Transformer Protection( Power Grid Ballabhgarh

Embed Size (px)

Citation preview

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    1/115

    TRANSFORMER PROTECTION

    Prof. M.L.Kothari

    Deptt of Electrical Engineering

    Indian Institute of TechnologyDelhi

    New Delhi INDIA

    Visiting Professor, HelsinkiUniversity of Technology

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    2/115

    2

    OUTLINE OF THE LESSON

    1. Introduction

    2.Types of faults affecting Power Transformers

    3.Buchholz Relay

    4.Nature and effect of transformer faults

    5.Magnetising inrush current of a transformer

    6.Transformer Differential protection

    7.Harmonic Restraint Differential Relay

    8.Restricted Earth Fault Protection

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    3/115

    3

    The power transformer is one of the

    most important links in a power

    transmission and distribution system.

    INTRODUCTION

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    4/115

    4

    It is a highly reliable piece of equipment.

    This reliability depends on

    adequate design

    careful erection

    proper maintenance

    application of protection

    system.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    5/115

    5

    1. Surge diverters

    2. Gas relay:

    It gives early warning of a slowlydeveloping fault, permitting shutdown

    and repair before severe damage

    can occur.3. Electrical relays.

    PROTECTION EQUIPMENT

    INCLUDES

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    6/115

    6

    The choice of suitable protection is also

    governed by economic considerations.

    Although this factor is not unique to power

    transformers, it is brought in prominence

    by the wide range of transformer ratings

    used( few KVA to several hundreds MVA)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    7/115

    7

    Only the simplest protection such as

    fuses can be justified for transformers of

    lower ratings.

    for large transformers best protection

    should be provided.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    8/115

    8

    THROUGH FAULTS

    a) Overload conditions.

    b) External short-circuit conditions.

    TYPES OF FAULTS AFFECTINGPOWER TRANSFORMER

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    9/115

    9

    The transformer must be disconnected

    when such faults occur only after allowing

    a predetermined time during which otherprotective gears should have operated.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    10/115

    10

    The primary protection of a power

    transformer is intended for conditions which

    arises as a result of faults inside the

    protection zone.

    INTERNAL FAULTS

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    11/115

    11

    Internal faults are very serious and there

    is always a risk of fire; these internal

    faults are classifieds into two groups.1. GROUP-A

    2. GROUP-B

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    12/115

    12

    Electrical faults which cause immediate

    serious damage but are generally

    detectable by unbalance of current or

    voltage such as:

    GROUP A

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    13/115

    13

    1. Phase-to-earth fault or phase- to-

    phase fault on HV and LV external

    terminals

    2. Phase-to-earth fault or phase-to- phase

    fault on HV and LV windings.

    3. Interturn faults of HV and LV windings.

    4. Earth fault on tertiary winding, or short

    circuit between turns of a tertiary

    windings.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    14/115

    14

    For Group(A) faults, it is important that

    the faulted equipment should be isolated

    as quickly as possible

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    15/115

    15

    So called incipient faults which are

    initially minor faults, causing slowly

    developing damage. These are NOTDETECTABLE at the winding terminals by

    unbalance current or voltage.

    GROUP B

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    16/115

    16

    A poor electrical connection of conductors

    or core faults (due to breakdown of the

    insulation of laminations, bolts or

    clamping rings which cause limited arcing

    under the oil.)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    17/115

    17

    Coolant failure, which will cause a rise oftemperature even below full load operation

    Related to above is the possibility of low oil

    content or clogged oil flow, which can readilycause local hot spot on the windings.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    18/115

    18

    Regulator faults and bad load sharingbetween transformers in parallel, which cancause overheating due to circulating

    currents The Group(B) faults, though not serious in

    their incipient stage, may cause major faults

    in due course of time and should thus be

    cleared as soon as possible.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    19/115

    19

    It should be emphasized that the means

    adopted for protection against faults in

    Groups (A) are not capable of detecting the

    faults of Groups of (B), where as the means

    applicable to detect the Group (B) faults can

    not necessarily detect the terminal faults and

    are not quick enough to clear other faults in

    Group (A)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    20/115

    20

    These ideas are basic to transformer

    protection, & the means of protection

    against the Group (A) & (B) should not be

    treated as alternatives but as supplements

    to each other.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    21/115

    21

    BUCHHOLZ RELAY

    All faults below the oil in transformer result inthe localized heating & breakdown of the oil,some degree of arcing will always take place in

    a winding fault & the resulting decomposition ofit will release gases such as hydrogen, carbonmonoxide & hydrocarbons.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    22/115

    22

    BUCHHOLZ RELAY

    When the fault is of a very minor type, suchas hot joints gas is released slowly, but amajor fault involving severe arcing causesrapid release of large volumes of gas aswell as oil vapour.

