbesimulated(rectifiereffect).Thefollow-ingvaluesareactiveontheionisationinputandoutputoftheMPA:230VAC+10%-15%.TheinternalresistanceoftheMPAisapprox1MΩ.Forsafetyreasons,theflamesensormustworkproperlyalsowithaninternalresistanceof360kΩ.Undertheseconditions,thesimula-tioncircuitintheflamedetectormustreachatleastadirectcurrent3µA.IfanalternatingcurrentwithaDCcomponentissimulated,theDCcom-ponentshouldreachatleast25%.ThecurrentcanbederivedtoN,PEorreturnedtoNontheMPA.WhenconnectedtoFLW2,theswitchingoutputofasuitableflamedetectormustbeconnectedtoFLW2NO(115VACor230VAC).Forcontinuousoperation,FLW2NCmustalsobeconnected(EXORsignal).Theselectedflamedetectormustalsobecertifiedforcontinuousoperation.Alternatively,aflamede-tectorforintermittentoperation(onlyFLW2NO)maybeusedincombina-tionwithaDUNGSshutterincontinu-ous operation.The EMC regulations must be ob-served(EN298).Theentiresystemmust not produce inadmissible emis-sions. MPA41xxisnotgalvanicallyisolated.MPA41xxandtheflamedetectormust be connected according to the correct phase.
Attention: DUNGScannotbeheldliableiftheflamedetectorandtheautomaticburner control do not work orderly together. Especially if the electromag-neticbehaviourisnotaccordingtothe regulations or if the time-depend-entbehaviourisnotcorrect.
Thequalityoftheflamesignalisdis-playedforflameguard1asanumberbetween0and58.Evaluationoftheflamesignalisonlypossiblewithionisationflamemoni-toring,alsobymonitoringwithUV41(HE).WhenusingtheUV42,FLW10IRorFLW20UV,themaximumvalueisalways displayed.
25
ION
/ μA
20
15
10
5
0
10 20 30 40 50 60
ION vs. digits MPA41
digits
107 … 126106 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Manufac-turer
Designa-tion
Type Output signal
Safety timeFlame de-tector
Total reac-tion time after flame lift-off
Intermittent
Continu-ousoperation
– Ionisation electrode
Ionisation Ionisation 0s P41 Yes Yes
DUNGS UV41(HE)
UVtube Ionisation 0.125s(=2/16s)
P41+0.125s Yes Continuous operation only to-gether with DUNGSshutter function
DUNGS UV42
UVtube Switchingoutput 230VAC
0.125s(=2/16s)
P41+0.125s Yes Continuous operation only to-gether with DUNGSshutter function
DUNGS FLW20 UVtube Ionisation 0.5s P41+0.5s Yes No
DUNGS FLW10
Flicker de-tectorwith fre-quency analysis
Ionisation 0.5s P41+0.5s Yes No
DUNGS FLW41I
Ionisation Switchingoutput 230VAC
0,19s(=3/16s)
P41+0,19s Yes Continuous operation only in con-nection with DUNGSshutter signal(e.g.EM2/4)
Flame detectors tested and authorised by DUNGS:
FlamedetectorsthatarenotincludedinthislistmustbeauthorisedbeforeusebyDUNGS
107 … 126106 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
M16x1,5
94 ø44,5
ø 42
UV 41 (HE)TheUV41isaflamedetectorwithUVtubeinmetaldesignforhighme-chanical stress.TheflamedetectorisconnectedtotheionisationinputoftheMPA41xxand is suitable for intermittent opera-tion.For use in continuous operation applications,theUV4xshutterisad-ditionally required.TheadapterUV4x-EM1/xmustbeusedformountingtheUV41.Other mounting adapters upon re-quest.
