STATIC LED TROFFER PENDANT OR SURFACE MOUNTED LINEAR LUMINAIRE LED STRIP LIGHT SURFACE MOUNTED ROUND LIGHT RECESSED DOWNLIGHT WALL MOUNTED LUMINAIRE DECORATIVE PENDANT SINGLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH DIRECTIONAL ARROWS AS INDICATED ON PLANS DOUBLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH DIRECTIONAL ARROWS AS INDICATED ON PLANS REMOTE EMERGENCY LIGHTING UNIT LIGHTING SYMBOLS SINGLE RECEPTACLE DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE SPECIAL RECEPTACLE (# = NEMA CONFIGURATION) FLUSH FLOOR DUPLEX RECEPTACLE SINGLE POLE WALL SWITCH TWO POLE WALL SWITCH THREE WAY WALL SWITCH KEYED WALL SWITCH SINGLE POLE, DOUBLE THROW (SPDT) SWITCH (CENTER OFF) MOTOR HP RATED SWITCH WITHOUT OVERLOAD PROTECTION MECHANICAL DIAL TIMER WALL SWITCH LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH DUAL RELAY LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH LOW VOLTAGE OCCUPANCY SENSOR POWER PACK FOR LOW VOLTAGE OCCUPANCY SENSORS LIGHTING CONTACTOR EXTERIOR PHOTOCELL CONTACTOR PUSH BUTTON OPERATOR CLASS 2 TRANSFORMER POWER SUPPLY DOOR ANNUNCIATOR A/V HORN STROBE JUNCTION BOX MOTOR MOTORIZED DAMPER DISCONNECT SWITCH BRANCH CIRCUIT PANELBOARD SWITCHBOARD POWER SYMBOLS # LC os P TELECOMMUNICATIONS SYMBOLS APARTMENT PHONE OUTLET TELECOMMUNICATIONS OUTLET APARTMENT CATV OUTLET TELEPHONE TERMINAL BOARD CLG CEILING MOUNTED FLUSH MOUNTED IN SUSPENDED OR HARD CEILINGS SURFACE MOUNTED TO STRUCTURE ABOVE IN OPEN CEILINGS CT MOUNT BOTTOM OF DEVICE AT 6" ABOVE COUNTERTOP EM PROVIDE LUMINAIRE WITH EMERGENCY BATTERY BACKUP GFI GROUND FAULT CIRCUIT INTERRUPTING DEVICE NL NIGHTLIGHT WIRED TO UNSWITCHED HOT CONDUCTOR WP PROVIDE WEATHERPROOF ENCLOSURE FOR DEVICE XX" MOUNTING HEIGHT OF DEVICE ABOVE FINISHED FLOOR SYMBOL MODIFYING DESIGNATORS ## ## CIRCUIT AND RACEWAY SYMBOLS CIRCUIT DESIGNATION: TOP INDICATES PANEL OF CIRCUIT ORIGIN BOTTOM INDICATES CIRCUIT NUMBER HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN PARTIAL HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN CONDUIT CONCEALED IN WALL OR ABOVE CEILING CONDUIT BELOW GRADE OR EMBEDDED IN CONCRETE LINE VOLTAGE CIRCUIT CONDUCTORS SHORT = HOT/TRACER/SWITCH LEG CONDUCTOR LONG = NEUTRAL (GROUNDED) CONDUCTOR CURVED = GROUNDING (BONDING) CONDUCTOR CONDUIT STUB OUT WITH NYLON END BUSHING CONDUIT TURNED UP CONDUIT TURNED DOWN GROUNDING CONNECTION PP 2 3 K m OS OS2 T J C DT D tv TV UG T UG E UG FIRE ALARM SYMBOLS P R FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATOR PANEL MANUAL PULL STATION HEAT DETECTOR SMOKE DETECTOR ADDRESSABLE MONITORING MODULE NOTIFICATION HORN APPLIANCE NOTIFICATION STROBE APPLIANCE NOTIFICATION HORN/STROBE APPLIANCE FIRE ALARM RELAY ELECTROMAGNETIC DOOR HOLDER SMOKE DAMPER OR COMBINATION FIRE/SMOKE DAMPER FIRE SPRINKLER FLOW SWITCH FIRE SPRINKLER TAMPER SWITCH FIRE SPRINKLER BELL/GONG OR HORN/STROBE 120V COMBINATION CO/SMOKE ALARM 120V, 177cd XENON STROBE SITE ELECTRICAL SYMBOLS UNDERGROUND ELECTRICAL SERVICE LATERAL UNDERGROUND ELECTRICAL PRIMARY UNDERGROUND TELEPHONE SERVICE UNDERGROUND CATV SERVICE POLE MOUNTED AREA LIGHT GRADE MOUNTED LIGHT RECESSED DOWNLIGHT/FLAG UPLIGHT POWER COMPANY PAD MOUNTED UTILITY TRANSFORMER POWER COMPANY UTILITY POLE SD AM TR HS FIRE ALARM DEVICE MOUNTING 1. VISUAL UNIT DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP 6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA) 2. AUDIO UNIT DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP 6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA) *TOP OF UNIT NOT LESS THAN 90" ABOVE FLOOR AND NOT LESS THAN 6" BELOW CEILING (NFPA) (BOTTOM AT 88" WITH CMU COURSES). MOUNT AT NFPA HEIGHT ONLY IF REQUIRED BY LOCAL AHJ. 3. AUDIO/VISUAL UNIT DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP 6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA) 4. PULL STATION HIGHEST OPERABLE PART SHALL NOT BE MORE THAN 48" ABOVE THE FLOOR (FRONT APPROACH) (PER ADA) ELECTRICAL DEVICE MOUNTING HEIGHTS No Scale 1 9" 16" 48" 54" 64" 80" 88" 90" AREA ALLOWED IF SIDE REACH IS POSSIBLE AREA ALLOWED IF SIDE REACH IS POSSIBLE 6" MIN. 72" FIRE ALARM POWER & TELECOM 9" 16" 48" 54" 64" 80" 88" 90" 72" TELECOM OUTLET RECEPTACLE GROUND BAR MANUAL PULL STATION REMOTE ANNUNCIATOR WALL SWITCH HVAC THERMOSTAT PHONE OUTLET CATV OUTLET * HORN/STROBE HORN STROBE HORN FIRE FIRE FIRE FIRE GENERAL SYMBOLS DETAIL REFERENCE DETAIL NUMBER SHEET NUMBER ELEVATION REFERENCE DETAIL NUMBER SHEET NUMBER SECTION CUT DETAIL NUMBER SHEET NUMBER KEYED PLAN NOTE REVISION NOTE ELEVATION CONNECT TO EXISTING. FIELD VERIFY LOCATION & MATERIAL OF EXISTING # ## # ## # ## # MECHANICAL AND ELECTRICAL SYMBOLS AND ABBREVIATIONS A ABOVE FINISH FLOOR AFF ABOVE FINISH GRADE AFG ACRYLONITRILE BUTADIENE STYRENE PIPE ABS AIR CONDITIONING A/C AIR HANDLING UNIT AHU ALTERNATING CURRENT AC ALUMINUM AL AMERICAN NATIONAL STANDARDS INSTITUTE ANSI AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASME AMERICAN WIRE GAUGE AWG AMERICANS WITH DISABILITIES ACT ADA AMPERE AMP or A ANALOG INPUT AI ANALOG OUTPUT AO ARCHITECT or ARCHITECTURAL ARCH AUTHORITY HAVING JURISDICTION AHJ AUTOMATIC TRANSFORMER SWITCH ATS B BELOW CEILING BC BELOW GRADE BG BINARY INPUT BI BINARY OUTPUT BO BOOT WASH BW BRITISH THERMAL UNIT BTU BTUs PER HOUR BTUH BUILDING BLDG C CABLE TELEVISION CATV CAPACITY CAP CATEGORY CAT CEILING MOUNT CLG CELSIUS C CHILLED WATER CHW CHILLED WATER RETURN CHWR CHILLED WATER SUPPLY CHWS CIRCUIT BREAKER CB CLEANOUT CO CLOTHES WASHER CONNECTION BOX CCB COLD WATER (DOMESTIC) CW COMMON C CONCRETE CONC CONDENSING UNIT CU CONDUIT C CONDUIT ONLY (WITH PULL STRING) CO COPPER CU COUNTER TOP CT CROSS-LINKED POLYETHYLENE PIPE PEX CUBIC FEET PER MINUTE CFM CUBIC YARD CU YD D DEPTH or DEEP D DIRECT CURRENT DC DIRECT DIGITAL CONTROL DDC DIRECT EXPANSION DX DISCONNECT SWITCH DS DISH WASHER DW DRINKING FOUNTAIN DF DRY BULB DB E ELECTRIC or ELECTRICAL E or ELEC ELECTRIC WATER COOLER EWC ELECTRIC HEATER EH ELECTRICAL CONTRACTOR EC ELECTRICAL METALLIC TUBING EMT ENTERING AIR TEMPERATURE EAT ENTERING WATER TEMPERATURE EWT EQUIPMENT EQUIP EXHAUST EXH EXHAUST AIR EA EXHAUST FAN EF EXHAUST GRILLE EG EXISTING EXIST EXISTING TO REMAIN ETR EXTERNAL STATIC PRESSURE ESP F FAHRENHEIT F FAN COIL UNIT FCU FEET FT FEET PER MINUTE FPM FIBER OPTIC CABEL FOC FINISH FLOOR CLEAN OUT FFCO FINISH GRADE FG FINISH GRADE CLEAN OUT FGCO FIRE ALARM FA FLEXIBLE METALLIC CONDUIT FMC FLOOR DRAIN FD FLOOR SINK FS G GALLON GAL GALLONS PER FLUSH GPF GALLONS PER HOUR GPH GALLONS PER MINUTE GPM GALVANIZED RIGID STEEL CONDUIT GRC GAS G GAUGE GA GENERAL CONTRACTOR GC GLOBAL POSITIONING SYSTEM GPS GOVERNMENT FURNISHED/CONTRACTOR INSTALLED GFCI GOVERNMENT FURNISHED/GOVERNMENT INSTALLED GFGI GROUNDING ELECTRODE CONDUCTOR GEC GROUNDING (BONDING) CONDUCTOR G GROUND FAULT CIRCUIT INTERRUPTER GFI GROUND FAULT PROTECTION FOR EQUIPMENT GFPE H HANDHOLE HH HEATING HTG HEATING WATER RETURN HR HEATING WATER SUPPLY HS HIGH DENSITY POLYETHYLENE CONDUIT HDPE HORSEPOWER HP HOT GAS RE-HEAT HGRH HOT WATER (DOMESTIC) HW HOT WATER HEATER HWH HOT WATER PUMP HWP HOT WATER RECIRC. (DOMESTIC) HWR HOUR HR K KELVIN K KILOWATT KW L LAUNDRY TUB LT LAVATORY LAV LEAVING AIR TEMPERATURE LAT LEAVING WATER TEMPERATURE LWT LIGHTING LTG LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMC M KCMIL (THOUSAND CIRCULAR MILLS) MCM MAIN CIRCUIT BREAKER MCB MAIN LUG ONLY MLO MANHOLE MH MANUFACTURER MANUF MAXIMUM MAX MAXIMUM OVERCURRENT PROTECTION MOCP MECHANICAL CONTRACTOR MC MINIMUM MIN MINIMUM CIRCUIT AMPACITY MCA NEMA RATED MOTOR STARTER MS MOUNTED MTD MULTIMODE MM N NATIONAL ELECTRICAL CODE (NFPA 70) NEC NATIONAL ELECTRICAL MANUFACTURER'S ASSOC. NEMA NATIONAL FIRE PROTECTION ASSOCIATION NFPA NATIONALLY RECOGNIZED TESTING LABORATORY NRTL NATURAL GAS G or NAT GAS NEUTRAL (GROUNDED) CONDUCTOR N NOMINAL NOM NON FUSED NF NORMALLY CLOSED NC NORMALLY OPEN NO NORTH N NOT APPLICABLE N/A NOT TO SCALE NTS O ON CENTER O.C. OUTDOOR AIR OA OUTSIDE DIAMETER OD OUTSIDE PLANT CABLE OSP OVERHEAD OH P PASSIVE INFRARED PIR PHASE PH OR Ø POLYVINYL CHLORIDE PVC POLYVINYL CHLORIDE CONDUIT PVC POUNDS LBS POUNDS PER SQUARE INCH PSI PRESSURE REDUCING VALVE PRV PULL BOX PB R RECEPTACLE RCPT REQUIRED REQ'D RETURN AIR RA RETURN GRILLE RG ROOF TOP UNIT RTU REVOLUTIONS PER MINUTE RPM S SENSIBLE SENS SERVICE ENTRANCE SWITCHBOARD SES SERVICE SINK SS SHOWER SH SINGLE MODE SM SINGLE POLE, DOUBLE THROW SPDT SPECIFICATIONS SPEC SQUARE FEET SQ FT or SF STRAND ST SUPPLY AIR SA SUPPLY DIFFUSER SD SURGE PROTECTION DEVICE SPD T TAMPERPROOF ENCLOSURE TP TELECOMMUNICATIONS ROOM TR TELEPHONE T TELEVISION TV TEMPERATURE (CHANGE IN) TEMP ( T) TEMPERATURE/PRESSURE T/P TEMPERATURE CONTROL CONTRACTOR TC THOUSAND BTUs PER HOUR MBH TOTAL TOT TRANSIENT VOLTAGE SURGE SUPPRESSION TVSS TYPICAL TYP U UNDERGROUND UG UNDERWRITERS LABRATORIES UL UNINTERRUPTIBLE POWER SUPPLY UPS UNLESS NOTED OTHERWISE UNO UNSHIELDED TWISTED PAIR UTP V VENT BELOW SLAB VBS VENT THROUGH ROOF VTR VENTILATION FAN VF VOLT-AMPERES VA VOLTS V VOLTS ALTERNATING CURRENT VAC W WALL HYDRANT WH WASH TUB WT WATER CLOSET WC WATER COLUMN (in inches) "WC WATER SERVICE W WATT(S) W WEATHERPROOF ENCLOSURE WP WET BULB WB WIRE WAY WW WITH W/ X TRANSFORMER XFMR MECHANICAL SYMBOLS THERMOSTAT RECTANGULAR RETURN OR RELIEF AIR DUCT UP RECTANGULAR SUPPLY AIR DUCT UP RECTANGULAR SUPPLY AIR DUCT DOWN WALL DIFFUSER SQUARE SUPPLY DIFFUSER - TYPE AND AIRFLOW INDICATED MANUAL BALANCING DAMPER SQUARE RETURN GRILLE - TYPE INDICATED TEMPERATURE SENSOR T FIRE/SMOKE DAMPER BELOW GRADE FINISH FLOOR CLEAN OUT FINISHED GRADE ABOVE FINISHED GRADE UNLESS NOTED OTHERWISE ABOVE FINISHED FLOOR OUTDOOR AIR RETURN AIR SUPPLY AIR TEMPERATURE CONTROL CONTRACTOR GENERAL CONTRACTOR DESIGNATORS/ABBREVIATIONS SYMBOL MODIFICATION BG FFCO FG AFG UNO AFF OA RA SA TC GC FINISH WALL CLEAN OUT FWCO FINISH GRADE CLEAN OUT FGCO RECTANGULAR RETURN OR RELIEF AIR DUCT UP FIRE DAMPER MECHANICAL CONTRACTOR MC DIRECT DIGITAL CONTROL DDC ELECTRICAL CONTRACTOR EC ROUND DUCT UP ROUND DUCT DOWN FLEXIBLE DUCTWORK - MAX 5' CONTROL CABLE, VERIFY TYPE WITH EQUIPMENT MANUFACTURER T RIGID DUCT RUNOUT 90° ELBOW WITH TURNING VANES GRILLE/DIFFUSER TAG TOP: DEVICE TAG (SEE SCHEDULE) MIDDLE: NECK SIZE BOTTOM: AIRFLOW XX XX X RECTANGULAR RETURN OR EXHAUST AIR DUCT DOWN PLUMBING SYMBOLS PIPE TURNING DOWN PIPE TURNING UP CONDENSATE DRAIN LINE D SANITARY DRAIN BELOW GRADE SANITARY DRAIN ABOVE GRADE SANITARY VENT DOMESTIC COLD WATER DOMESTIC HOT WATER DOMESTIC HOT WATER RECIRC WATER SERVICE PIPING FIRE PROTECTION PIPING NATURAL GAS G TEMPERED DOMESTIC WATER T BALL VALVE CHECK VALVE GATE VALVE BUTTERFLY VALVE STRAINER THERMOMETER GAUGE TEST PORT FLOW CONTROL VALVE GAS COCK SOLENOID VALVE PRESSURE REDUCING VALVE NATURAL GAS REGULATOR R GREASE SANITARY DRAIN BELOW GRADE GR UNION W FP # NEW SENIOR LIVING UNITS KERVILLE, TEXAS [email protected] 4809 Vue Du Lac Place, Suite 201 Manhattan, Kansas 66503 785.587.8042 FAX 785.587.8039 LST Consulting Engineers, PA Project 20026 MARCH 2021 ME0.1

20026 ME0.1 Symbols

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

STATIC LED TROFFER

PENDANT OR SURFACE MOUNTED LINEAR LUMINAIRE

LED STRIP LIGHT

SURFACE MOUNTED ROUND LIGHT

RECESSED DOWNLIGHT

WALL MOUNTED LUMINAIRE

DECORATIVE PENDANT

SINGLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH

DIRECTIONAL ARROWS AS INDICATED ON PLANS

DOUBLE FACE EXIT SIGN - WALL AND CEILING MOUNTED WITH

DIRECTIONAL ARROWS AS INDICATED ON PLANS

REMOTE EMERGENCY LIGHTING UNIT

LIGHTING SYMBOLS

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

SPECIAL RECEPTACLE (# = NEMA CONFIGURATION)

FLUSH FLOOR DUPLEX RECEPTACLE

SINGLE POLE WALL SWITCH

TWO POLE WALL SWITCH

THREE WAY WALL SWITCH

KEYED WALL SWITCH

SINGLE POLE, DOUBLE THROW (SPDT) SWITCH (CENTER OFF)

MOTOR HP RATED SWITCH WITHOUT OVERLOAD PROTECTION

MECHANICAL DIAL TIMER WALL SWITCH

LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH

DUAL RELAY LINE VOLTAGE OCCUPANCY SENSING WALL SWITCH

LOW VOLTAGE OCCUPANCY SENSOR

POWER PACK FOR LOW VOLTAGE OCCUPANCY SENSORS

LIGHTING CONTACTOR

EXTERIOR PHOTOCELL

CONTACTOR

PUSH BUTTON OPERATOR

CLASS 2 TRANSFORMER POWER SUPPLY

DOOR ANNUNCIATOR A/V HORN STROBE

JUNCTION BOX

MOTOR

MOTORIZED DAMPER

DISCONNECT SWITCH

BRANCH CIRCUIT PANELBOARD

SWITCHBOARD

POWER SYMBOLS

#

LC

os

P

TELECOMMUNICATIONS SYMBOLS

APARTMENT PHONE OUTLET

TELECOMMUNICATIONS OUTLET

APARTMENT CATV OUTLET

TELEPHONE TERMINAL BOARD

CLG CEILING MOUNTED

• FLUSH MOUNTED IN SUSPENDED OR HARD CEILINGS

• SURFACE MOUNTED TO STRUCTURE ABOVE IN OPEN CEILINGS

CT MOUNT BOTTOM OF DEVICE AT 6" ABOVE COUNTERTOP

EM PROVIDE LUMINAIRE WITH EMERGENCY BATTERY BACKUP

GFI GROUND FAULT CIRCUIT INTERRUPTING DEVICE

NL NIGHTLIGHT WIRED TO UNSWITCHED HOT CONDUCTOR

WP PROVIDE WEATHERPROOF ENCLOSURE FOR DEVICE

XX" MOUNTING HEIGHT OF DEVICE ABOVE FINISHED FLOOR

SYMBOL MODIFYING DESIGNATORS

##

##

CIRCUIT AND RACEWAY SYMBOLS

CIRCUIT DESIGNATION:

TOP INDICATES PANEL OF CIRCUIT ORIGIN

BOTTOM INDICATES CIRCUIT NUMBER

HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN

PARTIAL HOMERUN - WIRING TO PANEL OF CIRCUIT ORIGIN

CONDUIT CONCEALED IN WALL OR ABOVE CEILING

CONDUIT BELOW GRADE OR EMBEDDED IN CONCRETE

LINE VOLTAGE CIRCUIT CONDUCTORS

SHORT = HOT/TRACER/SWITCH LEG CONDUCTOR

LONG = NEUTRAL (GROUNDED) CONDUCTOR

CURVED = GROUNDING (BONDING) CONDUCTOR

CONDUIT STUB OUT WITH NYLON END BUSHING

CONDUIT TURNED UP

CONDUIT TURNED DOWN

GROUNDING CONNECTION

PP

2

3

K

m

OS

OS2

T

J

C

DT

D

tv

TV UG

T UG

E UG

FIRE ALARM SYMBOLS

P

R

FIRE ALARM CONTROL PANEL

FIRE ALARM REMOTE ANNUNCIATOR PANEL

MANUAL PULL STATION

HEAT DETECTOR

SMOKE DETECTOR

ADDRESSABLE MONITORING MODULE

NOTIFICATION HORN APPLIANCE

NOTIFICATION STROBE APPLIANCE

NOTIFICATION HORN/STROBE APPLIANCE

FIRE ALARM RELAY

ELECTROMAGNETIC DOOR HOLDER

SMOKE DAMPER OR COMBINATION FIRE/SMOKE DAMPER

FIRE SPRINKLER FLOW SWITCH

FIRE SPRINKLER TAMPER SWITCH

FIRE SPRINKLER BELL/GONG OR HORN/STROBE

120V COMBINATION CO/SMOKE ALARM

120V, 177cd XENON STROBE

SITE ELECTRICAL SYMBOLS

UNDERGROUND ELECTRICAL SERVICE LATERAL

UNDERGROUND ELECTRICAL PRIMARY

UNDERGROUND TELEPHONE SERVICE

UNDERGROUND CATV SERVICE

POLE MOUNTED AREA LIGHT

GRADE MOUNTED LIGHT

RECESSED DOWNLIGHT/FLAG UPLIGHT

POWER COMPANY PAD MOUNTED UTILITY TRANSFORMER

POWER COMPANY UTILITY POLE

SD

AM

TR

HS

FIRE ALARM DEVICE MOUNTING

1. VISUAL UNIT

DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP

6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)

2. AUDIO UNIT

DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP

6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)

*TOP OF UNIT NOT LESS THAN 90" ABOVE FLOOR AND NOT

LESS THAN 6" BELOW CEILING (NFPA) (BOTTOM AT 88"

WITH CMU COURSES). MOUNT AT NFPA HEIGHT ONLY IF

REQUIRED BY LOCAL AHJ.

3. AUDIO/VISUAL UNIT

DEVICE BOTTOM 80" ABOVE HIGHEST FLOOR LEVEL OR TOP

6" BELOW CEILING; WHICHEVER IS LOWER (PER ADA)

4. PULL STATION

HIGHEST OPERABLE PART SHALL NOT BE MORE THAN 48"

ABOVE THE FLOOR (FRONT APPROACH) (PER ADA)ELECTRICAL DEVICE MOUNTING HEIGHTS

No Scale1

9"

16"

48"

54"

64"

80"

88"90"

AREA ALLOWED IF SIDE REACH IS POSSIBLE

AREA ALLOWED IF SIDE REACH IS POSSIBLE

6" MIN.

72"

FIRE ALARMPOWER & TELECOM

9"

16"

48"

54"

64"

80"

88"90"

72"

TELECOM

OUTLETRECEPTACLE

GROUND

BAR

MANUAL

PULL

STATION

REMOTE

ANNUNCIATOR

WALL

SWITCH

HVAC

THERMOSTAT

PHONE

OUTLET

CATV

OUTLET

*

HORN/STROBEHORNSTROBE

HORN

FIRE FIRE

FIRE

FIRE

GENERAL SYMBOLS

DETAIL REFERENCE

DETAIL NUMBER

SHEET NUMBER

ELEVATION REFERENCE

DETAIL NUMBER

SHEET NUMBER

SECTION CUT

DETAIL NUMBER

SHEET NUMBER

KEYED PLAN NOTE

REVISION NOTE

ELEVATION

CONNECT TO EXISTING. FIELD VERIFY LOCATION &

MATERIAL OF EXISTING

#

##

#

##

#

##

#

MECHANICAL AND ELECTRICAL SYMBOLS AND ABBREVIATIONS

AABOVE FINISH FLOOR AFF

ABOVE FINISH GRADE AFG

ACRYLONITRILE BUTADIENE STYRENE PIPE ABS

AIR CONDITIONING A/C

AIR HANDLING UNIT AHU

ALTERNATING CURRENT AC

ALUMINUM AL

AMERICAN NATIONAL STANDARDS INSTITUTE ANSI

AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASME

AMERICAN WIRE GAUGE AWG

AMERICANS WITH DISABILITIES ACT ADA

AMPERE AMP or A

ANALOG INPUT AI

ANALOG OUTPUT AO

ARCHITECT or ARCHITECTURAL ARCH

AUTHORITY HAVING JURISDICTION AHJ

AUTOMATIC TRANSFORMER SWITCH ATS

BBELOW CEILING BC

BELOW GRADE BG

BINARY INPUT BI

BINARY OUTPUT BO

BOOT WASH BW

BRITISH THERMAL UNIT BTU

BTUs PER HOUR BTUH

BUILDING BLDG

CCABLE TELEVISION CATV

CAPACITY CAP

CATEGORY CAT

CEILING MOUNT CLG

CELSIUS C

CHILLED WATER CHW

CHILLED WATER RETURN CHWR

CHILLED WATER SUPPLY CHWS

CIRCUIT BREAKER CB

CLEANOUT CO

CLOTHES WASHER CONNECTION BOX CCB

COLD WATER (DOMESTIC) CW

COMMON C

CONCRETE CONC

CONDENSING UNIT CU

CONDUIT C

CONDUIT ONLY (WITH PULL STRING) CO

COPPER CU

COUNTER TOP CT

CROSS-LINKED POLYETHYLENE PIPE PEX

CUBIC FEET PER MINUTE CFM

CUBIC YARD CU YD

DDEPTH or DEEP D

DIRECT CURRENT DC

DIRECT DIGITAL CONTROL DDC

DIRECT EXPANSION DX

DISCONNECT SWITCH DS

DISH WASHER DW

DRINKING FOUNTAIN DF

DRY BULB DB

EELECTRIC or ELECTRICAL E or ELEC

ELECTRIC WATER COOLER EWC

ELECTRIC HEATER EH

ELECTRICAL CONTRACTOR EC

ELECTRICAL METALLIC TUBING EMT

ENTERING AIR TEMPERATURE EAT

ENTERING WATER TEMPERATURE EWT

EQUIPMENT EQUIP

EXHAUST EXH

EXHAUST AIR EA

EXHAUST FAN EF

EXHAUST GRILLE EG

EXISTING EXIST

EXISTING TO REMAIN ETR

EXTERNAL STATIC PRESSURE ESP

FFAHRENHEIT F

FAN COIL UNIT FCU

FEET FT

FEET PER MINUTE FPM

FIBER OPTIC CABEL FOC

FINISH FLOOR CLEAN OUT FFCO

FINISH GRADE FG

FINISH GRADE CLEAN OUT FGCO

FIRE ALARM FA

FLEXIBLE METALLIC CONDUIT FMC

FLOOR DRAIN FD

FLOOR SINK FS

GGALLON GAL

GALLONS PER FLUSH GPF

GALLONS PER HOUR GPH

GALLONS PER MINUTE GPM

GALVANIZED RIGID STEEL CONDUIT GRC

GAS G

GAUGE GA

GENERAL CONTRACTOR GC

GLOBAL POSITIONING SYSTEM GPS

GOVERNMENT FURNISHED/CONTRACTOR INSTALLED GFCI

GOVERNMENT FURNISHED/GOVERNMENT INSTALLED GFGI

GROUNDING ELECTRODE CONDUCTOR GEC

GROUNDING (BONDING) CONDUCTOR G

GROUND FAULT CIRCUIT INTERRUPTER GFI

GROUND FAULT PROTECTION FOR EQUIPMENT GFPE

H

HANDHOLE HH

HEATING HTG

HEATING WATER RETURN HR

HEATING WATER SUPPLY HS

HIGH DENSITY POLYETHYLENE CONDUIT HDPE

HORSEPOWER HP

HOT GAS RE-HEAT HGRH

HOT WATER (DOMESTIC) HW

HOT WATER HEATER HWH

HOT WATER PUMP HWP

HOT WATER RECIRC. (DOMESTIC) HWR

HOUR HR

KKELVIN K

KILOWATT KW

LLAUNDRY TUB LT

LAVATORY LAV

LEAVING AIR TEMPERATURE LAT

LEAVING WATER TEMPERATURE LWT

LIGHTING LTG

LIQUIDTIGHT FLEXIBLE METAL CONDUIT LFMC

MKCMIL (THOUSAND CIRCULAR MILLS) MCM

MAIN CIRCUIT BREAKER MCB

MAIN LUG ONLY MLO

MANHOLE MH

MANUFACTURER MANUF

MAXIMUM MAX

MAXIMUM OVERCURRENT PROTECTION MOCP

MECHANICAL CONTRACTOR MC

MINIMUM MIN

MINIMUM CIRCUIT AMPACITY MCA

NEMA RATED MOTOR STARTER MS

MOUNTED MTD

MULTIMODE MM

NNATIONAL ELECTRICAL CODE (NFPA 70) NEC

NATIONAL ELECTRICAL MANUFACTURER'S ASSOC. NEMA

NATIONAL FIRE PROTECTION ASSOCIATION NFPA

NATIONALLY RECOGNIZED TESTING LABORATORY NRTL

NATURAL GAS G or NAT GAS

NEUTRAL (GROUNDED) CONDUCTOR N

NOMINAL NOM

NON FUSED NF

NORMALLY CLOSED NC

NORMALLY OPEN NO

NORTH N

NOT APPLICABLE N/A

NOT TO SCALE NTS

OON CENTER O.C.

OUTDOOR AIR OA

OUTSIDE DIAMETER OD

OUTSIDE PLANT CABLE OSP

OVERHEAD OH

PPASSIVE INFRARED PIR

PHASE PH OR Ø

POLYVINYL CHLORIDE PVC

POLYVINYL CHLORIDE CONDUIT PVC

POUNDS LBS

POUNDS PER SQUARE INCH PSI

PRESSURE REDUCING VALVE PRV

PULL BOX PB

RRECEPTACLE RCPT

REQUIRED REQ'D

RETURN AIR RA

RETURN GRILLE RG

ROOF TOP UNIT RTU

REVOLUTIONS PER MINUTE RPM

SSENSIBLE SENS

SERVICE ENTRANCE SWITCHBOARD SES

SERVICE SINK SS

SHOWER SH

SINGLE MODE SM

SINGLE POLE, DOUBLE THROW SPDT

SPECIFICATIONS SPEC

SQUARE FEET SQ FT or SF

STRAND ST

SUPPLY AIR SA

SUPPLY DIFFUSER SD

SURGE PROTECTION DEVICE SPD

TTAMPERPROOF ENCLOSURE TP

TELECOMMUNICATIONS ROOM TR

TELEPHONE T

TELEVISION TV

TEMPERATURE (CHANGE IN) TEMP (∆T)

TEMPERATURE/PRESSURE T/P

TEMPERATURE CONTROL CONTRACTOR TC

THOUSAND BTUs PER HOUR MBH

TOTAL TOT

TRANSIENT VOLTAGE SURGE SUPPRESSION TVSS

TYPICAL TYP

UUNDERGROUND UG

UNDERWRITERS LABRATORIES UL

UNINTERRUPTIBLE POWER SUPPLY UPS

UNLESS NOTED OTHERWISE UNO

UNSHIELDED TWISTED PAIR UTP

VVENT BELOW SLAB VBS

VENT THROUGH ROOF VTR

VENTILATION FAN VF

VOLT-AMPERES VA

VOLTS V

VOLTS ALTERNATING CURRENT VAC

WWALL HYDRANT WH

WASH TUB WT

WATER CLOSET WC

WATER COLUMN (in inches) "WC

WATER SERVICE W

WATT(S) W

WEATHERPROOF ENCLOSURE WP

WET BULB WB

WIRE WAY WW

WITH W/

XTRANSFORMER XFMR

MECHANICAL SYMBOLS

THERMOSTAT

RECTANGULAR RETURN OR RELIEF AIR DUCT UP

RECTANGULAR SUPPLY AIR DUCT UP

RECTANGULAR SUPPLY AIR DUCT DOWN

WALL DIFFUSER

SQUARE SUPPLY DIFFUSER - TYPE AND AIRFLOW INDICATED

MANUAL BALANCING DAMPER

SQUARE RETURN GRILLE - TYPE INDICATED

TEMPERATURE SENSORT

FIRE/SMOKE DAMPER

BELOW GRADE

FINISH FLOOR CLEAN OUT

FINISHED GRADE

ABOVE FINISHED GRADE

UNLESS NOTED OTHERWISE

ABOVE FINISHED FLOOR

OUTDOOR AIR

RETURN AIR

SUPPLY AIR

TEMPERATURE CONTROL CONTRACTOR

GENERAL CONTRACTOR

DESIGNATORS/ABBREVIATIONS

SYMBOL MODIFICATION

BG

FFCO

FG

AFG

UNO

AFF

OA

RA

SA

TC

GC

FINISH WALL CLEAN OUTFWCO

FINISH GRADE CLEAN OUTFGCO

RECTANGULAR RETURN OR RELIEF AIR DUCT UP

FIRE DAMPER

MECHANICAL CONTRACTORMC

DIRECT DIGITAL CONTROLDDC

ELECTRICAL CONTRACTOREC

ROUND DUCT UP

ROUND DUCT DOWN

FLEXIBLE DUCTWORK - MAX 5'

CONTROL CABLE, VERIFY TYPE WITH EQUIPMENT MANUFACTURER

T

RIGID DUCT RUNOUT

90° ELBOW WITH TURNING VANES

GRILLE/DIFFUSER TAG

TOP: DEVICE TAG (SEE SCHEDULE)

MIDDLE: NECK SIZE

BOTTOM: AIRFLOW

XX

XX

X

RECTANGULAR RETURN OR

EXHAUST AIR DUCT DOWN

PLUMBING SYMBOLS

PIPE TURNING DOWN

PIPE TURNING UP

CONDENSATE DRAIN LINED

SANITARY DRAIN BELOW GRADE

SANITARY DRAIN ABOVE GRADE

SANITARY VENT

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RECIRC

WATER SERVICE PIPING

FIRE PROTECTION PIPING

NATURAL GASG

TEMPERED DOMESTIC WATERT

BALL VALVE

CHECK VALVE

GATE VALVE

BUTTERFLY VALVE

STRAINER

THERMOMETER

GAUGE

TEST PORT

FLOW CONTROL VALVE

GAS COCK

SOLENOID VALVE

PRESSURE REDUCING VALVE

NATURAL GAS REGULATORR

GREASE SANITARY DRAIN BELOW GRADEGR

UNION

W

FP

#

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

ME0.1

1" = 20'-0"

ELECTRICAL SITE PLAN1

4CONDUIT TRENCH DETAILS

No Scale

12

"

36

" M

IN C

OV

ER

FINISHED GRADE

SECTION "B"

12

"

FINISHED GRADE

SECTION "C"

12" MIN SEPARATION

3" SAND

ENCASEMENT

CONDUITS AS

INDICATED ON

DRAWINGS

BACKFILL

COMPACTED TO

95% RELATIVE

DENSITY

PLASTIC

CAUTION TAPE

3" SAND

ENCASEMENT

CONDUITS AS

INDICATED ON

DRAWINGS

BACKFILL

COMPACTED TO

95% RELATIVE

DENSITY

PLASTIC

CAUTION TAPE

12

"

48

" M

IN D

EPTH

FINISHED GRADE

SECTION "A"

3" SAND

ENCASEMENT

CONDUIT AS

INDICATED ON

DRAWINGS

BACKFILL

COMPACTED TO

95% RELATIVE

DENSITY

PLASTIC

CAUTION TAPE

36

" M

IN C

OV

ER F

OR

PO

WER

24"

MIN

IMU

M C

OV

ER

FO

R T

ELEC

OM

M

S

S

S

S

R2

R2R2

R3 R3 R3R3

R3 R3

R3

R3

R1

2"

MONUMENT LIGHT DETAIL

No Scale2

FLOODLIGHT WITH TILT

MOUNT FITTING

LIGHTING POLE

HAND HOLE

3" 3"

GROUT BETWEEN POLE

BASE PLATE AND TOP OF

CONCRETE BASE

3/4" CHAMFERED

CORNERS

#4 BAR HOOPS AT 16" O.C.

LAP ENDS 16" MIN.

(8) #6 VERTICAL BARS

EQUALLY SPACED

RIGID STEEL OR PVC

CONDUIT

POLE BASE BOLT DIA

PLUS 3", 18" Ø MIN.

No Scale

CONCRETE POLE BASE DETAIL3

BOND LIGHT POLE

TO GROUND WIRE

BASE COVER ATTACHED

TO POLE BASE

FINISHED GRADE

1"Ø ANCHOR BOLT.

NUMBER AND PLACEMENT

PER MANUFACTURER'S

RECOMMENDATIONS

HDPE OR PVC

CONDUIT

#6 GND IN 1"C

5/8"Ø x 10'

GROUND ROD

3'-0"

5'-0"

3/4" CONDUIT AT

MINIMUM 24" BELOW

GRADE, TYPICAL

WEATHERPROOF

JUNCTION BOX WITH

COVER

12" DEEP CONCRETE

PAD

30

A

12

A

16

R4

A

8

NOTES BY SYMBOL

BLDG TRANSFORMER BY UTILITY, CONCRETE PAD BY

GC. COORDINATE EXACT LOCATION AND SIZE WITH

UTILITY.

PROVIDE 4" CONDUIT BELOW GRADE FOR POWER

COMPANY PROVIDED PRIMARY CABLING. INSTALL

PULL ROPE IN RACEWAY. VERIFY TERMINATION POINT

ON SITE WITH LOCAL UTILITY.

SERVICE LATERAL (CONDUIT & WIRE) BY E.C. SEE

RISER DIAGRAMS ON SHEET E6.3.

(2) 4" CONDUITS FOR COMMUNICATIONS SERVICES.

PROVIDE PULL ROPE IN EACH RACEWAY. EXTEND

CONDUITS TO PROPERTY LINE, CAP AND FLAG.

MAKE FINAL CONNECTION TO OWNER PROVIDED

SINGLE PORT EV CHARGING STATION EQUIPMENT.

VERIFY EXACT REQUIREMENTS WITH

MANUFACTURER'S INSTRUCTIONS.

MOUNT RECEPTACLE ON BOLLARD 18" AFG.

COORDINATE EXACT LOCATION AND REQUIREMENTS

WITH G.C.

