Variable Frequency Drive / Inverter
STARVERT iS50.75 -55kW(1-75HP) 3 phase 200 -230Volts
0.75 -75kW(1-100HP) 3 phase 380 -460Volts
Starvert iS5
Overview
Features & Selection Guide
Specifications & Wiring
Terminal Configuration, Keypad & Parameter Navigation
Program Parameter Descriptions
Dimension
Options, DB Resistor & Peripheral Devices
RFI Filters
02
04
06
08
10
18
20
22
Contents
Overview
02
Sensorless, sensored vector controlled iS5, keeps your application in more stable, durable and precise condition.
Options■ Communications Board:•RS-485 •DeviceNet•F-Net•ModBus-RTU•ProfiBus DP•Extended I/O Module
-Sub-A Board: 3 Multi-Function Input3 Multi-Function Output
-Sub-B Board : Encoder Plus InputEncoder Plus Output
-Sub-C Board :3 Multi-Function Input3 Multi-Function OutputAux. Analog Reference Frequency (Isolated)
■ Cable for Remote Keypad Operations■ Dynamic Braking Units for 11~75kW Inverters■ Dynamic Braking Resistors
Application■ Traverse■ Draw■ MMC (Mult Motor Control)■ Converting■ Material Handling■ Web Processing■ Fan/Pump Controls■ Conveyors■ Industrial Washing machine, etc.
Conformity to global standards■ UL and cUL listed for North America■ CE marked for Europe■ Quality process controlled by ISO9001, ISO14000
Standard features■ kW / Voltage Ratings:•0.75~55kW, 200-230VAC, 3 phase •0.75~75kW, 380-480VAC, 3 phase
■ Enclosure: IP00 ~ IP20■ Inverter Type: PWM with IGBT■ Control Method: Sensorless/Sensored Vector ■ 1~15kHz Carrier Frequency (1~8kHz. over 30kW)■ 0~400Hz Output Frequency ■ Removable Keypad (Able to read & write parameters)■ Intelligent Accel/Decel for Trip-Free Operation■ Auto Tuning■ 8 Multi-Function Inputs■ 1 Multi-Function Outputs■ Failure Relay■ Built-in PID Control■ Pre-Set Speeds ■ Wire Operation■ Multi-step Programmable Run Patterns■ Auto Torque Boost■ DC Injection Braking■ Stall Prevention■ Built-In Braking Circuit for 0.75 ~ 7.5kW units
Starvert iS5
03
Extended I/O boardsThe iS5 has several additional I/O boards that can be easily mounted into the connection terminal on controlboard. Each I/O board is standardized for a specific I/O requirement.The three main I/O boards are "Sub-board A", "Sub-board B" and "Sub-board C".This helps system engineer to design most adequate and cost effective system using the exactly necessary number of I/Os and functions.It is extendable and changeable in case of system upgrade or change.The control parameters and detailed functions for these boards are not shown until any of them is inserted.
Diversity of communication interfacesThe iS5 provides most popular communication interfaces such as Device Net, Profibus DP, Modbus-RTU, RS485 and F-Net (LS proprietary protocol for LS PLC communication). The "DriveviewTM" software offers Window® based computer monitoring tool through RS-485 interface withgraphic capture, keypad emulator, parameter edit, and text monitor. It is applicable for all LS inverters.
Built-in PID controlIt is valuable in process control. The built-in PID algorithm controls flow, temperature, pressure, etc. through theproportional, integral and differential calculus between the feedback value and reference value in closed loop.The high speed CPU makes the calculation easy and fast.
Sensorless vector controlThe iS5 adopts sensorless vector control algorithm, and it improves not only the torque control characteristics, but the speed controlability in an uncertain condition caused by the load variation as well. The iS5 especially generates strong torque at a low speed range as shown below.
04
SV008iS5-4SV015iS5-4SV022iS5-4SV037iS5-4SV055iS5-4SV110iS5-4SV150iS5-4SV185iS5-4SV220iS5-4SV300iS5-4SV370iS5-4SV450iS5-4SV550iS5-4SV750iS5-4
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV055iS5-2SV110iS5-2SV150iS5-2SV185iS5-2SV220iS5-2SV300iS5-2SV370iS5-2SV450iS5-2SV550iS5-2
0.75 11.5 22.2 33.7 55.5 7.57.5 1011 1515 20
18.5 2522 3030 4037 5045 6055 7575 100
Features & Selection Guide
Auto tuningThe auto tuning algorithm in iS5 sets the motor factors automatically. It brings the traditional commissioning difficulties mainly inlow speed by the load variation and the low torque generation to a settlement.
Optimum acceleration and decelerationTo make a maximum torque during the acceleration and deceleration, so called "trip free" function is acting during accelerationand deceleration. Both of Acceleration and deceleration may cause a trip in case that it is manually programmed. The 32-bitDSP CPU monitors the current transition during the acceleration and deceleration to program an optimum curve that is underthe triptrigering level automatically.
Inverter rating selection guide
Inverter type nomenclature
Application motorKW HP
200~230V 380~460V
SV 008 iS5 -4 #
LS Starvert inverter
008015
.
220
0.75kW1.5kW
.
22kW
iG5iS5iHiV5
iG5 seriesiS5 seriesiH series*iV5 series
-2-4
3 phase 200~230V3 phase 380~480V
* iH inverter has a different designation in kW.
StoppedCH1=2VDC 10:1
CH3=5VDC 10:1
CH4=2VDC 10:1
1s/div[1s/div]NORM:1kS/s
=Trigger=Mode : AUTOType : EDGE CH1Delay : 0.0nsHold Off : MINIMUM
=Record Length=Main : 10kZoom : 500
=Filter=Smoothing : OFFBW : FULL
=Offset=Ch1 : 0.00VCh2 : 0.00VCH3 : 0.00VCH4 : 0.00V
3
StoppedCH1=2VDC 10:1
CH3=5VDC 10:1
CH4=2VDC 10:1
1s/div[1s/div]NORM:1kS/s
=Trigger=Mode : AUTOType : EDGE CH1Delay : 0.0nsHold Off : MINIMUM
=Record Length==Filter=Smoothing : OFFBW : FULL
=Offset=
3
Traditional curve Optimum curve
Trip
Main : 10kZoom : 500
Ch1 : 0.00VCh2 : 0.00VCH3 : 0.00VCH4 : 0.00V
# option built-in
Starvert iS5
05
Specifications 200~230V Class (0.75~55kW)Inverter Type (SV_ _ _iS5-_)
Motor Rating*1)
Output ratings
Input ratings
Weight[kg]
[HP][kW]Capacity[kVA]*2)
FLA[A]FrequencyVoltage Voltage Frequency
10.751.95
4.6
008-2 015-2 022-2 037-2 055-2 075-2 110-2 150-2 185-2 220-2 300-2 370-2 450-2 550-22
1.538
4.6
32.24.512
4.8
53.76.116
4.9
7.55.59.124
7.5
107.512.232
7.7
1511
17.546
13.8
2015
22.960
14.3
2518.528.274
19.4
3022
33.588
20
403046122
503755146
604568180
755584220
0 ~ 400 Hz200 ~ 230V*3)
3 phase 200 ~ 230 V (±10%) 50 ~ 60 Hz (±5%)
Specifications 380~480V Class (0.75~75kW)Inverter Type (SV_ _ _iS5-_)
Motor Rating*1)
Output ratings
Input ratings
Weight[kg]
Braking Torque
Cooling methodEnclosure
Braking circuitAverage braking torqueMax.continuousbrakingMax. duty
100%
5seconds
30 (3)%ED
100%
5seconds
30 (2)%ED
100%
5seconds
30 %EDForced air cooling
IP00
150%
Controlled by braking unit*4)
10 %ED
On board
Control
Operation
Control methodFrequency setting resolutionFrequency accuracyV/F ratioOverload capacityTorque boost
Operation methodFrequency settingStart signalMulti-step
Multi-step accel/decel time
Emergency stopJogAuto operationFault reset
Operation status
Fault outputIndicator
Operation function
Inverter trip
Inverter alarmMomentary power lossOperation informationTrip informationAmbient temperatureStorage temperatureAmbient humidityAltitude . VibrationApplication side
Key / terminal / communication operationAnalog : 0 ~ 10V / 4 ~ 20 mA / Additional port for Sub-board (0 ~10V)
forward, reverseUp to 8 speeds can be set (use multi-function terminal)
0 ~ 6,000 sec, up to 8 types can be set and selected for each setting (use the multi- function terminal), Accel/Decel pattern : linear pattern, U pattern, S pattern
Interrupts the output of the inverterJog operation
Operates from internal sequence by setting the multi-function terminal (5way x 8step)Trip status is removed when protective function isactive
Frequency level detection, Overload alarm, stalling, overvoltage, undervoltage, inverter overheating, running, stop, constant speed, exchange inverter to commercial line, speed searching, auto operation step, auto operation sequence
Contact output (30A,30C,30B) - AC250V 1A, DC30V 1AChoose 1 from Output frequency, output current, output voltage, DC voltage (Output voltage: 0 ~ 10V)
DC braking, frequency limit, frequency jump, second function, slip compensation, reverse rotation prevention, auto restart, exchange inverter to commercial line, auto-tuning, PID control
Overvoltage, undervoltage, overcurrent, fuse open, ground fault, inverter overheating, motor overheating, output phase loss, MC fail (over 30kW only), overload protection, external fault 1,2, communication error, loss of speed command, hardware fault, option fault etc.
