Antiinsularizare RELEU MFR11

Embed Size (px)

DESCRIPTION

Power Design

Citation preview

  • 5/19/2018 Antiinsularizare RELEU MFR11

    1/4

    Product Specificatio

    03244C

    MFR 11

    Multi Function Relay

    Protection

    APPLICATIONS

    The MFR 1 Series is a family of industrialgrade protective relays that offer multipleprotective features in a single package.

    Using a digital processor to measure true

    RMS values enables a high degree ofmeasuring accuracy regardless ofharmonics, transients or disturbing pulses.

    The MFR 11 model is a generator or mainsprotection unit packaged into one compactdevice. Typical applications are generatorsand switchgear equipment that requireindependent protection architecture. Differentpackages offer additional functionality.

    The MFR 11/MPis for mains protection usewith over-/undervoltage, -frequency and

    voltage asymmetry with 24 Vdc power supplywhile the MFR 11/NUhas the samefunctions, but utilizes a wide-range powersupply.

    The MFR 11/VDEWadds phase/vector jumpmonitoring to the MP package. TheMFR 11/G59package adds df/dt (ROCOF)protection. The MFR 11/G59Nhas the samefeatures as the G59package, but utilizes thewide-range power supply.

    The MFR 11/SCis used for synch-check and

    zero voltage detection to check whether twosystems are synchronous or de-energized.

    The compact size and multiple functions ofthe MFR 11 help to simplify switchgeardesign. The digital display offers a user-friendly interface to setup the unit as well asmonitor the operation and display anyalarms.

    DESCRIPTION

    Features(all versions) True RMS voltage

    Configurable trip/control set points

    Configurable delays for each alarm

    Two-line LC display

    MFR 11/MP 24 Vdc power supply

    3 configurable relays

    Over-/undervoltage monit. (59/27)

    Over-/underfrequency monit. (81O/U)

    Voltage asymmetry monitoring (47)

    MFR 11/NUSame features as MFR 11/MP, plus:

    Wide-range power supply (no 24 Vdc)(90 to 265 Vac/dc)

    MFR 11/VDEWSame features as MFR 11/MP, plus:

    Vector/phase shift monitoring (78)

    MFR 11/G59Same features as MFR 11/MP, plus:

    8 configurable relays

    Vector/phase shift monitoring (78)

    df/dt ROCOF monitoring (81RL)

    MFR 11/G59NSame features as MFR 11/G59, plus:

    Wide-range power supply (no 24 Vdc)

    (90 to 265 Vac/dc)

    MFR 11/SCSame features as MFR 11/MP, plus:

    2 configurable relays

    Synch-check (fixed to relay 3) (25)

    Zero voltage monitoring: dead bus startfunctionality (close CB to dead busbar)

    MFR 11/SC+NSame features as MFR 11/SC, but

    Wide-range power supply (no 24 Vdc)(90 to 265 Vac/dc)

    True RMS sens

    Synch-check

    Programmable routputs

    Discrete inputs enabling or remacknowledgmen

    PC and front paconfigurable

    Microprocessortechnology foraccurate, repeaand reliableoperation

    Programmablethreshold setpowith individual tidelays

    CE marked

    UL/cUL Listed

    GL Approval

  • 5/19/2018 Antiinsularizare RELEU MFR11

    2/4

    SPECIFICATIONS

    Accuracy..........................................................................................Class 1Power supply.............................................................24 Vdc (18 to 30 Vdc)

    Packages NU/G59N/SC+N: 90 to 265 Vac/dcIntrinsic consumption..................................................................max. 12 W

    Ambient temperature................................................................-20 to 70 CAmbient humidity......................................................95 %, non-condensing

    Voltage .........Rated /: [1] 66/115 Vac [4] 230/400 Vac [7] 398/690 VacMaximum value (Vmax): [1] 150 Vac [4] 300 Vac [7] 600 Vac

    Rated voltage Vph-ground: [1] 150 Vac [4] 300 Vac [7] 400 VacRated surge voltage: [1] 2.5 kV [4] 4.0 kV [7] 4.0 kV

    Linear measuring range up to.......................................................1.3VratedMeasuring frequency................................................50/60 Hz (40 to 70 Hz)

    Input resistance................................[1] 0.21 M, [4] 0.7 M, [7] 1.04 MMax. power consumption per path................................................ < 0.15 WDiscrete inputs .............................................................................. isolatedInput range....................................................................18 to 250 Vac or dc

    Input resistance.....................................................................approx. 68 k

    Relay out puts ................................................................................ isolaContact material...............................................................................AgCLoad (GP).................................................24 Vdc@2 Adc, 250 Vac@2 Pilot duty (PD)......................................................................24 Vdc@1 Housing ......................................................Type APRANORM DIN 43 Dimensions.........................................................................9672130 Front cutout.................................................................................9167 Connection................................................ screw/plug terminals depend

    on connector 1.5 mm or 2.5 mFront................................................................................. insulating surfProtection system................................................................................ IPWeight............................................... depending on version, approx. 80Disturbance test(CE).................................................. tested accordin

    applicable EN guidelListings .....................................UL/cUL listed (note: max. voltages ap

    for ordinary loc., file E212App rovals ........................................................... GL (Germanischer Llo

    DIMENSIONS

    Front view

    2005-09-09 | MFR 11 Dimensions r1ww-3605-ab.sk

    50 mm130 mm

    96mm

    8

    90mm

    130mm

    72mm

    65mm

    27mm

    35mm

    Back view withconnecting terminals

    Bottom view

    Back plate mountingoptional (please order

    brackets P/N 8923-1023)

    Configuration port

    Configuration port

    1 16

    70 75

    32 17

    Configuration port

  • 5/19/2018 Antiinsularizare RELEU MFR11

    3/4

    WIRING DIAGRAM

    superv

    ise

    dsys

    tem

    (varia

    ble)

    Subject to technical modifications.

    7

    8

    CB

    3/4

    Relay 2

    Relay 1(Ready for operation)

    2005-09-13 | MFR 11 Wiring Diagram r13ww-3705-ap.sk

    12

    11

    10

    9

    13

    16

    15

    14

    Pac

    k.

    SC

    5

    6

    70

    71

    72

    1

    2

    4

    3

    Measuring voltage L1

    not measured

    Blocking of protective functionsor remote acknowledgement

    Synchronizing voltage L2

    Synchronizing voltage L1

    Synchronizing voltage L3

    Measuring voltagethree-wire orfour-wire system Measuring voltage L2

    Measuring voltage L3

    (Measuring voltage N)

    Relay 8

    Pac

    ka

    ges

    G59/G59N

    MFR11(Mu

    ltiFunc

    tion

    Re

    lay

    )

    Relay 3(Package SC: Synch-check)

    Measuring voltage: 100 V AC or 400 V AC

    The socket for the PC parameterization is situatedon the side of the unit. This is where the DPCmust be plugged in.

    allPac

    kages

    allPackages

    0 Vdc

    24 VdcPackages SC+N/NU/G59N: 90 to 265 Vac/dc

    27

    21

    20

    19

    22

    26

    25

    24

    23

    28

    32

    31

    30

    29 Relay 7

    Relay 6

    Relay 5

    Relay 4

    3/4

    allPa

    ckages

    synchron

    izingsys

    tem

    (fixe

    d)

    2/3

    The synchronizing voltage must be connected three-phase if the measuring voltage is connected three-

    phase (N not connected). If the measuring voltage is

    connected four-phase (L1-L2-L3-N), the synchronizingvoltage may be connected two-phase (L1-L2). L3 is

    connected only for compensation and is not measured.

  • 5/19/2018 Antiinsularizare RELEU MFR11

    4/4

    InternationalWoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811Fax: +1 (970) 498-3058

    Europe

    Woodward Governor CompanyLeonhard-Reglerbau GmbHHandwerkstrasse 2970565 Stuttgart, GermanyPh: +49 (0) 711 789 54-0Fax: +49 (0) 711 789 54-100

    Distributors & ServiceWoodward has an internationalnetwork of distributors andservice facilities. For yournearest representative, call theFort Collins plant or see theWorldwide Directory on ourwebsite.

    Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441

    www.woodward.com/power

    Subject to technicalmodifications.

    This document is distributed forinformational purposes only. It is notto be construed as creating or

    becoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.

    We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]

    Woodward Governor

    Company

    All Rights Reserved

    03244C - 06/3/S

    FEATURES OVERVIEW

    MFR 11

    ANSI MP

    NU

    VDEW

    G59

    G59N

    SC

    SC+N

    Measuring/Display

    Voltage

    Voltage (2ndinput for synch-check)

    AccessoriesConfiguration via PC #1

    Protection

    Overvoltage 59

    Undervoltage 27

    Overfrequency 81O

    Underfrequency 81U

    Voltage asymmetry 47

    vector/phase shift (d/dt) 78

    df/dt (ROCOF) 81RL

    Function

    Synch-check 25

    Zero voltage monitoring: dead busstart (close CB to dead busbar)

    I/O's

    Output relays (configurable) 74 3 3 3 8 8 3 3

    Power Supply

    24 Vdc

    90 to 265 Vac/dc

    Listings/Approvals

    CE marked

    UL/cUL listed

    GL (Marine)

    Product Number P/N

    Measuring inputs 110 Vac 5448-884 LR20610 8441-1003 5448-885 8441-1004 8441-1005 8441-1110

    Measuring inputs 400 Vac 8441-1023 8441-1027 8441-1049 LR20406 8441-1103 8441-1097 8441-1111

    Measuring inputs 700 Vac LR21100 8441-1084

    Formoreinfo

    rmationcontact:

    #1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)

    TYPICAL APPLICATIONS

    MFR 11/MP MFR 11/G59 MFR 11/SC

    52 off

    MFR 11/MP

    I / O

    27

    59

    81O

    81U

    4752 off

    MFR 11/G59

    I / O

    27

    59

    81O

    81U

    47

    78

    81RL

    52 off

    MFR 11/SC

    I / O

    25