WATER GENERAL NOTES W - 000 JAN 2017 C.B. WATER SUPPLY ALL WATER SYSTEM WORK AND MATERIALS SHALL COMPLY WITH THE LATEST EDITION OF CITY SPECIFICATIONS, AND THE LATEST EDITION OF WSDOT/APWA SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPLE CONSTRUCTION, AND THE WASHINGTON STATE DIVISION ADMINISTRATIVE RULES CHAPTER 333, IN THAT ORDER. ALL WATER AND SANITARY SEWER LATERALS TO BE POTHOLED FOR PIPE SIZE, TYPE, AND DEPTH PRIOR TO CONSTRUCTION. SHOP DRAWINGS ARE REQUIRED AND SHALL BE APPROVED PRIOR TO ALL WATERLINE PIPE SHALL HAVE MINIMUM COVER OF 36 INCHES OVER TOP OF PIPE. THE CONTRACTOR SHALL TAKE PRECAUTIONS TO PROTECT PIPE INTERIORS, FITTINGS AND VALVES AGAINST CONTAMINATION. CONTRACTORS SHALL PROVIDE WRITTEN NOTIFICATION TO CUSTOMERS AND CITY 48 HOURS IN ADVANCE OF ANY PLANNED SHUT DOWN. WRITTEN NOTIFICATION TO BE APPROVED BY CITY. FITTINGS AND PIPE SECTIONS THAT WILL NOT BE DISINFECTED BY CHLORINE IN LINE FOR 24 TO 30 HOURS SHALL HAVE THE INTERIORS SWABBED WITH A 50 mg/l HYPOCHLORITE SOLUTION BEFORE THEY ARE INSTALLED. SWABBING SHALL BE WITNESSED BY CITY INSPECTOR. CONCRETE THRUST BLOCKS ARE TO BE CONSTRUCTED AT TEES, BENDS, FIRE HYDRANTS, BLOW-OFFS, AND WHERE INDICATED ON THE PLANS AND STANDARD DETAILS. THE MINIMUM BEARING SURFACE AGAINST UNDISTURBED SOIL IS SHOWN ON THE DETAIL SHEET. THRUST BLOCKS SHALL BE ALLOWED TO CURE 14 DAYS BEFORE PIPELINE PRESSURE TESTING UNLESS 3-DAY MIX IS USED. FITTINGS SHALL BE WRAPPED WITH A POLY PLASTIC AS A BOND BREAKER. BLOCKS SHALL BE FORMED THE PIPELINE SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE CITY SPECIFICATIONS. THE TEST IS TO BE WITNESSED BY THE CITY PUBLIC WORKS INSPECTOR. THE PIPELINE IS TO BE THOROUGHLY DISINFECTED AND FLUSHED (AT 6 FPS FLUSHING VELOCITY) IN ACCORDANCE WITH THE CURRENT CITY STANDARDS. DECHLORINATION REQUIRED. NO DISCHARGE OF CHLORINATED WATER ALLOWED. SANITARY SEWER NOT TO BE USED FOR DISCHARGE. SUBMIT CHLORINATION AND DE-CHLORINATION PLAN ONE WEEK PRIOR TO CHLORINATION. PRIOR TO ENERGIZING THE WATER SYSTEM, A BACTERIOLOGICAL WATER SAMPLE SHALL BE TAKEN BY THE CITY WATER DEPARTMENT INSPECTOR, SUBMITTED TO AN ACCREDITED TESTING LAB, AND RETURNED TO THE DEPARTMENT INDICATING NO HAZARDS EXISTS. NO ONE OTHER THAN CITY WATER DEPARTMENT PERSONNEL TO OPERATE VALVES. ALL VALVES TO REMAIN ACCESSIBLE. ALL PIPE AND FITTINGS SHALL BE RESTRAINED JOINT. FITTINGS SHALL BE GRIP RING OR MEGALUG DUCTILE IRON ONLY. PIPE TO HAVE FIELD LOCK GASKETS. ALL PIPE SHALL HAVE SECONDARY RESTRAINT TRACER WIRE - 12 GAUGE SOFT DRAWN (BLUE) TO BE USED. UTILITY MARKER TAPE SHALL BE INSTALLED 1.0' TO 1 1/2' ABOVE MAIN AND SERVICE LINES. ANY CONNECTIONS. PRIOR TO POUR. CHLORINATION TO BE PERFORMED AFTER THE LINES ARE FLUSHED AND HAVE PASSED PRESSURE TEST. WITH THRUST BLOCKS OR APPROVED EQUAL. AS BUILT DRAWINGS SHALL BE SUBMITTED & APPROVED PRIOR TO ACCEPTANCE.

WATER SUPPLY - mylongview.com

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: WATER SUPPLY - mylongview.com

WATER GENERAL NOTES

W - 000JAN 2017

C.B.

WATER SUPPLY

ALL WATER SYSTEM WORK AND MATERIALS SHALL COMPLY WITH THE LATEST EDITION OF CITYSPECIFICATIONS, AND THE LATEST EDITION OF WSDOT/APWA SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPLE CONSTRUCTION, AND THE WASHINGTON STATE DIVISION ADMINISTRATIVE RULESCHAPTER 333, IN THAT ORDER.

ALL WATER AND SANITARY SEWER LATERALS TO BE POTHOLED FOR PIPE SIZE, TYPE, AND DEPTH PRIOR TO CONSTRUCTION. SHOP DRAWINGS ARE REQUIRED AND SHALL BE APPROVED PRIOR TO

ALL WATERLINE PIPE SHALL HAVE MINIMUM COVER OF 36 INCHES OVER TOP OF PIPE.

THE CONTRACTOR SHALL TAKE PRECAUTIONS TO PROTECT PIPE INTERIORS, FITTINGS AND VALVES AGAINST CONTAMINATION. CONTRACTORS SHALL PROVIDE WRITTEN NOTIFICATION TO CUSTOMERS AND CITY 48 HOURS IN ADVANCE OF ANY PLANNED SHUT DOWN. WRITTEN NOTIFICATION TO BE APPROVED BY CITY.

FITTINGS AND PIPE SECTIONS THAT WILL NOT BE DISINFECTED BY CHLORINE IN LINE FOR 24 TO 30 HOURS SHALL HAVE THE INTERIORS SWABBED WITH A 50 mg/l HYPOCHLORITE SOLUTION BEFORE THEY ARE INSTALLED. SWABBING SHALL BE WITNESSED BY CITY INSPECTOR.

CONCRETE THRUST BLOCKS ARE TO BE CONSTRUCTED AT TEES, BENDS, FIRE HYDRANTS, BLOW-OFFS, AND WHERE INDICATED ON THE PLANS AND STANDARD DETAILS. THE MINIMUM BEARING SURFACE AGAINST UNDISTURBED SOIL IS SHOWN ON THE DETAIL SHEET. THRUST BLOCKS SHALL BE ALLOWED TO CURE 14 DAYS BEFORE PIPELINE PRESSURE TESTING UNLESS 3-DAY MIX IS USED.FITTINGS SHALL BE WRAPPED WITH A POLY PLASTIC AS A BOND BREAKER. BLOCKS SHALL BE FORMED

THE PIPELINE SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE CITY SPECIFICATIONS. THE TEST IS TO BE WITNESSED BY THE CITY PUBLIC WORKS INSPECTOR.