Stall prevention, overload alarmLess than 15 msec : continuous operation (over 30kW drives excluded), more than 15 msec : auto restart possible
Output frequency, output current, output voltage, frequency value setting, operating speed, DC voltageIndicates the fault when the protection function activates, memorizes up to 5 faults
-10 °C ~ 40 °C-20 °C ~ 65 °C
90 % RH max.(Non condensing)Below 1,000 m˙below 5.9m/sec2 (=0.6g)
No corrosive gas, combustible gas, oil mist, or dust
V/F control, sensorless vector control(selectable), sensored vector controlDigital reference : 0.01 Hz (below 100 Hz), 0.1 Hz (over 100 Hz) Analog reference : 0.03 Hz / 50 Hz
Digital : 0.01% of max. output frequency Analog : 0.1% of max. output frequencyLinear, Square pattern, User V/F
150 % of rated current for 1 min., 200% of rated current for 0.5 sec. (characteristic is inversely proportional to time)Manual torque boost (0 ~ 15 %), Auto torque boost
Optional (Braking unit, resistor)
[HP][kW]Capacity[kVA]*2)
FLA[A]FrequencyVoltage Voltage Frequency
10.751.92.5
4.6
008-4 015-4 022-4 037-4 055-4 075-4 110-4 150-4 185-4 220-4 300-4 370-4 450-4 550-4 750-42
1.534
4.6
32.24.56
4.8
53.76.18
4.9
7.55.59.112
7.5
107.512.216
7.7
1511
18.324
13.8
2015
22.930
14.3
2518.529.739
19.4
3022
34.345
20
40304561
50375675
60456891
755582110
10075100152
0 ~ 400 Hz380 ~ 480V*3)
3 phase 380 ~ 480V (±10%)50 ~ 60 Hz (±5%)
*1) Indicates the maximum applicable capacity when using 4 pole LS standard motor. *2) Rated capacity ( 3*V*I) is based on 220V for 200V class and 440V for 400V class. *3) Maximum output voltage will not be greater than the input voltage. Output voltage less than the input voltage can be set.*4) 0.75 ~ 3.7kW inverter have internal braking resistor inside. 5.5 ~ 75kW inverters need optional braking resistor.
Input
signa
lOu
tput s
ignal
Protective function
DisplayKeypad
Environment
√
Specifications & Wiring
06
Wiring
DB ResistorDC Bus Choke
DynamicBraking Unit
DB UNIT(OPTION)*4
DB Resistor
MOTOR
U
P1*1 P2*1 N*1
V
W
R
MCCB(OPTION)*4
DC BUS CHOKE(OPTION)*3
3ф230/460V50/60Hz
S
T
G
FX
RX
BX
RST
JOG
P1
P2
P3
CM
VR
30A
30C
30B
AXA
AXC
FM
5G
V1
I
5G
Forward Run/Stop
Reverse Run/Stop
Invert Disable
Fault Reset
Jog
Multi-function Input 1
Multi-function Input 2
Multi-function Input 3
Common Terminal
Potentiometer(1kohm, 1/2W) Shield
Factory Setting‘Speed-L‘‘Speed-M‘‘Speed-H‘
Power supply forspeed signal:+11V, 10mA
Output Frequency Meter(0 - 10V : pulse output)
Fault output relayIess than AC250V, 1AIess than DC30V, 1A
Mult-function output relay1Iess than AC250V, 1AIess than DC30V, 1AFactory setting:‘RUN‘
Speed signal input:0 ~10V
Speed signal input:4 ~ 20mA(250ohm)
Common forVR, V1, I
Speed signal Input *2
+
P N B1 B2
FM
Note) "● " display main circuit terminals, "○ " display control circuit terminals.1. The terminal configuration varies depend on the model name.
`P`terminal is available in 5.5 to 7.5kW inverters. `P1` and `P2` are available in 11 to 75kW inverters.`B1` and `B2` terminals are for braking resister or connection. `P1` and `P2` are for braking unit.
2. Analog speed command can be set by voltage, current and both of them.3. When installing the DC Reactor, the common busbar between P1 and P2 must be removed.4. 0.75 ~ 7.5kW inverters have on-board braking circuit. Braking resistor is only included for 0.75 ~ 3.7kW inverters.
11 ~ 75kW inverters need optional braking unit and resister for dynamic braking.5. Marked as “CM” for over 30kW drives.
Starvert iS5
07
Power terminal configuration
Keypad 1. LCD Keypad
Symbol FunctionRSTUVWP
P1P2B1B2NG
AC Line input (3 phase, 200~230 Vac for "-2" units and 380~480 Vac for "-4" units)
3 phase output terminals to motor
Positive DC Bus Terminals, DC Bus Choke (reactor)connection terminals. These terminals are available for 5.5 to 7.5kW inverter with optional DB unit when an application need braking torque over 30% EDPositive DC Bus Terminals, DC Bus Choke (reactor)connection terminals. These terminals are available for 11 to 22kW inverter with optional DB unit. These terminal are shorted when DB unit is not applied.Dynamic braking resistor connection terminals. These terminals are available for 0.75 to 3.7kW inverters in order to connect an external braking resistor.
Negative DC Bus terminalChassis ground (The ground terminal ("G") may be located on heat sink instead of terminal strip depend on the model type)
Control terminal configurationTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeTypeType
Starting ContactFunctionSelection
Analog/Digital
Pulse
Contact
RS232
Type SymbolP1, P2, P3
FXRX
JOGBX
RSTCMNC VRV1I
5GFM
30A,30C,30B
AXA,AXCCN3
NameMulti function input 1,2,3Forward run commandReverse run commandJog frequency reference Emergency stop
Fault resetSequence common-Frequency setting power (+12V)Frequency reference (Voltage)Frequency reference (Current)Frequency setting common terminalAnalog/digital output(For external monitoring)
Fault contact output
Multi-function outputCommunication port
DescriptionUsed for multi function input. Factory default is set to step frequency 1, 2, 3.Forward run when closed and stop when open.Reverse run when closed and stop when open.Runs at jog frequency when the jog signal is ON. The direction is set by the FX (or BX) signal.When the BX signal is ON, the output of the inverter is cut off. When the motor uses an electrical brake to stop, BX is used to cut off the output signal. When the BX signal, which does not cut off by latching, is OFF and the FX signal (or the RX signal) is ON, the motor keeps running, so be cautious.Used to release the protective status when the protective circuit is active.Used for the common terminal for contact input terminals.Not used.Used as power for the analog frequency setting. Maximum output is +12V, 100mA.Used for frequency reference and uses 0-10V for input. Input resistance is 20 k1Used for frequency reference and uses DC 4-20mA for input. Input resistance is 2501Common terminal for the analog frequency reference signal and the FM (for monitoring).Outputs one of the followings: output frequency, output current, output voltage, DC link voltage. Factory default is set to output frequency. Maximum output voltage and output current is 0-12V, 1mA. Output frequency is set to 500Hz.Activates when the protective function is operating. AC250V 1A or less, DC30V 1A or lessFault : 30A-30C short (30B-30C open)Normal : 30B-30C short (30A-30C open)Use after defining the multi-function output terminal. AC250V 1A or less, DC30V 1A or less.Use the keypad connector. Use the keypad connector for RS232 communication. Disconnect the keypad and connect the RS232-RS485 converter for RS485 communication.
Inpu
t sig
nal
Outp
ut si
gnal
Comm
.
Key/LED DescriptionMODEPROGENTUP
DOWNSHIFT/ESC
REWSTOP/RESET
FWDREV
STOP/RESETFWD
NameMode keyProgram keyEnter keyUp keyDown keyShift keyEscape keyReverse keyStop keyReset keyForward keyReverse runStop/resetForward run
The mode button moves you through the seven program groups : DRV, FUN1, FUN2, I/O, (EXT), (COM) and APP.The program button is used to go into programming mode to change data.The enter button is used to enter changed parameters.
The up and down arrows are used to move through and change data.
The button is used to move cursor across the display in a programming mode.This button is used to move the program code to DRV00 from any program code.The reverse run button is used to run the motor in reverse direction.The stop button is used to the drive from running.The reset button is used to reset faults.The forward run button is used to run the motor in forward direction.The LED blinks when th inverter accels or decels.The LED blinks when there is a fault.The LED blinks when the inverter accels or decels.
▲▼
2. LED Keypad (7-segment)Encoder knob
SETSHIFT/ESC
STOP/RESET
RUNSET
STOP/RESETRUNDRVFU1FU2I/O
EXTI/O+EXT
I/O+EXT+FU2
Encoder Knob
Set keyShift keyEscape keyStop keyReset keyRun keySetting statusStop/Fault statusRun statusDrive groupFunction1 groupFunction2 groupI/O groupSub-board groupOption-board groupApplication group
This is used to move you through seven parameter groups and parameter codes. Also, used to change data by rotating knob.This is used to go into program mode to change data and to enter the changed data.This is used to go into program mode to change data and to enter the changed data.This button is used to move cursor across the display in a programming mode.This is used to stop the inverter from running.The reset button is used to reset faults.This is used to run the inverter. The motor direction is set in DRV13.It blinks in setting mode.The LED is lit in Stop status and blinks in fault status.The LED is lit in Run status and blinks in fault status.It blinks in drive group.It blinks in Function1 group.It blinks in Function2 group.It blinks in I/O group.It blinks in Sub-board group.It blinks in Option board group.It blinks in Application group.
MODE PROG
LC-200
ENT
FWDREV
SHIFTESC
STOPRESET
PROGENT
LC-200
RUN
SHIFTESC
STOPRESET
DRV FU1 FU2 I / O EXT
Terminal Configuration, Keypad & Parameter Navigation
08
Parameter group
Parameter navigation
DriveFunction 1Function 2Input / OutputExternal boardCommunicationApplication
Parameter group LCD keypadDRVFU1
FUN2I/O
EXTCOMAPP
7-segment keypadDRV LED is lit
FU1 is litFU2 is litI/O is lit
EXT is litI/O + EXT are lit
I/O + EXT + FU2 are lit
DescriptionCommand frequency, accel/decel time, etc. Basic parameters.Max. frequency, amount of torque boost, etc. Basic function related parameters.Frequency jumps, max./min. limit of frequency etc. Application function related parameters.Multi function terminal setting, auto operation etc. Parameter needed for sequence operation.Displayed when sub-board is installed.Displayed when option board is installed.Specific application related parameters.
