PRODUCT DRAWING YORK INTERNATIONAL CORPORATION P.O. Box 1592, York, PA 17405
CONTRACTOR _______________________ PURCHASER ____________________________________________ ORDER NO. _________________________ JOB NAME ______________________________________________ YORK CONTRACT NO. _________________ LOCATION _____________________________________________ YORK ORDER NO. ____________________ ENGINEER ______________________________________________
REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE ________
Supersedes: 160.73-PW3 (703) Form 160.73-PW3 (405)
WIRING DIAGRAM, MAXE™MODEL YK (STYLE F) LIQUID CHILL ERS
OPTIVIEW CONTROL CENTERWITH VARIABLE FREQUENCY DRIVE
JOB DATA:
CHILLER MODEL NO. YK ________________________________________________________NO. OF UNITS _____________COMPRESSOR MOTOR ______________ VOLTS, 3-PHASE, _____________ HzOIL PUMP MOTOR _____________ VOLTS, 3-PHASE, _____________ Hz, _____________FLA
REMARKS:
YORK INTERNATIONAL2
FORM 160.73-PW3 (405)
ELEMENTARY DIAGRAM(UL APPLICATIONS ONLY)
LD10895
FIG. 1 – ELEMENTARY DIAGRAM (UL APPLICATIONS ONLY)
FORM 160.73-PW3 (405)
3YORK INTERNATIONAL
ELEMENTARY DIAGRAM (CON'T)(UL APPLICATIONS ONLY)
ELEMENTARY DIAGRAM (UL APPLICATIONS ONLY) (CONT)LD10896
YORK INTERNATIONAL4
FORM 160.73-PW3 (405)
LD10897
ELEMENTARY DIAGRAM(CE APPLICATIONS ONLY)
FIG. 2 – ELEMENTARY DIAGRAM (CE APPLICATIONS ONLY)
FORM 160.73-PW3 (405)
5YORK INTERNATIONAL
LD10898
ELEMENTARY DIAGRAM (CON'T)(CE APPLICATIONS ONLY)
ELEMENTARY DIAGRAM (CE APPLICATIONS ONLY) (CON'T)
YORK INTERNATIONAL6
FORM 160.73-PW3 (405)
LD10899FIG. 3 – ELEMENTARY DIAGRAM
ELEMENTARY DIAGRAM
FORM 160.73-PW3 (405)
7YORK INTERNATIONAL
LD10900
ELEMENTARY DIAGRAM (CON'T)
ELEMENTARY DIAGRAM (CON'T)
YORK INTERNATIONAL8
FORM 160.73-PW3 (405)
LD10901FIG. 4 – ELEMENTARY DIAGRAM (MICROBOARD 031-02430)
ELEMENTARY DIAGRAM (MICROBOARD 031-02430)
FORM 160.73-PW3 (405)
9YORK INTERNATIONAL
LD10902
ELEMENTARY DIAGRAM (MICROBOARD 031-02430)(CON'T)
ELEMENTARY DIAGRAM (MICROBOARD 031-02430) (CON'T)
YORK INTERNATIONAL10
FORM 160.73-PW3 (405)
LEGEND
LD09000
FORM 160.73-PW3 (405)
11YORK INTERNATIONAL
LD10915
DISPLAY INTERFACE BOARD
FIG. 5 – DISPLAY INTERFACE BOARD
NOTES: 1. This wiring diagram describes the standard elec tron ic
con trol scheme for use with a YORK V.S.D. for details of standard modifi cations, refer to Product Form 160.54-PW7.
2. Field wiring to be in accordance with the National Elec tri cal Code as well as all other applicable codes and spec i fi ca tions. See Product Form 160.54-PW6 for fi eld wiring con nec tions.
3. Numbers along the left side of diagram are line iden ti -fi ca tion numbers. The numbers along the right side in di cate the line num ber location of relay contacts. An un der lined con tact lo ca tion signifi es a normally closed con tact.
4. Main control panel Class 1 fi eld wiring terminal con- nec tion points are indicated by numbers within a rect an gle, i.e. 15 . Main con trol panel factory wiring terminal con- nec tion points are in di cat ed by numbers within a tri an gle, i.e. 5 . Com po nent terminal markings are in di cat ed by num bers within a circle, i.e. C1 . Num bers ad ja cent to cir cuit lines are the cir cuit iden ti fi ca tion num bers.
5. To cycle unit on and off automatically with contacts oth er than those shown, install a cycling device between ter mi nals 1 & 13 (line 37) (see note 7). If a cycling device is installed, jumper must be removed between ter mi nals 1 & 13 .