THE PIPELINE IS TO BE THOROUGHLY DISINFECTED AND FLUSHED (AT 6 FPS FLUSHING VELOCITY) IN ACCORDANCE WITH THE CURRENT CITY STANDARDS. DECHLORINATION REQUIRED. NODISCHARGE OF CHLORINATED WATER ALLOWED. SANITARY SEWER NOT TO BE USED FOR DISCHARGE.SUBMIT CHLORINATION AND DE-CHLORINATION PLAN ONE WEEK PRIOR TO CHLORINATION.

PRIOR TO ENERGIZING THE WATER SYSTEM, A BACTERIOLOGICAL WATER SAMPLE SHALL BE TAKEN BY THE CITY WATER DEPARTMENT INSPECTOR, SUBMITTED TO AN ACCREDITED TESTING LAB, ANDRETURNED TO THE DEPARTMENT INDICATING NO HAZARDS EXISTS.

NO ONE OTHER THAN CITY WATER DEPARTMENT PERSONNEL TO OPERATE VALVES. ALL VALVES TO REMAIN ACCESSIBLE.

ALL PIPE AND FITTINGS SHALL BE RESTRAINED JOINT. FITTINGS SHALL BE GRIP RING OR MEGALUG DUCTILE IRON ONLY. PIPE TO HAVE FIELD LOCK GASKETS. ALL PIPE SHALL HAVE SECONDARY RESTRAINT

TRACER WIRE - 12 GAUGE SOFT DRAWN (BLUE) TO BE USED.

UTILITY MARKER TAPE SHALL BE INSTALLED 1.0' TO 1 1/2' ABOVE MAIN AND SERVICE LINES.

ANY CONNECTIONS.

PRIOR TO POUR.

CHLORINATION TO BE PERFORMED AFTER THE LINES ARE FLUSHED AND HAVE PASSED PRESSURE TEST.

WITH THRUST BLOCKS OR APPROVED EQUAL.

AS BUILT DRAWINGS SHALL BE SUBMITTED & APPROVED PRIOR TO ACCEPTANCE.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 2: WATER SUPPLY - mylongview.com

WATER GENERAL NOTES

W - 001JAN 2017

C.B.

WATER NOTES ADDITIONAL

1. CONNECTION TO THE WATER SYSTEM SHALL BE INSPECTED BY PUBLIC WORKS DEPARTMENT PRIOR TO BACKFILL 48 HOURS (2 WORKING DAYS) NOTICE FOR INSPECTION.2. ALL WATER SYSTEM FLUSHING, INCLUDING FIRE LINES, SHALL BE SCHEDULED THROUGH THE PUBLIC WORKS DEPARTMENT WHO WILL IN TURN SCHEDULE THE WATER DEPARTMENT TO BE PRESENT TO RECORD WATER USED AND TO OPERATE VALVES.3. UTILITY PERMITS MUST BE APPLIED AND PAID FOR PRIOR TO ANY CONNECTIONS BEING MADE TO EITHER THE WATER OR SEWER SYSTEM.4. BACKFLOW DEVICES REQUIRED ON ALL COMMERCIAL, IRRIGATION AND FIRE SERVICE CONNECTIONS TO THE CITY SYSTEM. CITY TO DETERMINE LEVEL OF HAZARD & DEVICE REQUIRED DURING PLAN REVIEW/DESIGN.5. ONLY CITY WATER DEPARTMENT PERSONNEL SHALL OPERATE CITY VALVES.6. SHUT DOWNS OF THE WATER SYSTEM FOR CONNECTIONS WILL BE DONE BETWEEN TUESDAY THROUGH THURSDAY FROM 8 AM TO 4 PM. MAX TIME THE WATER MAY BE OFF IS 4 HOURS.7. SUBMITTALS AND SHOP DRAWINGS MUST BE APPROVED BEFORE THE SHUT DOWN IS SCHEDULED CONTRACTOR IS REQUIRED TO NOTIFY THE CUSTOMERS AFFECTED 2 WORKING DAYS IN ADVANCE IN WRITTING WITH CITY APPROVED LETTER. CONTRACTOR SHALL PRE-BOLT ALL MATERIALS & HAVE THE ASSEMBLY INSPECTED PRIOR TO ANY SHUT DOWN OF THE CITY SYSTEM. ALL BOLTS THAT WILL NOT UNDERGO PRESSURE TESTING SHALL BE TORQUE TIGHTENED TO MANUFACTURERES RECOMMENDATIONS IN THE PRESENCE OF THE INSPECTOR.8. METERS LARGER THAN 1" WILL BE SUPPLIED AND INSTALLED BY THE CONTRACTOR INCLUDING FACTORY ACCURACY CERTIFICATION PROVIDED TO THE CITY.9. IT SHALL BE THE CONTRACTORS RESPONSIBILITY TO ASSURE THAT WATER METERS OR CITY IDENTIFIED APPURTENANCES REMOVED DURING CONSTRUCTION OR DEVELOPMENT SHALL BE RETURNED TO CITY'S WATER DEPARTMENT WITHIN 24HRS OF REMOVAL OR ABANDONMENT.10. CONCRETE VALVE COLLARS SHALL BE STAMPED WITH PIPE SIZE AND FLOW DIRECTION.

(CITY SHALL SUPPLY/LOAN STAMPS)

PRESSURE TESTING AND CHLORINATION

THE CITY OF LONGVIEW OPERATIONS CREWS SHALL BE RESPONSIBLE FOR OPERATION OF ALL VALVES ONTHE CITY WATER SYSTEM. THIS CREW WILL PERFORM FLUSHING ACTIVITIES INCLUDING DECHLORINATIONOF FLUSHING WATER. THE CONTRACTOR WILL BE RESPONSIBLE TO CONSTRUCT AND INSTALL THE BLOWOFF (S) AS SHOWN ON THE PLANS AND SHALL BE RESPONSIBLE TO DETERMINE WATER DISPOSAL LOCATION(S) TOGETHER WITH PROPER AND SAFE PLUMBING TO DISCHARGE THE BLOW OFF WATER TO THE DISPOSALLOCATION. DISPOSAL LOCATION (S) SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TOSCHEDULING THE WORK.

ONCE FLUSHING HAS BEEN SATISFACTORILY COMPLETED, THE CONTRACTOR SHALL PERFORM THEPRESSURE TESTING REQUIREMENTS. THEY ARE RESPONSIBLE TO NOTIFY THE CITY 48 HOURS IN ADVANCEOF THE TEST TO SCHEDULE THE INSPECTION OF THE PRESSURE TEST.