1. LCD Keypad
MODE
MODE
MODE
MODE
MODE
MODE
MODE
DRV T/K 0.0A00 STP 60.00Hz
FU1 Jump coad00 1
FU2 Jump coad00 30
I/O Jump coad00 1
DRV Acc. time01 10.0sec
FU1 Run prohibit03 None
FU2 last trip-101 ______
I/O V1 filter01 10ms
MODE MODE MODE MODE
DRV Dc. time02 20.0sec
FU1 Acc.Pattern05 Linear
FU2 last trip-202 ______
I/O V1voltx102 0.00V
MODE MODE MODE MODE
DRV Drive mode03 Fx/Rx-1
FU1 Dec.Pattern06 Linear
FU2 last trip-3�03 ______
I/O V1 freqy103 0.00Hz
MODE MODE MODE MODE
DRV Freq mode04 Keypad-1
FU1 Stop mode07 Decel
FU2 last trip-404 ______
I/O V1 voltx204 10.00V
MODE MODE MODE MODE
DRV Step freq-105 10.00Hz
FU1 DcStvalue08 50%
FU2 last trip-505 ______
I/O V1 freq y203 60.00Hz
MODE
DRV Fault12 - - - - - - - - - - -
MODE
FU1 Stall Level60 150%
MODE
FU2 Para.lock94 0
MODE
I/O Way1/2D60 Forward
MODE
Drive group Function1 group Function2 group I / O group
Starvert iS5
09
2. LED keypad (7-segment)
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
DRV FU1 FU2 I/O EXT
SET
SET
SET
SET
ESC
FU 1
FU 2
I/O
DRV
SET
SET
Operation methodOperation method Function Function setting
Keypad
Terminal
Keypad and Terminal
Option board
Run/Stop command and frequency are set only through the keypad.Closing FX or RX terminal performs Run/Stop. Frequency reference isset through keypadRun/Stop command and frequency are set only through the terminal.Closing FX or RX terminal performs Run/Stop. Frequency reference is set through V1 or I or V1+I terminal.
Closing Fx or RX terminal performs Run/Stop. Frequency reference is set through keypad.Operation using additional sub or option board.Sub board : SUB-A, SUB B, .. SUB-HOption board : Device Net, Synchro, Profibus DP, Digital-in, RS485, Modbus-RTU
DRV 03 : KeypadDRV 04 : Keypad
DRV 03 : Fx/Rx-1 or -2DRV 04 : V1 or I or V1+IDRV 03 : Keypad-1 or -2DRV 04 : V1 or I or V1+IDRV 03 : Fx/Rx-1 or -2DRV 04 : Keypad-1 or -2
Program Parameter Descriptions
10
1. Drive Group [DRV]
Program parameter descriptions
Code Description UnitsLCD 7-segmentKeypad Display Setting Range Factory Adjustable
LCD 7-segment Default during run
DRV-00
DRV-01DRV-02DRV-03
DRV-04
DRV-05DRV-06DRV-07DRV-08DRV-09DRV-10DRV-11DRV-12DRV-13DRV-14DRV-15DRV-20DRV-21DRV-22DRV-23DRV-24DRV-25
Output Frequency or Reference Frequency. Output Current (LCD)Acceleration TimeDeceleration TimeDrive Mode (Run/Stop method)
Frequency Mode (Freq. setting method)
Step Frequency 1Step Frequency 2Step Frequency 3Output CurrentMotor SpeedDC link VoltageUser Display selectionFault DisplayMotor Direction setCommand/output frequencyCommand/feedback frequencyFU1 Group selectionFU2 Group selectionI/O Group selectionEXT Group selectionCOM Group selectionAPP Group selection
Cmd.freq
Acc.timeDec.time
Drive mode
Freq mode
Step freq-1Step freq-2Step freq-3
CurrentSpeed
DC link VtgUser disp
FaultNot displayed Tar/Out Freq.Ref/Fdb Freq.Not displayed
F or r (DRV-13)
0 I0203
04
0506070809I 0I II 2I 3I 4I 5202 I22232425
0.01
0.10.11
1
0.01----------------
0.00 [Hz]
10.0 [sec]20.0 [sec]1 (Fx/Rx-1)
0 (keypad-1)
10.00 [Hz] 20.00 [Hz] 30.00 [Hz]
# [A]# [rpm]
# [V]-
None nOn0
# [Hz]# [Hz]
111111
Yes
YesYesNo
No
Yes-----
Yes--
YesYesYesYesYesYesYesYes
KeypadFx/Rx-1Fx/Rx-2
Keypad-1Keypad-2
V1I
V1+I
01201234
-Not available
Not available
-0 [Forward]1 [reverse]
Press[Prog/ENT] key
0 to FU1-20 (Max.freq)
0 to 60000 to 6000
FU1-22 to Fu1-20(Starting freq to Max. freq)The load current in RMSThe motor speed in rpm
The DC link voltage inside inverterSelected in FU-73 (User disp)
Command/output frequencyCommand/feedback frequency
2. Function 1 Group [FU1]FU1-00FU1-03
FU1-05
FU1-06
FU1-07[1]
FU1-08FU1-09FU1-10FU1-11FU1-12FU1-13FU1-20FU1-21FU1-22FU123[2]
FU1-24FU1-25FU1-26
FU1-27FU1-28FU1-29[3]
FU1-30FU1-31FU1-32FU1-33FU1-34FU1-35FU1-36FU1-37FU1-38FU1-39FU150[4]
aJump to desired code #Run Prevention
Acceleration Pattern
Deceleration Pattern
Stop Mode
DC Injection Braking FrequencyDC Injection Braking On-delayDC Injection Braking VoltageDC Injection Braking TimeStartingDC Injection Braking VoltageStartingDC Injection Braking TimeMaximum FrequencyBase FrequencyStarting FrequencyFrequency Limit selection
Low Limit FrequencyHigh Limit Frequency Manual/Auto Torque Boost selection
Torque Boost in Forward DirectionTorque Boost in Reverse DirectionVolts/Hz Pattern
User V/F - Frequency 1User V/F - Voltage 1User V/F - Frequency 2User V/F - Voltage 2User V/F - Frequency 3User V/F - Voltage 3User V/F - Frequency 4User V/F - Voltage 4Output Voltage AdjustmentEnergy Save Level F39Electronic Thermal selection
Jump codeRun Prev.
Acc.pattern
Dec.pattern
Stop mode
DCBr freqDCBlk timeDcbr valueDcBr timeDcSt valueDcSt timeMax freqBase freqStart freqFreq limit
F-limit LoF-limit Hi
Torque booth
Fwd boothRev boothV/F pattern
User freq 1User volt 1User freq 2User volt 2User freq 3User volt 3User freq 4User volt 4Volt control
Energy saveETH select
Not displayed3
5
6
7
89I 0I II 2I 3202 I2223
242526
272829
303I323334353637383950
11
1
1
1
0.010.01
10.11
0.10.010.010.01
1
0.010.01
1
0.011
0.011
0.011
0.011
10 (None)
0 (Linear)
0 (Linear)
0 (Decel)
5.00 [Hz]0.1 [sec]50 [%]
1.0 [sec]50 [%]
0.0 [sec]60.00 [Hz]60.00 [Hz] 0.50 [Hz]
0 (No)
0.50[Hz]60.00[Hz]0 (Manual)
2.0 [%]2.0 [%]
0 (Linear)
15 [Hz]25 [%]
30.00 [Hz]50 [%]45 [Hz] 75 [%]
60.00 [Hz]100 [%]
100.0 [%]0 [%]0 (No)
YesNo
No
No
No
NoNoNoNoNoNoNoNoNoNo
NoNoNo
NoNoNo
NoNoNoNoNoNoNoNoNoYesYes
1 to 99None
Forward PrveReverse Prve
LinerS-curveU-curveMinimumOptimum
LinerS-curveU-curveMinimumOptimum
DecelDC-brakeFree-run
Not available0120123401234012
NoYes
01
FU1-22 to 60 [Hz]0 to 60 [sec]0 to 200 [sec]0 to 60 [sec]0 to 200 [sec]0 to 60 [sec]40 to 400[Hz]30 to FU1-200.01 to 10[Hz]
FU1-22 to Fu1-25FU1-22 to Fu1-25
ManualAuto
01
0 to 15 [%]0 to 15 [%]
LinearSquare
User V/F
012
0 to FU1-200 to 100 [%]0 to FU1-200 to 100 [%]0 to FU1-200 to 100 [%]0 to FU1-200 to 100 [%]
40 to 110.0 [%]0 to 30 [%]
01
NoYes
Starvert iS5
11
2. Function 1 Group [FU1]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
FU1-51FU1-52FU1-53FU1-54FU1-55FU1-56
FU1-57FU1-58FU1-59FU1-60FU1-99
Electronic Thermal Level for 1 minuteElectronic Thermal Level for continuousElectronic Thermal Characteristic selection (Motor type)Overload Warning LevelOverload Warning Hold TimeOverload Trip selection
Overload Trip LevelOverload Trip Delay TimeStall Prevention Mode selectionStall Prevention LevelReturn Code
ETH 1minETH contMotor type
OL levelOL time
OLT select
OLT levelOLT timeStall prev.Stall level
Not display
5 I5253
545556
5758596099
111
10.11
11bit11
150 [%]100 [%]
0 (self-cool)
150 [%]10.0 [sec]1 (Yes)
180 [%]60.0 [sec]
000150 [%]
1
YesYesYes
YesYesYes
YesYesNoNoYes
self-coolForced-coo
01
FU1-52 to 200 [%]50 to FU1-51
NoYes
01
30 to 150 [%]0 to 30 [sec]
Not available [PROG/ENT]or
[SHIFT/ESC]
30 to 150 [%]0 to 60 [sec]
000 to 111 (bit set)30 to 150 [%]
3. Function 2Group [FU2]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
FU2-00 FU2-01FU2-02FU2-03FU2-04FU2-05FU2-06
FU2-07
FU2-08FU2-10[5]
FU2-11FU2-12FU2-13FU2-14FU2-15FU2-16FU2-17FU2-18FU2-19FU2-20
FU2-21
FU2-22FU2-23FU2-24FU2-25FU2-26FU2-27FU2-30
FU2-31FU2-32FU2-33FU2-34FU2-36FU2-37FU2-38FU2-39
FU2-40
Jump to desired code #Previous Fault History 1Previous Fault History 2Previous Fault History 3Previous Fault History 4Previous Fault History 5Erase Fault History
Dwell Frequency
Dwell TimeFrequency Jump selection
Jump Frequency 1 Low Jump Frequency 1 HighJump Frequency 2 Low Jump Frequency 2 HighJump Frequency 3 Low Jump Frequency 3 HighStarting rate of S curveEnding rate of curveInput/Output Phase Loss ProtectionPower ON Start selection
Restart after Fault Reset
Speed Search selectionCurrent Limit Level during Speed SearchP Gain during Speed SearchI Gain during speed searchNumber of Auto Restart AttemptDelay Time before Auto RestartRated Motor selection
Number of Motor PoleRated Motor SlipRated Motor Current in RMSNo Load Motor Current in RMSMotor EfficiencyLoad InertiaCarrier FrequencyControl Mode selection
Auto tuning selection
Jump codeLast trip-1Last trip-2Last trip-3Last trip-4Last trip-5Erase trips
Dwell freq
Dwell timeJump Freq
Jump lo 1Jump Hi 1Jump lo 2Jump Hi 2Jump lo 3Jump Hi 3Start CurveEnd curveTrip selectPower-on run
RST restart
Speed SearchSS Sup-CurrSS P-gainSS I-gainRetrynumberRetry DelayMotor select
Pole numberRated-SlipRated-CurrNoload-CurrEfficiencyInertia rateCarrier freqControl mode
Auto tuning
Not displayedI23456
7
8I 0
I II 2I 3I 4I 5I 6I 9I 9I 920
2 I
22232425262730
3 I32333436373840
4 I
1
1
1
0.01
0.11
0.010.010.010.010.010.01
11-1
-1111
0.11
10.01
111111
1
300 (None)
0 (No)
5.00 [Hz]
0.0 [sec]0 (No)
10.00 [Hz]15.00 [Hz]20.00 [Hz]25.00 [Hz]30.00 [Hz]35.00 [Hz]
40 [%]40 [%]
000 (No)
0 (No)
0000100 [%]
1001000
01.0 [sec]
[6]
4[7]
05 [kHz]0 [V/F]
0 (No)
Yes
-
Yes
No
NoNo
NoNoNoNoNoNoNoNoYesYes
Yes
NoYesYesYesYesYesNo
NoNoNoNoNoNoYesNo
No
1 to 99
NoYes
NoYes
NoYesNoYes
0.75kW1.5kW2.2kW3.7kW5.5kW7.5kW11.0kW15.0kW18.5kW22.0kW30kW37kW45kW55kW75kW
V/FSlip comp
PIDSensorless
NoYes
Not available
01
01
0101
01234567891011121314
012301
By pressing[PROG]and[▲ ]key, the frequency, current, operation
status at the time of faultcan be seen.
