74

Click here to load reader

Power transformer protection

Embed Size (px)

Citation preview

Page 1: Power transformer protection

PowerPowerTransformerTransformerProtectionProtection

Page 2: Power transformer protection

The electrical windings and the magnetic core in a transformer are subject to a number of different forces during operation, for example:

Expansion and contraction due to thermal cycling

Vibration

Local heating due to magnetic flux

Impact forces due to through-fault current

Excessive heating due to overloading or inadequate cooling

Why do Transformers Fail?

Transformer Protection

Page 3: Power transformer protection

Cost of repairing damage

Cost of lost production

Adverse effects on the balance of the system

The spread of damage to adjacent equipment

The period of unavailability of the damaged equipment

Costs and other factors to be considered

Transformer Protection

Page 4: Power transformer protection

Windings- Insulation deterioration from:

MoistureOverheatingVibrationVoltage surgesMechanical Stress from through-faults

LTCs- Malfunction of mechanical switching mechanism- High resistance contacts- Overheating- Contamination of insulating oil

What Fails in Transformers?

Transformer Protection

Page 5: Power transformer protection

Bushings- General aging- Contamination- Cracking- Internal moisture

Core Problems- Core insulation failure- Open ground strap- Shorted laminations- Core overheating

What Fails in Transformers?

Transformer Protection

Page 6: Power transformer protection

Miscellaneous

- CT Issues

- Oil leakage

- Oil contamination

Metal particles

Moisture

What Fails in Transformers?

Transformer Protection

Page 7: Power transformer protection

1003891001127100262Total26101672412Miscellaneous1422437Core failures313671719

Terminal board failures

1142101141541Bushing failures2285212311949

Tap changer failures

371445561551134Winding failures% of TotalNumber% of TotalNumber% of TotalNumber

19881983-19821975-19651955-Failure Statistics of Transformers

Source: IEEE C37.91

Failure Statistics of Transformers

Transformer Protection

Page 8: Power transformer protection

87T

50

51 51G

High Side Low Side

“Guide for Protective Relay Applications for Power Transformers”ANSI / IEEE C37.91

Transformer Protection

Page 9: Power transformer protection

24: Overexcitation (V/Hz)46: Negative Sequence Overcurrent49: Thermal Overload50: Instantaneous Phase Overcurrent50G: Instantaneous Ground Overcurrent50N: Instantaneous Residual Overcurrent50BF: Breaker Failure51G: Ground Inverse Time Overcurrent51N: Residual Inverse Time Overcurrent63: Sudden Pressure Relay (Buccholtz Relay)81U: Underfrequency87H: Unrestrained Phase Differential87T: Transformer Phase Differential with Restraints’87GD: Ground Differential (also known as “restricted earth fault”)

IEEE Devices used in Transformer Protection

Transformer Protection

Page 10: Power transformer protection

Internal Short Circuits- Phase Faults- Ground Faults

System Short Circuits (Back Up Protection)- Buses and Lines

Phase FaultsGround Faults

Abnormal Conditions- Open Circuits- Overexcitation- Abnormal Frequency- Abnormal Voltage- Breaker Failure- Overload- Geo-magnetically induced current (GIC)

Transformer Protection Review

Transformer Protection

Page 11: Power transformer protection

Accumulated Gases- Arcing by-products (Ex: Buchholz Relay)

Pressure Relays- Arcing causing pressure waves in oil or gas space

(Sudden Pressure Relay)

Thermal- Caused by overload, overexcitation, harmonics

and Geo-magnetically induced currentsHot spot temperatureTop OilLTC Overheating

Types of ProtectionMechanical

Transformer Protection

Page 12: Power transformer protection

In and Out of Zone

PhaseFault

GroundFault

BreakerFailure

PhaseFault

GroundFault

BreakerFailure

Overexcitation

UndervoltageUnderfrequency

Open Conductor

Overload

Transformer Electrical Protection Issues

Overexcitation

Transformer Protection

Page 13: Power transformer protection

Internal Short Circuit- Phase: 87T, 87H- Ground: 87T, 87GD

System Short Circuit (Back Up Protection)- Phase and Ground Faults

50, 50G, 50N, 51, 51G, 51N, 46

Detection Elements

Transformer Protection

Page 14: Power transformer protection

Abnormal Operating Conditions

- Open Circuits: 46

- Overexcitation: 24

- Undervoltage: 27

- Abnormal Frequency: 81U

- Breaker Failure: 50BF, 50BF-N

Detection Elements

Transformer Protection

Page 15: Power transformer protection

Fuses- Small transformers (typ. <10 MVA)- Short circuit protection only

Overcurrent protection- High side

Through fault protectionDifferential back-up protection for high side faults

- Low sideSystem back up protectionUnbalanced load protection

Types of ProtectionElectrical

Transformer Protection

Page 16: Power transformer protection

Protection against heavy prolonged through faultsTransformer Category-IEEE Std. C57.109-1985 Curves

