STATIC LED TROFFER
PENDANT OR SURFACE MOUNTED LINEAR LUMINAIRE
LED STRIP LIGHT
SURFACE MOUNTED ROUND LIGHT
RECESSED DOWNLIGHT
WALL MOUNTED LUMINAIRE
DECORATIVE PENDANT
SINGLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH
DIRECTIONAL ARROWS AS INDICATED ON PLANS
DOUBLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH
DIRECTIONAL ARROWS AS INDICATED ON PLANS
REMOTE EMERGENCY LIGHTING UNIT
LIGHTING SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SPECIAL RECEPTACLE (# = NEMA CONFIGURATION)
FLUSH FLOOR DUPLEX RECEPTACLE
SINGLE POLE WALL SWITCH
TWO POLE WALL SWITCH
THREE WAY WALL SWITCH
KEYED WALL SWITCH
SINGLE POLE, DOUBLE THROW (SPDT) SWITCH (CENTER OFF)
MOTOR HP RATED SWITCH WITHOUT OVERLOAD PROTECTION
MECHANICAL DIAL TIMER WALL SWITCH
LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH
DUAL RELAY LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH
LOW VOLTAGE OCCUPANCY SENSOR
POWER PACK FOR LOW VOLTAGE OCCUPANCY SENSORS
LIGHTING CONTACTOR
EXTERIOR PHOTOCELL
CONTACTOR
PUSH BUTTON OPERATOR
CLASS 2 TRANSFORMER POWER SUPPLY
DOOR ANNUNCIATOR A/V HORN STROBE
JUNCTION BOX
MOTOR
MOTORIZED DAMPER
DISCONNECT SWITCH
BRANCH CIRCUIT PANELBOARD
SWITCHBOARD
POWER SYMBOLS
#
LC
os
P
TELECOMMUNICATIONS SYMBOLS
APARTMENT PHONE OUTLET
TELECOMMUNICATIONS OUTLET
APARTMENT CATV OUTLET
TELEPHONE TERMINAL BOARD
CLG CEILING MOUNTED
• FLUSH MOUNTED IN SUSPENDED OR HARD CEILINGS
• SURFACE MOUNTED TO STRUCTURE ABOVE IN OPEN CEILINGS
CT MOUNT BOTTOM OF DEVICE AT 6" ABOVE COUNTERTOP
EM PROVIDE LUMINAIRE WITH EMERGENCY BATTERY BACKUP
GFI GROUND FAULT CIRCUIT INTERRUPTING DEVICE
NL NIGHTLIGHT WIRED TO UNSWITCHED HOT CONDUCTOR
WP PROVIDE WEATHERPROOF ENCLOSURE FOR DEVICE
XX" MOUNTING HEIGHT OF DEVICE ABOVE FINISHED FLOOR
SYMBOL MODIFYING DESIGNATORS
##
##
CIRCUIT AND RACEWAY SYMBOLS
CIRCUIT DESIGNATION:
TOP INDICATES PANEL OF CIRCUIT ORIGIN
BOTTOM INDICATES CIRCUIT NUMBER
HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN
PARTIAL HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN
CONDUIT CONCEALED IN WALL OR ABOVE CEILING
CONDUIT BELOW GRADE OR EMBEDDED IN CONCRETE
LINE VOLTAGE CIRCUIT CONDUCTORS
SHORT = HOT/TRACER/SWITCH LEG CONDUCTOR
LONG = NEUTRAL (GROUNDED) CONDUCTOR
CURVED = GROUNDING (BONDING) CONDUCTOR
CONDUIT STUB OUT WITH NYLON END BUSHING
CONDUIT TURNED UP
CONDUIT TURNED DOWN
GROUNDING CONNECTION
PP
2
3
K
m
OS
OS2
T
J
C
DT
D
tv
TV UG
T UG
E UG
FIRE ALARM SYMBOLS
P
R
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR PANEL
MANUAL PULL STATION
HEAT DETECTOR
SMOKE DETECTOR
ADDRESSABLE MONITORING MODULE
NOTIFICATION HORN APPLIANCE
NOTIFICATION STROBE APPLIANCE
NOTIFICATION HORN/STROBE APPLIANCE
FIRE ALARM RELAY
ELECTROMAGNETIC DOOR HOLDER
SMOKE DAMPER OR COMBINATION FIRE/SMOKE DAMPER
FIRE SPRINKLER FLOW SWITCH
FIRE SPRINKLER TAMPER SWITCH
FIRE SPRINKLER BELL/GONG OR HORN/STROBE
120V COMBINATION CO/SMOKE ALARM
120V, 177cd XENON STROBE
SITE ELECTRICAL SYMBOLS
UNDERGROUND ELECTRICAL SERVICE LATERAL
UNDERGROUND ELECTRICAL PRIMARY
UNDERGROUND TELEPHONE SERVICE
UNDERGROUND CATV SERVICE
POLE MOUNTED AREA LIGHT
GRADE MOUNTED LIGHT
RECESSED DOWNLIGHT/FLAG UPLIGHT
POWER COMPANY PAD MOUNTED UTILITY TRANSFORMER
POWER COMPANY UTILITY POLE
SD
AM
TR
HS
FIRE ALARM DEVICE MOUNTING
1. VISUAL UNIT
DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP
6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)
2. AUDIO UNIT
DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP
6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)
*TOP OF UNIT NOT LESS THAN 90" ABOVE FLOOR AND NOT
LESS THAN 6" BELOW CEILING (NFPA) (BOTTOM AT 88"
WITH CMU COURSES). MOUNT AT NFPA HEIGHT ONLY IF
REQUIRED BY LOCAL AHJ.
3. AUDIO/VISUAL UNIT
DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP
6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)
4. PULL STATION
HIGHEST OPERABLE PART SHALL NOT BE MORE THAN 48"
ABOVE THE FLOOR (FRONT APPROACH) (PER ADA)ELECTRICAL DEVICE MOUNTING HEIGHTS
No Scale1
9"
16"
48"
54"
64"
80"
88"90"
AREA ALLOWED IF SIDE REACH IS POSSIBLE
AREA ALLOWED IF SIDE REACH IS POSSIBLE
6" MIN.
72"
FIRE ALARMPOWER & TELECOM
9"
16"
48"
54"
64"
80"
88"90"
72"
TELECOM
OUTLETRECEPTACLE
GROUND
BAR
MANUAL
PULL
STATION
REMOTE
ANNUNCIATOR
WALL
SWITCH
HVAC
THERMOSTAT
PHONE
OUTLET
CATV
OUTLET
*
HORN/STROBEHORNSTROBE
HORN
FIRE FIRE
FIRE
FIRE
GENERAL SYMBOLS
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
ELEVATION REFERENCE
DETAIL NUMBER
SHEET NUMBER
SECTION CUT
DETAIL NUMBER
SHEET NUMBER
KEYED PLAN NOTE
REVISION NOTE
ELEVATION
CONNECT TO EXISTING. FIELD VERIFY LOCATION &
MATERIAL OF EXISTING
#
##
#
##
#
##
#
MECHANICAL AND ELECTRICAL SYMBOLS AND ABBREVIATIONS
AABOVE FINISH FLOOR AFF
ABOVE FINISH GRADE AFG
ACRYLONITRILE BUTADIENE STYRENE PIPE ABS
AIR CONDITIONING A/C
AIR HANDLING UNIT AHU
ALTERNATING CURRENT AC
ALUMINUM AL
AMERICAN NATIONAL STANDARDS INSTITUTE ANSI
AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASME
AMERICAN WIRE GAUGE AWG
AMERICANS WITH DISABILITIES ACT ADA
AMPERE AMP or A
ANALOG INPUT AI
ANALOG OUTPUT AO
ARCHITECT or ARCHITECTURAL ARCH
AUTHORITY HAVING JURISDICTION AHJ
AUTOMATIC TRANSFORMER SWITCH ATS
BBELOW CEILING BC
BELOW GRADE BG
BINARY INPUT BI
BINARY OUTPUT BO
BOOT WASH BW
BRITISH THERMAL UNIT BTU
BTUs PER HOUR BTUH
BUILDING BLDG
CCABLE TELEVISION CATV
CAPACITY CAP
CATEGORY CAT
CEILING MOUNT CLG
CELSIUS C
CHILLED WATER CHW
CHILLED WATER RETURN CHWR
CHILLED WATER SUPPLY CHWS
CIRCUIT BREAKER CB
CLEANOUT CO
CLOTHES WASHER CONNECTION BOX CCB
COLD WATER (DOMESTIC) CW
COMMON C
CONCRETE CONC
CONDENSING UNIT CU
CONDUIT C
CONDUIT ONLY (WITH PULL STRING) CO
COPPER CU
COUNTER TOP CT
CROSS-LINKED POLYETHYLENE PIPE PEX
CUBIC FEET PER MINUTE CFM
CUBIC YARD CU YD
DDEPTH or DEEP D
DIRECT CURRENT DC
DIRECT DIGITAL CONTROL DDC
DIRECT EXPANSION DX
DISCONNECT SWITCH DS
DISH WASHER DW
DRINKING FOUNTAIN DF
DRY BULB DB
EELECTRIC or ELECTRICAL E or ELEC
ELECTRIC WATER COOLER EWC
ELECTRIC HEATER EH
ELECTRICAL CONTRACTOR EC
ELECTRICAL METALLIC TUBING EMT
ENTERING AIR TEMPERATURE EAT
ENTERING WATER TEMPERATURE EWT
EQUIPMENT EQUIP
EXHAUST EXH
EXHAUST AIR EA
EXHAUST FAN EF
EXHAUST GRILLE EG
EXISTING EXIST
EXISTING TO REMAIN ETR
EXTERNAL STATIC PRESSURE ESP
FFAHRENHEIT F
FAN COIL UNIT FCU
FEET FT
FEET PER MINUTE FPM
FIBER OPTIC CABEL FOC
FINISH FLOOR CLEAN OUT FFCO
FINISH GRADE FG
FINISH GRADE CLEAN OUT FGCO
FIRE ALARM FA
FLEXIBLE METALLIC CONDUIT FMC
FLOOR DRAIN FD
FLOOR SINK FS
GGALLON GAL
GALLONS PER FLUSH GPF
GALLONS PER HOUR GPH
GALLONS PER MINUTE GPM
GALVANIZED RIGID STEEL CONDUIT GRC
GAS G
GAUGE GA
GENERAL CONTRACTOR GC
GLOBAL POSITIONING SYSTEM GPS
GOVERNMENT FURNISHED/CONTRACTOR INSTALLED GFCI
GOVERNMENT FURNISHED/GOVERNMENT INSTALLED GFGI
GROUNDING ELECTRODE CONDUCTOR GEC
GROUNDING (BONDING) CONDUCTOR G
GROUND FAULT CIRCUIT INTERRUPTER GFI
GROUND FAULT PROTECTION FOR EQUIPMENT GFPE
H
HANDHOLE HH
HEATING HTG
HEATING WATER RETURN HR
HEATING WATER SUPPLY HS
HIGH DENSITY POLYETHYLENE CONDUIT HDPE
HORSEPOWER HP
HOT GAS RE-HEAT HGRH
HOT WATER (DOMESTIC) HW
HOT WATER HEATER HWH
HOT WATER PUMP HWP
HOT WATER RECIRC. (DOMESTIC) HWR
HOUR HR
KKELVIN K
KILOWATT KW
LLAUNDRY TUB LT
LAVATORY LAV
LEAVING AIR TEMPERATURE LAT
LEAVING WATER TEMPERATURE LWT
LIGHTING LTG
LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMC
MKCMIL (THOUSAND CIRCULAR MILLS) MCM
MAIN CIRCUIT BREAKER MCB
MAIN LUG ONLY MLO
MANHOLE MH
MANUFACTURER MANUF
MAXIMUM MAX
MAXIMUM OVERCURRENT PROTECTION MOCP
MECHANICAL CONTRACTOR MC
MINIMUM MIN
MINIMUM CIRCUIT AMPACITY MCA
NEMA RATED MOTOR STARTER MS
MOUNTED MTD
MULTIMODE MM
NNATIONAL ELECTRICAL CODE (NFPA 70) NEC
NATIONAL ELECTRICAL MANUFACTURER'S ASSOC. NEMA
NATIONAL FIRE PROTECTION ASSOCIATION NFPA
NATIONALLY RECOGNIZED TESTING LABORATORY NRTL
NATURAL GAS G or NAT GAS
NEUTRAL (GROUNDED) CONDUCTOR N
NOMINAL NOM
NON FUSED NF
NORMALLY CLOSED NC
NORMALLY OPEN NO
NORTH N
NOT APPLICABLE N/A
NOT TO SCALE NTS
OON CENTER O.C.