FU1-22 to FU1-20(starting freq.to Max.freq.)
0 to 10 [sec]
Fu1-22 to FU2-12Fu1-11 to FU2-20Fu1-22 to FU2-14Fu1-13 to FU2-20Fu1-22 to FU2-16Fu1-15 to FU2-20
0 - 100 [%]0 - 100 [%]
00 to 11 (bit set)
0000 to 1111 (bit set)80 to 200 [%]0 to 300000 to 30000
0 to 100 to 60 [sec]
2 to 120 to 10 [Hz]1 to 200 [A]
0.5 to 200 [A]70 to 100 [%]
0 to 1[8] 1 to 15 [kHz]
Program Parameter Descriptions
12
3. Function 2Group [FU2]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
FU2-41FU2-42FU2-43FU2-44FU2-45FU2-46FU2-47
FU2-48FU2-49
FU2-50
FU2-51[10]
FU2-52FU2-53FU2-54FU2-55FU2-56FU2-57
FU2-58FU2-59FU2-60FU2-69FU2-70
FU2-71
FU2-72FU2-73
FU2-74FU2-75
FU2-76[11]FU2-79FU2-81[12]FU2-82FU2-83FU2-84
FU2-85FU2-86FU2-87FU2-88FU2-89FU2-90FU2-91
FU2-92
FU2-93
FU2-94FU2-99
Stator resistanceLeakage inductanceStator inductanceRotor time constant P gain for sensorless modeI gain for sensorless mode PID operation selection
PID feed forward gainPID Reference mode selection
PID Output direction selection
PID feedback Signal selection
P Gain for PID ControlI Gain for PID ControlD Gain for PID ControlLimit (+) Frequency for PID ControlLimit (-) Frequency for PID ControlPID Output inverter
PID Output gain scalePID P2 scaleP gain scaleSpeed Acc/dec turning pointReference Frequency for Accel and Decel
Accel/Decel Time scale
Power On DisplayUser Display selection
Gain for Motor Speed DisplayDB (Dynamic Braking) Resistor Mode selection
Duty of Dynamic Braking ResistorSoftware Version2nd Acceleration Time2nd Deceleration Time2nd Base Frequency2nd Pattern
2nd Forward Torque Boost2nd Reverse Torque Boost2nd Stall Prevention Level2nd Electronic Thermal Level for 1 minute2nd Electronic Thermal Level for continuous2nd Rated Motor CurrentRead Parameters into Keypad from inverter
Write Parameter to inverter from Keypad
Initialize Parameter
Parameter Write ProtectionReturn Code
RsLsigmaLsTrSL P-gainSL I-gainProc PI mode
PID F- gainPID Ref
PID Ref Mode
PID F/B
PID P-gainPID I-gainPID D-gainPID+limitPID-limitPID Out Inv.
PID Out ScalePID P2-gainP-gain Scale
Acc/Dec freq
Time scale
PowerOn dispUser disp
RPM factorDB mode
DB %EDS/W version2nd Acc time2nd Dec time2nd Basefreq2nd V/F
2nd F-boost2nd R-boost2nd Stall2nd ETH 1min2ndETH cont2nd R-CurrPara. Read
Para. Write
Para. Init
Para. LockNot display
41424344454647
4849
50
51
525354555657
5859606970
7 I
7273
7475
76798 I828384
8586878889909 I
92
93
9499
0.0010.0010.001
1111
0.1[%]1
111
11
0.010.01
10.1 [%]
0.1 [%]0.1 [%]
1
1
1
11
11
-0.10.10.01
10.1
0.1111
0.111
1
1
1-
Decided depending on motor capacityDecided depending on motor capacityDecided depending on motor capacityDecided depending on motor capacity
10001000
0
0.0[%]0 (Freq mode)
0 (Ramp freq)
0 (I)
300.0 [%]30.0 [sec]
0 (No)60.00 [Hz]60.00 [Hz]
0 (No)
100.0 [%]100.0 [%]100.0 [%]
0 (Max.frq)
0 (0.01[sec])
00 (Voltage)
100 [%]1 (Int.DB-R)
10 [%]Ver.1.055.0 [sec]10.0 [sec]60.0 [Hz]0 (Liner)
2.0 [%]2.0 [%]150 [%]150 [%]100 [%]3.6 [A]0 (No)
0 (No)
0 (No)
01
NoNoNoYesYesNoNo
YesNo
No
No
YesYesYesYesNoNo
NoNoYes
Yes
Yes
Yes
YesYes
-YesYesNoNoNo
NoNoYesYesNoNoNo
No
Yes
YesYes
Decided depending on motor capacityDecided depending on motor capacityDecided depending on motor capacityDecided depending on motor capacity
0 to 32760 to 3276
0 (No)1 (Yes)
0~999.9[%]
0 to 999.9 [%]0to 32.0 [sec]
0 to 999.9 [msec]0 to FU1-200 to FU1-20
0.1 to 999.9 [%]0.0 to 999.9 [%]0.0 to 100 [%]
0 to 12
1 to 1000 [%]
0 to 30 [%]ver.1.05
0 to 6000 [sec]0 to 6000 [sec]30 to FU1-20
0 to 15 [%]0 to 15 [%]
30 to 150 [%]FU2-89 to 200 [%]
50 to FU2-88 (maximum150%)1 to 200 [A]
0 to 255
4. Input / Output [I/O]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
I/O-00I/O-01I/O-02I/O-03
I/O-04I/O-05
Jump to desired code#Filtering Time Constant for V1 Signal InputV1 Input Minimum VoltageFrequency corresponding to V1 Input Minimum Voltage V1 Input Maximum VoltageFrequency corresponding to V1 Input Minimum Voltage
JumpV1 Filter
V1 volt x1V1 freq y1
V1 volt x2V1 freq y2
Not DisplayedI23
45
11
0.010.01
0.010.01
110 [ms]0.00 [V]0.00 [Hz]
10.00 [V]60.00 [Hz]
YesYesYesYes
YesYes
1 to 99 Not available0 to 9999 [ms]
0 to 10 [V]0 to FU1-20 (Max.freq)
0 to 10 [V]0 to FU1-20 (Max.freq)
Freq. ModeKeypad-1Keypad-2
V1I
V1+IRamp freqTarget freq
IV1V2
NoYes
Max freqDelta freq0.01 [sec]0.1 [sec]1 [sec]
VoltageWatt
Torque
NoneInt. DB-RExt. DB-R
LinerSquare
User V/F
NoYesNoYesNo
All groupDRVFU1FU2I/O
EXT
Not available
01234501012
01
01012
012
012
012
01010123456
[PROG/ENT]or
[SHIFT/ESC]
Starvert iS5
13
4. Input / Output [I/O]
Code Description UnitsLCD 7-segmentKeypad Display Setting Range Factory Adjustable
LCD 7-segment Default during run
I/O-06I/O-07I/O-08
I/O-09I/O-10
I/O-11
I/O-12
I/O-13I/O-14I/O-15I/O-16I/O-17
I/O-20I/O-21I/O-22I/O-23I/O-24I/O-25I/O-26I/O-27I/O-28I/O-29I/O-30I/O-31I/O-32I/O-33I/O-34I/O-35I/O-36I/O-37I/O-38I/O-40
I/O-41I/O-42I/O-43I/O-44
Filtering Time Constant for V1 Signal Input Input Minimum CurrentFrequency corresponding to V1 InputMinimum VoltageI Input Minimum CurrentFrequency corresponding to I Input Maximum CurrentCriteria for Analog Input Signal Loss
Multi-function Input Terminal `P1`define
Multi-function Input Terminal `P2`defineMulti-function Input Terminal `P3`defineTerminal Input StatusTerminal Output StatusFiltering Time Constant for Multi-functionInput TerminalJog Frequency settingStep Frequency 4Step Frequency 5Step Frequency 6Step Frequency 7Acceleration Time 1 for Step FrequencyDeceleration Time 1 for Step FrequencyAcceleration Time 2Deceleration Time 2Acceleration Time 3Deceleration Time 3Acceleration Time 4Deceleration Time 4Acceleration Time 5Deceleration Time 5Acceleration Time 6Deceleration Time 6Acceleration Time 7Deceleration Time 7FM (Frequency Meter) Output selection
FM Output AdjustmentFrequency Detection LevelFrequency Detection BandwidthMulti-function AuxiliaryContact Output define(AXA, AXC)
I filterV1 curr x1V1 freq y1
V1 curr x2I freq y2
Wire broken
P1 define
P2 defineP3 defineIn statusOut statusTi Fit Num
Jog freqStep freq-4Step freq-5Step freq-6Step freq-7Acc time-1Dec time-1Acc time-2Dec time-2Acc time-3Dec time-3Acc time-4Dec time-4Acc time-5Dec time-5Acc time-6Dec time-6Acc time-7Dec time-7FM mode
FM adjustFDT freqFDT bandAux mode
678
9I0
I I
I2
I3I4I5I6I7
202I2223242526272829303 I3233343536373840
4 I424344
10.010.01
0.010.01
1
1
11--1
0.01
0.10.10.10.10.10.10.10.10.10.10.10.10.10.11
10.010.01
1
10 [ms]4.00 [mA]0.00 [Hz]
20.00 [mA]60.00 [Hz]
0 (None)
0 (Speed-L)
