Upload
anujayan
View
221
Download
1
Embed Size (px)
Citation preview
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
1/115
TRANSFORMER PROTECTION
Prof. M.L.Kothari
Deptt of Electrical Engineering
Indian Institute of TechnologyDelhi
New Delhi INDIA
Visiting Professor, HelsinkiUniversity of Technology
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
2/115
2
OUTLINE OF THE LESSON
1. Introduction
2.Types of faults affecting Power Transformers
3.Buchholz Relay
4.Nature and effect of transformer faults
5.Magnetising inrush current of a transformer
6.Transformer Differential protection
7.Harmonic Restraint Differential Relay
8.Restricted Earth Fault Protection
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
3/115
3
The power transformer is one of the
most important links in a power
transmission and distribution system.
INTRODUCTION
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
4/115
4
It is a highly reliable piece of equipment.
This reliability depends on
adequate design
careful erection
proper maintenance
application of protection
system.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
5/115
5
1. Surge diverters
2. Gas relay:
It gives early warning of a slowlydeveloping fault, permitting shutdown
and repair before severe damage
can occur.3. Electrical relays.
PROTECTION EQUIPMENT
INCLUDES
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
6/115
6
The choice of suitable protection is also
governed by economic considerations.
Although this factor is not unique to power
transformers, it is brought in prominence
by the wide range of transformer ratings
used( few KVA to several hundreds MVA)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
7/115
7
Only the simplest protection such as
fuses can be justified for transformers of
lower ratings.
for large transformers best protection
should be provided.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
8/115
8
THROUGH FAULTS
a) Overload conditions.
b) External short-circuit conditions.
TYPES OF FAULTS AFFECTINGPOWER TRANSFORMER
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
9/115
9
The transformer must be disconnected
when such faults occur only after allowing
a predetermined time during which otherprotective gears should have operated.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
10/115
10
The primary protection of a power
transformer is intended for conditions which
arises as a result of faults inside the
protection zone.
INTERNAL FAULTS
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
11/115
11
Internal faults are very serious and there
is always a risk of fire; these internal
faults are classifieds into two groups.1. GROUP-A
2. GROUP-B
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
12/115
12
Electrical faults which cause immediate
serious damage but are generally
detectable by unbalance of current or
voltage such as:
GROUP A
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
13/115
13
1. Phase-to-earth fault or phase- to-
phase fault on HV and LV external
terminals
2. Phase-to-earth fault or phase-to- phase
fault on HV and LV windings.
3. Interturn faults of HV and LV windings.
4. Earth fault on tertiary winding, or short
circuit between turns of a tertiary
windings.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
14/115
14
For Group(A) faults, it is important that
the faulted equipment should be isolated
as quickly as possible
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
15/115
15
So called incipient faults which are
initially minor faults, causing slowly
developing damage. These are NOTDETECTABLE at the winding terminals by
unbalance current or voltage.
GROUP B
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
16/115
16
A poor electrical connection of conductors
or core faults (due to breakdown of the
insulation of laminations, bolts or
clamping rings which cause limited arcing
under the oil.)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
17/115
17
Coolant failure, which will cause a rise oftemperature even below full load operation
Related to above is the possibility of low oil
content or clogged oil flow, which can readilycause local hot spot on the windings.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
18/115
18
Regulator faults and bad load sharingbetween transformers in parallel, which cancause overheating due to circulating
currents The Group(B) faults, though not serious in
their incipient stage, may cause major faults
in due course of time and should thus be
cleared as soon as possible.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
19/115
19
It should be emphasized that the means
adopted for protection against faults in
Groups (A) are not capable of detecting the
faults of Groups of (B), where as the means
applicable to detect the Group (B) faults can
not necessarily detect the terminal faults and
are not quick enough to clear other faults in
Group (A)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
20/115
20
These ideas are basic to transformer
protection, & the means of protection
against the Group (A) & (B) should not be
treated as alternatives but as supplements
to each other.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
21/115
21
BUCHHOLZ RELAY
All faults below the oil in transformer result inthe localized heating & breakdown of the oil,some degree of arcing will always take place in
a winding fault & the resulting decomposition ofit will release gases such as hydrogen, carbonmonoxide & hydrocarbons.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
22/115
22
BUCHHOLZ RELAY
When the fault is of a very minor type, suchas hot joints gas is released slowly, but amajor fault involving severe arcing causesrapid release of large volumes of gas aswell as oil vapour.
Recognition of the above action byBUCHHOLZ led to the development of theprotective device known as BUCHHOLZRELAY .
