Upload
armanksa
View
107
Download
5
Tags:
Embed Size (px)
DESCRIPTION
FAAST SYSTEM
Citation preview
1 Title of Slide Presentation
FAAST
Fire Alarm Aspiration Sensing Technology
2 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?
What do codes have to say about ASD?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for FAAST?
What’s the ROADMAP for FAAST?
3 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)? Why Aspirating Smoke Detection?
Why FAAST?
What do Codes have to say about ASD?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for ASD?
What’s the ROADMAP for FAAST?
4 Title of Slide Presentation
What is an Aspirating Smoke Detector?
5 Title of Slide Presentation
It’s a system that draws air from the area, via a pipe network, back to a central detector, which continually monitors for very small quantities of smoke. These devices typically include:
1. Aspirator or fan
2. Piping and sampling points (Active vs. Passive)
3. Filter
4. Sensing chamber
5. High sensitivity sensor
6 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?Why FAAST?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for ASD?
What’s the ROADMAP for FAAST?
7 Title of Slide Presentation
Why Aspirating Smoke Detection?
8 Title of Slide Presentation
What is Very Early Detection?
9 Title of Slide Presentation
Why do we need Early Detection?
• Early detection allows time to investigate the alarm and escalate if needed
• It gives time to resolve the situation before actual fire starts.
• It gives people some extra / crucial time to take decisions
• Provides extra time to take backup, switchover and shutdown the systems
• Most importantly prevents catastrophic loss of life , assets or business continuity
10 Title of Slide Presentation
What are applications of ASD?
Mission CriticalComputer and Data Processing
Historical/AestheticsMuseums, Churches, and Mansions
Large Public AreasShopping Malls , Airports , Stadiums
Difficult EnvironmentsCold Food Storage and Tunnels
Security ConcernsPrisons and Hospitals
Costs ConcernsIn Beam Pockets
Suppression SystemsIn Cross Zone, and Multi-Stage Activation
11 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for ASD?
What’s the ROADMAP for FAAST?
12 Title of Slide Presentation
Why FAAST?
13 Title of Slide Presentation
FAAST – Fire Alarm Aspiration Sensing Technology
FAAST is an Aspirating Smoke Detector which is Highly sensitive to smoke and has above average resistance to nuisance alarms.
14 Title of Slide Presentation
Why FAAST?
Unique Dual Detection Technology
Dual Source Optical Analysis
• Blue LED covers the widest ranges of fires
• Infrared Laser identifies non-fire particulates
• Advanced Algorithms discriminate between particulates and smoke
• Maximizes detection while minimizing nuisance alarms
15 Title of Slide Presentation
Why FAAST?
Three Stage Dust Discrimination
Stage 1: Particle Separator• It removes larger contaminates before they
enter the detection chamber and filter• Extends the life of the device
Stage 2: Field-Replaceable Filter• 30 micron• Only 1 filter to easily change every 4 years instead of 2• An initial warning is given to change the filter and a Minor
fault is generated
Stage 3: Unique Dual Detection Technology• Combination of Blue LED and Infrared laser along with
advanced algorithms to ensure it detects wide range of Smoke along with avoiding nuisance alarms
16 Title of Slide Presentation
Why FAAST?
One of the best Sensitivity range in its Segment
• FAAST has got one of the widest sensitivity range in its segment ranging from 0.00046% obs/ft to 6.25% obs/ ft
• It has Five programmable Alarm Thresholds : Alert, Action 1, Action2, Fire1 and Fire 2
• 8 Programmable Form C Relay contacts to integrate with any Fire panel or Suppression panel or be used as a stand alone system
17 Title of Slide Presentation
Why FAAST?
Advanced Communication Interfaces
Each unit comes with an inbuilt Ethernet Port for remote monitoring
Each unit comes with inbuilt Email support: FAAST can send alerts to 6 pre configured Email addresses
Each unit comes with an inbuilt ModBus interface for integration with third party systems
Each unit has an inbuilt Web Server: No need of software to remotely configure or monitor the system
All this included in the basic product, without any EXTRA COST!!!!
18 Title of Slide Presentation
Why FAAST?
Easy to use Software: Pipe IQ
• Single software that can be used to design the pipe layout, Configure the unit and monitor the unit after installation
• Very easy to use Graphical User Interface
• Can monitor up to 255 units connected in a network.
• FM approved to give results as per NFPA sensitivity and transport time requirements
• Available Free of Cost on System Sensor Website
19 Title of Slide Presentation
Why FAAST?
A Product from System Sensor, a Honeywell Company
FAAST is manufactured in System Sensor’s St. Charles Factory in Illinois, USA
System Sensor is World’s largest manufacturer by unit volume of fire detection and notification products.