1 (Speed-M)2 (Speed-H)000000000
000015
10.00 [Hz]40.00 [Hz]50.00 [Hz]40.00 [Hz]30.00 [Hz]20.0 [sec]20.0 [sec]30.0 [sec]30.0 [sec]40.0 [sec]40.0 [sec]50.0 [sec]50.0 [sec]40.0 [sec]40.0 [sec]30.0 [sec]30.0 [sec]20.0 [sec]20.0 [sec]
0 (Frequency)
100 [%]30.00 [Hz]10.00 [Hz]12 (run)
YesYesYes
YesYes
Yes
Yes
YesYes
--
Yes
YesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYes
YesYesYesYes
0 to 9999 [ms]0 to20 [ms]
0 to FU1-20 (Max.freq)
0 to20 [ms]0 to FU1-20
Same as aboveSame as above
000000000 to 111111110000 to 1111
2 to 50
FU1-22 to FU1-20 (Starting freq toMax, freq)
0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]0 to 6000 [sec]
10 to 200 [%]0 to FU1-200 to FU1-20
Nonehalf x1
below x1Speed -LSpeed -MSpeed -HXCEL-LXCEL-MXCEL-HDc-brake2nd FuncExchange-Reverse-
UpDown3-Wire
Ext Trip-AExt Trip-B-Reverse-Open-loopMain-DriveAnalog holdXCEL stop-Reverse-
SEQ-LSEQ-MSEQ-HManualGo step
Hold stepTrvOff. Lo
Trv Off. HiInterlock1Interlock2Interlock3Interlock4
FrequencyCurrentVoltage
DC link voltage
FDT-1FDT-2FDT-3FDT-4FDT-5
OLIOLStallOV
01201234567891011121314151617181920212223242526272829303132
0123
012345678
Program Parameter Descriptions
14
4. Input / Output [I/O]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
I/O-44
I/O-45I/O-46[13]I/O-47
I/O-48
I/O-49I/O-50
I/O-51I/O-52I/O-53[14]I/O-54I/O-55I/O-56
I/O-57I/O-58I/O-59I/O-60
I/O-99
Fault Output Relay setting (30A,30B,30C)Inverter NumberBaud Rate
Operation selection at loss of Freq. Reference
Waiting Time after Loss of Freq. ReferenceAuto (Sequence)Operation selection
Sequence Number selectionThe Number of steps of Sequence Number#1st Step Frequency of SequenceTransient Time to 1st Step of SequenceSteady Speed Time at 1st Step of SequenceMotor Direction of 1st Step of Sequence 1
1st Step of Frequency of Sequence 2Transient Time to 1st Step of Sequence 2Steady Speed Time at 1st Step of Sequence 2Motor Direction of 1st Step of Sequence 2
Return Code
Relay modeInv No.Baud rate
lost command
Time outAuto mode
Seq seletStep numberSeq1/1FSeq1/1TSeq1/1SSeq1/1D
Seq1/1FSeq1/1TSeq1/1SSeq1/1D
Not Disp layed
454647
48
4950
5 I5253545556
57585960
99
-11
1
0.11
11
0.010.10.1-
0.010.10.11
1
010 [bit]1
3 (9600bps)
0 (None)
0.1 [sec]
0 (None)12
11.00 [Hz]1.1 [sec]1.1 [sec]
1 (Forward)21.00 [Hz]1.1 [sec]1.1 [sec]
1 (Forward)1
YesYesYes
Yes
YesNo
YesYesYesYesYesYes
YesYesYesYes
Yes
000 to 111 (bit set)1 to 32
0.1 to 120[sec]
1 to 51 to 8
0.01 to FU1-20 (Max.freq.)0.1 to 6000 [sec]0.1 to 6000 [sec]
0.01 to FU1-20 (Max.freq.)0.1 to 6000 [sec]0.1 to 6000 [sec]
LVOHLost
CommandRunStop
1200bps2400bps4800bps9600bps19200bps
NoneFreerun
Stop
NoneAuto-AAuto-B
ReverseForward
ReverseForward
Not available
910111213
01234012
012
01
01
[PROG/ENT]or
[SHIFT/ESC]
5. External Group [EXT]
Code Description UnitsLCD 7-segmentKeypad Display Setting Range Factory Adjustable
LCD 7-segment Default during run
EXT-00EXT-01
EXT-02
Jump to desired code #Sub board Type display
Multi-function Input Terminal `P4`define
Jump code
Sub B/C
Not displayedI
2
11
1
10 (None)
3 (XCEL-L)
YesAutomatically
set
Yes
0 to 99None
SUB-ASUB-BSUB-CSUB-DSUB-ESUB-FSUB-GSUB-H
Speed -LSpeed -MSpeed -HXCEL-LXCEL-MXCEL-HDc-brake2nd FuncExchange-Reversed-
UpDown3-Wire
Ext Trip-AExt Trip-B-Reversed-Open-loopMain-DriveAnalog holdXCEL stop-Reversed-
SEQ-LSEQ-MSEQ-HManualGo step
Hold stepTrv Off. LoTrv Off. Hi
Not available012345678012345678910111213141516171819202122232425262728
EXT group appears only when the corresponding option boards are installed.
Starvert iS5
15
5. External Group [EXT]
Code Description UnitsLCD 7-segmentKeypad Display Setting Range Factory Adjustable
LCD 7-segment Default during run
EXT-02
EXT-03EXT-04EXT-05
EXT-06EXT-07EXT-08
EXT-09EXT-10
EXT-14
EXT-15
EXT-16EXT-17EXT-18EXT-19
EXT-20EXT-21
EXT-22EXT-23EXT-24EXT-30
EXT-31EXT-32EXT-34
EXT-35EXT-40
EXT-41EXT-42
EXT-43EXT-99
Multi-function Input Terminal `P5`defineMulti-function Input Terminal `P6`defineV2 Mode selection
Filtering Time Constant for V2 Signal InputV2 Input Minimum VoltageFrequency corresponding to V2 Input Minimum VoltageV2 Input Maximum VoltageFrequency corresponding to V2 InputMaximum VoltageUsage of Pulse Input Signal
Pulse Input Signal selection
Encoder Pulse NumberFiltering Time Constant for Pulse Input Signal Pulse Input Minimum FrequencyFrequency Output corresponding to PulseInput Minimum FrequencyPulse Input Maximum FrequencyFrequency Output corresponding to PulseInput Maximum FrequencyP-Gain for `Sub-B`I-Gain for `Sub-B`Slip P-Gain for Frequency `Sub-B`boardMulti-function Output Terminal `Q1` define
Multi-function Output Terminal `Q2` defineMulti-function Output Terminal `Q3` defineLM (Load Meter)Output selection
LM (Load Meter) AdjustmentAM1 (Analog Meter1)Output selection
AM1 (Analog Meter1)Output AdjustmentAM2 (Analog Meter2)Output selection
AM2 (Analog Meter2)Output AdjustmentReturn Code
P5 defineP6 defineV2 mode
V2 filterV2 volt x1V2 freq y2
V2 volt x2V2 freq y2
F mode
F pulse set
F pulse numF filterF pulse x1F freq y1
F pulse x2F freq y2
PG P-gainPG I-gainPG Slip freqQ1 define
Q2 defineQ3 defineLM mode
LM adjustAM1 mode
AM1 adjustAM2 mode
AM2 adjustNot displayed
345
678
9I 0
I 4
I 5
I 6I 7I 8I 9
202 I
22232430
3 I3234
3540
4 I42
4399
--
10.010.01
0.010.01
-
-
11
0.010.01
0.010.01
111-
-
4 (XCEL-M)5 (XCEL-H)
0 (None)
10 [ms]0.00 [V]0.00 [Hz]
10.00 [V]60.00 [Hz]
0 (None)
0 (A+B)
102410 [ms]
0.00 [kHz]0.00 [Hz]
10.00 [kHz]60.00 [Hz]
3000300
100 [%]0 (FDT-1)
1 (FDT-2)2 (FDT-3)1 (Current)
100 [%]0 (Frequency)
100 [%]3 (DC link Vtg)
100 [%]1
YesYesNo
YesYesYes
YesYes
No
Yes
NoYesYesYes
YesYes
YesYesYesYes
YesYesYes
YesYes
YesYes
YesYes
Same as aboveSame as above
0 to 10000 [ms]0 to 10 [V]
0 to FU1-20 (Max.freq.)
0 to 10 [V]0 to FU1-20 (Max.freq.)
360 to 40960 to 9999 [ms]0 to 100 [kH]
0 to FU1-20 (Max.freq.)
0 to 100 [kHz]0 to FU1-20 (Max.freq.)
0 to 99990 to 99990 to 20[%]
Same as aboveSame as above
100 to 200 [%]
100 to 200 [%]
100 to 200[%]
Interlock1Interlock2Interlock3Interlock4
NoneOverride
Reference
NoneFee-backReference
A+BA
FDT-1FDT-2FDT-3FDT-4FDT-5
OLIOLStallOVLVOH
Lost CommandRunStop
SteadyINV line
COMM lineSearch
Step pulseSeq pulse
ReadyTrv. ACCTrv. DEC
MMC
FrequencyCurrentVoltage
DC link Vtg
FrequencyCurrentVoltage
DC link Vtg
FrequencyCurrentVoltage
DC link Vtg
Not available
29303132
012
01201
0123456789
1 011121314151617181920212223
0123
0123
0123
[PROG/ENT]or
[SHIFT/ESC]
EXT group appears only when the corresponding option boards are installed.
