2
Ease and speed of assembly. No sealants are used on the tank shell. This means that site installation can make full use of hydraulic jacking with the confidence in knowing that the integrity of the tank is not reliant on a large number of individual panel seals. Simplicity of foundations. All that is required to site the tank is a flat load bearing surface, typically of reinforced concrete. The bottom rolled angle at the tank base is simply bolted to the concrete floor. Low maintenance. The galvanised steel panels to the tank are made from high quality pre-galvanised strip to BS2989 Grade Z35, with a zinc coating of 300g/m 2 each side of the panel. For plate thicknesses above 4.2mm, each plate is hot dip galvanised to the requirements of BS EN ISO 1461 (1999). This means a highly corrosion resistant exterior finish to the tank. Internally the hot vulcanised, tailor-made membrane liner separates the stored water from the tank shell, often a major cause of corrosion. The membrane liner itself will not rot or deteriorate in the same way that other coatings and finishes to the interior of tanks will. Galvanised Liquistore ® /Firestore ® Franklin HODGE A member of the Carter Thermal Industries Group For standard fire sprinkler water storage applications or general industrial water storage requirements, the Liquistore ® / Firestore ® tank is a cost effective solution. For standard fire sprinkler water storage applications or general industrial water storage requirements, the Liquistore ® / Firestore ® tank is a cost effective solution. Using site assembled components, consisting of overlapped and bolted galvanised steel panels with either a trough deck or aluminium sectional site assembled cover, together with an internal, open top membrane liner, the Liquistore ® /Firestore ® offers a truly long life and low maintenance water storage system. Standard tanks are available in capacities from 10m 3 (2,200 UK gallons) to 2,222m 3 (488,840 UK gallons) and in diameters from 3.06m to 21.40m and heights from 1.25m to 13.26m. Non standard and larger size tanks are available upon request. Firestore ® tanks are approved by the UK Loss Prevention Certification Board for storage of fire sprinkler water and by the UK Water Regulations Advisory Scheme for the storage of potable water under the name Liquistore ® . Assessed to ISO 9001:2000 Certificate Number 37

Water Tank Galvanised Liquistore

Embed Size (px)

DESCRIPTION

franklin hodge

Citation preview

  • Ease and speed of assembly. No sealants are used on the tank shell. This means that site installation can make full use of hydraulic jacking with the confidence in knowing that the integrity of the tank is not reliant on a large number of individual panel seals.

    Simplicity of foundations. All that is required to site the tank is a flat load bearing surface, typically of reinforced concrete. The bottom rolled angle at the tank base is simply bolted to the concrete floor.

    Low maintenance. The galvanised steel panels to the tank are made from high quality pre-galvanised strip to BS2989 Grade Z35, with a zinc coating of 300g/m2 each side of the panel. For plate thicknesses above 4.2mm, each plate is hot dip galvanised to the requirements of BS EN ISO 1461 (1999). This means a highly corrosion resistant exterior finish to the tank. Internally the hot vulcanised, tailor-made membrane liner separates the stored water from the tank shell, often a major cause of corrosion. The membrane liner itself will not rot or deteriorate in the same way that other coatings and finishes to the interior of tanks will.

    Galvanised

    Liquistore/Firestore

    FranklinHODGE

    A member of the Carter Thermal Industries Group

    For standard fire sprinkler water storage applications or general industrial water storage requirements, the Liquistore/Firestore tank is a cost effective solution.

    For standard fire sprinkler water storage applications or general industrial water storage requirements, the Liquistore/Firestore tank is a cost effective solution.

    Using site assembled components, consisting of overlapped and bolted galvanised steel panels with either a trough deck or aluminium sectional site assembled cover, together with an internal, open top membrane liner, the Liquistore/Firestore offers a truly long life and low maintenance water storage system.

    Standard tanks are available in capacities from 10m3 (2,200 UK gallons) to 2,222m3 (488,840 UK gallons) and in diameters from 3.06m to 21.40m and heights from 1.25m to 13.26m. Non standard and larger size tanks are available upon request.

    Firestore tanks are approved by the UK Loss Prevention Certification Board for storage of fire sprinkler water and by the UK Water Regulations Advisory Scheme for the storage of potable water under the name Liquistore.

    Assessed to ISO 9001:2000Certificate Number 37

  • Capacities From 10m3 to 2,222m3 in standard sizes. Larger capacities are available upon request. Maximum 1,300m3 for UK LPC approval.

    Dimensions From 3.06m to 21.39m in diameter, maximum height is dependent upon diameter. At 21.39m diameter maximum height is 6.33m. Larger diameters available upon request.

    Ancillaries/Accessories A wide range of extra equipment and fittings are available, including: Ball float valves, high/low level switches, internal ladders, sump liners, fire brigade couplings, low level manways. Standard accessories include: Immersion heater, anti-vortex device, contents gauge, external ladder and landing, WRc Type AB airgap.

    Foundations All that is required is a flat load bearing slab. A suggested layout for each of our standard tank dimensions is available on request. Foundation loading is based upon the rim height of the tank multiplied by 9.81 = kN/m2. Level tolerance should be +/- 6.0mm across base.

    Galvanised

    Liquistore/Firestore Technical Data

    Typical 135m3 Firestore Fire Sprinkler water storage tank. 6.11m diameter x 5.142m high.

    6810 Min. Foundation diameter

    6110 Diameter

    5977

    BVH heigh

    t

    5142

    Rim

    Galvanised ZPurlin

    Aluminium access ladder & top

    mounted platform to BS4211

    R32 plastic coatedprofile roof sheetingcolour, moorland green secured to top angle & Z purlins with tek screws

    Galvanised steelrestraint strut

    Ball valve housing835 high 1150 wide2100 long withlockable hinged lid

    Galvanised steelrolled plate flange

    3mm Thick neoprene gasket

    Galvanised pipe spoolNP.16 Flanges standard

    Butyl rubber liner

    Tank shell panel

    3mm Thick neoprene gasket

    Typical connection through tank wall

    FranklinHODGE

    Franklin Hodge Industries LtdJubilee Building, Westfields Trading EstateFaraday Road, Hereford HR4 9NSTelephone: +44 (0) 1432 269605Fax: +44 (0) 1432 277454Web: www.franklinhodge.com

    All information, including illustrations, contained in this brochure is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. Franklin Hodge Industries makes no warranties to the accuracy or completeness of the information and disclaims any liability regarding its use.

    4882

    Top

    water level

    1600 1600 1600

    567

    Elevation Plan

    Heater

    Inlet

    6391

    overall he

    ight