High Side Overcurrent

Above 30,000Above 10,000IV

5001-30,0001668-10,000III

501-5000501-1667II

15-5005-500I

Three-PhaseSingle-PhaseCategory

Minimum nameplate (kVA)

Transformer Protection

Page 17: Power transformer protection

Through Fault Category 1

Transformer Protection

Page 18: Power transformer protection

Through Fault Category 2

Transformer Protection

Page 19: Power transformer protection

Cat. 2 & 3 Fault Frequency Zones

Transformer Protection

Page 20: Power transformer protection

Through Fault Category 3

Transformer Protection

Page 21: Power transformer protection

Through Fault Category 4

Transformer Protection

Page 22: Power transformer protection

Failed Breaker

5151G

Provides protection against uncleared faults downstream of the transformer

May consist of phase and ground elements

Coordinated with line pro-tection off the bus

Low Side Overcurrent

Transformer Protection

Page 23: Power transformer protection

46

Negative sequence overcurrent provides protection against unbalanced loads and open conductors

Easy to coordinate with down stream devices

Low Side Overcurrent

Transformer Protection

Page 24: Power transformer protection

Overexcitation

- Responds to overfluxing; excessive V/Hz

- Constant operational limits

ANSI C37.106 & C57.12- 1.05 loaded, 1.10 unloaded

Inverse time curves typically available for values over the allowable maximum

Transformer Protection

Types of Protection

Page 25: Power transformer protection

Generating Plants-Excitation system runaway-Sudden loss of load-Operational issues (reduced frequency)

Static startsPumped hydro startingRotor warming

Transmission Systems-Voltage and Reactive Support Control Failures

Capacitor banks ON when they should be OFFShunt reactors OFF when they should be ONNear-end breaker failures resulting in voltagerise on line (Ferranti effect)Runaway LTCs

Causes of OverexcitationTransformer Protection

Page 26: Power transformer protection

30-40 MVAR

10-20 MVAR

10-20 MVAR

Caps ON When They Should Be Off

System Control Issues:Overvoltage and Overexcitation

Transformer Protection

Page 27: Power transformer protection

30-40 MVAR

10-20 MVAR

10-20 MVAR

Reactors OFF When They Should Be On

System Control Issues:Overvoltage and Overexcitation

Transformer Protection

Page 28: Power transformer protection

30-40 MVAR

10-20 MVAR

10-20 MVAR

Ferranti Effect

System Control Issues:Overvoltage and Overexcitation

Transformer Protection

Page 29: Power transformer protection

30-40 MVAR

10-20 MVAR

10-20 MVAR

Run-Away LTC

System Control Issues:Overvoltage and Overexcitation

Transformer Protection

Page 30: Power transformer protection

This is typically how the apparatus manufacturer specifies the V/Hz curves

0.010.1

1.010

1001000

MINUTES

v/H

z (%

)

90

100

110

120

130

140

150

Overexcitation Curve

Transformer Protection

Page 31: Power transformer protection

This is how protection engineers enter the v/Hz curve into a protective device

Overexcitation Curve

Transformer Protection

Page 32: Power transformer protection

Differential Protection

Transformer Protection

• Differential protection provides high speed detection of faults that can reduce damage due to the flow of fault currents

• The location of the fault is determined more precisely (i.e within the zone of differential protection)

Advantages:

Types of Protection

Page 33: Power transformer protection

Phase Differential

- Applied with variable percentage slopes to accommodate CT saturation and CT ratio errors

- Applied with inrush and overexcitation restraints

- Pickup/slope setting should consider: magnetizing current, turns ratio errors due to fixed taps and +/-10% variation due to LTC

- May not be sensitive enough for all faults (low level, ground faults near neutral)