OUTDOOR AIR OA
OUTSIDE DIAMETER OD
OUTSIDE PLANT CABLE OSP
OVERHEAD OH
PPASSIVE INFRARED PIR
PHASE PH OR Ø
POLYVINYL CHLORIDE PVC
POLYVINYL CHLORIDE CONDUIT PVC
POUNDS LBS
POUNDS PER SQUARE INCH PSI
PRESSURE REDUCING VALVE PRV
PULL BOX PB
RRECEPTACLE RCPT
REQUIRED REQ'D
RETURN AIR RA
RETURN GRILLE RG
ROOF TOP UNIT RTU
REVOLUTIONS PER MINUTE RPM
SSENSIBLE SENS
SERVICE ENTRANCE SWITCHBOARD SES
SERVICE SINK SS
SHOWER SH
SINGLE MODE SM
SINGLE POLE, DOUBLE THROW SPDT
SPECIFICATIONS SPEC
SQUARE FEET SQ FT or SF
STRAND ST
SUPPLY AIR SA
SUPPLY DIFFUSER SD
SURGE PROTECTION DEVICE SPD
TTAMPERPROOF ENCLOSURE TP
TELECOMMUNICATIONS ROOM TR
TELEPHONE T
TELEVISION TV
TEMPERATURE (CHANGE IN) TEMP (∆T)
TEMPERATURE/PRESSURE T/P
TEMPERATURE CONTROL CONTRACTOR TC
THOUSAND BTUs PER HOUR MBH
TOTAL TOT
TRANSIENT VOLTAGE SURGE SUPPRESSION TVSS
TYPICAL TYP
UUNDERGROUND UG
UNDERWRITERS LABRATORIES UL
UNINTERRUPTIBLE POWER SUPPLY UPS
UNLESS NOTED OTHERWISE UNO
UNSHIELDED TWISTED PAIR UTP
VVENT BELOW SLAB VBS
VENT THROUGH ROOF VTR
VENTILATION FAN VF
VOLT-AMPERES VA
VOLTS V
VOLTS ALTERNATING CURRENT VAC
WWALL HYDRANT WH
WASH TUB WT
WATER CLOSET WC
WATER COLUMN (in inches) "WC
WATER SERVICE W
WATT(S) W
WEATHERPROOF ENCLOSURE WP
WET BULB WB
WIRE WAY WW
WITH W/
XTRANSFORMER XFMR
MECHANICAL SYMBOLS
THERMOSTAT
RECTANGULAR RETURN OR RELIEF AIR DUCT UP
RECTANGULAR SUPPLY AIR DUCT UP
RECTANGULAR SUPPLY AIR DUCT DOWN
WALL DIFFUSER
SQUARE SUPPLY DIFFUSER - TYPE AND AIRFLOW INDICATED
MANUAL BALANCING DAMPER
SQUARE RETURN GRILLE - TYPE INDICATED
TEMPERATURE SENSORT
FIRE/SMOKE DAMPER
BELOW GRADE
FINISH FLOOR CLEAN OUT
FINISHED GRADE
ABOVE FINISHED GRADE
UNLESS NOTED OTHERWISE
ABOVE FINISHED FLOOR
OUTDOOR AIR
RETURN AIR
SUPPLY AIR
TEMPERATURE CONTROL CONTRACTOR
GENERAL CONTRACTOR
DESIGNATORS/ABBREVIATIONS
SYMBOL MODIFICATION
BG
FFCO
FG
AFG
UNO
AFF
OA
RA
SA
TC
GC
FINISH WALL CLEAN OUTFWCO
FINISH GRADE CLEAN OUTFGCO
RECTANGULAR RETURN OR RELIEF AIR DUCT UP
FIRE DAMPER
MECHANICAL CONTRACTORMC
DIRECT DIGITAL CONTROLDDC
ELECTRICAL CONTRACTOREC
ROUND DUCT UP
ROUND DUCT DOWN
FLEXIBLE DUCTWORK - MAX 5'
CONTROL CABLE, VERIFY TYPE WITH EQUIPMENT MANUFACTURER
T
RIGID DUCT RUNOUT
90° ELBOW WITH TURNING VANES
GRILLE/DIFFUSER TAG
TOP: DEVICE TAG (SEE SCHEDULE)
MIDDLE: NECK SIZE
BOTTOM: AIRFLOW
XX
XX
X
RECTANGULAR RETURN OR
EXHAUST AIR DUCT DOWN
PLUMBING SYMBOLS
PIPE TURNING DOWN
PIPE TURNING UP
CONDENSATE DRAIN LINED
SANITARY DRAIN BELOW GRADE
SANITARY DRAIN ABOVE GRADE
SANITARY VENT
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRC
WATER SERVICE PIPING
FIRE PROTECTION PIPING
NATURAL GASG
TEMPERED DOMESTIC WATERT
BALL VALVE
CHECK VALVE
GATE VALVE
BUTTERFLY VALVE
STRAINER
THERMOMETER
GAUGE
TEST PORT
FLOW CONTROL VALVE
GAS COCK
SOLENOID VALVE
PRESSURE REDUCING VALVE
NATURAL GAS REGULATORR
GREASE SANITARY DRAIN BELOW GRADEGR
UNION
W
FP
#
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
ME0.1
1" = 20'-0"
ELECTRICAL SITE PLAN1
4CONDUIT TRENCH DETAILS
No Scale
12
"
36
" M
IN C
OV
ER
FINISHED GRADE
SECTION "B"
12
"
FINISHED GRADE
SECTION "C"
12" MIN SEPARATION
3" SAND
ENCASEMENT
CONDUITS AS
INDICATED ON
DRAWINGS
BACKFILL
COMPACTED TO
95% RELATIVE
DENSITY
PLASTIC
CAUTION TAPE
3" SAND
ENCASEMENT
CONDUITS AS
INDICATED ON
DRAWINGS
BACKFILL
COMPACTED TO
95% RELATIVE
DENSITY
PLASTIC
CAUTION TAPE
12
"
48
" M
IN D
EPTH
FINISHED GRADE
SECTION "A"
3" SAND
ENCASEMENT
CONDUIT AS
INDICATED ON
DRAWINGS
BACKFILL
COMPACTED TO
95% RELATIVE
DENSITY
PLASTIC
CAUTION TAPE
36
" M
IN C
OV
ER F
OR
PO
WER
24"
MIN
IMU
M C
OV
ER
FO
R T
ELEC
OM
M
S
S
S
S
R2
R2R2
R3 R3 R3R3
R3 R3
R3
R3
R1
2"
MONUMENT LIGHT DETAIL
No Scale2
FLOODLIGHT WITH TILT
MOUNT FITTING
LIGHTING POLE
HAND HOLE
3" 3"
GROUT BETWEEN POLE
BASE PLATE AND TOP OF
CONCRETE BASE
3/4" CHAMFERED
CORNERS
#4 BAR HOOPS AT 16" O.C.
LAP ENDS 16" MIN.
(8) #6 VERTICAL BARS
EQUALLY SPACED
RIGID STEEL OR PVC
CONDUIT
POLE BASE BOLT DIA
PLUS 3", 18" Ø MIN.
No Scale
CONCRETE POLE BASE DETAIL3
BOND LIGHT POLE
TO GROUND WIRE
BASE COVER ATTACHED
TO POLE BASE
FINISHED GRADE
1"Ø ANCHOR BOLT.
NUMBER AND PLACEMENT
PER MANUFACTURER'S
RECOMMENDATIONS
HDPE OR PVC
CONDUIT
#6 GND IN 1"C
5/8"Ø x 10'
GROUND ROD
3'-0"
5'-0"
3/4" CONDUIT AT
MINIMUM 24" BELOW
GRADE, TYPICAL
WEATHERPROOF
JUNCTION BOX WITH
COVER
12" DEEP CONCRETE
PAD
30
A
12
A
16
R4
A
8
NOTES BY SYMBOL
BLDG TRANSFORMER BY UTILITY, CONCRETE PAD BY
GC. COORDINATE EXACT LOCATION AND SIZE WITH
UTILITY.
PROVIDE 4" CONDUIT BELOW GRADE FOR POWER
COMPANY PROVIDED PRIMARY CABLING. INSTALL
PULL ROPE IN RACEWAY. VERIFY TERMINATION POINT
ON SITE WITH LOCAL UTILITY.
SERVICE LATERAL (CONDUIT & WIRE) BY E.C. SEE
RISER DIAGRAMS ON SHEET E6.3.
(2) 4" CONDUITS FOR COMMUNICATIONS SERVICES.
PROVIDE PULL ROPE IN EACH RACEWAY. EXTEND
CONDUITS TO PROPERTY LINE, CAP AND FLAG.
MAKE FINAL CONNECTION TO OWNER PROVIDED
SINGLE PORT EV CHARGING STATION EQUIPMENT.
VERIFY EXACT REQUIREMENTS WITH
MANUFACTURER'S INSTRUCTIONS.
MOUNT RECEPTACLE ON BOLLARD 18" AFG.
COORDINATE EXACT LOCATION AND REQUIREMENTS
WITH G.C.
#
1
2
3
4
5
6
JWP/GFI
A
46
A
43
4
E1.1
B
4
E1.1
A
4
E1.1
B
2
E1.1(TYP)
3
E1.1(TYP)
4
E1.1
A
4
E1.1
C
1
1
2
4
56
3
3
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E1.1
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE
EXACT LOCATION WITH ELEVATOR EQUIPMENT.
2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR
CONTINUOUS OPERATION.
3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.
4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.
5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE
CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S
COMMISSIONING.
6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.
7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.
8. nLIGHT POWER SUPPLY, MODEL NPS 80.
9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.
10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.
# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
PPPP PPPPP P P PPPE E EEE
J E
P
P
PPPPPP
P
P
P
P
P
P
P
P
P P
P
K
J
J
JJ
J J
J
J J
J
J J
JJ
J
J J
J J
J J
J
J
JJ
JJ
J J
J
nL,a
U
EE
J
JJ
JJ J JJ
J
J
J
J
JJ
J
J J
J
MS
MS
MS
MS
U
K
E
OS
OS
P
P
K
K
K
T
P
Y
6'-6" AFF
E1 Y6'-6" AFF
P
P
P
P
P
E1
L18'-0" AFF
L18'-0" AFF
J
XE
XE
XE
OS
OS
OS
OS
XE
XE
EE
E
XE
E
E1
J
J
PP P PP
EF-2
EF-2
EF-2
MR MR
MR MR
MR MR MR
os
os
PP
J
JJ
J
J
J
E
K
XE
E
E
A
5
A
3
A
1
J
D
1
P
os
os
nL,b
nL,a
nL,b
a
a
a
a
a
a
a
a
nL
b
b
b
b
b
b
b
b b
b
b
b
b
b
b
b
b
b
bb
bb
anL
bPS
nL
nL
nL
A
2
A
2
X
X
TO 2ND
FLOOR
TO 2ND
FLOOR
1
2
TC
C
P
4
4
D
7
D
9
2
E4.1
1
E4.1
1
E4.1
1
E4.14
E4.1
AMDP
DD
3
D
5
6
7
7
8
9
9
A
7
MA
TC
HLIN
EM
AT
CH
LIN
E
COORDINATE ROUTING OF CONDUIT ABOVE
FIRST FLOOR COMMON AREA CEILINGS WITH
LOCATIONS OF PRE-MANUFACTURED HOLES IN
BEAMS. SEE STRUCTURAL AND ARCHITECTURAL
DRAWINGS FOR MORE INFORMATION. FINAL
ROUTING SHALL BE COORDINATED WITH G.C.
AND OTHER TRADES PRIOR TO INSTALLATION.
XEPPPPPPE
E
L18'-0" AFF
J J
A
2
X
TO 2ND
FLOOR
L18'-0" AFF
K
K
K
K
E
E
3
E4.1
MA
TC
HLIN
EM
AT
CH
LIN
E
1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.1
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING PLAN2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
J
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J J J
D
L318'-0" AFG
L318'-0" AFG
L318'-0" AFG
L318'-0" AFG
L318'-0" AFG
A
4
L3
18'-0" AFG
os
PP
os
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P
P P
P
P
P
P
K
OS
U
U
OS
OS
P
PK
K
OS
J
J
J
J
J
J J
P PP P P P P P P P PPP P P
JJ
JJ
J
J
J
J
P P PP P PP P PP
J
J
J
J
J
J
J
D
L318'-0" AFG
EF-2
EF-2
EF-2
EF-3
P
PP PP
os
B
1
FROM 1ST
FLOOR
TO 3RD
FLOOR
XE
E
E
XE
X
E
X
XE
E
E
E
E
FROM 1ST
FLOOR
X
B
3
B
5
X
E
J J
FROM 1ST
FLOOR
TO 3RD
FLOOR
E
TO 3RD
FLOOR
JJJ
JJJ
JJJ
J
J
3,D
3,D
os
2
3
3
3
3
3 3
1
E4.1
1
E4.1
1
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
B
1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE
EXACT LOCATION WITH ELEVATOR EQUIPMENT.
2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR
CONTINUOUS OPERATION.
3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.
4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.
5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE
CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S
COMMISSIONING.
6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.
7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.
8. nLIGHT POWER SUPPLY, MODEL NPS 80.
9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.
10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.
# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
1/8" = 1'-0"
SECOND FLOOR LIGHTING PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
P
P
P
P
P
P
P
P
P
P
P
P
P P P P P
P P
P
P
P
P
K
OS
U
U
OS
OS
P
PK
K
OS
J
J
J
J
J
J
J J
3,D
D
P PP P P P P P P P PPP P P
JJ
JJ
J
J
J
J
P P PP P PP P PP
J
J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
J
3,D
D
J
J
J
EF-2
EF-2
EF-2
EF-3
P
L2
18'-0
" A
FG
L218'-0" AFG
L218'-0" AFG
L218'-0" AFG
L218'-0" AFG
L218'-0" AFG
os
PP PP
os
C
1
FROM 2ND
FLOOR
XE
E
E
XE
X
E
X
XE
E
E
E
E
FROM 2ND
FLOOR
X
C
3
C
5
X
E
J J
FROM 2ND
FLOOR
E
os
2
3 3 3 3 3
1
E4.1
1
E4.11
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
C
1
E4.1
L2
18'-0
" A
FG
A
6
1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE
EXACT LOCATION WITH ELEVATOR EQUIPMENT.
2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR
CONTINUOUS OPERATION.
3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.
4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.
5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE
CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S
COMMISSIONING.
6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.
7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.
8. nLIGHT POWER SUPPLY, MODEL NPS 80.
9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.
10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.
# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
1/8" = 1'-0"
THIRD FLOOR LIGHTING PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.3
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT
SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH
EQUIPMENT PROVIDED.
2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A
DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR
ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF
BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH
CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND
REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE
FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.
3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE
WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V
CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY
TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR
ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.
COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE
EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR
EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO
ELEVATOR CONTROLLER.
4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT
LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.
5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER
CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL
STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.
COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.
6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP
SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.
MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.
7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.
MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.
8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')
THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE
CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .
9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.
MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC
RACEWAY.
10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.
PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT
GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN
ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH
FIRE SPRINKLER SYSTEM INSTALLER.
11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR
POWER TO FIRE PUMP AND ACCESSORIES.
12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.
# PLAN NOTES BY SYMBOL
A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
A
6-20
6-20
6-20
6-20
6-20
6-20
60"
CT
2
E4.1
1
E4.1
1
E4.1
1
E4.14
E4.1
MDP
CTCT/GFICT/GFICT/GFICT/GFICT
CTCT
CT
A
41
A
39
A
37
CT/GFI
CT/GFI
GFI
CTCT
CT
WP/GFI
GFI
GFI
GFI
A
27
A
21A
23
A
25
A
29
A
35
A
33
A
11
A
9
PTAC-07
PTAC-07
PTAC-07
PTAC-07
PTAC-07
PTAC-15
BC-1
HP-1
PTAC-15
PTAC-15
PTAC-07
PTAC-07
HP-3
A
19
A
17
A
15
A
13
6-20
6-20
6-20
6-20
A
18
A
22
A
30
D
31
D
23
D
27D
10
D
12
D
14
A
31
1(TYP)
1(TYP)
A
26
1
(TYP)
A
19
A
15 D
11
D
4
D
2
5
MDP
D
6
D
18
3
2
D
8
4
5
D
D
20
D
16
7
A
38
A
42
SDS
TRANSOCKET
WEST METER CENTER
A
34
WP/GFI
HW
H
HWP
A
45
A
50
8
MA
TC
HLIN
EM
AT
CH
LIN
E
J
D
5
3
E4.1
BC-2
WP/GFI
m
D
35
6
EAST METER CENTER
FIRE PUMP METER
EWH-2
EWH-1
9
D
30
D
24
J
10
D
34
D
22
D
26
D
28
11
MA
TC
HLIN
EM
AT
CH
LIN
E
1/8" = 1'-0"
PARTIAL FIRST FLOOR POWER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.4
RE:
2/E2.4
RE:
2/E2.4
1/8" = 1'-0"
PARTIAL FIRST FLOOR POWER PLAN2
RE:
1/E2.4
RE:1
/E2
.4
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT
SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH
EQUIPMENT PROVIDED.
2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A
DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR
ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF
BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH
CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND
REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE
FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.
3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE
WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V
CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY
TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR
ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.
COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE
EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR
EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO
ELEVATOR CONTROLLER.
4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT
LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.
5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER
CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL
STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.
COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.
6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP
SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.
MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.
7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.
MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.
8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')
THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE
CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .
9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.
MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC
RACEWAY.
10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.
PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT
GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN
ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH
FIRE SPRINKLER SYSTEM INSTALLER.
11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR
POWER TO FIRE PUMP AND ACCESSORIES.
12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.