ONCE THE TEST HAS SATISFACTORILY PASSED THE TESTING REQUIREMENTS, THE CONTRACTOR SHALLNOTIFY THE CITY. THE CITY WILL THEN SCHEDULE THE CHLORINATION, DECHLORINATION AND BACTERIATEST. ONCE THE BACTERIA SAMPLE HAS SATISFACTORILY PASSED THE CITY WILL NOTIFY THECONTRACTOR AND TURN ON THE WATER SYSTEM WHEN REQUESTED BY THE CONTRACTOR.

THE CONTRACTOR CAN THEN SCHEDULE FINAL CONNECTION (S) AND TRANSFER/CONNECTION OF WATERSERVICE (S).

PAYMENT FOR ALL OF THE CONTRACTORS WORK ASSOCIATED WITH THESE ACTIVITIES WILL BEINCIDENTAL TO OTHER CONTRACT ITEMS AND NO ADDITIONAL PAYMENT SHALL BE MADE.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 3: WATER SUPPLY - mylongview.com

1.

CL

EA

RA

NC

ES

:

MIN

. 5

' F

RO

M E

DG

E O

F D

RIV

EW

AY

- N

O M

ET

ER

S IN

D

RIV

EW

AY

SE

CT

IO

N

MIN

. 1

0' F

RO

M T

RE

ES

MIN

. 5

' F

RO

M O

TH

ER

U

TIL

IT

IE

S, E

XC

EP

T S

EW

ER

@

1

0'

MIN

. D

EP

TH

A

T R

IG

HT

O

F W

AY

IS

3

6"

MIN

. D

EP

TH

O

N C

US

TO

ME

R S

ID

E IS

1

8"

2.

CT

S =

C

OM

PR

ES

SIO

N A

LL

B

RA

SS

&

C

OP

PE

R.T

HE

S

ER

VIC

E L

IN

E

SH

AL

L B

E C

ON

TIN

UO

US

W

IT

HO

UT

C

OU

PL

IN

GS

B

ET

WE

EN

T

HE

CO

RP

OR

AT

IO

N S

TO

P A

ND

C

UR

B S

TO

P V

AL

VE

U

NL

ES

S A

PP

RO

VE

D

BY

T

HE

E

NG

IN

EE

R.

3.

NO

D

IR

EC

T T

AP

S A

LL

OW

ED

.

4.

ME

TE

R L

OC

AT

IO

N T

O B

E D

ET

ER

MIN

ED

B

Y T

HE

C

IT

Y.

5.

SA

DD

LE

S S

HA

LL

B

E D

OU

BL

E B

AN

D D

UC

TIL

E IR

ON

, B

RO

NZ

E,

ST

AIN

LE

SS

S

TE

EL

, O

R B

AN

D-T

YP

E W

IT

H I.P

. S

TA

ND

AR

D T

AP

PIN

G.

6.

BA

LL

C

OR

PO

RA

TIO

N S

TO

PS

F

OR

U

SE

W

IT

H S

AD

DL

ES

S

HA

LL

B

E

OF

B

RO

NZ

E A

LL

OY

W

IT

H IN

LE

T I.P

. S

TA

ND

AR

D T

HR

EA

D A

ND

C

OM

PR

ES

SIO

N O

UT

LE

T C

OM

PA

TIB

LE

W

IT

H C

ON

NE

CT

IO

N P

IP

IN

G,

WIT

H N

O A

DA

PT

ER

S.

7.

SE

RV

IC

E P

IP

E S

HA

LL

B

E A

M

IN

IM

UM

O

F 1

" T

YP

E K

S

OF

T C

OP

PE

R

OR

1

" P

OL

Y C

TS

P

IP

E (2

50

PS

I M

IN

. R

AT

IN

G) C

OM

PR

ES

SIO

N

CO

UP

LIN

G F

OR

U

SE

IN

C

ON

NE

CT

IN

G P

LA

IN

E

ND

W

AT

ER

S

ER

VIC

E

PIP

ES

S

HA

LL

B

E A

PP

LIC

AB

LE

F

OR

T

HE

T

YP

E O

F P

IP

E B

EIN

G

CO

UP

LE

D. C

OM

PR

ES

SIO

N C

OU

PL

IN

GS

S

HA

LL

H

AV

E A

RM

OR

ED

GA

SK

ET

S W

HE

N D

IS

-S

IM

IL

AR

M

ET

AL

P

IP

ES

A

RE

B

EIN

G JO

IN

ED

.

8. W

AT

ER

M

ET

ER

S S

HA

LL

N

OT

B

E P

LA

CE

D IN

S

ID

EW

AL

K.

9. C

OR

PO

RA

TIO

N S

TO

PS

A

ND

C

OU

PL

IN

GS

S

HA

LL

B

E O

F T

HE

FO

LL

OW

IN

G M

AN

UF

AC

TU

RE

R B

RA

ND

S A

ND

B

E C

OM

PR

ES

SIO

N

DE

SIG

N.

MU

EL

LE

R

McD

ON

AL

D

FO

RD

ME

TE

R B

OX

&

L

ID

P

ER

ST

AN

DA

RD

P

LA

NS

W

-1

00

A

ND

W

-1

10 M

ET

ER

B

OX

SE

T A

T P

RO

PE

RT

Y

LIN

E O

R E

DG

E O

F R

OW

4"

8"

2"±

6" M

IN

.

NO

TE

S:

R / W

ME

TE

R T

O B

E P

LU

MB

A

ND

S

ET

O

N A

H

OR

IZ

ON

TA

L P

LA

NE

ME

TE

R T

O B

E C

EN

TE

RE

D E

AC

H W

AY

IN

SID

E M

ET

ER

B

OX

A

B

C

BA

LL

C

OR

P. S

TO

P

M.I.P

. x C

.T

.S

.

CO

MP

RE

SS

IO

N

DIS

TR

IB

UT

IO

N M

AIN

20

2S

S

AD

DL

E

(D

OU

BL

E B

AN

D)

1" T

YP

E "K

" O

R

PO

LY

S

ER

VIC

E

PIP

E

12

" o

f

5

8

" C

ST

C T

O S

ET

M

ET

ER

B

OX

ON

. L

EA

VE

1

" A

IR

G

AP

B

EL

OW

M

ET

ER

FR

EE

ZE

P

LA

TE

.

IN

ST

AL

L B

RA

SS

2

" -

4" N

IP

PL

E

FIN

IS

H G

RA

DE

(N

O L

OW

ER

T

HA

N

EL

EV

. O

F B

AC

K

OF

S

ID

EW

AL

K)

WA

TE

R M

ET

ER

S

HA

LL

B

E

PR

OV

ID

ED

B

Y T

HE

C

IT

Y U

P T

O

1". C

ON

TR

AC

TO

R T

O P

RO

VID

E

LA

RG

ER

M

ET

ER

S.

