Transcript
Page 1: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

460

460 Lightning Surge Protectors for Electronics Equipment

M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

M-System Lightning Surge Protectors absorb only the lightning surges with no interruption of the instrumentation signal.

◆ Protects sensor, signal and power lines

◆ Can be removed and tested without disconnecting wires (MDP series)

◆ Superior protection and selection across a wide range of applications including:

Frequency generating devicesTelemetering devicesRS-485 / RS-422, Ethernet, DeviceNet, PROFIBUS, LONWORKS, FOUNDATION FieldbusAC/DC Power supply lines (1 amp up to 30 amps)

4–20mA & pulse signalThermocoupleRTDPotentiometerStrain gauge

■ Standard Signal Line & Pulse Use

Model Function Page

MD7AST Lightning Surge Protector for Standard Signal Line (ultra-slim; life monitor) P.462

MDPA-24 Lightning Surge Protector for Standard Signal Line & Pulse Use (life monitor) P.462

MDPA-65 Lightning Surge Protector for Standard Signal Line & Pulse Use (life monitor) P.462

MDM2A-24 Lightning Surge Protector for Standard Signal Line & Pulse Use (life monitor) P.462

MDM2A-65 Lightning Surge Protector for Standard Signal Line & Pulse Use (life monitor) P.462

MD7ST Lightning Surge Protector for Standard Signal Line (ultra-slim) P.462

MDP-24-1 Lightning Surge Protector for Standard Signal Line & Pulse Use P.462

MDP-65-1 Lightning Surge Protector for Standard Signal Line & Pulse Use P.462

MDK-24 Lightning Surge Protector for Standard Signal Line Use P.463

MDJST Lightning Surge Protector for Standard Signal Use (fast response: 3 nsec.) P.463

MMDHLightning Surge Protector for Standard Signal Line Use (high speed/high discharge current capacity)

P.463

MMD Lightning Surge Protector for Standard Signal Line Use (high discharge current capacity) ***

MD72W Lightning Surge Protector for Two-wire Signal Loop (ultra-slim) P.463

MD72WD Lightning Surge Protector for Two-wire Signal Loop (ultra-slim; 2 channels) P.463

MD73W Lightning Surge Protector for Three-wire Signal Loop (ultra-slim) P.463

MD6N-24 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

MD6N-65 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

MD6T-24 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

MD6T-65 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

MD6P-24 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

MD6P-65 Lightning Surge Protector for Standard Signal Line & Pulse Use (conduit mount, weather-proof) P.464

■ Sensor Use

Model Function Page

MD7TC Lightning Surge Protector for Thermocouple (ultra-slim) P.465

MDP-TC Lightning Surge Protector for Thermocouple Use P.465

MD7RB Lightning Surge Protector for RTD (ultra-slim) P.465

MDP-RB Lightning Surge Protector for RTD Use P.465

MD7PM Lightning Surge Protector for Potentiometer (ultra-slim) P.465

MDP-PM Lightning Surge Protector for Potentiometer Use P.465

MD7LC Lightning Surge Protector for Strain Gauge Use (ultra-slim) P.466

MDP-LC Lightning Surge Protector for Strain Gauge Use P.466

MDK-LC Lightning Surge Protector for Strain gauge Use P.466

MD-LC2 Lightning Surge Protector for Strain gauge Use (6-wire remote sensing) P.466

MDK-LV Lightning Surge Protector for Signal Line with Excitation Use P.466

MD7JS Lightning Surge Protector for Self-Synch Use (ultra-slim) P.467

MDP-JS Lightning Surge Protector for Self-Synch Use P.467

MD7PL Lightning Surge Protector for Pulse Signal (ultra-slim) P.467

MDP-SP Lightning Surge Protector for Low Frequency Use P.467

MDR2 Lightning Surge Protector for Multi-channel Use (high discharge current capacity) P.467

■ Transmission Line Use

Model Function Page

MD74R Lightning Surge Protector for RS-485/RS-422 (ultra-slim) P.468

MDP-4R Lightning Surge Protector for RS-485/RS-422 P.468

MDW5-4R Lightning Surge Protector for RS-485/RS-422 (full-duplex) P.468

MDW2A-4R Lightning Surge Protector for RS-485/RS-422 (life monitor) P.468

MDCAT Lightning Surge Protector for Ethernet (PoE / 10 BASE-T / 100 BASE-TX / 1000 BASE-T) P.468

MDM5E-A Lightning Surge Protector for Ethernet (100 BASE-TX / 10 BASE-T) P.468

SHSP 8-Port Ethernet Switch (with surge protector) P.469

MD7AST,MDPA-24,MDPA-65,MDM2A-24,MDM2A-65,MD7ST,MDP-24-1,MDP-65-1,MDK-24,MDJST,MMDH,MMD,MD72W,MD72WD,MD73W,MD6N-24,MD6N-65,MD6T-24,MD6T-65,MD6P-

