Upload
singh1515
View
19.298
Download
22
Embed Size (px)
DESCRIPTION
fire detection
Citation preview
FIRE DETECTION & ALARM SYSTEMFIRE DETECTION & ALARM SYSTEM
RAVI SHANKAR SINGH(E6S304)
1
2
Why are fire detection and alarm systems required?
Detect fire in the areas.Notify building occupants to take evasive action to escape the
dangers of a hostile fire.Summon organized assistance to initiate or assist in fire control
activities. Initiate automatic fire control & suppression systems & to sound
alarm.Supervise fire control & suppression systems to assure operational
status is maintained Initiate auxiliary functions involving environmental, utility & process controls
Systems may incorporate one or all of these functions
Block diagram of FDA systemBlock diagram of FDA system
3
Input Devices
OutputDevices
Control Panel
4
Input Devices
Fire Box (Manual Pull Station)When shorted trips an alarm (usually fire) Installed in the normal exit path
Types of Fire BoxSingle Action
Pull handle once
Glass Break Glass rod or plate is broken
Double Action Lifting of a cover or opening a door
5
3.1) Heat detectors 1. fixed temp type heat detector2. rate-of-rise type heat detector
3.2) Smoke detectors1. Photoelectric2. Ionization
3.3) Flame detectors1. Ultraviolet light (UV)2. Infrared (IR)
3.4) Fire-gas detectors
FIRE DETECTORS
Input Devices
Heat Detectors
Smoke Detector
6
Fixed temp. heat detectors Fixed temp. heat detectors
Detect heat by one or more of 3 primary principles of physics:
Expansion of heated material Melting of heated material Changes in resistance of heated material
Rate-of-rise heat detectorsRate-of-rise heat detectors Operate on the principle that the temperature in a room will
increase faster from fire than from atmospheric temperature Will initiate an alarm when the rise in temp. exceeds 12-15F (7-8C)
per minute Alarm can be initiated at a temp. far below that required for a fixed-
temp. device
◦Reliable devices, not subject to false activations◦But if not properly installed, they can be activated under non fire
conditions (eg. detector located too close to doorway and subject to extreme fluctuations in temperatures)
Pneumatic rate-of-rise spot detector Pneumatic rate-of-rise line detector Thermoelectric detector
9
Photoelectric smoke detectorUses a photocell coupled with a specific light source.
Basically smoke entering the smoke detector chamber disrupts the
light beam causing an alarm signal to be initiated
More sensitive to smoldering fires
1: optical chamber2: cover3: case moulding4: Photodiode (detector)5: infrared LED
10
Circuit of Photoelectric Smoke Detector
11
Ionization smoke detectorInvisible products of combustion enter the chamber
decreasing the current between the –ve & +ve plates, thereby
initiating an alarm signal.
Generally responds faster to flaming fires versus smoldering
fires
Automatically resets when the atmosphere clears
Fire-gas detectorsFire-gas detectors
Monitors levels of carbon dioxide and carbon monoxide
(common to all fires)
More discriminating than other detectors – can be designed to
be sensitive only to gases produced by specific types of hostile
fires and ignores gases produced by friendly fires
Not many in use – very specialized applications
Combination detectorsCombination detectors
Single device can be designed to have more than 1 function eg.
heat/smoke, smoke/carbon monoxide detectors
Different combination make the detectors more versatile and
more responsive to fire conditions
14
S.No PLANT AREA TYPE OF DETECTORS
1. Main control room, Computer room, Electronic cubicle room and control rooms in outlying areas.
Combination of -
Ionisation smoke detector
Optical type smoke detector
2. Switchgear rooms in main Plant and outlying areas, battery charger room, record and shift-in-charge engineers room
Ionisation type smoke detector.
3. Office rooms / storage rooms Ionisation type smoke detector
4. Battery rooms and chemically corrosive areas.
Corrosion resistant, Rate of rise of temperature heat detector with fixed temperature setting.
5. Cable gallery Combination of Optical type smoke detectors and Linear heat sensor running above all HV and LV power cable trays. Unless the vertical distance between cable tray is less than 500 mm in which case alternate trays (in addition to the top and bottom trays). The optical smoke detector and LHS detectors along with necessary number of interface units in the cable gallery will be cross zoned to actuate the water spray system
6. Station building / Plant area Infrared flame detectors (where oil tanks are located), spray tanks rate of rise of temp. detector with fixed element
Selection of Detectors for different Area
15
7. Coal Conveyors Analogue Linear heat sensor cable, infra red spark / ember detectors and manual call points. If water spray system is provided the LHS cable and IR detector will be cross zoned to actuate the same
8. Dusty areas in coal handling plants like crusher house
Flame proof manual call points
9. Junction towers Flame proof heat detectors, flame proof manual call points
10. Conveyor tunnels Flame proof infrared detectors, flame proof MCPs, LHS cables
11. Hazardous plant areas such as fuel oil / lube oil, DG houses, H2 generating plants and hydrogen storage areas.
Flame proof rate of rise of temperature detector with fixed element and flame proof MCP
16
Audible Output DevicesAn audible alarm signal lets people know
the alarm system has been activatedDevices may be mounted inside or outside
based on level of protection required May consist of:
SirensBells BuzzersHorns Voice Drivers
Output Devices
17
Visual Output Devices
A visual signal lets users know the status of the alarm system if activated
Visual devices may be mounted inside or outside
May consist of...Strobe lightsLED’sOn / Off site printer
Output Devices
18
Criteria to determine layout of the fire detectors
The design, construction and operational features of all types of
detectors shall be in accordance with relevant standards.