6. To stop unit and not permit it to start again, install a stop device between terminals 1 & 8 (Line 33) (see note 7). A re mote start-stop switch may be connected to ter mi nals 1 , 7 & 8 (Lines 32 & 33) (see note 7). Remote start-stop switch (Line 32) is op er a tive only in the “re mote” op er at ing mode.
7. Device contact rating to be 5 milliamperes @ 115 volts A.C.
8. Contact rating is 5 Amps resistive @ 120 volts A.C. or 240 volts A.C.
10. For wiring diagram of V.S.D refer to product form 160.49-PW9.
11. A jumper is installed between terminals 24 & 25 for normal operation.
CAUTION: The jumper is the only connection permitted between terminals 24 & 25 . Connections of any other devices to either terminals 24 & 25 may cause inadver-tent compressor start-up.
12. Stop contact on V.S.D logic board is set to trip at 105% FLA.
13. Contact rating is 5 Amps resistive @ 250 Volts A.C. & 30 Volts D.C., 2 Amp Inductive (.4 PF) @ 250 Volts A.C. & 30 Volts D.C.
14. Field connected control power supply is not required, as control transformer is supplied on the V.S.D.
15. For high and low voltage units, the factory supplied jumper between 15 & 53 must be removed when elec-tromechanical starter overloads and/or safety devices are used. For high voltage (2300-4160) UL and CUL ap-proved units only. Elecromechanical compressor motor starter overloads (normally closed) must be connected between 15 & 53 .
16. Each 115VAC fi eld-connected inductive load: i.e. relay coil, mo tor starter coil, etc., shall have a transient sup- pres sor wired in parallel with its coil, physically located at the coil. Spare tran sient suppressors and control cir cuit fuses are sup plied in a bag attached to green ground screw in lower left corner of control panel.
17. Resistor for use with Belimo actuator. Remove resis-tor if hot gas actuator is a Dodge Engineering, Bray or Landis-Staefa actuator.
YORK INTERNATIONAL12
FORM 160.73-PW3 (405)
LD10903FIG. 6 – CONNECTION DIAGRAM (UL APPLICATIONS ONLY)
CONNECTION DIAGRAM(UL APPLICATIONS ONLY)
FORM 160.73-PW3 (405)
13YORK INTERNATIONAL
LD10904
CONNECTION DIAGRAM (CON'T)(UL APPLICATIONS ONLY)
CONNECTION DIAGRAM (UL APPLICATIONS ONLY) (CON'T)
YORK INTERNATIONAL14
FORM 160.73-PW3 (405)
LD10905FIG. 7 – CONNECTION DIAGRAM (CE APPLICATION ONLY)
CONNECTION DIAGRAM(CE APPLICATION ONLY)
FORM 160.73-PW3 (405)
15YORK INTERNATIONAL
LD10906
CONNECTION DIAGRAM (CON'T)(CE APPLICATION ONLY)
CONNECTION DIAGRAM (CE APPLICATION ONLY) (CON'T)
YORK INTERNATIONAL16
FORM 160.73-PW3 (405)
LD10907FIG. 8 – CONNECTION DIAGRAM
CONNECTION DIAGRAM
FORM 160.73-PW3 (405)
17YORK INTERNATIONAL
LD10908CONNECTION DIAGRAM (CON'T)
CONNECTION DIAGRAM (CON'T)
YORK INTERNATIONAL18
FORM 160.73-PW3 (405)
LD10909FIG. 9 – CONNECTIONS TO CONTROL PANEL
CONNECTION DIAGRAM
FORM 160.73-PW3 (405)
19YORK INTERNATIONAL
LD10910
CONNECTION DIAGRAM (CON'T)
CONNECTIONS TO CONTROL PANEL (CON'T)
YORK INTERNATIONAL20
FORM 160.73-PW3 (405)
LD10911FIG. 10 – CONNECTION DIAGRAM
CONNECTION DIAGRAM
FORM 160.73-PW3 (405)
21YORK INTERNATIONAL
LD10912
CONNECTION DIAGRAM (CON'T)
CONNECTION DIAGRAM (CON'T)
YORK INTERNATIONAL22
FORM 160.73-PW3 (405)
FIG. 11 – WIRING FOR 380V THRU 480V UNITS
VARIABLE SPEED OIL PUMP DRIVE PANEL
LD10913
FORM 160.73-PW3 (405)
23YORK INTERNATIONAL
LD10914
PRESSURE - TEMPERATURE CHART
(717) 771-7890www.york.com
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USACopyright © by YORK International Corporation 2005 ALL RIGHTS RESERVEDForm 160.73-PW3 (405) Supersedes: 160.73-PW3 (703)