ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Embed Size (px)

DESCRIPTION

The ECHO system monitors and controls temperature, airflow and pressure; ensuring the right air temperature, in the correct quantity and at the correct pressure is presented to the server inlet, enabling the utmost of efficiency. By varying airflow, ECHO operates not only with air volumes 50% less than traditional cooling systems but also much more efficiently and with elevated water temperatures that allow up to 95% free cooling (London, UK). In the following presentation which took place at Airedale International Air Conditioning's Head Office, Leeds, UK; Paul Oliver (Airedale Sales Director) and Tom Absalom (JCA Managing Director) will provide you with a detailed insight into the ECHO IT cooling system and how it can provide up to 95% free-cooling and a PUE of 1.2, providing outstanding energy efficiency, reduced operational costs and carbon impact. Full explanations of the products and controls involved are presented and an Illumina case study will profile real-life energy savings and benefits.

Citation preview

Page 1: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Welcome to the launch of Echo Paul Oliver, Airedale Tom Absalom, JCA

Page 2: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Airedale - an overview

25,000m2

Globaldistribution450 staff

UK premier test centre

A Modine company

Modine centre of excellence

Page 3: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Airedale - an overview

Page 4: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Why Airedale?• Approx 40 years of experience of designing precision air conditioning• Pioneer of free-cooling chillers• Experts in controls and system integration• Energy efficiency focusedAbout JCA• £33m group turnover per annum• Innovative data centre engineering solutions• Client focussed, non contractual collaborative approach• Specialists in live environment engineering

2007

Patent filed

2008

Design on system begins

Prototype and lifecycle

testing

Live application2009 2010 2011

Launch

JCA and Airedale

Page 5: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Designing for Demand – What do we mean?

30 mph 120 mph

30 mph 120 mph

Design criteria

Design criteria

Page 6: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Efficiency – Factors that affect!

Extra-urban

Urban

Combined

Page 7: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Why/How does Demand vary in a DC?

Daily

Infrastructure

Seasonal

Page 8: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Daily & Infrastructure Affects

% Load

Time

100%

Page 9: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Increasing Temperature = Increasing Opportunity

ROOM

ROOM = 20 - 27°C

RACK

RACK = 28 - 47°CCPU

CPU = 60 - 100°C

Increasing Opportunity

Increasing Opportunity

Page 10: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

ASHRAE – TC 9.9 Thermal Guidelines

Increasing Opportunity

Page 11: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Rising Temperature and Cost Savings

Room temp ºC

№ CRAC units for 800kW

22 27

12

8

300,000 kgCO2 200,000 kgCO2

£63,000 £42,000

CO2

£

CRAC unit

CRAC unit

Running costs

Page 12: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Air Containment – Why is it so important?

Page 13: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Airflow Management

Mixing of Air

Page 14: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

What is PUE?

UTILITYCOMPANY Power

•Switchgear•UPS•Battery BackupCooling•Chillers•CRACs

IT EQUIPMENTPOWER•Servers•Storage

Power Usage EffectivenessPower Usage Effectiveness

PowerEquipmentIT

PowerFacilityTotalPUE

..

..

Power In Power In

TOTAL FACILITY POWER

Page 15: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Containing P.U.E. at part load

P.U.E.

Data Centre Load

1

100%50%0%

3

5

Desired

Typical

Page 16: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Bespoke Solution

Dynamic Performance

Efficient design

IntegratedFree Cooling

Designing for

Demand

Page 17: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Z

Taking Advantage of Ambient Temperatures

Page 18: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Capacity (kW)

Ambient temp (ºC)

5 10 15 20 25 30

400

800Cooling required

Frequency

7% 30% 70% 93%

All Free Cooling Systems are Not Equal

Page 19: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

ECHO – System Components

ECHO RacksECHO Racks

ECHO Active ECHO Active Cabinet ExhaustCabinet Exhaust

ECHO Free Cooling ECHO Free Cooling ChillerChiller

ECHO Chilled Water ECHO Chilled Water CRAC’sCRAC’s

Page 20: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Paul Oliver Sales Director