Types of Protection

Transformer Protection

Page 34: Power transformer protection

TRANSFORMER

TAP W-1TAP W-2

Restraint W-1 Restraint W-2

OperateRELAY

Basic Differential Relay

Transformer Protection

Phase Differential

Page 35: Power transformer protection

TRANSFORMER

TAP W-1TAP W-2

Restraint W-1 Restraint W-2

OperateRELAY

= 0

Basic Differential Relay - External Fault

Transformer Protection

Page 36: Power transformer protection

TRANSFORMER

TAP W-1TAP W-2

Restraint W-1 Restraint W-2

OperateRELAY

Basic Differential Relay - Internal Fault

Transformer Protection

Page 37: Power transformer protection

Ground Differential- Sensitive detection of ground faults, including

those near the neutral

- Does not require inrush or overexcitation restraint

- Low impedance grounded systems use directional signal for added stability

- Low impedance grounded systems do not require dedicated CTs, same set of CTs can be used for phase differential, phase overcurrent, ground differential and ground overcurrent protection

Types of Protection

Transformer Protection

Page 38: Power transformer protection

What goes into a “unit” comes out of a “unit”

Kirchoff’s Law: The sum of the currents entering and leaving a junction is zero

Straight forward concept, but not that simple in practice with transformers

A host of issues presents itself to decrease security and reliability of transformer differential protection

Differential Protection

Transformer Protection

Page 39: Power transformer protection

UNITI1 I2

I3

I1 + I2 + I3 = 0

Typical Phase Differential Characteristic

Transformer Protection

Page 40: Power transformer protection

CT ratio caused current mismatch

Transformation ratio caused current mismatch (fixed taps)

LTC induced current mismatch

Delta-wye transformation of currents- Vector group and current derivation issues

Zero-sequence current elimination for external ground faults on wye windings

Inrush phenomena and its resultant current mismatch

Unique Issues Applying to Transformer Differential Protection

Transformer Protection

Page 41: Power transformer protection

Harmonic content available during inrush period due to point-on-wave switching (especially with newer transformers with step-lap core construction)

Overexcitation phenomena and its resultant current mismatch

Internal ground fault sensitivity concerns

Switch onto fault concerns

CT saturation, remanance and tolerance

Unique Issues Applying to Transformer Differential Protection

Transformer Protection

Page 42: Power transformer protection

CT ratios must be selected to account for:

- Transformer ratios- If delta or wye connected CTs are applied- Delta increases ratio by 1.73

Delta CTs must be used to filter zero-sequence current on wye transformer windings

Classical Differential Compensation

Transformer Protection

Page 43: Power transformer protection

Classical Differential Compensation

Transformer Protection

Page 44: Power transformer protection

Transformer ratio

CT ratio

Phase angle shift and √ 3 factor due to delta/wye connection

Zero-sequence current filtering for wye windings so the differential quantities do not occur from external ground faults

Compensation in Digital Relays

Transformer Protection

Page 45: Power transformer protection

The compensation for the phase shift is achieved as follows:Iabc: Measured CT currents (assuming CTs are connected in Y)I'abc: Compensated three-phase currents.

Assuming a two winding transformer with a phase angle difference between the primary and secondary as shown in the following 12 cases.

Phase angle shift due to transformer connection in electromechanical and static relays is accomplished using appropriate connection of the cts.

The phase angle shift in Numerical Relays can easily be compensated in software for any transformer type. All cts can be connected in Y which allows the same cts to be used for both metering and backup overcurrent functions

Phase Angle compensation in Numerical Relays

Transformer Protection

Page 46: Power transformer protection

ABCABC II⎥⎥⎥

⎢⎢⎢

⎡=

100010001

' ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

101110

011

31'

A

C B

C

B

A

A

C

BB

C A

C

B A

A

B C

B

A C

C

A B

B

A

C

C

B

A

A

C

B

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

001100

010'

ABCABC II⎥⎥⎥

⎢⎢⎢

⎡=

010001100

'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

100010001

'

ABCABC II⎥⎥⎥

⎢⎢⎢

⎡=

001100010

'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

010001100

'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

011101

110

31'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

110011101

31'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

101110011

31'

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

011101110

31'

1:0O

3:60O

5:120O

7:180O

9:240O

11:300O

B

A

C

ABCABC II⎥⎥⎥

⎢⎢⎢

−−

−=

110011101

31'

2:30O

4:90O

6:150O

8:210O

10:270O

12:330O

y g

As an example, if we have a two winding transformer with Y/Delta-AC connection (or YD1)with Y-Y cts. This will be equivalent to case 2 with a 30o phase shift.