24,MD6P-65,MD7TC,MDP-TC,MD7RB,MDP-RB,MD7PM,MDP-PM,MD7LC,MDP-LC,MDK-LC,MD-LC2,MDK-LV,MD7JS,MDP-JS,MD7PL,MDP-SP,MDR2,MD74R,MDP-4R,MDW5-

4R,MDW2A-4R,MDCAT,MDM5E-A,SHSP,MD7PA,MDP-PA,MD7LWA,MDP-LWA,MD-DNM,MD-DNS,MD7FB,MDP-DM3,MDP-EC,MDP-MFA,MDP-FT,MD-INS,MD-TL,MDP-TL,MDA-

TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA,MAAC,MMAJ,MMA,MMAH,MAX,MAH,MMH,MH-105A,MH-110A,MH-130A,MH-205A,MH-210A,MH-230A,MH-1201,MH-2201,MH-

2203,MD7DP,MDP-D,MDHA,MDH,MAT2,MAKF,C-106A-1,A-33,MD7F,MD7G,MBS,CNB,BX-W1

Page 2: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

461

461Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

To find a product in the list with “***”, visit M-System Data Library.If you cannot find a product here, please contact: [email protected]

Model Function Page

MD7PA Lightning Surge Protector for PROFIBUS-PA (ultra-slim) P.469

MDP-PA Lightning Surge Protector for PROFIBUS-PA P.469

MD7LWA Lightning Surge Protector for LONWORKS (ultra-slim, FTT-10A) P.470

MDP-LWA Lightning Surge Protector for LONWORKS (FTT-10A) P.470

MD-DNM Lightning Surge Protector for DeviceNet (load capacity 8A) P.470

MD-DNS Lightning Surge Protector for DeviceNet (load capacity 2A) P.470

MD7FB Lightning Surge Protector for FOUNDATION Fieldbus (ultra-slim) P.470

MDP-DM3 Lightning Surge Protector for MsysNet Use ***MDP-EC Lightning Surge Protector for EC-Cable Use ***

MDP-MFA Lightning Surge Protector for Telemetering Use (50 bps) ***

MDP-FT Lightning Surge Protector for Telemetering Use (3.4 kHz) ***

MD-INS Lightning Surge Protector for ISDN Circuit Use ***

MD-TL Lightning Surge Protector for Telecommunication Line Use ***

MDP-TL Lightning Surge Protector for Telecommunication Line Use ***

MDA-TL Lightning Surge Protector for Analog Telecom Line Use (life monitor) ***

■ Power Supply Use

Model Function Page

MD7AP Lightning Surge Protector for AC Power Supply (max. 3A; ultra-slim) P.470

MDP-100 Lightning Surge Protector for AC/DC Power Supply Use (1A) P.470

MDP-200 Lightning Surge Protector for AC/DC Power Supply Use (1A) P.470

MA-100 Lightning Surge Protector for Power Supply (2A) P.471

MA-200 Lightning Surge Protector for Power Supply (2A) P.471

MAALightning Surge Protector for Power Supply Use (5A; high discharge current capacity; life monitor)

P.471

MAACLightning Surge Protector for Power Supply Use (5A; high discharge current capacity; life monitor/surge counter)

P.471

MMAJ Lightning Surge Protector for Power Supply Use (fast responce: 3 nsec.) P.471

MMA Lightning Surge Protector for Power Supply Use (10A;high discharge current capacity) P.471

MMAH Lightning Surge Protector for Power Supply Use (10A; high speed/high discharge current capacity) P.471

MAX Lightning Surge Protector for Power Supply Use (5A; high discharge current capacity) P.472

MAH Lightning Surge Protector for Power Supply Use (20A) ***

MMH Lightning Surge Protector for Power Supply Use (10–30A; replaceable arrester module) P.472

MH-105A Lightning Surge Protector for Power Supply Use (5A) ***

MH-110A Lightning Surge Protector for Power Supply Use (10A) ***

MH-130A Lightning Surge Protector for Power Supply Use (30A) ***

Model Function Page

MH-205A Lightning Surge Protector for Power Supply Use (5A) ***

MH-210A Lightning Surge Protector for Power Supply Use (10A) ***

MH-230A Lightning Surge Protector for Power Supply Use (30A) ***

MH-1201 Lightning Surge Protector for Power Supply Use (200A) ***

MH-2201 Lightning Surge Protector for Power Supply Use (200A) ***

MH-2203 Lightning Surge Protector for Power Supply Use (200A) ***

■ DC Power Supply Use

Model Function Page

MD7DP Lightning Surge Protector for DC Power Supply (max. 1.2A; ultra-slim) P.472