Program Parameter Descriptions
16
6. Communication Group [COM]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
COM-00COM-01
COM-02
COM-03COM-04
COM-05COM-10COM-11
COM-12
COM-13
COM-17COM-20COM-30COM-31COM-32COM-33COM-34COM-35COM-36COM-37COM-38COM-40COM-41COM-42COM-43COM-44COM-45COM-46COM-47COM-48COM-52COM-99
Jump to desired code #Option board Type display
Option mode
Option versionDigital (Binary)option input mode selection
Digital (Binary)input filterDevice Net IDDevice Net baud rate
Device Net output impedence
Device Net input impedence
PLC station IDProfibus-DP IDNumber of outputOutput 1Output 2Output 3Output 4Output 5Output 6Output 7Output 8Number of inputInput 1 Input 2Input 3Input 4Input 5Input 6Input 7Input 8Modbus-RTU modeReturn Code
Jump codeOpt B/D
Opt Mode
Opt VersionD-in Mode
Digital FtrMAC IDBaud Rate
Out Instance
In Instance
Station IDProfi MAC IDOutput NumOutput 1Output 1Output 1Output 1Output 1Output 1Output 1Output 1Input NumInput 1Input 2Input 3Input 4Input 5Input 6Input 7Input 8ModBus Modenot displayed
Not DisplayedI
2
34
5I 0I I
I 2
I 3
I 720303I32333435363738404 I424344454647485299
11
1
1
111
1
1
111--------1----------
10 (None)
0 (None)
0 (8BitBin)
150
0 (125 bps)
0 (20)
0 (70)
113
000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)
2000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)000A (HEX)
ModBus-RTU1
YesYes
No
NoYes
YesYesYes
Yes
Yes
YesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYesYes
Option version
0 to 500 to 63
0 to 630 to 127 0 to 8
0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)
0 to 80000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)0000 to 57FF (HEX)
Mofibus-RTU
0 to 99None
Device NetSynchroPLC-GF
Profibus-DPDigital-inRS485
Mofibus-RTUNone
CommandFrequencyCmd+Freq
8bit Bin8 BCD 1%8 BCD 1Hz12 Bit Bin
12 BCD 0.1%12 BCD 0.1Hz12 BCD 1Hz
125kbps250kbps500kbps
20211001017071110111
Not available
Not available012345670123
1234567
01201230123
[PROG/ENT]or
[SHIFT/ESC]
7. Application Group [APP]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
APP-00APP-01
APP-02APP-03APP-04APP-05APP-06APP-07APP-08APP-09APP-10APP-11APP-12APP-13APP-14
Jump to desired code #Application mode
Traverse operation bandTraverse scramble bandTraverse acceleration timeTraverse deceleration timeTraverse offset HighTraverse offset LowNo. of Aux. Motor in runningStart aux. MotorOperation time display by auto-changeStarting frequency of Aux. Motor 1Starting frequency of Aux. Motor 2Starting frequency of Aux. Motor 3Starting frequency of Aux. Motor 4
Jump codeApp Mode
Trv. AmpTrv. ScrTrv Acc TimeTrv Dec TimeTrv Off HiTrv Off LoAux Mot RunStart AuxAuto Op TimeStart freq 1Start freq 2Start freq 3Start freq 4
Not DisplayedI
23456789I 0I II 2I 3I 4
11
0.10.10.10.10.10.1-1
0.010.010.010.010.01
10 (None)
0.0 [%]0.0 [%]
2.0 [sec]3.0 [sec]0.0 [%]0.0 [%]
#1#
49.99 [Hz]49.99 [Hz]49.99 [Hz]49.99 [Hz]
YesNo
YesYesYesYesYesYes
-Yes
-YesYesYesYes
0 to 99None
TraverseMMC
DRAW
Not available0123
0.0 to 20.0 [%]0.0 to 50.0 [%]
0.1 to 6000 [sec]0.1 to 6000 [sec]0.0 to 20.0 [%]0.0 to 20.0 [%]
#1 to 4
#0 to FU1-20 (Max.freq)0 to FU1-20 (Max.freq)0 to FU1-20 (Max.freq)0 to FU1-20 (Max.freq)
Starvert iS5
17
7. Application Group [APP]Code Description UnitsLCD 7-segment
Keypad Display Setting Range Factory AdjustableLCD 7-segment Default during run
APP-17APP-18APP-19APP-20APP-21APP-22
APP-23APP-24APP-25APP-26APP-27APP-28APP-29
APP-30APP-31APP-32
APP-33
Starting frequency of Aux. Motor 3Starting frequency of Aux. Motor 4Aux.Motor starting delay timeAux.Motor stop delay timeNumber of Aux. MotorBypass selection
Sleep delaySleep frequencyWakeup levelAuto change mode selectionAuto change timeAuto change levelInterlock selection
Actual value displayActual value percentageDraw mode selection
Draw percentage selection
Stop freq 3Stop freq 4Aux start DTAux stop DTNbr Aux`sRegul Bypass
Sleep DelaySleep FreqWakeup levelAutoCh_ModeAutoCh_intvAutoCh_Mode levelInter-lock
Actal ValueActal PercDraw Mod
DrawPerc
I 7I 8I 9202 I22
23242526272829
303 I32
22
0.010.010.10.111
0.10.010.11
00 : 010.11
--1
0.1
15.00 [Hz]15.00 [Hz]60.00 [sec]60.00 [sec]
40 (None)
60.00 [sec]19.00 [Hz]35.0 [%]
172:00
20.0 [%]0 (None)
##
0( None)
00.0 [%]
YesYesYesYesYesYes
YesYesYesYesYesYesYes
--
Yes
Yes
0 to FU1-20 (Max.freq)0 to FU1-20 (Max.freq)
0.0 to 9999 [sec]0.0 to 9999 [sec]
0 to 4
0.0 to 9999 [sec]0 to FU1-20 (Max.freq)
0.0 to 100.0 [%]0 to 2
00:00 to 99:000.0 to 100.0 [%]
##
0.0 to 150.0 [%]
NoneYes
NoneYes
NoneV1_DrawI_Draw
V2_Draw
01
0
10123
Code Function Description LCD 7-segmentKeypad Display Sub-Board Type
Sub-A Board Sub-A Board Sub-C Board EXT-01EXT-02EXT-03EXT-04EXT-05EXT-06EXT-07EXT-08
EXT-09EXT-10
EXT-14EXT-15EXT-16EXT-17EXT-18EXT-19
EXT-20EXT-21
EXT-22EXT-23EXT-24EXT-30EXT-31EXT-32EXT-34EXT-35EXT-40EXT-41EXT-42EXT-43
Sub-board selectionMulti-function Input Terminal `P4`Multi-function Input Terminal `P5`Multi-function Input Terminal `P6`V2 Mode selectionFiltering Time Constant for V2 Input SignalV2 Input Minnmum VoltageFrequency corresponding to V2 Input Minnmum VoltageV2 Input Maximum VoltageFrequency corresponding to V2 Input Maximum VoltageUsage for Pulse Input SignalPulse Input Signal selectionEncoder Pulse selectionFiltering Time Constant for pulse Input SignalPulse Input Minimum FrequencyFrequency Output corresponding to PulseInput Minimum FrequencyPulse Input Maximum FrequencyFrequency Output corresponding to PulseInput Minimum FrequencyP-Gain for PG OptionI-Gain for PG OptionSlip Frequency for PG OptionMulti-function Output Terminal `Q1`Multi-function Output Terminal `Q2`Multi-function Output Terminal `Q3`LM (Load Meter) Output selectionLM (Load Meter) Output AdjustmentAM1 (Analog Meter1) Output selectionAM1 (Analog Meter1) Output AdjustmentAM2 (Analog Meter2) Output selectionAM2Analog Meter2) Output Adjustment
Sub B/DP4 defineP5 defineP6 defineV2 modeV2 filterV2 volt x1V2 freq y1
V2 volt x2V2 freq y2
F modeF pulse setF pulse numF filterF pulse x1f freq y1
F pulse x2f freq y2
PG P-gainPG I-gainPG Slip freqq1 defineq2 defineq3 defineLM modeLM adjustAM1 modeAM1 adjustAm2 modeAM2 adjust
I2345678
9I 0
I 4I 5I 6I 7I 8I 9
202 I
222324303 I323435404 I4243
●●●●●●●●
●●
●●●●●
●
●●●●●●
●●
●●●
●●●●●●●●
●●
●
●●●●
Note)Sub-Board Selection Guide according to its Function
[1] Code FU1-08 through FU1-11 appears only when FU1-07 is set at ‘DC-brake‘.[2] Code FU1-24 through FU1-25 appears only when FU1-23 is set at ‘Yes‘.[3] Code FU1-30 through FU1-37 appears only when FU1-29 is set at ‘User V/F‘.[4] Code FU1-51 through FU1-53 appears only when FU1-50 is set at ‘Yes‘.[5] Code FU2-11 through FU2-16 appears only when FU2-10is set at ‘Yes‘.[6] The rated motor is automatically set according to the inverter model name. If different motor is used, set the rated motor capacity connected.[7] This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value as the motor.[8] The setting range of carrier frequency is decided depending on drives’ capacity (over 30kW).[9] This value is automatically entered according to the rated motor set in FU2-30. If different, set the correct value as the motor.[10] Code FU2-47 through FU2-60 appears only when FU2-39 is set at ‘PID‘.[11] Code FU2-76 appears only when FU2-75 is set at ‘Ext.DB-R‘.[12] Code FU2-81 through FU2-90 appears only when one of I/O-12 ~ I/O-14 is set at ‘2nd function‘.[13] Code/O-46 through I/O-49are used in Option Board like RS485, Device Net and F-net etc.[14] The ‘Seq#‘ of code I/O-53 through I/O-60 varies according to the sequence number selected in I/O-51.
The parameter code may be extended to I/O-84 dependon the number of steps set in I/O-52 because the steps can be set up to 8.
Dimension
18
Dimension (mm)
MODE PROG
LC-200
ENT
FWDREV
SHIFTESC
STOPRESET
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
PROGENT
LC-200
RUN
SHIFTESC
STOPRESET
DRV FU1 FU2 I / O EXT
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
W1W2
6
H17.