A B

C

3

4

" B

AL

L V

AL

VE

-

FE

MA

LE

I.P

. x

ME

TE

R W

/ H

AN

DL

E

1" X

3

4

" A

NG

LE

B

AL

L

VA

LV

E S

TO

P IP

x

ME

TE

R

1" B

AL

L V

AL

VE

-

FE

MA

LE

I.P

. x

ME

TE

R W

/ H

AN

DL

E

1" A

NG

LE

B

AL

L

VA

LV

E S

TO

P IP

x

ME

TE

R

3

4

" M

ET

ER

1" M

ET

ER

VA

LV

E

1" B

AL

L V

AL

VE

- F

.I.P

. x C

TS

CO

MP

RE

SS

IO

N W

IT

H L

OC

KIN

G

OP

ER

AT

IN

G N

UT

. (N

O A

DA

PT

ER

S

AL

LO

WE

D)

BA

LL

V

AL

VE

T

O B

E IN

ST

AL

LE

D A

T 9

0° T

O

AN

GL

E S

TO

P

10

. M

ET

ER

B

OX

L

ID

S S

HA

LL

B

E T

OU

CH

R

EA

D A

PP

LIC

AT

IO

N W

IT

H P

LU

G

IN

K

NO

CK

-O

UT

.

11

. P

OL

Y P

IP

E R

EQ

UIR

ES

IN

TE

RN

AL

S

TA

IN

LE

SS

S

TE

EL

S

LE

EV

E F

OR

CO

NN

EC

TIO

N T

O C

OM

PR

ES

SIO

N B

RA

SS

F

IT

TIN

GS

.

12

. U

TIL

IT

Y M

AR

KE

R T

AP

E S

HA

LL

B

E IN

ST

AL

LE

D 1

.0

' T

O 1

-1

/2

' A

BO

VE

SE

RV

IC

E L

IN

E.

13

. A

LL

F

IT

TIN

GS

S

HA

LL

M

EE

T S

EC

TIO

N 1

41

2 S

DW

A.

14

. M

AR

KIN

G T

AP

E S

HA

LL

B

E B

LU

E IN

C

OL

OR

.

12

ga

S

OF

T D

RA

WN

C

OP

PE

R

TR

AC

ER

W

IR

E - B

LU

E IN

C

OL

OR

WIR

E S

PL

IC

E A

T E

AC

H S

ER

VIC

E T

O

BE

M

AD

E W

IT

H D

IR

EC

T B

UR

Y L

UG

MA

NU

FA

CT

UR

ED

K

IN

G IN

NO

VA

TIO

N,

CO

PP

ER

HE

AD

, O

R A

PP

RO

VE

D

EQ

UA

L D

ES

IG

N T

O N

OT

C

UT

T

HE

ME

TA

L W

IR

E O

R T

HE

M

AIN

T

RA

CE

R

WIR

E.

IN

ST

AL

L A

M

cD

ON

AL

D, F

OR

D, O

R A

PP

RO

VE

D E

QU

AL

S

ER

VIC

E

FIT

TIN

G &

F

IP

\C

TS

C

OM

P B

AL

L V

AL

VE

(M

cD

ON

AL

D #

AY

76

10

2W

PA

-1

W/ A

NO

DE

; F

OR

D B

41

-4

44

-T

W-Q

-N

L-W

) A

ND

A

TT

AC

H T

RA

CE

W

IR

E.

AL

L O

TH

ER

S

ER

VIC

E F

IT

TIN

GS

O

TH

ER

T

HA

N M

cD

ON

AL

D A

ND

FO

RD

, A

NO

DE

A

TT

AC

HM

EN

T D

EV

IC

E M

US

T B

E A

PP

RO

VE

D.

S

OM

E C

US

TO

ME

R S

ID

E S

ER

VIC

E L

IN

ES

M

AY

B

E O

LD

A

ND

DE

FIC

IE

NT

. IT

IS

U

P T

O T

HE

C

ON

TR

AC

TO

R T

O D

IS

CU

SS

TH

IS

W

IT

H H

OM

EO

WN

ER

A

S A

NY

IS

SU

ES

A

RIS

E A

ND

C

OM

E

TO

A

R

ES

OL

UT

IO

N P

RIO

R T

O D

AM

AG

IN

G P

IP

E T

HA

T W

AS

T

O

RE

MA

IN

A

FT

ER

C

ON

NE

CT

IO

N O

F M

ET

ER

. N

O A

DD

IT

IO

NA

L

PA

YM

EN

T W

IL

L B

E M

AD

E D

UE

T

O D

AM

AG

E T

O T

HE

CU

ST

OM

ER

S

ER

VIC

E L

IN

E.

AN

GL

E B

AL

L

VA

LV

E S

TO

PS

AR

E A

CC

EP

TA

BL

E

K.H.

W-010

MAR 2021

1" DOMESTIC WATER SERVICE

AutoCAD SHX Text
STANDARD PLAN:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
Longview:
Page 4: WATER SUPPLY - mylongview.com

METER

P

L

7

1

4

"

12

"

ANGLE BALL VALVE

ELBOW

BALL VALVE

CURB

STAMP FACE OF CURB

WITH "W"

FINISHED STREET GRADE

36

" C

OV

ER

STANDARD

VALVE BOX

(SEE W-250)

WATER MAIN

SERVICE SADDLE

DOUBLE STRAP

ROMAC TYPE 202S

2" GATE VALVE, IP x IP

W/ 2" OPERATING NUT

2" MIP x COMP

250 PSI P

OLY

12" OF

5

8

" CSTC

TEE

1" COPPER

TUBE2" COPPER TUBE

TYP BOTH SIDES

BURY LINE

2" BELOW

BYPASS

TEE

COUPLING

1

1

4

" COPPER TUBE

ELBOW

2" FL INLET

& OUTLET FIP

METER BOXES PER STANDARD PLAN W-080

ALL SERVICES REQUIRE AN APPROVED

BACKFLOW PREVENTION ASSEMBLY

FLOW

A

A

SECTION A-A

3"LONG 2" NIPPLE

MIP x MIP

2" ADAPTER

MIP x COMP.

TYPE "K" C

OPPER

OR

1. CLEARANCES:

MIN. 5' FROM EDGE OF DRIVEWAY - NO METERS IN DRIVEWAY SECTION

MIN. 10' FROM TREES

MIN. 5' FROM OTHER UTILITIES, EXCEPT SEWER @ 10'

MIN. DEPTH AT RIGHT OF WAY IS 36"

MIN. DEPTH ON CUSTOMER SIDE IS 18"

2. CTS = COMPRESSION ALL BRASS & COPPER.THE SERVICE LINE SHALL BE

CONTINUOUS WITHOUT COUPLINGS BETWEEN THE CORPORATION STOP

AND CURB STOP VALVE UNLESS APPROVED BY THE ENGINEER.

3. NO DIRECT TAPS ALLOWED.

4. METER LOCATION TO BE DETERMINED BY THE CITY.

5. SADDLES SHALL BE DOUBLE BAND DUCTILE IRON, BRONZE, STAINLESS

STEEL, OR BAND-TYPE WITH I.P. STANDARD TAPPING.

6. BALL CORPORATION STOPS FOR USE WITH SADDLES SHALL BE OF BRONZE

ALLOY WITH INLET I.P. STANDARD THREAD AND

COMPRESSION OUTLET COMPATIBLE WITH CONNECTION PIPING, WITH NO

ADAPTERS.

7. SERVICE PIPE SHALL BE A MINIMUM OF 2" TYPE K SOFT COPPER OR 2" POLY

CTS PIPE (250PSI MIN. RATING) COMPRESSION COUPLING FOR USE IN

CONNECTING PLAIN END WATER SERVICE PIPES SHALL BE APPLICABLE FOR

THE TYPE OF PIPE BEING COUPLED. COMPRESSION COUPLINGS SHALL

HAVE ARMORED GASKETS WHEN DIS-SIMILAR METAL PIPES ARE BEING

JOINED.

8. WATER METERS SHALL NOT BE PLACED IN SIDEWALK.

9. CORPORATION STOPS AND COUPLINGS SHALL BE OF THE FOLLOWING

MANUFACTURER BRANDS AND BE COMPRESSION DESIGN.

MUELLER

McDONALD

FORD

NOTES:

10. METER BOX LIDS SHALL BE TOUCH READ APPLICATION WITH PLUG IN

KNOCK-OUT.

11. POLY PIPE REQUIRES INTERNAL STAINLESS STEEL SLEEVE FOR

CONNECTION TO COMPRESSION BRASS FITTINGS.

12. UTILITY MARKER TAPE SHALL BE INSTALLED 1.0' TO 1-1/2' ABOVE SERVICE

LINE.

13. ALL FITTINGS SHALL MEET SECTION 1412 SDWA.

14. MARKING TAPE SHALL BE BLUE IN COLOR.

15. METER LAYING LENGTH: 1

1

2

" = 13"

2" = 17"

PLUS

1

2

" FOR GASKETS

16. ALL METERS SHALL READ IN ONE CUBIC FEET.

17. METERS LARGER THAN 1" WILL BE SUPPLIED BY THE CONTRACTOR.

A. MUST BE DELIVERED TO THE WATER DEPARTMENT SHOP FOR

ACCURACY.

B. MUST BE INSTALLED BY THE CONTRACTOR.

18. METER SIZE TO BE APPROVED BY THE CITY.

19. METER TO BE REMOTE READ TYPE.

20. 1

1

2

" METERS WILL REQUIRE 2" x 1

1

2

" METER FLANGE REDUCERS.

21. FINAL GRADE ADJUSTMENTS SHALL BE PERFORMED BY MODIFYING &

STACKING BOXES.

BOXES SHALL NOT BE GROUTED TOGETHER

22. SETTER SHALL BE AY McDONALD #720R718WWFF 2" OR APPROVED EQUAL.

12ga SOFT DRAWN COPPER

TRACE WIRE - BLUE IN COLOR

WIRE SPLICE AT EACH SERVICE TO

BE MADE WITH 3M DIRECT BURY

SPLICE KIT #DBR/Y6 OR APPROVED

EQUAL

INSTALL A McDONALD SERVICE

FITTING 2" CTS COMP x 2" MIP

#AY74753Q-2 W/ ANODE ADPT TO

BOTTOM OF SETTER AND ATTACH

TRACE WIRE

2" DOMESTIC WATER SERVICE

W - 020JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 5: WATER SUPPLY - mylongview.com

METER

P

L

2" IRRIGATION WATER SERVICE

12"

CURB

STAMP FACE OF CURB

WITH "W"

FINISHED STREET GRADE

36" C

OV

ER

STANDARD

VALVE BOX

(SEE W-250)

WATER MAIN

SERVICE SADDLE

DOUBLE STRAP

ROMAC TYPE 202S

3" NIPPLE,

MIP x MIP

2" GATE VALVE, IP x IP

W/ 2" OPERATING NUT

2" MIP x COMP

1. ALL FITTINGS SHALL BE BRASS.

2. NO FITTING ALLOWED FROM MAIN TO SETTER.

3. METER LAYING LENGTH: 1

1

2

" = 13"

2" = 17"

PLUS

1

2

" FOR GASKETS

4. ALL METERS SHALL READ IN ONE CUBIC FEET.

5. METERS LARGER THAN 1" WILL BE SUPPLIED BY THE CONTRACTOR.

A. MUST BE DELIVERED TO THE WATER DEPARTMENT.

B. MUST BE INSTALLED BY THE CONTRACTOR.

6. METER SIZE TO BE APPROVED BY THE CITY.

7. METER TO BE REMOTE READ TYPE.

8. 1

1

2

" METERS WILL REQUIRE 2" x 1

1

2

" METER FLANGE REDUCERS.

9. FINAL GRADE ADJUSTMENT SHALL BE PERFORMED BY MODIFYING & STACKING BOXES.

METER BOX PER STANDARD PLAN

ALL SERVICES REQUIRE AN APPROVED

BACKFLOW PREVENTION ASSEMBLY

NOTES:

TYPE "K" COPPER

12"

90° ELBOW

HT-20 TEST TEE

2" ANGLE BALL VALVE

CURB STOP x C.T.S.

5

8

" CSTC

12" OF

5

8" CSTC

8" MIN

14" MAX

2" IRRIGATION WATER SERVICE

W - 030JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 6: WATER SUPPLY - mylongview.com

P

L

1

3" AND LARGER ABOVE GROUND DOMESTIC METER

STRAINER

3" METER ONLY

USE 4" TO 3" REDUCER

MJ TEE MJ VALVE MJ TEE

THRUST BLOCK (4 TYP.)

CL BFP

FLOW

3'

MIN.

BOTTOM MJ 90°

THRUST BLOCK (4 TYP.)

NRS

SPOOL

CITY APPROVED

METER

SPOOL

NRS

BOTTOM MJ 90°

CITY APPROVED

METER AND STRAINER

RSW GATE VALVE NRSRSW GATE VALVE NRS

PIT READ MODULE

ON STATIONARY PART

OF BOX FACING STREET

12"

HOT BOX OR EQUAL

PASSIVE INSULATION

BOX NEEDS TO BE SIZED

APPROPRIATELY FOR

DEVICE SIZE

IF NOT FLANGED

3

4

" STAINLESS STEEL ALLTHREAD

ROD BOTH SIDES

MJ W/ MEGA LUGS AND

VERTICAL RODS, BOTH SIDES

FLOW

D.I.P. FLG.

SPOOL x PE

BOTH SIDES

FLG

1. INSULATED ENCLOSURES INTERIOR CLEARANCE TO BE 12"

MINIMUM AND PER MANUFACTURERS SPECIFICATIONS.

2. ALL THRUST BLOCKS TO BE CLASS 4000

3. 5 PIPE DIAMETER MIN. PRIOR TO THE STRAINER AND AFTER THE

METER.

4. METERS LARGER THAN 1" WILL BE SUPPLIED BY THE CONTRACTOR.

A. MUST BE DELIVERED TO THE WATER DEPARTMENT SHOP

FOR ACCURACY.

B. MUST BE INSTALLED BY THE CONTRACTOR.

NOTES: 2" TEST PLUG, 4" BRASS NIPPLE,

WITH 2" BALL VALVE AND PLUG WITH

ROMAC SST SADDLE.