# PLAN NOTES BY SYMBOL
A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
72"
72"
72"
84"
84"
GFI
CT/GFI
CT/GFI
GFI
B
6-20
6-20
6-20
1
E4.1
1
E4.1
1
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
B
9
B
7
B
11
B
23
B
25
B
19B
17
B
21
B
27
B
31
PTAC-07
PTAC-07
PTAC-07
BC-4
BC-3
PTAC-07
6-20
B
15
B
13
HP-4 HP-5
HP-2
B
2
m6 B
18B
29
1
(TYP)
B
14
B
10
m
B
22
B
30
B
34 B
B
6
WP/GFI
7 7
7
WP/GFI
HWH-AHWP
B
42
B
38
8
6
1
(TYP)
1/8" = 1'-0"
SECOND FLOOR POWER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.5
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT
SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH
EQUIPMENT PROVIDED.
2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A
DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR
ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF
BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH
CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND
REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE
FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.
3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE
WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V
CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY
TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR
ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.
COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE
EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR
EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO
ELEVATOR CONTROLLER.
4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT
LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.
5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER
CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL
STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.
COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.
6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP
SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.
MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.
7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.
MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.
8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')
THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE
CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .
9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.
MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC
RACEWAY.
10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.
PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT
GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN
ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH
FIRE SPRINKLER SYSTEM INSTALLER.
11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR
POWER TO FIRE PUMP AND ACCESSORIES.
12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.
# PLAN NOTES BY SYMBOL
A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS
RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.
B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE
PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .
C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN
UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.
D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,
ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED
OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT
46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH
NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS
FOR LOCATIONS OF DEVICES.
E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE
THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND
MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS
WHERE POSSIBLE.
F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL
CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING
DRAWINGS PRIOR TO FINAL PLACEMENT.
G. DEFINITION OF TERMS
* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.
* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.
* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND
CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,
CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.
* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL
GENERAL ELECTRICAL NOTES
C
72"
84"
84"
CT/GFI
CT/GFIGFI
6-20
6-20
6-20
6-20
1
E4.1
1
E4.11
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
C
11
C
15
C
13
C
9
C
7
C
25
C
23
C
19
C
17
C
21
PTAC-15
PTAC-07
PTAC-09
PTAC-12
PTAC-07
BC-5
GFI
C
10
C
18
C
14
C
2 1
(TYP)
6-20
C
6
1
(TYP)
m
C
22
6
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI
GFI
GFI
GFI
C
27 C
29
12
12
12
12
12
12
12
12
12
12
12
1/8" = 1'-0"
THIRD FLOOR POWER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.6
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.
2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.
3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.
4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,
AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.
SEE DETAIL 3:E6.1.
5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC
DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.
6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE
SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE
REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES
IN SERVICE PIPING WITH CIVIL ENGINEER.
7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS
NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING
GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT
BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER
PRIOR TO INSTALLATION OF ANY EQUIPMENT.
8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED
COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL
BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.
9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR
CONTINUATION.
10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER
LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.
11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.
12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S
NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE
APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND
UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT
UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.
13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING
OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.
14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE
WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.
SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#
ALL AUDIBLE NOTIFICATION DEVICES IN
LIVING UNITS SHALL COMPLY WITH LOW
FREQUENCY SIGNALING REQUIREMENTS OF
NFPA 72 SECTION 18.4.5.3
A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS
INDICATED ON SHEET E4.1.
B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x
2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO
MECHANICAL ROOM 107.
C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR
FITTING TO PROTECT CABLING FROM DAMAGE.
D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM
OUTLETS NOT ACTIVATED BY OWNER.
E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.
F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT
AND TESTING SHALL BE PROVIDED BY OWNER.
TELECOMMUNICATIONS GENERAL NOTES
FA
A
75cd
75cd
P
15cd
15cd15cd
P
P
P
15cd
15cd
15cd
75cd
30cd 15cd15cd
15cd
tv
60"
60"
CT
GB
FA
CP
177cd 75cd
15cd
177cd
75cd
11
11
12
12
1
11
11
2
4
3
8
7
2
E4.1
1
E4.1
1
E4.1
1
E4.14
E4.1
R
R
R
AM
R
AM
MA
TC
HLIN
EM
AT
CH
LIN
E
15cd
AM
9
75cd
15cd
15cd
R
5
COORDINATE ROUTING OF CONDUIT ABOVE
FIRST FLOOR COMMON AREA CEILINGS WITH
LOCATIONS OF PRE-MANUFACTURED HOLES IN
BEAMS. SEE STRUCTURAL AND ARCHITECTURAL
DRAWINGS FOR MORE INFORMATION. FINAL
ROUTING SHALL BE COORDINATED WITH G.C.
AND OTHER TRADES PRIOR TO INSTALLATION.
P
15cd
177cd
11
63
E4.1
MA
TC
HLIN
EM
AT
CH
LIN
E
15cd
AM
13
15cd
1/8" = 1'-0"
PARTIAL FIRST FLOOR SPECIAL SYSTEMS PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.7
1/8" = 1'-0"
PARTIAL FIRST FLOOR SPECIAL SYSTEMS PLAN2
RE:
2/E2.7
RE:
2/E2.7
RE:
1/E2.7
RE:
1/E2.7
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.
2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.
3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.
4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,
AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.
SEE DETAIL 3:E6.1.
5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC
DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.
6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE
SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE
REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES
IN SERVICE PIPING WITH CIVIL ENGINEER.
7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS
NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING
GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT
BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER
PRIOR TO INSTALLATION OF ANY EQUIPMENT.
8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED
COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL
BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.
9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR
CONTINUATION.
10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER
LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.
11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.
12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S
NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE
APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND
UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT
UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.
13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING
OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.
14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE
WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.
SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#
ALL AUDIBLE NOTIFICATION DEVICES IN
LIVING UNITS SHALL COMPLY WITH LOW
FREQUENCY SIGNALING REQUIREMENTS OF
NFPA 72 SECTION 18.4.5.3
A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS
INDICATED ON SHEET E4.1.
B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x
2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO
MECHANICAL ROOM 107.
C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR
FITTING TO PROTECT CABLING FROM DAMAGE.
D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM
OUTLETS NOT ACTIVATED BY OWNER.
E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.
F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT
AND TESTING SHALL BE PROVIDED BY OWNER.
TELECOMMUNICATIONS GENERAL NOTES
P P
P
15cd 15cd15cd
15cd
15cd
15cd
15cd
30cd
84"
tv84" 84"
tv84"
75cd
72"
tv72"
15cd
15cd
72"
tv
72"
72"tv
72"
177cd75cd
15cd
R
5
11
11
1
E4.1
1
E4.1
1
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
AM
12
1
75cd
15cd 15cd
14
1/8" = 1'-0"
SECOND FLOOR SPECIAL SYSTEMS PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.8
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.
2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.
3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.
4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,
AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.
SEE DETAIL 3:E6.1.
5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC
DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.
6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE
SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE
REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES
IN SERVICE PIPING WITH CIVIL ENGINEER.
7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS
NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING
GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT
BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER
PRIOR TO INSTALLATION OF ANY EQUIPMENT.
8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED
COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL
BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.
9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR
CONTINUATION.
10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER
LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.
11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.
12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S
NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE
APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND
UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT
UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.
13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING
OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.
14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE
WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.
SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#
ALL AUDIBLE NOTIFICATION DEVICES IN
LIVING UNITS SHALL COMPLY WITH LOW
FREQUENCY SIGNALING REQUIREMENTS OF
NFPA 72 SECTION 18.4.5.3
A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS
INDICATED ON SHEET E4.1.
B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x
2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO
MECHANICAL ROOM 107.
C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR
FITTING TO PROTECT CABLING FROM DAMAGE.
D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM
OUTLETS NOT ACTIVATED BY OWNER.
E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.
F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT
AND TESTING SHALL BE PROVIDED BY OWNER.
TELECOMMUNICATIONS GENERAL NOTES
P P
P
15cd 15cd15cd
15cd
15cd
15cd
15cd
75cd
84"
tv84"
84"
tv84"75cd
72"
tv72"
15cd
15cd
177cd75cd
15cd
R
11
11
10
1
E4.1
1
E4.11
E4.1
1
E4.1
3
E4.1
3
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
1
E4.1
2
E4.1
1
E4.11
E4.1
1
E4.1
1
E4.1
1
E4.1
1
AM
12
15cd 15cd
14
5
1/8" = 1'-0"
THIRD FLOOR SPECIAL SYSTEMS PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E2.9
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
tv
14-50
48"CT
CT
CT
CT
CT
CT/GFI
14-30
b a
D
CT
tv
B1
tv
tv
G
D D
D D
F
b b
bC
CC
D
H
aa
D
DD
a D
2
HWH
a
14-30
3
tv
A6
tv
tv
tv
G
3
CT/GFI
F
F
D
H
D D
2
HWH
tv
14-50
48"CT
CT
CT
CT
CT
b
CT
D
a
tv
a a
a
D D
D D
b b
bC
CC
D
DD
a D
1. PROVIDE NEMA6-20R RECEPTACLE FOR CORD AND PLUG CONNECTION OF PTAC.
VERIFY RECEPTACLE CONFIGURATION WITH PTAC SUPPLIED BY MECHANICAL
CONTRACTOR. INSTALL RECEPTACLE CONCEALED IN UNIT SUB-BASE.
2. CONNECT EXHAUST FAN/LIGHT PROVIDED BY MECHANICAL CONTRACTOR.
3. SWITCH CLOSEST TO THE DOOR SHALL CONTROL ALL LIGHTS IN BATHROOM, AND
THE OTHER SWITCH SHALL CONTROL THE EXHAUST FAN.
4. CEILING MOUNTED SMOKE ALARM IN APARTMENTS TO BE 120VAC WITH 9V BATTERY
BACKUP, INTERCONNECTED TO OTHERS IN SAME APARTMENT. DEVICE SHALL HAVE
CARBON MONOXIDE DETECTOR AND PHOTOELECTRIC TYPE SMOKE DETECTOR WITH
SOUNDER HORN HAVING AN 85dB OUTPUT AT 10', SHALL HAVE A SINGLE BUTTON
FOR TEST/SILENCE AND LED INDICATOR LIGHTS, AND SHALL BE UL 217 LISTED. BRK
#SC7010B OR EQUAL.
5. COORDINATE FINAL LOCATIONS OF ALL CATV AND PHONE OUTLETS WITH OWNER.
SEE 5:E6.1 FOR OUTLET DETAILS.
6. TELECOM DISTRIBUTION DEVICE APPROXIMATELY 4'-0" AFF. SEE DETAIL 5:E6.1.
7. SWITCHED RECEPTACLE BELOW COUNTER FOR GARBAGE DISPOSAL.
8. PROVIDE 120V CONNECTION TO RANGE HOOD/MICROWAVE. STANDARD AND
ADAPTABLE UNITS WILL HAVE MICROWAVE ABOVE RANGE. ACCESSIBLE UNITS WILL
HAVE RANGE HOOD. COORDINATE EXACT ELECTRICAL ROUGH-IN REQUIREMENTS
WITH EQUIPMENT PROVIDED. IF EQUIPMENT IS CORD AND PLUG, PROVIDE
RECEPTACLE INSIDE CABINET ABOVE RANGE.
9. PROVIDE RECEPTACLE BELOW COUNTER FOR CORD AND PLUG CONNECTION OF
DISHWASHER. PROVIDE CORD AND GROUNDING PLUG AS REQUIRED.
10. MOUNT RECEPTACLE IN FACE OF CABINET 6" BELOW COUNTER TOP.
11. PROVIDE PRESET SLIDE DIMMER COMPATIBLE WITH ASSOCIATED LIGHT FIXTURES.
12. SWITCH BOTTOM HALF OF RECEPTACLE AND WIRE TOP HALF TO UNSWITCHED
CIRCUIT.
13. PROVIDE DOOR ANNUNCIATOR SYSTEM A/V HORN/STROBE DEVICE AND LOW
VOLTAGE TRANSFORMER AT ALL ACCESSIBLE APARTMENTS AND ALSO AT
APARTMENTS DESIGNATED FOR HEARING-IMPAIRED GUESTS. REFER TO ARCH
DRAWINGS FOR APPLICABLE ROOMS. INSTALL HORN/STROBE APPLIANCE AT 80" AFF
PER ADA. INSTALL TRANSFORMER IN DOUBLE GANG JUNCTION BOX ABOVE
HORN/STROBE WITH BLANK COVER PLATE AND PROVIDE LOW VOLTAGE CONTROL
WIRING. REFER TO DETAIL 2, SHEET E6.1. PROVIDE ENGRAVED SIGN AT THE
HORN/STROBE DEVICE TO READ "DOOR".
14. PROVIDE PUSH BUTTON AT 48" AFF FOR ANNUNCIATOR SYSTEM AT ALL ACCESSIBLE
APARTMENTS AND ALSO AT APARTMENTS DESIGNATED FOR HEARING-IMPAIRED.
REFER TO ARCH DRAWINGS FOR APPLICABLE ROOMS. REFER TO DETAIL 2, SHEET
E6.1.
15. PROVIDE SWITCH IN ACCESSIBLE UNITS FOR CONTROL OF RANGE HOOD.
16. IN ACCESSIBLE UNITS, INSTALL COUNTERTOP RECEPTACLES A MINIMUM 36" AWAY
FROM CORNER PER FAIR HOUSING ACT DESIGN MANUAL CHAPTER 5 'SIDE REACH
OVER AN OBSTRUCTION' REQUIREMENTS. WHERE AN OBSTRUCTION PREVENTS 36"
DISTANCE REQUIREMENT, INSTALL RECEPTACLE AS FAR FROM CORNER AS
POSSIBLE.PROVIDE ADDITIONAL OUTLETS WITHIN 36" OF CORNER TO ENSURE
COMPLIANCE WITH NEC SPACING REQUIREMENTS.
ELECTRICAL PLAN NOTES BY SYMBOL#
14-30
3
tv
A5
tv
tv
tv
G
3
CT/GFI
F
F
D
H
D D
2
HWH
tv
14-50
48"
CT
CT
b
CT
D
a
tv
aa
a
D D
D D
b b
bC
CC
D
DD
a D
1 1
1
tv
14-50
48"CT
CT
CT
CT
CT
14-30
b a
D
CT
tv
B13
tv
tv
D D
D D
F
b b
bC
CC
D
H
aa
D
DD
a D
2
HWH
a
1
1
2
2
3
3
4
4
4
4
4
TR
HS
13
14
5
5
5
5
5
5
5
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
12
12
12
12
12
TRHS
13
TRHS
14
1 1
1
2
34
4
4
5
5
5
5
5
6
7
8
10
11
12
12
12
15
1
1
4
4
5
5
5
5
6
7
8
10
11
12
12
12
12
13
15
A5
3A5
1
A5
5
A5
7A5
9
A5
11
A5
1312
A5
15
A5
17
A5
19
A5
21
A5
2
A5
4
A5
6
A5
10
A5
14
A5
22
A5
18
A5
26
A6
3
A6
1
A6
5
A6
7
A6
9
A6
11
A6
13
A6
15
A6
17
A6
19
A6
21
A6
2
A6
4
A6
6
A6
10
A6
14
A6
22A6
18
A6
26
12
B13
3B13
1
B13
5
B13
7B13
9
B13
11
B13
13
B13
2
B13
4
B13
10
B13
14
B13
22
B13
17
B13
19
B13
6
B13
18
B1
3
B1
1
B1
5
B1
7
B1
9
B1
11
B1
13
B1
15
B1
2
B1
4
B1
10
B1
14
B1
22
B1
17
B1
19
B1
6
B1
18
GENERAL NOTE:
PROVIDE TAMPER PROOF RECEPTACLES IN DWELLING UNITS PER NEC REQUIREMENTS.