5
D1
H2
MODE PROG
LC-200
ENT
FWDREV
SHIFTESC
STOPRESET
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
LC-200SHIFTESC
PROGENT RUNSTOP
RESET
DRV FU1 FU2 I / O EXT
H1
W1W2
6
D1
7.5
H2Inverter
SV008iS5-2/4SV015iS5-2/4SV022iS5-2/4SV037iS5-2/4SV055iS5-2/4SV075iS5-2/4
W1
150150150150200200
W2
130130130130180180
H1
284284284284355355
H2
269269269269340340
D2
156.5156.5156.5156.5182.5182.5
InverterSV110iS5-2/4SV150iS5-2/4SV185iS5-2/4SV220iS5-2/4
W1
250250304304
W2
230230284284
H1
385385460460
H2
370370445445
D2
201201234234
1. SV008iS5-2 SV015iS5-2 SV022iS5-2 SV037iS5-2 SV055iS5-2 SV075iS5-2 SV008iS5-4 SV015iS5-4 SV022iS5-4 SV037iS5-4 SV055iS5-4SV075iS5-4
Class Type W1 W2 W3 H1 H2 D1 D2
200-230V
380-480V
SV300iS5-2 375 360 275 615 593.5 277.5 230.5SV370iS5-2 375 360 275 615 593.5 277.5 230.5SV450iS5-2 375 360 275 780 758.5 300.7 230.5SV550iS5-2 375 360 275 780 758.5 300.7 230.5SV300iS5-4 350 319.2 270 680 662 311.2 256.6SV370iS5-4 350 319.2 270 680 662 311.2 256.6SV450iS5-4 375 359.6 275 780 760.5 329 259SV550iS5-4 375 359.6 275 780 760.5 329 259SV750iS5-4 375 359.6 275 780 760.5 329 259
(unit : mm)
(unit : mm)
(unit : mm)
2. SV110iS5-2 SV150iS5-2 SV185iS5-2 SV220iS5-2 SV110iS5-4 SV150iS5-4 SV185iS5-4 SV220iS5-4
3. SV300iS5-2 SV370iS5-2 SV450iS5-2 SV550iS5-2 SV300iS5-4 SV370iS5-4 SV450iS5-4 SV550iS5-4 SV750iS5-4
MODE PROG
LC-200
ENT
FWDREV
SHIFTESC
STOPRESET
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
CAUTION
Read the manual and follow the safety instruction before installation or operationDo not the power supply to the drive output terminal (U, V, W)Before opening the cover, disconnect all power and wait at least 3 minutes untill DC bus capacitors discharge.`Risk of Electric Shock`-more than one disconnect switch is required to de -energize the equipment before servicing.
LC-200SHIFTESC
PROGENT RUNSTOP
RESET
DRV FU1 FU2 I / O EXT
H1
W1W2
6
D1
7.5
H2
Starvert iS5
19
Options
Internal Installation
External Installation
Option Name
Sub Board
Option Board
Keypad
Remote Cable
Dynamic Braking
Description
Sub-A Board (Extended I/O)
Sub-B Board (speed Feedback)
Sub-C Board (Extended I/O)
Device Net
PLC Communication (F-Net)
RS-485
Profi-Bus
ModBus-RTU
LCD
LED (7-segment)Remote CableDB ResistorDB Unit
Extended I/O module3 multi-function inputs (P4, P5, P6)3 multi-function outputs (Q1, Q2, Q3)Auxiliary analog frequency reference (V2)Lm (Load meter) Output (0 ~ 10V)Encoder pulse input-Speed feedback (AOC, BOC /A+, A-, B+ B-)Encoder pulse output (FBA, FBB)Extended I/O module3 multi-function inputs (P4, P5, P6)1 multi-function outputs (Q1)Isolated auxiliary analog frequency reference (V2)2 Isolated analog meter output (AM1.AM2)Embedded DeviceNet protrolCan ControllerInverter Connection : Max.64Input Voltage : DC 11 ~25VBaud Rate : 125, 250, 500k bpsCSMA/CD-NBA methodConnection with Fnet communication module of GLOFA PLCInverter Connection : Max.64Baud Rate : Max. 1M bpsToken methodRS-485 CommunicationInverter Connection : Max.32Baud Rate : Max. 19200 bpsConnection to ProfiBus networkDevice Type : Profibus Dp SlaveInverter Connection : Max. 64Baud Rate : Max. 12M bpsModBus-RTU CommunicationInverter Connection : Max. 32Baud Rate : Max.19200bps32 Character displayDownload and Upload from the keypad6 digit 7-segment display2n, 3m, 5m long keypad cables for separate keypad instaiiation.Enables inverter to decelerate rapidlyDB units are provided as an option for 15~75kW inverters
88.5
172
125150
12.512.5
3.5
Dynamic Braking Unit
WRINO
183
192
Dynamic braking (DB)unit
Max. DC Input VoltageApplication Motor [kW]DB Resistor Wattage [kW]*
Resistor Value [1]Average Braking TorqueEnable Duty (ED)Output SignalProtectionEnvironment Ambient Temp.HumidityAltitudeCooling MethodInstallation
Model Name SV150DBU-2DC400V
15 202.4 2.415 10
150%50%
SV220DBU-2DC400V
25 303.65
150%50%
SV370DBU-2DC400V
30 376.4 6.4
4.2100%
SV550DBU-4DC400V
45 559.6 9.6
2.8100%10%
SV150DBU-4DC800V
15 2022.44030150%10%
SV220DBU-4DC800V
25 303.620
150%10%
SV370DBU-4DC800V
30 376.416.9
150%10%
SV550DBU-4DC800V
45 559.611.4
100%10%
SV750DBU-4DC800V
7512.88.4
100%10%
Heat sink over-heat signal outputHeat sink over-heat output cut-off
-10˚C ~ 40˚CBelow 90% Relative Humidity (Non Condensing)
Less than 3,300ft (1,000m) without deratingSelf-cooling
Avoid corrosive gas, oil mist, flammable gas and dust
*This resister wattage is based on 150% braking torque and 5% ED. Double the wattage in case of using with 10% ED application.
20
1. Internal (built-in) resistorsThe DB resistors are built-in for 0.75 ~ 3.7kW models.
*Above table is based on 100% braking torque
Dynamic braking (DB)unit
Peripheral Devices
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2
Model Name kW0.75 1.52.23.7
0.751.52.23.7
Internal DB Resistor200 1, 100Watt100 1, 100Watt60 1, 100Watt40 1, 100Watt
900 1, 100Watt450 1, 100Watt300 1, 100Watt200 1, 100Watt
ED / Continuous Braking time3% / 5seconds3% / 5seconds2% / 5seconds2% / 5seconds3% / 5seconds3% / 5seconds2% / 5seconds2% / 5seconds
2.External (optional) resistors
*Above table is based on 100% braking torque
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV055iS5-2SV075iS5-2SV110iS5-2SV150iS5-2SV185iS5-2SV220iS5-2SV300iS5-2SV370iS5-2SV450iS5-2SV550iS5-2SV008iS5-4SV015iS5-4SV022iS5-4SV037iS5-4SV055iS5-4SV075iS5-4SV110iS5-4SV150iS5-4SV185iS5-4SV220iS5-4SV300iS5-4SV370iS5-4SV450iS5-4SV550iS5-4SV750iS5-4
Model Name kW
0.751.52.23.75.57.51115
18.52230374555
0.751.52.23.75.57.51115
18.5223037455575
DB Resistor (100% Braking Torque)
200 1, 100Watt100 1, 200Watt60 1, 300Watt40 1, 500Watt3 1, 700Watt
20 1, 1000Watt15 1, 1400Watt11 1, 2000Watt9 1, 2400Watt8 1, 2800Watt
4.2 1, 6400Watt4.2 1, 6400Watt2.8 1, 9600Watt2.8 1, 9600Watt900 1, 100Watt450 1, 200Watt300 1, 300Watt200 1, 500Watt120 1, 700Watt90 1, 1000Watt60 1, 1400Watt45 1, 2000Watt35 1, 2400Watt30 1, 2800Watt
16.9 1, 6400Watt16.9 1, 6400Watt11.4 1, 9600Watt11.4 1, 9600Watt8.4 1, 12800Watt
DB Resistor (150% Braking Torque)
150 1, 150Watt60 1, 300Watt50 1, 400Watt33 1, 600Watt20 1, 800Watt
15 1, 1200Watt10 1, 2400Watt8 1, 2400Watt51, 3600Watt51, 3600Watt
----
600 1, 150Watt300 1, 300Watt200 1, 400Watt130 1, 600Watt85 1, 1000Watt60 1, 1200Watt40 1, 2000Watt30 1, 2400Watt20 1, 3600Watt20 1, 3600Watt
-----
Inverter Models HP MCCB, ELB Magnetic Contactor DC ReactorAC Input Fuse AC ReactorWire, mm2 (AWG)
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV055iS5-2SV075iS5-2SV110iS5-2SV150iS5-2SV185iS5-2SV220iS5-2SV300iS5-2SV370iS5-2SV450iS5-2SV550iS5-2SV008iS5-4SV015iS5-4SV022iS5-4SV037iS5-4SV055iS5-4SV075iS5-4
1235
7.51015202530405060751235
7.510
ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33ABS53a, EBS53ABS63a, EBS63
ABS103a, EBS103ABS103a, EBS103ABS203a, EBS203ABS203a, EBS203ABS203a, EBS225ABS203a, EBS225ABS403a, EBS300ABS403a, EBS350
ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33ABS33a, EBS33
SMC-10PSMC-10PSMC-15PSMC-20PSMC-25PSMC-35PSMC-50PSMC-65PSMC-80P
SMC-100PGMC-150GMC-180GMC-220GMC-300SMC-10PSMC-10PSMC-20PSMC-20PSMC-20PSMC-20P
2 (14)2 (14)2 (14)
3.5 (12)5.5 (10)
8 (8)14 (6)22 (4)30 (3)30 (3)
6060
100100
2 (14)2 (14)2 (14)2 (14)2 (14)
3.5 (12)
3.5 (12)3.5 (12)3.5 (12)3.5 (12)5.5 (10)5.5 (10)
14 (6)14 (6)22 (4)22 (4)
22223838
2 (14)2 (14)2 (14)2 (14)
3.5 (12)3.5 (12)
7.00mH, 5.7A4.05mH, 9.2A2.92mH, 13A1.98mH, 19A1.37mH, 29A1.05mH, 38A0.74mH, 56A0.57mH, 71A0.49mH, 91A
0.42mH, 107A0.35mH, 152.0A0.3mH, 180.0A
0.28mH, 221.0A0.25mH, 270.0A28.62mH, 2.7A16.14mH, 4.6A11.66mH, 7.1A
7.83mH, 10A5.34mH, 14A4.04mH, 19A
R,S,T U,V,W Ground
2 (14)2 (14)2 (14)
3.5 (12)5.5 (10)
8 (8)14 (6)22 (4)30 (3)38 (2)
6060
100100
2 (14)2 (14)2 (14)
3.5 (12)3.5 (12)5.5 (10)
10A15A25A40A40A50A70A
100A100A125A150A200A250A300A
6A10A10A20A20A30A
2.13mH, 5.7A1.20mH, 10A0.88mH, 14A0.56mH, 20A0.39mH, 30A0.28mH, 40A0.20mH, 59A0.15mH, 75A0.12mH, 96A
0.10mH, 112A0.08mH, 134.2A0.07mH, 160.6A0.06mH, 198.0A0.05mH, 242.0A
8.63mH, 2.8A4.81mH, 4.8A3.23mH, 7.5A2.34mH, 10A1.22mH, 15A1.14mH, 20A
Options, DB Resistor& Peripheral Devices
Starvert iS5
21
RFI FilterIS5 Series Footprinting Filter
Inverter
THREE PHASE NOM. MAX.