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
23/115
23
BUCHHOLZ RELAY
A buchholz is contained in a cast housingwhich is connected as shown below
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
24/115
24
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
25/115
25
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
26/115
26
BUCHHOLZ RELAY
A typical buchholz relay comprises twopivoted aluminum brackets, each counterbalance so that when empty or completely
full of oil, the bucket is in high position.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
27/115
27
BUCHHOLZ RELAY
Each pivoted bucket assembly carries amercury switch.
In the normal condition the casing is filled
with oil, so that mercury switches are open. If gas bubbles pass up the piping, they will
be trapped in the relay casing, so displacingthe oil .
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
28/115
28
BUCHHOLZ RELAY
As the oil level falls the upper bucket willfollow, since the weight of the bucket filledwith oil exceeds that of the counterbalance
when the buoyancy from the surrounding oil islost.
As the bucket falls, the mercury switch tilts &closes the alarm circuit.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
29/115
29
BUCHHOLZ RELAY
A similar operation will occurs if tank leakscauses the oil level to fall.
A major winding faults causes a surge of oilwhich displaces the lower bucket & thusisolates the transformer.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
30/115
30
BUCHHOLZ RELAY
Relay is usually provided with an inspectionwindow on each side of the gas collectionspace, through which the oil level can be
observed. This may also helps in diagnosingthe fault.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
31/115
31
BUCHHOLZ RELAY
Because of its universal response to faultswithin the transformer, some of which aredifficult to detect by other means, the
BUCHHOLZ RELAY is invaluable, whetherregarded as a main protection or assupplement to other protection schemes
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
32/115
32
BUCHHOLZ RELAY
The minimum operating time of the
BUCHHOLZ RELAY is about 0.1 sec & the
average operating time is 0.2 sec
Transformer without conservator can not
be provided with BUCHHOLZ RELAY
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
33/115
33
NATURE & EFFECT OF
TRANSFRMER FAULTS
A faults on transformer winding is
controlled in magnitude by
a) Source & neutral earthing impedance
b) Leakage reactance of the transformer
c) Position of the fault on the winding.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
34/115
34
NATURE & EFFECT OFTRANSFORMER FAULTS
Following distinct cases are examined
below
(1) Star connected winding with neutral pointearthed through an impedance
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
35/115
35
If
If
Rnp
Earth fault on resistance earthed star winding
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
36/115
36
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
37/115
37
An earth fault on resistance earthed starwinding will give rise to a fault current (IF) depends on the value of the earthing
impedance. is proportional to the distance of the
fault from the neutral point since thefault voltage will be directly
proportional to the distance from theneutral
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
38/115
38
The ratio of transformation between theprimary winding and short circuited turnsalso varies with the position of the fault, so
that the current which flows into thetransformer primary terminals will be inproportion to the square of the fraction ofthe winding which is short circuited.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
39/115
39
The variation of magnitude of the faultcurrent (% of respective maximum singlephase earth fault current) with the distance
of the fault measured from the neutral ( % ofthe winding) is shown
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
40/115
40
Star connected winding withNeutral point solidly earthed
The fault current in this case is controlledmainly by the leakage reactance of the
transformer which varies in a complexmanner ( approximately, proportional to thesquare of the number of turns involved)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
41/115
41
Further, the voltage is not proportional tothe turns involved by the fault near theneutral because of the increased magnetic
leakage. The variation of the fault current with fault
position is shown in the fig
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
42/115
42
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
43/115
43
The fault current reflected to the input sideis modified as before by the variabletransformation ratio.
The fault current magnitude remains highthroughout the winding.
Further, the general current scale is high inthe absence of current limiting resistance.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
44/115
44
Delta Connected Winding
No part of the delta-connected windingoperates with a voltage to earth less than50% of the phase voltage.
The range of fault current magnitude forsuch a winding is therefore less than for astar winding
The actual value of the fault current will still
depend on the way the system is earthed
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
45/115
45
The impedance of the deltawinding isparticularly high to the fault currents flowingto a centrally placed fault on one leg
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
46/115
46
Phase to Phase faults
Faults between phases within a transformer
are relatively rare; if such a fault occurs it
will give rise to substantial current
comparable to the earth fault currents.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
47/115
47
Interturn Faults
A high voltage transformer connected to anoverhead transmission system is very likelyto be subjected to steep fronted impulse
voltage A line surge, which may be of several times
the rated system voltage, will concentrateon the end turns of the winding because of
the high equivalent frequency of the surgefront
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
48/115
48
The interturn insulation of the end turns isreinforced,but can not be increased inproportion to the insulation to earth,which is
relatively great.