MDP-D Lightning Surge Protector for DC Power Supply Use P.472

MDHA Lightning Surge Protector for Power Supply Use (DC power use; life monitor) P.472

MDH Lightning Surge Protector for Power Supply Use (DC power use) P.472

■ One-port Surge Protector

Model Function Page

MAT2 Lightning Surge Protector for Three-phase Power Supply P.473

MAKF One-port Surge Protector for Power Supply Use P.473

■ Accessories

Model Function Page

C-106A-1 M-RESTER Tester P.473

A-33 DIN Rail Mounting Adaptor P.473

MD7F Loop Disconnect Fuse ***MD7G Terminal Block For Grounding (ultra-slim) ***MBS Single Mount Adaptor ***CNB Wiring Bridge ***BX-W1 Outdoor Housing (weather-proof) P.473

Page 3: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

462

462 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

4–20mA & Pulse Signal, Ultra-slim Type

Model MD7ST-24 MD7ST-60Max. Cont. Operat. Volt. (Uc) 30V 70V

Voltage Protection Level (Up) 60V max. 115V max.

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs), 1.0 kA (10/350 μs.)Nominal Current (IN) 250 mAInternal Resistance (Ω ±10%, per line)

4.7 Ω w/o fuse7.5 Ω w/ fuse

10 Ω w/o fuse12.5 Ω w/ fuse

Test Standard IEC 61643-21 (Categories C1, C2, D1)

4–20mA & Pulse Signal, Plug-in Type

Model MDP-24-1 MDP-65-1Max. Cont. Operat. Volt. (Uc) 30V min. 70V min.

Voltage Protection Level (Up) 40V max.@1kV (100A) 45V max.@2kV (1kA)

80V max.@1kV (100A) 110V max.@2kV (1kA)

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mA

Internal Resistance 20 Ω ±10% (incl. return)

Test Standard IEC 61643-21 (Categories C1, C2)

4–20mA & Pulse Signal, Ultra-slim Type, with Life Monitor

Model MD7AST-24 MD7AST-60Max. Cont. Operat. Volt. (Uc) 30V 70V

Voltage Protection Level (Up) 60V max. 115V max.

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs), 1.0 kA (10/350 μs.)Nominal Current (IN) 250 mAInternal Resistance 4.7 Ω ±10% per line 10 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

4–20mA & Pulse Signal, Plug-in Type, with Life Monitor

Model MDPA-24 MDPA-65Max. Cont. Operat. Volt. (Uc) 30V min. 70V min.

Voltage Protection Level (Up) 45V max.@1kV (100A) 50V max.@2kV (1kA)

85V max.@1kV (100A) 100V max.@2kV (1kA)

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance 20 Ω ±10% (incl. return)Test Standard IEC 61643-21 (Categories C1, C2)

4–20mA & Pulse Signal, Plug-in Type, with Life Monitor

Model MDM2A-24 MDM2A-65Discharge Voltage 30V min. 70V min.Max. Surge Voltage 45V max. 85V max.Response Time 0.1 μsec. max.Discharge Current 5000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 20 Ω (incl. return)Test Standard ----

■ Standard Signal Line & Pulse Use

LIFEMONITOR

MD7AST,MDPA-24,MDPA-65,MDM2A-24,MDM2A-65,MD7ST,MDP-24-1,MDP-65-1,

LIFEMONITOR

LIFEMONITOR

Page 4: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

463

463Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

Two-Wire Transmitter Loop, Ultra-slim Type

Model MD72W-07 MD72W-16 MD72W-32 MD72W-55Max. Cont. Operat. Volt. (Uc) ±7V ±16V ±32V ±55VVoltage Protection Level (Up) 20V max. 30V max. 50V max. 80V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs), 1.0 kA (10/350 μs.)Nominal Current (IN) 400 mA w/o fuse, 250 mA w/ fuseInternal Resistance (Ω ±20%, per line) 2.2 Ω w/o fuse, 4 Ω w/ fuse

Test Standard IEC 61643-21 (Categories C1, C2, D1)

Two-Wire Transmitter Loop, 2 channels, Ultra-slim Type

Model MD72WD-07 MD72WD-16 MD72WD-32Max. Cont. Operat. Volt. (Uc) ±7V ±16V ±32VVoltage Protection Level (Up) 30V max. 45V max. 70V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs), 1.0 kA (10/350 μs.)Nominal Current (IN) 250 mAInternal Resistance 4.7 Ω ±20% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

4–20mA & Pulse Signal, High Speed, Plug-in Type

Model MDJST-12 MDJST-24 MDJST-48Max. Cont. Operat. Volt. (Uc) ±18V ±36V ±60VVoltage Protection Level (Up) ±30V max. ±50V max. ±90V max.Response Time 3 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs)Nominal Current (IN) 1AInternal Resistance 3Ω max.Test Standard IEC 61643-21 (Categories C1, C2)

