5/19/2018 Antiinsularizare RELEU MFR11
1/4
Product Specificatio
03244C
MFR 11
Multi Function Relay
Protection
APPLICATIONS
The MFR 1 Series is a family of industrialgrade protective relays that offer multipleprotective features in a single package.
Using a digital processor to measure true
RMS values enables a high degree ofmeasuring accuracy regardless ofharmonics, transients or disturbing pulses.
The MFR 11 model is a generator or mainsprotection unit packaged into one compactdevice. Typical applications are generatorsand switchgear equipment that requireindependent protection architecture. Differentpackages offer additional functionality.
The MFR 11/MPis for mains protection usewith over-/undervoltage, -frequency and
voltage asymmetry with 24 Vdc power supplywhile the MFR 11/NUhas the samefunctions, but utilizes a wide-range powersupply.
The MFR 11/VDEWadds phase/vector jumpmonitoring to the MP package. TheMFR 11/G59package adds df/dt (ROCOF)protection. The MFR 11/G59Nhas the samefeatures as the G59package, but utilizes thewide-range power supply.
The MFR 11/SCis used for synch-check and
zero voltage detection to check whether twosystems are synchronous or de-energized.
The compact size and multiple functions ofthe MFR 11 help to simplify switchgeardesign. The digital display offers a user-friendly interface to setup the unit as well asmonitor the operation and display anyalarms.
DESCRIPTION
Features(all versions) True RMS voltage
Configurable trip/control set points
Configurable delays for each alarm
Two-line LC display
MFR 11/MP 24 Vdc power supply
3 configurable relays
Over-/undervoltage monit. (59/27)
Over-/underfrequency monit. (81O/U)
Voltage asymmetry monitoring (47)
MFR 11/NUSame features as MFR 11/MP, plus:
Wide-range power supply (no 24 Vdc)(90 to 265 Vac/dc)
MFR 11/VDEWSame features as MFR 11/MP, plus:
Vector/phase shift monitoring (78)
MFR 11/G59Same features as MFR 11/MP, plus:
8 configurable relays
Vector/phase shift monitoring (78)
df/dt ROCOF monitoring (81RL)
MFR 11/G59NSame features as MFR 11/G59, plus:
Wide-range power supply (no 24 Vdc)
(90 to 265 Vac/dc)
MFR 11/SCSame features as MFR 11/MP, plus:
2 configurable relays
Synch-check (fixed to relay 3) (25)
Zero voltage monitoring: dead bus startfunctionality (close CB to dead busbar)
MFR 11/SC+NSame features as MFR 11/SC, but
Wide-range power supply (no 24 Vdc)(90 to 265 Vac/dc)
True RMS sens
Synch-check
Programmable routputs
Discrete inputs enabling or remacknowledgmen
PC and front paconfigurable
Microprocessortechnology foraccurate, repeaand reliableoperation
Programmablethreshold setpowith individual tidelays
CE marked
UL/cUL Listed
GL Approval
5/19/2018 Antiinsularizare RELEU MFR11
2/4
SPECIFICATIONS
Accuracy..........................................................................................Class 1Power supply.............................................................24 Vdc (18 to 30 Vdc)
Packages NU/G59N/SC+N: 90 to 265 Vac/dcIntrinsic consumption..................................................................max. 12 W
Ambient temperature................................................................-20 to 70 CAmbient humidity......................................................95 %, non-condensing
Voltage .........Rated /: [1] 66/115 Vac [4] 230/400 Vac [7] 398/690 VacMaximum value (Vmax): [1] 150 Vac [4] 300 Vac [7] 600 Vac
Rated voltage Vph-ground: [1] 150 Vac [4] 300 Vac [7] 400 VacRated surge voltage: [1] 2.5 kV [4] 4.0 kV [7] 4.0 kV
Linear measuring range up to.......................................................1.3VratedMeasuring frequency................................................50/60 Hz (40 to 70 Hz)
Input resistance................................[1] 0.21 M, [4] 0.7 M, [7] 1.04 MMax. power consumption per path................................................ < 0.15 WDiscrete inputs .............................................................................. isolatedInput range....................................................................18 to 250 Vac or dc
Input resistance.....................................................................approx. 68 k
Relay out puts ................................................................................ isolaContact material...............................................................................AgCLoad (GP).................................................24 Vdc@2 Adc, 250 Vac@2 Pilot duty (PD)......................................................................24 Vdc@1 Housing ......................................................Type APRANORM DIN 43 Dimensions.........................................................................9672130 Front cutout.................................................................................9167 Connection................................................ screw/plug terminals depend
on connector 1.5 mm or 2.5 mFront................................................................................. insulating surfProtection system................................................................................ IPWeight............................................... depending on version, approx. 80Disturbance test(CE).................................................. tested accordin
applicable EN guidelListings .....................................UL/cUL listed (note: max. voltages ap
for ordinary loc., file E212App rovals ........................................................... GL (Germanischer Llo
DIMENSIONS
Front view
2005-09-09 | MFR 11 Dimensions r1ww-3605-ab.sk
50 mm130 mm
96mm
8
90mm
130mm
72mm
65mm
27mm
35mm
Back view withconnecting terminals
Bottom view
Back plate mountingoptional (please order
brackets P/N 8923-1023)
Configuration port
Configuration port
1 16
70 75
32 17
Configuration port
5/19/2018 Antiinsularizare RELEU MFR11
3/4
WIRING DIAGRAM
superv
ise
dsys
tem
(varia
ble)
Subject to technical modifications.