Technical Data
Dimensions
UV41(HE)
UV4xEM1/xadapter
UV 41 GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <1WType of protection IP54Ambienttemperature -40°C...+60°C
-40°C...+80°CwithreducedlifetimeoftheUVtubeStorageandtransport -40°C...+80°Cmaximumstoragetimewithoutpowersupply:3monthHumidity DIN60730-1,nodewingadmissibleLifetime 10,000operatinghours(Ausführung(HE)verminderteLebensdauer)Mounting position as desiredDimensionsinmm Diameter:44.5mm
Length:94mmLengthwithUV4x-EM1:approx.128-143mm
Max. line length 10m
39,5
28,5
50
50
36
50
3628,5
G1/8"
EM1/3 EM1/4EM1/6
EM1/5EM1/7
EM1/8EM1/9
1/4"NPT 1/2"
NPT
G1/8" G3/4"
109 … 126108 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
G
G
G
G
L (PIN3)
L (PIN3)
N�(PIN2)
N�(PIN2)
O�(PIN1)
O�(PIN1)
PE�(6,3x0.8)
PE�(6,3x0.8)
11
11
22
22
33
33
X101 X101
InstallationTheUV41(HE)mustbemountedascloselyaspossibletotheflametobemonitored. TheUV41(HE)EM1/3adapterfitsa1"inspectiontube;whenmountingit,makesurethattherubbersealingringenclosedwiththeUV41(HE)isinsertedbetweentheUV41(HE)andthe mounting adapter.TheUVsensorwillalsodetectex-ternallightasaflame,whichiswhytheUV41(HE)mustbemountedsuchthat,forexample,nodaylight,ignitionsparksorotherflamescanbedetected.TheUV41(HE)tubeissensitivetoimpacts,vibrations,etc.,whichiswhyitmustbemountedwithoutvibratingit.Afterthemountingworkiscomplete,all screws must be checked for tight fit.Iftemperaturesofmorethan60°CarereachedattheUV41(HE),anadapterfittedwithaquartzcoverglassand,ifnecessary,anadditionalpurging air connection must be used (uponrequest).
AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.
AttentionTheflamedetectorUV41(HE)isdeliveredwithoutcablescrewcon-nection. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof16).Theprotectiveearthconductormustbe connected using an insulated femaleconnectoraccordingtoDIN46245.
Electrical connection
Connection UV 41 (HE) MPA 41xxPin1 Out Ionisation(5)Pin2 N NPin3 L Vers.FLW(7)PE
109 … 126108 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
M16x1,5
94 ø44,5
ø 42
UV 42TheUV42isaflamedetectorwithUVtubeinmetaldesignforhighme-chanical stress.TheflamedetectorisconnectedtotheionisationinputoftheMPA41xxand is suitable for intermittent opera-tion.For use in continuous operation applications,theUV4xshutterisad-ditionally required.TheadapterUV4x-EM1/xmustbeusedformountingtheUV42.
Technical Data
Dimensions
UV42
UV4xEM1/3adapter
UV 42 GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <1WType of protection IP54Ambienttemperature -20°C...+60°C
-40°C...+80°CwithreducedlifetimeoftheUVtubeStorageandtransport -40°C...+80°Cmaximumstoragetimewithoutpowersupply:3monthHumidity DIN60730-1,nodewingadmissibleLifetime 10,000operatinghoursMounting position as desiredDimensionsinmm Diameter:44.5mm
Length:94mmLengthwithUV4x-EM1:approx.128-143mm
Max. line length 100m
39,5
28,5
50
50
36
50
3628,5
G1/8"
EM1/3 EM1/4EM1/6
EM1/5EM1/7
EM1/8EM1/9
1/4"NPT 1/2"
NPT
G1/8" G3/4"
111 … 126110 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
InstallationTheUV42mustbemountedascloselyaspossibletotheflametobemonitored. TheUV42EM1/3adapterfitsa1"inspectiontube;whenmountingit,make sure that the rubber sealing ring enclosedwiththeUV42isinsertedbetweentheUV42andthemountingadapter.TheUVsensorwillalsodetectexter-nallightasaflame,whichiswhytheUV42mustbemountedsuchthat,forexample,nodaylight,ignitionsparksorotherflamescanbedetected.TheUVtubeissensitivetoimpacts,vibrations,etc.,whyitmustmountedinavibrationfreearea.Afterthemountingworkiscomplete,all screws must be checked for tight fit.Iftemperaturesofmorethan60°CarereachedattheUV42,anadapterfittedwithaquartzcoverglassand,ifnecessary,anadditionalpurgingairconnectionmustbeused(uponrequest).
AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.
Attention TheflamedetectorUV42isdeliv-ered without cable screw connection. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof16).Theprotectiveearthconductormustbe connected using an insulated femaleconnectoraccordingtoDIN46245.
G
G
G
G
L (PIN3)
L (PIN3)
N�(PIN2)
N�(PIN2)
O�(PIN1)
O�(PIN1)
PE�(6,3x0.8)
PE�(6,3x0.8)
11
11
22
22
33
33
X101 X101
Connection UV 42 MPA 41xxPin1 Out FLW2NO(16)Pin2 N NPin3 L Vers.FLW(7)PE
Electrical connection
111 … 126110 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
UV 4x EM 1/1 (shutter module)TheUV4xshuttermoduleallowscontinuousoperationoftheUV41andUV42flamesafeguards.Theshutter module is inserted between theflamesafeguardandthecorre-sponding mounting adapter.Aseparatepowersupplyisnotnecessary,asonlytheshuttersignalprovidedbytheMPA41xxviaanextensionmodule(e.g.EM2/4)mustbe connected.