It comes with a Three Year Warranty from the manufacturer
20 Title of Slide Presentation
Why FAAST?Required Agency Approvals:
UL, ULC
FM
CSFM
VdS approval
Australian approvals
Korean approvals
China
Additional agencies to follow:
Singapore
21 Title of Slide Presentation
Why FAAST?
At your Service…
Initial BOQ Support
Pipe layout design
Training for Partners, Consultants and End Customers
22 Title of Slide Presentation
Why FAAST?
Unique Dual Detection Technology : Blue LED and Infrared
3 Stage Dust Discrimination to reduce Nuisance alarms
One of the best Sensitivity range in its segment
8 Inbuilt programmable relays One of the most advanced communication
protocols: TCP/ IP, ModBus, Email support and inbuilt Web Server
One in All Software and that too FREE OF COST!!!
A product from System Sensor …a Honeywell Company
Manufactured in USA Three Year Warranty Support BOQ Support, Design Support and Trainings
for your Partners, Consultants and End Customers
23 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?
What do codes have to say about ASD?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for FAAST?
What’s the ROADMAP for FAAST?
24 Title of Slide Presentation
What do Codes have to say about ASD?
25 Title of Slide Presentation
• Advises detector spacing
• Standard coverage area reduced in high air flow
Codes and Aspiration: NFPA 72
26 Title of Slide Presentation
• Prescriptive and performance-based approach
• Requires automatic detection with early warning of fire
Codes and Aspiration: NFPA 75
27 Title of Slide Presentation
8.2* Automatic Detection Systems
Automatic detection equipment shall be installed to provide early warning of fire. The equipment used shall be a listed smoke detection-type system
NFPA 75: IT Equipment Rooms
28 Title of Slide Presentation
8.2.1* Automatic detection systems shall be installed in the following locations:
1. At the ceiling level throughout the IT equipment area
2. Below the raised floor of the IT equipment area containing cables
3. Above the suspended ceiling and below the raised floor in the IT equipment area where these spaces are used to recirculate air to other parts of the building
NFPA 75: IT Equipment Rooms
29 Title of Slide Presentation
• Prescriptive and performance-based
• Defines detector/port spacing, area coverage, and sensitivity
Codes and Aspiration: NFPA 76
30 Title of Slide Presentation
Detection Systems Definitions
NFPA 76: Fire Protection of Telecom Facilities
3.5.1 Early Warning Fire Detection (EWFD) Systems. Systems that use smoke, heat, or flame detectors to detect fires before high heat conditions threaten human life or cause significant damage to telecommunications service.
31 Title of Slide Presentation
3.5.5 Standard Fire Detection (SFD) Systems. Systems that use fire detection initiating devices to achieve certain life safety and property protection in accordance with applicable standards.
Detection Systems Definitions
NFPA 76: Fire Protection of Telecom Facilities
32 Title of Slide Presentation
3.5.6 Very Early Warning Fire Detection (VEWFD) Systems. Systems that detect low-energy fires before the fire conditions threaten telecommunications service.
Detection Systems Definitions
NFPA 76: Fire Protection of Telecom Facilities
33 Title of Slide Presentation
Fire Detection
NFPA 76: Fire Protection of Telecom Facilities
6.8.6.1 General. In telecommunications facilities containing greater than 232 m2 (2,500 ft2) of signal-processing equipment areas, the signal-processing equipment areas shall be provided with a VEWFD system for detection and alarm processing in accordance with Chapter 8.
34 Title of Slide Presentation
6.8.6.1.1 In telecommunications facilities containing 232 m2 (2,500 ft2) or less of signal-processing equipment areas, the signal-processing equipment areas shall be provided with an EWFD system for detection and alarm processing in accordance with Chapter 8.
Fire Detection
NFPA 76: Fire Protection of Telecom Facilities
35 Title of Slide Presentation
8.4.1.2 Fire alarm, supervisory, and trouble signals shall be annunciated at a constantly attended location
8.4.1.3* Use of VEWFD systems with an alert (pre-alarm) condition shall provide for an initial response by authorized personnel prior to fire dept. notification
8.4.1.4 Alarm monitoring centers maintained by the telecom service provider that have dedicated personnel 24 / 7 shall be permitted to be the supervising station
Chapter 8.4
NFPA 76: Fire Protection of Telecom Facilities
36 Title of Slide Presentation
Chapter 8.4
NFPA 76: Fire Protection of Telecom Facilities
8.4.2.1.3 Automatic fire alarm signals shall be initiated by, but not be limited to, the following:
1. Smoke detectors
2. Heat detectors
3. Flame detectors
4. Suppression system release
5. Water flow initiating devices
37 Title of Slide Presentation
8.4.2.1.4 Fire alarm signals shall take precedence in processing over all other signals
8.4.2.1.5 The automatic or manual initiation of alarm conditions shall cause the building fire alarm notification appliances to operate in accordance with the requirements of NFPA 72
Chapter 8.4
NFPA 76: Fire Protection of Telecom Facilities
38 Title of Slide Presentation
8.4.2.2.4 Supervisory signals shall include but not be limited to:
1. Alert signal (pre-alarm) from a VEWFD system
2. Fire alarm initiating devices, where designated as such (e.g., duct smoke detectors)
3. Sprinkler valve supervisory switches
4. Fire pump off-normal conditions
5. Other abnormal fire safety–related conditions
Chapter 8.4
NFPA 76: Fire Protection of Telecom Facilities
39 Title of Slide Presentation
8.4.2.2.7 The alert pre-alarm signal from a VEWFD system shall be distinguishable from all other fire alarm, supervisory, and trouble signals.
Chapter 8.4
NFPA 76: Fire Protection of Telecom Facilities
40 Title of Slide Presentation
Chapter 8.5.2 Detection Systems
NFPA 76: Fire Protection of Telecom Facilities
8.5.2.1 EWFD and VEWFD smoke detection systems shall use sensors or ports with spacing that is less than that normally required by NFPA 72.
41 Title of Slide Presentation
8.5.3.1.2 VEWFD Sensor and Port Installation
NFPA 76: Fire Protection of Telecom Facilities
8.5.3.1.2.1* Every type of sensor and port installed in an area shall be limited to a maximum coverage area of 18.6 m2 (200 ft2)
42 Title of Slide Presentation
8.5.3.1.2 VEWFD Sensor and Port Installation
NFPA 76: Fire Protection of Telecom Facilities
8.5.3.1.2.2* Where two levels (high and low) of ports or sensors are provided, the following requirements shall be met:
1. Each level shall be limited to a coverage of 400 ft2 or less per port or sensor.
2. The coverage limitation between high and low levels shall be limited to 200 ft2 or less providing for staggered port or sensor arrangements between each level.
43 Title of Slide Presentation
8.5.3.1.2 VEWFD Sensor and Port Installation
NFPA 76: Fire Protection of Telecom Facilities
8.5.3.1.2.3* Sensors or ports shall be installed to monitor return air from the space.
44 Title of Slide Presentation
Staggered Layout of Sample Ports/Sensors
• High-level sensors or ports at 37.2 m2 (400 ft2) or less
• Low-level sensors or ports at 37.2 m2 (400 ft2) or less
• Effective net coverage per sensor or port is 18.6 m2 (200 ft2) or less
NFPA 76: Fire Protection of Telecom Facilities
45 Title of Slide Presentation
8.5.3.1.2.5* Minimum sensitivity settings above ambient airborne levels for the VEWFD systems installed shall be:
1.Alert condition:
a. Air-sampling systems: 0.2% per foot obs. *(effective sensitivity at each port)
b. Spot-type sensors: 0.2% per foot obs.
2.Alarm condition:
a. Air-sampling systems: 1.0% per foot obs. *(effective sensitivity at each port)
b. Spot-type sensors: 1.0% per foot obs.
Chapter 8: VEWFD Levels
NFPA 76: Fire Protection of Telecom Facilities
46 Title of Slide Presentation
Chapter 8: VEWFD Levels
NFPA 76: Fire Protection of Telecom Facilities
8.5.3.1.2.6 Maximum transport time from the most remote port to the detection unit of an air-sampling system shall not exceed 60 seconds.
47 Title of Slide Presentation
Chapter 8: EWFD Levels
NFPA 76: Fire Protection of Telecom Facilities
Levels for the EWFD systems installed shall be as follows:
• 8.5.3.2.1.3 The minimum alarm sensitivity setting at the sensor or port used for EWFD in telecommunications equipment areas shall be 1.5% per foot
• 8.5.3.2.1.4 Maximum transport time from the most remote port to the detection unit of an air-sampling system shall be a maximum of 90 seconds.
48 Title of Slide Presentation
8.7.2* Design and Installation
NFPA 76: Fire Protection of Telecom Facilities
Where provided, smoke management systems shall be designed, installed, and acceptance tested in accordance with accepted engineering practice
49 Title of Slide Presentation
8.5.3.1.2.3* Sensors or ports shall be installed to monitor return air from the space.
a) Where stand-alone packaged HVAC units are installed, sensors or ports shall be installed where return air is brought back to the unit.
b) Sensors or ports shall be installed such that each covers no greater than 0.4 m2 (4 ft2) of the return air opening.