7
8
CB
3/4
Relay 2
Relay 1(Ready for operation)
2005-09-13 | MFR 11 Wiring Diagram r13ww-3705-ap.sk
12
11
10
9
13
16
15
14
Pac
k.
SC
5
6
70
71
72
1
2
4
3
Measuring voltage L1
not measured
Blocking of protective functionsor remote acknowledgement
Synchronizing voltage L2
Synchronizing voltage L1
Synchronizing voltage L3
Measuring voltagethree-wire orfour-wire system Measuring voltage L2
Measuring voltage L3
(Measuring voltage N)
Relay 8
Pac
ka
ges
G59/G59N
MFR11(Mu
ltiFunc
tion
Re
lay
)
Relay 3(Package SC: Synch-check)
Measuring voltage: 100 V AC or 400 V AC
The socket for the PC parameterization is situatedon the side of the unit. This is where the DPCmust be plugged in.
allPac
kages
allPackages
0 Vdc
24 VdcPackages SC+N/NU/G59N: 90 to 265 Vac/dc
27
21
20
19
22
26
25
24
23
28
32
31
30
29 Relay 7
Relay 6
Relay 5
Relay 4
3/4
allPa
ckages
synchron
izingsys
tem
(fixe
d)
2/3
The synchronizing voltage must be connected three-phase if the measuring voltage is connected three-
phase (N not connected). If the measuring voltage is
connected four-phase (L1-L2-L3-N), the synchronizingvoltage may be connected two-phase (L1-L2). L3 is
connected only for compensation and is not measured.
5/19/2018 Antiinsularizare RELEU MFR11
4/4
InternationalWoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811Fax: +1 (970) 498-3058
Europe
Woodward Governor CompanyLeonhard-Reglerbau GmbHHandwerkstrasse 2970565 Stuttgart, GermanyPh: +49 (0) 711 789 54-0Fax: +49 (0) 711 789 54-100
Distributors & ServiceWoodward has an internationalnetwork of distributors andservice facilities. For yournearest representative, call theFort Collins plant or see theWorldwide Directory on ourwebsite.
Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441
www.woodward.com/power
Subject to technicalmodifications.
This document is distributed forinformational purposes only. It is notto be construed as creating or
becoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.
We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]
Woodward Governor
Company
All Rights Reserved
03244C - 06/3/S
FEATURES OVERVIEW
MFR 11
ANSI MP
NU
VDEW
G59
G59N
SC
SC+N
Measuring/Display
Voltage
Voltage (2ndinput for synch-check)
AccessoriesConfiguration via PC #1
Protection
Overvoltage 59
Undervoltage 27
Overfrequency 81O
Underfrequency 81U
Voltage asymmetry 47
vector/phase shift (d/dt) 78
df/dt (ROCOF) 81RL
Function
Synch-check 25
Zero voltage monitoring: dead busstart (close CB to dead busbar)
I/O's
Output relays (configurable) 74 3 3 3 8 8 3 3
Power Supply
24 Vdc
90 to 265 Vac/dc
Listings/Approvals
CE marked
UL/cUL listed
GL (Marine)
Product Number P/N
Measuring inputs 110 Vac 5448-884 LR20610 8441-1003 5448-885 8441-1004 8441-1005 8441-1110
Measuring inputs 400 Vac 8441-1023 8441-1027 8441-1049 LR20406 8441-1103 8441-1097 8441-1111
Measuring inputs 700 Vac LR21100 8441-1084
Formoreinfo
rmationcontact:
#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)
TYPICAL APPLICATIONS
MFR 11/MP MFR 11/G59 MFR 11/SC
52 off
MFR 11/MP
I / O
27
59
81O
81U
4752 off
MFR 11/G59
I / O
27
59
81O
81U
47
78
81RL
52 off
MFR 11/SC
I / O
25