    Recognition of the above action byBUCHHOLZ led to the development of theprotective device known as BUCHHOLZRELAY .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    23/115

    23

    BUCHHOLZ RELAY

    A buchholz is contained in a cast housingwhich is connected as shown below

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    24/115

    24

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    25/115

    25

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    26/115

    26

    BUCHHOLZ RELAY

    A typical buchholz relay comprises twopivoted aluminum brackets, each counterbalance so that when empty or completely

    full of oil, the bucket is in high position.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    27/115

    27

    BUCHHOLZ RELAY

    Each pivoted bucket assembly carries amercury switch.

    In the normal condition the casing is filled

    with oil, so that mercury switches are open. If gas bubbles pass up the piping, they will

    be trapped in the relay casing, so displacingthe oil .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    28/115

    28

    BUCHHOLZ RELAY

    As the oil level falls the upper bucket willfollow, since the weight of the bucket filledwith oil exceeds that of the counterbalance

    when the buoyancy from the surrounding oil islost.

    As the bucket falls, the mercury switch tilts &closes the alarm circuit.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    29/115

    29

    BUCHHOLZ RELAY

    A similar operation will occurs if tank leakscauses the oil level to fall.

    A major winding faults causes a surge of oilwhich displaces the lower bucket & thusisolates the transformer.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    30/115

    30

    BUCHHOLZ RELAY

    Relay is usually provided with an inspectionwindow on each side of the gas collectionspace, through which the oil level can be

    observed. This may also helps in diagnosingthe fault.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    31/115

    31

    BUCHHOLZ RELAY

    Because of its universal response to faultswithin the transformer, some of which aredifficult to detect by other means, the

    BUCHHOLZ RELAY is invaluable, whetherregarded as a main protection or assupplement to other protection schemes

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    32/115

    32

    BUCHHOLZ RELAY

    The minimum operating time of the

    BUCHHOLZ RELAY is about 0.1 sec & the

    average operating time is 0.2 sec

    Transformer without conservator can not

    be provided with BUCHHOLZ RELAY

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    33/115

    33

    NATURE & EFFECT OF

    TRANSFRMER FAULTS

    A faults on transformer winding is

    controlled in magnitude by

    a) Source & neutral earthing impedance

    b) Leakage reactance of the transformer

    c) Position of the fault on the winding.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    34/115

    34

    NATURE & EFFECT OFTRANSFORMER FAULTS

    Following distinct cases are examined

    below

    (1) Star connected winding with neutral pointearthed through an impedance

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    35/115

    35

    If

    If

    Rnp

    Earth fault on resistance earthed star winding

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    36/115

    36

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    37/115

    37

    An earth fault on resistance earthed starwinding will give rise to a fault current (IF) depends on the value of the earthing

    impedance. is proportional to the distance of the

    fault from the neutral point since thefault voltage will be directly

    proportional to the distance from theneutral

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    38/115

    38

    The ratio of transformation between theprimary winding and short circuited turnsalso varies with the position of the fault, so

    that the current which flows into thetransformer primary terminals will be inproportion to the square of the fraction ofthe winding which is short circuited.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    39/115

    39

    The variation of magnitude of the faultcurrent (% of respective maximum singlephase earth fault current) with the distance

    of the fault measured from the neutral ( % ofthe winding) is shown

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    40/115

    40

    Star connected winding withNeutral point solidly earthed

    The fault current in this case is controlledmainly by the leakage reactance of the

    transformer which varies in a complexmanner ( approximately, proportional to thesquare of the number of turns involved)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    41/115

    41

    Further, the voltage is not proportional tothe turns involved by the fault near theneutral because of the increased magnetic

    leakage. The variation of the fault current with fault

    position is shown in the fig

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    42/115

    42

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    43/115

    43

    The fault current reflected to the input sideis modified as before by the variabletransformation ratio.

    The fault current magnitude remains highthroughout the winding.

    Further, the general current scale is high inthe absence of current limiting resistance.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    44/115

    44

    Delta Connected Winding

    No part of the delta-connected windingoperates with a voltage to earth less than50% of the phase voltage.

    The range of fault current magnitude forsuch a winding is therefore less than for astar winding

    The actual value of the fault current will still

    depend on the way the system is earthed

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    45/115

    45

    The impedance of the deltawinding isparticularly high to the fault currents flowingto a centrally placed fault on one leg

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    46/115

    46

    Phase to Phase faults

    Faults between phases within a transformer

    are relatively rare; if such a fault occurs it

    will give rise to substantial current

    comparable to the earth fault currents.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    47/115

    47

    Interturn Faults

    A high voltage transformer connected to anoverhead transmission system is very likelyto be subjected to steep fronted impulse

    voltage A line surge, which may be of several times

    the rated system voltage, will concentrateon the end turns of the winding because of

    the high equivalent frequency of the surgefront

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    48/115

    48

    The interturn insulation of the end turns isreinforced,but can not be increased inproportion to the insulation to earth,which is

    relatively great.