Technical data
DimensionsUV 4x EM 1/1
UV 4x EM 1/1 general (Shuttermodul)Schutzkleinspannung 24VDCType of protection IP54Ambienttemperature -20°C...+60°C
-40°C...+80°C(with reduced lifetime)Storageandtransport -40°C...+80°CHumidity DIN60730-1,nodewingadmissibleLifetime 1millionswitchings(at10min/switching,20a)Mounting position as desiredDimensionsinmm Diameter:44,5mm
Length:75mmHeight:ca.101mm
Max. line length 100m
101
75
M16 x 1,5ø 44,5
ø 42
113 … 126112 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
AttentionThe maximum allowed line lengths mustnotbeexceeded.Supplyandsignallinesmustbelaidseparately,as far as possible.
AttentionTheflamesafeguardUV41isdeli-veredwithoutcablescrewconnec-tion. To guarantee the required traction reliefandIPprotectionclassIP54,acablescrewconnectionM16x1.5forcablediameters5-9mmisrequired(3x0.75mm²,whichcorrespondstoanAWGof20,to3x1.5mm²,whichcorrespondstoanAWGof1).
AttentionAlsoiftheshutterisclosedarentoflightcanfullontheUV-cell.Throughthissafetyshutdown'scanoccureveniftheUV-cellworkscorrectly.In such case the mounting position oftheUV-cellhastobechangendora mounting adaptor with a reduced diameters has to take place.Alternativelythediametercanbereduced by additional nipple.
Electrical connection
GND+24 V DC PE
Connection UV 4x EM 1/1 MPA 41xx EM 2/xPin1 +24VDC +24VDCPin2Pin3 GND GND
The shutter module is mounted bet-weentheUV41(HE)orUV42flamesafeguard and the mounting adapter UV4xEM1/x.
113 … 126112 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
FLW 20UV
TheFLW20UVisaflamedetectorwithUVtubeinplasticdesign.TheuseofaUVtubeguaranteesthatbackgroundradiation,forexamplefrom red-hot walls or parts of the mix-ingdevice,willnotbedetected.TheflamesignalintensitycanbeseendirectlyontheopticalLEDdis-playoftheflamedetector.TheFLW20UVisconnectedtotheionisationinputoftheMPA41xxandissuitableexclusivelyforintermittentoperation.TheFLWflangesaresuitableformounting.
Technical DataRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption 5.5mAOutput data Reactiontimewithflameontyp.:0.5sec.
Reactiontimewithflameout<0.5sec.Switchingoutput max.switchingcurrent15mA,
max.switchingpower0.3Wmax.switchingvoltage280VAC/400VDC
Opticevaluation Spectralregion185–260nmAlignmenttotheflame Radial,leftType of protection IP41Ambienttemperature -20°C…50°C
-20°C…60°CwithreducedlifetimeTransport and storage -20°C…60°CHumidity max.95%ofr.h.,nodewingadmissibleLifetime 10,000operatinghoursMounting position as desiredMax. line length 10m
115 … 126114 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
13,5
30
115
50 55
22
31
Dimensions [mm]FLW 20 UV
FLW flange
Installation
TheFLW20UVmustbemountedascloselyaspossibletotheflametobemonitored.ItismountedbymeansofaFLWflange(height7or13mm)orofaholderwitha14mmmountingbore.Theflamedetectormustbefirmlyinserted into the holder. No external lightmustbeincidentonthesensor,anddirectviewoftheignitionsparkmustbeavoidedaswell.
Attention:The maximum allowed line lengths must not be exceeded. Supplyandsignallinesmustbelaidseparately,asfaraspossible.
Inspection openingRadial
115 … 126114 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
LED
Electrical connection
Operation display LED
TheflamesignalintensityoftheflamedetectorFLW20UVisshownonthebuilt-inLED.
LED offFLWisdeadornoflameisdetected.