Power Code Current TensionVoltage
LeakageCurrent
DimensionsL W H
MountingY X Weight Mount Output
Chokes
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV055iS5-2SV075iS5-2SV110iS5-2SV150iS5-2SV185iS5-2SV220iS5-2SV008iS5-4SV015iS5-4SV022iS5-4SV037iS5-4SV055iS5-4SV075iS5-4SV110iS5-4SV150iS5-4SV185iS5-4SV220iS5-4
FFS5-T012-(X)
FFS5-T020-(X)
FFS5-T030-(X)FFS5-T050-(X)
FFS5-T006-(X)
FFS5-T012-(X)
FFS5-T030-(X)
FFS5-T051-(X)
FFS5-T060-(X)FFS5-T070-(X)
0.75kW1.5kW2.2kW3.7kW5.5kW7.5kW11kW15kW18kW22kW
0.75kW1.5kW2.2kW3.7kW5.5kW7.5kW11kW15kW18kW22kW
12A
20A
30A50A
100A
120A
6A
12A
30A
51A
60A70A
250VA
250VA
250VA250VA
250VA
250VA
380VA
380VA
380VA
380VA
380VA380VA
0.3A 18A
0.3A 18A
0.3A 18A0.3A 18A0.3A 18A
0.3A 18A
0.5A 27A
0.5A 27A
0.5A 27A
0.5A 27A
0.5A 27A0.5A 27A
329 X 149.5 X 50
329 X 149.5 X 50
415 X 199.5 X 60415 X 199.5 X 60
329 X 149.5 X 50
329 X 149.5 X 50
415 X 199.5 X 60
466 X 258 X 65
541 X 332 X 65541 X 332 X 65
315 X 120
315 X 120
410 X160410 X 160
315 X 120
315 X 120
401 X 160
515.5 X 255
515.5 X 255
M5
M5
M5M5
M5
M5
M5
M8
M8M8
FS-2
FS-2
FS-2FS-2FS-3
FS-3
FS-1
FS-2
FS-2
FS-2
FS-2FS-2
IS5 Series Standard Filter
Inverter
THREE PHASE NOM. MAX.
Power Code Current TensionVoltage
LeakageCurrent
DimensionsL W H
MountingY X Weight Mount Output
Chokes
SV008iS5-2SV015iS5-2SV022iS5-2SV037iS5-2SV055iS5-2SV075iS5-2SV110iS5-2SV150iS5-2SV185iS5-2SV220iS5-2SV300iS5-2SV370iS5-2SV450iS5-2SV550iS5-2SV008iS5-4SV015iS5-4SV022iS5-4SV037iS5-4SV055iS5-4SV075iS5-4SV110iS5-4SV150iS5-4SV185iS5-4SV220iS5-4SV300iS5-4SV370iS5-4SV450iS5-4SV550iS5-4SV750iS5-4
FE-T012-(X)
FE-T020-(X)
FE-T030-(X)FE-T050-(X)
FE-T100-(x)
FE-T120-(x)
FE-T150-2FE-T170-2FE-T230-2FE-T260-2
FE-T006-(X)
FE-T012-(X)
FE-T030-(X)
FE-T050-(X)
FE-T060-(X)FE-T070-(X)FE-T070-2FE-T100-2FE-T120-2FE-T120-2FE-T170-2
--
--
------
--
--
--
--
--
----
(X) (1) Industrial environment EN 50081-1 (A class)(2) Domestic and industrial environment EN 50081-1 (B class)
Peripheral DevicesInverter Models kW MCCB, ELB Magnetic Contactor DC ReactorAC Input Fuse AC ReactorWire, mm2 (AWG)
SV110iS5-4SV150iS5-4SV185iS5-4SV220iS5-4SV300iS5-4SV370iS5-4SV450iS5-4SV550iS5-4SV750iS5-4
1520253040506075
100
ABS53a, EBS53ABS63a, EBS63
ABS103a, EBS103ABS103a, EBS103ABS203a, EBS125ABS203a, EBS150ABS203a, EBS175ABS203a, EBS225ABS203a, EBS225
SMC-20PSMC-25PSMC-35PSMC-50PGMC-85
GMC-100GMC-125GMC-150GMC-180
5.5 (10)8 (8)8 (8)
14 (6)2222383860
8 (8)8 (8)
14 (6)14 (6)
1414222222
2.76mH, 29A2.18mH, 36A1.79mH, 48A1.54mH, 55A
1.19mH, 76.0A0.98mH, 93.0A
0.89mH, 112.0A0.75mH, 135.0A0.44mH, 187.0A
R,S,T U,V,W Ground
8 (8)14 (6)14 (6)22 (4)
2222383860
35A45A60A70A
100A100A100A150A200A
0.81mH, 30A0.61mH, 38A0.45mH, 50A0.39mH, 58A
0.33mH, 67.1A0.27mH, 82.5A
0.22mH,100.1A0.18mH, 121.0A0.13mH, 167.2A
0.75kW1.5kW2.2kW3.7kW5.5kW7.5kW11kW15kW18kW22kW30kW37kW45kW55kW
0.75kW1.5kW2.2kW3.7kW5.5kW7.5kW11kW15kW18kW22kW30kW37kW45kW55kW75kW
12A
20A
30A50A
100A
120A
150A170A230A280A
6A
12A
30A
50A
60A70A70A
100A120A120A170A
250VA
250VA
250VA250VA250VA
250VAC
250VAC250VAC250VAC250VAC
380VAC
380VAC
380VAC
380VAC
380VAC380VAC380VAC38VAC38VAC38VAC38VAC
0.3A 18A
0.3A 18A
0.3A 18A0.3A 18A0.3A 18A
1.3A 180A
1.3A 150A1.3A 150A1.3A 150A1.3A 150A
0.5A 27A
0.5A 27A
0.5A 27A
0.5A 27A
0.5A 27A0.5A 27A1.3A 150A1.3A 150A1.3A 150A1.3A 150A1.3A 150A
250 X 110 X 60
270 X 140 X 60
270 X 140 X 60270 X 140 X 60420 X 200 X 130
420 X 200 X 130
480 X 200 X 160480 X 200 X 160580 X 250 X 205580 X 250 X 205
250 X 110 X 60
250 X 110 X 60
270 X 140 X 60
270 X 140 X 90
270 X 140 X 90350 X 180 X 90350 X 180 X 90425 X 200 X 130425 X 200 X 130425 X 200 X 130480 X 200 X 160
238 X 76
258 X 106
258 X 106258 X 106408 X 166
408 X 106
468 X 166468 X 166560 X 170560 X 170
238 X 76
238 X 76
258 X 106
258 X 106
258 X 106338 X 146338 X 146408 X 166408 X 166408 X 166468 X 166
FS-2
FS-2
FS-2FS-2FS-3
FS-3
FS-3FS-3FS-4FS-4
FS-2
FS-2
FS-2
FS-2
FS-2FS-2FS-3FS-3FS-3FS-3FS-3
22
FF Series (Footprint)
FS Series (output chokes)
FE Series (Standard)
Dimensions
FF Series (Footprint)
FE Series (Standard)
RFI Filter
TypeFS-1FS-2FS-3FS-4
D21
28.54858
W85105150200
H4662110170
X7090
125 x 30180 x 45
O5555
HH
W X
Y
L
WX
Y
HD
W X
Y
L
RED
CARG
A
MOTOR
INVERTER
FILTER
SHIELDED CABLE
INVERTERFILTER
SHIELDED CABLEMOTOR
RFI Filters
www.lsis.biz2003.2 LSIS Co.,Ltd. All rights reserved.
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
HEAD OFFICELS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si,Gyeonggi-do 431-848, Korea
Middle East +82-2-2034-4901 / [email protected]
Europe & Africa +82-2-2034-4376 / [email protected]
Asia Pacific +82-2-2034-4645 / [email protected]
2011. 05 STARVERT iS5 (E) 2003. 2/(14) 2011. 05 Printed in Korea STAFF
LSIS (Middle East) FZE Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected]
Dalian LSIS Co., Ltd. Dalian, ChinaAddress: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]
LSIS (Wuxi) Co., Ltd. Wuxi, ChinaAddress: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]
LSIS-VINA Co., Ltd. Hanoi, VietnamAddress: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]
LSIS-VINA Co., Ltd. Hochiminh , VietnamAddress: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]
LSIS Tokyo Office Tokyo, JapanAddress : 16th, Higashi-Kan, Akasaka Twin Tower, 2-17-22, Akasaka, Minato-ku, Tokyo, JapanTel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: [email protected]
LSIS Shanghai Office Shanghai, ChinaAddress: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. ChinaTel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]
LSIS Beijing Office Beijing, ChinaAddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]
LSIS Guangzhou Office Guangzhou, ChinaAddress: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. ChinaTel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]
LSIS Chengdu Office Chengdu, ChinaAddress: Room 1701 17Floor, huanminhanjun internationnal Building, No1 Fuxing Road Chengdu, 610041, P.R. ChinaTel: 86-28-8670-3101 Fax: 86-28-8670-3203 e-mail: [email protected]
LSIS Qingdao Office Qingdao, ChinaAddress: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. ChinaTel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected]
Global Network
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact a qualified service technician when you need maintenance.Do not disassemble or repair by yourself!
Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions