Download pdf - Matrix CRH 004

Transcript
Page 1: Matrix CRH 004

SERVICE MANUAL

English

Cod. 273044Rev. 25.05.2005 Issued by T.D.Service

HIGH PERFORMANCE AIR COOLED CHILLER

R [004-032]

Page 2: Matrix CRH 004
Page 3: Matrix CRH 004

CautionIt is recommended that:S the manual is retained for the entire service life of the machine;S the user reads the manual carefully before carrying out any operations on the machine;S the machine is used exclusively for the purpose for which it is intended; incorrect use of the machine shall release themanufacturer from any liability.

This manual has been prepared to enable the end---user to carry out only those operations that can be donewith the panelsclosed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified person-nel.Each machine is equipped with an electric isolating device which allows the operator to work in conditions of safety. Thisdevice must always be used to eliminate risks during maintenance (electric shocks, scalds, automatic restarting, movingparts and remote control).The panel key supplied with the unit must be kept by the person responsible for maintenance.For identification of the unit (model and serial no.) in caseof thenecessity for assistance or spare parts, read the identificationlabels affixed to the outside and inside of the unit.

IMPORTANT: This manual may be subject to modification; for complete and up---to---date information the user shouldalways consult the manual supplied with the machine.

Index

1 -- Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 --- Foreword 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 --- Responsibility 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 --- Inspection 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 --- General description 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 -- Preliminary Operations 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.1 --- Operating limits 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.2 --- Sound pressure levels 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.3 --- Transport 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.4 --- Foundations 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2.5 --- Service area 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 -- Installation 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 --- Aeraulic connections 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2 --- Hydraulic connections 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.3 --- Connection of the safety valve discharge 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.4 --- Electrical connections 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4 -- Start--Up and Operation 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 --- Initial check 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.2 --- First start ---up (or after a long stop) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.3 --- Starting and stopping 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.4 --- Chillers serving special plants 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.5 --- Freecooling 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.6 --- Microprocessor control 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5 -- Refrigerant and Oil Charge 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.1 --- Refrigerant charge 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5.2 --- Oil charge 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6 -- Safety Devices Settings 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6.1 --- Setting thermostatic expansion valve 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7 -- Maintenance 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.1 --- Spare parts 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.2 --- Dismantling the unit 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 -- Options and Accessories 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.1 --- Pump set 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.2 --- Water chiller with partial heat recovery (20%) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.3 --- Water chiller with total heat recovery (100%) 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.4 --- Hydraulic circuit accessories 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8.5 --- Water chiller with inertia tank 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tables 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Drawings 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Circuits 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Matrix CRH 004

1

1 --- Introduction1.1 --- ForewordThishandbook isaimedatenablingboth the installerand theop-erator to carry out the correct installation, operation andmainte-nanceof the refrigeratingmachine,without damaging it or caus-ing injuries to the relevant staff.Thehandbook is thusan aid for thequalified staff in thearrange-mentof the specific equipment for thecorrect installation,opera-tion and maintenance in compliance with the local regulationsin force.The MATRIX R water chillers can be identified as follows:

CRH004

Version:R Radial

Execution:C ChillerS Superchiller

Compressor:H Hermetic Scroll

Cooling Capacity �kW�Nominal cooling capacity / 10

1.2 --- ResponsibilityLiebert Hiross accepts no present or future responsibility fordamage to persons, things or to themachine itself due toopera-tors� negligence, failing tocomplywith the installation, operationand maintenance instructions of this handbook, failed applica-tion of the safety norms in force for the system and the qualifiedstaff charged with the operation and maintenance.

1.3 --- InspectionAll units are fully assembled and wired in the manufacturingplant. Before shipment they are charged with the necessaryquantities of refrigerant and oil and then tested at the operatingconditions normally required by the customer. The machine�shydraulic circuit is equipped with drain plugs and open ventvalves; the free---cooling coils are supplied dry to avoid possibleproblemsdue to frost in the storageperiod. Immediately inspectthe machine carefully on delivery to check for damage duringtransportation ormissing components; possible claimsmustbemade immediately to thecarrier and the factoryor its representa-tive.

1.4 --- General descriptionMATRIX R units with air ---cooled condensers have been de-signed and manufactured for producing chilled water.They are also available in versions with a built --- in freecoolingmodule, in versionswith heat recovery for simultaneous heatingof thermal circuit water, with a pump assembly installed on themachine and/or inertial buffer tank inside themachine; the chill-ing units can be equipped with several options indicated in theprice list.The �MATRIX R� product line has been designed utilising thestate---of --- the---art techniques available nowadays in the indus-try, and includes all the components necessary for automaticand efficient operation.The Matrix R units are specifically designed for indoor installa-tion (protected from weather agents), for the connection with

ducts of condensation air in machine intake (if present) andoutlet.Eachunit is completely factory assembled; after evacuation, thenecessary quantity of refrigerant is added to the refrigerant cir-cuit(s) and the unit is tested.All theunitsareequippedwithoneor two independent refrigerat-ing circuits, each one composed of: an air ---cooled condenser,a hermeticScroll compressor andabraze---weldedplateevapo-rator. The components of the liquid line are the charging valves,filters---dryers, solenoidvalve, shut---off valve,moisture indicatorand thermostatic expansion valve.The hydraulic circuit --- with max. working pressure 5 bar --- ismade up on mod. 004---016 of hydraulic lines both in steel andflexibleEPDM rubber, connectedby fittingsand threaded joints,on mod. 017---032 of carbon steel pipes connected withgrooved---end (Victaulic) fittingsand couplingsand includealsoa flow switch (optional) and, in the freecooling versions, chilledwater coils and a three---way valve.Thehermeticscroll compressorsare completewith the followingprotection/safety devices: oil heater (if necessary), electronicprotection monitoring the temperature of the motor windingsand the direction of rotation (the latter may be enclosed in theelectronics of the compressor or external, depending on themodel).Fans are radial type, with aluminum reverse curved blades andstructure, statically and dynamically balanced, directly coupledto amotor with external rotor. It is always available the fan speedcontrolwhichnormally is achieved throughanadjusterwithcon-tinuous speed modulation.By simplymodifying theparameters (of theMicrofacemicropro-cessor control), limiting the fanmax. rotation speed, it ispossibleto change the useful air static pressure (equal to the differenceof the static pressure between the delivery and suction ductsconnected with the unit).The �MATRIX R�water chillers are controlled by the �MICROFA-CE�microprocessor,managingall theunit operatingconditions.The user can change and/or modify the operating parametersthrough the display keyboard installed on the electrical panel.The electrical control board is equipped with all the safety andoperating devices required for reliable operation. The compres-sormotors are equippedwith protectionon all three phasesandare started by three---pole contactors.

2 --- Preliminary Operations2.1 --- Operating limitsThe units can operate within the indicated operating limits (seeTab. 6). These limits apply to new machines, subject to correctinstallation and maintenance.S Ambient air minimum temperature: ---25ûC for Superchiller,---10ûC for Chiller (either Triac or EC fan);

S Maximumoutdoor air temperature is in relation toeachmod-el, as indicated in Tab. 6. In any case outdoor temperaturesaver 45ûC are not admitted; such limits are determined byelectrical and electronic components fitted on units;

S Maximum water flow allowed: depending on the pressuredrop corresponding to the required thermal difference (usu-ally not lower than 3.5ûC --- 4ûC);

S Minimum allowed water flow: compatible with a sufficientevaporation temperature, to avoid the intervention of thesafety devices (to be evaluated for a thermal difference nothigher than 8ûC);

S Temperature range of the water exiting the evaporator: 4ûC--- 15ûC;

S Maximum temperature of the water entering the unit: 20ûC;higher temperatures are allowed only at the system start---up and not during normal operation;

S Maximum glycol concentration: 50% (35%with the optionalpump assembly installed on the machine);

Page 5: Matrix CRH 004

2

S Minimum allowed glycol concentration: depending on theminimum temperature of the ambient air expected at theinstallation site (see Tab. a);

S Maximum difference of air side pressure (between the onein the delivery duct and the one, possibly negative, in thecoil suction) equal to the max. one indicated in Tab. 9 nextto the max. signal = 10 V set on the microprocessor;

S Maximum pressure of the hydraulic circuit: 5 bar;S Voltage range for the electric supply: 400 V +/---10%; max.phase difference: 3%; tolerance on frequency: 1%.

Storage conditions: ---20ûC ÷ 45ûC for all MATRIX R models.

2.2 --- Sound pressure levelsTheTab. 7 shows the noisedata for the units in standard config-uration (without pumps), operating continuously andmeasuredat 1 m from the coil side unit, with ducted air delivery and 50 Paof useful static pressure, in free field conditions.The highest noise levels are detected for higher useful staticpressures of the air.Note:Avoid positioning in areas with possible reverberation of thesound waves; acoustically insulate both the delivery and the in-take ducts (if installed); failure to do this can adversely effect thenoise levels.

2.3 --- TransportS Handle the unit by lifting it with a crane from above;S The lifting holes arepositioned in the frame�sbase (when lift-ing, use spreader bars to protect the sides, see Fig. 3, Fig. 4and Fig. 5).

Note:Place the lifting tubes in the holes in the base indicated by �LIFTHERE�. Lock the ends of the tubes with the locking pins andsplits pins as shown in Fig. 3 and Fig. 5. As an alternative (onmod. 004---016 only), shackles/hooks (optional) fastened at thebase ends can be used as a lifting system: in this case the liftingpointmust be on the vertical line passing through themachine�scentre of gravity (as indicated in Fig. 4) to prevent any load im-balance.The capacity of the lifting gear must be adequate to lift the loadin question. Check theweight of the units, the capacity of the lift-ing gear and ropes and the condition and suitability of theafore-mentioned equipment.

2.4 --- FoundationsS Theunitmust beplacedon a level surfacewhich will supportits weight.

S If necessary, position theunit on suitable anti ---vibration sup-ports that canbesupplied asanoption (in rubber or spring---type). Refer to the manual �Installation of the spring anti ---vibration supports� for their correct positioning.

S When positioned, level the unit.Note:For weight distribution see Fig. 6 and Fig. 7.Note:Theweights and their distribution refer to standard units withoutoptions; if the pump assembly, or other options are installed onthe machine, add the weights of the installed accessories tothose of the standard units (see Tab. 8).

2.5 --- Service areaS In order to allow free air flow or to enable the ducting installa-tion and maintenance of the unit, a minimum area must beleft free of obstructions around the unit (see Fig. 1 andFig. 2).

S Avoid recirculation of hot air between the outlet and the out-door intake of the air conveyed in the ducts, otherwise theunit performance may be impaired or the standard oper-ation can be interrupted.

3 --- Installation3.1 --- Aeraulic connectionsThe Matrix R units are arranged with connection flanges for theair intake and delivery ducts; if the units are ordered with metalfilters to protect the condensing coils, the connection flanges forthe intake side ducting are not supplied, as there is no duct toenable the cleaning of such filter.Connect the ducts fitting flexible joints to prevent transmittingvibrations and to compensate thermal expansion. Check if theholes on the walls --- where the intake and delivery ducts arefitted --- are protected by suitable anti ---rain grilles (equippedwith pre--- filter like the intakeones) toavoidwater or dust toenterin the chiller.All fans are adjusted at the same speed, so that it is not necess-ary to install overpressure dampers next to each fan discharge.The units are supplied with a setting in the microprocessor forthemax. fan speed of 50 Pa useful pressure; set themax. speedaccording to the features required by the installation (seeTab. 9).The units are supplied with the condensation air discharge up-wards; during the installation, it is possible to change the posi-tion of the air discharge opening (with right or left horizontaldirection) by simply inverting the position of the drilled panelwith the closed one of the required side (see size drawings).

3.1.1 -- External air temperature probe installationInstall the external air temperature probe (shipped inside theelectric panel), at the end of the air intake duct.The bulb must be positioned as much outside as possible butmust not be exposed to direct sunlight or weather agents suchas rain or snow. The unit operation could be jeopardized if theseprecautions are not applied.If the intake sideduct is not present, fasten the probe in the roomso that it can correctly detect the external temperature of the coilintakeouterairwithoutbeing influencedbyother external factors(sun rays, rain or snow, other heat or radiation sources, etc.).

3.2 --- Hydraulic connections3.2.1 -- Hydraulic circuit construction (Fig. a)The piping must be connected to the chiller. Construct a chilledwater circuit as described below, see Fig. a:1) Place shut---off valves within the circuit to allow servicing;2) Install a pump system suitable for the flow rate required ata pressure head equal to the sum of all the pressure drops(see project data).Matrix R chillers can be equipped, upon request, withpumps having performance as indicated in Tab. 8;

3) Install manometers at the chiller inlet/outlet;4) Install thermometers at the chiller inlet/outlet;5) Connect the pipes to the chiller by flexible joints to avoidtransmitting vibrations and to balance the thermal expan-sion; proceed in the same way even if the pump set is out-side the chiller;

6) It is useful to include awater pressure switch to give an earlywarning of low water pressure;

7) Place a mesh filter at the inlets of the pump and water chiller(Can be supplied as an optional accessory ---Not fitted);

8) Install, at the highest points in the circuit, apparatus whichallows the bleeding of air and possibly the filling of glycol;

9) Place a drain valve at the lowest point in the circuit and im-mediately at the outlet of the water chiller;

10) Install a water filling set including the following:a) filling water meter;b) manometer;c) non---return valve;d) air separator;e) removable supply tube, which must be disconnectedafter each charge/top---up;

Page 6: Matrix CRH 004

3

11) For maximum protection ensure that all tubing exposed tolow outdoor temperatures is fitted with anti --- freeze heatersand insulated using closed cell synthetic rubber (elasto-mer);

12) The circuit must include an expansion vessel (with safetyvalve) of suitable capacity;

13) Connect the lines avoiding stresses on the machine innerparts.

Note:If the water chiller is complete with an expansion vessel (sup-plied as an option), check if the capacity is enough, and installa second vessel in the circuit, if required (see par. 8.4).Follow the indications in Fig. c for the correct sizing.Note:The whole circuit must contain a water volume suitable for thecapacity of the installed chiller. Check if the inertial capacity giv-en by the sum of the hydraulic volume inside the machine (in-cluding the volume of the optional interna tank, if fitted) and thesystemvolume issufficient,orpossibly install a tank in thecircuit.Follow the indications in Fig. b for the correct sizing.Note:The hydraulic circuit must ensure a constant water supply to theevaporator in every operating condition. Otherwise, the com-pressorsmaybedamagedby repeated returnsof liquid refriger-ant on their suction.Note:The water flow switch is a compulsory safety component thatmust be installed and correctly wired to the Matrix R chillers,otherwise the guarantee will be invalidated.It is installed, as standard, on units with the optional on---boardpump set, and is available as a option for units without pumpson board: in the latter case the flow switch, if not installed on themachine, canbe installedon thehydraulic circuit by the installer,but it is compulsory that it is wired to the electric panel terminalboard, as indicated on the wiring diagram.

3.2.2 -- Addition of water and ethylene glycolVery important:Add water and ethylene glycol to the circuit with a %dependingon the minimum temperature of the outside air expected at theinstallation site. Do not exceed the nominal operating pressureof the circuit�s components.Notes:

S To avoid stratification run the circulation pump for at least 30minutes after adding any glycol.

S After adding water to the hydraulic circuit always discon-nect the water supply coming from the sanitary supply;this avoids the danger of glycol entering the sanitary watersystem.

S After any topping---up of the water check the concentrationand add glycol if necessary.

3.2.3 -- Water--glycol mixtureWater---glycol mixtures are used as the thermal carrier fluid inverycoldclimatesorwith temperaturesbelowzerodegreescen-tigrade. Determine the ethylene glycol % which must be addedto the water, with the assistance of Tab. a.

Tab. a --Ethylene glycol to be added to water (% inweight of total mixture)

Ethylene glycol(% in weight) 0 10 20 30 40 50

Freezing tempera-ture, ûC (*) 0 ---4.4 ---9.9 ---16.6 ---25.2 ---37.2

Mixture density at20ûC (*), kg/l --- 1.017 1.033 1.048 1.064 1.080

(*) Values are for Shell antifreeze 402. For different brands, checkmanufacturer�s data.

For the chiller internalwater volume refer toTab. 1. If theoptionalbuffer tank is installed on the machine, add the tank hydraulicvolume.ALWAYS CHARGE THE HYDRAULIC CIRCUIT WITH THE RE-QUIRED GLYCOL % NECESSARY FOR THE MINIMUM AMBI-ENT TEMPERATURE AT THE INSTALLATION SITE. FAILINGTO COMPLY WITH THIS INSTRUCTION SHALL INVALIDATETHE UNIT WARRANTY.

3.3 --- Connection of the safety valve dis-charge

Safety valvesare installedon thehighpressure sideof the refrig-eration circuit(s): the discharge of these valves must be con-veyed outside through a suitable pipe, having a diameter of atleast that of the valve outlet, without burdening the valve body.Convey the discharge to areas where the jet cannot harmpeople and the surrounding environment.

Fig. a -- Ideal chilled water circuit

CHILLER

11

1 1327436

9

4

8

11

flow

12

10e10d10c10b10a

T T

USER

5 5 9

disconnect af-ter charge

VptTank

5

Page 7: Matrix CRH 004

Fig. c --Sizing of the expansion vesselThe total volume of the expansion vessel is calculated with the following formula:

where:--- C=quantity of water inside the system expressed in litres--- e=water expansion coefficient, with water at 10ûC as a reference--- Pi=absolute pressure of initial charging, equivalent to the vessel pre---charge pressure (typical value2.5 bara)

--- Pf=absolute final tolerated pressure, lower than the operating pressure of the safety valve calibrationpressure (typical value 4.0 bara).

Use the values of the water expansion coefficient indicated in the table below:

V =C x e

Pi1 --

Pf

4

Fig. b -- Inertia tank sizing

The total optimum hydraulic volume of the system where the Matrix R chiller is installed can be calculated by thefollowing formula:

where:--- V=minimum required total water volume expressed in litres--- Rt=refrigeration capacity expressed in kW--- Xd=differential band set on the control and expressed in degrees centigrade

Please note that the sum of the hydraulic volume of the Matrix R chiller (Vm) plus the volume of the hydraulic circuitconnected to it (Vpc) must be greater than, or equal to the minimum required total water volume (V). If this condi-tion is not satisfied, it is necessary to install an inertia tank (Vpt, as indicated in the Fig. a) with a volume at leastequal to the following value: Vpt=V---Vm---Vpc

V =43 x Rt

Xd

H2O T [°C] Density [kg/m3] Expansion coefficient �e�

10 999.6 --- --- ---

20 997.9 0.0017

30 995.6 0.0040

40 992.2 0.0075

50 988.1 0.0116

3.4 --- Electrical connections1) Before proceeding with the electrical connections, ensurethat:S all electrical components are undamaged;S all terminal screws are tight;S the supply voltageand frequency are in accordancewiththe rating (with tolerance in accordance with IEC 8---6norms, March 1990)

S the allowed phase to phase variability is 3% maximum(see Fig. d). Variability in excess of 3% invalidates theguarantee.

2) Supply cable connections (see Tab. 5):S Connect the cable to the supply terminals.S Use appropriately sized 3---pole cable. An earth wiremust also be connected.

S Afterhavingopened thepassagein theframework (pre---punched knock---outs) for the supply line entry, restorethe original degree of protection using suitable accesso-ries for thewiring and junction boxes.

Fig. d --Example of calculating phaseto phase variability

1) The 400 V supply hasthe following variability:RS = 388 VST = 401 VRT = 402 V

2) The average voltage is:

3) The maximum deviation from the average is:

4) The phase to phase variability is:

388 + 401 + 4023 = 397

5397 x 100 = 1.26 (acceptable)

R S T

402 --- 397 = 5 V

Page 8: Matrix CRH 004

5

Note:The power supply should never be disconnected, except whenperforming maintenance.Operate (open) themain switch before carrying out anymainte-nance work on electrical components.Note:It is forbidden to work on the electrical components withoutusing insulating platforms, and in the presence of water or fogor mist.Note:Thesupply to theexternal pumpassemblymustbemadebeforestarting the chiller and must be kept on as long as the chiller isin use. Incorrect operation will cause the unit to lock---out be-cause of the internal protections (flow switch intervention).Note:Thecompressors are equippedwith anelectronicprotectionde-vice blocking their start if the phase sequence is not correct, orstopping their operation if a thermal relay intervenes. Thisdeviceis essential for the integrity of themechanical andelectricalcom-ponents of the compressors. Reset the standard functions byisolating this device and removing the causes of the lock---out.Note:The chillers are equippedwith their ownmicroprocessor controladjustment. The use of the remote ON---OFF input (located inthe electric panel terminal board) as a system temperature con-trol element is forbidden.

4 --- Start---Up and Operation4.1 --- Initial check1) Check all water connections.2) Open the shut---off valve on the liquid line.3) Ensure that the intake pressure is higher than 4.0 bar; if thisis not the case, prolong pre---heating of the compressor (ifpossible) and check that the refrigerant shut---off valve isproperly sealed, seeFig. 12, Fig. 13, Fig. 14, Fig. 15, Fig. 16and Fig. 17.

4) Open all isolating valves and/or water ball valves.5) In case of climateswith temperatures below zero degreesC,make sure the chilled water circuit is filled with the correctconcentration of water/glycol.

6) Bleed all air out of the chilled water circuit.7) Verify the water flow rate and its direction.8) Ensure that the thermal load is sufficient for start ---up.Caution:The ambient air temperature probe must be positioned in theshade and protected against the weather.

4.2 --- First start---up(or after a long stop)

Operate as follows:1) At least 8 hours before the start ---up, power the crank-case heaters (if any, see point 4) by setting the main iso-lator switchON.Make sure the auxiliary circuit has beenpowered and check the operation (a fault due to an in-correct procedure will invalidate the compressor guar-antee).

2) Open the valves of the refrigeration circuit that had beenclosed before the initial check.

3) Check themachinery supplying the thermal load connectedwith the unit and start the system pump(s).

4) MAKESURETHECOMPRESSOROILHASBEENHEATEDFOR AT LEAST 8 HOURS; start the unit only then. In theunits not equippedwith crankcase heaters (Chillers for sum-mer operation only, without modulating fan speed control),the start must be carried out in the warm season only (exter-nal T > 15ûC), and thus oil pre---heating is not necessary.

5) Make sure the fans rotate in the correct direction (anticlock-wise): check the electrical connections, if necessary.

6) Make sure the pumps rotate in the correct direction.

7) During the unit start ---up an inlet water temperaturehigher than 20ûC is allowed. Under standard operatingconditions check that the limits indicated in paragraph2.1 are not exceeded.

8) Check the correct operation of the control and safety de-vices.

9) Check the outlet temperature of the chilled water (check ifthe set---point set on the controller is reached).

10) Check the compressor oil level.11)With the compressor at full load, check there are nobubbles visible in the frefrigerant sight glass. If there are any,charge the unit according to par. 5.

4.3 --- Starting and stoppingALWAYS ENSURE THAT THE COMPRESSOR OIL HAS BEENPREHEATED.FOR BRIEF STOPPAGES MAINTAIN THE SUPPLY TO THECRANKCASE HEATER (IF ANY).S Start the unit setting the Microprocessor switch ON.S Stop the unit setting the Microprocessor switch OFF.S In case of long stops, turn the machine off using the Micro-processor switch OFF.In this case the compressor crankcase heaters (if any) re-main powered.

S For seasonal shutdown of the unit operate the main switchlocatedon themain electrical power supply. This will discon-nect the compressor crankcase heaters.

4.4 --- Chillers serving special plantsThe units are capable of cooling a water---glycolmixture to tem-peratures close to 0ûC without the need for significantmodifica-tions. In the caseof modification, the set values of the safety andcontrol components must also be changed. This can be carriedout in the factory (at the time of testing) or at the time of installa-tion, only by qualified and authorised personnel.

4.5 --- FreecoolingThe �freecooling� is a system of pre---cooling and/or cooling thewater/glycolmixtureusing ambient airwhen the latter isat a tem-perature below the return mixture temperature. If the outsidetemperature is sufficiently low to dissipate the entire heat load,the refrigeration compressors automatically switch off, and themixture�s temperature is controlled by the fan speed adjust-ment.If the mixture temperature is too high for freecooling, the com-pressors will operate as long as necessary to ensure the correctwater/glycol mixture temperature.

4.6 --- Microprocessor controlConsult the �Microface and Hiromatic� Service Manual.

5 --- Refrigerant and Oil ChargeAll work on pipes or components of the refrigerating circuit un-der pressure must be exclusively carried out by qualified staff,competent in such works.

5.1 --- Refrigerant chargeWHILST REPAIRING THE REFRIGERATING CIRCUIT RE-COVERALLTHEREFRIGERANT INACONTAINER:DONOTALLOW IT TO ESCAPE. NEVER USE THE COMPRESSORFOR THE SYSTEM VACUUM (THIS INVALIDATES THEWARRANTY).S The unit is delivered charged according to the Tab. 2.Warning for the refrigerant charge:S Ensure there are no refrigerant leaks.S Check the refrigerant type in the refrigeration circuit: a unitoriginally charged by the manufacturer with R407C cannotbe charged with R22 and vice versa; possibly apply to theTechnical Support Department.