1

PLAN

ELEVATION

PAD TO BE 12" OUT FROM

ALL SIDES OF ENCLOSURE

CLASS 3000 CONCRETE

SPOOL

FINISH GRADE

SLOPE AWAY FROM

STRUCTURE

3'

MIN.

(PER INSPECTOR)

12"

TEE

90°

90°

90° BENDS SHALL BE THRUST BLOCKED

OR APPROVED RESTRAINT USED

VALVE TO BE

TURNED 90°

4" DOMESTIC WATER SERVICE ABOVE GROUND

W - 050JAN 2017

C.B.

AutoCAD SHX Text
STRAINER
AutoCAD SHX Text
STRAINER
AutoCAD SHX Text
AWWA PLATE
AutoCAD SHX Text
AWWA PLATE
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 7: WATER SUPPLY - mylongview.com

P

L

FINISHED GRADE

1

AWWA

PLATE

STRAINER

AWWA

PLATE

STRAINER

PLAIN END x

FLANGE SPOOL

NRS

16" MIN.

NRS

SPOOL

CITY APPROVED

METER

FLOW

DOOR SEAM

16" MIN.

PLAIN END x

FLANGE

SPOOL

A A

RSW GATE

VALVE NRS

TOP OF DOOR TO

FINISH GRADE

PLAIN END x

FLANGE

SPOOL

PLAIN END x

FLANGE SPOOL

RSW GATE VALVE NRS

CITY APPROVED / CITY TESTED

METER AND STRAINER TO BE

PROVIDED BY CONTRACTOR

24

" M

IN

.

RSW GATE VALVE NRS

6" MIN.

12" MIN.

18" MAX.

6" MIN.

FLOW

3" MIN.

6" MAX.

SECTION A - A

PLAN

1. LINK SEALS AROUND ALL PIPE OPENINGS.

2. NOT TO BE LOCATED IN TRAFFIC AREAS OR PARKING LOTS.

3. UTILITY VAULT OR EQUAL.

4. USE DOUBLE RAISE ALUMINUM LW PRODUCTS HHD-1 HYDRAULIC

ASSIST LOCKING HATCH (MIN. 36" x 60") (HS20 LOADING) LEAK

PROOF GASKET.

5. ALL THUST BLOCKS TO BE CLASS 4000.

6. FIVE (5) PIPE DIAMETERS MIN. PRIOR TO THE STRAINER AND AFTER

THE METER.

7. ALL METERS SHALL READ IN ONE CUBIC FEET.

8. HATCH DRAINS TO BE PLUMBED TO DAYLIGHT.

9. METERS LARGER THAN 1" WILL BE SUPPLIED BY THE CONTRACTOR.

A. MUST BE DELIVERED TO THE WATER SHOP FOR ACCURACY.

B. MUST BE INSTALLED BY CONTRACTOR.

NOTES:RSW = RESILIENT SEAT WEDGE

NRS = NON-RISING STEM

KNOCKOUTS NOT ALLOWED IN VAULTS

2" TEST PLUG, 4" BRASS NIPPLE, WITH 2"

BALL VALVE WITH PLUG

1

SPOOL

3" METER ONLY

USE 4" TO 3" REDUCER

STRAINER

SPOOL

REMOTE

READER

4" DOMESTIC WATER SERVICE BELOW GROUND

W - 060JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 8: WATER SUPPLY - mylongview.com

ARMORCAST POLYMER

CONCRETE COVER

NO:A60001947T-H7

ARMORCAST POLYMER

CONCRETE BOX

NO:A6001640PCX18

3" MOUSE HOLE

PLUG REMOTE READ

HOLE IF REMOTE READ

IS NOT INSTALLED W/

METER

19

1

4

"

32

1

4

"

16

1

4

"

1

2

"

17

1

8

"

30

1

2

"

17

1

2

"

2"

TOUCH READ HOLE

41

8

" X

3

8

"

DEEP W/ 1

7

8

" D THROUGH

HOLE

MAGNET (2X)

NON SKID

PICK HOLE

TRAFFIC COVER & BOX, TOUCH AND READ APPLICATION 1 1/2" & 2" METER

W - 080

JUNE 2020

K.H.

AutoCAD SHX Text
PW DIRECTOR APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 9: WATER SUPPLY - mylongview.com

TRAFFIC COVER AND BOX

TOUCH AND READ APPLICATION

ARMORCAST POLYMER

CONCRETE COVER NO:

A6000484T-H7

3" MOUSE HOLE

PLUG REMOTE READ

HOLE IF REMOTE READ

IS NOT INSTALLED W/

METER

ARMORCAST POLYMER

CONCRETE BOX NO:

A6000485

13

1

4

"

20

1

4

"

12"

10

1

4

"

1

2

"

17

1

8

"

18

1

8

"

11

1

4

"

1

3

4

"

TOUCH READ HOLE

41

8

" X

3

8

"

DEEP W/ 1

7

8

" D THROUGH

HOLE

MAGNET (2X)

NON SKID SURFACE

PICK HOLE

TOUCH AND READ FOR 3/4" WATER METER BOX

W - 100

JUNE 2020

K.H.

AutoCAD SHX Text
PW DIRECTOR APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 10: WATER SUPPLY - mylongview.com

ARMORCAST POLYMER

CONCRETE COVER

NO:A60001969-H7

ARMORCAST POLYMER

CONCRETE BOX

NO:A6001946PCX12

23

1

4

"

13

3

4

"

3" MOUSE HOLE

PLUG REMOTE READ

HOLE IF REMOTE READ IS

NOT INSTALLED W/

METER

2"

15

1

2

"

25"

12

5

8

"

1

2

"

22

1

4

"

NON SKID SURFACE

MAGNET (2X)

TOUCH READ HOLE 4

1

8

" X

3

8

"

DEEP W/ 1

7

8

" D HOLE

PICK HOLE

TRAFFIC COVER & BOX, TOUCH & READ APPLICATION - 1" METERS

W - 110

JUNE 2020

K.H.

AutoCAD SHX Text
PW DIRECTOR APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 11: WATER SUPPLY - mylongview.com

FIN

IS

HE

D G

RA

DE

18

" M

IN

.

36

" M

AX

.

SS

S

CR

EE

N

3" T

O 6

"

12

" M

IN

.

36

" M

AX

.

1

5

2

5

9

13

SE

CT

ION

MIN

. 1

6" C

LE

AR

AN

CE

B

ET

WE

EN

VA

UL

T S

ID

E A

ND

P

RV

9

5

2

15

6

8

6" T

YP

.

12

" M

IN

.

(B

OT

H S

ID

ES

)

16

"

"Y

" S

TR

AIN

ER

14

7

11

10

13

3

4

12

12

8

9

6

12

7

NO

RM

AL

LY

C

LO

SE

D

FL

OW

2" M

IN

.

2

1. A

LL

P

EN

ET

RA

TIO

NS

O

F V

AU

LT

S

HA

LL

B

E

LIN

K S

EA

L O

R E

QU

AL

.