LED flashingFlameisdetected,theflashingpulsesoftheLEDsignallingtheflamesignal intensity – Increasingflashingpulses=higherintensity
LED permanently onFlame is detected at the highest flameintensity
Commissioning and maintenance
SincetheUVtubeissubjecttoageing,asafetycheckoftheflamedetector must be carried out dur-ing each commissioning and each maintenance.The following functions must be checked:
Start-up without flame signallingDarkentheflamedetectorduringstart-up,theautomaticburnercontrolsystem must either output a fault at the end of the safety time or perform a restart.
Start-up with flame signallingDuringthestartupattemptoftheautomaticburnercontrolsystem,theflamedetectorisexposedtoanexternalUVradiation,forexamplefromalighteroragasflame(avail-ableroomlightisnotsufficient).Theautomatic burner control system reports external light.
Burner operationCovertheflamedetectorwhiletheburner is running – depending on the parameter setting of the automatic burnercontrolsystem,alock-outorsafetyshutdown,followedbyarestartattempt,willtakeplace.
Incaseofmalfunctions,theflamedetector must be replaced. Afteraruntimeof10,000h,theflamedetector should be replaced as a preventivemeasure.AreplacementoftheUVtubeisnotpossible.
Blue,terminalnumber:N
Black,terminalnumber:5/Ion
Brown,terminalnumber:7/FLWpwr.
117 … 126116 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
FLW 10IR
TheFLW10IRisaflamedetec-torequippedwithanIRsensorformonitoring burners with blue-burning flames.Theflamedetectordetectstheflickerfrequencyoftheflame.Lightraysthatemitauniformfrequencyarefilteredout. External light like that caused by glowingcomponentsorfluorescenttubesisnotdetectedasflame.TheflamesignalintensitycanbeseendirectlyontheopticalLEDdis-playoftheflamedetector.TheFLW10IRisconnectedtotheionisationinputoftheMPA41xxandissuitableexclusivelyforintermittentoperation.TheFLWflangesaresuitableformounting.
Technical DataRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption 3...4mAOutput data Reactiontimewithflameontyp.:0.5sec.
Reactiontimewithflameout<0.5sec.Switchingoutput max.switchingcurrent15mA,
max.switchingpower0.3Wmax.switchingvoltage280VAC/400VDC
Opticevaluation Spectralregion380-1150nm,maximumsensitivityat920nmAlignmenttotheflame RadialType of protection IP41Ambienttemperature -20°C…60°CTransport and storage -20°C…60°CHumidity max.95%ofr.h.,nodewingadmissibleMounting position as desiredMax. line length 10m
117 … 126116 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Dimensions [mm]FLW 10IR
FLW flange
Installation
TheFLW10IRmustbemountedascloselyaspossibletotheflametobemonitored.ItismountedbymeansofanFLWflange(height7or13mm)orofaholderwitha14mmmountingbore.Theflamedetectormustbefirmlyinserted into the holder. No external lightmustbeincidentonthesensor,anddirectviewoftheignitionsparkmustbeavoidedaswell.
Attention:Themaximumallowedline lengths must not be exceeded. Supplyandsignallinesmustbelaidseparately,asfaraspossible.
13,5
30
115
50 55
22Inspection opening
119 … 126118 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Electrical connection
Operation display LED
TheflamesignalintensityoftheflamedetectorFLW10IRisshownonthebuilt-inLED.
LED offFLWisdeadornoflameisdetected.
LED flashingFlameisdetected,theflashingpulsesoftheLEDsignallingtheflamesignal intensity – Increasingflashingpulses=higherintensity
LED permanently onFlame is detected at the highest flameintensity
Commissioning and maintenance
TheFLW10IRismaintenance-free.
LED
Blue,terminalnumber:N
Black,terminalnumber:5/Ion
Brown,terminalnumber:7/FLWpwr.
119 … 126118 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
FLW 41ITheflamesafeguardmoduleFLW41IisconnectedtothesecondflameguardinputoftheMPA41xx.Flame monitoring is done by means of an ionisation electrode. This allows burners to be monitored viatwomeasuringpoints.Suitableforintermittentoperation,inconnection with an electronic shutter signal(e.g.EM2/3orEM2/4)alsosuitable for continuous operation.
Technical data
DimensionsFLW 41I
FLW 41I GeneralRatedvoltage 230VAC-15%...+10%Frequency 50…60HzPowerconsumption <3WType of protection IP54Ambienttemperature -40°C...+70°C
Storageandtransport -40°C...+80°CHumidity DIN60730-1,notdewingadmissibleMounting position as desiredDimensionsinmm(LxHxT)
approx.152,5x151,5x77mm
Weigth 0,6kgMax.linelengthtoMPA 100mMax.ionizationlinelength 10m
77
151,5
152,5
121 … 126120 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
AssemblyTheFLW41canbemountedeitheron a hat rail or by means of a direct screwconnection(alldimensionsasforMPA411)
AttentionThe maximum allowed line lengths must not be exceeded.Supplyandsignallinesmustbelaidseparately.