CT/GFI
G
2
3
B1
15
1. CIRCUIT SHALL BE PROTECTED BY AFCI TYPE BREAKER.
2. CIRCUIT SHALL BE PROTECTED BY COMBINATION AFCI/GFCI TYPE BREAKER.
PANEL SCHEDULE NOTES BY SYMBOL#
2
2
2
2
2
2
1
1
1
1
1
2
1. CIRCUIT SHALL BE PROTECTED BY AFCI TYPE BREAKER.
2. CIRCUIT SHALL BE PROTECTED BY COMBINATION AFCI/GFCI TYPE BREAKER.
PANEL SCHEDULE NOTES BY SYMBOL#
2
2
2
2
2
2
1
1
1
1
2
36"
MIN
.
36" MIN.
16
9
CT
CT
CT
36"
MIN
.
36" MIN.
16
9
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
1/4" = 1'-0"
2 BEDROOM ELECTRICAL PLAN3
1/4" = 1'-0"
1 BEDROOM ACCESSIBLE ELECTRICAL PLAN2
1/4" = 1'-0"
1 BEDROOM ELECTRICAL PLAN1
1/4" = 1'-0"
2 BEDROOM ACCESSIBLE ELECTRICAL PLAN4
REFER TO SPECIAL SYSTEMS PLANS ON
SHEETS E2.7-E2.9 FOR SMOKE DETECTORS
TO BE INSTALLED IN ALL ACCESSIBLE AND
HEARING IMPAIRED UNITS.
E4.1
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
EXTERIOR LIGHTING CONTROL DIAGRAM
No Scale1
ON
AUTO
OFF
A:12
120V
120V PHOTOCELL WITH 1/2" PIPE NIPPLEAND SWIVEL MOUNT. INTERMATIC #K4236COR EQUAL, SEE 1:E1.1 FOR LOCATION.
TO PARKING LOT LIGHTS
CIRCUIT 'A:37'L N
C
CONTACTOR 'C'JAN 113
PROVIDE LIGHTING CONTACTORS WITH QUANTITY OF POLES SHOWN,120V COIL,INTEGRAL 3-POSITION MANUAL SELECTOR SWITCH, AND NEMA 1 ENCLOSURE.
A:14
A:16 TO MONUMENT LIGHTS
PIT
ELEVATOR
LOGICCONTROLLER
SMOKE DETECTOR AND HEAT DETECTOR IN
ELEVATOR EQUIPMENT ROOM
FIRE ALARM
CONTROL PANEL
ELEVATORPOWER
ADDRESSABLE RELAY FOR SHUNT TRIP
OF ELEVATOR MAIN LINE POWER.LABEL "ELEVATOR SHUT-DOWN RELAY".WIRE TO N.O. CONTACTS.
NOTE: HEAT DETECTORS SHALL BE SENSITIVE, 135° FFIXED TEMPERATURE, WITH A LISTED SPACING OF 40'
ON CENTER OR GREATER. LOCATE HEAT DETECTORSWITHIN 24" OF SPRINKLER HEADS.
HEAT DETECTOR INELEVATOR PIT
FACP
LOBBY SMOKE
DETECTOR
1ST FLOOR
SMOKE DETECTOR AND HEATDETECTOR AT TOP OF ELEVATOR
HOISTWAY
ELEVATOR
EQUIPMENT
ROOM
ELEVATOR SEQUENCE OF OPERATION: (DURING SMOKE/HEAT ALARM)
1. UPON SENSING SMOKE FROM ONE OR MORE LOBBY, ELEVATOR HOISTWAY OR ELEVATOR EQUIPMENT ROOM, THE SMOKE DETECTOR SHALL
SIGNAL THE FACP, WHICH WILL FORWARD THE SIGNAL TO THE ELEVATOR LOGIC CONTROLLER TO RECALL ELEVATOR CAB TO THEDESIGNATED MAIN FLOOR. IF DESIGNATED FLOOR'S LOBBY SMOKE DETECTOR SENSES SMOKE AT THAT FLOOR, THE ELEVATOR CONTROLLERWILL SEND THE ELEVATOR CAB TO THE NEXT FLOOR CLEAR OF SMOKE. ONCE THE ELEVATOR CAB HAS REACHED THE DESIGNATED FLOOR,
THE ELEVATOR CAB DOORS WILL OPEN AND THE CONTROLLER WILL LOCK THE ELEVATOR CAB AT THAT FLOOR, DISABLING THE ELEVATORCAB CONTROLS, UNLESS A FIREMAN'S KEY IS USED TO OVERRIDE AUTOMATIC CONTROLS.
2. ALL SMOKE DETECTORS (LOBBIES, HOISTWAY, MACHINE ROOM) SHALL TRANSMIT A SEPARATE AND DISTINCT VISIBLE ANNUNCIATION AT
THE FACP AND ANNUNCIATOR PANEL.
3. HEAT DETECTORS IN THE ELEVATOR HOISTWAY AND ELEVATOR EQUIPMENT ROOM WILL SEND A SIGNAL TO THE SHUNT-TRIP SWITCH
POWERING THE ELEVATOR SO AS TO SHUT DOWN POWER TO THAT CIRCUIT. (THIS IS A NON-AUTO RESET SWITCH). WHEN THE SPRINKLERHEAD HAS REACHED ITS CRITICAL TEMPERATURE OF 165° F., THE HEAD WILL BEGIN DISCHARGE OF WATER.
ELEVATOR POWER MODULE WITHSHUNT-TRIP COIL AND INTERNAL FA
SHUNT TRIP VOLTAGE MONITORINGRELAY AS NOTED ON PLANS
LOBBY SMOKEDETECTOR
No Scale
ELEVATOR INTERLOCK WITH FIRE ALARM3
2ND FLOOR
ELEVATORHOISTWAY
AM RR R R
ADDRESSABLE RELAYS FOR ELEVATOR PRIMARYRECALL, ALTERNATE LEVEL RECALL, AND
FIREMAN'S HAT. LABEL WITH APPROPRIATE NAME.
ADDRESSABLE MONITOR MODULE
FOR MONITORING OF SHUNT TRIP
VOLTAGE
FIRE ALARM SIGNALING
LINE CIRCUIT (TYP)
TELECOM GROUNDING & BONDING DIAGRAMNo Scale
4
NOTES:
TGB1
BOND TOBUILDING
STEEL
1. ALL GROUNDING / BONDING
CONDUCTORS SHALL BE #4 AWG
INSULATED STRANDED COPPER. INSTALL
IN 3/4" CONDUIT WHERE EXPOSED AND
WHERE SUBJECT TO PHYSICAL DAMAGE.
2. ALL CONNECTIONS TO GROUND BAR
SHALL BE MADE USING COMPRESSION
TYPE LUGS (MECHANICAL LUGS ARE NOT
ACCEPTABLE).
MECH 107
D
#4 CU#4 CU
BOND TO
EQUIPMENTGROUND BUS
5APARTMENT TELECOM WIRING SCHEMATIC
NO SCALE
PHONE WALL OUTLET:
CAT 5e 8-POSITIONMODULAR CONNECTOR,WALL PLATE AND
TELECOM BOX.
RG-6 COAXIAL CABLEFROM DISTRIBUTIONDEVICE TO WALL OUTLET.
CATV WALL OUTLET: TYPE FCONNECTOR, WALL PLATE
AND TELECOM BOX.CAT 5e, 4PR UTP CABLE TO
SERVICE PROVIDER EQUIPMENT
ON MAIN BUILDING TELEPHONETERMINAL BOARD INMECHANICAL ROOM 119.
RG-6 COAXIAL CABLE TO SERVICEPROVIDER EQUIPMENT. SEE SPECIAL
SYSTEMS PLANS FOR LOCATION.
TELECOM DISTRIBUTION DEVICE:PRE-CONFIGURED 1X9 BRIDGEDTELEPHONE BOARD AND 6-WAY
VIDEO SPLITTER, LEVITON MODEL47603-1G6 OR SIMILAR. INSTALLIN 14" FLUSH MOUNTED
ENCLOSURE WITH COVER, MODEL47605-140 OR SIMILAR.
CAT 5e, 4PR UTP CABLE
FROM DISTRIBUTIONDEVICE TO WALL OUTLET
120 VAC 24 VAC
DOOR ALARM BUZZER SYSTEM NOTES
1. PROVIDE DOOR ANNUNCIATOR SYSTEM COMPLETE WITH PUSH BUTTON, HORN/STROBE(S), POWER SUPPLIES
AND ALL WIRING REQUIRED. HORN/STROBE SHALL ACTIVATE WHEN PUSH BUTTON IS DEPRESSED.
2. HORN/STROBE SHALL OPERATE AT 24VAC, HAVE A CLEAR LENS WITH 50cd STROBE AND HORN WITH 82dBAT 10', UL 1638 LISTED, EDWARDS #6536-G5. FLUSH MOUNT IN WALL AT 6'-8" AFF.
3. PUSH BUTTON SHALL BE WHITE WITH CHROME RIM, NON-ILLUMINATED, WITH N.O. MOMENTARYCONTACTS, RATED FOR 0.67 AMPS AT 24VAC, EDWARDS #620. PROVIDE WITH STAINLESS STEEL COVERPLATE, EDWARDS #147-10. MOUNT AT 48" AFF.
4. POWER SUPPLY SHALL BE A LOW VOLTAGE CLASS 2 TRANSFORMER WITH 120VAC PRIMARY AND 24VACSECONDARY, 20VA, EDWARDS #598. FLUSH MOUNT IN 2-GANG WALL BOX WITH BLANK COVER PLATE,
DIRECTLY ABOVE HORN/STROBE.
5. LOW VOLTAGE CLASS 2 CABLING SHALL BE MINIMUM 18 AWG UNSHIELDED.
POWER SUPPLY
S H
L
N
HS
PUSH BUTTON
HORN/STROBE
APARTMENT DOORBELL WIRING SCHEMATIC
No Scale2
A:10
A:8TO DRIVEWAY LIGHTS
A:6
A:4 TO BUILDING MOUNTED LIGHTS
TO BUILDING MOUNTED LIGHTS
LIGHT FIXTURE SCHEDULE
MARK MANUFACTURER MODEL NUMBERLAMP / LED DATA
BALLAST/DRIVER MOUNTING FINISH DESCRIPTION NOTESWATT/LUMENS COLOR
C KICHLER 42517OZ 200 3000°K INTEGRAL DRIVERPENDANT AT 6'-6"AFF TO BOTTOM
OLD BRONZE 3"Ø x 12" HIGH DECORATIVE MINI-PENDANT .
D HALO SMD6R-6-930-WH9.6W LED
750 LUMENS3000°K INTEGRAL DRIVER SURFACE BRONZE 6" ROUND SURFACE MOUNT DOWNLIGHT .
E SURE-LITES SEL25SD --- WHITE N/A WALL AT 7'-6" AFF WHITE TWIN HEAD POLYCARBONATE EMERGENCY LIGHT 1,2
E1 MULE EOE-BB-10L2-B-DG-LT(2) 10W
LED--- N/A
ON WALL ABOVEDOOR
BRONZEDIE-CAST ALUMINUM EMERGENCY LIGHT WITH POLYCARBONATE
LENS, INTEGRAL BATTERY1,2,3,6
F SEAGULL 15040EN-782(2) 10W
LED3000°K INTEGRAL DRIVER SURFACE BRONZE 52" DIAMETER CEILING FAN WITH LED LIGHT KIT
G SEAGULL 4423003EN3-710(3) 9.5W
LED3000°K INTEGRAL DRIVER WALL AT 7'-0" BURNT SIENNA 3-LAMP LED VANITY LIGHT .
H SEAGULL 5913291S-1538W LED
3,500 LUMENS3000°K INTEGRAL DRIVER SURFACE WHITE 4' LINEAR FLUORESCENT WITH PRISMATIC ACRYLIC LENS .
J LITHONIA FMML-13-830-DDBT28W LED
1,900 LUMENS3000°K INTEGRAL DRIVER SURFACE WHITE 13" ROUND LED SURFACE MOUNT .
K METALUX 4SNLED-LD4-56SL-LW-UNV-L835-CD151W LED
5,600 LUMENS3500°K
0-10V DIMMING
(10%-100%)SURFACE WHITE 4' LED STRIP WITH FROSTED LENS, WIDE DISTRIBUTION .
L1 LITHONIA WSR-LED-P1-40K-SR4-MVOLT-E10WH20W LED
2,180 LUMENS4000°K STANDARD WALL BLACK
EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION ANDBATTERY BACK-UP
6
L2 LITHONIA WSR-LED-P2-40K-SR4-MVOLT29W LED
3,050 LUMENS4000°K STANDARD WALL BLACK EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION 6
L3 LITHONIA WSR-LED-P3-40K-SR4-MVOLT40W LED
4,300 LUMENS4000°K STANDARD WALL BLACK EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION 6
MR METALUX 24FP4735C41W LED
4,700 LUMEN3500°K 0-10V DIMMING LAY-IN WHITE 2x4 LED FLAT PANEL .
MS METALUX 24FP4735C41W LED
4,700 LUMEN3500°K 0-10V DIMMING SURFACE WHITE 2x4 LED FLAT PANEL .
P HALO COMMERCIAL PD615ED010-PDM6A830-64VH17.1W LED
1,500 LUMENS3000°K 0-10V DIMMING RECESSED
SEMI-SPECULARCLEAR
6" ROUND SHALLOW LENS DOWNLIGHT WITH SELF-FLANGED
ALUMINUM WIDE BEAM REFLECTOR; 80 CRI5
R1 LITHONIA DSX0-LED-P1-40K-T2S-MVOLT-HS-DDBXD38 W LED
4,300 LUMENS4000°K
FIXED OUTPUTDRIVER
20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE II
DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8
R2 LITHONIA DSX0-LED-P3-40K-T2M-MVOLT-HS-DDBXD71 W LED
7,800 LUMENS4000°K
FIXED OUTPUTDRIVER
20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE II
DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8
R3 LITHONIA DSX0-LED-P3-40K-T4M-MVOLT-HS-DDBXD71W LED
7,700 LUMENS4000°K
FIXED OUTPUTDRIVER
20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE IV
DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8
R4 LITHONIA DSX0-LED-P3-40K-T5W-MVOLT-DDBXD71W LED
8,200 LUMENS4000°K
FIXED OUTPUTDRIVER
20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE V
DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8
S ACCLAIM DFB-111-AKEU50W LED
2,455 LUMENS4000°K
FIXED OUTPUTDRIVER
GRADE BLACK IP-66 RATED, GRADE MOUNTED LED FLOOD LIGHT 7
T WILLIAMS 96-4-L40/830-HIAFR-WET/1-DRV-UNV30W LED
4,000 LUMENS3000°K
FIXED OUTPUTDRIVER
SURFACE WHITE4' FULLY ENCLOSED AND GASKETED INDUSTRIAL FIXTURE WITH
FROSTED, RIBBED, IMPACT-RESISTANT ACRYLIC LENS.