The number of fire detectors to be installed is governed by
total area to be protected
type of building construction
air movement & air velocity
ceiling obstructions
concentration of equipment in the area covered
sensitivity required
Area is divided into zones to be protected
The zones of individual detectors should overlap and no blind zone
should be left.
19
Areas above false ceiling and below false flooring shall be
considered as separate zones.
Under ideal conditions of smooth ceiling and average room size, one
detector is recommended to protect the area.
Ionisation type detectors should be located where the largest
combustible gas concentration can be expected.
In the air conditioned areas both ionisation and optical type smoke
detectors are used.
Detectors must always installed at the highest point of the ceiling
and minimum coverage indicated by manufacture shall be
considered.
The number of detectors and their location should be so selected that
complete coverage is obtained
20
Initial quantity estimation of smoke / heat detectors
35 to 40 sq.m per detector for general application. 20 to 25 sq.m per detector for main control room, electronic
cubicle room, computer room, etc., in view of high valve concentration
The exact requirement shall calculated based on relevant IS/NFPA standard
TYPES OF FIRE DETECTION SYSTEMTYPES OF FIRE DETECTION SYSTEM
A. Conventional FDA System
B. µ-P Based Addressable FDA System
21
CONVENTIONAL FIRE DETECTION AND ALARM SYSTEMCONVENTIONAL FIRE DETECTION AND ALARM SYSTEM
Conventional fire sensors and manual call points shall provide for continuous
surveillance the area.
Main fire alarm panel shall derive signals from the zone indicating panels and
audible and visual annunciation shall be provided in the event of fire.
Repeater panel shall be located in security house / fire station to alert fire
fighting / security personnel.
Fire detectors shall be selected depending on the type of fire expected in a
particular area.
22
23
All the fire alarm circuits shall be of modular design using electronic printed card circuits to facilitate easy replacement.
The system design shall be such that operation / resetting of alarms for one zone / detector will not block availability of alarm for any other zone.
the alarm / system resetting shall be by common push button and not by individual switches for different zones / detectors.
24
Addressable Fire Detection & Alarm System
It is an automatic fire detection & alarm system consists of fire detectors & manual call points positioned in Zones/ loop through out a building(Area).
These are wired to control & indicating equipment which shows the location of alarm call, & actuates audible alarm sounders.
Industrial/ Non Industrial Buildings
Institutional Buildings
Residential Apartments
Hotel & Hospitals
All Industries
Mall & Multi Storied Complexes
Offices & Control Rooms
25
Addressable µ-P based FDA system
Addressable I/P devices
Addressable O/P devices
Control panel
Constant power supply
Emergency Battery supply
26
Microprocessor Based control Panel
Processor(CPU)
Adequate number of loop modules for detector loops
A coloured VDU monitor with keyboard
Output modules for alarm
Output control & interlocks
Communication modules for interfacing
27
Continuous supervision of the detector connecting lines, individual
detector performance / operation and disconnection / removal of
detectors.
Discrimination between a real fire and false fire conditions by
incorporating signal verification and other features.
Individual detector addressing capability.
Detection of over / under sensitive detectors and automatic calibration by
increasing or decreasing their sensitivity levels based on environmental
conditions like air movement, fumes, humidity, etc.
Pre-alarm in case of any detector / detectors requiring maintenance.
Facility shall be provided for alteration programme according to needs.
BENEFITS OF µ-P BASED ADDRESSABLE FDA SYSTEM
CLEARANCE AND APPROVALSCLEARANCE AND APPROVALS
All detectors and sensors shall be approved by any of the
following bodies as applicable :
A. Under writers’ Laboratories (UL) – USA
B. Fire Officers Committee (FOC) – UK
C. Any other internationally recognised body acceptable to
Purchaser / Consultant. Approval certificates shall be
furnished with the bid.
28
The Contractor shall be solely responsible for obtaining the required approval and clearance for the different components and systems of the fire detection and alarm system from the following authorities as applicable.
A. Tariff Advisory Committee (TAC) of the Insurance Association of India.
B. Dept. of Atomic Energy (DAE) Certification of safety from radioactivity.
C. Central Building Research Institute (CBRL), RoorkeeD. Central Mining Research Station (CMRS), Dhanbad.E. Local Fire Authority.
29
SOME APPLICABLE STANDARDSSOME APPLICABLE STANDARDS
Code of practice for selection, installation & maintenance of
automatic fire alarm & detection system-IS-2189,BS-5839
PART1,ANSI-NFPA-72,FOC RULES
Code of practice for fire safety of buildings - IS-1646
Smoke detectors for use in automatic fire alarm system-IS-11360,
BS-5445 PART-7, ANSI-UL268
30