    The risk of the partial winding flashovercompared to that of the breakdown to earthis comparatively high. It is claimed that 70-80% of all transformer failures arise fromfaults between turns.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    49/115

    49

    A short circuit of few turns of the windingwill give rise to heavy fault currents in theshort circuited loop, but the terminal

    currents will be very small, because of thehigh ratio of the transformation between thewhole winding and short circuited turns

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    50/115

    50

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    51/115

    51

    Externally Applied Conditions

    Sources of abnormal stress in a transformer

    are :

    a) Overload

    b) System faults

    c) Over voltage

    d) Reduced System Frequency

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    52/115

    52

    Overload causes increased copper loss

    and a consequent temperature rise.Overloads can be carried for a limited

    periods, depending on the initialtemperature and cooling conditions

    System short-circuits produce a relativelyintense rate of heating of the feeding

    transformer, the copper loss increasingproportional to the square of the per unitfault current.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    53/115

    53

    The duration of the external short circuitthat a transformer can withstand withoutdamage if the current is limited only by self

    reactance is shown in Table on the nextslide

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    54/115

    54

    Transformerreactance(%)

    Faultcurrent(multiple of

    rating)

    Permittedfaultduration

    (seconds)4 25 2

    5 20 3

    6 16.6 4

    7 14.2 5

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    55/115

    55

    Large fault currents produce severemechanical stresses in the transformers;the maximum stress occurs during the first

    cycle of the asymmetric fault current and socannot be averted by automatic tripping ofthe circuit

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    56/115

    56

    Overvolatges

    Transient surge voltages

    Power frequency voltages

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    57/115

    57

    Transient Surge Overvoltages

    Transient over voltages arise from switchingand lightning disturbances and are liable tocause inter-turn faults

    These voltages are usually limited byproviding lightening arrester (Metal ZincOxide).

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    58/115

    58

    Power Frequency Overvoltages

    Causes increase in stress on insulation

    Increase in working flux

    Increase in iron loss

    Disproportionality increase in magnetizingcurrent

    Flux is diverted from the laminated core tothe steel structure

    Increase in heating and temperature rise

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    59/115

    59

    Reduction in Frequency

    It has an effect with regard to flux densitysimilar to that of power frequencyovervolatges.

    Operation must not be continued with a highvoltage input at a low frequency

    V/f > 1.1 is not permissible where V and fare expressed in p.u. of their rated value

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    60/115

    60

    MAGNETISING INRUSH CURRENT

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    61/115

    61

    MAGNETISING INRUSH CURRENTOF A TRANSFORMER

    When a transformer is first energized,a

    transient exciting current flows to bridge the

    gap between the conditions existing before the

    transformer is energized and the conditions

    dictated by the steady state requirements

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    62/115

    62

    For any given transformer this transientcurrent depends upon:

    The point on the voltage wave at which

    the switch is closed.

    The value and direction of the residualcore flux.

    The shape of the saturation curve ,andthe normal flux density used.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    63/115

    63

    Often the magnitude of this transient

    current exceeds full load current and may

    reach 8-10 times full load current.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    64/115

    64

    In studying the phenomena that occur when

    a transformer is energized, it is more

    satisfactory to determine the flux in themagnetic circuit first and then derive the

    current from the flux.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    65/115

    65

    This procedure is preferred because the

    flux does not depart much from the sine

    wave even though the current wave isdistorted.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    66/115

    66

    If the secondary of the transformer is open ,

    the transformer can be treated as an iron-

    core reactor, the differential equation for

    the circuit consisting of the supply and

    transformer can be written as

    1de Ri ndt

    (1)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    67/115

    67

    Normally the resistance R is small and can

    be ignored for simplicity.

    Under this condition the equation (1) can

    be written as

    1

    de n

    dt (2)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    68/115

    68

    If the supply voltage is sine wave voltage,

    where,

    = rms value of the supply voltage

    e= instantaneous voltage applied to transformer

    2 sin( )e E t

    E

    2 f

    .(3)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    69/115

    69

    Substituting in equation (2)

    1 2 sin( )

    dn E t

    dt

    Solving the above equation

    1

    2cos( )

    t

    Et

    n

    ..(4)

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    70/115

    70

    Equation (4) can be used to determine the

    transient flux in the core immediately after

    the transformer is energized.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    71/115

    71

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    72/115

    72

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    73/115

    73

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    74/115

    74

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    75/115

    75

    Amplitude of Harmonics in a typical

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    76/115

    76

    Component Typical Value(%)offundamental

    DC 55

    2nd Harmonic 633rd Harmonic 26.8

    4th Harmonic 5.1

    5th

    Harmonic 4.16th Harmonic 3.7

    7th Harmonic 2.4

    Amplitude of Harmonics in a typicalMagnetizing Inrush current wave

    TRANSFORMER DIFFERENTIAL

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    77/115

    77

    TRANSFORMER DIFFERENTIALPROTECTION

    BASIC CONSIDERATIONS

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    78/115

    78

    The nominal currents in the primary and

    secondary sides of the transformer vary in

    inverse ratio to the corresponding voltages.