U WILLIAMS WMA-3-L46/835-AF-DRV-UNV57W LED
4,600 LUMEN3500°K INTEGRAL DRIVER
WALL AT 7'-0" AFF
(TO BOTTOM)WHITE 3' ARCHITECTURAL WALL BRACKET UP/DOWN LIGHT .
X1 MULE MXBRU-SD --- RED N/A CEILING/WALL/END WHITE SINGLE FACE POLYCARBONATE LED EXIT 1,2
X2 MULE MXBRU-SD --- RED N/A CEILING/END WHITE DOUBLE FACED POLYCARBONATE LED EXIT 1,2
XE MULE SQC-LED-1-R-WW-SD---
1 WATTRED
WHITEN/A CEILING/WALL WHITE
SINGLE FACE COMINATION POLYCARBONATE EXIT SIGN/TWIN HEAD
EMERGENCY LIGHT1,2
Y --- SELECTED BY OWNER, PROVIDED BY E.C. --- --- --- WALL ---DECORATIVE EXTERIOR WALL SCONCE SELECTED BY OWNER,
PROVIDED BY E.C.6
GENERAL:
● All interior LED fixtures shall be 3000°K corrected color temperature, min. 80 CRI.
● All exterior LED fixtures shall be 4000°K corrected color temperature, min. 70 CRI.
● All light fixtures shall be provided with universal drivers capable of operating at 120V or 208V UNO.
● All LED fixtures shall adhere to LM79 and LM80 standards.
● All apartment light fixtures shall be Energy Star certified.
NOTES:
1. Fixture shall have self-diagnostic/self-testing electronics.
2. Provide with emergency battery integral charger.
3. Fixture shall be capable of operation in temperatures ranging from -40°F through 104°F.
4. Provide fixture/pole assembly with 20' round straight steel pole, bronze to match fixture. Fixture height shall not exceed 23'-0" AFG.
5. Provide with bar hangers appropriate for ceiling system in which fixture is installed.
6. U.L. listed for 'wet location'.
7. See detail 3:E1.0 for more information.
8. Fixture/pole assembly shall be rated for 100 mph wind loads. Provide with vibration damper per manufacturer's recommendations.
TC
7DAY/24HR TIME CLOCK. INTERMATICMODEL T2005 OR EQUAL
LOBBY SMOKEDETECTOR
3RD FLOOR
SPARE
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E6.1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E6.2
GENERAL NOTES:
• All conductor sizes are based on copper, U.N.O.
• Entire installation shall comply with NEC.
• Coordinate all responsibilities and requirements with utility company and pay associated fees. Contact
Information:Lou Graves
Kerrville Public Utility Board
lgraves@kpub.com
(830) 792-8241
• Coordinate final location of meter assemblies with utility company. Provide shop drawings of proposed
equipment whether as specified or substituted to utility company for approval.
• Some branch circuits & feeders may need to be upsized due to length. Refer to sheet E0.1, note
16120.05 & coordinate with field conditions.
• All meter center components shall be NEMA 3R
• All dimensions based on Square D equipment
• For each meter, provide a permanent brass, copper or aluminum tag identifying the apartment served.
Tags shall be securely fastened to the meter base and be stamped with 1/8" letters, minimum.
• At each service, provide engraved plastic sign identifying "Service Disconnect ## of 3"
FOR FEEDER SIZE, SEE APARTMENT
FEEDER SCHEDULE ABOVE.
2'-0" AFG
(MINIMUM)
C BOTTOM METER:
±4'-0" AFG
C MOUNTING CHANNEL:
(2) 4-SOCKET METER CENTER
WITH BRANCH CIRCUIT
BREAKERS. SQUARE D EZ METER
PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH
BREAKERS
#2/0 Cu GROUNDING ELECTRODE CONDUCTOR TOCONCRETE ENCASED ELECTRODE, UNDERGROUND METALWATER PIPE, AND DRIVEN GROUND ROD. BOND ALL ITEMS
IN ACCORDANCE WITH NEC ARTICLE 250.
(2) SETS OF (4) #350 KCMIL IN4" CONDUIT FROM PAD MOUNT
TRANSFORMER TO METERCENTER.
FINISHED GRADE
2 SETS: (4)#500 KCM,
#2/0G IN 4"C.
2 SETS: (4)#500 KCMIL IN 4"C.
800A/600V/3P, NEMA 3R, SERVICERATED DISCONNECT SWITCH WITH
SOLID NEUTRAL AND (3) 800ADUAL-ELEMENT, TIME-DELAY FUSES
#2/0 Cu GROUNDING ELECTRODECONDUCTOR TO CONCRETE ENCASED
ELECTRODE, UNDERGROUND METAL
WATER PIPE, AND DRIVEN GROUNDROD. BOND ALL ITEMS IN
ACCORDANCE WITH NEC ARTICLE 250.
125A
125A
125A
125A
125A
125A
125A
18.66"12.25" 12.25"
55.41"
ELECTRICAL RISER DIAGRAM - WEST
No Scale1
(MAXIMUM)
6'-0" AFG
125A
125A
125A
SPACE
125A
125A
12.25"12.25"
(1) 3-SOCKET METER CENTER
WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER
PAK #EZMR313125, WITH (3)MODEL #QBP22125TM BRANCH
BREAKERS
FOR FEEDER SIZE, SEE APARTMENTFEEDER SCHEDULE ABOVE.
2'-0" AFG
(MINIMUM)
C BOTTOM METER:
±4'-0" AFG
C MOUNTING CHANNEL:
(4) 4-SOCKET METER CENTER
WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER
PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH
BREAKERS
#3/0 Cu GROUNDING ELECTRODE CONDUCTOR TO
CONCRETE ENCASED ELECTRODE, UNDERGROUND METAL
WATER PIPE, AND DRIVEN GROUND ROD. BOND ALL ITEMSIN ACCORDANCE WITH NEC ARTICLE 250.
(3) SETS OF (4) #500 KCMIL IN 4"
CONDUIT FROM PAD MOUNT
TRANSFORMER TO METER CENTER.
FINISHED GRADE
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
125A
30.19"12.25" 12.25"12.25"12.25"
128.19"
ELECTRICAL RISER DIAGRAM - EAST
No Scale2
(MAXIMUM)
6'-0" AFG
12.25"
125A
125A
125A
125A
125A
125A
125A
125A
SPACE
125A
125A
12.25"12.25"
125A
125A
125A
125A
(3) 4-SOCKET METER CENTER
WITH BRANCH CIRCUIT
BREAKERS. SQUARE D EZ METER
PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH
BREAKERS
125A
125A
125A
125A
12.25"
METER CENTER MAIN CIRCUIT
BREAKER. SQUARE D EZ METER
PAK #EZM3600, 208/120VTHREE PHASE, 4 WIRE, WITH
600A/3P CB, 65KAIC RATED
METER CENTER MAIN CIRCUIT
BREAKER. SQUARE D EZ METER
PAK #EZM31200, 208/120VTHREE PHASE, 4 WIRE, WITH
1200A/3P CB, 65KAIC RATED
TRANSOCKET
'TSN-310935'
(30"W x 42"H x 14"D)PROVIDED AND
INSTALLED BY
UTILITY COMPANY.
MDPA
B
C
ELEVATOR #1
MDP:2
MDP:3
MDP:1
MDP:5
APARTMENT FEEDER SCHEDULE
Apartment # Feeder Size
A2, A3, A4, A5, A6, B2, B3, B4, B5, B6, B7, B8, B9,B10, B14, B15, B16, B17, B18, C3, C4, C5, C6, C7,
C8, C9, C10, C14, C15, C16, C17, C18, C19
BASE BID (COPPER): (3)#1/0,#4G IN 1-1/2" C OR MC
CABLE
ALTERNATE BID (ALUMINUM):
(3)#3/0, #3G IN 2" C OR MC CABLE
A1, B1, B11, B12, B13, C1, C2, C11, C12, C13
BASE BID (COPPER): (3)#2/0,#3G IN 2" C. OR MC CABLE
ALTERNATE BID (ALUMINUM):
(3)#4/0, #2G IN 2" C OR MC CABLE
NOTES:
1. Voltage drop has been accounted for in sizes indicated, further up-sizing of feeders is not necessary
2. Ensure panel lugs are adequately sized to handle up-sized feeders.
C18APT
C19APT
EMPTY
B17APT
C17APT
B18APT
B15APT
C15APT
B16APT
C16APT
B13APT
C13APT
B14APT
B11APT
C11APT
B12APT
C12APT
B9APT
C9APT
B10APT
C10APT
B7APT
C7APT
B8APT
C8APT
C5APT
A6APT
B6APT
C6APT
B4APT
C4APT
A5APT
B5APT
A3APT
B3APT
C3APT
A4APT
C1APT
A2APT
B2APT
C2APT
A1APT
B1APT
EMPTY
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
(1) 3-SOCKET METER CENTER WITH
BRANCH CIRCUIT BREAKERS.SQUARE D EZ METER PAK
#EZMR313125, WITH (2) MODEL#QBP22125TM BRANCH BREAKERS
125A
C14APT
(1) 3-SOCKET METER CENTER
WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER
PAK #EZMR313125, WITH (2)MODEL #QBP22125TM BRANCH
BREAKERS
SDS
D
MDP:4
2 SETS: (4)#500 KCMILIN 4"C.
FIRE PUMP
CONTROLLER
(BY OTHERS)
JOCKEY PUMP
CONTROLLER
(BY OTHERS)
JOCKEY PUMP
(BY OTHERS)
FIRE PUMP
20 HP
(BY OTHERS)
4"x4" WIREWAY WITH
GROUND BAR
4#1 IN 2" C
3#8, #8G,
3/4" RMC
GRADE
3#8, #8G,
3/4" RMC
3#2, #8G,
1-1/4" RMC
3#2, #8G,
1-1/4" RMC
M
60"
MIN
/ 6
6"
MA
X
INSTALL POWER COMPANYFURNISHED METER SOCKET,
COORDINATE REQUIREMENTSWITH POWER UTILITY CO. SEE2:E1.4 FOR METER LOCATION.
3" SLIP JOINT ONCONDUIT RISER
#6 Cu GROUNDING ELECTRODE CONDUCTOR TO
CONCRETE ENCASED ELECTRODE,UNDERGROUND METAL WATER PIPE, AND DRIVEN
GROUND ROD. BOND ALL ITEMS IN ACCORDANCEWITH NEC ARTICLE 250.
FLOOR
ELECTRICAL RISER DIAGRAM - FIRE PUMP
No Scale3
(4) #1 IN 2" CONDUITFROM PAD MOUNT
TRANSFORMER TO METER.
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E6.3
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
E6.4
NOTES:
• PROVIDE RADIATION DAMPERS AT ALL
PENETRATIONS OF FIRE RATED FLOOR/CEILING
ASSEMBLY.
• ALL DUCTWORK SHALL BE SEALED AND TESTED IN
ACCORDANCE WITH 403.3 OF THE 2018 IECC.
• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE
INSULATED WITH MINIMUM R-6 DUCT
INSULATION.
• REFRIGERANT PIPING SHALL BE INSULATED PER
TABLE C403.11.3 OF 2018 IECC.
1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.
2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO
MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.
3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN
WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF
CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH
= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE
PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT
INSTALLED PER IMC 504.
NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL
PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE
STOPPING SYSTEM.
4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS
REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED
WITHOUT OFFSETS.
5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN
APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.
6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.
7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING
EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.
PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR
LOCATIONS OF BLOWER COILS. (TYPICAL)
8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.
COORDINATE WITH G.C.
9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR
AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE
VENT.
10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE
WITH ARCHITECTURAL PLANS.
11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS
POSSIBLE.
12. MOUNT TOP OF GRILLE 6" BELOW CEILING.
13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF
VENTILATION FAN.
# PLAN NOTES BY SYMBOL
PTAC-09
PTAC-15
PTAC-09 PTAC-09 PTAC-09
PTAC-15 PTAC-15 PTAC-15
PTAC-07
PTAC-07
PTAC-07
PTAC-07
PTAC-07
PTAC-15
TT
TT
TT
TT
T
T
T
T
EF-1 EF-1EF-1 EF-1
EF-2
EF-2
EF-2
BC-1
HP-1
PTAC-15
PTAC-15
PTAC-07
PTAC-07
10/8
6/6
T
HP-3
RG
16x8
T
1
2 2 2 2
3 3 3 3
VF-1
11
12
TG
14x12
T
13
66
6
5 5 5 5
7 8
9
40 CFM
SD
150
8x8
'BC-1'
SD
100
6x6
TG
8x8
SD
50
6x6
SD
200
10x10
6/6
8/8
MA
TC
HLIN
EM
AT
CH
LIN
E
PTAC-09 PTAC-09
PTAC-09
PTAC-09
PTAC-09
PTAC-15 PTAC-15
T
T T T T T T
EF-1
EF-1
EF-1
10/8
8/8
BC-2
22 2
3
3 3
EWH-2
EWH-1
5
5
5 5
5
5
'BC-2'T
SD
250
10x106/8
RG
14x10 10/10
MA
TC
HLIN
EM
AT
CH
LIN
E
1/8" = 1'-0"
FIRST FLOOR HVAC PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
M2.1
1/8" = 1'-0"
PARTIAL FIRST FLOOR HVAC PLAN2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
NOTES:
• PROVIDE RADIATION DAMPERS AT ALL
PENETRATIONS OF FIRE RATED FLOOR/CEILING
ASSEMBLY.
• ALL DUCTWORK SHALL BE SEALED AND TESTED IN
ACCORDANCE WITH 403.3 OF THE 2018 IECC.
• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE
INSULATED WITH MINIMUM R-6 DUCT
INSULATION.
• REFRIGERANT PIPING SHALL BE INSULATED PER
TABLE C403.11.3 OF 2018 IECC.
1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.
2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO
MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.
3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN
WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF
CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH
= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE
PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT
INSTALLED PER IMC 504.
NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL
PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE
STOPPING SYSTEM.
4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS
REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED
WITHOUT OFFSETS.
5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN
APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.
6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.
7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING
EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.
PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR
LOCATIONS OF BLOWER COILS. (TYPICAL)
8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.
COORDINATE WITH G.C.
9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR
AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE
VENT.
10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE
WITH ARCHITECTURAL PLANS.
11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS
POSSIBLE.
12. MOUNT TOP OF GRILLE 6" BELOW CEILING.
13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF
VENTILATION FAN.