Page 9: Matrix CRH 004

6

S Charge with the compressor in operation, connecting thecylinder with the charge connector after the thermostatic ex-pansion valve.Flush the connection pipe between the cylinder and thecharging point; tighten the seal joint and then start chargingthe unit. It is imperative that the cylinder is weighed both be-fore and after the operation.

S For the units with R407C the refrigerant charge must bemade exclusively with liquid refrigerant.

S Charge the unit until the bubbles in the sight glass have dis-appeared and the working conditions of the entire refrigera-tion circuit have returned to normal (sub---cooling and su-perheating within the limits indicated below).

S Measure the superheating as follows:1) Detect the temperature on the suction line, close to thebulb of the thermostatic expansion valve,using acontactthermometer.

2) Connect a pressure gauge (bymax. a 30---cm pipe) withthe Schraeder connection and read the correspondingsaturated evaporating temperature.

3) The superheating is the difference between the tworeadings.

4) For the units with R407C refer to the pressure gaugescale indicated with the initials D.P. (Dew Point)

S Verify that the superheating is 5ûC --- 8ûC.S Measure the sub---cooling as follows:1) Detect the temperature on the liquid line using a contactthermometer.

2) Connect a pressure gauge (bymax. a 30---cm pipe) withthe Schraeder connection on the liquid line and read thecorresponding saturated condensing temperature.

3) The sub---cooling is thedifferencebetween the tworead-ings.

4) For the units with R407C refer to the pressure gaugescale indicated with the initials B.P. (Bubble Point)

S Verify that at the condenser outlet, sub---cooling is 3ûC ---5ûC.

IT IS IMPORTANT TO CARRY OUT CHARGING CORRECTLY.Anexcess of refrigerant causesan increase in sub---cooling and

consequent operating difficulties in the hot season; a shortageof charge generates an increase in superheating and possiblecompressor stoppages. Whenever work is carried out on theunit, ensure afterwards that the working conditions are correct,checking sub---cooling and superheating.

5.2 --- Oil chargeContact theTechnical SupportDepartment for thespecificationsof the oil to be used for topping up; the oil changes according tothe type of used refrigerant.NEVER MIX DIFFERENT OILS TOGETHER. CLEAN THE PIP-ING COMPLETELY BEFORE CHANGING THE TYPE OF OILUSED.TOP---UPS OF UP TO 20---30% OF THE TOTAL AMOUNT OFOIL CONTAINED IN THE COMPRESSOR CRANKCASE AREPERMITTED; FOR LARGER PERCENTAGES CONTACT THETECHNICAL SUPPORT DEPARTMENT.

5.2.1 -- Procedure for oil topping--upIf there has been any loss of oil then this must be topped up asfollows:1) Take a clean, dry, transparent container (with volume cal-ibrations) and fill it with at least twice the amount of oil re-quired.

2) Isolate the compressor by closing thecock on the liquid line.3) Connect to the fittings on the compressor body (Schraedervalves) and empty it of refrigerant until atmospheric pres-sure (1 bar) is reached.

4) Using apipe, connect theoil container to theoil service fittingon the lower part of the compressor.

5) Open the oil service cock, lifting the container, so that the oilflows by gravity.

6) Charge the required quantity of oil (make sure the tube al-ways remains below the oil level in the container).

7) Stop the oil flow by closing the oil service fitting, open theshut---off cock on the refrigerating circuit and restore thedrained refrigerant charge.

6 --- Safety Devices SettingsThe water chiller has already been tested and set up by the manufacturer. The following setting values are suggested in the field.

COMPONENT SETTING NOTES

Low pressure switch (LP)

Operation with R407C/R22(standard factory setting):

START : 3.6 barDIFF. : 0.8 barSTOP : 2.8 bar

bar5

0.2 1.5

0.5bar

diff.set

High pressure switch (HP)

Operation with R407C/R22(standard factory setting):

STOP : 26 barSTART : 20 barDIFF. : 6 bar (fixed) reset

The settings for the safety valves installed on the machine are indicated below:

MODELS SETTINGS SAFETY VALVE004---204---206---207---008 28 bar006---007---011---014---016

017---020---023---025---028---030---032 29 barHP side

Page 10: Matrix CRH 004

7

6.1 --- Setting thermostatic expansionvalve

THIS OPERATION MUST BE PERFORMED BY AN EXPERI-ENCED REFRIGERATION TECHNICIAN.Before beginning this adjustment be sure that the refrigerantcharge is correct, checking the the sub---cooling (3ûC --- 5ûC, asspecified in par. 5.1).The valve has already been factory---set and should be resetwhen the superheating is not between 5ûC --- 8ûC, as follows:1) Important:Ensure that the instructions in par. 5.1 havebeen carriedout.

2) Allow the compressor to operate for 15 mins.3) Measure the superheating as follows:a) Connect a manometer to the Schraeder connection lo-cated on the evaporator outlet tube, and read themano-metric temperature on the scale for the refrigerant used(for the units with R407C refer to the pressure gaugescale indicated with the initials D.P. = Dew Point).

b) Using a contact thermometer, measure the temperatureon the tube coming out of the evaporator, next to thesocket used for the manometer.

c) The superheating is the difference between the tworeadings (b ---a).

4) The superheating must be 5ûC --- 8ûC; if not, set the expan-sion valve as follows:a) Remove the protective cover;b) Turn the adjustment screw to return to the optimum val-ues, tightening it in a clockwise direction to increase thesuperheating, or slackening it to reduce the superheat-ing.

c) Wait about 10 minutes;d) Measure the superheating and repeat the operation ifnecessary.

N.B:If the superheating is too low, there is a risk of poor lubricationandconsequentbreakageof the compressor as a result of pres-sure shock.If the superheating is too high the output of the system is limitedand the compressor overheats.

7 --- MaintenanceThe Maintenance Programme below must be carried out by aqualified technician, preferably working under a maintenancecontract.Before any intervention on the unit or accessing the inner com-ponents (removing the outer panels), always ensure the ma-chine is switched off. If the panels are removed (fans compart-ment) wait for the fan(s) to come to a complete stop beforeaccessing the compartment; if the front panels are removed (onmod. 004---016) or the front lower panels (on mod. 017---032),pay special attention whenworking near the compressor upperpart and the discharge line: they are very hot; possibly wait forthem to cool. Be very careful when operating close to the finnedcoils, as the fins are very sharp.Donot remove the fanprotectiongrille before electrically isolating the whole machine. Do not in-sert foreign matter through the fan protection grille. After themaintenance interventions, always close the unit with the suit-able panels, fastened by the tightening system.

7.1 --- Spare partsThe use of original spare parts is recommended.When placing an order refer to the �Component List� enclosedwith the machine and quote the unit model no. and serial no.

7.2 --- Dismantling the unitThemachinehasbeen designedandbuilt to ensurecontinuousoperation.The working life of some of the main components, such as thefans and the compressors, depends on the maintenance thatthey receive.If the unit has to be dismantled, the job must be done by skilledrefrigeration technicians.The refrigerant and the lubricating oil in the circuit must be dis-posed of in conformity with the laws in force in your country.

Maintenance programme -- Monthly check

FANSS Check that the fan motor rotates freely without any abnormal noise, and ensure that thebearings are not running hot.

S Also check the current absorption.

CONDENSER AND AIR FILTERS Check the conditions of the filters (if they are supplied); if necessary clean them (includingthe electrical panel ventilation filter).

S Check the condenser coils and clean if necessary with compressed air or soft brushes.

CONTROL S Check that the control equipment, LEDs and display are operating correctly.

ELECTRICAL CIRCUIT S Check the electrical supply on all phases.S Ensure that all electrical connections are tight.

REFRIGERATION CIRCUIT

S Check the condensing and the evaporating pressures (to be done by a refrigeration techni-cian).

S Check the compressor�s current absorption, the delivery temperature and possible unusualnoises.

S Check the refrigerant charge by means of the sight glass.S Check that the safety devices operate correctly.S Check the correct operation of the thermostatic valve (superheating between 5ûC---8ûC).S Check that the oil level indicated by the compressor sight glass is higher than the min. value.

CHILLED WATER CIRCUIT

S Ensure that there are no water leaks.S Bleed any air out of the hydraulic circuit using the bleed valves.S Verify that the water flow rate is correct.S Check the inlet --- outlet liquid temperature and pressure.S Check the correct operation of the three---way valve (Versions with free---cooling only).S Check if the system is charged with the specified glycol percentage and that no ice hasformed in the hydraulic circuit.

S Check the evaporator cleanliness.

Page 11: Matrix CRH 004

8

8 --- Options and Accessories8.1 --- Pump setOnmod. 004---016 the centrifugal pump units are direct driven,withclose---coupledmotorsandasingleshaft; the inductionmo-tor has 2 poles with IP 54 protection and class F insulation.The materials used for the pump main components are:S Pump body in plastic material PA 6.6 (cast iron in all highpressure freecooling versions and on model 016 in theChil-ler high head pressure version and Superchiller standardhead pressure version);

S Impeller in in plastic material PPO (stainless steel in all highpressure freecooling versions and on model 016 in theChil-ler high head pressure version and Superchiller standardhead pressure version);

S Stainless steel shaft;S Graphite impregnated ceramic mechanical seal (EPDM inall high pressure freecooling versions and on model 016 inthe Chiller high head pressure version and Superchillerstandard head pressure version), suitable for the use ofmix-tures containing ethylene glycol.

The pump units have been chosen and sized to operate withinspecific limits, namely:S Water / ethylene glycol mixtures up to 65% / 35% by weight;S Temperatures of the standard pumped fluid not lower than4°C.

Thehydrauliccircuit includes, foreachpump,a suctionshut---offvalve and a delivery check valve if two pumps are installed, orsuction anddelivery shut---off valves if a singlepump is installed.

Onmod. 017---032 the centrifugal pump units are direct driven,withclose---coupledmotorsandasingleshaft; the inductionmo-tor has 2 poles with IP 55 protection and class F insulation.Pumpcasingsand impellersare incast ironEN---GJL 200,shaftsare in stainless steel, the shaft seal is a unbalanced,mechanicalshaft seal with dimensions according toDIN 24 960 and assem-bly length according to EN 12 756, brass neck ring permits idealconditions for the use of watermixtures containing ethylenegly-col. The pump housing, the motor stool and the motor statorhousing are electrocoated.The pump units have been chosen and sized to operate withinspecific limits, namely:S Water / ethylene glycol mixtures up to 65% / 35% by weight;S Temperatures of the standard pumped fluid not lower than4°C.

The motor stool forms connection between the pump housingand the motor, and is equipped with a manual air vent screw forventing of the pump housing and the shaft seal chamber. It isvery important to carry out this operation as the circulationof liq-uid through theduct of theair vent screwensures lubricationandcooling of the shaft seal.Between the outlets of the two chambers and the dischargeflange, twin---head pumps have a non---return flap valve inEPDM rubber. The flap is opened by the flow of the pumped liq-uid and cuts off the port of the idle pump chamber.

In the electrical panel there are, for all the models of pumps, au-tomaticcircuitbreakers foreachpump; themicroprocessorcon-trolmanages theoperating rotationbetween the twopumpsandstart---up of the stand---by pump if the primary pump fails.For the technical features of the pumps and the hydraulic sche-matic see Tab. 8, Fig. 18, Fig. 19, Fig. 20, Fig. 21, Fig. 21 andFig. 22.

8.2 --- Water chiller with partial heatrecovery (20%)

Thisoptionenables the recovery ofup to20%of theheatnormal-ly rejected by the condensers. The system does not require anyadjustment and is made up of plate heat exchangers installedon each circuit before the condenser. The exchangers are pro-

tected by a suitable anti --- frost heater that operateswhen the sy-stem is stopped. It is recommended that a safety valve beinstalled in thehydrauliccircuit toavoidhazardsdue tooverpres-sures, if there is no water flow through the recuperator.The water temperature at the recuperator inlet (in stable operat-ingconditions)mustbe in the rangeof 25ûC --- 45ûC,with anout-let differential of between 3.5ûC --- 8ûC.

