Abstract
Purpose:
This study has made to measure the effectiveness of Clina Shaft-unit in UAE.
Method:
Install Clina system in the Constructional model Considering the following
elements:
- 4 shaft-units
- Control System.
- Constructional model ( 43.8 m ²). Drawing(1)
- Glass Flats (Windows ,Doors)
- External Walls
- External Walls Directions
- The non-exposed parts to the direct Sun radiation of the constructional
model.
- 2 Split Unit A/C (2 Ton each) –for Consumption Comparison Study
Sample used LG split unit, power input under normal operation 2.4 Kwh and
the maximum power input 4.0 Kwh, in our study we choose the normal
operation.
- Location
- Date , Time
Results:
Clina System Power Consumption:
Clina Sys Power Consumption
Time Temp.on150
cm Humidity % Power CONS. KW Power CONS. KW/H
1:00 AM 20.5 47.00 7163 5
2:00 AM 20.2 47.00 7166 3
3:00 AM 20 46.00 7169 3
4:00 AM 20.2 46.00 7172 3
5:00 AM 19.9 46.00 7175 3
6:00 AM 19.1 46.00 7178 3
7:00 AM 19.7 46.00 7181 3
8:00 AM 20.2 47.00 7184 3
9:00 AM 20.3 45.00 7187 3
10:00 AM 20.3 47.00 7190 3
11:00 AM 24.2 52.00 7194 4
12:00 PM 23.9 48.00 7199 5
1:00 PM 22.5 52.00 7204 5
2:00 PM 22.4 55.00 7208 4
3:00 PM 22.7 57.00 7211 3
4:00 PM 23.4 58.00 7215 4
5:00 PM 23.4 56.00 7220 5
6:00 PM 21.8 55.00 7223 3
7:00 PM 20.8 47.00 7227 4
8:00 PM 20.3 47.00 7231 3
9:00 PM 20.2 46.00 7234 3
10:00 PM 20.2 47.00 7237 3
11:00 PM 20.2 48.00 7240 3
12:00 AM 20.3 50.00 7243 3
1:00 AM 20.2 48.00 7246 3
AVG Power Consumption/H 3.625
* Water Chiller Temperature = 8 C
* OutSide Weather ( Dubai 08-09/oct/2016 ) = (HI 38 C , Lo 29 C ) , H =52% *Location : (Alwrqaa ,Dubai ,UAE)
20.5 20.2 20 20.2 19.9 19.1 19.7 20.2 20.3 20.324.2 23.9 22.5 22.4 22.7 23.4 23.4 21.8 20.8 20.3 20.2 20.2 20.2 20.3 20.2
47.0047.0046.0046.0046.0046.0046.0047.0045.00
47.00
52.0048.00
52.0055.00
57.0058.0056.0055.00
47.0047.0046.0047.0048.0050.00
48.00
53 3 3 3 3 3 3 3 3 4 5 5 4 3 4 5
3 4 3 3 3 3 3 30
10
20
30
40
50
60
70
Clina Sys Power Consumption
Temp.on150 cm Humidity % Power CONS. KW/H
Clina & A/C Power Consumption Comparison
Time Temp.on150
cm Clina Power CONS. KW/H
Clina Power CONS. KW/H/T
2 Split Unit Power CONS. KW/H
2 Split Unit Power CONS.
KW/H/T
1:00 AM 20.5 5.00 1.00 4.80 1.20
2:00 AM 20.2 3.00 0.6 4.8 1.20
3:00 AM 20 3.00 0.6 4.8 1.20
4:00 AM 20.2 3.00 0.6 4.8 1.20
5:00 AM 19.9 3.00 0.6 4.8 1.20
6:00 AM 19.1 3.00 0.6 4.8 1.20
7:00 AM 19.7 3.00 0.6 4.8 1.20
8:00 AM 20.2 3.00 0.6 4.8 1.20
9:00 AM 20.3 3.00 0.6 4.8 1.20
10:00 AM 20.3 3.00 0.6 4.8 1.20
11:00 AM 24.2 4.00 0.8 4.8 1.20
12:00 PM 23.9 5.00 1.00 4.8 1.20
1:00 PM 22.5 5.00 1.00 4.8 1.20
2:00 PM 22.4 4.00 0.8 4.8 1.20
3:00 PM 22.7 3.00 0.6 4.8 1.20
4:00 PM 23.4 4.00 0.8 4.8 1.20
5:00 PM 23.4 5.00 1.00 4.8 1.20
6:00 PM 21.8 3.00 0.6 4.8 1.20
7:00 PM 20.8 4.00 0.8 4.8 1.20
8:00 PM 20.3 3.00 0.6 4.8 1.20
9:00 PM 20.2 3.00 0.6 4.8 1.20
10:00 PM 20.2 3.00 0.6 4.8 1.20
11:00 PM 20.2 3.00 0.6 4.8 1.20
12:00 AM 20.3 3.00 0.6 4.8 1.20
1:00 AM 20.2 3.00 0.6 4.8 1.20
Total 87.00 16.4 120.00 30.00
AVGs Clina AVG Power Consumption/H/T 0.683333333 A/C AVG Power Consumption/H/T 1.25
Conclusion:
Consumption AVGs:
- Clina AVG Power Consumption/H/T = 0.683333333 KW
- A/C AVG Power Consumption/H/T =1.25 KW
Clina saving energy 54 % compared to Split Unit A/C
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1:00AM
2:00AM
3:00AM
4:00AM
5:00AM
6:00AM
7:00AM
8:00AM
9:00AM
10:00AM
11:00AM
12:00PM
1:00PM
2:00PM
3:00PM
4:00PM
5:00PM
6:00PM
7:00PM
8:00PM
9:00PM
10:00PM
11:00PM
12:00AM
1:00AM
Clina & A/C Power Consumption Comparison
Clina Power CONS. KW/H/T 2 Split Unit Power CONS. KW/H/T
Saving Energy Recommendations:
- )The more insolation + Chiller efficiency( The more saving energy .
- Economy , Comfortable Mode:
Test Outcomes:
Start 8:00pm ,Power meter =7390 , Temperature =22.6c ,Economy Mode
End 8:00am , Power meter =7401 , Temperature =26.6c ,Starting
Comfortable Mode ,After 10 minutes Temperature=24.6c