FunctionTheFLW41Iallowsaflametobemonitored at two measuring points or twoflamestobemonitoredindepen-dently of one another.IftheshuttersignaloftheMPA41xxisconnected,theFLW41Iissuitablefor continuous operation.
Example
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
N G
G
ShuttersignalFlame signalVoltagesupplyON
77
151,5
152,5
MPA41xxFlamedetector1
FLW41IFlame detector 2
FLWOutput
toMPA
FLWPower
fromMPA
ION
N
Shutter
1(+)
2(-)
PE
N
1.0AT
Display:
Electrical connection
121 … 126120 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
DEZ ignition transformers
Technology
TheDUNGSDEZareelectronichigh-performance ignition transform-ers with high-frequency oscillation technology.Comparedwithconventionalinduc-tiveignitiontransformers,theDEZare much smaller and lighter.Designsforoneortwoignitionelectrodesareavailableindifferentvoltageversions.
Application
Foroilandgasburners,ignitiontakesplace,dependingondesign,withoneignition electrode against the burner mass or with two ignition electrodes between the electrodes.
Approval
73/23/EECLow-VoltageDirective89/336/EECEMCDirective
123 … 126122 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
DEZ 1xx DEZ 2xx
Parameter overview
DEZ function
TheDEZignitiontransformersareavailableintwoversions.Eitherwithahigh-voltageoutput(DEZ1xx)forignitionagainsttheburnermassorwithtwohigh-voltage
outputs(DEZ2xx)forignitionbe-tween the electrodes.Bothversionsareavailablewithdif-ferent performance data.For use in burner systems in which ignitionandionisationflamemoni-toringtakesplaceviaacommonelectrode,the"SEO"versionsmustbe used.
DEZ Versions
DEZ 100 DEZ 101 DEZ 100 SEO DEZ 101 SEO DEZ 200
High-voltageoutputs 1 1 1 1 2Mainsvoltage[VAC] 230/240 120 230 120 230/240Frequency[Hz] 50/60 50/60 50/60 50/60 50/60Currentconsumption[A] 0.3 0.5 0.3 0.5 0.14Powerconsumption[VA] 69 55 69 60 32Secondaryvoltage[kV]+/-10%
1x15 1x15 1x15 1x15 2x10
Secondaryfrequency[kHz] 10 13 10 16 10Short-circuitcurrent[mA] 30 30 30 30 20Dutycycle3min. 33% 33% 33% 33% 100%Type of protection IP54 IP54 IP54 IP54 IP54Ambienttemperatureta[°C] -20…60°C -20…60°C -20…60°C -20…60°C -20…60°CWeight[kg] 0.32 0.32 0.32 0.32 0.32Part-No. 252113 255018 257126 257127 252114
Electrical connectionConnection to the mains is made through pre-fabricated connection linesDEZ1xx/2xx,whichareavail-ableindifferentlengths.
The ignition electrodes are con-nectedviapre-fabricatedcarbonfibreignition lines. The high line resistance oftheignitionlineof10kOhm/mef-fectivelysuppressesEMCfaults.
Theignitionlinesarefittedwithaninsulated 6.5 mm angle plug on the electrode side.
DEZconnection
PowersupplyconnectionL1:blackN:blue:green-yellow
123 … 126122 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
Dimensions
AttentionTheoperationoftheDEZignitiontransformersproducesveryhighvoltages.Theignitiontransformersmay only be put into operation if the ignition electrodes were built into the burner/burnerchambertouch-proofandallliveconnectionsbymeansofthelinesprovidedforthispurposewere made touch-proof.
Thelengthoftheignitionline(s)mustnotexceed1m.
Connectingtheprotectiveearthismandatory.
Connectingtheprotectiveearthismandatory.Inthe"SEO"versionforsingle-elec-trodeoperation,theprotectiveearthisconnectedtoterminal5oftheMPA41xx.
DEZconnection Electrode connectionø6.3mm
125 … 126124 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4
VisionBoxTheVisionBoxisusedforaccesstotheMPAviaaPC.SeeVisionBoxdocumentation
125 … 126124 … 126
Prin
ted
in G
erm
any
• Edi
tion
02.1
4 • N
r. 25
7 45
4