8.3 --- Water chiller with total heat recovery(100%)

All heat discharged by the unit to the condenser is recovered.The system includes an additional refrigerating circuit made upof a three---way solenoid valve, supplying --- in case of hot waterdemand --- a plate exchanger, usually by---passed and sized soas to discharge all condensing heat (also installed before thefinned air condenser in series with it); a check valve, a liquid re-ceiver at the exit of the finned air condenser working as storagefor the needed additional refrigerant charge (see refrigeratingscheme). The recuperator is insulated with closed cell polyure-thane and is equippedwith heaters activated when the recuper-ator is deactivated to prevent frost in winter with the systemstopped or not perfectly drained.The operation in total recovery mode is enabled by an externalcontact. The Microface control will simultaneously suit the fanspeedchanging the fan speed setpoint differently from the stan-dard operation without recovery (practically slowing the fansdown till they switch off); anyway, the operation in recoverymode is enabled alsowithout loadat theusers. Indeed, if theus-ers do not demand heat, the water flowing to the condenserreaches a temperature that does not enable the total condensa-tion of the compressed gas, and the remaining portion of thephase change can thus take place in finned coil without inter-rupting the recovery process through the interventionof thema-chine safety devices.If the plate exchanger is supplied with too coldwater, or if the sy-stem is not preset by the installation technician with a three ortwo---way proportional adjustment valve for the exchanger by-pass (indispensable for cold starts, see following �Recom-mended hydraulic circuit� ), the condensing pressure tends todecrease too much; a prolonged condition of low condensingtemperature below the safety threshold leads the Microface mi-croprocessor control to disable the heat recovery, protecting thesystem from any possible malfunctioning.

Fig. e --Recommended hydraulic circuit

Heat recoveryusers

Heat recoveryexchanger

8.4 --- Hydraulic circuit accessoriesMade up of an expansion vessel (pre---charged at 1.5 bar, max.operating pressure 10 bar) and a safety valve, set at 5 bar. Theirposition in the hydraulic circuit is illustrated in Fig. 18, Fig. 19,Fig. 20, Fig. 21, Fig. 21 and Fig. 22.S Expansion vessel volume:--- 8 litres for all 004---016 units,--- 12 litres for all 017---032 units.

It is recommended that the total required expansion vessel ca-pacity is always checked, depending on the unit�s internal hy-draulic volume (with the volume of the buffer tank, if installed),theuser circuit volume, theglycolpercentage in themixture,andthe expected maximum temperature variation of the mixture.Thewater flow switch is a compulsory deviceprotecting theunit.It is installed, as standard, on units with the optional on---boardpump set, and is available as a option for units without pumps

Page 12: Matrix CRH 004

9

on board: in the latter case the flow switch, if not installed on themachine,must be installed on thehydraulic circuit by the install-er andwired to theelectric panel terminal board, as indicatedonthe wiring diagram.

8.5 --- Water chiller with inertia tankThemachinecanbesupplied complete with a buffer tank; it per-forms the inertial stabilizer function, for better compressor op-eration, summed up in the following two points:S it reduces the frequency of the compressor peaks, which ishigher the lower the system thermal inertia, improving theirperformance;

S it naturally eliminates the operational problems caused bysudden load variations (shown by variations of the chilledwater temperature).

The buffer tank is supplied insulated, with a drain valve, ventvalve and connection for immersion electric heaters; maximumoperating pressure 6 bar.Built in carbon steel and coatedwith anti ---condensation insula-tion. It can be installed in all MATRIX R 004---016 versions insidethe coil compartment, while on mod. 017---032 it is installed in-side a cabinet which can be supplied either already connectedto the unit (mechanically and hydraulically jointed to it) or loose(completely separate from the unit).

Mod. 004---006---007 technical dataS Internal volume: 200 litresS Net weight: 110 kgS Working weight: 310 kg

Mod. 008---011---014---016 technical dataS Internal volume: 400 litresS Net weight: 140 kgS Working weight: 540 kg

Mod. 204---206---207 technical dataS Internal volume: 160 litresS Net weight: 100 kgS Working weight: 260 kg

Mod. 017---032 technical dataS Internal volume: 1000 litresS Net weight: 400 kgS Working weight: 1400 kg

Page 13: Matrix CRH 004

10

Tab. 1 --- Internal hydraulic volume

Model Unit volume (*) [l] Model Unit volume (*) [l]

004 8 004 37

006 9 006 38

007 14 007 75

204 10 204 39

CRH206 10

SRH206 40

CRH207 18

SRH207 79

008 24 008 97

011 27 011 101

014 38 014 146

016 46 016 156

017 37 017 129

020 37 020 129

023 45 023 158

CRH 025 45 SRH 025 158

028 51 028 186

030 60 030 195

032 60 032 195(*) Add the tank�s volume for the units with optional buffer tank

Tab. 2 --- R 407C refrigerant and oil charge

CRH 004--016

Models 004 006 007 204 206 207 008 011 014 016

Refrigerant charge (each circuit) [kg] 12.6 7.5 13.9 7.7 23.7 12.9 12.9 14.5 19.9 20.8

Oil charge (each circuit) [lt] 6.2 8.0 8.0 3.25 3.25 3.3 6.2 8.0 8.0 8.0

CRH 017--032

Models 017 020 023 025 028 030 032

Refrigerant charge (each circuit) [kg] 21.0 21.6 30.7 30.8 36.8 39.4 39.5

Oil charge (each circuit) [lt] 12.4 14.2 16.0 16.0 16.0 16.0 16.0

SRH 004--016

Models 004 006 007 204 206 207 008 011 014 016

Refrigerant charge (each circuit) [kg] 12.6 7.5 13.9 7.7 23.7 12.9 12.9 14.5 19.9 20.8

Oil charge (each circuit) [lt] 6.2 8.0 8.0 3.25 3.25 3.3 6.2 8.0 8.0 8.0

SRH 017--032

Models: 017 020 023 025 028 030 032

Refrigerant charge (each circuit) [kg] 21.0 21.6 30.7 30.8 36.8 39.4 39.5

Oil charge (each circuit) [lt] 12.4 14.2 16.0 16.0 16.0 16.0 16.0

Page 14: Matrix CRH 004

11

Tab. 3 --- CRH/SRH 004---032 --- Partial heat recovery (20%)

CRH/SRH 004--016

Model 004204

006206

007207 008 011 014 016

Heating capacity kW 10,8 14,8 18,2 21,6 29,6 36,4 44,3

Water flow l/s 0,516 0,707 0,870 1,032 1,414 1,739 2,117

Water pressure drop kPa 8 11 14 8 11 14 21

Water connections BSP---T 1� 1� 1� 11/4� 11/4� 11/4� 11/4�Working conditions: outdoor temperature 35ûC, water inlet/outlet 12/7ûC (Chiller versions), glycol mixture 30% inlet/outlet 15/10ûC (SuperChiller versions).Heat recovery conditions: water inlet/outlet 40/45ûC.

CRH/SRH 017--032

Model 017 020 023 025 028 030 032

Heating capacity kW 40 48 56 62 68 79 86

Water flow l/s 1.91 2.29 2.68 2.96 3.25 3.77 4.11

Water pressure drop kPa 15 20 16 19 16 17 20

Water connections BSP---T 2�Working conditions: outdoor temperature 35ûC, water inlet/outlet 12/7ûC (Chiller versions), glycol mixture 30% inlet/outlet 15/10ûC (SuperChiller versions).Heat recovery conditions: water inlet/outlet 40/45ûC.

Tab. 4 --- CRH/SRH 004---032 --- Total heat recovery (100%)

CRH/SRH 004--016

Model 004204

006206

007207 008 011 014 016

Heating capacity kW 53 74 91 105 144 177 223

Water flow l/s 2,53 3,54 4,35 5,02 6,88 8,46 10,65

Water pressure drop kPa 60 70 80 60 70 80 90

Water connections BSP---T 2� 2� 2� 21/2� 21/2� 21/2� 21/2�Working conditions: water inlet/outlet 12/7ûC (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.

CRH/SRH 017--032

Model 017 020 023 025 028 030 032

Heating capacity kW 212 238 290 320 357 412 453

Water flow l/s 10.13 11.37 13.86 15.29 17.06 19.68 21.64

Water pressure drop kPa 52 65 71 82 83 85 99

Water connections BSP---T DN 80 --- 3�Working conditions: water inlet/outlet 12/7ûC (Chiller versions). Heat recovery conditions: water inlet/outlet 40/45ûC.

Page 15: Matrix CRH 004

12

Tab. 5 --- Electrical characteristics

CRH 004--016 -- R 407C

Size 004 204 006 206 007 207 008 011 014 016

Power supply --- 400 V / 3 Ph / 50 Hz

OA (1)FLALRACompressors power input (1)Compressors nominal current (1)Compressor max. currentFans power input

AAAkWAAkW

314318313.223352.9

324612513.224192.9

405822319.332503.3

426616719.034293.3

487727824.140693.1

507218524.642323.1

628622626.346355.8

8011628138.664506.8

9916336443.6746910.1

12316941759.4987210.2

Fans max. power inputFans max. current

kWA

4.98.2

SHC std. head pressure pump model (Opt.)Std. head pressure pump motor nom. powerStd. head pressure pump motor max. powerStd. head pressure pump max. currentSHC high head pressure pump model (Opt.)FHE high head pressure pump model (Opt.)High head pressure pump motor nom. powerHigh head pressure pump motor max. powerHigh head pressure pump max. current

---kWkWA------kWkWA

12 --- 1290.751.081.85

12 --- 136---1.11.442.67

12 --- 1361.11.442.6720---128---1.51.923.90

20 --- 1281.51.923.90

20 --- 134---1.852.454.61

20---1341.852.454.61---

40---160/404.04.08.50

Electrical cable section (min.) mm2 16 16 25 25 35 35 35 50 70 95

(1) Outdoor air temperature 35ûC; water inlet/outlet temperature 12/7ûC.Nominal air flow and 50 Pa available air static pressure.

CRH 017--032 -- R 407C

Size 017 020 023 025 028 030 032

Power supply --- 400 V / 3 Ph / 50 Hz

OA (1)FLALRACompressors power input (1)Compressors nominal current (1)Compressor max. currentFans power input

AAAkWAAkW

12516530557.3100359.7

13519536064.9110509.7

16323339877.71305013.1

18327147290.11506913.1

19931751894.51586916.5

225323571111.71847216.5

245329577124.82047218.1

Fans max. power inputFans max. current

kWA

4.98.2

SHC std. head pressure pump model (Opt.)Std. head pressure pump motor powerStd. head pressure pump max. currentHigh head pressure pump model (Opt.)High head pressure pump motor powerHigh head pressure pump max. current

---kWA---kWA

65 --- 190/22.24.45

65 --- 260/24.08.00

65 --- 230/23.05.95

65 --- 260/24.08.00

65 --- 260/24.08.00

65 --- 340/25.511.20

Electrical cable section (min.) mm2 70 95 120 150 185 185 185

(1) Outdoor air temperature 35ûC; water inlet/outlet temperature 12/7ûC.Nominal air flow and 50 Pa available air static pressure.

Page 16: Matrix CRH 004

13

SRH 004--016 -- R 407C

Size 004 204 006 206 007 207 008 011 014 016

Power supply --- 400 V / 3 Ph / 50 Hz

OA (1)FLALRACompressors power input (1)Compressors nominal current (1)Compressor max. currentFans power input

AAAkWAAkW

324318313.424353.2

324612513.424193.2

415822319.833503.8

426616719.434293.8

497727824.841693.3

507218525.042323.3

648622626.748356.5

8211628139.666507.6

10116336444.5766911.4

12516941760.81007211.4

Fans max. power inputFans max. current

kWA

4.98.2

SHC std. head pressure pump model (Opt.)FHE std. head pressure pump model (Opt.)Std. head pressure pump motor nom. powerStd. head pressure pump motor max. powerStd. head pressure pump max. currentSHC high head pressure pump model (Opt.)High head pressure pump motor nom. powerHigh head pressure pump motor max. powerHigh head pressure pump max. current

------kWkWA---kWA

12 --- 136---1.11.442.67

32---160/303.06.50

20 --- 128---1.51.923.90

32 --- 160/303.06.50

20 --- 134---1.852.454.61

40---160/404.08.50

---40---160/404.04.08.50

40---200/757.515.50

Electrical cable section (min.) mm2 16 16 25 25 35 35 35 50 70 95

(1) Outdoor air temperature 35ûC; 30% glycol water mixture; water inlet/outlet temperature 15/10ûC.Nominal air flow and 50 Pa available air static pressure.

SRH 017--032 -- R 407C

Size 017 020 023 025 028 030 032

Power supply --- 400 V / 3 Ph / 50 Hz

OA (1)FLALRACompressors power input (1)Compressors nominal current (1)Compressor max. currentFans power input

AAAkWAAkW

12716530558.51023510.8

13719536066.51125010.8

16523339879.71325014.6

18527147292.51526914.6

20331751896.91626918.3

229323571114.81887218.3

249329577128.12087220.3

Fans max. power inputFans max. current

kWA

4.98.2

Std. head pressure pump model (Opt.)Std. head pressure pump motor powerStd. head pressure pump max. currentHigh head pressure pump model (Opt.)High head pressure pump motor powerHigh head pressure pump max. current

---kWA---kWA

65 --- 260/24.08.00

65 --- 340/25.511.20

65 --- 340/25.511.20

65 --- 410/27.515.20

65 --- 410/27.515.20

65 --- 460/211.021.40

Electrical cable section (min.) mm2 70 95 120 150 185 185 185

(1) Outdoor air temperature 35ûC; 30% glycol water mixture; water inlet/outlet temperature 15/10ûC.Nominal air flow and 50 Pa available air static pressure.