#

1

2

3

4

5

6

JWP/GFI

A

46

A

43

4

E1.1

B

4

E1.1

A

4

E1.1

B

2

E1.1(TYP)

3

E1.1(TYP)

4

E1.1

A

4

E1.1

C

1

1

2

4

56

3

3

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E1.1

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE

EXACT LOCATION WITH ELEVATOR EQUIPMENT.

2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR

CONTINUOUS OPERATION.

3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.

4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.

5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE

CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S

COMMISSIONING.

6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.

7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.

8. nLIGHT POWER SUPPLY, MODEL NPS 80.

9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.

10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.

# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

PPPP PPPPP P P PPPE E EEE

J E

P

P

PPPPPP

P

P

P

P

P

P

P

P

P P

P

K

J

J

JJ

J J

J

J J

J

J J

JJ

J

J J

J J

J J

J

J

JJ

JJ

J J

J

nL,a

U

EE

J

JJ

JJ J JJ

J

J

J

J

JJ

J

J J

J

MS

MS

MS

MS

U

K

E

OS

OS

P

P

K

K

K

T

P

Y

6'-6" AFF

E1 Y6'-6" AFF

P

P

P

P

P

E1

L18'-0" AFF

L18'-0" AFF

J

XE

XE

XE

OS

OS

OS

OS

XE

XE

EE

E

XE

E

E1

J

J

PP P PP

EF-2

EF-2

EF-2

MR MR

MR MR

MR MR MR

os

os

PP

J

JJ

J

J

J

E

K

XE

E

E

A

5

A

3

A

1

J

D

1

P

os

os

nL,b

nL,a

nL,b

a

a

a

a

a

a

a

a

nL

b

b

b

b

b

b

b

b b

b

b

b

b

b

b

b

b

b

bb

bb

anL

bPS

nL

nL

nL

A

2

A

2

X

X

TO 2ND

FLOOR

TO 2ND

FLOOR

1

2

TC

C

P

4

4

D

7

D

9

2

E4.1

1

E4.1

1

E4.1

1

E4.14

E4.1

AMDP

DD

3

D

5

6

7

7

8

9

9

A

7

MA

TC

HLIN

EM

AT

CH

LIN

E

COORDINATE ROUTING OF CONDUIT ABOVE

FIRST FLOOR COMMON AREA CEILINGS WITH

LOCATIONS OF PRE-MANUFACTURED HOLES IN

BEAMS. SEE STRUCTURAL AND ARCHITECTURAL

DRAWINGS FOR MORE INFORMATION. FINAL

ROUTING SHALL BE COORDINATED WITH G.C.

AND OTHER TRADES PRIOR TO INSTALLATION.

XEPPPPPPE

E

L18'-0" AFF

J J

A

2

X

TO 2ND

FLOOR

L18'-0" AFF

K

K

K

K

E

E

3

E4.1

MA

TC

HLIN

EM

AT

CH

LIN

E

1/8" = 1'-0"

FIRST FLOOR LIGHTING PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.1

1/8" = 1'-0"

PARTIAL FIRST FLOOR LIGHTING PLAN2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J J J

D

L318'-0" AFG

L318'-0" AFG

L318'-0" AFG

L318'-0" AFG

L318'-0" AFG

A

4

L3

18'-0" AFG

os

PP

os

P

P

P

P

P

P

P

P

P

P

P

P

P P P P P

P P

P

P

P

P

K

OS

U

U

OS

OS

P

PK

K

OS

J

J

J

J

J

J J

P PP P P P P P P P PPP P P

JJ

JJ

J

J

J

J

P P PP P PP P PP

J

J

J

J

J

J

J

D

L318'-0" AFG

EF-2

EF-2

EF-2

EF-3

P

PP PP

os

B

1

FROM 1ST

FLOOR

TO 3RD

FLOOR

XE

E

E

XE

X

E

X

XE

E

E

E

E

FROM 1ST

FLOOR

X

B

3

B

5

X

E

J J

FROM 1ST

FLOOR

TO 3RD

FLOOR

E

TO 3RD

FLOOR

JJJ

JJJ

JJJ

J

J

3,D

3,D

os

2

3

3

3

3

3 3

1

E4.1

1

E4.1

1

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

B

1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE

EXACT LOCATION WITH ELEVATOR EQUIPMENT.

2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR

CONTINUOUS OPERATION.

3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.

4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.

5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE

CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S

COMMISSIONING.

6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.

7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.

8. nLIGHT POWER SUPPLY, MODEL NPS 80.

9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.

10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.

# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

1/8" = 1'-0"

SECOND FLOOR LIGHTING PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

P

P

P

P

P

P

P

P

P

P

P

P

P P P P P

P P

P

P

P

P

K

OS

U

U

OS

OS

P

PK

K

OS

J

J

J

J

J

J

J J

3,D

D

P PP P P P P P P P PPP P P

JJ

JJ

J

J

J

J

P P PP P PP P PP

J

J

J

J

J

J

J

J

J

J

J

J

J J

J

J

J

J

3,D

D

J

J

J

EF-2

EF-2

EF-2

EF-3

P

L2

18'-0

" A

FG

L218'-0" AFG

L218'-0" AFG

L218'-0" AFG

L218'-0" AFG

L218'-0" AFG

os

PP PP

os

C

1

FROM 2ND

FLOOR

XE

E

E

XE

X

E

X

XE

E

E

E

E

FROM 2ND

FLOOR

X

C

3

C

5

X

E

J J

FROM 2ND

FLOOR

E

os

2

3 3 3 3 3

1

E4.1

1

E4.11

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

C

1

E4.1

L2

18'-0

" A

FG

A

6

1. LOCATE LIGHT FIXTURE AND SWITCH IN ELEVATOR PIT. COORDINATE

EXACT LOCATION WITH ELEVATOR EQUIPMENT.

2. CONNECT EXHAUST FAN TO UNSWITCHED HOT CONDUCTOR FOR

CONTINUOUS OPERATION.

3. INSTALL LIGHT FIXTURE IN LINE WITH TOP OF 2ND FLOOR WINDOWS.

4. EXTERIOR LIGHTING CONTROLS. SEE 1:E6.1 FOR MORE INFORMATION.

5. DAYLIGHT RESPONSE CONTROLS REQUIRED IN THIS AREA. PROVIDE

CONTROL SYSTEM EQUAL TO ACUITY nLIGHT AND MANUFACTURER'S

COMMISSIONING.

6. nLIGHT CEILING MOUNT PHOTOCELL SENSOR, MODEL NCM ADCX.

7. nLIGHT CEILING MOUNT OCCUPANCY SENSOR, MODEL NCM PDT 9.

8. nLIGHT POWER SUPPLY, MODEL NPS 80.

9. nLIGHT DIMMING RELAY PACK, MODEL NSP5 PCD 2W.

10. nLIGHT WALLPOD SWITCH, MODEL NPODMA DX XX.

# PLAN NOTES BY SYMBOLA. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

1/8" = 1'-0"

THIRD FLOOR LIGHTING PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.3

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT

SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH

EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH

EQUIPMENT PROVIDED.

2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A

DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR

ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF

BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH

CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND

REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE

FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.

3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE

WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V

CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY

TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR

ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.

COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE

EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR

EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO

ELEVATOR CONTROLLER.

4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT

LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.

5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER

CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL

STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.

COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.

6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP

SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.

MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.

7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.

MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.

8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')

THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE

CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .

9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.

MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC

RACEWAY.

10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.

PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT

GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN

ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH

FIRE SPRINKLER SYSTEM INSTALLER.

11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR

POWER TO FIRE PUMP AND ACCESSORIES.

12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.

# PLAN NOTES BY SYMBOL

A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

A

6-20

6-20

6-20

6-20

6-20

6-20

60"

CT

2

E4.1

1

E4.1

1

E4.1

1

E4.14

E4.1

MDP

CTCT/GFICT/GFICT/GFICT/GFICT

CTCT

CT

A

41

A

39

A

37

CT/GFI

CT/GFI

GFI

CTCT

CT

WP/GFI

GFI

GFI

GFI

A

27

A

21A

23

A

25

A

29

A

35

A

33

A

11

A

9

PTAC-07

PTAC-07

PTAC-07

PTAC-07

PTAC-07

PTAC-15

BC-1

HP-1

PTAC-15

PTAC-15

PTAC-07

PTAC-07

HP-3

A

19

A

17

A

15

A

13

6-20

6-20

6-20

6-20

A

18

A

22

A

30

D

31

D

23

D

27D

10

D

12

D

14

A

31

1(TYP)

1(TYP)

A

26

1

(TYP)

A

19

A

15 D

11

D

4

D

2

5

MDP

D

6

D

18

3

2

D

8

4

5

D

D

20

D

16

7

A

38

A

42

SDS

TRANSOCKET

WEST METER CENTER

A

34

WP/GFI

HW

H

HWP

A

45

A

50

8

MA

TC

HLIN

EM

AT

CH

LIN

E

J

D

5

3

E4.1

BC-2

WP/GFI

m

D

35

6

EAST METER CENTER

FIRE PUMP METER

EWH-2

EWH-1

9

D

30

D

24

J

10

D

34

D

22

D

26

D

28

11

MA

TC

HLIN

EM

AT

CH

LIN

E

1/8" = 1'-0"

PARTIAL FIRST FLOOR POWER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.4

RE:

2/E2.4

RE:

2/E2.4

1/8" = 1'-0"

PARTIAL FIRST FLOOR POWER PLAN2

RE:

1/E2.4

RE:1

/E2

.4

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT

SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH

EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH

EQUIPMENT PROVIDED.

2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A

DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR

ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF

BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH

CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND

REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE

FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.

3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE

WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V

CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY

TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR

ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.

COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE

EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR

EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO

ELEVATOR CONTROLLER.

4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT

LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.

5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER

CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL

STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.

COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.

6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP

SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.

MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.

7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.

MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.

8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')

THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE

CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .

9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.

MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC

RACEWAY.

10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.

PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT

GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN

ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH

FIRE SPRINKLER SYSTEM INSTALLER.

11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR

POWER TO FIRE PUMP AND ACCESSORIES.

12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.

# PLAN NOTES BY SYMBOL

A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

72"

72"

72"

84"

84"

GFI

CT/GFI

CT/GFI

GFI

B

6-20

6-20

6-20

1

E4.1

1

E4.1

1

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

B

9

B

7

B

11

B

23

B

25

B

19B

17

B

21

B

27

B

31

PTAC-07

PTAC-07

PTAC-07

BC-4

BC-3

PTAC-07

6-20

B

15

B

13

HP-4 HP-5

HP-2

B

2

m6 B

18B

29

1

(TYP)

B

14

B

10

m

B

22

B

30

B

34 B

B

6

WP/GFI

7 7

7

WP/GFI

HWH-AHWP

B

42

B

38

8

6

1

(TYP)

1/8" = 1'-0"

SECOND FLOOR POWER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.5

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. MOUNT RECEPTACLE FOR PTAC UNIT CONCEALED INSIDE UNIT

SUB-BASE. COORDINATE EXACT LOCATION AND REQUIREMENTS WITH

EQUIPMENT INSTALLER. VERIFY EXACT RECEPTACLE TYPE WITH

EQUIPMENT PROVIDED.

2. 30A/2P FUSED DISCONNECT SWITCH WITH SOLID NEUTRAL AND (1) 20A

DUAL-ELEMENT, TIME DELAY FUSE IN NEMA 1 ENCLOSURE FOR

ELEVATOR CAB LIGHTS & EXHAUST. SWITCH SHALL BE CAPABLE OF

BEING LOCKED "OFF". MOUNT AT 6'-0" AFF TO TOP AND LABEL WITH

CIRCUIT NUMBER. COORDINATE EXACT MOUNTING LOCATION AND

REQUIREMENTS WITH ELEVATOR EQUIPMENT INSTALLER. PROVIDE

FINAL ELECTRICAL CONNECTION TO ELEVATOR CONTROLLER.

3. ELEVATOR POWER MODULE SWITCH: 200A/208V/3P SWITCH COMPLETE

WITH 175A DUAL ELEMENT, TIME DELAY CLASS 'J' FUSES, 120V

CONTROL TRANSFORMER, FIRE ALARM SAFETY INTERFACE RELAY, KEY

TEST SWITCH, GREEN PILOT LIGHT, AUXILIARY CONTACTS FOR

ELEVATOR RECALL, AND FIRE ALARM VOLTAGE MONITORING RELAY.

COOPER BUSSMAN #PS-2-T20-R1-K-G-B-F1 OR EQUAL. COORDINATE

EXACT MOUNTING LOCATION AND REQUIREMENTS WITH ELEVATOR

EQUIPMENT INSTALLER. PROVIDE FINAL ELECTRICAL CONNECTION TO

ELEVATOR CONTROLLER.

4. INSTALL RECEPTACLE ON WALL OF ELEVATOR PIT. VERIFY EXACT

LOCATION WITH ELEVATOR EQUIPMENT INSTALLER.

5. ELEVATOR SUMP PUMP ALARM PANEL. PROVIDE 120V POWER

CONNECTION AND (2) 1" CONDUITS WITH PULL STRINGS FROM PANEL

STUBBED INTO ELEVATOR PIT FOR POWER AND CONTROL CABLING.

COORDINATE ALL WORK WITH PLUMBING CONTRACTOR.

6. PROVIDE 40A/2P, SINGLE THROW, MANUAL MOTOR CONTROLLER SNAP

SWITCH IN NEMA 1 ENCLOSURE. HUBBELL #HBL7842D OR EQUAL.

MAKE FINAL FLEXIBLE CONNECTION TO EQUIPMENT.

7. 30A/2P NON-FUSED DISCONNECT SWITCH IN NEMA 3R ENCLOSURE.

MAKE FINAL CONNECTION TO EQUIPMENT IN LFMC RACEWAY.

8. ROUTE 120V CIRCUIT FOR HOT WATER RECIRCULATION PUMP ('HWP')

THROUGH ADJACENT AQUASTAT AND MAKE FINAL FLEXIBLE

CONNECTION. COORDINATE WITH PLUMBING CONTRACTOR .

9. CONNECT CIRCUIT TO DOMESTIC WATER BOOSTER PUMP CONTROLLER.

MAKE FINAL CONNECTION TO BOOSTER PUMP MOTOR IN LFMC

RACEWAY.

10. 120V POWER FOR FIRE SPRINKLER SYSTEM FLOW SWITCH(ES) AND BELL.

PROVIDE #8 CU BONDING JUMPER FROM CIRCUIT EQUIPMENT

GROUNDING CONDUCTOR TO METAL SPRINKLER SYSTEM PIPING AT AN

ACCESSIBLE LOCATION PER NEC 250.104(B). COORDINATE WORK WITH

FIRE SPRINKLER SYSTEM INSTALLER.

11. REFER TO FIRE PUMP ELECTRICAL SERVICE RISER DIAGRAM, 3/E6.3, FOR

POWER TO FIRE PUMP AND ACCESSORIES.

12. PROVIDE RECEPTACLE IN ATTIC FOR FUTURE RADON FAN.

# PLAN NOTES BY SYMBOL

A. ELECTRICAL EQUIPMENT AND DEVICES SHALL BE "LISTED" AND "IDENTIFIED" AS

RATED FOR A MINIMUM OF 75°C CONDUCTOR TERMINATION.

B. THE CIRCUITING OF ALL LIGHT AND RECEPTACLE OUTLETS HAS BEEN SHOWN ON THE

PLANS, AND THE CONTRACTOR SHALL FOLLOW THIS CIRCUITING LAYOUT .

C. CIRCUIT ALL EMERGENCY LIGHTS, NIGHT LIGHTS AND EXIT LIGHTS TO AN

UNSWITCHED HOT CONDUCTOR , UPSTREAM OF ALL CONTROLS.

D. WALL MOUNTED HVAC CONTROL DEVICES (THERMOSTATS, TEMPERATURE SENSORS,

ETC) SHALL BE PROVIDED BY MECHANICAL CONTRACTOR. UNLESS NOTED

OTHERWISE, ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE GANG WALL BOX AT

46" AFF AND 1/2" CONDUIT STUBBED OUT TO ABOVE ACCESSIBLE CEILING WITH

NYLON BUSHINGS AND PULLSTRING IN RACEWAY. REFER TO MECHANICAL DRAWINGS

FOR LOCATIONS OF DEVICES.

E. COORDINATE INSTALLATION OF ELECTRICAL WORK ABOVE THE CEILING TO PROVIDE

THE GREATEST POSSIBLE CLEARANCE FOR INSTALLATION OF PLUMBING AND

MECHANICAL INSTALLATION. CONDUITS SHALL BE ROUTED THROUGH JOIST WEBS

WHERE POSSIBLE.

F. VERIFY EXACT PLACEMENT OF ALL DEVICES SHOWN ON THE ELECTRICAL

CONSTRUCTION DOCUMENTS WITH ARCHITECTURAL, MECHANICAL AND PLUMBING

DRAWINGS PRIOR TO FINAL PLACEMENT.

G. DEFINITION OF TERMS

* SHALL - ACTION THAT IS REQUIRED WITHOUT OPTION OR QUALIFICATION.

* FURNISH - CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING.

* INSTALL - CONTRACTOR SHALL BE RESPONSIBLE FOR LABOR AND

CONSTRUCTION EQUIPMENT NECESSARY TO SET IN PLACE, CONNECT,

CALIBRATE AND TEST EQUIPMENT FURNISHED BY HIM OR OTHERS.

* PROVIDE - CONTRACTOR SHALL FURNISH AND INSTALL

GENERAL ELECTRICAL NOTES

C

72"

84"

84"

CT/GFI

CT/GFIGFI

6-20

6-20

6-20

6-20

1

E4.1

1

E4.11

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

C

11

C

15

C

13

C

9

C

7

C

25

C

23

C

19

C

17

C

21

PTAC-15

PTAC-07

PTAC-09

PTAC-12

PTAC-07

BC-5

GFI

C

10

C

18

C

14

C

2 1

(TYP)

6-20

C

6

1

(TYP)

m

C

22

6

GFI

GFI

GFI

GFIGFI

GFI

GFI

GFI

GFI

GFI

GFI

C

27 C

29

12

12

12

12

12

12

12

12

12

12

12

1/8" = 1'-0"

THIRD FLOOR POWER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.6

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.

2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.

3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.

4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,

AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.

SEE DETAIL 3:E6.1.

5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC

DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.

6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE

SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE

REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES

IN SERVICE PIPING WITH CIVIL ENGINEER.

7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS

NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING

GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT

BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER

PRIOR TO INSTALLATION OF ANY EQUIPMENT.

8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED

COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL

BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.

9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR

CONTINUATION.

10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER

LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.

11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.

12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S

NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE

APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND

UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT

UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.

13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING

OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.

14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE

WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.

SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#

ALL AUDIBLE NOTIFICATION DEVICES IN

LIVING UNITS SHALL COMPLY WITH LOW

FREQUENCY SIGNALING REQUIREMENTS OF

NFPA 72 SECTION 18.4.5.3

A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS

INDICATED ON SHEET E4.1.

B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x

2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO

MECHANICAL ROOM 107.

C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR

FITTING TO PROTECT CABLING FROM DAMAGE.

D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM

OUTLETS NOT ACTIVATED BY OWNER.

E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.

F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT

AND TESTING SHALL BE PROVIDED BY OWNER.