# PLAN NOTES BY SYMBOL
PTAC-09
PTAC-15
PTAC-09 PTAC-09 PTAC-09 PTAC-09
PTAC-09
PTAC-09
PTAC-09PTAC-15 PTAC-15 PTAC-15
PTAC-15 PTAC-15
PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-12PTAC-15
PTAC-15PTAC-15PTAC-15PTAC-15
PTAC-15
PTAC-15PTAC-15
PTAC-09PTAC-09
PTAC-15
PTAC-09
PTAC-09
PTAC-09
PTAC-09
PTAC-15
PTAC-15
PTAC-15 PTAC-07
PTAC-07 PTAC-07
PTAC-07
PTAC-07
TT
TT
TT
TT
TT
TT
T T T T T T
TT
TT
TT
TT
T
T
T
T
T
T
T
T
T
T
TT
TT
EF-1
EF-1
EF-1EF-1 EF-1
EF-1
EF-1EF-1EF-1 EF-1EF-1 EF-1EF-1EF-1
EF-1
EF-1
EF-1
EF-1
HP-4 HP-5
BC-4EF-2
EF-2
EF-2
10/8 BC-3
EF-3
HP-2
PTAC-07
T
50
8/10 10/10
16/10
12/10
6/10
2
2
2
2
2 2 2 2 2 2 2
2
222222
3
4
3
4
3
4
3
4
34 34
33333333
3
3
3
3
5 5 5 55
5
5 5
5
5
55555555
5
5
5
5
7
8
7
8
9
170 CFM 8"Ø
SD
175
8x8
SD
175
8x8
8"Ø
8"Ø 10
SD
125
8x8
SD
125
8x8
SD
200
8x8SD
50
6x6
2
2 2
RG
16x6
RG
16x8
RG
16x6
10/6
CD
CD
CD CD
CD
CD
CD
SD
175
8x8
SD
175
8x8
CD
RG
12x12
8"Ø
8"Ø
9
85 CFM
6"Ø
T'BC-4'
'BC-3'
1/8" = 1'-0"
SECOND FLOOR HVAC PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
M2.2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
NOTES:
• PROVIDE RADIATION DAMPERS AT ALL
PENETRATIONS OF FIRE RATED FLOOR/CEILING
ASSEMBLY.
• ALL DUCTWORK SHALL BE SEALED AND TESTED IN
ACCORDANCE WITH 403.3 OF THE 2018 IECC.
• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE
INSULATED WITH MINIMUM R-6 DUCT
INSULATION.
• REFRIGERANT PIPING SHALL BE INSULATED PER
TABLE C403.11.3 OF 2018 IECC.
1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.
2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO
MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.
3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN
WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF
CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH
= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE
PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT
INSTALLED PER IMC 504.
NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL
PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE
STOPPING SYSTEM.
4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS
REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED
WITHOUT OFFSETS.
5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN
APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.
6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.
7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING
EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.
PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR
LOCATIONS OF BLOWER COILS. (TYPICAL)
8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.
COORDINATE WITH G.C.
9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH
BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR
AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE
VENT.
10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE
WITH ARCHITECTURAL PLANS.
11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS
POSSIBLE.
12. MOUNT TOP OF GRILLE 6" BELOW CEILING.
13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF
VENTILATION FAN.
# PLAN NOTES BY SYMBOL
PTAC-09
PTAC-15
PTAC-09 PTAC-09 PTAC-09 PTAC-09
PTAC-09
PTAC-09
PTAC-09PTAC-15 PTAC-15 PTAC-15
PTAC-15 PTAC-15
PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-12PTAC-15
PTAC-15PTAC-15PTAC-15PTAC-15
PTAC-15
PTAC-15PTAC-15
PTAC-09PTAC-09
PTAC-15
PTAC-09
PTAC-09
PTAC-09
PTAC-09
PTAC-15
PTAC-15
PTAC-15
PTAC-15
PTAC-09
PTAC-15
PTAC-07
PTAC-09
PTAC-12
T
T T
T
T
T
T
T
TT
TT
TT
TT
TT
TT
T T T T T
TT
TT
TT
TT
T
T
T
T
T
T
TT
TT
T
T
EF-1
EF-1
EF-1EF-1 EF-1
EF-1
EF-1EF-1EF-1 EF-1EF-1 EF-1EF-1EF-1
EF-1
EF-1
EF-1
EF-1
EF-1
EF-2
EF-2
EF-2
EF-2
EF-2
EF-3BC-5
PTAC-07
T
10/10
2
2
2
2
2 2 2 2 2 2 2
2
222222
2
3
4
3
4
3
4
34 34
33333333
4
34
3
3
3
5 5 5 55
5
5 5
5
5
55555555
5
5
5
5
T
2
SD
200
10x10 CD
CD
CD
CD
SD
200
10x10 9
105 CFM
'BC-5'
SD
50
6x6
SD
50
6x6
8"Ø
8"Ø
12/10
RG
12x12CD
2
1/8" = 1'-0"
THIRD FLOOR HVAC PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
M2.3
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
EXTERIOR PIPE SUPPORT DETAIL
NO SCALE2
INSULATED PIPE SUPPORTK-FLEX 360 OR EQUAL
APPLY CONTACT ADHESIVE TO COLLARJOINT AND SEAL THE SUPPORT BY
OVERLAPPING ADHESIVE TABS.
PROVIDE COLLAR TO FIX AROUND SUPPORTEQUAL TO CADDY CUSHION CLAMP PCC.
GLUE INSULATION TO PIPE
SUPPORT (TYPICAL BOTH SIDES).
1-1/4" ANGLE IRONFRAME WHEN REQ'D.FOR BOTTOM RETURN
SET BLOWER COIL ON
RUBBER VIBRATIONISOLATION PAD
SUPPLY AIR DUCT
SEE PLANS FOR SIZE
AND ROUTING
TO WALL CAP SEEPLANS FOR SIZEAND ROUTING
R.A. DUCT SEEPLANS FOR SIZE
AND ROUTING
O.A. DUCT
MANUAL BALANCING
DAMPER (TYP.)
FLEXIBLE DUCT CONN. (TYP.)
FILTER WITH PIANOHINGE AND LATCH
90 DEGREE ELBOW WITH TURNING VANES
3/4" TO FLOOR DRAIN
BLOWER COIL DETAIL
NO SCALE1
BLOWER
COIL
PACKAGED TERMINAL AIR CONDITIONER SCHEDULE
MARK MANUFACTURERMODELNUMBER
NOMINAL CAPACITIES
MIN. CKT.
AMPSMAX. OCPD
ELECTRICAL
CHARACTERISTICSWEIGHT
TOTALCOOLING
TOTALHEATING
AIRFLOW
PTAC-07 GE AZ41E07D 7,100 BTUH 2.32 kW 215 11.6 20 208V-1PH 100
PTAC-09 GE AZ41E09D 9,250 BTUH 2.32 kW 230 11.6 20 208V-1PH 100
PTAC-12 GE AZ41E12D 11,600 BTUH 2.32 kW 325 11.6 20 208V-1PH 100
PTAC-15 GE AZ41E15D 14,500 BTUH 2.32 kW 325 11.6 20 208V-1PH 100
NOTES:
1. PROVIDE WITH MANUFACTURER'S LINE CORD CONNECTION KIT.
2. PROVIDE WITH WALL CASE COMPATIBLE WITH WALL CONSTRUCTION COORDINATE WITH G.C.
3. PROVIDE WITH REMOTE WALL MOUNTED PROGRAMMABLE THERMOSTAT WITH TWO SPEED FAN CONTROL.
4. PROVIDE WITH MANUFACTURER'S SUB-BASE ACCESSORY. PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE INSTALLATION.
AIR DEVICE SCHEDULE
MARK MANUFACTURER MODEL
APPLICATION
FINISH MOUNTING DAMPER DESCRIPTION
SU
PPLY
RET
URN
EXH
AU
ST
TR
AN
SFER
SD PRICE 520 ● White Surface NoSteel double deflection supply grille with
front blades paralles to long dimension
RG PRICE 530 ● White Surface No Steel louvered return grille
TG PRICE 530 ● WhiteSurface
Wall/CeilingNo Steel louvered transfer grille
GENERAL NOTES:
● Maximum noise criteria shall be 25.
● Runouts to diffusers shall be same size as neck, U.N.O.
● Paint objects visible through grilles with flat black paint.
● Provide mounting frame as required for ceiling type. Coordinate with Architect.
● Verify finish with Architect.
● Provide devices with raditaion dampers as required in rated ceilings. Coordinate with Arch.
ELECTRIC HEATER SCHEDULE
MARK MANUF. MODEL MOUNTING WATTS VOLTAGE/PHASE DESCRIPTION NOTES
EWH TRANE UHWA WALL 1,500 120/1Architectural fan forced wall
heater1,2,3
NOTES:
1. Provide with high temp. thermal cutout and fan delay.
2. Provide with integral thermostat and unit mounted disconnect switch.
3. Provide with manufacturer's surface mounting adapter sleeve. Coordinate exact mounting requirements and
locations with Arch. and rated construction.
EXHAUST FAN SCHEDULE
MARK MANUFACTURER MODEL CFM ESP (" wg) POWERVOLTS/PHASE
NOTES
EF-1 BROAN XB80 80 0.4" 6 W 120 / 11,2,3,4,
5,6,7
EF-2 COOK GC-128 60 0.25 30 W 120/1 3,4,5,6
EF-3 COOK GC-148 130 0.25 46 W 120/1 3,4,5,6
NOTES:
1. Fixture shall be Energy Star listed.
2. Fixture shall operate at <1 SONE
3. Provide integral disconnect.
4. Provide manufacturer's wall cap or roof jack, see plans.
5. Provide integral backdraft damper.
6. Provide with manufacturer's ceiling radiation damper.
7. Fixture occurs in each tenant unit.
HEAT PUMP SCHEDULE
MARK MANUF. MODELNOMINAL
TONS
INDOORUNIT
AIRFLOW
COOLING CAPACITY HEATING CAPACITY MINHSPF
ELECTRICAL
OA DBENT AIR
DB/WBSENS MBH TOT MBH MIN SEER OA DB
ENT AIRDB
TOTMBH
MCA MOCP V/PH
HP-1,2,3 TRANE 4TWR6018H1 1.5 350 105 78/67 11.6 16.8 16 47 70 17.5 8.55 12 20 208/1
HP-4 TRANE 4TWR6030H1 2.5 850 105 78/67 20.3 28.0 16 47 70 28.8 9 17 25 208/1
HP-5 TRANE 4TWR6024H1 2 500 105 78/67 17.0 23.0 16 47 70 23.0 8.2 14 25 208/1
Notes:
1. Refrigerant lines shall be field fabricated. Coordinate line sizing requirements with equipment manufacturer for length of run for each apartment. Provide suction accumulators, etc. as
required.
2. Provide 7-day programmable thermostat.
3. Provide with R410a refrigerant.
4. Provide 2 sets of MERV-7 filters.
BLOWER COIL SCHEDULE
MARK MANUF. MODELFAN HEATING
KWV/Ph
MOTORFLA
MCA MOCPCFM ESP SPEED
BC-1,2,3 TRANE GAM5B0A18 350 0.7 MED-LOW 2.88 208/1 4 21 25
BC-4 TRANE GAM5B0B30 850 0.7 HIGH 5.76 208/1 2.8 38 40
BC-5 TRANE GAM5B0C30 500 0.7 MED 5.76 208/1 2.8 38 40
Notes:
1. Single point connection required, coordinate the exact electrical requirements of equipment provided with E.C.
2. Electric heater shall not operate simultaneously with heat pump. Electric heater shall be used as back-up heat only.
VENTILATION FAN SCHEDULE
MARK MANUFACTURER MODEL CFM ESP (" wg) POWERVOLTS/
PHASENOTES
VF-1 COOK GC-148 130 0.25 46 W 120/1 1
NOTES:
1. Provide integral disconnect.
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
M6.1
PLUMBING SIZING SYMBOLS
DRAIN (X = SIZE)
VENT (X = SIZE)
WASTE STACK VENT (X = SIZE)
NOTES:
SEE SHEET M1.2 FOR FIXTURE TYPES.X"
X"
X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2
FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND
ADDITIONAL INFORMATION.
1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.
COORDINATE WITH G.C.
2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED
ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN
HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE
WITH G.C.
3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH
ARCHITECT.
4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"
ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.
COORDINATE WITH G.C.
5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.
6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.
7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT
DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,
COORDINATE EXACT ROUTING WITH G.C.
NOTES BY SYMBOL#
3"
2"
3"
2"
3"
3"
2"
3"3"4"
2"
3"
3"
2"
3" 3" 4"
2"
3"
2"
3" 3" 4"
4"
3"
2"
3"
2"
3"3"4"
4"
4"
4"
4"
4"
FFCO
2-WAY
FGCO
4"
4"
2"
2"
3"
4"
2"
4"
3"2"
4"
7 7 7 7 7
4"
MA
TC
HLIN
E
NE
3
3
3
3 3
3" 2-WAY
FGCO3"3"
2"
3"
4"
2"
4"3"
2"
3"
4"
2"
4"3"
6"4"
7 7
MA
TC
HLIN
E
MA
TC
HLIN
E
2"
3
1/8" = 1'-0"
UNDERFLOOR WASTE AND VENT PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P2.0
1/8" = 1'-0"
PARTIAL UNDERFLOOR WASTE AND VENT PLAN2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
PLUMBING SIZING SYMBOLS
DRAIN (X = SIZE)
VENT (X = SIZE)
WASTE STACK VENT (X = SIZE)
NOTES:
SEE SHEET M1.2 FOR FIXTURE TYPES.X"
X"
X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2
FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND
ADDITIONAL INFORMATION.
1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.
COORDINATE WITH G.C.
2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED
ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN
HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE
WITH G.C.
3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH
ARCHITECT.
4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"
ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.
COORDINATE WITH G.C.
5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.
6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.
7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT
DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,
COORDINATE EXACT ROUTING WITH G.C.
NOTES BY SYMBOL#
11
11
11
11
1
2
1
1
1
2
2"
2"
4"
2" 4"
2"
2"
3"
2"
2"
2"
2"
4"
4"
2-WAY
FGCO
2"
3"
2"
2"
2"
4"
4"
2-WAY
FGCO
2"
3"
2"
2"
2"
2"
4"
4"
2-WAY
FGCO
2"
3"
2"
2"
2"
4"
4"
2-WAY
FGCO
2" 3"
2"
2"
2"
4"
2"
3"
2"2"
2"
2"
4"
4"
2-WAY
FGCO
2"
3"
2"2"
2"
2"
4"
4"
2-WAY
FGCO
3"
2"
3"
FD
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
2"
4"
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
2"
4"
SH-A
WC-A
CCB
LAV-A
2"
3"
2"
FD
2"
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
2"
4"
KS-A
3"
2"
2"
2" 3"
2"
4"
2"
2" 3" 2"
2"4"
2"
2"
2"
3"
2-WAY
FGCO
4"
2"
3"
4"
2"
3"3"3"3"3"3"
4"
3"
3"
3"
3"
2"
2"
3"4"
1
KS-B
ST
3
3
3
3
3 35
4
2"
1
1
3"
2"
4"
7 7 7 7 7
2
WC
-BW
C-B
SS
FD
FD
LAV-B
EWC
LAV-B
FFCO
BS
MA
TC
HLIN
E
MA
TC
HLIN
E
4"
COORDINATE ROUTING OF PIPING ABOVE FIRST
FLOOR COMMON AREA CEILINGS WITH
LOCATIONS OF PRE-MANUFACTURED HOLES IN
BEAMS. SEE STRUCTURAL AND ARCHITECTURAL
DRAWINGS FOR MORE INFORMATION. FINAL
ROUTING SHALL BE COORDINATED WITH G.C.
AND OTHER TRADES PRIOR TO INSTALLATION.