• Nominal power supply = 400 V; 3 Ph; 50 Hz• Nominal power supply tolerance = 400 V ±10 %• Max. voltage unbalance = 3 %• The cables have to be sized in compliance with local standards and according to the type and characteristics of installation. Suggested cables section are

referred to PVC insulation with a max. working temperature of 70 ûC and an ambient temperature of 30 ûC.

Page 17: Matrix CRH 004

14

Tab. 6 --- Operating limits

CRH 004--016 -- R 407C

Size 004 006 007 204 206 207 008 011 014 016

Working Range

Max. outdoor air temperature (1) ûC 45 45 42 42 42 42 45 43 45 42

Safety Device Settings

High pressure switchHigh pressure safety valveLow pressure switch

BargBargBarg

26.028.0 / 29.02.8

(1) With nominal air flow; water flow outlet at 7ûC; full load

CRH 017--032 -- R 407C

Size 017 020 023 025 028 030 032

Working Range

Max. outdoor air temperature (1) ûC 42.5 40.5 42.5 40.5 43.0 40.0 39.5

Safety Device Settings

High pressure switchHigh pressure safety valveLow pressure switch

BargBargBarg

26.029.02.8

(1) With nominal air flow; water flow outlet at 7ûC; full load

SRH 004--016 -- R 407C

Size 004 006 007 204 206 207 008 011 014 016

Working Range

Max. outdoor air temperature (2) ûC 45.0 45.0 41.5 41.5 41.0 41.0 45.0 42.0 45.0 41.0

Safety Device Settings

High pressure switchHigh pressure safety valveLow pressure switch

BargBargBarg

26.028.0 / 29.02.8

(2) With nominal air flow; 30% mixture flow outlet at 10ûC; full load

SRH 017--032 -- R 407C

Size 017 020 023 025 028 030 032

Working Range

Max. outdoor air temperature (2) ûC 41.5 39.5 41.5 39.5 42.0 39.0 38.5

Safety Device Settings

High pressure switchHigh pressure safety valveLow pressure switch

BargBargBarg

26.029.02.8

(2) With nominal air flow; 30% mixture flow outlet at 10ûC; full load

Page 18: Matrix CRH 004

15

Tab. 7 --- Noise levels

The following table indicates the overall sound pressure level at full load conditions, measured 1m from the unit, coil side, with ductedair discharge (50 Pa static pressure), with an outdoor temperature of 35 ûC and referred to free field conditions.

ModelsTotal

sound level ModelsTotal

sound levelModels[dB(A)]

Models[dB(A)]

CRH / SRH 004 --- 204 70 CRH / SRH 017 74.5

CRH / SRH 006 --- 206 73 CRH / SRH 020 74.5

CRH / SRH 007 --- 207 74 CRH / SRH 023 75

CRH / SRH 008 71.5 CRH / SRH 025 75

CRH / SRH 011 74.5 CRH / SRH 028 76

CRH / SRH 014 75.5 CRH / SRH 030 76

CRH / SRH 016 75.5 CRH / SRH 032 78

Tab. 8 --- Pump set characteristics (opt.)

2 pole pump set, standard head pressure (data refers to each pump)

Models 004 204 006 206 007 207 008 011 014 016

CRHWater flow m3/h 6.79 6.79 8.86 8.73 10.94 11.11 13.41 17.53 22.78 28.00

CRHAvailable head pressure kPa 127 156 122 146 104 127 141 142 88 78

Pump quantity Nr. 1 2

Pump rotor model --- 12---129 12---136 20---128 20---134

Nominal motor power kW 0.75 1.1 1.5 1.85

Noise level (*) dB(A) 58 63 65

Pump weight kg 10.4 12.7 13.8 15.4(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)

Models 004 204 006 206 007 207 008 011 014 016

CRHWater flow m3/h 6.79 6.79 8.86 8.73 10.94 11.11 13.41 17.53 22.78 28.00

CRHAvailable head pressure kPa 169 198 163 187 145 168 167 191 145 173

Pump quantity Nr. 1 2

Pump rotor model --- 12---136 20---128 20---134 40---160/40

Nominal motor power kW 1.1 1.5 1.85 4

Noise level (*) dB(A) 58 63 65 70

Pump weight kg 12.7 13.8 15.4 42

(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)

Models 017 020 023 025 028 030 032

CRHWater flow m3/h 26.93 29.26 35.67 38.38 44.20 50.71 55.23

CRHAvailable head pressure kPa 119 107 136 123 145 111 73

Pump quantity Nr. 1/2

Pump rotor model --- 65---190 / 2 65---230 / 2 65---260 / 2

Nominal motor power kW 2.2 3 4

Noise level (*) dB(A) 60 59 63

Pump weight kg 57.9 / 116.4 69.3 / 139.2 74.3 / 149.2(*) According to ISO 3744

Page 19: Matrix CRH 004

16

2 pole pump set, high head pressure (data refers to each pump)

Models 017 020 023 025 028 030 032

CRHWater flow m3/h 26.93 29.26 35.67 38.38 44.20 50.71 55.23

CRHAvailable head pressure kPa 197 187 182 170 230 204 173

Pump quantity Nr. 1/2

Pump rotor model --- 65---260 / 2 65---340 / 2

Nominal motor power kW 4 6

Noise level (*) dB(A) 63

Pump weight kg 74.3 / 149.2 89.2 / 178.9(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)

Models 004 204 006 206 007 207 008 011 014 016

SRH30% glycol/water mixture flow m3/h 7.83 7.83 10.26 10.08 12.58 12.64 15.45 20.12 26.24 31.92

SRHAvailable head pressure kPa 98 142 62 100 93 128 96 91 50 79

Pump quantity Nr. 1 2

Pump rotor model --- 12---136 20---128 20---134 40---160/40

Nominal motor power kW 1.1 1.5 1.85 4

Noise level (*) dB(A) 58 63 65 70

Pump weight kg 12.7 13.8 15.4 42

(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)

Models 004 204 006 206 007 207 008 011 014 016

SRH30% glycol/water mixture flow m3/h 7.83 7.83 10.26 10.08 12.58 12.64 15.45 20.12 26.24 31.92

SRHAvailable head pressure kPa 233 277 183 221 199 234 197 170 138 223

Pump quantity Nr. 1 2

Pump rotor model --- 32---160/30 40---160/40 40---200/75

Nominal motor power kW 3 4 7.5

Noise level (*) dB(A) 66 70 74

Pump weight kg 35 42 64

(*) According to ISO 3744

2 pole pump set, standard head pressure (data refers to each pump)

Models 017 020 023 025 028 030 032

SRH30% glycol/water mixture flow m3/h 31.06 33.49 41.26 43.98 51.08 58.3 63.27

SRHAvailable head pressure kPa 77 51 118 92 103 146 94

Pump quantity Nr. 1/2

Pump rotor model --- 65---260 / 2 65---340 / 2 65---410 / 2

Nominal motor power kW 4 5.5 7.5

Noise level (*) dB(A) 63 63 68

Pump weight kg 74.3 / 149.2 89.2 / 178.9 91.1 / 182.7

(*) According to ISO 3744

2 pole pump set, high head pressure (data refers to each pump)

Models 017 020 023 025 028 030 032

SRH30% glycol/water mixture flow m3/h 31.06 33.49 41.26 43.98 51.08 58.3 63.27

SRHAvailable head pressure kPa 157 133 207 183 190 205 159

Pump quantity Nr. 1/2

Pump rotor model --- 65---340 / 2 65---410 / 2 65---460 / 2

Nominal motor power kW 5.5 7.5 11

Noise level (*) dB(A) 63 68 65

Pump weight kg 89.2 / 178.9 91.1 / 182.7 149.4 / 306.4

(*) According to ISO 3744

Page 20: Matrix CRH 004

17

Tab. 9 --- Fan performances and settings

Standard air flow [12000 m3/h], 3 Ph fan + TRIACModels: CRH 004 --- 204 --- 008

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.01034286087

1005.21066309088

1505.41097332088

2005.61128353088

2505.81158372089

3006.01189391089

3506.31220409089

4006.71252425090

4507.21283442090

5007.91313460091

5509.51343476091

57010.01352481091

Models: SRH 004 --- 204 --- 008

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.31081321088

1005.51113343088

1505.71143362089

2005.91173381089

2506.11204401089

3006.51236417090

3506.91268433090

4007.61298451091

4508.61328468091

49010.01351481091

Standard air flow [12000 m3/h], EC fanModels: CRH 004 --- 204 --- 008

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

508.21041156086

1008.51080179087

1508.81117203087

2009.11153227088

2509.41190252088

3009.61225278089

3509.91259304089

37010.01270312089

Models: SRH 004 --- 204 --- 008

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

508.61099191087

1008.91135214088

1509.21172239088

2009.51208265088

2509.81242291089

29010.01270312089

Standard air flow [14000 m3/h], 3 Ph fan + TRIACModels: CRH 006 --- 206 --- 011 --- 014 --- 016

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.61162332091

1005.81189355091

1506.11216377092

2006.41245398092

2506.91274417092

3007.51302436092

3508.41329456093

39510.01354474093

Models: SRH 006 --- 206 --- 011 --- 014 --- 016

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

506.11215376092

1006.41243397092

1506.91273416092

2007.51301436092

2508.31328455093

29810.01355474093

Standard air flow [14000 m3/h], EC fanModels: CRH 006 --- 206 --- 011 --- 014 --- 016

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.11165210090

1009.41200236090

1509.71233262091

21010.01271294091

Models: SRH 006 --- 206 --- 011 --- 014 --- 016

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.71232261091

1009.91264288091

11210.01271294091

Unit performances are referred to sea level conditions.

Page 21: Matrix CRH 004

18

Standard air flow [15000 m3/h], 3 Ph fan + TRIACModels: CRH 007 --- 207

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.51179314093

1005.81205338093

1506.11232361093

2006.41259383093

2506.91287404093

3007.61313425093

3508.61339445094

38810.01360462094

Models: SRH 007 --- 207

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.71197330093

1006.01223354093

1506.31250377093

2006.81278398093

2507.41305418093

3008.11331438094

35410.01360462094

Standard air flow [15000 m3/h], EC fanModels: CRH 007 --- 207

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.21169195091

1009.41204221091

1509.71236248092

20610.01272278092

Models: SRH 007 --- 207

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.41193213091

1009.61226239092

1509.91258266092

17210.01272278092

Standard air flow [13250 m3/h], 3 Ph fan + TRIACModels: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.41123323090

1005.61151344090

1505.81179366090

2006.11208387091

2506.41237406091

3006.91268424091

3507.51296443092

4008.31325462092

44810.01352479092

Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

505.81172360090

1006.01200381091

1506.31229401091

2006.81260419091

2507.31289438091

3007.91317457092

3509.61346475092

36010.01352479092

Standard air flow [13250 m3/h], EC fanModels: CRH 017 --- 020 --- 023 --- 025 --- 028 --- 030

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

508.91129196089

1009.11164220089

1509.41199246090

2009.71233272090

25810.01271303090

Models: SRH 017 --- 020 --- 023 --- 025 --- 028 --- 030

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.41190239089

1009.61224265090

1509.91257292090

17010.01271303090

Unit performances are referred to sea level conditions.

Page 22: Matrix CRH 004

19

Standard air flow [14500 m3/h], 3 Ph fan + TRIACModels: CRH 032

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

506.01216362092

1006.31243385092

1506.81272405093

2007.31299425093

2508.01325445093

3009.71353466093

30810.01357469094

Models: SRH 032

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

506.81272405093

1007.31300425093

1508.01326445093

2009.81354466093

20610.01357469094

Standard air flow [14500 m3/h], EC fanModels: CRH 032

Useful static pressureMax. fan speed signalFan speedAbsorbed unitary powerFan discharge sound power [PWL]

PaVRpmWdB(A)

509.61225247091

1009.91257274091

12410.01272287091

Unit performances are referred to sea level conditions.