The risk of the partial winding flashovercompared to that of the breakdown to earthis comparatively high. It is claimed that 70-80% of all transformer failures arise fromfaults between turns.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
49/115
49
A short circuit of few turns of the windingwill give rise to heavy fault currents in theshort circuited loop, but the terminal
currents will be very small, because of thehigh ratio of the transformation between thewhole winding and short circuited turns
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
50/115
50
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
51/115
51
Externally Applied Conditions
Sources of abnormal stress in a transformer
are :
a) Overload
b) System faults
c) Over voltage
d) Reduced System Frequency
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
52/115
52
Overload causes increased copper loss
and a consequent temperature rise.Overloads can be carried for a limited
periods, depending on the initialtemperature and cooling conditions
System short-circuits produce a relativelyintense rate of heating of the feeding
transformer, the copper loss increasingproportional to the square of the per unitfault current.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
53/115
53
The duration of the external short circuitthat a transformer can withstand withoutdamage if the current is limited only by self
reactance is shown in Table on the nextslide
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
54/115
54
Transformerreactance(%)
Faultcurrent(multiple of
rating)
Permittedfaultduration
(seconds)4 25 2
5 20 3
6 16.6 4
7 14.2 5
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
55/115
55
Large fault currents produce severemechanical stresses in the transformers;the maximum stress occurs during the first
cycle of the asymmetric fault current and socannot be averted by automatic tripping ofthe circuit
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
56/115
56
Overvolatges
Transient surge voltages
Power frequency voltages
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
57/115
57
Transient Surge Overvoltages
Transient over voltages arise from switchingand lightning disturbances and are liable tocause inter-turn faults
These voltages are usually limited byproviding lightening arrester (Metal ZincOxide).
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
58/115
58
Power Frequency Overvoltages
Causes increase in stress on insulation
Increase in working flux
Increase in iron loss
Disproportionality increase in magnetizingcurrent
Flux is diverted from the laminated core tothe steel structure
Increase in heating and temperature rise
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
59/115
59
Reduction in Frequency
It has an effect with regard to flux densitysimilar to that of power frequencyovervolatges.
Operation must not be continued with a highvoltage input at a low frequency
V/f > 1.1 is not permissible where V and fare expressed in p.u. of their rated value
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
60/115
60
MAGNETISING INRUSH CURRENT
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
61/115
61
MAGNETISING INRUSH CURRENTOF A TRANSFORMER
When a transformer is first energized,a
transient exciting current flows to bridge the
gap between the conditions existing before the
transformer is energized and the conditions
dictated by the steady state requirements
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
62/115
62
For any given transformer this transientcurrent depends upon:
The point on the voltage wave at which
the switch is closed.
The value and direction of the residualcore flux.
The shape of the saturation curve ,andthe normal flux density used.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
63/115
63
Often the magnitude of this transient
current exceeds full load current and may
reach 8-10 times full load current.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
64/115
64
In studying the phenomena that occur when
a transformer is energized, it is more
satisfactory to determine the flux in themagnetic circuit first and then derive the
current from the flux.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
65/115
65
This procedure is preferred because the
flux does not depart much from the sine
wave even though the current wave isdistorted.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
66/115
66
If the secondary of the transformer is open ,
the transformer can be treated as an iron-
core reactor, the differential equation for
the circuit consisting of the supply and
transformer can be written as
1de Ri ndt
(1)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
67/115
67
Normally the resistance R is small and can
be ignored for simplicity.
Under this condition the equation (1) can
be written as
1
de n
dt (2)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
68/115
68
If the supply voltage is sine wave voltage,
where,
= rms value of the supply voltage
e= instantaneous voltage applied to transformer
2 sin( )e E t
E
2 f
.(3)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
69/115
69
Substituting in equation (2)
1 2 sin( )
dn E t
dt
Solving the above equation
1
2cos( )
t
Et
n
..(4)
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
70/115
70
Equation (4) can be used to determine the
transient flux in the core immediately after
the transformer is energized.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
71/115
71
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
72/115
72
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
73/115
73
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
74/115
74
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
75/115
75
Amplitude of Harmonics in a typical
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
76/115
76
Component Typical Value(%)offundamental
DC 55
2nd Harmonic 633rd Harmonic 26.8
4th Harmonic 5.1
5th
Harmonic 4.16th Harmonic 3.7
7th Harmonic 2.4
Amplitude of Harmonics in a typicalMagnetizing Inrush current wave
TRANSFORMER DIFFERENTIAL
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
77/115
77
TRANSFORMER DIFFERENTIALPROTECTION
BASIC CONSIDERATIONS
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
78/115
78
The nominal currents in the primary and
secondary sides of the transformer vary in
inverse ratio to the corresponding voltages.