11
11
11
2"
3"
2"2"
2"
2"
4"
4"
2-WAY
FGCO
2"
3"
2"2"
2"
2"
4"
4"
2-WAY
FGCO
2"
SH-A
WC-A
LAV-A
CCB
KS-A
3"3"
2"
3"
4"
2"
FD3" 3"
2"
3"
4"
2"
FD
SH-A
WC-A
V-A
3"
2"
D
2"2"
4"
3"
SH-B
WC-B
LAV-B
CCB
KS-B
3
7 7
MA
TC
HLIN
E
MA
TC
HLIN
E
2" VTR
FS
FS
1/8" = 1'-0"
FIRST FLOOR WASTE AND VENT PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P2.1
1/8" = 1'-0"
PARTIAL FIRST WASTE AND VENT PLAN2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
PLUMBING SIZING SYMBOLS
DRAIN (X = SIZE)
VENT (X = SIZE)
WASTE STACK VENT (X = SIZE)
NOTES:
SEE SHEET M1.2 FOR FIXTURE TYPES.X"
X"
X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2
FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND
ADDITIONAL INFORMATION.
1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.
COORDINATE WITH G.C.
2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED
ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN
HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE
WITH G.C.
3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH
ARCHITECT.
4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"
ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.
COORDINATE WITH G.C.
5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.
6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.
7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT
DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,
COORDINATE EXACT ROUTING WITH G.C.
NOTES BY SYMBOL#
SH-A
WC-A
LAV-A
CCB
KS-A
3"3"
2"
3"
4"
2"
FD
SH-A
WC-A
LAV-A
CCB
KS-A
3" 3"
2"
3"
4"
2"
FD
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
1
1 1
1 1
1 1
1 1 1
1 1
1 1
1
1 1
1 1 1 1
1 1
1 1
1 1
1
1
1
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
2"FD
1
1
1
1
1
1
1
1
1
2"
2"
2"
4"
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
2"
4"
SH-A
WC-A
CCB
LAV-A
2"
3"
2"
FD
2"
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"
3"
2"
3"
FD
2"
4"
2"
2"
2"
4"
SH-A
WC-A
CCB
LAV-A
KS-A
2"
3"2"
FD
2"
2"
2"
4"
SH-A
WC
-A
CCB
LAV-A
KS-A
2"
3"
2"FD
2"
2"
4"
SH-A
WC
-A
CCB
LAV-A
KS-A
2"
3"
FD
2"
2"
4"
SH-A
WC
-A
CCB
LAV-A
KS-A
2"
3"
FD
2"
2"
4"
SH-A
WC
-A
CCB
LAV-A
KS-A
2"
3"
FD
2"
2"
4"
SH-A
WC-A
CCB
LAV-B
KS-B
2"
3"
FD
2"
2"
4"
SH-B
WC-B
CCB
LAV-A
KS-A
2"
3"
FD
2"
2"
4"
SH-A
CCB
LAV-A
2" 3"
2"
FD
2"
2"
4"
WC
-BW
C-B
FD
FD
LA
V-B
EWC
LAV-B
SS
FWCO
CCB
2" 3"
2"
2"
2"
CCB
2" 3"
2"
2"
KS-A
3"
2" 2"2"
2" 2"2"
2"2"2"
CCB
LAV-A
KS-A
FD
WC-A
WC-A
SH-A
SH-A
SH-A
FD
FD
FD
LAV-A
LAV-A
LAV-A
WC-A
WC-A
KS-A
KS-A
KS-A
CCB
2"
2"
4"
2"
2" 3" 2"
2"4"
2"
3"
2"2"
3"
2"
1
1
11
1
3
3
3
3
3
3
3
3 3 3
3
1
4"
1
3"
7 7 7 7 7 7
7 77 77
7
77
7
7
7
7
3
1/8" = 1'-0"
SECOND FLOOR WASTE AND VENT PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P2.2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
PLUMBING SIZING SYMBOLS
DRAIN (X = SIZE)
VENT (X = SIZE)
WASTE STACK VENT (X = SIZE)
NOTES:
SEE SHEET M1.2 FOR FIXTURE TYPES.X"
X"
X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2
FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND
ADDITIONAL INFORMATION.
1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.
COORDINATE WITH G.C.
2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"
CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND
TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED
ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN
HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE
WITH G.C.
3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH
ARCHITECT.
4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"
ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.
COORDINATE WITH G.C.
5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.
6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.
7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT
DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,
COORDINATE EXACT ROUTING WITH G.C.
NOTES BY SYMBOL#
SH-A
LAV-A
WC-ACCB KS-A
2"
3"
3"2"
FD
3"
2"
WC
-BW
C-B
FD
FD
LAV-B
EWC
LAV-B
SS
1
1 1
1 1
1 1
1 1 1
1 1
1 1
1
1
1
11
11
11
1111
11
1
SH-A
WC-A
LAV-ACCB
KS-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
WC-A
CCB
LAV-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FDSH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
CCB
LAV-A
KS-A
FD
SH-A
CCB
LAV-A
KS-A
FD
SH-B
WC-B
CCB
LAV-B
KS-B
FD
SH-A
WC-A
CCB
LAV-A
KS-A
FD
SH-A
CCB
LAV-A
KS-A
FD
WC-A
WC-AWC-A
KS-A
2"
3"
2"
2"
3"2"
2"
3"
3"
2"
3"
2"
2"
2"
3"
2"
2"
3"
2"
2"2"
3"
2"
2"2"
3"
2"
2"2"
3"
2"
2"
3"
2"
2"
3"
2"3"
2"
2"
3"3"
2"3"
2"
2"
2"3"
2"
2"
3"3"
2"3"
2"
2"
WC-A
SH-A
SH-A
SH-A
FD
FD
FD
LAV-A
LAV-A
LAV-A
WC-A
WC-A
KS-A
KS-A
KS-A
2" 3" 2"
2"
2"
2"
2" 3" 2"
2"
2"
2"
2" 3" 2"
2" 3" 2"
2"
2"
3"3" VTR3"3"
3"3"
3"
3"3" 3"
3" VTR3" 3"3" VTR
3"
3" 3"
3"3" VTR
2"2" 3"
3"
3"
2"
3"
3"
3"
3"
3" VTR
2"
3"
3"
3"
3" VTR
1
1
1
1
1
1
1
1
11
1
1
1
3
3
3
3
33
3
3
3
3
3
1
LAV-A
WC-A
SH-A
CCB
FD
KS-A
7
7
7
7
7
77 77 77 77
77 77 7 7
CCB
CCB
CCB
1/8" = 1'-0"
THIRD FLOOR WASTE AND VENT PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P2.3
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
NOTES:
• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET
P6.1 FOR INDIVIDUAL FIXTURE CONNECTION
SIZES AND ADDITIONAL INFORMATION.
• 1/2" HOT WATER PIPING SHALL BE ROUTED TO
ENSURE THE MAX. DISTANCE FROM THE HOT
WATER RECIRCULATION LOOP TO PUBLIC
LAVATORIES DOES NOT EXCEED 2', PER 2018
IECC TABLE C404.5.1
NOTES BY SYMBOL# NOTES BY SYMBOL
1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.
2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.
3. SEE CIVIL DRAWINGS FOR CONTINUATION.
4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.
6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED
PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED
SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/
APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT
7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF
98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)
5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT
POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO
INSTALLATION.
8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.
9. PROVIDE SKID MOUNTED FIRE PUMP.
10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.
COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.
11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
#
WC
-BW
C-B
SS
LA
V-B
EWC
LA
V-B
HWH
HWP
SH-BWC-B
LA
V-B
CCB
KS-BSH-A
WC-A
CCB
LAV-A
KS-ASH-A
WC-A
CCB
LAV-A
KS-ASH-A
WC-A
CCB
LAV-A
SH-A
WC-A
CCB
LAV-A
KS-A KS-A
2"1-1/2"
1-1/2"
1-1/4"
3/4"
1-1/4"
6 6 6 6
6
4
P4.1
2
P4.1
2
P4.1
2
P4.12
P4.1
5
5
5
WH
WH
WH
MA
TC
HLIN
EM
AT
CH
LIN
E
BS
4
P6.1
4
COORDINATE ROUTING OF PIPING ABOVE FIRST
FLOOR COMMON AREA CEILINGS WITH
LOCATIONS OF PRE-MANUFACTURED HOLES IN
BEAMS. SEE STRUCTURAL AND ARCHITECTURAL
DRAWINGS FOR MORE INFORMATION. FINAL
ROUTING SHALL BE COORDINATED WITH G.C.
AND OTHER TRADES PRIOR TO INSTALLATION.
FP
WW
SH-A
WC-A
LAV-A
CCB
KS-ASH-B
WC-B
LA
V-B
CCB
3"
3" UP
10
9
8
7
66
1
P4.1
5WH
1
2
MA
TC
HLIN
EM
AT
CH
LIN
E
3
4
1/8" = 1'-0"
FIRST FLOOR DOMESTIC WATER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT
TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN
CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS
ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.
P2.4
1/8" = 1'-0"
PARTIAL FIRST FLOOR DOMESTIC WATER PLAN2
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
HWH-AHWPSS
WC
-BW
C-B
LAV-B
EWC
LA
V-B
SH-A
WC-A
LAV-A
CCB
KS-ASH-A
WC-A
LAV-A
CCB
KS-ASH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-ASH-A
WC-A
CCB
LAV-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
CCB
LAV-A
KS-A
SH-A
CCB
LAV-A
KS-ASH-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-B
KS-B
SH-B
WC-B
CCB
LAV-A
KS-ASH-A
CCB
LAV-A
CCB
CCB
KS-A
CCB
LAV-A
KS-A
SH-A
SH-A
SH-A
LAV-A
LAV-A
LAV-A
WC-A
WC-A
KS-A
KS-A
KS-A
CCB
WC-A WC-A WC-A
3"
2"
3"
1-1/2"
1-1/2"
6
6
6
6 6
6
66
6 6
6 6
6
6
6 6
6
1
P4.1
1
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
3
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
5 5
5
WH WH
WH
2"
1-1/2"
1-1/4"
1"
3
P6.1
11111111
11
6
6
NOTES:
• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET
P6.1 FOR INDIVIDUAL FIXTURE CONNECTION
SIZES AND ADDITIONAL INFORMATION.
• 1/2" HOT WATER PIPING SHALL BE ROUTED TO
ENSURE THE MAX. DISTANCE FROM THE HOT
WATER RECIRCULATION LOOP TO PUBLIC
LAVATORIES DOES NOT EXCEED 2', PER 2018
IECC TABLE C404.5.1
NOTES BY SYMBOL# NOTES BY SYMBOL
1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.
2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.
3. SEE CIVIL DRAWINGS FOR CONTINUATION.
4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.
6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED
PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED
SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/
APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT
7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF
98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)
5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT
POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO
INSTALLATION.
8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.
9. PROVIDE SKID MOUNTED FIRE PUMP.
10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.
COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.
11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
#
1/8" = 1'-0"
SECOND FLOOR DOMESTIC WATER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT
TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN
CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS
ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.
P2.5
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
SS
WC-B
WC-B
LAV-B
EWC
LAV-B
SH-A
LAV-A
WC-ACCB KS-A
SH-A
WC-A
LAV-ACCB
KS-ASH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-ASH-A
WC-A
CCB
LAV-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-ASH-A
WC-A
CCB
LAV-A
KS-A
SH-A
WC-A
CCB
LAV-A
KS-A
SH-A
CCB
LAV-A
KS-ASH-A
CCB
LAV-A
KS-ASH-B
WC-B
CCB
LAV-B
KS-B
SH-A
WC-A
CCB
LAV-A
KS-ASH-A
CCB
LAV-A
KS-A
WC-AWC-A
KS-A
SH-A
SH-A
SH-A
LAV-A
LAV-A
LAV-A
WC-A
WC-A
KS-A
KS-A
KS-A
1
P4.1
1
P4.1
2
P4.1
3
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
2
P4.1
SH-AWC-A
LAV-A
KS-A
CCB
CCB
CCB
CCB
NOTES:
• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET
P6.1 FOR INDIVIDUAL FIXTURE CONNECTION
SIZES AND ADDITIONAL INFORMATION.
• 1/2" HOT WATER PIPING SHALL BE ROUTED TO
ENSURE THE MAX. DISTANCE FROM THE HOT
WATER RECIRCULATION LOOP TO PUBLIC
LAVATORIES DOES NOT EXCEED 2', PER 2018
IECC TABLE C404.5.1
NOTES BY SYMBOL# NOTES BY SYMBOL
1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.
2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.
3. SEE CIVIL DRAWINGS FOR CONTINUATION.
4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.
6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED
PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED
SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/
APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT
7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF
98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)
5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT
POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO
INSTALLATION.
8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.
9. PROVIDE SKID MOUNTED FIRE PUMP.
10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.
COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.
11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE
SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH
ARCHITECT.
#
1/8" = 1'-0"
THIRD FLOOR DOMESTIC WATER PLAN1
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT
TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN
CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS
ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.
P2.6
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
KS-A
ICB
CCB SH-A
WC-A
LAV-A
HWH
1" 3/4"
3/4"
1"
3/4"
1-1/4"1-1/4"
1
3
1
25
P6.1
KS-B
ICB
CCB
SH-B
WC-B
LAV-B
HWH
3/4" 3/4"
1"1"
1-1/4" 1-1/4"
1 1
2
3
5
P6.1
KS-A
ICB
CCB
SH-A
WC-A
LAV-A
HWH
3/4" 3/4"
1"1"
1-1/4" 1-1/4"
11
2
3
5
P6.1
CCB SH-B
WC-B
LAV-B
HWH
KS-B
ICB
1"3/4"
3/4"
1"
3/4"
1-1/4"
1
3
5
P6.1
ENLARGED PLAN NOTES BY SYMBOL#
1. SEE OVERALL DOMESTIC WATER PLANS FOR CONTINUATION.
2. 1-1/4" WATER SERVICE FOR UNIT ABOVE. ROUTE PIPING FOR 3RD FLOOR UNITS
BELOW FLOOR ABOVE SECOND FLOOR CEILING SIMILAR TO PIPING SHOWN. DO NOT
ROUTE PIPING IN ATTIC.
3. PROVIDE 1/2" VALVED BRANCH BELOW SINK AND CONNECT DISHWASHER. ROUTE
PIPING ALONG BACK OF CABINETRY, COORDINATE EXACT ROUTING WITH G.C.
COORDINATE EXACT REQUIREMENTS WITH DISHWASHER PROVIDED.
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
1/4" = 1'-0"
1 BEDROOM ENLARGED DOMESTIC WATER2
1/4" = 1'-0"
2 BEDROOM ENLARGED DOMESTIC WATER1
1/4" = 1'-0"
1 BEDROOM HC ENLARGED DOMESTIC WATER3
1/4" = 1'-0"
2 BEDROOM HC ENLARGED DOMESTIC WATER3
P4.1
PROJECT SHALL COMPLY WITH ALL
REQUIREMENTS OF THE 2018 IECC.
REFERENCE SPECIFICATIONS FOR
COMMISSIONING REQUIREMENTS.
NOTE:
FIXTURE TAGS INDICATED ARE FOR TYPICAL
APARTMENT. SEE PLANS AND PLUMBING
FIXTURE SCHEDULE FOR EXACT FIXTURE TYPES.