2. P

RV

H

AS

T

O B

E S

IZ

ED

T

O R

EL

IE

VE

TO

TA

L C

AP

AC

IT

Y O

F S

TA

TIO

N IN

AC

CO

RD

AN

CE

W

IT

H M

AN

UF

AC

TU

RE

RS

RE

CO

MM

EN

DA

TIO

N.

3. A

LL

T

HR

US

T B

LO

CK

S T

O B

E C

LA

SS

4

00

0

CO

NC

RE

TE

.

4. H

AT

CH

T

O D

RA

IN

O

UT

SID

E V

AU

LT

.

5. A

LL

M

J F

IT

TIN

GS

T

O B

E R

ES

TA

IN

ED

.

NO

TE

S:

PLA

N

1

PR

ES

SU

RE

R

ED

UC

IN

G V

AL

VE

9

0-0

1 W

IT

H S

TE

M IN

DIC

AT

OR

(C

LA

-V

AL

VE

O

R E

QU

AL

) (F

IR

E A

ND

/O

R P

EA

K D

EM

AN

D).

"Y

" S

TR

AIN

ER

F

LG

x M

J

LO

W F

LO

W P

RE

SS

UR

E R

ED

UC

IN

G V

AL

VE

9

0-0

1 W

IT

H S

TE

M

IN

DIC

AT

OR

(C

LA

-V

AL

VE

O

R E

QU

AL

) (D

OM

ES

TIC

A

ND

/O

R

PE

AK

D

EM

AN

D).

PR

ES

SU

RE

R

EL

IE

F V

AL

VE

5

0-0

1 &

D

IS

CH

AR

GE

P

IP

E S

HA

LL

BE

S

IZ

ED

F

OR

T

OT

AL

F

LO

W.

RS

WG

V F

LG

x M

J

FL

G x M

J 9

0d

B

EN

D

FL

G x F

LG

T

EE

RE

SIL

IA

NT

S

EA

T W

ED

GE

G

AT

E V

AL

VE

FL

G x M

J D

.I. S

PO

OL

FL

G x M

J A

DA

PT

OR

. U

SE

R

OM

AC

F

LG

C

OU

PL

IN

G A

DA

PT

OR

FO

R IN

ST

AL

LIN

G IN

E

XIS

TIN

G P

IP

E.

MJ x F

LG

R

SW

GV

(Z

ON

E V

AL

VE

C

LO

SE

D P

OS

IT

IO

N)

FL

G T

O U

PS

TR

EA

M T

EE

O

NL

Y.

RE

SIL

IA

NT

S

EA

T W

ED

GE

G

AT

E V

AL

VE

VA

UL

T (U

TIL

IT

Y V

AU

LT

O

R E

QU

AL

)

AL

UM

IN

UM

H

YD

RA

LIC

L

IF

T A

SS

IS

T L

OC

KIN

G H

AT

CH

LW

H

DD

-1

L

EA

K P

RO

OF

G

AS

KE

TE

D. (M

IN

3

6" x 6

0")

2 3 4 5 6 7 8 9

10

11

12

13

14

6. L

AR

GE

V

AL

VE

T

O H

AN

DL

E F

IR

E F

LO

W, S

MA

LL

V

AL

VE

T

O H

AN

DL

E

10

FL

G x M

J V

AL

VE

15

15

15

7. V

AU

LT

S

HO

P D

RA

WIN

G R

EQ

UIR

ED

P

RIO

R T

O O

RD

ER

IN

G M

AT

ER

IA

LS

.

8. IN

ST

AL

L 4

" L

IQ

UID

F

IL

LE

D A

SH

CR

OF

T G

AU

GE

S. G

AU

GE

S S

HA

LL

B

E

SIZ

ED

F

OR

O

PE

RA

TIN

G IN

M

ID

-R

AN

GE

O

F G

AU

GE

. G

AU

GE

S

IN

ST

AL

LE

D O

N B

OT

H H

IG

H S

ID

E &

L

OW

S

ID

E O

F L

OW

F

LO

W &

H

IG

H

FL

OW

P

RV

's.

DO

ME

ST

IC

M

AX

D

A.

4" L

IQ

UID

F

IL

LE

D G

AU

GE

S1

6

16

16

16

16

4" - 12" TYPICAL PRESSURE REGULATION STATION

W - 140JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 12: WATER SUPPLY - mylongview.com

CLASS 4000

THRUST BLOCK

FLANGE JOINT

6" SCHEDULE 3034 PVC PIPE

MODEL 910 VALVE BOX & TOP

(SEE STD. DETAIL W-250)

AUXILIARY GATE VALVE

(MECH. JOINT BY FLANGE JOINT)

MJ & RJ

NO VERTICAL OR HORIZONTAL

BENDS WITHOUT CITY APPROVAL

6" DIA. PIPE

HYDRANT PAD

CLASS 4000 CONCRETE

3' x 3' x 6"

NO GRADE EXTENSIONS

ALLOWED IN THIS AREA

CLASS 4000,

THRUST BLOCK

UNDISTURBED GROUND

12" x 12" x 4"

CONCRETE BLOCK

1

2

CU. YD. CLEAN,

ROUND DRAIN ROCK

MJ & RJ

2

3

4

" GRADE 304-SS

ALL THREAD RODS

(SEE NOTE #7)

1. TO ASSURE UNIFORMITY OF PARTS STOCKING,

HYDRANTS SHALL BE AVK SERIES 27 MODERN STYLE, 5

1

4

" MUELLAR CENTURION, WATEROUS PACER 90 OR

KENNEDY K81D GUARDIAN, WITH 16" TOP SECTION.

2. ALL HYDRANTS SHALL HAVE NATIONAL STANDARD

THREAD OUTLETS, TWO 2

1

2

" PORTS AND SHALL BE

EQUIPPED WITH ONE 4

1

2

" PUMPER CONNECTION WHICH

FACES THE MAIN ROADWAY.

3. ALL HYDRANTS SHALL STAND PLUMB WITH THE LOWEST

OUTLET OF THE HYDRANT NO LESS THAN 18" ABOVE

FINISHED GRADE.

4. 10 MIL. PLASTIC SHEETING SHALL BE USED AS A BOND

BREAKER BETWEEN CONCRETE BLOCKING AND PIPE

FITTING AS WELL AS BETWEEN HYDRANT BARREL AND

HYDRANT PAD.

5. VALVE TO BE SET MINIMUM 3' FROM FACE OF HYDRANT.

INCLUDE VALVE BOX IN HYDRANT PAD WHEN BOTH FALL

BETWEEN WALK AND CURB.

6. ALL HYDRANTS SHALL BE BAGGED UNTIL SYSTEM IS

APPROVED.

7. TO BE RODDED OR RESTAINED JOINTS INCLUDING

THRUST BLOCKS.

8. HYDRANT MUST COMPLY TO ADA REQUIREMENTS.

9. CHAINS TO REMAIN ATTACHED TO HYDRANT.

FACE OF CURB

2" MIN.

8" MAX.

NOTES:

10. THRUST BLOCKS SHALL BE CURED TO A MINIMUM OF 3500

PSI PRIOR TO TESTING, FLUSHING OR PLACING HYDRANT

IN SERVICE.

