Air Handling Systems
Air Handling Systems
The EDPAC Air Handling products are Modular in construction with 13 frame cross sections. Air flow
capacities range from 2500m3/hr (0.7m
3/s) to 90,000m
3/hr (25m
3/s). Each system is designed and
configured to suit a specific application and includes a combination of sections to match the specific
requirements of the application. This flexibility affords us significant latitude when seeking to match a
system with the constraints of your project – whether it is a low noise application requiring reduced
velocities or a compact unit size to meet restricted
available space.
Features and Options:
� Modular frame construction comprising profiled
aluminium section complete with flanges to
accommodate sealing gaskets.
� Doubleskin panels in 50mm or 25mm with plastic coated exterior and galvanised interior enclosing a
CFC free panel or rock wool liner as required. Thermal break is available with the 50mm panel
construction.
� Fan options that include EC direct drive fans (that do not require any control drives), or direct drive
backward curved fans and backward curved centrifugal fans with
optional VSD.
� Heat Recovery systems that can be thermal wheel, counter flow
heat exchanger or coil based.
� Heating sections that can be Low Pressure Hot Water, Direct
Expansion (when coupled to a Heat Pump), gas fired (natural or
LPG) or electric.
� Air Mixing utilising opposed blade dampers with appropriate edge
sealing.
� Pre-piping of coils including control valves, balancing devices and
isolation valves.
� Cooling sections that include coils mounted in stainless steel pans in
either chilled water or direct expansion, which can be coupled to a
chiller, heat-pump or condensing unit; cooling coils can be fitted with
droplet eliminators, if the design requires coil velocities in excess of
2.5m/s. Drain pans and coils can be removable to meet specific
requirements.
� Filter options include all grades of panels, bags and HEPA with factory DOP testing as required.
Air Handling Systems
� Roofing sections are also available for weathering purposes in a colour to match the panels.
� Attenuation is offered either within the system or as duct mounted. Selections can be made to meet
the lowest NR or PN criteria.
� Humidification options include evaporative, spray or electric.
� Driers or dehumidifiers can be integrated for material storage, test facilities or archives.
Controls:
The system can be supplied with or without controls as required.
We are happy to provide a system with full controls, pre-wired
and factory tested prior to shipping. The controls can be
integrated to any Building Management system available or
integrated to the facility fire alarm system, as required. Control
options include:
� Remote or local mounting of the MCC panel
� Factory fitting of actuators, sensors or valves
� Pre-wiring of VSD’s or EC Fans and MCC panels
� Control wiring / testing of Condensers or Heat-pumps
� BMS interfaces to Bacnet/IP, Modbus, Trend, Cirus, SNMP
The EDPAC control strategies have been developed over several years and include all of the features and
options expected within modern Air Handling Systems.
System Design:
All selections are made using our computerised AHU selection and design software. All coils and fans are
chosen to meet the specific customer conditions and requirements using proven computerised selection
software. All these data are made available with the Operation and Maintenance data provided at
handover.
Design parameters for cooling coil systems are typically based on airflow velocities of up to 2.5m/s over
the coil face. Higher velocities will typically require the use of droplet eliminators. For heating systems
only, face velocities of 3.5 m/s can be achieved. Drawing preparation and submittal can be made available
prior to sign-off and approval. All products are designed and manufactured in Carrigaline.
Air Handling Systems
Energy Saving Technologies:
EDPAC incorporates all current available energy savings technologies in our AHU’s;
these include:
� High efficiency heat recovery products including thermal wheels (TWE), plate
heat exchangers (PHE) and coil to coil recovery (CTC) products. PHE systems
are selected with Plate Heat Exchanger efficiencies in excess of 50% and
pressure drops over exchanger of less than 250Pa. TWE systems are selected
with Thermal Wheel exchanger efficiencies greater than 70 % and pressure
drop across the wheel less than 200 Pa.
� Free air cooling options are available and managed within our control
strategies.
� Free cooling options using integrated drycooler systems or appropriate
chillers.
� Use of energy efficient, brushless EC fan technology where their use permits (some high
pressure applications may limit their use).
� System design to meet specific criteria for Specific Fan Powers (SPF); SPF can be lowered
significantly with prudent design incorporating low air velocities with low total pressure
management of the system design.
� EC Fan technology or VSD management of fans/motors in
part load can reduce the energy consumption within the
system with energy consumption of less than 0.8W/l/sec
readily achievable.
� Fan speed control can in many cases eliminate the use of
volume control dampers and the associated energy losses
across them.
� Management of Specific Fan Power can be achieved using air path over sizing to reduce
power consumption through reduced system pressure – as power
consumption is a cubic relationship to fan speed, considerable
operating savings can be achieved with proper selection of the system
components and overall size.
� Smart system control strategies that include free-cooling, fan
management, set-back for heating or cooling and variable air volume
control also present operating savings.
Air Handling Systems
Configurations:
Final system configuration will depend on the specific requirements of the facility. The table outlines the
nominal capacities available in either heating or cooling.
Nominal Dimensions Cooling Capacities Heating Capacities
Model
Panel
Thickness
(mm)
WIDTH
(mm)
HEIGHT
(mm)
Airflow
(m3/s)
Cooling
kW
Airflow
(m3/s)
Heating
kW
E-10 PHE / TWE 25/50 800 800 0.7 21 1.0 29
E-15 PHE / TWE 25/50 1155 800 1.2 35 1.7 48
E-20 PHE / TWE 25/50 1155 1155 2.0 58 2.8 80
E-30 PHE / TWE 25/50 1510 1155 2.8 80 3.9 112
E-40 PHE / TWE 25/50 1510 1510 3.8 113 5.4 158
E-50 PHE / TWE 25/50 1865 1510 4.8 142 6.5 210
E-60 PHE / TWE 25/50 1865 1865 6.4 185 8.8 258
E-75 PHE / TWE 25/50 2220 1865 7.9 235 10.8 320
E-90 PHE / TWE 25/50 2220 2220 9.5 284 13.1 390
E-105 PHE / TWE 50 2575 2220 11.3 330 15.5 470
E-120 PHE / TWE 50 2930 2220 13.1 390 18.0 535
E-140 PHE / TWE 50 2930 2575 15.7 460 21.0 645
E-160 PHE / TWE 50 2930 2930 18.1 510 24.8 700
Notes:
a) Panel thicknesses of less than 50mm are only available on systems up to 2200mm wide or high;
b) Cooling Capacities are based on system velocities of 2.5m/s
c) Heating Capacities are based on system velocities of 3.5m/s.
d) PHE refers to Plate exchanger type and TWE refers to Thermal Wheel type.
Compliance and Standards:
All our Air Handling products are manufactured and assembled in Ireland in accordance with good design
and manufacturing practises; our Quality System is approved to ISO9001:2000 and our products are CE
certified to the Machinery and Low Voltage directives. Standard systems comply with the requirements of
BSEN13053:2006, Ventilation for buildings - Air handling units - Mechanical performance and
EN1886:1998, Ventilation for buildings - Air handling units - Mechanical performance. Other special
requirements can be catered for including HTM 3-01 (Health Technical Memorandum), Specialised
ventilation for healthcare premises or GMP systems.
Product Summary
Computer
Room Air
Conditioning
Air Handling Systems
Heat Recovery
EDPAC International Ltd
Carrigaline Industrial Park
Carrigaline, Co. Cork, Ireland
Tel: +353-21-4372850
Fax: +353-21-4373975
Email: [email protected]
http://www.edpac.com
ISO9001:2008