Page 23: Matrix CRH 004

20

Fig. 1 --- Service areas CRH/SRH 004---016 (top view)

Ordinarymaintenance area

Extraordinarymaintenance area

Notes:Minimum distance between 2 units from condensing coil side = 2 m(*) 1500 mm (with 160 --- 200 Lt Tank); 2500 mm (with 400 Lt Tank)

1000 1000 (*)

1000

500(withduct)

1500(withoutduct)

AIR

Fig. 2 --- Service areas CRH/SRH 017---032 (top view)

Ordinarymaintenance area

Extraordinarymaintenance area

Notes:Minimum distance between 2 units from condensing coil side = 3 m

1000 1000

1500

AIR

Page 24: Matrix CRH 004

21

Fig. 3 --- Lifting instructions with tubes CRH/SRH 004---016

LIFTING TUBE(NOT SUPPLIED)(BASE HOLES Ø45)

LIFTING SYSTEM WITH TUBES

BELT OR CHORD

BLOCKING PEG(NOT SUPPLIED)

SPLIT PIN(NOT SUPPLIED)

PART. �A�

N.B: Place the lifting tubes in the holes in the base indicated by the words �LIFT HERE�. Lock the ends of the tubes in position withthe locking pins and split pins as shown above �A�.The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of thelifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitablefor the load to be moved, so as not to damage the structure.

PART. �A�

PROTECTION PLANK

RIGID STRUTS(POSSIBILY STEEL)

PART. �A�

Lifting

Models �L�(mm)

�A�(m)

�B�(m)

�C�(m)

CRH / SRH 004 - 204 - 006 - 206 2006 1.7 ' 3.5 ' 8.5

CRH / SRH 007 - 207 - 008 - 011 3006 1.7 ' 4.5 ' 8.5

CRH / SRH 014 - 016 4006 1.7 ' 4.5 ' 8.5

Page 25: Matrix CRH 004

22

Fig. 4 --- Lifting instructions with straight shackle CRH/SRH 004---016

N.B: The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of thelifting gear and ropes and the condition and suitability of the aforementioned equipment.Lift the unit with a speed suitable for the load to be moved, so as not to damage the structure.

STRAIGHT SHACKLE Ø 14 (UNI 1947) �A� TYPE(OPTIONAL)

LIFTING SYSTEM WITHSTRAIGHT SHACKLE

PART. �A�

N.B.: LIFT IN THE BARICENTRE LINE �G� OF THE UNIT

”A1”

”A2”

PART. �A�

”G”

”Xg”

”Yg

”L”

”G”

Lifting

Models �L�(mm)

�A1 + A2�(m)

CRH / SRH 004 - 204 - 006 - 206 2006 ' 5.5

CRH / SRH 007 - 207 - 008 - 011 3006 ' 6.5

CRH / SRH 014 - 016 4006 ' 6.5

Page 26: Matrix CRH 004

23

Baricentre �G� --- CRH/SRH 004---016

Unit baricentre position �G� --- (without water)

Models Without tank With tankModels�Xg�(m)

�Yg�(m)

�Xg�(m)

�Yg�(m)

CRH 004 0.83 0.58 0.89 0.58CRH 204 0.79 0.62 Not available

CRH 006 0.80 0.56 0.86 0.56

CRH 206 0.78 0.62 Not available

CRH 007 1.22 0.59 1.32 0.59

CRH 207 1.18 0.64 Not available

CRH 008 1.17 0.63 1.25 0.63CRH 011 1.10 0.63 1.18 0.62

CRH 014 1.50 0.64 1.62 0.63

CRH 016 1.45 0.63 1.57 0.63

SRH 004 0.86 0.60 0.92 0.60

SRH 204 0.82 0.64 Not available

SRH 006 0.83 0.58 0.89 0.59

SRH 206 0.82 0.64 Not available

SRH 007 1.27 0.63 1.36 0.62

SRH 207 1.23 0.67 Not available

SRH 008 1.22 0.66 1.30 0.65SRH 011 1.16 0.65 1.23 0.65

SRH 014 1.58 0.67 1.68 0.66

SRH 016 1.53 0.67 1.64 0.66

Page 27: Matrix CRH 004

24

Fig. 5 --- Lifting instructions with tubes CRH/SRH 017---032

LIFTING TUBE(NOT SUPPLIED)(BASE HOLES Ø56)

BELTOR CHORD

BLOCKING PEG(NOT SUPPLIED)

SPLIT PIN(NOT SUPPLIED)

PROTECTION PLANK

RIGID STRUTS(POSSIBILY STEEL)

N.B: Place the lifting tubes in the holes in the base indicated by the words �LIFT HERE�. Lock the ends of the tubes in position withthe locking pins and split pins as shown above �A�.The capacity of the lifting gear must be adequate to lift the load in question. Check the weight of the unit, the capacity of thelifting gear and ropes and the condition and suitability of the aforementioned equipment. Lift the unit with a speed suitablefor the load to be moved, so as not to damage the structure.

Lifting

Models �A�(m)

�B�(m)

�C�(m)

CRH 017 - 020 - 023 - 025 - 028 - 030 - 0321 0 5 5 9 0

SRH 017 - 020 - 023 - 025 - 028 - 030 - 0321.0 ' 5.5 ' 9.0

Page 28: Matrix CRH 004

25

Fig. 6 --- Support positions and loads (Note: weights refer to standard units)

CRH/SRH 004 - 016

120 120

1711

6117

d=14

”A”

1195

”C” ”C”

”D” ”E” ”D”

W1 W2 W3 W4 W5

W10W9W8W7W6

”B”

3411

2734

FOOT PRINT

Dimensions --- CRH/SRH 004 --- 016

Dimensions (mm) A B C D E

Model Size

CRHSRH

004 --- 204 --- 006 --- 206004 --- 204 --- 006 --- 206 2000 1760 --- --- ---

CRHSRH

007 --- 207 --- 008 --- 011007 --- 207 --- 008 --- 011 3000 --- 1380 --- ---

CRHSRH

014 --- 016014 --- 016 4000 --- --- 1160 1440

Weight distribution --- CRH/SRH 004 --- 016

Weight distribution (kg) W 1 W 2 W 3 W 4 W 5 W 6 W 7 W 8 W 9 W 10

Model Size

CRH 004 221 --- --- --- 151 241 --- --- --- 165

204 276 --- --- --- 173 262 --- --- --- 164

006 238 --- --- --- 151 276 --- --- --- 176

206 283 --- --- --- 174 269 --- --- --- 165

007 240 --- 137 --- 137 246 --- 140 --- 140

207 288 --- 152 --- 152 253 --- 134 --- 134

008 314 --- 164 --- 164 285 --- 149 --- 149

011 369 --- 169 --- 169 338 --- 155 --- 155

014 299 299 --- 136 136 265 265 --- 121 121

016 320 320 --- 136 136 285 285 --- 121 121

SRH 004 254 --- --- --- 193 241 --- --- --- 183

204 308 --- --- --- 215 262 --- --- --- 182

006 271 --- --- --- 192 275 --- --- --- 195

206 316 --- --- --- 216 268 --- --- --- 184

007 280 --- 186 --- 186 241 --- 161 --- 161

207 328 --- 203 --- 203 248 --- 154 --- 154

008 361 --- 222 --- 222 278 --- 171 --- 171

011 419 --- 227 --- 227 329 --- 178 --- 178

014 356 356 --- 198 198 265 265 --- 148 148

016 378 378 --- 197 197 284 284 --- 148 148

Page 29: Matrix CRH 004

26

Weight distribution with tank --- CRH/SRH 004 --- 016

Weight distribution (kg) W 1 W 2 W 3 W 4 W 5 W 6 W 7 W 8 W 9 W 10

Model Size

CRH 004 271 --- --- --- 257 288 --- --- --- 272

204 Not available

006 289 --- --- --- 255 322 --- --- --- 285

206 Not available

007 230 --- 219 --- 219 235 --- 223 --- 223

207 Not available

008 334 --- 289 --- 289 312 --- 270 --- 270

011 389 --- 294 --- 294 365 --- 277 --- 277

014 310 310 --- 260 260 283 283 --- 238 238

016 331 331 --- 259 259 304 304 --- 238 238

SRH 004 301 --- --- --- 300 290 --- --- --- 289

204 Not available

006 320 --- --- --- 298 323 --- --- --- 302

206 Not available

007 267 --- 267 --- 273 237 --- 237 --- 243

207 Not available

008 375 --- 350 --- 350 311 --- 290 --- 290

011 433 --- 354 --- 354 362 --- 297 --- 297

014 362 362 --- 326 326 289 289 --- 259 259

016 385 385 --- 325 325 308 308 --- 260 260

Page 30: Matrix CRH 004

27

Fig. 7 --- Support positions and loads (Note: weights refer to standard units)

Dimensions --- CRH/SRH 017 --- 032

Dimensions (mm) A B

Model Size

CRH / SRH 017 --- 020 3750 1000

CRH / SRH 023 --- 025 4750 1500

CRH / SRH 028 --- 030 --- 032 5750 2000

Weight distribution --- CRH/SRH 017 --- 032

Weight distribution (kg) W 1 W 2 W 3 W 4 W 5 W 6 W 7 W 8

Model Size

CRH 017 196 196 233 233 261 261 310 310

020 203 203 250 250 274 274 337 337

023 240 240 327 327 312 312 427 427

025 240 240 327 327 312 312 427 427

028 273 273 382 382 345 345 482 482

030 281 281 383 383 368 368 502 502

032 280 280 393 393 371 371 520 520

SRH 017 252 252 283 283 293 293 328 328

020 259 259 300 300 306 306 355 355

023 305 305 395 395 348 348 450 450

025 305 305 395 395 348 348 450 450

028 351 351 463 463 385 385 508 508

030 359 359 471 471 402 402 528 528

032 358 358 482 482 405 405 545 545

Weight distribution with tank --- CRH/SRH 017 --- 032

Weight distribution (kg) WT1 W 1 W 2 W 3 W 4 WT2 W 5 W 6 W 7 W 8

Model Size

CRH 017 443 443 261 261 261 462 462 273 273 273

020 440 440 279 279 279 467 467 296 296 296

023 447 447 351 351 351 477 477 374 374 374

025 447 447 351 351 351 477 477 374 374 374

028 460 460 400 400 400 489 489 425 425 425

030 464 464 403 403 403 508 508 441 441 441

032 460 460 412 412 412 507 507 455 455 455

SRH 017 478 478 309 309 309 467 467 302 302 302

020 475 475 326 326 326 473 473 325 325 325

023 486 486 413 413 413 482 482 410 410 410

025 486 486 413 413 413 482 482 410 410 410

028 507 507 475 475 475 496 496 464 464 464

030 508 508 485 485 485 505 505 483 483 483

032 504 504 494 494 494 505 505 496 496 496

CRH/SRH 017 - 032

60

WA WB

WDWC

1000

125

120

1060

120

750 125

1180

60

1300

d = 20

1300

W6 W7 W8

W1 W2 W3 W4

W5

”A”

125 ”B” 1500 ”B” 125

WT1

WT2

1000

125 875

d = 20

120

1060

120

6011

8060

FOOT PRINT

WA = WB = 406 kgWC = WD = 299 kg

Tank(supply not mounted on unit)

TANKMOUNTED(OPTION)

FOOT PRINT

Page 31: Matrix CRH 004

28

Fig. 8 --- Rubber anti---vibration support + 1000 liters tank

Unit base

Rubber support dimensions Rubber support installation

CF

A

B

S

L

F

P

G

Fixing screw

Screw anchor(not supplied)

Cement base

Access hole forsupport fixing

Single support code

Code A(mm)

B(mm)

P(mm)

F(mm)

CF(mm)

G(mm)

L(mm)

S(mm)

270327 82 35 M10 11.0 110 60 128 2

270326 108 50 M16 16.5 160 83 190 5

Rubber supports + 1000 liters tank

Unit Configuration Supportkit code

Single supportcode

Kit supportpieces

CRH --- SRH204---206---004---006 485620 4

CRH --- SRH207---007---008---011

With or withouttank 485621 270327 6

CRH --- SRH014---016

ta

485622 8

CRH --- SRH017---020---023---025---028---030---032 Without tank 485625

2703268

CRH --- SRH017---020---023---025---028---030---032 With tank 485626

27032610

1000 liters tank Loose supplied 485620 270327 4

Each kit is complete with stainless steel fixing screws and plain washers for unit assembly.

Page 32: Matrix CRH 004

29

Fig.9---OveralldimensionsCRH/SRH004---016

Rightairdischarge

(movethe�A�with�B�panel/s)

Overairdischarge

(Standardsupply)

Leftairdischarge

(movethe�A�with�C�panel/s)

X Y

236±5

699±5

X Y

WZ

M

M

M

M

MM

M M

M

MM

MM

M

M

E

E

E

F

Ext.

A

CB

699±5

==

151352

1739

151 352Ext. 1739

158352Ext.691

30

3030

875

852Ext.

279

148

852Ext.279

148

852Ext.279

875

852Ext.

279

148

852Ext.

279

148

852Ext.

279

875

279

148

279

148

852Ext.279

1201

600 1642

2242

132

140802022

1522720

430,5170600,5

==

�A�+40

1101501

30

11030144130

769

30

942

30

1942

30

2942

30

30

30(Opt.)