This should be compensated for by usingdifferent transformation ratios for the CTs on
the primary and secondary sides of the
transformer.
a. Transformation ratio
b Current Transformer
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
79/115
79
b. Current TransformerConnections
When a transformer is connected in
star/delta, the secondary current has a
phase shift of 300 relative to the primary
This phase shift can be offset by suitable
secondary CT connections
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
80/115
80
The zero-sequence currents flowing on
the star-side of the transformer will not
produce current outside the delta on theother side. The zero sequence current
must therefore be eliminated from the star-
side by connecting the CTs in delta.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
81/115
81
The CTs on delta side should be
connected in star in order to give 300
phase shift.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
82/115
82
When CTs are connected in delta, their
secondary ratings must be reduced to
1/3 times the secondary ratings of the
star-connected transformer, in order that
the currents outside the delta may
balance with the secondary currents of
the star-connected CTs.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
83/115
83
If transformers were connected in
star/star, the CTs on both sides would
need be connected in delta-delta.
c. Bias to cover tap-changing
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
84/115
84
If the transformer has the benefit of a tap
changer, it is possible to vary its
transformation ratio for voltage control.
c as to co e tap c a g g
facility and CT mismatch
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
85/115
85
The differential protection system should
be able to cope with this variation.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
86/115
86
This is because if the CTs are chosen to
balance for the mean ratio of the power
transformer, a variation in ratio from the
mean will create an unbalance
proportional to the ratio change. At
maximum through fault current, the spill
output produced by the small percentageunbalance may be substantial.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
87/115
87
Differential protection should be provided
with a proportional bias of an amount
which exceeds in effect the maximum ratio
deviation. This stabilizes the protection
under through fault conditions while still
permitting the system to have good basic
sensitivity.
d Magnetization Inrush
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
88/115
88
The magnetizing inrush produces a
current flow into the primary winding that
does not have any equivalent in the
secondary winding. The net effect is thus
similar to the situation when there is an
internal fault on the transformer.
d. Magnetization Inrush
Contd
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
89/115
89
Since the differential relay sees the
magnetizing current as an internal fault, it
is necessary to have some method ofdistinguishing between the magnetizing
current and the fault current, These
methods include:
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
90/115
90
Using a differential relay with a suitable
sensitivity to cope with the magnetizing
current, usually obtained by a unit thatintroduces a time delay to cover the
period of the initial inrush peak.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
91/115
91
Using a harmonic-restraint unit, or a
supervisory unit, in conjunction with adifferential unit.
Inhibiting the differential relay during the
energizing the transformer.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
92/115
92
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
93/115
93
Example:
A 3-phase, 33000/6600V transformer is
connected star/delta an the protecting CTs
on the low voltage side have a ratio of
300/5. What will be ratio of the CTS on the
H.V. side?
[20:8:1]
RESTRICTED EARTH FAULT
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
94/115
94
PROTECTION
Fig : Restricted earth fault protection for starconnected winding
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
95/115
95
Fig Amount of winding protected when transformer isresistance earthed and ratings of transformer andresistor are equal
Percentage of winding protected
Primaryoperating
current
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
96/115
96
Degree of protection is very much improved
with the application of a restricted earth fault(REF) protection
OVERFLUXING PROTECTION
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
97/115
97
OVERFLUXING PROTECTION
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
98/115
98
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
99/115
99
The system voltage, as measured by a
voltage transformer, is applied to a resistance
to produce a proportionate current; this
current , on being passed through a
capacitor, produces a voltage drop which is
proportional to the function in question, E/f,
and hence to the flux in the powertransformer.
HARMONIC RESTRAINT
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
100/115
100
DIFFERENTIAL RELAY
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
101/115
101
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
102/115
102
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
103/115
103
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
104/115
104
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
105/115
105
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
106/115
106
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
107/115
107
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
108/115
108
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
109/115
109
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
110/115
110
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
111/115
111
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
112/115
112
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
113/115
113
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
114/115
114
.
8/3/2019 Transformer Protection( Power Grid Ballabhgarh
115/115
.