4–20mA & Pulse Signal, Low Profile Type

Model MDK-24Discharge Voltage 30V min.Max. Surge Voltage 40V max.Response Time 0.1 μsec. max.Discharge Current 5000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance 20 Ω ±5%Test Standard ----

4–20mA & Pulse Signal, High Speed, High Discharge Current Capacity

Model MMDH-24Discharge Voltage ±40V min.Max. Surge Voltage ±50V max.Response Time 4 nanosec.Discharge Current 20000A (8/20 μsec.)Max. Load Current 0.1 A

Internal Resistance ≤0.4 Ω (incl. return)

Test Standard ----

Three-Wire Transmitter Loop, Ultra-slim Type

Model MD73WMax. Cont. Operat. Volt. (Uc) ±32VVoltage Protection Level (Up) ±60V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20 kA (8/20 μs), 1.0 kA (10/350 μs.)Nominal Current (IN) 400 mAInternal Resistance ≤2.2 Ω ±20% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

■ Standard Signal Line & Pulse Use

MDK-24,MDJST,MMDH,MD72W,MD72WD,MD73W,

Page 5: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

464

464 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

4–20mA & Pulse Signal, Conduit Mount, Weather-Proof (Terminal Block Connection Type)

Model MD6T-24 MD6T-65Discharge Voltage 30V min. 70V min.Max. Surge Voltage 40V max. 100V max.Response Time 4 nanosec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 22 Ω (incl. return)

Approvals

• FM intrinsically safe• CENELEC intrinsically

safe (ATEX)• CENELEC flameproof

(ATEX)• FM nonincendive

• CENELEC flameproof (ATEX)

4–20mA & Pulse Signal, Conduit Mount, Weather-Proof (Leadwire Connection, Pipe Nipple Type)

Model MD6N-24 MD6N-65Discharge Voltage 30V min. 70V min.Max. Surge Voltage 40V max. 100V max.Response Time 4 nanosec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 22 Ω (incl. return)

Approvals

• FM intrinsically safe• CENELEC intrinsically

safe (ATEX)• FM explosion-proof• CENELEC flameproof

(ATEX)• FM nonincendive

• FM explosion-proof• CENELEC flameproof

(ATEX)

4–20mA & Pulse Signal, Conduit Mount, Weather-Proof (Leadwire Connection, Stopping Plug Type)

Model MD6P-24 MD6P-65Discharge Voltage 30V min. 70V min.Max. Surge Voltage 40V max. 100V max.Response Time 4 nanosec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 22 Ω (incl. return)

Approvals

• FM intrinsically safe• CENELEC intrinsically

safe (ATEX)• FM explosion-proof• CENELEC flameproof

(ATEX)• FM nonincendive

• FM explosion-proof• CENELEC flameproof

(ATEX)

■ Standard Signal Line & Pulse Use

MD6N-24,MD6N-65,MD6T-24,MD6T-65,MD6P-24,MD6P-65,

Page 6: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

465

465Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

Thermocouple, Ultra-slim Type

Model MD7TCMax. Cont. Operat. Volt. (Uc) 7.5VVoltage Protection Level (Up) 25V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance 4.7 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

Thermocouple, Plug-in Type

Model MDP-TCMax. Cont. Operat. Volt. (Uc) 7.5V min.Voltage Protection Level (Up) 16V max.@1kV (100A), 20V max.@2kV (1kA)Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance 20 Ω ±10% (incl. return)Test Standard IEC 61643-21 (Categories C1, C2)

RTD, Ultra-slim Type

Model MD7RBMax. Cont. Operat. Volt. (Uc) ±3V

Voltage Protection Level (Up) ±25V max.

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance 5.12 Ω ±0.3%, ±30 ppm/°C per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

RTD, Plug-in Type

Model MDP-RBMax. Cont. Operat. Volt. (Uc) ±6V min. (B to C), ±3V min. (B or C to A)

Voltage Protection Level (Up) ±40V max.@2kV (1kA) (2 to 3), ±25V max.@2kV (1kA) (2 or 3 to 1)

Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance 10 Ω ±0.1%, 30 ppm/°CTest Standard IEC 61643-21 (Categories C1, C2)

Potentiometer, Ultra-slim Type

Model MD7PMMax. Cont. Operat. Volt. (Uc) 7.5VVoltage Protection Level (Up) 25V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance 4.7 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

Potentiometer, Plug-in Type

Model MDP-PMMax. Cont. Operat. Volt. (Uc) 7.5V min.Voltage Protection Level (Up) 16V max.@1kV (100A), 25V max.@2kV (1kA)Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance 10 Ω ±0.1%, 30 ppm/°CTest Standard IEC 61643-21 (Categories C1, C2)