Tom Absalom, JCA

Page 21: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Four Fast Facts

Heat (n) : the energy transferred as a result of a difference in temperature

Cooling capacity is a direct function of the cooling medium type, flow rate of that medium and temperature difference of that medium

With the exception of some direct water cooled systems, the vast majority of IT equipment deployed in data centres today is air cooled

Whether the cooling system uses water, refrigerant or CO₂ as the secondary cooling medium, the fluid that directly cools electronic components is air

Page 22: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Methods of Cooling

Conventional Downflow CRAC/CCU

+ Chilled water or direct expansion (DX)

+ Cooling units can be mounted external to the technical space

+ Redundancy achieved at room/zone level

– Approx 4-5kW maximum cooling per rack at standard conditions

– Prone to short cycling & hot spots

Page 23: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Methods of Cooling

Rack Cooling

+ Chilled water, CO₂, pumped R134a

+ 30kW cooling capacity or more per rack

+ Control of cooling at rack level

– Cooling services in technical space

– Redundancy and infrastructure cost is minimum 2N

– Temperature rise on cooling failure is rapid

Page 24: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Q = M Cp Δt

Where :

Q = nett sensible cooling capacity (enthalpy change kW) M = mass flow rate (kg/s) Cp = specific heat capacity (kJ/kg) Δt = dry bulb temperature differential (°K)

First law of thermodynamics : Energy can neither be created or destroyed

Page 25: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Evaluating Cooling Requirements

A CRAC unit rated at 30kW supplies 2.5m³/s of air with a supply temperature of 14°C and return air temperature of 24°C (temperature differential 10°K) to achieve 30kW nett sensible cooling capacity

A rack cooler rated at 30kW supplies 1.25m³/s of air with supply temperature of 20°C and return air temperature of 40°C (temperature differential 20°K) to achieve 30kW nett sensible cooling capacity

Page 26: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

CRAC 30kW = 2.94 x 1.02 x 10

Rack Cooler 30kW = 1.47 x 1.02 x 20

Blade 30kW = 1.56 x 1.02 x 19

Evaluating Cooling Requirements

Page 27: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Typical Cooling Parameters

CRAC/CCU Method

Page 28: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

What Is Being Cooled?

Approx 5.1kW heat rejection per chassis 465cfm (0.22m3/s) per chassis Temp. difference of 19°K required for 5.1kW

at airflow rate shown

Typical Blade Server

Page 29: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Criteria Example Server CRAC/CCU Rack

Cooler

Supply temperature (°C) 20.0 14.0 20.0

Return temperature (°C) 39.0 24.0 40.0

Temperature differential (°K) 19.0 10.0 20.0

l/s air per kW cooling 44.0 83.3 41.6

Parameters Compared

Cooling Parameters of Blade Server and Different Cooling Methods

Page 30: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Interim Conclusion

Operational Imbalance

Page 31: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

The Solution

Echo IT Cooling System (patent applications 0711247.7 & 0911444.8)

Page 32: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Not Just Another Chimney

Sensing Locations

Page 33: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Active Cabinet Exhaust

Control it, Optimise it

Twin EC variable Speed Fans (N+1 up to 18kW per rack)

Quick swap ACE controller

Quick swap fan tray

Dual temperature sensors in air stream

Incident panel releases upon high temperature alarm to vent

cabinet to room.

Pressure monitoring at front & rear of

cabinet

Page 34: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Pressure Control

1U server heat sink fanexternal static 0-5pa

Closed loop = fans in series

100kW CRAC unit8480l/s

1U server heat sink fan50l/s

100kW CRAC unitexternal static 50-100pa

Page 35: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Flexible DeploymentLoad server cabinets as required

Day 1Low load <4kW

Day 2Medium load 4-10kW

Day 3High load 11-20kW

Page 36: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Echo System Benefits

Page 37: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Energy Saving

By matching the server parameters there is no need to overcool i.e. maintain a room between 14 and 24°C when the server should be between 20 and 40°C or even higher!