Transformer Protection

Page 47: Power transformer protection

1:1, Y-Y

1:1, 3Y1:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA' = Ia'IB' = Ib'IC' = Ic'

IA', IB', IC' Ia', Ib', Ic'

Compensation: Base Model

Transformer Protection

Page 48: Power transformer protection

1:1, Y-Y

1:1, 3Y4:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA' = Ia' / 4IB' = Ib' / 4IC' = Ic' / 4

IA', IB', IC' Ia', Ib', Ic'

Compensation: Change in CT Ratio

Transformer Protection

Page 49: Power transformer protection

2:1, Y-Y

1:1, 3Y1:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA' = Ia' / 2IB' = Ib' / 2IC' = Ic' / 2

IA', IB', IC' Ia', Ib', Ic'

Compensation: Transformer Ratio

Transformer Protection

Page 50: Power transformer protection

1:1, -Y

1:1, 3Y1:1, 3Y

IA, IB, IC Ia, Ib, Ic

IA' = Ia' * 1.73IB' = Ib' * 1.73IC' = Ic' * 1.73

ANSI standard, high lead low by 30,Current pairs are: IA-IB, IB-IC, IC-IA

IA', IB', IC' Ia', Ib', Ic'

Compensation: Delta – Wye Transformation

Transformer Protection

Page 51: Power transformer protection

3I0 = [Ia + Ib + Ic]I0 = 1/3 *[Ia + Ib + Ic]

Used where filtering is required (Ex: Y/Y transformer).

Compensation: Zero-Sequence elimination

Transformer Protection

Page 52: Power transformer protection

All wye CTs shown

Digital Relay Application

Transformer Protection

Page 53: Power transformer protection

Phase segregated line currents

- Individual line current oscillography

- Currents may be easily used for overcurrent protection and metering

- Easier to commission and troubleshoot

- Zero sequence elimination performed by calculation

However, for protection upgrade applications where one wants to keep the existing wiring, it will be necessary for the relay to accept either delta or wye CTs and recalculate the phase currents from delta CTs for overcurrent function (Some digital relays like M-3310/3311 have these features).

Benefits of Wye CTs

Transformer Protection

Page 54: Power transformer protection

Inrush Detection and Restraint- Initial inrush occurs during transformer energizing as the

core magnetizes

- Sympathy inrush occurs from adjacent transformer(s) energizing, fault removal, allowing the transformer to undergo a low level inrush

- Characterized by current into one winding of transformer, and not out of the other winding(s)

- This causes a differential element to pickup

- Use inrush restraint to block differential elementduring inrush period

Inrush Restraint

Transformer Protection

Page 55: Power transformer protection

Inrush Detection and Restraint

- 2nd harmonic restraint has been employed for years

- “Gap” detection has also been employed

- As transformers are designed to closer tolerances, the incidence of both 2nd harmonic and low current gaps in waveform have decreased

- If 2nd harmonic restraint level is set too low, differential element may be blocked for internal faults with CT saturation (with associated harmonics generated)

Classical Inrush Detection

Transformer Protection

Page 56: Power transformer protection

Inrush Detection and Restraint

- 4th harmonic is also generated during inrush

- Even harmonics are more prevalent than odd harmonics during inrush

Odd harmonics are more prevalent during CT saturation

- Use 4th harmonic and 2nd harmonic together

Use RMS sum of the 2nd and 4th harmonic as inrush restraint

- Result: Improved security while not sacrificingreliability

Advanced Inrush Detection

Transformer Protection

Page 57: Power transformer protection

2nd and 4thHarmonicsDuringInrush

Typical Transformer Inrush Waveform

Inrush Oscillograph

Transformer Protection

Page 58: Power transformer protection

As most circuit breakers are ganged three-pole, one phase will be near voltage zero at the moment of transformer energization

When a phase of a transformer is switched on near zero voltage, the inrush is increased and so is the resultant harmonics

Low levels of harmonics (especially modern transformers) may not provide inrush restraint for affected phase – security risk!