■ Sensor Use

MD7TC,MDP-TC,MD7RB,MDP-RB,MD7PM,MDP-PM,

Page 7: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

466

466 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

Strain Gauge, Ultra-slim Type

Model MD7LC-0* MD7LC-1

Max. Cont. Operat. Volt. (Uc)Line Side ±0.2VExc. Side 15V

Voltage Protection Level (Up)Line Side ±15V max. @0.2kV (1.2 / 50 μs) ±40V max. @6kV (1.2 / 50 μs)Exc. Side 30V max. @0.2kV (1.2 / 50 μs) 50V max. @6kV (1.2 / 50 μs)

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 100A (8/20 μsec.) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) ---- 250 mAInternal Resistance ---- 1.5 Ω ±10% per lineTest Standard ---- IEC 61643-21 (Categories C1, C2, D1)

Strain Gauge, Plug-in Type

Model MDP-LC

Max. Cont. Operat. Volt. (Uc)

Line Side ±0.3V min.Exc. Side 15V min.

Voltage Protection Level (Up)

Line Side ±15V max.Exc. Side 30V max.

Response Time 5 nanosec. max.Max. Discharge Curr. (Imax)

Line Side 100A (8/20 μsec.), 25A (10/1000 μsec.)Exc. Side 50A (8/20 μsec.), 25A (10/1000 μsec.)

Test Standard IEC 61643-21 (Category C3)

Strain Gauge, 6-wire Remote Sensing

Model MD-LC2

Discharge VoltageLine Side ±0.3V min.Exc. Side 15V min.

Max. Surge Voltage

Line Side ±20V max.Exc. Side 40V max.

Response Time 4 nanosec. max.Discharge Current 5000A (8/20 μsec.)Test Standard ----

Strain Gauge, Low Profile Type

Model MDK-LC

Discharge VoltageLine Side ±0.3V min.Exc. Side 15V min.

Max. Surge Voltage

Line Side ±15V max.Exc. Side 30V max.

Response Time 5 nanosec. max.

Discharge CurrentLine Side 100A (8/20 μsec.)Exc. Side 50A (8/20 μsec.)

Test Standard ----

Signal Line with Excitation, Low Profile Type

Model MDK-LV

Discharge VoltageLine Side 10V min.Exc. Side 30V min.

Max. Surge Voltage

Line Side 20V max.Exc. Side 40V max.

Response Time 0.1 μsec. max.Discharge Current 5000A (8/20 μsec.)Test Standard ----

■ Sensor Use

* No CE marking.

MD7LC,MDP-LC,MDK-LC,MD-LC2,MDK-LV,

Page 8: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

467

467Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

Self-Synch, Ultra-slim Type

Model MD7JSMax. Cont. Operat. Volt. (Uc) ±130V

Voltage Protection Level (Up) ±450V max.

Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 500 mAInternal Resistance 2 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

Self-Synch, Plug-in Type

Model MDP-JSMax. Cont. Operat. Volt. (Uc) ±170V min. (A to B to C)

Voltage Protection Level (Up) ±350V max.@1kV (100A) (1 to 2 to 3), ±450V max.@2kV (1kA) (1 to 2 to 3)

Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 500 mAInternal Resistance Approx. 2 Ω per wireTest Standard IEC 61643-21 (Categories C1, C2)

2-Point Pulse with Common Negative, Ultra-slim Type

Model MD7PL-P Positive (PNP)

MD7PL-N Negative (NPN)

Max. Cont. Operat. Volt. (Uc) -30V +30VVoltage Protection Level (Up) -50V max. +50V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance 11 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

Low Frequency Pulse, Plug-in Type

Model MDP-SP

Max. Cont. Operat. Volt. (Uc) 14V min.Voltage Protection Level (Up) 30V max.@1kV (100A), 30V max.@2kV (1kA)Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 50 mAInternal Resistance 10 Ω ±10%Test Standard IEC 61643-21 (Categories C1, C2)

High Discharge, 8-point Pulse Signal, Terminal Board Type

Model MDR2-8NY Negative (NPN)

MDR2-8NA Negative (NPN) with

Leakage current Indicator

MDR2-8PY Positive (PNP)

MDR2-8PA Positive (PNP) with

Leakage current IndicatorMax. Cont. Operat. Volt. (Uc) +30V -30VVoltage Protection Level (Up) @4kV / 2kA (1.2 / 50 μsec.) +50V +60V -50V -60VResponse Time 4 nanosec. max.Max. Discharge Curr. (Imax) 10kANominal Current (IN) 150 mAInternal Resistance 22 Ω ±20%Test Standard IEC 61643-21 (Categories C1, C2)

■ Sensor Use

MD7JS,MDP-JS,MD7PL,MDP-SP,MDR2,

Page 9: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

468

468 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

RS-485/RS-422, Ultra-slim Type

Model MD74RMax. Cont. Operat. Volt. (Uc) ±5VVoltage Protection Level (Up) ±25V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance 2 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

RS-485/RS-422, Plug-in Type

Model MDP-4RMax. Cont. Operat. Volt. (Uc) ±5V min. (B to C)Voltage Protection Level (Up) ±20V max. (2 to 3)Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance Approx. 4.5 Ω (incl. return)Test Standard IEC 61643-21 (Categories C1, C2)

RS-485/RS-422, Plug-in Type with Life Monitor

Model MDW2A-4RDischarge Voltage ±5V min. (7 to 8)Max. Surge Voltage ±25V max. (4 to 5)Response Time 4 nanosec. max.Discharge Current 5000A (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 5 Ω (incl. return)Test Standard ----

RS-485/RS-422, Full-duplex

Model MDW5-4RDischarge Voltage ±5V min. (6 to 7, 8 to 9)Max. Surge Voltage ±25V max. (1 to 2, 3 to 4)Response Time 4 nanosec. max.Discharge Current 10kA (8/20 μsec.)Max. Load Current 100 mAInternal Resistance Approx. 4 Ω (incl. return)Test Standard ----

Ethernet, 100 BASE-TX / 10 BASE-T

Model MDM5E-ADischarge Voltage ±6V min.Max. Surge Voltage 38V max.Response Time 4 nanosec. max.Discharge Current 500A (8/20 μsec.)Series Resistance Approx. 0 ΩImpulse durability Category c1Test Standard IEC 61643-21 : 2000

Ethernet, PoE / 10 BASE-T / 100 BASE-TX / 1000 BASE-T

Model MDCAT-5E (CAT5e) MDCAT-6 (CAT6)Max. Cont. Operat. Volt. (Uc) ±6V ±3.3VVoltage Protection Level (Up) ±15V max. @2kV ±10V max. @2kVResponse Time 4 nanosec. max.Max. Discharge Curr. (Imax) 100ANominal Current (IN) 1AInternal Resistance Approx. 0 ΩTest Standard IEC 61643-21 (Categories C1, C2)

■ Transmission Line Use

MD74R,MDP-4R,MDW5-4R,MDW2A-4R,MDCAT,MDM5E-A,

LIFEMONITOR

Page 10: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

469

469Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

PROFIBUS-PA, Ultra-slim Type

Model MD7PAMax. Cont. Operat. Volt. (Uc) ±32VVoltage Protection Level (Up) ±60V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 400 mAInternal Resistance 1.5 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

PROFIBUS-PA, Plug-in Type

Model MDP-PAMax. Cont. Operat. Volt. (Uc) 27V min.Voltage Protection Level (Up) ±60V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 500 mAInternal Resistance ≤3.3 Ω (incl. return)Test Standard IEC 61643-21 (Categories C1, C2)

■ Transmission Line Use

8-Port Ethernet Switch (with surge protector)

Surge protector function for each port ◆ Protects Ethernet devices from surges

entering through LAN cables

◆ Surge protector life monitor function with LED and contact output alarm

◆ Data transfer rate can be fixedModel: SHSP

■ LAN PORT SPECIFICATIONSStandards IEEE 802.3, IEEE 802.3u, IEEE 802.3xNumber of ports 8; All ports support AUTO-MDIX*

Data transfer rate10 Mbps (10 BASE-T), 100 Mbps (100 BASE-TX); Supports Auto-Negotiation

Cable 10 BASE-T (STP cable, category 5)100 BASE-TX (STP cable, category 5e)

Maximum segment length 100 metersSwitching Store & Forward

Flow controlFull duplex PAUSE FramesHalf duplex Back pressure

Buffer 64 KBMAC address table 1024

■ SURGE PROTECTOR PERFORMANCECompliant standard EN61000-4-5 level X Between ports 1kV (combination waveform)** Port to G 10kV (combination waveform) FG (shield) to G 15kV (combination waveform)***

Voltage protection level

Port to FG or G 160V min.Between each port 160V min.

FG to G 160V min. (with the shortcircuit bar removed)

SHSP,MD7PA,MDP-PA,

LIFEMONITOR

* Automatically sensing cable type, straight-through or cross-over.** RJ-45 connector contact is out of the scope of this protection. Using twisted-pair (STP) LAN cable is effective to reduce risk of fusing contact.*** With the shortcircuit bar

Page 11: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

470

470 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

1A Load Rating, Plug-in Type

Model MDP-100 MDP-200Max. Line Volt. (Uc) 120V AC 250V ACVoltage Protection Level (Up) 400V max. 800V max.Response Time 0.1 μsec. max.Max. Discharge Curr. (Imax) 1000A (8/20 μsec.)Nominal Current (IN) 1AInternal Resistance ≤0.4 Ω (incl. return)Test Standard IEC 61643-1 (Class III)

3A Load Rating, Ultra-slim Type

Model MD7AP-100 MD7AP-200Max. Cont. Operat. Volt. (Uc) 140V AC 275V ACVoltage Protection Level (Up) ±550V max. ±850V max.Response Time 20 nanosec. max.Max. Discharge Curr. (Imax) 10kA (8/20 μsec.)Nominal Current (IN) 3ATest Standard IEC 61643-21 (Categories C1, C2)

■ Power Supply Use

■ Transmission Line Use

DeviceNet

Model MD-DNM MD-DNS

Discharge VoltageLine Side ±5V min.Exc. Side 26V min.

Max. Surge Voltage

Line Side ±15V max.Exc. Side 120V max.

Response Time 0.1 μsec. max.

Discharge CurrentLine Side

1500A Exc. Side

Load Capacity 8A 2ATest Standard ----

FOUNDATION Fieldbus, Ultra-slim Type

Model MD7FBMax. Cont. Operat. Volt. (Uc) ±32VVoltage Protection Level (Up) ±60V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 400 mAInternal Resistance 1.5 Ω ±10% per lineTest Standard IEC 61643-21 (Categories C1, C2, D1)

LONWORKS (FTT-10A), Ultra-slim Type

Model MD7LWAMax. Cont. Operat. Volt. (Uc) ±1.5V min.Voltage Protection Level (Up) ±30V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 100 mAInternal Resistance ≤3.3 Ω (incl. return)Test Standard IEC 61643-21 (Categories C1, C2, D1)

LONWORKS (FTT-10A), Plug-in Type

Model MDP-LWAMax. Cont. Operat. Volt. (Uc) ±1.5V min.Voltage Protection Level (Up) ±40V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 100 mAInternal Resistance ≤3.3 Ω (incl. return)Test Standard IEC 61643-21 (Categories C1, C2)

MD7LWA,MDP-LWA,MD-DNM,MD-DNS,MD7FB,MD7AP,MDP-100,MDP-200,

Page 12: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

471

471Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

2A Load Rating, Plug-in Type

Model MA-100 MA-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 350V max. 700V max.Response Time 0.1 μsec. max.Discharge Current 1000A (8/20 μsec.)Max. Load Current 2AVoltage Drop ≤2V (50/60Hz)Test Standard ----

5A Load Rating, with Life Monitor

Model MAA-100 MAA-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 380V max. 700V max.Response Time 0.01 μsec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 5AInternal Resistance ≤0.5 Ω (incl. return)Test Standard ----

5A Load Rating, with Life Monitor / Surge Counter

Model MAAC-100 MAAC-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 400V max. 750V max.Response Time 0.01 μsec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 5AInternal Resistance ≤0.5 Ω (incl. return)Test Standard ----

10A/20A/30A Load Rating, Wall-mounted, High Speed, High Discharge Current Capacity

Model MMAJ-100 MMAJ-200Max. Cont. Operat. Volt. (Uc) 132V AC 264V ACVoltage Protection Level (Up) 900V max. 1500V max.Response Time 3 nanosec.Max. Discharge Curr. (Imax) 10kA, 20kAMax. Load Current 10A, 20A, 30ATest Standard IEC 61643-1 (Class II, III)

10A Load Rating, Wall-mounted, High Speed, High Discharge Current Capacity

Model MMAH-100 MMAH-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 400V max 750V max.Response Time 4 nanosec.Discharge Current 20000A (8/20 μsec.)Max. Load Current 10AInternal Resistance ≤0.5 Ω (incl. return)Test Standard ----

10A Load Rating, Wall-mounted

Model MMA-100 MMA-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 350V max 700V max.Response Time 0.01 μsec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 10AInternal Resistance ≤0.5 Ω (incl. return)Test Standard ----

■ Power Supply Use

LIFEMONITOR

MA-100,MA-200,MAA,MAAC,MMAJ,MMA,MMAH,

LIFEMONITOR

Page 13: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Data sheets available on Web in PDF. Visit M-System Data Library at www.m-system.co.jp ISP ’12

J

472

472 Lightning Surge Protectors for Electronics Equipment M-RESTERSignal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Standard Signal Line & Pulse Use

Lightning Surge Protectors

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

DC Power Supply Line, 1.2A Load Rating, Ultra-slim Type

Model MD7DP-12 MD7DP-24Max. Cont. Operat. Volt. (Uc) 14V 27VVoltage Protection Level (Up) ±150V max. ±170V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 1.0kA (10/350 μsec.)Nominal Current (IN) 1.2AInternal Resistance ≤0.8 Ω (incl. return)Test Standard IEC 61643-21 (Categories C1, C2, D1)

DC Power Supply Line, 1A Load Rating, Plug-in Type

Model MDP-D12 MDP-D24Max. Cont. Operat. Volt. (Uc) 14V min. 30V min.Voltage Protection Level (Up) 20V max. 40V max.Response Time 4 nanosec. max.Max. Discharge Curr. (Imax) 5000A (8/20 μsec.)Nominal Current (IN) 1AInternal Resistance ≤0.6 Ω (incl. return)Test Standard IEC 61643-1 (Class III)

DC Power Supply Line, 5A Load Rating, Plug-in Type

Model MDH-12 MDH-24 MDH-48Discharge Voltage 24V min. 50V min. 88V min.Max. Surge Voltage 70V max. 140V max. 210V max.Response Time 0.1 μsec. max.Discharge Current 2000A (8/20 μsec.)Max. Load Current 5AInternal Voltage Drop ≤1VTest Standard ----

DC Power Supply Line, 5A Load Rating, with Life Monitor

Model MDHA-12 MDHA-24Discharge Voltage ±15V min. ±30V min.Max. Surge Voltage ±80V max. ±120V max.Response Time 4 nanosec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 5AInternal Resistance ≤0.2 Ω (incl. return)Test Standard ----

LIFEMONITOR

5A Load Rating, Replaceable Surge Absorber

Model MAX-100 MAX-200Discharge Voltage 190V min. 410V min.Max. Surge Voltage 350V max. 700V max.Response Time 0.01 μsec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 5AInternal Resistance ≤0.5 Ω (incl. return)Test Standard ----

Medium Capacity 10A, 30A, Replaceable Surge Absorber

Model MMH-110 MMH-130 MMH-210 MMH-230Discharge Voltage 130V min. 285V min.Max. Surge Voltage 350V max. 700V max.Response Time 0.01 μsec. max.Discharge Current 10000A (8/20 μsec.)Max. Load Current 10A 30A 10A 30AVoltage Drop ≤1V (50/60Hz)Test Standard ----

■ Power Supply Use

■ DC Power Supply Use

MAX,MMH,MD7DP,MDP-D,MDHA,MDH,

Page 14: 460 TL,MD7AP,MDP-100,MDP-200,MA-100,MA-200,MAA ...Data sheets available on Web in PDF. Visit M-System Data Library at ISP ’12 J 460 460 Lightning Surge Protectors for Electronics

Lightning Surge Protectors for Electronics Equipment M-RESTER

Specifications are subject to change without notice.ISP ’12

J

473

473Signal Conditioners

Two-wire Signal Conditioners

Power Transducers

Indicators

Limit Alarms

Gateway,Remote I/O

Paperless RecordingSystem

PC Recorder

Electric Actuators& Position Sensors

Lightning Surge Protectors

Lightning Surge ProtectorsM-RESTER

Lightning Surge Protectors

Standard Signal Line & Pulse Use

Sensor Use

Transmission Line Use

Power Supply Use

DC Power Supply UseOne-port Surge Protector

Accessories

Three-phase Power Supply

Model MAT2-240 MAT2-440Max. Cont. Operat. Volt. (Uc) 240V AC 440V ACVoltage Protection Level (Up) 1500V 2500VResponse Time 4 nanosec. max.Max. Discharge Curr. (Imax) 20kA (8/20 μsec.), 40kA (8/20 μsec.)Nominal Current (IN) 10kA (8/20 μsec.), 20kA (8/20 μsec.)Test Standard IEC 61643-1 (Class II)

One-port Surge Protector

Model MAKF-120 MAKF-240 MAKF-280 MAKF-400 MAKF-480Uc (AC) 150V 275V 320V 440V 530VDischarge Voltage 250V min. 420V min. 460V min. 670V min. 820V min.

[email protected] (8/20ms) 600V max. 1000V max. 1100V max. 1500V max. 1800V [email protected] (8/20ms) 650V max. 1100V max. 1200V max. 1700V max. 2100V max.

Response Time 20 nanosec. max.Max. Discharge Curr. 20kA × twice (8/20 μsec.)Test Standard ----

■ One-port Surge Protector

■ Accessories

M-RESTER Testermodel: C-106A-1

DIN Rail Mounting Adaptormodel: A-33

Outdoor Housing (weather-proof) model: BX-W1

Connected in parallel between the power and ground lines regardless of load current

Connected in parallel between the power and ground lines regardless of load current

MAT2,MAKF,C-106A-1,A-33,BX-W1

◆ Applicable to single phase 2/3-wire and three-phase 3/4- wire system.

◆ Degraded head element is automatically sepa-rated from the power lines by the incorporated thermal breaker, and the LED lamp (turns off) and the relay contact alerts the failure status.

◆ Thermal breaker ensures degraded head element to be automatically separated from the power lines to prevent overheating.

◆ Head-base connection is keyed so that only a head element of correct line voltage can be mounted.


Recommended