Speed controlled fans ensure that airflow matches IT requirements Elevated return air temperatures make cooling coils more efficient Elevated water temperatures allow for partial free-cooling for 95% of

the year & full free-cooling for 50% (London, UK)

How is it Achieved?

Page 38: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Energy SavingHow is it Achieved?

Page 39: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

How Much Does It Cost?

£2,000,000

£1,000,000 Standard Free - cooling

System

Echo Cooling System21%

increase in cost

Page 40: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

How Much Can Be Saved?

Standard Free - cooling

System

Echo Cooling System

£500,000

£250,000

Annual difference

55.8%

Typical payback < 27 months

Page 41: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Project Meridian - an OverviewNew HQ for Illumina Europe

Page 42: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

• Mission: Illumina’s mission is to be the leading provider of integrated solutions that advance the understanding of genetics and health.

• Consumables Manufacturing– Sequencing Consumables Mfg– Robust reagent mfg capability

• Commercial– European HQ for Commercial– High Quality Customer facing

attributes– Support for European field teams

• Research– Primary Illumina site for Sequencing

Research & Development– Sequencing applications research &

development

Project Meridian - an OverviewNew HQ for Illumina Europe

Page 43: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Project Meridian - an OverviewData Centre

Page 44: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Energy SavingIllumina Operational Data

+ Full free-cooling was recorded up to 13°C ambient providing a PUE of 1.14

+ Echo cooling system COP 7.79 up to 13°C ambient + Based on test data predicted annualised PUE would be 1.22 to

1.28

+ 12 month record data shows 70% of year on full free cooling

+ Annualised PUE at part load 1.34

NOTE : this is without changes to operating temperatures as defined in the revised ASHRAE guidelines

Page 45: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Energy SavingIllumina Operational Data

Mechanical Cooling 21%

Partial Free -cooling 9%

Full Free -cooling 70%

Page 46: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Achieving Project Requirements

Energy efficient cooling solution Cost effective solution 12kW average load density per rack

position Maximum of 20kW in any single

rack position No fixed location of high density

cabinets at design stage Mixture of 19” rack based

hardware and free standing open post equipment

Page 47: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

SummaryEcho Cooling System

The Echo cooling system innovatively combines the benefits of traditional data centre cooling methods with the advantages of the latest rack based cooling systems, culminating in a uniquely distilled system offering the best of both approaches without compromise.

Page 48: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Echo Cooling Unit (ECU)

Key features at a glance:

• 6-150 kW• Chilled water• EC Fan• Latest controls technology• Class A EER’s• More cooling per m2

• Variable air volume• Dual power supply

Page 49: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Echo Free-cooling Chiller

Key features at a glance:

• 20-1350 kW• R410A, R407C, R134a• ESEER up to 5.69• Class A EER up to 3.68• Free-cooling virtually all year round• E-coated microchannel coils reduce life

cycle costs• EC fan for ultimate system efficiency• Interactive head pressure setpoint

management for energy optimisation

Page 50: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Active Cabinet Exhaust (ACE)

Key features at a glance:

• 2 – 20kW• Twin EC variable Speed Fans (N+1 up to 18kW per rack)• Pressure monitoring at front and rear of cabinet• Dual temperature sensors in air stream• Exhaust damper

Page 51: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Controls

Key features at a glance:

• Complete system control• Real time analysis• Complete System Diagnostics

Page 52: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

DeltaChill (FC) + SmartCool

Page 53: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

AiredalePrecision Air Conditioning

Market leader

#1 for R410A

6-150kW 7 system types

Energy efficientReliability / redundancy

Page 54: ECHO IT Cooling Seminar - How To... drive down IT cooling costs

Integrated solutions

#1 UK manufacturer

40-1200kW #1 for TurboCor

UK pioneer ofFree-cooling

First TurboCor FreeCool

AiredaleChillers