NFPA classifies air exchange area as:
• Medium – 6 air exchanges per hour
• High – 12 air exchanges per hour
NFPA 76: Fire Protection of Telecom Facilities
50 Title of Slide Presentation
8.2* Automatic Detection Systems. Automatic detection equipment shall be installed to provide early warning of fire. The equipment used shall be a listed smoke detection–type system and shall be installed and maintained in accordance with NFPA 72, National Fire Alarm Code.
NFPA 75 SummaryClick icon for
Code Details.
51 Title of Slide Presentation
200 sq ft required spacing in room and sub-floor (VEWFD)
400 sq ft (EWFD)
4 sq ft spacing at return air registers
• 0.2% (Alert) & 1.0% (Alarm) Minimum Sensitivity (VEWFD) 1.5% (Alarm) Minimum Sensitivity (EWFD)
• 60 second maximum transport times (VEWFD) 90 second (EWFD) / 120 second (SFD)
• Normal NFPA 72 requirements for Standard Fire Detection (SFD)
NFPA 76 SummaryClick icon for
Code Details.
52 Title of Slide Presentation
EN 54 – 20
Classification of Sensitivity
53 Title of Slide Presentation
EN 54 – 20
VDE 0833 – 2: At least Class B for High – ceiling Applications
54 Title of Slide Presentation
EN 54 – 20
It is not the detector class that is the critical factor, but the classof the project design itself
55 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?
Is Multi Pipe ASD actually better than a Single Pipe ASD? Is it really difficult to design a BOQ for ASD?
What’s the ROADMAP for FAAST?
56 Title of Slide Presentation
Is Multi Pipe ASD actually better than Single Pipe ASD?
57 Title of Slide Presentation
Is Multi pipe ASD better than Single Pipe?
Not Always!!!!
Single Pipe ASD total Maximum Pipe Length = 100 meters
Four Pipe ASD total Maximum Pipe Length = 200 m
Hence,
In terms of area covered
1 No. Four Pipe ASD = 2 No. Single Pipe ASDs
Let’s understand using a Scenario….
58 Title of Slide Presentation
Is Multi pipe ASD better than Single Pipe?
70 meters
10 Meters
Dimensions: 10 X10 X 70 meters (H X W X L)
No. of Four pipe units required = 1 No. of One pipe units required = 2
Unit Cost of Four Pipe unit with pipe addressability = USD 13K
Unit Cost of one pipe unit = USD 5K
Hence total cost of units with one pipe System = 10K
59 Title of Slide Presentation
Is Multi pipe ASD better than Single Pipe?
It does not END here:
Advantage of using a single pipe system Vs four pipe system
Incase if a four pipe system breaks down because of any reason, your larger area goes down, as compared to a single pipe system in which case smaller area is affected.
60 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for ASD? What’s the ROADMAP for FAAST?
61 Title of Slide Presentation
Is it really difficult to design a BOQ for FASST?
62 Title of Slide Presentation
Is it really difficult to design a BOQ for FAAST?
Not Really!!!
• Less than 15 SKUs in the Price list
• Unit with inbuilt Filter, Ethernet port, ModBus Interface, Display LEDs, etc, hence no extra SKUs required.
• Lets create a BOQ and see for ourselves
63 Title of Slide Presentation
Is it really difficult to design a BOQ for FAAST?
Not Really!!!
• Less than 15 SKUs in the Price list
• Unit with inbuilt Filter, Ethernet port, ModBus Interface, Display LEDs, etc, hence no extra SKUs required.
• Lets create a BOQ and see for ourselves
Microsoft Office Excel Worksheet
64 Title of Slide Presentation
70 meters
10 Meters
Dimensions: 10 X10 X 70 meters (H X W X L)
Let’s consider the same old scenario.
Above are the dimensions of a work shop. Customer wants aspiration detection at the ceiling level above cable trays.
Microsoft Office Excel 97-2003 Worksheet
Is it really difficult to design a BOQ for FAAST?
65 Title of Slide Presentation
What is an Aspirating Smoke Detector (ASD)?
Why Aspirating Smoke Detection?
Why FAAST?
Is Multi Pipe ASD actually better than a Single Pipe ASD?
Is it really difficult to design a BOQ for ASD?
What’s the ROADMAP for FAAST?
66 Title of Slide Presentation
What is the ROADMAP for FAAST?
67 Title of Slide Presentation
Roadmap
2013Intelligent/Modbus
FAAST
2012FAAST LT
2014FAAST XL
2015FAAST XS
Continuous
68 Title of Slide Presentation