    This should be compensated for by usingdifferent transformation ratios for the CTs on

    the primary and secondary sides of the

    transformer.

    a. Transformation ratio

    b Current Transformer

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    79/115

    79

    b. Current TransformerConnections

    When a transformer is connected in

    star/delta, the secondary current has a

    phase shift of 300 relative to the primary

    This phase shift can be offset by suitable

    secondary CT connections

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    80/115

    80

    The zero-sequence currents flowing on

    the star-side of the transformer will not

    produce current outside the delta on theother side. The zero sequence current

    must therefore be eliminated from the star-

    side by connecting the CTs in delta.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    81/115

    81

    The CTs on delta side should be

    connected in star in order to give 300

    phase shift.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    82/115

    82

    When CTs are connected in delta, their

    secondary ratings must be reduced to

    1/3 times the secondary ratings of the

    star-connected transformer, in order that

    the currents outside the delta may

    balance with the secondary currents of

    the star-connected CTs.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    83/115

    83

    If transformers were connected in

    star/star, the CTs on both sides would

    need be connected in delta-delta.

    c. Bias to cover tap-changing

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    84/115

    84

    If the transformer has the benefit of a tap

    changer, it is possible to vary its

    transformation ratio for voltage control.

    c as to co e tap c a g g

    facility and CT mismatch

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    85/115

    85

    The differential protection system should

    be able to cope with this variation.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    86/115

    86

    This is because if the CTs are chosen to

    balance for the mean ratio of the power

    transformer, a variation in ratio from the

    mean will create an unbalance

    proportional to the ratio change. At

    maximum through fault current, the spill

    output produced by the small percentageunbalance may be substantial.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    87/115

    87

    Differential protection should be provided

    with a proportional bias of an amount

    which exceeds in effect the maximum ratio

    deviation. This stabilizes the protection

    under through fault conditions while still

    permitting the system to have good basic

    sensitivity.

    d Magnetization Inrush

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    88/115

    88

    The magnetizing inrush produces a

    current flow into the primary winding that

    does not have any equivalent in the

    secondary winding. The net effect is thus

    similar to the situation when there is an

    internal fault on the transformer.

    d. Magnetization Inrush

    Contd

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    89/115

    89

    Since the differential relay sees the

    magnetizing current as an internal fault, it

    is necessary to have some method ofdistinguishing between the magnetizing

    current and the fault current, These

    methods include:

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    90/115

    90

    Using a differential relay with a suitable

    sensitivity to cope with the magnetizing

    current, usually obtained by a unit thatintroduces a time delay to cover the

    period of the initial inrush peak.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    91/115

    91

    Using a harmonic-restraint unit, or a

    supervisory unit, in conjunction with adifferential unit.

    Inhibiting the differential relay during the

    energizing the transformer.

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    92/115

    92

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    93/115

    93

    Example:

    A 3-phase, 33000/6600V transformer is

    connected star/delta an the protecting CTs

    on the low voltage side have a ratio of

    300/5. What will be ratio of the CTS on the

    H.V. side?

    [20:8:1]

    RESTRICTED EARTH FAULT

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    94/115

    94

    PROTECTION

    Fig : Restricted earth fault protection for starconnected winding

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    95/115

    95

    Fig Amount of winding protected when transformer isresistance earthed and ratings of transformer andresistor are equal

    Percentage of winding protected

    Primaryoperating

    current

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    96/115

    96

    Degree of protection is very much improved

    with the application of a restricted earth fault(REF) protection

    OVERFLUXING PROTECTION

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    97/115

    97

    OVERFLUXING PROTECTION

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    98/115

    98

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    99/115

    99

    The system voltage, as measured by a

    voltage transformer, is applied to a resistance

    to produce a proportionate current; this

    current , on being passed through a

    capacitor, produces a voltage drop which is

    proportional to the function in question, E/f,

    and hence to the flux in the powertransformer.

    HARMONIC RESTRAINT

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    100/115

    100

    DIFFERENTIAL RELAY

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    101/115

    101

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    102/115

    102

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    103/115

    103

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    104/115

    104

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    105/115

    105

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    106/115

    106

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    107/115

    107

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    108/115

    108

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    109/115

    109

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    110/115

    110

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    111/115

    111

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    112/115

    112

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    113/115

    113

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    114/115

    114

    .

  • 8/3/2019 Transformer Protection( Power Grid Ballabhgarh

    115/115

    .