PLUMBING SIZING SYMBOLS
DRAIN (X = SIZE)
VENT (X = SIZE)
WASTE STACK VENT (X = SIZE)
X"
X"
X"
LAV
LAV
CCB
CCB
WC
WC
SH
SEE PLANS FOR
CONTINUATION OF
VENT PIPING, TYPICAL.
SH
KS-A
KS-A
KS-A
LAV
CCB
WC
SH
NO SCALE1
TYPICAL 2 BEDROOM
WASTE & VENT ISOMETRIC
FD
FD
FD
LAV-A
LAV-A
SH-A
CCB
CCB
SEE PLANS FOR
CONTINUATION OF
VENT PIPING, TYPICAL.
KS-A
KS-A
SH-A
NO SCALE2
TYPICAL 1 BEDROOM (3-FLOOR)
WASTE & VENT ISOMETRIC
WC-A
WC-A
LAV-A
CCB
KS-A
FD
FD
SH-A
LAV-A
LAV-A
CCB
CCB
SEE PLANS FOR
CONTINUATION OF
VENT PIPING, TYPICAL.
KS-A
KS-A
NO SCALE3
TYPICAL 1 BEDROOM (2-FLOOR)
WASTE & VENT ISOMETRIC
FD
FD
SH-A
SH-A
WC-A
WC-A
WC-A
WC-B
WC-B
WC-B WC-B
SEE PLANS FOR
CONTINUATION OF
VENT PIPING, TYPICAL.
LAV-B
LAV-B
LAV-B
LAV-B
FD
FD
FD
FD
EWC
EWC
NO SCALE4
PUBLIC RESTROOMS
WASTE & VENT ISOMETRIC
SS
SS
KS-A
KS-A
NO SCALE5
TYPICAL 1 BEDROOM ABOVE COMMONS
WASTE & VENT ISOMETRIC
FD
WC-A
WC-A
SH-A
SH-A
FD
LAV-A
LAV-A
CCB
CCB
FD
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P5.1
FIRE PROTECTION RISER DIAGRAM
Not to Scale1
GROUND FLOOR
CHECK VALVE.PROVIDE BALLDRIP AS REQUIRED.
PRESSURE GAUGEWITH VALVE, TYPICAL
TAMPER SWITCH, TYP.
WATER FLOW DETECTOR.
ANGLE VALVE
2" TEST/DRAIN
TO AUTOMATICSPRINKLER SYSTEM
CLOSET WALL
WET HEADS.
PROVIDE 4" LINE TO FIRE
DEPARTMENT CONNECTION.COORDINATE LOCATION AND
SIZE WITH FIRE DEPARTMENT.
PROVIDE THRUST BLOCKSAT CHANGES IN DIRECTION.
FIRE SPRINKLER SERVICE.
VERIFY SIZE
REQUIREMENTS WITHPRESSURE AVAILABILITYAND FIRE SPRINKLER
REQUIREMENTS.
PR
EV
EN
TER
, W
AT
TS 7
09 O
R E
QU
AL.
DO
UBLE C
HEC
K T
YPE B
AC
KFLO
W
FLO
W T
EST
ING
PER
NFPA
REQ
UIR
EM
EN
TS.
PR
OV
IDE A
PPR
OV
ED
MEA
NS O
F F
ORW
ARD
VERIFY BACKFLOW PREVENTER
REQUIREMENTS WITH CITY PRIORTO PURCHASE AND INSTALLATION.
PLUMBING FIXTURE SCHEDULE
MARK MANUFACTURER DESCRIPTION
TRIM ROUGH-IN SIZES
NOTES
MANUFACTURER DESCRIPTION WASTE VENT CW HW
WC-A KOHLER
Model #K-3658-(RA)-0 "Highline Classic" ADA
compliant flush tank water closet, white vitreous
china, two piece, 12" rough-in, elongated 16-1/2"
high bowl, siphon jet flushing action, 1.28 GPF,
polished chrome actuator. Coordinate location
of trip lever with installation.
KOHLER#K-4636-0 white, closed front plastic seat
with slow closing lid.4" 2" 1/2" --- 1
WC-B KOHLER
Model #K-3658-(RA)-0 "Highline Classic" ADA
compliant flush tank water closet, white vitreous
china, two piece, 12" rough-in, elongated 16-1/2"
high bowl, siphon jet flushing action, 1.28 GPF,
polished chrome actuator. Coordinate location
of trip lever with installation.
KOHLER
#K-4731-CA-0 white, open front,
anti-microbial plastic seat without lid, with
check hinge.4" 2" 1/2" --- 1
LAV-A KOHLERModel 2196-4-0 self-rimming lavatory, white
vitreous china, 20"W x 17", faucet holes on 4"centers.
KOHLER#K-394-4-2 two handle faucet with pop-up
drain and nickel finish.2" 1-1/2" 1/2" 1/2" 1,2,3
LAV-B KOHLERModel #K-2196-4-0 self-rimming lavatory, white
vitreous china, 20"W x 17", faucet holes on 4"centers.
KOHLER
#K-393-N4-2BZ faucet. Provide grid drain,
nickel finish, and point of use tempering
valve.
2" 1-1/2" 1/2" 1/2" 1,2,3
KS-A KOHLER
Model K-3369-3 two compartment 18 GA
stainless steel top-mount sink,
14-1/2"x16-1/2"x8"D inside, fully undercoated,
faucet holes as required.
KOHLER
INSINKERATOR
#K-780 single handle pull down kitchen
sink faucet with chrome finish, single hole
installation. Provide basket strainer.
Badger 5 12 HP garbage disposal with
dishwasher waste connection.
2" 1-1/2" 1/2" 1/2" 1,2,3,5
KS-B JUST
Model DL-ADA-2233-A-GR two compartment 18
GA stainless steel sink, self rimming,
14"x16"x5"D inside, fully undercoated, faucet
holes as required, and drain hole center rear.
KOHLER
IN-SINK-ERATOR
#K-780 single handle pull down kitchen
sink faucet with chrome finish, single hole
installation. Provide basket strainer.
Badger 5 12 HP garbage disposal withdishwasher waste connection.
2" 1-1/2" 1/2" 1/2" 1,3,2,4
BS ELKAY
Model DLR172210 single compartment 18 GA.
Stainless steel sink, self rimming, 14"x16"x10"D
inside, fully undercoated, faucet holes as
required.
DELTA
Model 27C4844 two handle bar sink
faucet, 4-1/2" gooseneck spout, 1.5 GPM
aerator, 4" blade handles, chrome finish.
Provide basket strainer.
2" 1-1/2" 1/2" 1/2" 2,4
SH-A AQUARIUS
Model 'G-3682BF RFF' reinforced fiberglass ADA
shower, 36"W x36"D x76-1/2"H, with integral
soap/toiletry shelves and grab bars in
accordance with ADA requirements. Provide
blocking for future installation of fold-up seat,
right or left hand rough-in as required. Provide
with collapsible dam.
KOHLER
#K-304 pressure balancing valve with
integral temperature limits and stops,
#K-TS10584-4 valve trim, #K-355 wall
supply elbow, #K-9514 60" hose,
#K-10549 hand shower, and
#K-8524/K-349 slide bar. Entire assembly
shall have nickel finish.
2" 1-1/2" 1/2" 1/2" 1
SH-B AQUARIUS
Model 'G-3682BF RFF' reinforced fiberglass ADA
shower, 36"W x36"D x76-1/2"H, with integral
soap/toiletry shelves and grab bars in
accordance with ADA requirements, fold-up seat,
right or left hand rough-in as required, white
finish. Provide with collapsible dam.
KOHLER
#K-304 pressure balancing valve with
integral temperature limits and stops,
#K-TS10584-4 valve trim, #K-355 wall
supply elbow, #K-9514 60" hose,
#K-10549 hand shower, and
#K-8524/K-349 slide bar. Entire assembly
shall have nickel finish.
2" 1-1/2" 1/2" 1/2" 1
SS FIAT
Model MSB-2424 one piece molded stone mop
basin, 24" square, stainless steel integral drain
body with caulk connection, stainless steel wall
guards.
DELTA
Model 28T9 faucet with hose thread outlet,
vacuum breaker, pail hook, wall brace,
metal lever handles.
3" 1-1/2" 3/4" 3/4" 4
WH WOODFORD Model 25 frost proof wall hydrant with anti-siphon vacuum breaker, metal handle. --- --- 3/4" ---
CCB WATER-TITEModel W4700 recessed washing machine box with 2"PVC/ABS drain coupling and knockout test cap. Two brass
1/4 turn adaptor ball valves with hammer arresters, sweat connection.2" 2" 1/2" 1/2"
ICB OATEY Model 3848X fire rated ice maker connection box with 1/4 turn ball valve. --- --- 1/2" ---
FD WADEModel 1102STD5 floor drain with satin nickel bronze strainer. Provide trap protection device equal to ProSet
Trapguard.2" 1-1/2" --- ---
FS WADEModel 9140 floor sink with 8" deep body, enameled interior, sediment bucket, nickel bronze trim and grate with
openings as requried. Provide trap protection device equal to ProSet Trapguard.3" 1-1/2" --- ---
EWC ELKAY
Model EZTL8C ADA compliant dual height, self-contained water cooler with stainless steel basin, front push bar
actuator, lead-free cooling system capable of cooling 8.0 GPH, 120 volts. Provide cane apron equal to Elkay
model 'LKAPREZL'
2" 1-1/2" 1/2" ---
HWH-A A.O. SMITHModel EJCS-20, 20 gallon electric water heater, 2500 watts, 208 volts heating element, 11 GPH recovery @ 90°F temp rise. Supplied with temperature
& pressure relief valve and brass drain valve.6
HWH A.O. SMITHModel ENT-40, 40 gallon electric water heater, 4500 watts, 208 volts heating element, 21 GPH recovery @ 90°F temp rise. Supplied with temperature
& pressure relief valve and brass drain valve.
HWP BELL & GOSSETT Model NBF-33 circulation pump, bronze body, 10 GPM @ 10' head, 120 VAC. Provide clamp-on aquastat for pump control. 7
GENERAL:
• Provide fixtures with all trim necessary for complete installation.
• Ensure all fixtures meet the requirements of the Texas Administrative Code Chapter 372.
• All toilets, lavatory faucets, showerheads, and kitchen faucets shall have EPA's WaterSense label.
NOTES:
1. In areas open to the public, fixture and installation to meet requirements of Americans with Disabilities Act. In apartments, fixture and installation to meet requirements of the Fair Housing Act.
2. Provide Dearborn supplies with stops and escutcheon plate, 1-1/4" cast brass p-trap.
3. Insulate water and waste piping below lavatory. Utilize insulation kit equivalent to LavGuard by Truebro. Provide Plumberex Model #3071WD-N disposal cover.
4. Trim shall be provided with polished chrome finish.
5. Provide Plumberex model #3071WD-N waste disposal cover.
6. Provide wall hung platform for water heater equal to Holdrite #50-SWHP-W-C. Coordinate exact location and mounting height with architect.
7. Pump shall have controls to prevent startup within 5 minutes from the end of the previous heating cycle. Hot water recirculation system shall meet all requirements of 2018 IECC.
FROM FIRE SPRINKLERAIR COMPRESSOR
HEADSTO DRY
GATE VALVE
SEE PLANS FOR CONTINUATION
DISCHARGE TO DAYLIGHT
CHECK VALVE - INSIDE BUILDING
UNION
SEE ELECTRICAL PLANS.ELECTRICAL CONNECTION.
AUDIBLE ALARMHIGH WATER
2"
ELEVATOR SUMP PUMP DETAIL
NO SCALE2
LIGHTHIGH WATER
WEIL #8341K1015SIMPLEX PUMP
CONTROL PANEL
24"Ø x 2'-0" DEEP OPEN FIBERGLASSBASIN WITH ANTI-FLOAT RINGS,
FIBERBASIN OR EQUAL, 3/16" WALLTHICKNESS, INLETS AS INDICATED ON
PLANS. PROVIDE WITH GRATE COVER.
DISCHARGE ELBOW AND DISCHARGEFLANGE KIT WEIL 2613K202
TETHERED LEVEL CONTROL,WEIL 8233K1006 WITHMOUNTING PLATE AND PIPE
OIL SMART WATER PUMP SWITCHMODEL OSS20PBPR6, MOUNT LOWESTPART OF PROBE 6" ABOVE THE
BOTTOM OF THE BASIN.
MOUNT ALARM SWITCH
SO THAT ALARM SOUNDSWHEN WATER LEVEL IS 6"BELOW TOP OF SUMP
SUBMERSIBLE SUMP PUMP,WEIL 1411, 50 GPM @20'
HEAD, 2" DISCHARGE, 1/2
HP MOTOR, 120V/1Ø.
HWH-A
JANITOR 207 WATER HEATER PIPING DIAGRAM
NO SCALE3
PROVIDE T & P RELIEF
VALVE. ROUTE 3/4" PIPE
FROM VALVE TO ABOVE 'SS'
1-1/4"
SHUT-OFF VALVE
UNION
HWP
A
PROVIDE CLAMP-ONAQUASTAT FOR
CONTROL OF CIRC. PUMP
SEE PLANS FORCONTINUATION
HWH
JANITOR 113 WATER HEATER PIPING DIAGRAM
NO SCALE4
PROVIDE T & P RELIEF VALVE.
ROUTE 3/4" PIPE FROM
VALVE TO DRAIN PAN
PROVIDE MOUNT AND
DRAIN PAN, SEEPLUMBING FIXTURESCHEDULE FOR MORE
INFORMATION.
PROVIDE WATTS MODEL
DETA-12 EXPANSIONTANK, OR EQUIVALENT.
ROUTE OVERFLOW DRAINTO SPILL DIRECTLY
ABOVE FLOOR DRAIN.
ROUTE OVERFLOWDRAIN TO SPILL IN 'SS'.
PROVIDE WATER HEATERDRAIN PAN.
HWH-A
APARTMENT WATER HEATER PIPING DIAGRAM
NO SCALE5
PROVIDE T & P RELIEF
VALVE. ROUTE 3/4" PIPEFROM VALVE TO DRAIN PAN
SHUT-OFF VALVE
UNIONPROVIDE WATTS MODELDETA-12 EXPANSION
TANK, OR EQUIVALENT.
ROUTE OVERFLOW DRAINTO SPILL DIRECTLY
ABOVE FLOOR DRAIN.
PROVIDE WATER HEATERDRAIN PAN.
ROUTE HOT AND COLD WATERPIPING TO APARTMENT FIXTURES.
SEE ENLARGED DOMESTIC WATERPLAN P4.1 FOR CONTINUATION.
APARTMENT WATERSERVICE - SEE PLANS FORROUTING AND SIZE
1-1/4"
UNION
HWP
A
PROVIDE CLAMP-ON
AQUASTAT FORCONTROL OF CIRC. PUMP
SEE PLANS FOR
CONTINUATION
PROVIDE WATTS MODELDETA-12 EXPANSION
TANK, OR EQUIVALENT.
SHUT-OFF VALVE
1"
NE
W S
EN
IOR
LIV
ING
UN
ITS
KE
RV
ILL
E,
TE
XA
S
mail@LSTengineers.com
4809 Vue Du Lac Place, Suite 201
Manhattan, Kansas 66503
785.587.8042 FAX 785.587.8039
LST Consulting Engineers, PAProject 20026 MARCH 2021
P6.1