Employ cross-phase averaging to compensate for this issue

Point-on-Wave Considerations During Switch On

Transformer Protection

Page 59: Power transformer protection

Provides security if any phase has low harmonic content during inrush

Cross phase averaging uses the sum of harmonics on all three phases as the restraint value

Cross Phase Averaging

Transformer Protection

Page 60: Power transformer protection

Overexcitation occurs when volts per hertz level rises (V/Hz) above the rated valueThis may occur from:- Load rejection (generator transformers)- Malfunctioning of voltage and reactive support elements- Malfunctioning of breakers and line protection (including transfer

trip communication equipment schemes)- Malfunctioning of generator AVRs

The voltage rise at nominal frequency causes the V/Hz to riseThis causes the transformer core to saturate and thereby increase the magnetizing current. The increased magnetizing current contains 5th harmonic componentThis magnetizing current causes the differential element to pickup

Overexcitation Restraint

Transformer Protection

Page 61: Power transformer protection

Volta

geC

urre

nt

Transformer Magnetizing Current

Current into Transformer due to Overfluxing

Rated Voltage Overvoltage Voltage

24 Elements Tripping

Overexcitation EventTransformer Protection

Page 62: Power transformer protection

Volta

geC

urre

nt

11.57kV (RMS)19.40kV (RMS

0.0 kA (RMS)

1.42kA (RMS) !!!

24 Elements Tripping

Overexcitation EventTransformer Protection

Page 63: Power transformer protection

High 5th Harmonic Currents

Overexcitation Event

Transformer Protection

Page 64: Power transformer protection

259V of 5th Harmonic

190 A of 5th Harmonic !!!

Overexcitation Event

Transformer Protection

Page 65: Power transformer protection

Use 5th harmonic level to detect overexcitation

Most relays block the differential element from functioning during transformer overexcitation

An improved strategy is to raise the pick up level to accommodate the increased difference currents caused by the transformer saturation

This allows the differential element to rapidly trip if an internal fault occurs during the overexcitation period

Result: Improved reliability while not sacrificing security

Overexcitation Restraint

Transformer Protection

Page 66: Power transformer protection

Trip Characteristic – 87TTransformer Protection

0.5

1.0

1.5

2.0

0.5 1.0 1.5 2.0

87T Pick Up

87T Pick Upwith 5th Harmonic Restraint

Slope 1

Slope 2

Slope 2Breakpoint

TRIP

RESTRAIN

Page 67: Power transformer protection

87T element is typically set with 30-40% pickup

This is to accommodate Class “C” CT accuracy during a fault plus the effects of LTCs

That leaves a portion of the winding not covered for a ground fault

Employ a ground differential element to improve sensitivity (87GD)

Improved Ground Fault Sensitivity

Transformer Protection

Page 68: Power transformer protection

Use 87GDIA + IB + IC = 3I0

If fault is internal, opposite polarityIf fault is external, same polarity IG

IA

IB

IC

.

Improved Ground Fault Sensitivity

Transformer Protection

Page 69: Power transformer protection

IG

IA

IB

IC

IG

IA

IB

IC

Internal ExternalInternal External

• .

Improved Ground Fault Sensitivity

Transformer Protection

Page 70: Power transformer protection

- The directional element is used to provide security against relay misoperation due to ct saturation. With low level faults, the directional element is not necessary as the CTs will not saturate.

Improved Ground Fault Sensitivity

Transformer Protection

Page 71: Power transformer protection

IG

IA

IB

IC

3I0IG

Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

0

90

180

270IG

3IO

-3Io x IG cos (180) = 3IoIG

Trip Characteristic – 87GD

Transformer Protection

Page 72: Power transformer protection

IG

IA

IB

IC

3I0IG

Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

0

90

180

270

IG3IO

-3Io x IG cos (0) = -3IoIG

Trip Characteristic – 87GD

Transformer Protection

Page 73: Power transformer protection

Transformer is faulted on energizing

Harmonic restraint on unfaulted phases may work against trip decision if cross phase averaging is used. This may delay tripping until the inrush current is reduced

- Unfaulted phase may have high harmonics and delay 87T operation

87H and 87GD can be used to provide high speed protection for this condition

Switch-onto-Fault

Transformer Protection

Page 74: Power transformer protection

High set element 87H can provide high speed protection for severe faults as this function is not restrained by harmonics

87H is set above the worst case inrush current

If fault is near the bushing end of the winding, the current will be higher than the inrush current

Ground differential function can provide fast protection during switching onto ground faults as this element is not restrained using harmonics

Switch-onto-Fault

Transformer Protection

©2008 Beckwith Electric Co., Inc.