30

�A�

236±5

Supplycableinlet

(Prepunchø67+ø30)

Fanandholepanelnot

presentonmod.007-207

�A�+40(Heatrecovery,Opt.) 852Ext.

852Ext.

Fanandholepanelnot

presenton

mod.007-207

Flanged(Opt.)

Frontview

Topview

Lateralview

Rearview

(withheatrecovery)

Rearview

(Std.unit)

Lateralview

(from�D�)

MM

MM

M

MM

M

Flanged(Opt.)

Flanged(Opt.)

Flanged

(Opt.)

�D�

DuctFlanged(Opt.),

notpossiblewithcoilmetalfilters

Coilmetalfilters(Opt.),notpossible

withductedflange

M

Airflow

Removablepanel

A B C E F

Flanged(Opt.)

Electricpaneland

controlunit

(rearfront

removablepanel)

Fanandholepanelnot

presentonmod.007-207

Page 33: Matrix CRH 004

30

Tab.10---ChilledwaterconnectionCRH/SRH004---016

j=Standard,withtank,with

tank+pump/s

CRH/SRH

004---204(*)---006---206(*)

CRH/SRH

007---207(*)---008---011

CRH/SRH

014---016

pp

J=Withpump/s(withouttank)

jJ

jJ

jJ

�A�

mm

2006

3006

4006

Fansnumber

---1

1(007---207)---2(008---011)

3

Chilledwater

XInlet

2�Gasmale

Outlet

2�Gasmale

Inlet

2�Gasmale(mod.007---207)

21/ 2�Gasmale(mod.008---011)

Outlet

2�Gasmale(mod.007---207)

21/ 2�Gasmale(mod.008---011)

Inlet

21/ 2�Gasmale

Outlet

21/ 2�Gasmale

Chilledwater

connection

YOutlet

2�Gasmale

Inlet

2�Gasmale

Outlet

2�Gasmale(mod.007---207)

21/ 2�Gasmale(mod.008---011)

Inlet

2�Gasmale(mod.007---207)

21/ 2�Gasmale(mod.008---011)

Outlet

21/ 2�Gasmale

Inlet

21/ 2�Gasmale

(*)ON204---206---207MODELS,TANKVERSIONWITH/WITHOUTPUMPISNOTAVAILABLE

Tab.11---Heatrecoverywaterconnection(optional)CRH/SRH004---016

Models

CRH

004---006---007---204---206---207

SRH

004---006---007---204---206---207

CRH

008---011---014---016

SRH

008---011---014---016

Partial

heatrecoveryinlet

W1�Gasmale

1�Gasmale

11/ 4�Gasmale

11/ 4�Gasmale

Total

heatrecoveryinlet

W2�Gasmale

Notavailable

21/ 2�Gasmale

Notavailable

Partial

heatrecoveryoutlet

Z1�Gasmale

1�Gasmale

11/ 4�Gasmale

11/ 4�Gasmale

Total

heatrecoveryoutlet

Z2�Gasmale

Notavailable

21/ 2�Gasmale

Notavailable

Page 34: Matrix CRH 004

31

Fig.10---OveralldimensionsCRH/SRH017---032

BC

A

EM

MM

M MM

M

M M

M M

M

M M

M M

MM

MM

MM

Z W X Y

MX Y

180035288

1791382Ext.

3030 30(Opt.)

850

352

98

180035288

1300

2240

459

832Ext.168

168

459

168

459

168

459

30

2557651220

1185

115

MM

MM

M

MM

MM

M

M

M

M

M

EE

E

E

F

459

832Ext.168

168

459

168

459

168

459

405

4940Ext.

405

3940Ext.

405

2940Ext.

405

459

168

168

459

168

459168

832Ext.

459

1791382Ext.

679

�A�

60

MXWZ Y

255765300765155

1185

115

Rearview

(from�D�)

Topview

Frontview

Rightlateral

view

Leftlateralview

(Std.unit)

Leftlateralview

(withheatrecovery)

Flanged(Opt.)

Electricpanelandcontrolunit

(behindfrontremovablepanel)

832Ext.

832Ext.

832Ext.

832Ext.

Part.G

Heatrecovery

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

Flanged(Opt.)

Flanged(Opt.)

Flanged(Opt.)

Flanged(Opt.)

Heatrecoveryandstd.pipeprojection

�D�

�N�

60

YX

Victaulic

coupling

Unitconnecting

pipe

Unitoverallframe(�A�)

YX�N�View

PART.G

UNITCONNECTINGSYSTEM

Part.L

Part.H

2108090

102

27

27

Supplycableinlet

(PrepunchsNo2ø67-N

o1ø30)

Part.H

Part.L

2940Ext.

3940Ext.

4940Ext.

Flanged(Opt.)

1382Ext.Flanged(Opt.)

Planefor

canalizationfixingall

aroundtheopening

Rightairdischarge(movethe�A�with�B�panel/s)

Overairdischarge(Standardsupply)

Leftairdischarge(movethe�A�with�C�panel/s)

DuctFlanged(Opt.),notpossiblewithcoilmetalfilters

Coilmetalfilters(Opt.),notpossiblewithductedflange

M

Airflow

Removablepanel

A B C E F

Page 35: Matrix CRH 004

32

Tab.12---ChilledwaterconnectionCRH/SRH017---032

Models

CRH/SRH

017---020

CRH/SRH

023---025

CRH/SRH

028---030---032

�A�

mm

3750

4750

5750

Fansnumber

---3

45

Chilledwater

XInlet

DN80---3�---88.9mm

Inlet

DN80---3�---88.9mm

Inlet

DN80---3�---88.9mm

Chilledwater

connection

YOutlet

DN80---3�---88.9mm

Outlet

DN80---3�---88.9mm

Outlet

DN80---3�---88.9mm

Tab.13---Heatrecoverywaterconnection(optional)CRH/SRH017---032

Models

CRH

017---020---023---025---028---030---032

SRH

017---020---023---025---028---030---032

Partial

heatrecoveryinlet

W2�Gasmale

2�Gasmale

Total

heatrecoveryinlet

WDN80---3�---88.9mm

(likePart.�G�)

Notavailable

Partial

heatrecoveryoutlet

Z2�Gasmale

2�Gasmale

Total

heatrecoveryoutlet

ZDN80---3�---88.9mm

(likePart.�G�)

Notavailable

Page 36: Matrix CRH 004

33

Fig.11---OverallDimensions(withtank)CRH/SRH017---032

Overairdischarge

(standardsupply)

BC

A

EM

MM

M MM

M

M M

M M

M

M M

M M

M M

MM

MM

MM

M

X Y

X Y

M

180035288

1791382Ext.

3030 30(Opt.)

850

352

98

180035288

1300

2240

459

832Ext.168

168

459

168

459

168

459

30

1185

1152551065920

1000

MM

MM

M

MM

MM

M

M

M

M

M

EE

E

E

F

M

459

832Ext.168

168

459

168

459

168

459

405

4940Ext.

405

3940Ext.

405

2940Ext.

405

459

168

168

459

168

459

168

832Ext.

459

1791382Ext.

679

60

Electricpanelandcontrolunit

(behindfrontremovablepanel)

�A�832Ext.

832Ext.

832Ext.

832Ext.

Part.G

Frontview

Topview

Rearview

(from�D�)

Rightlateral

view

Leftlateralview

Flanged(Opt.)

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

832Ext.

Flanged(Opt.)

Flanged(Opt.)

Flanged(Opt.)

Flanged(Opt.)

�D�

Part.H

Part.L

2108090

102

Supplycableinlet

(Prepunchs

No2ø67-N

o1ø30)

27

272940Ext.

3940Ext.

4940Ext.

Flanged(Opt.)

1382Ext.

Flanged(Opt.)

Planefor

canalizationfixingall

aroundtheopening

Part.L

�N�

60

YX

Victaulic

coupling

Unitconnecting

pipe

Unitoverallframe(�A�)

YX�N�View

PART.G

UNITCONNECTINGSYSTEM

Rightairdischarge

(movethe�A�with�B�panel/s)

Leftairdischarge

(movethe�A�with�C�panel/s)

DuctFlanged(Opt.),

notpossiblewithcoilmetalfilters

Coilmetalfilters(Opt.),

notpossiblewithductedflange

M

Airflow

Removablepanel

A B C E F

Part.H

Inlet/Outletpipes

projection

Page 37: Matrix CRH 004

34

Tab.14---Chilledwaterconnection(withtank)CRH/SRH017---032

Models

CRH/SRH

017---020

CRH/SRH

023---025

CRH/SRH

028---030---032

�A�

mm

4750

5750

6750

Fansnumber

---3

45

Chilledwater

XInlet

DN80---3�---88.9mm

Inlet

DN80---3�---88.9mm

Inlet

DN80---3�---88.9mm

Chilledwater

connection

YOutlet

DN80---3�---88.9mm

Outlet

DN80---3�---88.9mm

Outlet

DN80---3�---88.9mm

Page 38: Matrix CRH 004

35

Fig. 12 ---Refrigerant circuit (std.) with partial recovery (opt.)CRH/SRH 004---006---007

HEAT RECOVERY WATER OUTLET1� GAS MALE (OPT.)

HEAT RECOVERY WATER INLET1� GAS MALE (OPT.)

MC

1

T

T

FG

2

4

5 6 3

7

88

9

11

12

13

14

15

16

17

18

20

19

19

19

22

21

19

10

CHILLED WATER INLET2� GAS MALE

CHILLED WATER OUTLET2� GAS MALE

19

Refrigerant components

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorPartial recovery heat exchanger (Opt.)Antifreeze heater (Std. with heat recovery)

Page 39: Matrix CRH 004

36

Fig. 13 ---Refrigerant circuit (std.) with partial recovery (opt.)CRH/SRH 204---206---207---008---011---014---016

MC

1

2

4

5 3

7

8

15

16

17

20

19

19

21

25

7

8

9

15

19

19

22

21

18

6 3 6

MC

1

4

FG

11

12

13

14

19

11

12

13

19

19

10

19

10

22

FG14T

T

19 19

CHILLED WATERINLET

ØH --- GAS MALE

HEAT RECOVERYWATER INLET

ØG --- GAS MALE (OPT.)

HEAT RECOVERY WATER OUTLETØG --- GAS MALE (OPT.)

CHILLED WATER OUTLETØH --- GAS MALE

CRH/SRH204 206 207 008 011 014 016

Ø G 1� 1� 1� 11/4� 11/4� 11/4� 11/4�

Ø H 2� 2� 2� 21/2� 21/2� 21/2� 21/2�

Refrigerant components

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorPartial recovery heat exchanger (Opt.)Antifreeze heater (Std. with heat recovery)

Page 40: Matrix CRH 004

37

Fig. 14 ---Refrigerant circuit with total recovery (opt.)CRH 004---006---007

MC

T

T

FG

HEAT RECOVERY WATER OUTLET2� GAS MALE

HEAT RECOVERYWATER INLET2� GAS MALE

CHILLED WATER INLET2� GAS MALE

CHILLED WATER OUTLET2� GAS MALE

ONLY FOR:CRH 004---006---007

25

7

9

25

22

8 8

19

11

12

14

13

19 2 5 36

4

1

19

15 19

16

18

20

23

24

2110

19

17

25

ONLY FOR:CRH 007

Refrigerant components

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122232425

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorTotal recovery heat exchangerThree way valveNon return valveAntifreeze heaterLiquid receiver

Page 41: Matrix CRH 004

38

Fig. 15 ---Refrigerant circuit with total recovery (opt.)CRH 204---206---207---008---011---014---016

HEAT RECOVERYWATER OUTLETØG --- GAS MALE

CHILLED WATERINLET

ØH --- GAS MALE

HEAT RECOVERYWATER INLETØG --- GAS MALE

MC

T

T

MC

FG FG

CHILLED WATER OUTLETØH --- GAS MALE

25 25

9

8 8

25 2519

11

12

14

19

13

11

12

14

19

19

13

2 5 5 23 66 3

19 19

1919

18

20

41

41

22 22

19

10

19

10

23 23

2424

21 21

16

17

1515

7 7

ONLY FOR:CRH 207---008---011---014---016

ONLY FOR:CRH 207---008---011---014---016

CRH204 206 207 008 011 014 016

Ø G 2� 2� 2� 21/2� 21/2� 21/2� 21/2�

Ø H 2� 2� 2� 21/2� 21/2� 21/2� 21/2�

Refrigerant components

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122232425

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorTotal recovery heat exchangerThree way valveNon return valveAntifreeze heaterLiquid receiver

Page 42: Matrix CRH 004

39

Fig. 16 ---Refrigerant circuit (std.) with partial recovery (opt.)CRH/SRH 017---020---023---025---028---030---032

HEAT RECOVERY WATER OUTLET2� GAS MALE (OPT.)