TELECOMMUNICATIONS GENERAL NOTES

FA

A

75cd

75cd

P

15cd

15cd15cd

P

P

P

15cd

15cd

15cd

75cd

30cd 15cd15cd

15cd

tv

60"

60"

CT

GB

FA

CP

177cd 75cd

15cd

177cd

75cd

11

11

12

12

1

11

11

2

4

3

8

7

2

E4.1

1

E4.1

1

E4.1

1

E4.14

E4.1

R

R

R

AM

R

AM

MA

TC

HLIN

EM

AT

CH

LIN

E

15cd

AM

9

75cd

15cd

15cd

R

5

COORDINATE ROUTING OF CONDUIT ABOVE

FIRST FLOOR COMMON AREA CEILINGS WITH

LOCATIONS OF PRE-MANUFACTURED HOLES IN

BEAMS. SEE STRUCTURAL AND ARCHITECTURAL

DRAWINGS FOR MORE INFORMATION. FINAL

ROUTING SHALL BE COORDINATED WITH G.C.

AND OTHER TRADES PRIOR TO INSTALLATION.

P

15cd

177cd

11

63

E4.1

MA

TC

HLIN

EM

AT

CH

LIN

E

15cd

AM

13

15cd

1/8" = 1'-0"

PARTIAL FIRST FLOOR SPECIAL SYSTEMS PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.7

1/8" = 1'-0"

PARTIAL FIRST FLOOR SPECIAL SYSTEMS PLAN2

RE:

2/E2.7

RE:

2/E2.7

RE:

1/E2.7

RE:

1/E2.7

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.

2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.

3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.

4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,

AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.

SEE DETAIL 3:E6.1.

5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC

DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.

6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE

SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE

REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES

IN SERVICE PIPING WITH CIVIL ENGINEER.

7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS

NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING

GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT

BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER

PRIOR TO INSTALLATION OF ANY EQUIPMENT.

8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED

COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL

BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.

9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR

CONTINUATION.

10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER

LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.

11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.

12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S

NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE

APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND

UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT

UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.

13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING

OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.

14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE

WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.

SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#

ALL AUDIBLE NOTIFICATION DEVICES IN

LIVING UNITS SHALL COMPLY WITH LOW

FREQUENCY SIGNALING REQUIREMENTS OF

NFPA 72 SECTION 18.4.5.3

A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS

INDICATED ON SHEET E4.1.

B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x

2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO

MECHANICAL ROOM 107.

C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR

FITTING TO PROTECT CABLING FROM DAMAGE.

D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM

OUTLETS NOT ACTIVATED BY OWNER.

E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.

F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT

AND TESTING SHALL BE PROVIDED BY OWNER.

TELECOMMUNICATIONS GENERAL NOTES

P P

P

15cd 15cd15cd

15cd

15cd

15cd

15cd

30cd

84"

tv84" 84"

tv84"

75cd

72"

tv72"

15cd

15cd

72"

tv

72"

72"tv

72"

177cd75cd

15cd

R

5

11

11

1

E4.1

1

E4.1

1

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

AM

12

1

75cd

15cd 15cd

14

1/8" = 1'-0"

SECOND FLOOR SPECIAL SYSTEMS PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.8

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

1. ELEVATOR LOBBY SMOKE DETECTOR. SEE DETAIL 3:E6.1.

2. INSTALL HEAT DETECTOR IN ELEVATOR PIT. SEE DETAIL 3:E6.1.

3. ELEVATOR MACHINE ROOM SMOKE AND HEAT DETECTORS. SEE DETAIL 3:E6.1.

4. ADDRESSABLE RELAYS FOR ELEVATOR RECALL, FIREMAN'S HAT, AND POWER SHUNT-TRIP,

AND ADDRESSABLE MONITORING MODULE FOR MONITORING OF SHUNT TRIP VOLTAGE.

SEE DETAIL 3:E6.1.

5. SMOKE DETECTORS AND ADDRESSABLE RELAY FOR CONTROL OF ELECTROMAGNETIC

DOOR HOLDERS. DOORS SHALL RELEASE UPON DETECTION OF SMOKE.

6. PROVIDE ALL REQUIRED FIRE ALARM RELAYS AND MONITORING MODULES FOR ALL FIRE

SPRINKLER FLOW SWITCHES, TAMPER SWITCHES AND BELL/GONG. COORDINATE

REQUIREMENTS WITH FIRE SPRINKLER CONTRACTOR. COORDINATE LOCATIONS OF VALVES

IN SERVICE PIPING WITH CIVIL ENGINEER.

7. TELECOM TERMINAL BOARD: TWO LAYERS OF 3/4" ACX FIRE RESISTANT PLYWOOD (SIZE AS

NOTED) PERMANENTLY FASTENED TO THE WALL BY MEANS OF WALL ANCHORS UTILIZING

GALVANIZED, ZINC PLATED, OR STAINLESS STEEL HARDWARE WITH A FLAT HEAD. MOUNT

BOTTOM AT 6" AFF. PAINT WITH TWO COATS OF LIGHT GRAY FIRE RETARDANT SEALER

PRIOR TO INSTALLATION OF ANY EQUIPMENT.

8. TELECOMMUNICATIONS GROUND BAR: 13-1/4"W x 2"H x 1/4" THICK ELECTRO-TIN PLATED

COPPER BUS BAR, COMPLETE WITH INSULATED STAND-OFFS AND STAINLESS STEEL

BRACKETS, ERICO #TGBA14L06PT OR EQUAL. SEE 4:E6.1.

9. (2) 4" CONDUITS FOR COMMUNICATIONS SERVICES. SEE SITE PLAN, SHEET E1.1, FOR

CONTINUATION.

10. INSTALL SMOKE DETECTOR AND HEAT DETECTOR AT TOP OF ELEVATOR HOISTWAY PER

LOCAL JURISDICTION REQUIREMENTS. SEE DETAIL 1:E6.1.

11. FIRE ALARM SYSTEM COMBINATION CO / SMOKE DETECTOR.

12. FIRE ALARM ADDRESSABLE CONTROL MODULE FOR CONTROL OF APARTMENT UNIT'S

NOTIFICATION APPLIANCE CIRCUIT. MODULE SHALL BE PROGRAMMED TO ACTIVATE

APARTMENT UNIT'S NOTIFICATION APPLIANCES UPON GENERAL BUILDING FIRE ALARM AND

UPON ACTIVATION OF ANY SMOKE DETECTOR OR CO DETECTOR WITHIN APARTMENT

UNIT. MOUNT FLUSH IN WALL AT 8'-0" AFF.

13. PROVIDE REQUIRED ADDRESSABLE FIRE ALARM MONITORING MODULE(S) FOR MONITORING

OF FIRE PUMP EQUIPMENT. VERIFY REQUIREMENTS WITH FIRE PUMP EQUIPMENT INSTALLER.

14. (2) 4" EMT CONDUIT SLEEVES THROUGH FLOOR FOR COMMUNICATIONS CABLING. PROVIDE

WITH FIRESTOPPING FITTINGS (WIREMOLD # FS4R-RED) AT BOTH ENDS.

SPECIAL SYSTEMS PLAN NOTES BY SYMBOL#

ALL AUDIBLE NOTIFICATION DEVICES IN

LIVING UNITS SHALL COMPLY WITH LOW

FREQUENCY SIGNALING REQUIREMENTS OF

NFPA 72 SECTION 18.4.5.3

A. PROVIDE COMPLETE WIRED PHONE AND CATV OUTLETS IN APARTMENT UNITS AS

INDICATED ON SHEET E4.1.

B. AT TELECOMMUNICATIONS OUTLETS IN COMMON AREAS, PROVIDE 4" SQUARE x

2-1/8" DEEP BOX WITH 1-GANG DEVICE RING AND (1) 1" CONDUIT STUBBED INTO

MECHANICAL ROOM 107.

C. PROVIDE NYLON BUSHINGS FOR ALL CONDUIT ENDS NOT CONNECTED TO A BOX OR

FITTING TO PROTECT CABLING FROM DAMAGE.

D. PROVIDE BLANK, STAINLESS STEEL COVER PLATES FOR ALL COMMON AREA TELECOM

OUTLETS NOT ACTIVATED BY OWNER.

E. PROVIDE SUITABLE PULL STRING IN ALL CONDUITS.

F. ALL TELECOM DATA CABLING, JACKS, CONNECTORS, TERMINATIONS, EQUIPMENT

AND TESTING SHALL BE PROVIDED BY OWNER.

TELECOMMUNICATIONS GENERAL NOTES

P P

P

15cd 15cd15cd

15cd

15cd

15cd

15cd

75cd

84"

tv84"

84"

tv84"75cd

72"

tv72"

15cd

15cd

177cd75cd

15cd

R

11

11

10

1

E4.1

1

E4.11

E4.1

1

E4.1

3

E4.1

3

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

1

E4.1

2

E4.1

1

E4.11

E4.1

1

E4.1

1

E4.1

1

E4.1

1

AM

12

15cd 15cd

14

5

1/8" = 1'-0"

THIRD FLOOR SPECIAL SYSTEMS PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E2.9

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

tv

14-50

48"CT

CT

CT

CT

CT

CT/GFI

14-30

b a

D

CT

tv

B1

tv

tv

G

D D

D D

F

b b

bC

CC

D

H

aa

D

DD

a D

2

HWH

a

14-30

3

tv

A6

tv

tv

tv

G

3

CT/GFI

F

F

D

H

D D

2

HWH

tv

14-50

48"CT

CT

CT

CT

CT

b

CT

D

a

tv

a a

a

D D

D D

b b

bC

CC

D

DD

a D

1. PROVIDE NEMA6-20R RECEPTACLE FOR CORD AND PLUG CONNECTION OF PTAC.

VERIFY RECEPTACLE CONFIGURATION WITH PTAC SUPPLIED BY MECHANICAL

CONTRACTOR. INSTALL RECEPTACLE CONCEALED IN UNIT SUB-BASE.

2. CONNECT EXHAUST FAN/LIGHT PROVIDED BY MECHANICAL CONTRACTOR.

3. SWITCH CLOSEST TO THE DOOR SHALL CONTROL ALL LIGHTS IN BATHROOM, AND

THE OTHER SWITCH SHALL CONTROL THE EXHAUST FAN.

4. CEILING MOUNTED SMOKE ALARM IN APARTMENTS TO BE 120VAC WITH 9V BATTERY

BACKUP, INTERCONNECTED TO OTHERS IN SAME APARTMENT. DEVICE SHALL HAVE

CARBON MONOXIDE DETECTOR AND PHOTOELECTRIC TYPE SMOKE DETECTOR WITH

SOUNDER HORN HAVING AN 85dB OUTPUT AT 10', SHALL HAVE A SINGLE BUTTON

FOR TEST/SILENCE AND LED INDICATOR LIGHTS, AND SHALL BE UL 217 LISTED. BRK

#SC7010B OR EQUAL.

5. COORDINATE FINAL LOCATIONS OF ALL CATV AND PHONE OUTLETS WITH OWNER.

SEE 5:E6.1 FOR OUTLET DETAILS.

6. TELECOM DISTRIBUTION DEVICE APPROXIMATELY 4'-0" AFF. SEE DETAIL 5:E6.1.

7. SWITCHED RECEPTACLE BELOW COUNTER FOR GARBAGE DISPOSAL.

8. PROVIDE 120V CONNECTION TO RANGE HOOD/MICROWAVE. STANDARD AND

ADAPTABLE UNITS WILL HAVE MICROWAVE ABOVE RANGE. ACCESSIBLE UNITS WILL

HAVE RANGE HOOD. COORDINATE EXACT ELECTRICAL ROUGH-IN REQUIREMENTS

WITH EQUIPMENT PROVIDED. IF EQUIPMENT IS CORD AND PLUG, PROVIDE

RECEPTACLE INSIDE CABINET ABOVE RANGE.

9. PROVIDE RECEPTACLE BELOW COUNTER FOR CORD AND PLUG CONNECTION OF

DISHWASHER. PROVIDE CORD AND GROUNDING PLUG AS REQUIRED.

10. MOUNT RECEPTACLE IN FACE OF CABINET 6" BELOW COUNTER TOP.

11. PROVIDE PRESET SLIDE DIMMER COMPATIBLE WITH ASSOCIATED LIGHT FIXTURES.

12. SWITCH BOTTOM HALF OF RECEPTACLE AND WIRE TOP HALF TO UNSWITCHED

CIRCUIT.

13. PROVIDE DOOR ANNUNCIATOR SYSTEM A/V HORN/STROBE DEVICE AND LOW

VOLTAGE TRANSFORMER AT ALL ACCESSIBLE APARTMENTS AND ALSO AT

APARTMENTS DESIGNATED FOR HEARING-IMPAIRED GUESTS. REFER TO ARCH

DRAWINGS FOR APPLICABLE ROOMS. INSTALL HORN/STROBE APPLIANCE AT 80" AFF

PER ADA. INSTALL TRANSFORMER IN DOUBLE GANG JUNCTION BOX ABOVE

HORN/STROBE WITH BLANK COVER PLATE AND PROVIDE LOW VOLTAGE CONTROL

WIRING. REFER TO DETAIL 2, SHEET E6.1. PROVIDE ENGRAVED SIGN AT THE

HORN/STROBE DEVICE TO READ "DOOR".

14. PROVIDE PUSH BUTTON AT 48" AFF FOR ANNUNCIATOR SYSTEM AT ALL ACCESSIBLE

APARTMENTS AND ALSO AT APARTMENTS DESIGNATED FOR HEARING-IMPAIRED.

REFER TO ARCH DRAWINGS FOR APPLICABLE ROOMS. REFER TO DETAIL 2, SHEET

E6.1.

15. PROVIDE SWITCH IN ACCESSIBLE UNITS FOR CONTROL OF RANGE HOOD.

16. IN ACCESSIBLE UNITS, INSTALL COUNTERTOP RECEPTACLES A MINIMUM 36" AWAY

FROM CORNER PER FAIR HOUSING ACT DESIGN MANUAL CHAPTER 5 'SIDE REACH

OVER AN OBSTRUCTION' REQUIREMENTS. WHERE AN OBSTRUCTION PREVENTS 36"

DISTANCE REQUIREMENT, INSTALL RECEPTACLE AS FAR FROM CORNER AS

POSSIBLE.PROVIDE ADDITIONAL OUTLETS WITHIN 36" OF CORNER TO ENSURE

COMPLIANCE WITH NEC SPACING REQUIREMENTS.

ELECTRICAL PLAN NOTES BY SYMBOL#

14-30

3

tv

A5

tv

tv

tv

G

3

CT/GFI

F

F

D

H

D D

2

HWH

tv

14-50

48"

CT

CT

b

CT

D

a

tv

aa

a

D D

D D

b b

bC

CC

D

DD

a D

1 1

1

tv

14-50

48"CT

CT

CT

CT

CT

14-30

b a

D

CT

tv

B13

tv

tv

D D

D D

F

b b

bC

CC

D

H

aa

D

DD

a D

2

HWH

a

1

1

2

2

3

3

4

4

4

4

4

TR

HS

13

14

5

5

5

5

5

5

5

5

5

6

6

7

7

8

8

9

9

10

10

11

11

12

12

12

12

12

12

12

TRHS

13

TRHS

14

1 1

1

2

34

4

4

5

5

5

5

5

6

7

8

10

11

12

12

12

15

1

1

4

4

5

5

5

5

6

7

8

10

11

12

12

12

12

13

15

A5

3A5

1

A5

5

A5

7A5

9

A5

11

A5

1312

A5

15

A5

17

A5

19

A5

21

A5

2

A5

4

A5

6

A5

10

A5

14

A5

22

A5

18

A5

26

A6

3

A6

1

A6

5

A6

7

A6

9

A6

11

A6

13

A6

15

A6

17

A6

19

A6

21

A6

2

A6

4

A6

6

A6

10

A6

14

A6

22A6

18

A6

26

12

B13

3B13

1

B13

5

B13

7B13

9

B13

11

B13

13

B13

2

B13

4

B13

10

B13

14

B13

22

B13

17

B13

19

B13

6

B13

18

B1

3

B1

1

B1

5

B1

7

B1

9

B1

11

B1

13

B1

15

B1

2

B1

4

B1

10

B1

14

B1

22

B1

17

B1

19

B1

6

B1

18

GENERAL NOTE:

PROVIDE TAMPER PROOF RECEPTACLES IN DWELLING UNITS PER NEC REQUIREMENTS.

CT/GFI

G

2

3

B1

15

1. CIRCUIT SHALL BE PROTECTED BY AFCI TYPE BREAKER.

2. CIRCUIT SHALL BE PROTECTED BY COMBINATION AFCI/GFCI TYPE BREAKER.

PANEL SCHEDULE NOTES BY SYMBOL#

2

2

2

2

2

2

1

1

1

1

1

2

1. CIRCUIT SHALL BE PROTECTED BY AFCI TYPE BREAKER.

2. CIRCUIT SHALL BE PROTECTED BY COMBINATION AFCI/GFCI TYPE BREAKER.

PANEL SCHEDULE NOTES BY SYMBOL#

2

2

2

2

2

2

1

1

1

1

2

36"

MIN

.

36" MIN.

16

9

CT

CT

CT

36"

MIN

.

36" MIN.

16

9

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

1/4" = 1'-0"

2 BEDROOM ELECTRICAL PLAN3

1/4" = 1'-0"

1 BEDROOM ACCESSIBLE ELECTRICAL PLAN2

1/4" = 1'-0"

1 BEDROOM ELECTRICAL PLAN1

1/4" = 1'-0"

2 BEDROOM ACCESSIBLE ELECTRICAL PLAN4

REFER TO SPECIAL SYSTEMS PLANS ON

SHEETS E2.7-E2.9 FOR SMOKE DETECTORS

TO BE INSTALLED IN ALL ACCESSIBLE AND

HEARING IMPAIRED UNITS.

E4.1

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

EXTERIOR LIGHTING CONTROL DIAGRAM

No Scale1

ON

AUTO

OFF

A:12

120V

120V PHOTOCELL WITH 1/2" PIPE NIPPLEAND SWIVEL MOUNT. INTERMATIC #K4236COR EQUAL, SEE 1:E1.1 FOR LOCATION.

TO PARKING LOT LIGHTS

CIRCUIT 'A:37'L N

C

CONTACTOR 'C'JAN 113

PROVIDE LIGHTING CONTACTORS WITH QUANTITY OF POLES SHOWN,120V COIL,INTEGRAL 3-POSITION MANUAL SELECTOR SWITCH, AND NEMA 1 ENCLOSURE.

A:14

A:16 TO MONUMENT LIGHTS

PIT

ELEVATOR

LOGICCONTROLLER

SMOKE DETECTOR AND HEAT DETECTOR IN

ELEVATOR EQUIPMENT ROOM

FIRE ALARM

CONTROL PANEL

ELEVATORPOWER

ADDRESSABLE RELAY FOR SHUNT TRIP

OF ELEVATOR MAIN LINE POWER.LABEL "ELEVATOR SHUT-DOWN RELAY".WIRE TO N.O. CONTACTS.

NOTE: HEAT DETECTORS SHALL BE SENSITIVE, 135° FFIXED TEMPERATURE, WITH A LISTED SPACING OF 40'

ON CENTER OR GREATER. LOCATE HEAT DETECTORSWITHIN 24" OF SPRINKLER HEADS.

HEAT DETECTOR INELEVATOR PIT

FACP

LOBBY SMOKE

DETECTOR

1ST FLOOR

SMOKE DETECTOR AND HEATDETECTOR AT TOP OF ELEVATOR

HOISTWAY

ELEVATOR

EQUIPMENT

ROOM

ELEVATOR SEQUENCE OF OPERATION: (DURING SMOKE/HEAT ALARM)

1. UPON SENSING SMOKE FROM ONE OR MORE LOBBY, ELEVATOR HOISTWAY OR ELEVATOR EQUIPMENT ROOM, THE SMOKE DETECTOR SHALL

SIGNAL THE FACP, WHICH WILL FORWARD THE SIGNAL TO THE ELEVATOR LOGIC CONTROLLER TO RECALL ELEVATOR CAB TO THEDESIGNATED MAIN FLOOR. IF DESIGNATED FLOOR'S LOBBY SMOKE DETECTOR SENSES SMOKE AT THAT FLOOR, THE ELEVATOR CONTROLLERWILL SEND THE ELEVATOR CAB TO THE NEXT FLOOR CLEAR OF SMOKE. ONCE THE ELEVATOR CAB HAS REACHED THE DESIGNATED FLOOR,

THE ELEVATOR CAB DOORS WILL OPEN AND THE CONTROLLER WILL LOCK THE ELEVATOR CAB AT THAT FLOOR, DISABLING THE ELEVATORCAB CONTROLS, UNLESS A FIREMAN'S KEY IS USED TO OVERRIDE AUTOMATIC CONTROLS.

2. ALL SMOKE DETECTORS (LOBBIES, HOISTWAY, MACHINE ROOM) SHALL TRANSMIT A SEPARATE AND DISTINCT VISIBLE ANNUNCIATION AT

THE FACP AND ANNUNCIATOR PANEL.

3. HEAT DETECTORS IN THE ELEVATOR HOISTWAY AND ELEVATOR EQUIPMENT ROOM WILL SEND A SIGNAL TO THE SHUNT-TRIP SWITCH

POWERING THE ELEVATOR SO AS TO SHUT DOWN POWER TO THAT CIRCUIT. (THIS IS A NON-AUTO RESET SWITCH). WHEN THE SPRINKLERHEAD HAS REACHED ITS CRITICAL TEMPERATURE OF 165° F., THE HEAD WILL BEGIN DISCHARGE OF WATER.

ELEVATOR POWER MODULE WITHSHUNT-TRIP COIL AND INTERNAL FA

SHUNT TRIP VOLTAGE MONITORINGRELAY AS NOTED ON PLANS

LOBBY SMOKEDETECTOR

No Scale

ELEVATOR INTERLOCK WITH FIRE ALARM3

2ND FLOOR

ELEVATORHOISTWAY

AM RR R R

ADDRESSABLE RELAYS FOR ELEVATOR PRIMARYRECALL, ALTERNATE LEVEL RECALL, AND

FIREMAN'S HAT. LABEL WITH APPROPRIATE NAME.

ADDRESSABLE MONITOR MODULE

FOR MONITORING OF SHUNT TRIP

VOLTAGE

FIRE ALARM SIGNALING

LINE CIRCUIT (TYP)

TELECOM GROUNDING & BONDING DIAGRAMNo Scale

4

NOTES:

TGB1

BOND TOBUILDING

STEEL

1. ALL GROUNDING / BONDING

CONDUCTORS SHALL BE #4 AWG

INSULATED STRANDED COPPER. INSTALL

IN 3/4" CONDUIT WHERE EXPOSED AND

WHERE SUBJECT TO PHYSICAL DAMAGE.

2. ALL CONNECTIONS TO GROUND BAR

SHALL BE MADE USING COMPRESSION

TYPE LUGS (MECHANICAL LUGS ARE NOT

ACCEPTABLE).

MECH 107

D

#4 CU#4 CU

BOND TO

EQUIPMENTGROUND BUS

5APARTMENT TELECOM WIRING SCHEMATIC

NO SCALE

PHONE WALL OUTLET:

CAT 5e 8-POSITIONMODULAR CONNECTOR,WALL PLATE AND

TELECOM BOX.

RG-6 COAXIAL CABLEFROM DISTRIBUTIONDEVICE TO WALL OUTLET.

CATV WALL OUTLET: TYPE FCONNECTOR, WALL PLATE

AND TELECOM BOX.CAT 5e, 4PR UTP CABLE TO

SERVICE PROVIDER EQUIPMENT

ON MAIN BUILDING TELEPHONETERMINAL BOARD INMECHANICAL ROOM 119.

RG-6 COAXIAL CABLE TO SERVICEPROVIDER EQUIPMENT. SEE SPECIAL

SYSTEMS PLANS FOR LOCATION.

TELECOM DISTRIBUTION DEVICE:PRE-CONFIGURED 1X9 BRIDGEDTELEPHONE BOARD AND 6-WAY

VIDEO SPLITTER, LEVITON MODEL47603-1G6 OR SIMILAR. INSTALLIN 14" FLUSH MOUNTED

ENCLOSURE WITH COVER, MODEL47605-140 OR SIMILAR.

CAT 5e, 4PR UTP CABLE

FROM DISTRIBUTIONDEVICE TO WALL OUTLET

120 VAC 24 VAC

DOOR ALARM BUZZER SYSTEM NOTES

1. PROVIDE DOOR ANNUNCIATOR SYSTEM COMPLETE WITH PUSH BUTTON, HORN/STROBE(S), POWER SUPPLIES

AND ALL WIRING REQUIRED. HORN/STROBE SHALL ACTIVATE WHEN PUSH BUTTON IS DEPRESSED.

2. HORN/STROBE SHALL OPERATE AT 24VAC, HAVE A CLEAR LENS WITH 50cd STROBE AND HORN WITH 82dBAT 10', UL 1638 LISTED, EDWARDS #6536-G5. FLUSH MOUNT IN WALL AT 6'-8" AFF.

3. PUSH BUTTON SHALL BE WHITE WITH CHROME RIM, NON-ILLUMINATED, WITH N.O. MOMENTARYCONTACTS, RATED FOR 0.67 AMPS AT 24VAC, EDWARDS #620. PROVIDE WITH STAINLESS STEEL COVERPLATE, EDWARDS #147-10. MOUNT AT 48" AFF.

4. POWER SUPPLY SHALL BE A LOW VOLTAGE CLASS 2 TRANSFORMER WITH 120VAC PRIMARY AND 24VACSECONDARY, 20VA, EDWARDS #598. FLUSH MOUNT IN 2-GANG WALL BOX WITH BLANK COVER PLATE,

DIRECTLY ABOVE HORN/STROBE.

5. LOW VOLTAGE CLASS 2 CABLING SHALL BE MINIMUM 18 AWG UNSHIELDED.

POWER SUPPLY

S H

L

N

HS

PUSH BUTTON

HORN/STROBE

APARTMENT DOORBELL WIRING SCHEMATIC

No Scale2

A:10

A:8TO DRIVEWAY LIGHTS

A:6

A:4 TO BUILDING MOUNTED LIGHTS

TO BUILDING MOUNTED LIGHTS

LIGHT FIXTURE SCHEDULE

MARK MANUFACTURER MODEL NUMBERLAMP / LED DATA

BALLAST/DRIVER MOUNTING FINISH DESCRIPTION NOTESWATT/LUMENS COLOR

C KICHLER 42517OZ 200 3000°K INTEGRAL DRIVERPENDANT AT 6'-6"AFF TO BOTTOM

OLD BRONZE 3"Ø x 12" HIGH DECORATIVE MINI-PENDANT .

D HALO SMD6R-6-930-WH9.6W LED

750 LUMENS3000°K INTEGRAL DRIVER SURFACE BRONZE 6" ROUND SURFACE MOUNT DOWNLIGHT .

E SURE-LITES SEL25SD --- WHITE N/A WALL AT 7'-6" AFF WHITE TWIN HEAD POLYCARBONATE EMERGENCY LIGHT 1,2

E1 MULE EOE-BB-10L2-B-DG-LT(2) 10W

LED--- N/A

ON WALL ABOVEDOOR

BRONZEDIE-CAST ALUMINUM EMERGENCY LIGHT WITH POLYCARBONATE

LENS, INTEGRAL BATTERY1,2,3,6

F SEAGULL 15040EN-782(2) 10W

LED3000°K INTEGRAL DRIVER SURFACE BRONZE 52" DIAMETER CEILING FAN WITH LED LIGHT KIT

G SEAGULL 4423003EN3-710(3) 9.5W

LED3000°K INTEGRAL DRIVER WALL AT 7'-0" BURNT SIENNA 3-LAMP LED VANITY LIGHT .

H SEAGULL 5913291S-1538W LED

3,500 LUMENS3000°K INTEGRAL DRIVER SURFACE WHITE 4' LINEAR FLUORESCENT WITH PRISMATIC ACRYLIC LENS .

J LITHONIA FMML-13-830-DDBT28W LED

1,900 LUMENS3000°K INTEGRAL DRIVER SURFACE WHITE 13" ROUND LED SURFACE MOUNT .

K METALUX 4SNLED-LD4-56SL-LW-UNV-L835-CD151W LED

5,600 LUMENS3500°K

0-10V DIMMING

(10%-100%)SURFACE WHITE 4' LED STRIP WITH FROSTED LENS, WIDE DISTRIBUTION .

L1 LITHONIA WSR-LED-P1-40K-SR4-MVOLT-E10WH20W LED

2,180 LUMENS4000°K STANDARD WALL BLACK

EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION ANDBATTERY BACK-UP

6

L2 LITHONIA WSR-LED-P2-40K-SR4-MVOLT29W LED

3,050 LUMENS4000°K STANDARD WALL BLACK EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION 6

L3 LITHONIA WSR-LED-P3-40K-SR4-MVOLT40W LED

4,300 LUMENS4000°K STANDARD WALL BLACK EXTERIOR LED WALL PACK WITH IES TYPE IV DISTRIBUTION 6

MR METALUX 24FP4735C41W LED

4,700 LUMEN3500°K 0-10V DIMMING LAY-IN WHITE 2x4 LED FLAT PANEL .

MS METALUX 24FP4735C41W LED

4,700 LUMEN3500°K 0-10V DIMMING SURFACE WHITE 2x4 LED FLAT PANEL .

P HALO COMMERCIAL PD615ED010-PDM6A830-64VH17.1W LED

1,500 LUMENS3000°K 0-10V DIMMING RECESSED

SEMI-SPECULARCLEAR

6" ROUND SHALLOW LENS DOWNLIGHT WITH SELF-FLANGED

ALUMINUM WIDE BEAM REFLECTOR; 80 CRI5

R1 LITHONIA DSX0-LED-P1-40K-T2S-MVOLT-HS-DDBXD38 W LED

4,300 LUMENS4000°K

FIXED OUTPUTDRIVER

20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE II

DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8

R2 LITHONIA DSX0-LED-P3-40K-T2M-MVOLT-HS-DDBXD71 W LED

7,800 LUMENS4000°K

FIXED OUTPUTDRIVER

20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE II

DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8

R3 LITHONIA DSX0-LED-P3-40K-T4M-MVOLT-HS-DDBXD71W LED

7,700 LUMENS4000°K

FIXED OUTPUTDRIVER

20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE IV

DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8

R4 LITHONIA DSX0-LED-P3-40K-T5W-MVOLT-DDBXD71W LED

8,200 LUMENS4000°K

FIXED OUTPUTDRIVER

20' SSS POLE BRONZELED AREA LIGHT, SINGLE HEAD FULL CUT-OFF WITH IES TYPE V

DISTRIBUTION AND HOUSE SIDE SHIELD4,6,8

S ACCLAIM DFB-111-AKEU50W LED

2,455 LUMENS4000°K

FIXED OUTPUTDRIVER

GRADE BLACK IP-66 RATED, GRADE MOUNTED LED FLOOD LIGHT 7

T WILLIAMS 96-4-L40/830-HIAFR-WET/1-DRV-UNV30W LED

4,000 LUMENS3000°K

FIXED OUTPUTDRIVER

SURFACE WHITE4' FULLY ENCLOSED AND GASKETED INDUSTRIAL FIXTURE WITH

FROSTED, RIBBED, IMPACT-RESISTANT ACRYLIC LENS.

U WILLIAMS WMA-3-L46/835-AF-DRV-UNV57W LED

4,600 LUMEN3500°K INTEGRAL DRIVER

WALL AT 7'-0" AFF

(TO BOTTOM)WHITE 3' ARCHITECTURAL WALL BRACKET UP/DOWN LIGHT .

X1 MULE MXBRU-SD --- RED N/A CEILING/WALL/END WHITE SINGLE FACE POLYCARBONATE LED EXIT 1,2

X2 MULE MXBRU-SD --- RED N/A CEILING/END WHITE DOUBLE FACED POLYCARBONATE LED EXIT 1,2

XE MULE SQC-LED-1-R-WW-SD---

1 WATTRED

WHITEN/A CEILING/WALL WHITE

SINGLE FACE COMINATION POLYCARBONATE EXIT SIGN/TWIN HEAD

EMERGENCY LIGHT1,2

Y --- SELECTED BY OWNER, PROVIDED BY E.C. --- --- --- WALL ---DECORATIVE EXTERIOR WALL SCONCE SELECTED BY OWNER,

PROVIDED BY E.C.6

GENERAL:

● All interior LED fixtures shall be 3000°K corrected color temperature, min. 80 CRI.

● All exterior LED fixtures shall be 4000°K corrected color temperature, min. 70 CRI.

● All light fixtures shall be provided with universal drivers capable of operating at 120V or 208V UNO.

● All LED fixtures shall adhere to LM79 and LM80 standards.

● All apartment light fixtures shall be Energy Star certified.

NOTES:

1. Fixture shall have self-diagnostic/self-testing electronics.

2. Provide with emergency battery integral charger.

3. Fixture shall be capable of operation in temperatures ranging from -40°F through 104°F.

4. Provide fixture/pole assembly with 20' round straight steel pole, bronze to match fixture. Fixture height shall not exceed 23'-0" AFG.

5. Provide with bar hangers appropriate for ceiling system in which fixture is installed.

6. U.L. listed for 'wet location'.

7. See detail 3:E1.0 for more information.

8. Fixture/pole assembly shall be rated for 100 mph wind loads. Provide with vibration damper per manufacturer's recommendations.

TC

7DAY/24HR TIME CLOCK. INTERMATICMODEL T2005 OR EQUAL

LOBBY SMOKEDETECTOR

3RD FLOOR

SPARE

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E6.1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E6.2

GENERAL NOTES:

• All conductor sizes are based on copper, U.N.O.

• Entire installation shall comply with NEC.

• Coordinate all responsibilities and requirements with utility company and pay associated fees. Contact

Information:Lou Graves

Kerrville Public Utility Board

[email protected]

(830) 792-8241

• Coordinate final location of meter assemblies with utility company. Provide shop drawings of proposed

equipment whether as specified or substituted to utility company for approval.

• Some branch circuits & feeders may need to be upsized due to length. Refer to sheet E0.1, note

16120.05 & coordinate with field conditions.

• All meter center components shall be NEMA 3R

• All dimensions based on Square D equipment

• For each meter, provide a permanent brass, copper or aluminum tag identifying the apartment served.

Tags shall be securely fastened to the meter base and be stamped with 1/8" letters, minimum.

• At each service, provide engraved plastic sign identifying "Service Disconnect ## of 3"

FOR FEEDER SIZE, SEE APARTMENT

FEEDER SCHEDULE ABOVE.

2'-0" AFG

(MINIMUM)

C BOTTOM METER:

±4'-0" AFG

C MOUNTING CHANNEL:

(2) 4-SOCKET METER CENTER

WITH BRANCH CIRCUIT

BREAKERS. SQUARE D EZ METER

PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH

BREAKERS

#2/0 Cu GROUNDING ELECTRODE CONDUCTOR TOCONCRETE ENCASED ELECTRODE, UNDERGROUND METALWATER PIPE, AND DRIVEN GROUND ROD. BOND ALL ITEMS

IN ACCORDANCE WITH NEC ARTICLE 250.

(2) SETS OF (4) #350 KCMIL IN4" CONDUIT FROM PAD MOUNT

TRANSFORMER TO METERCENTER.

FINISHED GRADE

2 SETS: (4)#500 KCM,

#2/0G IN 4"C.

2 SETS: (4)#500 KCMIL IN 4"C.

800A/600V/3P, NEMA 3R, SERVICERATED DISCONNECT SWITCH WITH

SOLID NEUTRAL AND (3) 800ADUAL-ELEMENT, TIME-DELAY FUSES

#2/0 Cu GROUNDING ELECTRODECONDUCTOR TO CONCRETE ENCASED

ELECTRODE, UNDERGROUND METAL

WATER PIPE, AND DRIVEN GROUNDROD. BOND ALL ITEMS IN

ACCORDANCE WITH NEC ARTICLE 250.

125A

125A

125A

125A

125A

125A

125A

18.66"12.25" 12.25"

55.41"

ELECTRICAL RISER DIAGRAM - WEST

No Scale1

(MAXIMUM)

6'-0" AFG

125A

125A

125A

SPACE

125A

125A

12.25"12.25"

(1) 3-SOCKET METER CENTER

WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER

PAK #EZMR313125, WITH (3)MODEL #QBP22125TM BRANCH

BREAKERS

FOR FEEDER SIZE, SEE APARTMENTFEEDER SCHEDULE ABOVE.

2'-0" AFG

(MINIMUM)

C BOTTOM METER:

±4'-0" AFG

C MOUNTING CHANNEL:

(4) 4-SOCKET METER CENTER

WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER

PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH

BREAKERS

#3/0 Cu GROUNDING ELECTRODE CONDUCTOR TO

CONCRETE ENCASED ELECTRODE, UNDERGROUND METAL

WATER PIPE, AND DRIVEN GROUND ROD. BOND ALL ITEMSIN ACCORDANCE WITH NEC ARTICLE 250.

(3) SETS OF (4) #500 KCMIL IN 4"

CONDUIT FROM PAD MOUNT

TRANSFORMER TO METER CENTER.

FINISHED GRADE

125A

125A

125A

125A

125A

125A

125A

125A

125A

125A

125A

125A

30.19"12.25" 12.25"12.25"12.25"

128.19"

ELECTRICAL RISER DIAGRAM - EAST

No Scale2

(MAXIMUM)

6'-0" AFG

12.25"

125A

125A

125A

125A

125A

125A

125A

125A

SPACE

125A

125A

12.25"12.25"

125A

125A

125A

125A

(3) 4-SOCKET METER CENTER

WITH BRANCH CIRCUIT

BREAKERS. SQUARE D EZ METER

PAK #EZMR314125, WITH (4)MODEL #QBP22125TM BRANCH

BREAKERS

125A

125A

125A

125A

12.25"

METER CENTER MAIN CIRCUIT

BREAKER. SQUARE D EZ METER

PAK #EZM3600, 208/120VTHREE PHASE, 4 WIRE, WITH

600A/3P CB, 65KAIC RATED

METER CENTER MAIN CIRCUIT

BREAKER. SQUARE D EZ METER

PAK #EZM31200, 208/120VTHREE PHASE, 4 WIRE, WITH

1200A/3P CB, 65KAIC RATED

TRANSOCKET

'TSN-310935'

(30"W x 42"H x 14"D)PROVIDED AND

INSTALLED BY

UTILITY COMPANY.

MDPA

B

C

ELEVATOR #1

MDP:2

MDP:3

MDP:1

MDP:5

APARTMENT FEEDER SCHEDULE

Apartment # Feeder Size

A2, A3, A4, A5, A6, B2, B3, B4, B5, B6, B7, B8, B9,B10, B14, B15, B16, B17, B18, C3, C4, C5, C6, C7,

C8, C9, C10, C14, C15, C16, C17, C18, C19

BASE BID (COPPER): (3)#1/0,#4G IN 1-1/2" C OR MC

CABLE

ALTERNATE BID (ALUMINUM):

(3)#3/0, #3G IN 2" C OR MC CABLE

A1, B1, B11, B12, B13, C1, C2, C11, C12, C13

BASE BID (COPPER): (3)#2/0,#3G IN 2" C. OR MC CABLE

ALTERNATE BID (ALUMINUM):

(3)#4/0, #2G IN 2" C OR MC CABLE

NOTES:

1. Voltage drop has been accounted for in sizes indicated, further up-sizing of feeders is not necessary

2. Ensure panel lugs are adequately sized to handle up-sized feeders.

C18APT

C19APT

EMPTY

B17APT

C17APT

B18APT

B15APT

C15APT

B16APT

C16APT

B13APT

C13APT

B14APT

B11APT

C11APT

B12APT

C12APT

B9APT

C9APT

B10APT

C10APT

B7APT

C7APT

B8APT

C8APT

C5APT

A6APT

B6APT

C6APT

B4APT

C4APT

A5APT

B5APT

A3APT

B3APT

C3APT

A4APT

C1APT

A2APT

B2APT

C2APT

A1APT

B1APT

EMPTY

FIRST FLOOR

SECOND FLOOR

THIRD FLOOR

(1) 3-SOCKET METER CENTER WITH

BRANCH CIRCUIT BREAKERS.SQUARE D EZ METER PAK

#EZMR313125, WITH (2) MODEL#QBP22125TM BRANCH BREAKERS

125A

C14APT

(1) 3-SOCKET METER CENTER

WITH BRANCH CIRCUITBREAKERS. SQUARE D EZ METER

PAK #EZMR313125, WITH (2)MODEL #QBP22125TM BRANCH

BREAKERS

SDS

D

MDP:4

2 SETS: (4)#500 KCMILIN 4"C.

FIRE PUMP

CONTROLLER

(BY OTHERS)

JOCKEY PUMP

CONTROLLER

(BY OTHERS)

JOCKEY PUMP

(BY OTHERS)

FIRE PUMP

20 HP

(BY OTHERS)

4"x4" WIREWAY WITH

GROUND BAR

4#1 IN 2" C

3#8, #8G,

3/4" RMC

GRADE

3#8, #8G,

3/4" RMC

3#2, #8G,

1-1/4" RMC

3#2, #8G,

1-1/4" RMC

M

60"

MIN

/ 6

6"

MA

X

INSTALL POWER COMPANYFURNISHED METER SOCKET,

COORDINATE REQUIREMENTSWITH POWER UTILITY CO. SEE2:E1.4 FOR METER LOCATION.

3" SLIP JOINT ONCONDUIT RISER

#6 Cu GROUNDING ELECTRODE CONDUCTOR TO

CONCRETE ENCASED ELECTRODE,UNDERGROUND METAL WATER PIPE, AND DRIVEN

GROUND ROD. BOND ALL ITEMS IN ACCORDANCEWITH NEC ARTICLE 250.

FLOOR

ELECTRICAL RISER DIAGRAM - FIRE PUMP

No Scale3

(4) #1 IN 2" CONDUITFROM PAD MOUNT

TRANSFORMER TO METER.

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E6.3

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

E6.4

NOTES:

• PROVIDE RADIATION DAMPERS AT ALL

PENETRATIONS OF FIRE RATED FLOOR/CEILING

ASSEMBLY.

• ALL DUCTWORK SHALL BE SEALED AND TESTED IN

ACCORDANCE WITH 403.3 OF THE 2018 IECC.

• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE

INSULATED WITH MINIMUM R-6 DUCT

INSULATION.

• REFRIGERANT PIPING SHALL BE INSULATED PER

TABLE C403.11.3 OF 2018 IECC.

1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.

2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO

MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.

3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN

WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF

CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH

= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE

PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT

INSTALLED PER IMC 504.

NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL

PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE

STOPPING SYSTEM.

4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS

REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED

WITHOUT OFFSETS.

5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN

APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.

6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.

7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING

EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.

PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR

LOCATIONS OF BLOWER COILS. (TYPICAL)

8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.

COORDINATE WITH G.C.

9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR

AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE

VENT.

10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE

WITH ARCHITECTURAL PLANS.

11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS

POSSIBLE.

12. MOUNT TOP OF GRILLE 6" BELOW CEILING.

13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF

VENTILATION FAN.

# PLAN NOTES BY SYMBOL

PTAC-09

PTAC-15

PTAC-09 PTAC-09 PTAC-09

PTAC-15 PTAC-15 PTAC-15

PTAC-07

PTAC-07

PTAC-07

PTAC-07

PTAC-07

PTAC-15

TT

TT

TT

TT

T

T

T

T

EF-1 EF-1EF-1 EF-1

EF-2

EF-2

EF-2

BC-1

HP-1

PTAC-15

PTAC-15

PTAC-07

PTAC-07

10/8

6/6

T

HP-3

RG

16x8

T

1

2 2 2 2

3 3 3 3

VF-1

11

12

TG

14x12

T

13

66

6

5 5 5 5

7 8

9

40 CFM

SD

150

8x8

'BC-1'

SD

100

6x6

TG

8x8

SD

50

6x6

SD

200

10x10

6/6

8/8

MA

TC

HLIN

EM

AT

CH

LIN

E

PTAC-09 PTAC-09

PTAC-09

PTAC-09

PTAC-09

PTAC-15 PTAC-15

T

T T T T T T

EF-1

EF-1

EF-1

10/8

8/8

BC-2

22 2

3

3 3

EWH-2

EWH-1

5

5

5 5

5

5

'BC-2'T

SD

250

10x106/8

RG

14x10 10/10

MA

TC

HLIN

EM

AT

CH

LIN

E

1/8" = 1'-0"

FIRST FLOOR HVAC PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

M2.1

1/8" = 1'-0"

PARTIAL FIRST FLOOR HVAC PLAN2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

NOTES:

• PROVIDE RADIATION DAMPERS AT ALL

PENETRATIONS OF FIRE RATED FLOOR/CEILING

ASSEMBLY.

• ALL DUCTWORK SHALL BE SEALED AND TESTED IN

ACCORDANCE WITH 403.3 OF THE 2018 IECC.

• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE

INSULATED WITH MINIMUM R-6 DUCT

INSULATION.

• REFRIGERANT PIPING SHALL BE INSULATED PER

TABLE C403.11.3 OF 2018 IECC.

1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.

2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO

MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.

3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN

WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF

CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH

= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE

PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT

INSTALLED PER IMC 504.

NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL

PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE

STOPPING SYSTEM.

4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS

REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED

WITHOUT OFFSETS.

5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN

APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.

6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.

7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING

EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.

PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR

LOCATIONS OF BLOWER COILS. (TYPICAL)

8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.

COORDINATE WITH G.C.

9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR

AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE

VENT.

10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE

WITH ARCHITECTURAL PLANS.

11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS

POSSIBLE.

12. MOUNT TOP OF GRILLE 6" BELOW CEILING.

13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF

VENTILATION FAN.

# PLAN NOTES BY SYMBOL

PTAC-09

PTAC-15

PTAC-09 PTAC-09 PTAC-09 PTAC-09

PTAC-09

PTAC-09

PTAC-09PTAC-15 PTAC-15 PTAC-15

PTAC-15 PTAC-15

PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-12PTAC-15

PTAC-15PTAC-15PTAC-15PTAC-15

PTAC-15

PTAC-15PTAC-15

PTAC-09PTAC-09

PTAC-15

PTAC-09

PTAC-09

PTAC-09

PTAC-09

PTAC-15

PTAC-15

PTAC-15 PTAC-07

PTAC-07 PTAC-07

PTAC-07

PTAC-07

TT

TT

TT

TT

TT

TT

T T T T T T

TT

TT

TT

TT

T

T

T

T

T

T

T

T

T

T

TT

TT

EF-1

EF-1

EF-1EF-1 EF-1

EF-1

EF-1EF-1EF-1 EF-1EF-1 EF-1EF-1EF-1

EF-1

EF-1

EF-1

EF-1

HP-4 HP-5

BC-4EF-2

EF-2

EF-2

10/8 BC-3

EF-3

HP-2

PTAC-07

T

50

8/10 10/10

16/10

12/10

6/10

2

2

2

2

2 2 2 2 2 2 2

2

222222

3

4

3

4

3

4

3

4

34 34

33333333

3

3

3

3

5 5 5 55

5

5 5

5

5

55555555

5

5

5

5

7

8

7

8

9

170 CFM 8"Ø

SD

175

8x8

SD

175

8x8

8"Ø

8"Ø 10

SD

125

8x8

SD

125

8x8

SD

200

8x8SD

50

6x6

2

2 2

RG

16x6

RG

16x8

RG

16x6

10/6

CD

CD

CD CD

CD

CD

CD

SD

175

8x8

SD

175

8x8

CD

RG

12x12

8"Ø

8"Ø

9

85 CFM

6"Ø

T'BC-4'

'BC-3'

1/8" = 1'-0"

SECOND FLOOR HVAC PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

M2.2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

NOTES:

• PROVIDE RADIATION DAMPERS AT ALL

PENETRATIONS OF FIRE RATED FLOOR/CEILING

ASSEMBLY.

• ALL DUCTWORK SHALL BE SEALED AND TESTED IN

ACCORDANCE WITH 403.3 OF THE 2018 IECC.

• ALL DUCTWORK INSTALLED IN ATTIC SHALL BE

INSULATED WITH MINIMUM R-6 DUCT

INSULATION.

• REFRIGERANT PIPING SHALL BE INSULATED PER

TABLE C403.11.3 OF 2018 IECC.

1. ROUTE 4"Ø EXHAUST DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER, COORDINATE ROUTING WITH STRUCTURE.

2. ROUTE 4"Ø EXHAUST DUCT FROM EXHAUST FAN UP IN WALL TO

MANUFACTURER'S ROOF JACK. COORDINATE WITH G.C.

3. PROVIDE UL LISTED DRYER BOX EQUAL TO IN-O-VATE TECHNOLOGIES IN

WALL INSTALLED IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS, AND ROUTE 4"Ø DRYER EXHAUST DUCT TO ROOF

CAP WITH BACKDRAFT DAMPER. MAXIMUM ALLOWABLE DUCT LENGTH

= 45' WITH ONE 90° ELBOW AND TWO 45° ELBOWS. PROVIDE

PERMANENT LABEL IDENTIFYING EQUIVALENT LENGTH OF DRYER DUCT

INSTALLED PER IMC 504.

NOTE: ANNULAR SPACE AROUND DUCT IS TO BE SEALED AT ALL

PENETRATIONS OF FLOORS AND CEILINGS WITH U.L. LISTED FIRE

STOPPING SYSTEM.

4. OFFSET SECOND AND THIRD FLOOR DRYER VENT DUCTWORK AS

REQUIRED TO ALLOW FIRST FLOOR DRYER DUCT TO BE INSTALLED

WITHOUT OFFSETS.

5. PROVIDE WALL MOUNTED THERMOSTAT FOR EACH PTAC IN

APARTMENTS. COORDINATE FINAL LOCATION WITH OWNER.

6. PROVIDE SINGLE THERMOSTAT FOR CONTROL OF MULTIPLE PTACS.

7. ROUTE REFRIGERANT PIPING FROM HEAT PUMP TO MATCHING

EVAPORATOR COIL CONCEALED IN WALLS AND ABOVE CEILINGS.

PENETRATE EXTERIOR WALL 18" A.F.G. SEE M2.1, M2.2, AND M2.3 FOR

LOCATIONS OF BLOWER COILS. (TYPICAL)

8. MOUNT HEAT PUMP ON LEVEL 3-1/2" THICK CONCRETE PAD.

COORDINATE WITH G.C.

9. ROUTE OUTDOOR AIR DUCT TO MANUFACTURER'S WALL CAP WITH

BACKDRAFT DAMPER AND BIRDSCREEN, AND BALANCE OUTDOOR AIR

AS INDICATED ON PLANS. AT THIRD FLOOR, PROVIDE SOFFIT INTAKE

VENT.

10. ROUTE RETURN AIR DUCTWORK CONCEALED IN SOFFIT. COORDINATE

WITH ARCHITECTURAL PLANS.

11. SUSPEND VENTILATION FAN 'VF-1' EXPOSED IN ROOM AS HIGH AS

POSSIBLE.

12. MOUNT TOP OF GRILLE 6" BELOW CEILING.

13. PROVIDE LINE VOLTAGE THERMOSTAT SET TO 80°F FOR CONTROL OF

VENTILATION FAN.

# PLAN NOTES BY SYMBOL

PTAC-09

PTAC-15

PTAC-09 PTAC-09 PTAC-09 PTAC-09

PTAC-09

PTAC-09

PTAC-09PTAC-15 PTAC-15 PTAC-15

PTAC-15 PTAC-15

PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-09 PTAC-12PTAC-15

PTAC-15PTAC-15PTAC-15PTAC-15

PTAC-15

PTAC-15PTAC-15

PTAC-09PTAC-09

PTAC-15

PTAC-09

PTAC-09

PTAC-09

PTAC-09

PTAC-15

PTAC-15

PTAC-15

PTAC-15

PTAC-09

PTAC-15

PTAC-07

PTAC-09

PTAC-12

T

T T

T

T

T

T

T

TT

TT

TT

TT

TT

TT

T T T T T

TT

TT

TT

TT

T

T

T

T

T

T

TT

TT

T

T

EF-1

EF-1

EF-1EF-1 EF-1

EF-1

EF-1EF-1EF-1 EF-1EF-1 EF-1EF-1EF-1

EF-1

EF-1

EF-1

EF-1

EF-1

EF-2

EF-2

EF-2

EF-2

EF-2

EF-3BC-5

PTAC-07

T

10/10

2

2

2

2

2 2 2 2 2 2 2

2

222222

2

3

4

3

4

3

4

34 34

33333333

4

34

3

3

3

5 5 5 55

5

5 5

5

5

55555555

5

5

5

5

T

2

SD

200

10x10 CD

CD

CD

CD

SD

200

10x10 9

105 CFM

'BC-5'

SD

50

6x6

SD

50

6x6

8"Ø

8"Ø

12/10

RG

12x12CD

2

1/8" = 1'-0"

THIRD FLOOR HVAC PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

M2.3

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

EXTERIOR PIPE SUPPORT DETAIL

NO SCALE2

INSULATED PIPE SUPPORTK-FLEX 360 OR EQUAL

APPLY CONTACT ADHESIVE TO COLLARJOINT AND SEAL THE SUPPORT BY

OVERLAPPING ADHESIVE TABS.

PROVIDE COLLAR TO FIX AROUND SUPPORTEQUAL TO CADDY CUSHION CLAMP PCC.

GLUE INSULATION TO PIPE

SUPPORT (TYPICAL BOTH SIDES).

1-1/4" ANGLE IRONFRAME WHEN REQ'D.FOR BOTTOM RETURN

SET BLOWER COIL ON

RUBBER VIBRATIONISOLATION PAD

SUPPLY AIR DUCT

SEE PLANS FOR SIZE

AND ROUTING

TO WALL CAP SEEPLANS FOR SIZEAND ROUTING

R.A. DUCT SEEPLANS FOR SIZE

AND ROUTING

O.A. DUCT

MANUAL BALANCING

DAMPER (TYP.)

FLEXIBLE DUCT CONN. (TYP.)

FILTER WITH PIANOHINGE AND LATCH

90 DEGREE ELBOW WITH TURNING VANES

3/4" TO FLOOR DRAIN

BLOWER COIL DETAIL

NO SCALE1

BLOWER

COIL

PACKAGED TERMINAL AIR CONDITIONER SCHEDULE

MARK MANUFACTURERMODELNUMBER

NOMINAL CAPACITIES

MIN. CKT.

AMPSMAX. OCPD

ELECTRICAL

CHARACTERISTICSWEIGHT

TOTALCOOLING

TOTALHEATING

AIRFLOW

PTAC-07 GE AZ41E07D 7,100 BTUH 2.32 kW 215 11.6 20 208V-1PH 100

PTAC-09 GE AZ41E09D 9,250 BTUH 2.32 kW 230 11.6 20 208V-1PH 100

PTAC-12 GE AZ41E12D 11,600 BTUH 2.32 kW 325 11.6 20 208V-1PH 100

PTAC-15 GE AZ41E15D 14,500 BTUH 2.32 kW 325 11.6 20 208V-1PH 100

NOTES:

1. PROVIDE WITH MANUFACTURER'S LINE CORD CONNECTION KIT.

2. PROVIDE WITH WALL CASE COMPATIBLE WITH WALL CONSTRUCTION COORDINATE WITH G.C.

3. PROVIDE WITH REMOTE WALL MOUNTED PROGRAMMABLE THERMOSTAT WITH TWO SPEED FAN CONTROL.

4. PROVIDE WITH MANUFACTURER'S SUB-BASE ACCESSORY. PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE INSTALLATION.

AIR DEVICE SCHEDULE

MARK MANUFACTURER MODEL

APPLICATION

FINISH MOUNTING DAMPER DESCRIPTION

SU

PPLY

RET

URN

EXH

AU

ST

TR

AN

SFER

SD PRICE 520 ● White Surface NoSteel double deflection supply grille with

front blades paralles to long dimension

RG PRICE 530 ● White Surface No Steel louvered return grille

TG PRICE 530 ● WhiteSurface

Wall/CeilingNo Steel louvered transfer grille

GENERAL NOTES:

● Maximum noise criteria shall be 25.

● Runouts to diffusers shall be same size as neck, U.N.O.

● Paint objects visible through grilles with flat black paint.

● Provide mounting frame as required for ceiling type. Coordinate with Architect.

● Verify finish with Architect.

● Provide devices with raditaion dampers as required in rated ceilings. Coordinate with Arch.

ELECTRIC HEATER SCHEDULE

MARK MANUF. MODEL MOUNTING WATTS VOLTAGE/PHASE DESCRIPTION NOTES

EWH TRANE UHWA WALL 1,500 120/1Architectural fan forced wall

heater1,2,3

NOTES:

1. Provide with high temp. thermal cutout and fan delay.

2. Provide with integral thermostat and unit mounted disconnect switch.

3. Provide with manufacturer's surface mounting adapter sleeve. Coordinate exact mounting requirements and

locations with Arch. and rated construction.

EXHAUST FAN SCHEDULE

MARK MANUFACTURER MODEL CFM ESP (" wg) POWERVOLTS/PHASE

NOTES

EF-1 BROAN XB80 80 0.4" 6 W 120 / 11,2,3,4,

5,6,7

EF-2 COOK GC-128 60 0.25 30 W 120/1 3,4,5,6

EF-3 COOK GC-148 130 0.25 46 W 120/1 3,4,5,6

NOTES:

1. Fixture shall be Energy Star listed.

2. Fixture shall operate at <1 SONE

3. Provide integral disconnect.

4. Provide manufacturer's wall cap or roof jack, see plans.

5. Provide integral backdraft damper.

6. Provide with manufacturer's ceiling radiation damper.

7. Fixture occurs in each tenant unit.

HEAT PUMP SCHEDULE

MARK MANUF. MODELNOMINAL

TONS

INDOORUNIT

AIRFLOW

COOLING CAPACITY HEATING CAPACITY MINHSPF

ELECTRICAL

OA DBENT AIR

DB/WBSENS MBH TOT MBH MIN SEER OA DB

ENT AIRDB

TOTMBH

MCA MOCP V/PH

HP-1,2,3 TRANE 4TWR6018H1 1.5 350 105 78/67 11.6 16.8 16 47 70 17.5 8.55 12 20 208/1

HP-4 TRANE 4TWR6030H1 2.5 850 105 78/67 20.3 28.0 16 47 70 28.8 9 17 25 208/1

HP-5 TRANE 4TWR6024H1 2 500 105 78/67 17.0 23.0 16 47 70 23.0 8.2 14 25 208/1

Notes:

1. Refrigerant lines shall be field fabricated. Coordinate line sizing requirements with equipment manufacturer for length of run for each apartment. Provide suction accumulators, etc. as

required.

2. Provide 7-day programmable thermostat.

3. Provide with R410a refrigerant.

4. Provide 2 sets of MERV-7 filters.

BLOWER COIL SCHEDULE

MARK MANUF. MODELFAN HEATING

KWV/Ph

MOTORFLA

MCA MOCPCFM ESP SPEED

BC-1,2,3 TRANE GAM5B0A18 350 0.7 MED-LOW 2.88 208/1 4 21 25

BC-4 TRANE GAM5B0B30 850 0.7 HIGH 5.76 208/1 2.8 38 40

BC-5 TRANE GAM5B0C30 500 0.7 MED 5.76 208/1 2.8 38 40

Notes:

1. Single point connection required, coordinate the exact electrical requirements of equipment provided with E.C.

2. Electric heater shall not operate simultaneously with heat pump. Electric heater shall be used as back-up heat only.

VENTILATION FAN SCHEDULE

MARK MANUFACTURER MODEL CFM ESP (" wg) POWERVOLTS/

PHASENOTES

VF-1 COOK GC-148 130 0.25 46 W 120/1 1

NOTES:

1. Provide integral disconnect.

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

M6.1

PLUMBING SIZING SYMBOLS

DRAIN (X = SIZE)

VENT (X = SIZE)

WASTE STACK VENT (X = SIZE)

NOTES:

SEE SHEET M1.2 FOR FIXTURE TYPES.X"

X"

X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2

FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND

ADDITIONAL INFORMATION.

1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.

COORDINATE WITH G.C.

2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED

ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN

HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE

WITH G.C.

3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH

ARCHITECT.

4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"

ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.

COORDINATE WITH G.C.

5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.

6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.

7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT

DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,

COORDINATE EXACT ROUTING WITH G.C.

NOTES BY SYMBOL#

3"

2"

3"

2"

3"

3"

2"

3"3"4"

2"

3"

3"

2"

3" 3" 4"

2"

3"

2"

3" 3" 4"

4"

3"

2"

3"

2"

3"3"4"

4"

4"

4"

4"

4"

FFCO

2-WAY

FGCO

4"

4"

2"

2"

3"

4"

2"

4"

3"2"

4"

7 7 7 7 7

4"

MA

TC

HLIN

E

NE

3

3

3

3 3

3" 2-WAY

FGCO3"3"

2"

3"

4"

2"

4"3"

2"

3"

4"

2"

4"3"

6"4"

7 7

MA

TC

HLIN

E

MA

TC

HLIN

E

2"

3

1/8" = 1'-0"

UNDERFLOOR WASTE AND VENT PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P2.0

1/8" = 1'-0"

PARTIAL UNDERFLOOR WASTE AND VENT PLAN2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

PLUMBING SIZING SYMBOLS

DRAIN (X = SIZE)

VENT (X = SIZE)

WASTE STACK VENT (X = SIZE)

NOTES:

SEE SHEET M1.2 FOR FIXTURE TYPES.X"

X"

X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2

FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND

ADDITIONAL INFORMATION.

1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.

COORDINATE WITH G.C.

2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED

ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN

HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE

WITH G.C.

3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH

ARCHITECT.

4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"

ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.

COORDINATE WITH G.C.

5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.

6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.

7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT

DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,

COORDINATE EXACT ROUTING WITH G.C.

NOTES BY SYMBOL#

11

11

11

11

1

2

1

1

1

2

2"

2"

4"

2" 4"

2"

2"

3"

2"

2"

2"

2"

4"

4"

2-WAY

FGCO

2"

3"

2"

2"

2"

4"

4"

2-WAY

FGCO

2"

3"

2"

2"

2"

2"

4"

4"

2-WAY

FGCO

2"

3"

2"

2"

2"

4"

4"

2-WAY

FGCO

2" 3"

2"

2"

2"

4"

2"

3"

2"2"

2"

2"

4"

4"

2-WAY

FGCO

2"

3"

2"2"

2"

2"

4"

4"

2-WAY

FGCO

3"

2"

3"

FD

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

2"

4"

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

2"

4"

SH-A

WC-A

CCB

LAV-A

2"

3"

2"

FD

2"

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

2"

4"

KS-A

3"

2"

2"

2" 3"

2"

4"

2"

2" 3" 2"

2"4"

2"

2"

2"

3"

2-WAY

FGCO

4"

2"

3"

4"

2"

3"3"3"3"3"3"

4"

3"

3"

3"

3"

2"

2"

3"4"

1

KS-B

ST

3

3

3

3

3 35

4

2"

1

1

3"

2"

4"

7 7 7 7 7

2

WC

-BW

C-B

SS

FD

FD

LAV-B

EWC

LAV-B

FFCO

BS

MA

TC

HLIN

E

MA

TC

HLIN

E

4"

COORDINATE ROUTING OF PIPING ABOVE FIRST

FLOOR COMMON AREA CEILINGS WITH

LOCATIONS OF PRE-MANUFACTURED HOLES IN

BEAMS. SEE STRUCTURAL AND ARCHITECTURAL

DRAWINGS FOR MORE INFORMATION. FINAL

ROUTING SHALL BE COORDINATED WITH G.C.

AND OTHER TRADES PRIOR TO INSTALLATION.

11

11

11

2"

3"

2"2"

2"

2"

4"

4"

2-WAY

FGCO

2"

3"

2"2"

2"

2"

4"

4"

2-WAY

FGCO

2"

SH-A

WC-A

LAV-A

CCB

KS-A

3"3"

2"

3"

4"

2"

FD3" 3"

2"

3"

4"

2"

FD

SH-A

WC-A

V-A

3"

2"

D

2"2"

4"

3"

SH-B

WC-B

LAV-B

CCB

KS-B

3

7 7

MA

TC

HLIN

E

MA

TC

HLIN

E

2" VTR

FS

FS

1/8" = 1'-0"

FIRST FLOOR WASTE AND VENT PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P2.1

1/8" = 1'-0"

PARTIAL FIRST WASTE AND VENT PLAN2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

PLUMBING SIZING SYMBOLS

DRAIN (X = SIZE)

VENT (X = SIZE)

WASTE STACK VENT (X = SIZE)

NOTES:

SEE SHEET M1.2 FOR FIXTURE TYPES.X"

X"

X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2

FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND

ADDITIONAL INFORMATION.

1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.

COORDINATE WITH G.C.

2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED

ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN

HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE

WITH G.C.

3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH

ARCHITECT.

4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"

ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.

COORDINATE WITH G.C.

5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.

6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.

7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT

DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,

COORDINATE EXACT ROUTING WITH G.C.

NOTES BY SYMBOL#

SH-A

WC-A

LAV-A

CCB

KS-A

3"3"

2"

3"

4"

2"

FD

SH-A

WC-A

LAV-A

CCB

KS-A

3" 3"

2"

3"

4"

2"

FD

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

1

1 1

1 1

1 1

1 1 1

1 1

1 1

1

1 1

1 1 1 1

1 1

1 1

1 1

1

1

1

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

2"FD

1

1

1

1

1

1

1

1

1

2"

2"

2"

4"

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

2"

4"

SH-A

WC-A

CCB

LAV-A

2"

3"

2"

FD

2"

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"

3"

2"

3"

FD

2"

4"

2"

2"

2"

4"

SH-A

WC-A

CCB

LAV-A

KS-A

2"

3"2"

FD

2"

2"

2"

4"

SH-A

WC

-A

CCB

LAV-A

KS-A

2"

3"

2"FD

2"

2"

4"

SH-A

WC

-A

CCB

LAV-A

KS-A

2"

3"

FD

2"

2"

4"

SH-A

WC

-A

CCB

LAV-A

KS-A

2"

3"

FD

2"

2"

4"

SH-A

WC

-A

CCB

LAV-A

KS-A

2"

3"

FD

2"

2"

4"

SH-A

WC-A

CCB

LAV-B

KS-B

2"

3"

FD

2"

2"

4"

SH-B

WC-B

CCB

LAV-A

KS-A

2"

3"

FD

2"

2"

4"

SH-A

CCB

LAV-A

2" 3"

2"

FD

2"

2"

4"

WC

-BW

C-B

FD

FD

LA

V-B

EWC

LAV-B

SS

FWCO

CCB

2" 3"

2"

2"

2"

CCB

2" 3"

2"

2"

KS-A

3"

2" 2"2"

2" 2"2"

2"2"2"

CCB

LAV-A

KS-A

FD

WC-A

WC-A

SH-A

SH-A

SH-A

FD

FD

FD

LAV-A

LAV-A

LAV-A

WC-A

WC-A

KS-A

KS-A

KS-A

CCB

2"

2"

4"

2"

2" 3" 2"

2"4"

2"

3"

2"2"

3"

2"

1

1

11

1

3

3

3

3

3

3

3

3 3 3

3

1

4"

1

3"

7 7 7 7 7 7

7 77 77

7

77

7

7

7

7

3

1/8" = 1'-0"

SECOND FLOOR WASTE AND VENT PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P2.2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

PLUMBING SIZING SYMBOLS

DRAIN (X = SIZE)

VENT (X = SIZE)

WASTE STACK VENT (X = SIZE)

NOTES:

SEE SHEET M1.2 FOR FIXTURE TYPES.X"

X"

X"SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET M6.2

FOR INDIVIDUAL FIXTURE CONNECTION SIZES AND

ADDITIONAL INFORMATION.

1. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G., ABOVE SPLASH BLOCK.

COORDINATE WITH G.C.

2. CONNECT 3/4" CONDENSATE DRAIN FROM EACH PTAC TO COMMON 1"

CONDENSATE PIPE. ROUTE 1" CONDENSATE PIPE CONCEALED IN WALL AND

TERMINATE WITH ELBOW DOWN AT 12" A.F.G. WHERE PTAC IS LOCATED

ADJACENT TO EXTERIOR CONCRETE PAVING, SPILL CONDENSATE TO 2" OPEN

HUB DRAIN, ROUTE 2" PVC PIPE 3" BELOW GRADE TO DAYLIGHT. COORDINATE

WITH G.C.

3. 4" PVC PIPE FOR RADON SYSTEM. COORDINATE EXACT REQUIREMENTS WITH

ARCHITECT.

4. ROUTE 2" DISCHARGE FROM SUMP PUMP THROUGH EXTERIOR WALL AT 18"

ABOVE GRADE AND TERMINATE ABOVE SPLASH BLOCK WITH ELBOW DOWN.

COORDINATE WITH G.C.

5. ELEVATOR PIT SUMP PUMP, SEE 2:M6.2 FOR MORE INFORMATION.

6. ROUTE HORIZONTAL CONDENSATE PIPING ABOVE CEILING.

7. PROVIDE INDIRECT CONNECTION AT GARBAGE DISPOSER AND CONNECT

DISHWASHER. ROUTE DRAIN FROM DISHWASHER AT BACK OF CABINETRY,

COORDINATE EXACT ROUTING WITH G.C.

NOTES BY SYMBOL#

SH-A

LAV-A

WC-ACCB KS-A

2"

3"

3"2"

FD

3"

2"

WC

-BW

C-B

FD

FD

LAV-B

EWC

LAV-B

SS

1

1 1

1 1

1 1

1 1 1

1 1

1 1

1

1

1

11

11

11

1111

11

1

SH-A

WC-A

LAV-ACCB

KS-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

WC-A

CCB

LAV-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FDSH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

CCB

LAV-A

KS-A

FD

SH-A

CCB

LAV-A

KS-A

FD

SH-B

WC-B

CCB

LAV-B

KS-B

FD

SH-A

WC-A

CCB

LAV-A

KS-A

FD

SH-A

CCB

LAV-A

KS-A

FD

WC-A

WC-AWC-A

KS-A

2"

3"

2"

2"

3"2"

2"

3"

3"

2"

3"

2"

2"

2"

3"

2"

2"

3"

2"

2"2"

3"

2"

2"2"

3"

2"

2"2"

3"

2"

2"

3"

2"

2"

3"

2"3"

2"

2"

3"3"

2"3"

2"

2"

2"3"

2"

2"

3"3"

2"3"

2"

2"

WC-A

SH-A

SH-A

SH-A

FD

FD

FD

LAV-A

LAV-A

LAV-A

WC-A

WC-A

KS-A

KS-A

KS-A

2" 3" 2"

2"

2"

2"

2" 3" 2"

2"

2"

2"

2" 3" 2"

2" 3" 2"

2"

2"

3"3" VTR3"3"

3"3"

3"

3"3" 3"

3" VTR3" 3"3" VTR

3"

3" 3"

3"3" VTR

2"2" 3"

3"

3"

2"

3"

3"

3"

3"

3" VTR

2"

3"

3"

3"

3" VTR

1

1

1

1

1

1

1

1

11

1

1

1

3

3

3

3

33

3

3

3

3

3

1

LAV-A

WC-A

SH-A

CCB

FD

KS-A

7

7

7

7

7

77 77 77 77

77 77 7 7

CCB

CCB

CCB

1/8" = 1'-0"

THIRD FLOOR WASTE AND VENT PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P2.3

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

NOTES:

• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET

P6.1 FOR INDIVIDUAL FIXTURE CONNECTION

SIZES AND ADDITIONAL INFORMATION.

• 1/2" HOT WATER PIPING SHALL BE ROUTED TO

ENSURE THE MAX. DISTANCE FROM THE HOT

WATER RECIRCULATION LOOP TO PUBLIC

LAVATORIES DOES NOT EXCEED 2', PER 2018

IECC TABLE C404.5.1

NOTES BY SYMBOL# NOTES BY SYMBOL

1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.

2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.

3. SEE CIVIL DRAWINGS FOR CONTINUATION.

4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.

6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED

PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED

SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/

APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT

7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF

98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)

5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT

POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO

INSTALLATION.

8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.

9. PROVIDE SKID MOUNTED FIRE PUMP.

10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.

COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.

11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

#

WC

-BW

C-B

SS

LA

V-B

EWC

LA

V-B

HWH

HWP

SH-BWC-B

LA

V-B

CCB

KS-BSH-A

WC-A

CCB

LAV-A

KS-ASH-A

WC-A

CCB

LAV-A

KS-ASH-A

WC-A

CCB

LAV-A

SH-A

WC-A

CCB

LAV-A

KS-A KS-A

2"1-1/2"

1-1/2"

1-1/4"

3/4"

1-1/4"

6 6 6 6

6

4

P4.1

2

P4.1

2

P4.1

2

P4.12

P4.1

5

5

5

WH

WH

WH

MA

TC

HLIN

EM

AT

CH

LIN

E

BS

4

P6.1

4

COORDINATE ROUTING OF PIPING ABOVE FIRST

FLOOR COMMON AREA CEILINGS WITH

LOCATIONS OF PRE-MANUFACTURED HOLES IN

BEAMS. SEE STRUCTURAL AND ARCHITECTURAL

DRAWINGS FOR MORE INFORMATION. FINAL

ROUTING SHALL BE COORDINATED WITH G.C.

AND OTHER TRADES PRIOR TO INSTALLATION.

FP

WW

SH-A

WC-A

LAV-A

CCB

KS-ASH-B

WC-B

LA

V-B

CCB

3"

3" UP

10

9

8

7

66

1

P4.1

5WH

1

2

MA

TC

HLIN

EM

AT

CH

LIN

E

3

4

1/8" = 1'-0"

FIRST FLOOR DOMESTIC WATER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT

TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN

CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS

ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.

P2.4

1/8" = 1'-0"

PARTIAL FIRST FLOOR DOMESTIC WATER PLAN2

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

HWH-AHWPSS

WC

-BW

C-B

LAV-B

EWC

LA

V-B

SH-A

WC-A

LAV-A

CCB

KS-ASH-A

WC-A

LAV-A

CCB

KS-ASH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-ASH-A

WC-A

CCB

LAV-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

CCB

LAV-A

KS-A

SH-A

CCB

LAV-A

KS-ASH-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-B

KS-B

SH-B

WC-B

CCB

LAV-A

KS-ASH-A

CCB

LAV-A

CCB

CCB

KS-A

CCB

LAV-A

KS-A

SH-A

SH-A

SH-A

LAV-A

LAV-A

LAV-A

WC-A

WC-A

KS-A

KS-A

KS-A

CCB

WC-A WC-A WC-A

3"

2"

3"

1-1/2"

1-1/2"

6

6

6

6 6

6

66

6 6

6 6

6

6

6 6

6

1

P4.1

1

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

3

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

5 5

5

WH WH

WH

2"

1-1/2"

1-1/4"

1"

3

P6.1

11111111

11

6

6

NOTES:

• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET

P6.1 FOR INDIVIDUAL FIXTURE CONNECTION

SIZES AND ADDITIONAL INFORMATION.

• 1/2" HOT WATER PIPING SHALL BE ROUTED TO

ENSURE THE MAX. DISTANCE FROM THE HOT

WATER RECIRCULATION LOOP TO PUBLIC

LAVATORIES DOES NOT EXCEED 2', PER 2018

IECC TABLE C404.5.1

NOTES BY SYMBOL# NOTES BY SYMBOL

1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.

2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.

3. SEE CIVIL DRAWINGS FOR CONTINUATION.

4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.

6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED

PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED

SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/

APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT

7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF

98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)

5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT

POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO

INSTALLATION.

8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.

9. PROVIDE SKID MOUNTED FIRE PUMP.

10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.

COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.

11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

#

1/8" = 1'-0"

SECOND FLOOR DOMESTIC WATER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT

TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN

CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS

ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.

P2.5

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

SS

WC-B

WC-B

LAV-B

EWC

LAV-B

SH-A

LAV-A

WC-ACCB KS-A

SH-A

WC-A

LAV-ACCB

KS-ASH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-ASH-A

WC-A

CCB

LAV-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-ASH-A

WC-A

CCB

LAV-A

KS-A

SH-A

WC-A

CCB

LAV-A

KS-A

SH-A

CCB

LAV-A

KS-ASH-A

CCB

LAV-A

KS-ASH-B

WC-B

CCB

LAV-B

KS-B

SH-A

WC-A

CCB

LAV-A

KS-ASH-A

CCB

LAV-A

KS-A

WC-AWC-A

KS-A

SH-A

SH-A

SH-A

LAV-A

LAV-A

LAV-A

WC-A

WC-A

KS-A

KS-A

KS-A

1

P4.1

1

P4.1

2

P4.1

3

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

2

P4.1

SH-AWC-A

LAV-A

KS-A

CCB

CCB

CCB

CCB

NOTES:

• SEE PLUMBING ROUGH-IN SCHEDULE ON SHEET

P6.1 FOR INDIVIDUAL FIXTURE CONNECTION

SIZES AND ADDITIONAL INFORMATION.

• 1/2" HOT WATER PIPING SHALL BE ROUTED TO

ENSURE THE MAX. DISTANCE FROM THE HOT

WATER RECIRCULATION LOOP TO PUBLIC

LAVATORIES DOES NOT EXCEED 2', PER 2018

IECC TABLE C404.5.1

NOTES BY SYMBOL# NOTES BY SYMBOL

1. FIRE PROTECTION RISER. SEE DIAGRAM ON SHEET M6.2 FOR MORE INFORMATION.

2. 3" DOMESTIC WATER SERVICE AND SHUT OFF VALVE.

3. SEE CIVIL DRAWINGS FOR CONTINUATION.

4. DOMESTIC WATER PIPING OCCURS BETWEEN FIRST AND SECOND FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

5. COORDINATE WALL HYDRANT MOUNTING HEIGHT WITH ARCHITECT.

6. PROVIDE 1-1/4" WATER SERVICE TO EACH APARTMENT, REFERENCE ENLARGED

PLUMBING PLANS ON SHEET P4.1 FOR MORE INFORMATION. PROVIDE FULL-SIZED

SHUT-OFF VALVE FOR EACH APARTMENT. LABEL EACH SHUTOFF VALVE W/

APARTMENT NUMBER OF UNIT BEING SERVED. COORDINATE W/ ARCHITECT

7. PROVIDE WATER PRESSURE BOOSTER SYSTEM CAPABLE OF INCREASING PRESSURE OF

98 GPM BY 50 PSI, EQUIVALENT TO QUANTUM FLO "PRODIGY E2", COMPLETE WITH (2)

5 HP VARIABLE SPEED DUPLEX PUMPS, 3" HEADERS, 208V/3Ø MOTORS, SINGLE POINT

POWER CONNECTION. PROVIDE MANUFACTURER'S ANALYSIS OF SYSTEM PRIOR TO

INSTALLATION.

8. PROVIDE FULL SIZED VALVED BYPASS OF BOOSTER SYSTEM.

9. PROVIDE SKID MOUNTED FIRE PUMP.

10. FIRE PROTECTION SERVICE ENTRANCE. INSTALL IN ACCORDANCE WITH NFPA 13R.

COORDINATE LOCATION OF ALL VALVES AND APPURTENANCES WITH AHJ.

11. DOMESTIC WATER PIPING OCCURS BETWEEN SECOND AND THIRD FLOOR. LOCATE

SHUT-OFF VALVES ABOVE LAY-IN CEILINGS. COORDINATE LOCATIONS WITH

ARCHITECT.

#

1/8" = 1'-0"

THIRD FLOOR DOMESTIC WATER PLAN1

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

AVAILABLE SPACE ABOVE CEILINGS IS LIMITED. ROUTE FIRE PROTECTION PIPING TIGHT

TO STRUCTURE, AND PROVIDE OFFSETS AND DRAINS AS REQUIRED TO MAINTAIN

CEILING HEIGHTS AS INDICATED ON ARCHITECTURAL DRAWINGS. SHOP DRAWINGS

ARE TO INCLUDE CEILING HEIGHTS AND INDICATE COORDINATION WITH SAME.

P2.6

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

KS-A

ICB

CCB SH-A

WC-A

LAV-A

HWH

1" 3/4"

3/4"

1"

3/4"

1-1/4"1-1/4"

1

3

1

25

P6.1

KS-B

ICB

CCB

SH-B

WC-B

LAV-B

HWH

3/4" 3/4"

1"1"

1-1/4" 1-1/4"

1 1

2

3

5

P6.1

KS-A

ICB

CCB

SH-A

WC-A

LAV-A

HWH

3/4" 3/4"

1"1"

1-1/4" 1-1/4"

11

2

3

5

P6.1

CCB SH-B

WC-B

LAV-B

HWH

KS-B

ICB

1"3/4"

3/4"

1"

3/4"

1-1/4"

1

3

5

P6.1

ENLARGED PLAN NOTES BY SYMBOL#

1. SEE OVERALL DOMESTIC WATER PLANS FOR CONTINUATION.

2. 1-1/4" WATER SERVICE FOR UNIT ABOVE. ROUTE PIPING FOR 3RD FLOOR UNITS

BELOW FLOOR ABOVE SECOND FLOOR CEILING SIMILAR TO PIPING SHOWN. DO NOT

ROUTE PIPING IN ATTIC.

3. PROVIDE 1/2" VALVED BRANCH BELOW SINK AND CONNECT DISHWASHER. ROUTE

PIPING ALONG BACK OF CABINETRY, COORDINATE EXACT ROUTING WITH G.C.

COORDINATE EXACT REQUIREMENTS WITH DISHWASHER PROVIDED.

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

1/4" = 1'-0"

1 BEDROOM ENLARGED DOMESTIC WATER2

1/4" = 1'-0"

2 BEDROOM ENLARGED DOMESTIC WATER1

1/4" = 1'-0"

1 BEDROOM HC ENLARGED DOMESTIC WATER3

1/4" = 1'-0"

2 BEDROOM HC ENLARGED DOMESTIC WATER3

P4.1

PROJECT SHALL COMPLY WITH ALL

REQUIREMENTS OF THE 2018 IECC.

REFERENCE SPECIFICATIONS FOR

COMMISSIONING REQUIREMENTS.

NOTE:

FIXTURE TAGS INDICATED ARE FOR TYPICAL

APARTMENT. SEE PLANS AND PLUMBING

FIXTURE SCHEDULE FOR EXACT FIXTURE TYPES.

PLUMBING SIZING SYMBOLS

DRAIN (X = SIZE)

VENT (X = SIZE)

WASTE STACK VENT (X = SIZE)

X"

X"

X"

LAV

LAV

CCB

CCB

WC

WC

SH

SEE PLANS FOR

CONTINUATION OF

VENT PIPING, TYPICAL.

SH

KS-A

KS-A

KS-A

LAV

CCB

WC

SH

NO SCALE1

TYPICAL 2 BEDROOM

WASTE & VENT ISOMETRIC

FD

FD

FD

LAV-A

LAV-A

SH-A

CCB

CCB

SEE PLANS FOR

CONTINUATION OF

VENT PIPING, TYPICAL.

KS-A

KS-A

SH-A

NO SCALE2

TYPICAL 1 BEDROOM (3-FLOOR)

WASTE & VENT ISOMETRIC

WC-A

WC-A

LAV-A

CCB

KS-A

FD

FD

SH-A

LAV-A

LAV-A

CCB

CCB

SEE PLANS FOR

CONTINUATION OF

VENT PIPING, TYPICAL.

KS-A

KS-A

NO SCALE3

TYPICAL 1 BEDROOM (2-FLOOR)

WASTE & VENT ISOMETRIC

FD

FD

SH-A

SH-A

WC-A

WC-A

WC-A

WC-B

WC-B

WC-B WC-B

SEE PLANS FOR

CONTINUATION OF

VENT PIPING, TYPICAL.

LAV-B

LAV-B

LAV-B

LAV-B

FD

FD

FD

FD

EWC

EWC

NO SCALE4

PUBLIC RESTROOMS

WASTE & VENT ISOMETRIC

SS

SS

KS-A

KS-A

NO SCALE5

TYPICAL 1 BEDROOM ABOVE COMMONS

WASTE & VENT ISOMETRIC

FD

WC-A

WC-A

SH-A

SH-A

FD

LAV-A

LAV-A

CCB

CCB

FD

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P5.1

FIRE PROTECTION RISER DIAGRAM

Not to Scale1

GROUND FLOOR

CHECK VALVE.PROVIDE BALLDRIP AS REQUIRED.

PRESSURE GAUGEWITH VALVE, TYPICAL

TAMPER SWITCH, TYP.

WATER FLOW DETECTOR.

ANGLE VALVE

2" TEST/DRAIN

TO AUTOMATICSPRINKLER SYSTEM

CLOSET WALL

WET HEADS.

PROVIDE 4" LINE TO FIRE

DEPARTMENT CONNECTION.COORDINATE LOCATION AND

SIZE WITH FIRE DEPARTMENT.

PROVIDE THRUST BLOCKSAT CHANGES IN DIRECTION.

FIRE SPRINKLER SERVICE.

VERIFY SIZE

REQUIREMENTS WITHPRESSURE AVAILABILITYAND FIRE SPRINKLER

REQUIREMENTS.

PR

EV

EN

TER

, W

AT

TS 7

09 O

R E

QU

AL.

DO

UBLE C

HEC

K T

YPE B

AC

KFLO

W

FLO

W T

EST

ING

PER

NFPA

REQ

UIR

EM

EN

TS.

PR

OV

IDE A

PPR

OV

ED

MEA

NS O

F F

ORW

ARD

VERIFY BACKFLOW PREVENTER

REQUIREMENTS WITH CITY PRIORTO PURCHASE AND INSTALLATION.

PLUMBING FIXTURE SCHEDULE

MARK MANUFACTURER DESCRIPTION

TRIM ROUGH-IN SIZES

NOTES

MANUFACTURER DESCRIPTION WASTE VENT CW HW

WC-A KOHLER

Model #K-3658-(RA)-0 "Highline Classic" ADA

compliant flush tank water closet, white vitreous

china, two piece, 12" rough-in, elongated 16-1/2"

high bowl, siphon jet flushing action, 1.28 GPF,

polished chrome actuator. Coordinate location

of trip lever with installation.

KOHLER#K-4636-0 white, closed front plastic seat

with slow closing lid.4" 2" 1/2" --- 1

WC-B KOHLER

Model #K-3658-(RA)-0 "Highline Classic" ADA

compliant flush tank water closet, white vitreous

china, two piece, 12" rough-in, elongated 16-1/2"

high bowl, siphon jet flushing action, 1.28 GPF,

polished chrome actuator. Coordinate location

of trip lever with installation.

KOHLER

#K-4731-CA-0 white, open front,

anti-microbial plastic seat without lid, with

check hinge.4" 2" 1/2" --- 1

LAV-A KOHLERModel 2196-4-0 self-rimming lavatory, white

vitreous china, 20"W x 17", faucet holes on 4"centers.

KOHLER#K-394-4-2 two handle faucet with pop-up

drain and nickel finish.2" 1-1/2" 1/2" 1/2" 1,2,3

LAV-B KOHLERModel #K-2196-4-0 self-rimming lavatory, white

vitreous china, 20"W x 17", faucet holes on 4"centers.

KOHLER

#K-393-N4-2BZ faucet. Provide grid drain,

nickel finish, and point of use tempering

valve.

2" 1-1/2" 1/2" 1/2" 1,2,3

KS-A KOHLER

Model K-3369-3 two compartment 18 GA

stainless steel top-mount sink,

14-1/2"x16-1/2"x8"D inside, fully undercoated,

faucet holes as required.

KOHLER

INSINKERATOR

#K-780 single handle pull down kitchen

sink faucet with chrome finish, single hole

installation. Provide basket strainer.

Badger 5 12 HP garbage disposal with

dishwasher waste connection.

2" 1-1/2" 1/2" 1/2" 1,2,3,5

KS-B JUST

Model DL-ADA-2233-A-GR two compartment 18

GA stainless steel sink, self rimming,

14"x16"x5"D inside, fully undercoated, faucet

holes as required, and drain hole center rear.

KOHLER

IN-SINK-ERATOR

#K-780 single handle pull down kitchen

sink faucet with chrome finish, single hole

installation. Provide basket strainer.

Badger 5 12 HP garbage disposal withdishwasher waste connection.

2" 1-1/2" 1/2" 1/2" 1,3,2,4

BS ELKAY

Model DLR172210 single compartment 18 GA.

Stainless steel sink, self rimming, 14"x16"x10"D

inside, fully undercoated, faucet holes as

required.

DELTA

Model 27C4844 two handle bar sink

faucet, 4-1/2" gooseneck spout, 1.5 GPM

aerator, 4" blade handles, chrome finish.

Provide basket strainer.

2" 1-1/2" 1/2" 1/2" 2,4

SH-A AQUARIUS

Model 'G-3682BF RFF' reinforced fiberglass ADA

shower, 36"W x36"D x76-1/2"H, with integral

soap/toiletry shelves and grab bars in

accordance with ADA requirements. Provide

blocking for future installation of fold-up seat,

right or left hand rough-in as required. Provide

with collapsible dam.

KOHLER

#K-304 pressure balancing valve with

integral temperature limits and stops,

#K-TS10584-4 valve trim, #K-355 wall

supply elbow, #K-9514 60" hose,

#K-10549 hand shower, and

#K-8524/K-349 slide bar. Entire assembly

shall have nickel finish.

2" 1-1/2" 1/2" 1/2" 1

SH-B AQUARIUS

Model 'G-3682BF RFF' reinforced fiberglass ADA

shower, 36"W x36"D x76-1/2"H, with integral

soap/toiletry shelves and grab bars in

accordance with ADA requirements, fold-up seat,

right or left hand rough-in as required, white

finish. Provide with collapsible dam.

KOHLER

#K-304 pressure balancing valve with

integral temperature limits and stops,

#K-TS10584-4 valve trim, #K-355 wall

supply elbow, #K-9514 60" hose,

#K-10549 hand shower, and

#K-8524/K-349 slide bar. Entire assembly

shall have nickel finish.

2" 1-1/2" 1/2" 1/2" 1

SS FIAT

Model MSB-2424 one piece molded stone mop

basin, 24" square, stainless steel integral drain

body with caulk connection, stainless steel wall

guards.

DELTA

Model 28T9 faucet with hose thread outlet,

vacuum breaker, pail hook, wall brace,

metal lever handles.

3" 1-1/2" 3/4" 3/4" 4

WH WOODFORD Model 25 frost proof wall hydrant with anti-siphon vacuum breaker, metal handle. --- --- 3/4" ---

CCB WATER-TITEModel W4700 recessed washing machine box with 2"PVC/ABS drain coupling and knockout test cap. Two brass

1/4 turn adaptor ball valves with hammer arresters, sweat connection.2" 2" 1/2" 1/2"

ICB OATEY Model 3848X fire rated ice maker connection box with 1/4 turn ball valve. --- --- 1/2" ---

FD WADEModel 1102STD5 floor drain with satin nickel bronze strainer. Provide trap protection device equal to ProSet

Trapguard.2" 1-1/2" --- ---

FS WADEModel 9140 floor sink with 8" deep body, enameled interior, sediment bucket, nickel bronze trim and grate with

openings as requried. Provide trap protection device equal to ProSet Trapguard.3" 1-1/2" --- ---

EWC ELKAY

Model EZTL8C ADA compliant dual height, self-contained water cooler with stainless steel basin, front push bar

actuator, lead-free cooling system capable of cooling 8.0 GPH, 120 volts. Provide cane apron equal to Elkay

model 'LKAPREZL'

2" 1-1/2" 1/2" ---

HWH-A A.O. SMITHModel EJCS-20, 20 gallon electric water heater, 2500 watts, 208 volts heating element, 11 GPH recovery @ 90°F temp rise. Supplied with temperature

& pressure relief valve and brass drain valve.6

HWH A.O. SMITHModel ENT-40, 40 gallon electric water heater, 4500 watts, 208 volts heating element, 21 GPH recovery @ 90°F temp rise. Supplied with temperature

& pressure relief valve and brass drain valve.

HWP BELL & GOSSETT Model NBF-33 circulation pump, bronze body, 10 GPM @ 10' head, 120 VAC. Provide clamp-on aquastat for pump control. 7

GENERAL:

• Provide fixtures with all trim necessary for complete installation.

• Ensure all fixtures meet the requirements of the Texas Administrative Code Chapter 372.

• All toilets, lavatory faucets, showerheads, and kitchen faucets shall have EPA's WaterSense label.

NOTES:

1. In areas open to the public, fixture and installation to meet requirements of Americans with Disabilities Act. In apartments, fixture and installation to meet requirements of the Fair Housing Act.

2. Provide Dearborn supplies with stops and escutcheon plate, 1-1/4" cast brass p-trap.

3. Insulate water and waste piping below lavatory. Utilize insulation kit equivalent to LavGuard by Truebro. Provide Plumberex Model #3071WD-N disposal cover.

4. Trim shall be provided with polished chrome finish.

5. Provide Plumberex model #3071WD-N waste disposal cover.

6. Provide wall hung platform for water heater equal to Holdrite #50-SWHP-W-C. Coordinate exact location and mounting height with architect.

7. Pump shall have controls to prevent startup within 5 minutes from the end of the previous heating cycle. Hot water recirculation system shall meet all requirements of 2018 IECC.

FROM FIRE SPRINKLERAIR COMPRESSOR

HEADSTO DRY

GATE VALVE

SEE PLANS FOR CONTINUATION

DISCHARGE TO DAYLIGHT

CHECK VALVE - INSIDE BUILDING

UNION

SEE ELECTRICAL PLANS.ELECTRICAL CONNECTION.

AUDIBLE ALARMHIGH WATER

2"

ELEVATOR SUMP PUMP DETAIL

NO SCALE2

LIGHTHIGH WATER

WEIL #8341K1015SIMPLEX PUMP

CONTROL PANEL

24"Ø x 2'-0" DEEP OPEN FIBERGLASSBASIN WITH ANTI-FLOAT RINGS,

FIBERBASIN OR EQUAL, 3/16" WALLTHICKNESS, INLETS AS INDICATED ON

PLANS. PROVIDE WITH GRATE COVER.

DISCHARGE ELBOW AND DISCHARGEFLANGE KIT WEIL 2613K202

TETHERED LEVEL CONTROL,WEIL 8233K1006 WITHMOUNTING PLATE AND PIPE

OIL SMART WATER PUMP SWITCHMODEL OSS20PBPR6, MOUNT LOWESTPART OF PROBE 6" ABOVE THE

BOTTOM OF THE BASIN.

MOUNT ALARM SWITCH

SO THAT ALARM SOUNDSWHEN WATER LEVEL IS 6"BELOW TOP OF SUMP

SUBMERSIBLE SUMP PUMP,WEIL 1411, 50 GPM @20'

HEAD, 2" DISCHARGE, 1/2

HP MOTOR, 120V/1Ø.

HWH-A

JANITOR 207 WATER HEATER PIPING DIAGRAM

NO SCALE3

PROVIDE T & P RELIEF

VALVE. ROUTE 3/4" PIPE

FROM VALVE TO ABOVE 'SS'

1-1/4"

SHUT-OFF VALVE

UNION

HWP

A

PROVIDE CLAMP-ONAQUASTAT FOR

CONTROL OF CIRC. PUMP

SEE PLANS FORCONTINUATION

HWH

JANITOR 113 WATER HEATER PIPING DIAGRAM

NO SCALE4

PROVIDE T & P RELIEF VALVE.

ROUTE 3/4" PIPE FROM

VALVE TO DRAIN PAN

PROVIDE MOUNT AND

DRAIN PAN, SEEPLUMBING FIXTURESCHEDULE FOR MORE

INFORMATION.

PROVIDE WATTS MODEL

DETA-12 EXPANSIONTANK, OR EQUIVALENT.

ROUTE OVERFLOW DRAINTO SPILL DIRECTLY

ABOVE FLOOR DRAIN.

ROUTE OVERFLOWDRAIN TO SPILL IN 'SS'.

PROVIDE WATER HEATERDRAIN PAN.

HWH-A

APARTMENT WATER HEATER PIPING DIAGRAM

NO SCALE5

PROVIDE T & P RELIEF

VALVE. ROUTE 3/4" PIPEFROM VALVE TO DRAIN PAN

SHUT-OFF VALVE

UNIONPROVIDE WATTS MODELDETA-12 EXPANSION

TANK, OR EQUIVALENT.

ROUTE OVERFLOW DRAINTO SPILL DIRECTLY

ABOVE FLOOR DRAIN.

PROVIDE WATER HEATERDRAIN PAN.

ROUTE HOT AND COLD WATERPIPING TO APARTMENT FIXTURES.

SEE ENLARGED DOMESTIC WATERPLAN P4.1 FOR CONTINUATION.

APARTMENT WATERSERVICE - SEE PLANS FORROUTING AND SIZE

1-1/4"

UNION

HWP

A

PROVIDE CLAMP-ON

AQUASTAT FORCONTROL OF CIRC. PUMP

SEE PLANS FOR

CONTINUATION

PROVIDE WATTS MODELDETA-12 EXPANSION

TANK, OR EQUIVALENT.

SHUT-OFF VALVE

1"

NE

W S

EN

IOR

LIV

ING

UN

ITS

KE

RV

ILL

E,

TE

XA

S

[email protected]

4809 Vue Du Lac Place, Suite 201

Manhattan, Kansas 66503

785.587.8042 FAX 785.587.8039

LST Consulting Engineers, PAProject 20026 MARCH 2021

P6.1