Upload
terry-penney
View
25
Download
1
Embed Size (px)
Citation preview
P bar Y Safety Consultants Alberta Canada
Arc Flash is not just in plants
Arc Flash can and does occur in a variety of locations have you covered this risk
with staff?
P bar Y Safety Consultants Alberta Canada
OK what is all the babble
P bar Y Safety Consultants Alberta Canada
High Risk
• In the United States alone!On the average, every day in the U.S. five to ten people are sent to special burn units due to arc-flash burns. “There are one or two deaths per day from these multi-trauma events,”
P bar Y Safety Consultants Alberta Canada
A large flash with burning results
P bar Y Safety Consultants Alberta Canada
Not always the cause
P bar Y Safety Consultants Alberta Canada
Big issues BIGGER Picture
P bar Y Safety Consultants Alberta Canada
Regardless if you are
• Regardless if you are the investigator or the worker, arc flash incidents can and have occurred in a variety of workplaces, so what have you covered with staff and what do you know?
P bar Y Safety Consultants Alberta Canada
Avoidance is not enough• The most common arc-flash hazard reduction methods
are: • Avoid the hazard area • Install arc-resistant switchgear • Add current-limiting devices • Reduce the relay time coordination settings • Improve protection schemes
• The energy produced by an arc-flash event is proportional to the voltage, current, and duration of the event (V • I • t). IEEE 1584-2002 concluded that arc time has a linear effect on incident energy. Therefore, reducing fault clearing times proportionately reduces arc flash.
P bar Y Safety Consultants Alberta Canada
Before they started work did they cover the minimum safety knowledge
P bar Y Safety Consultants Alberta Canada
Do you understandVoltage• NFPA 70E requires the voltage exposure to be identified as part of the shock hazard analysis
and that it is included on the energized electrical work permit and arc flash warning labels. This item documents the voltage for the specific equipment.
Equipment type• Depending on the equipment type, such as panel or switchgear, the IEEE 1584 arc flash
calculations may use different arc gaps, working distance and rate of decay of the incident energy as a function of distance. Each of these values affects the results and makes defining the correct equipment type very important.
Arc gap• An arc flash occurs when short-circuit current jumps across an air gap. The gap’s size affects
the arcing short-circuit current calculations and possibly also the duration. These values are used to calculate the prospective incident energy.
Bolted fault current• “Bolted” refers to a short circuit where the faulted conductors act as though they are solidly
connected or bolted together. This current is used to evaluate equipment’s interrupting or withstand rating and to calculate the arcing fault current.
P bar Y Safety Consultants Alberta Canada
Do you understandEstimated arcing fault current• The arcing fault current is the current that flows across the arc gap. It is used for determining
the arcing time and incident energy and is influenced by variables, such as system grounding, the arc gap, and whether the arc flash occurs in equipment or in open air.
Arcing time• The duration of an arc flash is normally defined by the time it takes an upstream protective
device to clear the fault. Time-current curves from a coordination study and the estimated arcing short circuit are used to determine this value. (Editor’s note: Stay tuned for Jim Phillips’ article about coordination in the May issue.)
Arc flash boundary• The distance from an arc that it takes for the incident energy to fall to 1.2 cal/cm2 is known as
the arc flash boundary and is part of the calculation process. Defining this boundary is an NFPA 70E requirement for the arc flash hazard analysis.
Working distance• The working distance defines the distance from the arc flash where the incident energy is
calculated. It is normally considered where a worker’s head and torso would be located.
P bar Y Safety Consultants Alberta Canada
Do you understand
Incident energy• The incident energy at a specific working distance defines
the severity of the arc flash and is used to determine the minimum protection for the worker.
PPE level• Although there sometimes is debate about using personal
protective equipment levels, it is still a common practice. Many in the industry will assign a level using numbers that typically correspond to a minimum arc-rating requirement for protective clothing and equipment of 4, 8, 25 and 40 cal/cm2 respectively
P bar Y Safety Consultants Alberta Canada
Did you cover
P bar Y Safety Consultants Alberta Canada
Risks and what is around the door
P bar Y Safety Consultants Alberta Canada
The risks are closer than you think!
P bar Y Safety Consultants Alberta Canada
Mines are not the only risk, think any site with electrical operations
P bar Y Safety Consultants Alberta Canada
So before you enter before the work
P bar Y Safety Consultants Alberta Canada
Everyone on site needs this talk