9

MC

8

44

1144

11

3 66

3

77

22

5

MC

MC

MCFGFG

T

T

2222

10

19

10

19

19

19

1919

19 19

19

19

21 21

1111

1212

1515

17

16

18

20

13 13

14 14

1919

2

5

2

HEAT RECOVERY WATER INLET2� GAS MALE (OPT.)

CHILLED WATER INLETVICTAULIC COUPLINGDN 80 --- 3� --- 88.9 mm

CHILLED WATER OUTLETVICTAULIC COUPLINGDN 80 --- 3� --- 88.9 mm

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorPartial recovery heat exchanger (Opt.)Antifreeze heater (Std. with heat recovery)

Page 43: Matrix CRH 004

40

Fig. 17 ---Refrigerant circuit with total recovery (opt.)CRH 017---020---023---025---028---030---032

T

TMC

MC

MC

MC

HEAT RECOVERYWATER OUTLET

VICTAULIC COUPLING (OPT.)DN 80 --- 3� --- 88.9 mm

HEAT RECOVERYWATER INLET

VICTAULIC COUPLING (OPT.)DN 80 --- 3� --- 88.9 mm

CHILLED WATER INLETVICTAULIC COUPLINGDN 80 --- 3� --- 88.9 mm

CHILLED WATER OUTLETVICTAULIC COUPLINGDN 80 --- 3� --- 88.9 mm

NOT PRESENT FOR:CRH 017---020

NOT PRESENT FOR:CRH 017---020

FG FG

1919

19 19

19

19

19

19

24 24

2424

11 11

5 56

61819 19

3

3

2 2 2 2

23 23

13

13

13

13

77

8

9

19

10

19

10

21

22

15 15

17

20

16 1313

14141

1

4

4

1

4

4

1

1212

Item Description Item Description

1234567891011121314

CompressorHigh pressure switch (HP)Low pressure switch (LP)Crankcase heaterHigh pressure manometer (Opt.)Low pressure manometer (Opt.)Safety valveCondenserFan(s)Pressure transducerShut---off valveFilter dryerShut---off solenoid valveSight glass

1516171819202122232425

Thermostatic expansion valveEvaporatorAntifreeze heater (Opt.)Control temperature sensorCharge connectionAntifreeze sensorTotal recovery heat exchangerThree way valveNon return valveAntifreeze heaterLiquid receiver

Page 44: Matrix CRH 004

41

Fig. 18 ---Hydraulic circuit --- CRH 004---006---007---204---206---207

1

2

5 56

7

48

9

4

3

10

16

13

15T

11

12TF

18

LIEBERT---HIROSS UNIT

ONLY WITH PUMP VERSION

ONLY WITH TANK VERSION

CHILLED WATER INLET2� GAS MALE

CHILLED WATER OUTLET2� GAS MALE

11

1

12

2

TT

NOT AVAILABLE IN204---206---207 MODELS

ONLY FOR 204---206---207 MODELS

ONLY FOR 004---006---007 MODELS

F

14a

14b

Hydraulic components

Item Description Item Description

12345678910

EvaporatorEvaporator antifreeze heater (Opt.)Rubber flexible pipe (only with pumps and/or tank))Manual air valveGate valvePumpSafety valveExpansion tankService ball valveDrain valve

11121314a14b15161718

Control temperature sensorAntifreeze temperature sensorTank antifreeze heater (Opt.)Flow switch (unit without tank, Opt. without pumps)Flow switch (unit with tank, Opt. without pumps)Rubber flexible pipe (only with pumps, without tank)Filter (Opt.)Non return valveExpansion tank + Safety valve (Opt. without tank)

Page 45: Matrix CRH 004

42

Fig. 19 ---Hydraulic circuit --- CRH 008---011---014---016

CHILLED WATER INLET21/2� GAS MALE

11

1

7

48

9

3

10

13

12

4

6

65

517

17

2

16

15F

18

TT

ONLY WITH PUMP VERSION

ONLY WITH TANK VERSION

CHILLED WATER OUTLET21/2� GAS MALE

LIEBERT---HIROSS UNIT

F

14a

14b

Hydraulic components

Item Description Item Description

12345678910

EvaporatorEvaporator antifreeze heater (Opt.)Rubber flexible pipe (only with pumps and/or tank))Manual air valveGate valvePumpSafety valveExpansion tankService ball valveDrain valve

11121314a14b15161718

Control temperature sensorAntifreeze temperature sensorTank antifreeze heater (Opt.)Flow switch (unit without tank, Opt. without pumps)Flow switch (unit with tank, Opt. without pumps)Rubber flexible pipe (only with pumps, without tank)Filter (Opt.)Non--- return valveExpansion tank + Safety valve (Opt. without tank)

Page 46: Matrix CRH 004

43

Fig. 20 ---Hydraulic circuit --- SRH 004---006---007---204---206---207

2

5 56

4

11

1

7

48

9

10

13

12

16

3

15

44

1010

20

19

1822

21

F

23

23

23

23

2323

24

22 T

T

TT

ONLY WITH PUMP VERSION

ONLY WITH TANK VERSION

CHILLED WATER INLET2� GAS MALE

CHILLED WATER OUTLET2� GAS MALE

LIEBERT---HIROSS UNIT

11

1

12

2

TT

ONLY FOR 204---206---207 MODELS

ONLY FOR 004---006---007 MODELS

NOT AVAILABLE IN204---206---207 MODELS

F

14a

14b

Hydraulic components

Item Description Item Description

12345678910111213

EvaporatorEvaporator antifreeze heater (Opt.)Rubber flexible pipe (only with pumps and/or tank))Manual air valveGate valvePumpSafety valveExpansion tankService ball valveDrain valveControl temperature sensorAntifreeze temperature sensorTank antifreeze heater (Opt.)

14a14b15161718192021222324

Flow switch (unit without tank, Opt. without pumps)Flow switch (unit with tank, Opt. without pumps)Rubber flexible pipe (only with pumps, without tank)Filter (Opt.)Non return valveAir temperature sensor3---way valveFreecooling control temperature sensorFan(s)Freecooling coilRubber flexible pipeExpansion tank + Safety valve (Opt. without tank)

Page 47: Matrix CRH 004

44

Fig. 21 ---Hydraulic circuit --- SRH 008---011---014---016

11

1

7

48

9

10

13

12

46

65

517

17

2

16

3

15

20

19

F

44

1010

182222

21

23

23

23

23

24

T

T

TT

CHILLED WATER INLET21/2� GAS MALE

ONLY WITH PUMP VERSION

ONLY WITH TANK VERSION

CHILLED WATER OUTLET21/2� GAS MALE

LIEBERT---HIROSS UNIT

F

14a

14b

Hydraulic components

Item Description Item Description

12345678910111213

EvaporatorEvaporator antifreeze heater (Opt.)Rubber flexible pipe (only with pumps and/or tank))Manual air valveGate valvePumpSafety valveExpansion tankService ball valveDrain valveControl temperature sensorAntifreeze temperature sensorTank antifreeze heater (Opt.)

14a14b15161718192021222324

Flow switch (unit without tank, Opt. without pumps)Flow switch (unit with tank, Opt. without pumps)Rubber flexible pipe (only with pumps, without tank)Filter (Opt.)Non--- return valveAir temperature sensor3---way valveFreecooling control temperature sensorFansFreecooling coilRubber flexible pipeExpansion tank + Safety valve (Opt. without tank)

Page 48: Matrix CRH 004

45

Fig.22---Hydrauliccircuit---CRH017---020---023---025---028---030---032

T

M2

M1

M1

ONLYWITHTWIN

PUMPVERSION

LIEBERT---HIROSSBASEUNIT

ONLYWITHSINGLE

PUMPVERSION

UNITFRAME(WITHASSEMBLEDTANK)

UNITFRAME(WITHOUTTANK)

TANKFRAME

ONLYWITHWATERTANKVERSION

ASSEMBLYWITHUNIT

OPTION:

WATERTANKNOTASSEMBLY

WITHUNIT

T

F

10

5

7

5

4

9

13

45

56

49

13

10

3

8

14

11 12

1 2

15

15

WATERTANKOUTLET---

VICTAULICCONNECTION

DN80---3�---88.9mm

WATERTANKINLET---

VICTAULIC

CONNECTION

DN80---3�---88.9mm

CHILLEDWATERINLET

VICTAULICCONNECTION

DN80---3�---88.9mm

CHILLEDWATEROUTLET

VICTAULICCONNECTION

DN80---3�---88.9mm

p16

Hydrauliccomponents

Item

Description

Item

Description

1 2 3 4 5 6 7 8 9 10

Evaporator

Evaporatorantifreezeheater(Opt.)

Filter(Opt.)

Manualairvalve

Butterflyvalve

Singlepump

Twinpump

Expansiontank+Safetyvalve(Opt.)

Manometer

Dischargevalve

11 12 13 14 15 16

Controltemperaturesensor

Antifreezetemperaturesensor

Tankantifreezeheater(Opt.)

Flow

switch(Opt.withoutpumps)

Servicevalvewithcap

Differentialtrasducer(onlywithelectronicpump)

Page 49: Matrix CRH 004

46

Fig.23---Hydrauliccircuit---SRH017---020---023---025---028---030---032

T

M2

M1

M1

ONLYWITHTWIN

PUMPVERSION

LIEBERT---HIROSSBASEUNIT

ONLYWITHSINGLE

PUMPVERSION

UNITFRAME(WITHASSEMBLEDTANK)

UNITFRAME(WITHOUTTANK)

TANKFRAME

ONLYWITHWATERTANKVERSION

ASSEMBLYWITHUNIT

OPTION:

WATERTANKNOTASSEMBLY

WITHUNIT

T

F

10

5

7

5

4

9

13

55

6

49

13

10

3

8

14

11 121

2

T

+

T

204

10

17

19 18

16

15

15

WATERTANKOUTLET---

VICTAULICCONNECTION

DN80---3�---88.9mm

WATERTANKINLET---

VICTAULIC

CONNECTION

DN80---3�---88.9mm

CHILLEDWATERINLET

VICTAULICCONNECTION

DN80---3�---88.9mm

CHILLEDWATEROUTLET

VICTAULICCONNECTION

DN80---3�---88.9mm

p21 15

Hydrauliccomponents

Item

Description

Item

Description

1 2 3 4 5 6 7 8 9 10

Evaporator

Evaporatorantifreezeheater(Opt.)

Filter(Opt.)

Manualairvalve

Butterflyvalve

Singlepump

Twinpump

Expansiontank+Safetyvalve(Opt.)

Manometer

Dischargevalve

11 12 13 14 15 16 17 18 19 20 21

Controltemperaturesensor

Antifreezetemperaturesensor

Tankantifreezeheater(Opt.)

Flow

switch(Opt.withoutpumps)

Servicevalvewithcap

Freecoolingcoil

Airtemperaturesensor

3wayvalve

Controlfreecoolingthermostatsensor

Fans

Differentialtrasducer(onlywithelectronicpump)

Page 50: Matrix CRH 004
Page 51: Matrix CRH 004

PrintedinItalybyLiebertHIROSS

S.pA.

IssuedbyT.D.Service

Since the Liebert HIROSS Company has a policy of continuousproduct improvement, it reserves the right to change design andspecifications without previous notice.

Il Fabbricante dichiara che questo prodotto è conforme alle direttive Europee:The Manufacturer hereby declares that this product conforms to the European Union directives:Der Hersteller erklärt hiermit, dass dieses Produkt den Anforderungen der Europäischen Richtlinien gerecht wird:Le Fabricant déclare que ce produit est conforme aux directives Européennes:El Fabricante declara que este producto es conforme a las directivas Europeas:O Fabricante declara que este produto está em conformidade com as directivas Europeias:Tillverkare försäkrar härmed att denna produkt överensstämmer med Europeiska Uniones direktiv:De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is:Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU-direktiivien vaatimukset:Produsent erklærer herved at dette produktet er i samsvar med EU-direktiver:Fabrikant erklærer herved, at dette produkt opfylder kravene i EU direktiverne:Ο ΚατασÀευαστÞj δηλþνει üτι το παÃüν πÃοΪüν εßναι ÀατασÀευασmÝνο αýmφωνα mε τιj οδηγßεj τηj Ε.Ε.:

98/37/CE; 89/336/CEE; 73/23/CEE; 97/23/CE

Page 52: Matrix CRH 004

Zona Industriale TognanaVia Leonardo da Vinci, 16/1835028 Piove di Sacco (PD)

ITALY

Liebert HIROSSis a division ofEMERSON

Tel. +39 049 9719111Telefax +39 049 5841257

Internet : www.liebert-hiross.com

PrintedinItalybyLiebertHIROSS

S.pA.

IssuedbyT.D.Service

Since the Liebert HIROSS Company has a policy of continuousproduct improvement, it reserves the right to change design andspecifications without previous notice.


Recommended