11. 6" MIN CLEARANCE FROM SIDEWALK TO ANY PORTION OF

FIRE HYDRANT.

12. 3' MINIMUM OBSTRUCTION CLEARANCE ANY PORTION OF

HYDRANT.

13. UTILITY MARKER TAPE SHALL BE INSTALLED 1.0' TO 1-1/2'

ABOVE SERVICE LINE.

14. TRACER WIRE SHALL BE INSTALLED ALONG 6" PIPE &

SHALL BE CONNECTED TO MAIN LINE TRACER WIRE WITH

3M DIRECT BURY SPLICE KIT.

15. INSTALL SNAKEPIT TRACING WIRE ACCESS BOXES OR

APPROVED EQUAL PER DETAIL W-280.

16. HYDRANTS SHALL BE STANDARD YELLOW IN COLOR.

17. HYDRANTS SHALL NOT BE LOCATED ANY CLOSER THAN 7'

FROM DRIVEWAY OR ALLEY APPROACH, UNLESS APPROVED

BY CITY ENGINEER.

2' MIN'

P

L

TRACE

WIRE

SEE NOTE 15

HYDRANTS

W - 150JAN 2017

C.B.

AutoCAD SHX Text
18" MIN.
AutoCAD SHX Text
3' MIN.
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 13: WATER SUPPLY - mylongview.com

ST

RA

DD

LE

B

LO

CK

ST

D. P

LA

N

W

- 2

10

P

IP

E D

.I. P

IP

ED

.I. P

IP

E

2' M

IN

.2

' M

IN

.

TR

AC

E W

IR

E

ST

D. P

LA

N

W - 2

80

6" 3

03

4

PV

C P

IP

E

ST

AN

DA

RD

V

AL

VE

B

OX

D

ES

IG

N

SE

T A

T F

IN

IS

H G

RA

DE

W

IT

H

CO

NC

RE

TE

C

OL

LA

R (S

EE

W

- 2

50

)

SC

H 8

0 M

.I.P

. P

LU

G

W/ 2

" O

PE

RA

TIN

G N

UT

SC

H 8

0 M

.I.P

. x F

.I.P

.

CL

AS

S 4

00

0

TH

RU

ST

B

LO

CK

90

° B

EN

D

MJ X

F

LG

GA

TE

V

AL

VE

MJ X

M

J W

IT

H

GR

IP

R

IN

GS

CL

AS

S 4

00

0

TH

RU

ST

B

LO

CK

MJ X

M

J

RE

DU

CE

R W

IT

H

RE

ST

RA

IN

IN

G G

LA

ND

S

UN

DIS

TU

RB

ED

EA

RT

H

BL

OW

O

FF

P

IP

E S

IZ

E S

HA

LL

O

BT

AIN

6

FP

S F

LO

W

FL

G x IP

A

DA

PT

ER

4" M

IN

BLOWOFF ASSEMBLY

W - 170JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 14: WATER SUPPLY - mylongview.com

BRASS "RISER", 180° RETURN BEND

OR TWO 90° BENDS WITH1/8"WIRE

SST 24" MIN. ABOVE GRADE

2" GALVANIZED FENCE POST W/ CAP

SECURE TO RISER W/ SS HOSE CLAMPS

2" MIN. "L" BRACKETS

(3) - EVENLY SPACED

(STAINLESS STEEL

BRACKETS AND BOLTS)

1" MIN - 2" MAX GAP

AIR RELEASE VALVE

APCO MODEL 200A

BRASS PIPE

BRASS 90° ELBOW

4" x 8" CONCRETE PAD

BALL VALVE COMP X IP

1

4

TURN - VALVE STACK

TO BE 6" ABOVE ROCK GRADE

(FOR 2" USE RSWGV INSIDE)

8" OF 5/8" DRAIN ROCK

SADDLE - ROMAC SST 202S MINIMUM

CRUSHED

SURFACING TOP

COURSE

BALL VALVE TYPE CORP STOP

RATED TO WITHSTAND HYDROSTATIC

PRESSURE TEST - TYPE "K"

COPPER TAP TO BE AT TOP

OF PIPE.

WATER MAIN

6"

BRASS

UNION

6" PVC

VALVE STACK

NO LID

NOTE:

NOT TO BE LOCATED IN TRAFFIC

AREAS OR PARKING LOTS.

CONCRETE COLLAR AROUND

STRUCTURE SEE PLAN SS-090

INSTALL

1/2" x 2"

REDUCER

ARMORCAST 36" x 36"

IN GROUND VAULT #A6001441

OR APPROVED EQUAL

BRASS PIPE

ARMORCAST AIR VACUUM

VALVE ENCLOSURE

OR APPROVED EQUAL

1 " AND 2 " AIR RELEASE VALVE

W - 190AUG 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 15: WATER SUPPLY - mylongview.com

VA

RIE

S

VA

RIE

SV

AR

IE

SV

AR

IE

S

OR

IG

IN

AL

G

RO

UN

D

3'- 0

" M

IN

.

C

OV

ER

45

° B

EN

D

45

° B

EN

D

VA

LV

E

D.I.

PIP

E

#6

B

AR

S

MIN

. E

MB

ED

. 3

0"

AL

L JO

IN

TS

T

O B

E R

ES

TR

AIN

ED

C

LA

SS

4

00

0 C

ON

CR

ET

E

SIZ

E V

AR

IE

S

S

E

E

T

Y

P

I

C

A

L

D

E

T

A

I

L

D.I. P

IP

E

2" M

IN

.

MJ A

LL

OW

ED

W

IT

H M

EG

AL

UG

&

R

OD

DIN

G

SE

E S

TD

. D

ET

. W

-2

20

F

OR

T

HR

US

T L

OA

D T

AB

LE

SIV

E O

F G

RA

VIT

Y B

LO

CK

S

HA

LL

B

E:

BL

OC

K S

IZ

E (F

T ) =

3

TH

RU

ST

F

OR

CE

(L

B) P

ER

S

TD

. D

ET

. W

-2

20

DE

NS

IT

Y O

F B

LO

CK

M

AT

ER

IA

L (L

B/F

T )

3

AN

A

CC

EP

TA

BL

E A

LT

ER

NA

TIV

E T

O T

HIS

S

TA

ND

AR

D P

LA

N IS

W

SD

OT

S

P B

-2

2

(C

ON

CR

ET

E B

LO

CK

IN

G F

OR

C

ON

VE

X V

ER

TIC

AL

B

EN

DS

)

ST

RA

DD

LE

B

LO

CK

ST

AN

DA

RD

P

LA

N

# W

-2

10

BLOCKING FOR CONVEX VERTICAL BEND

W - 200JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 16: WATER SUPPLY - mylongview.com

2 X

P

IP

E D

IA

.

2 X

P

IP

E D

IA

.

1 1/2 X

P

IP

E D

IA

.

12" M

IN

.

12" M

IN

.

WA

TE

R

M

AIN

54

1

6

TR

EN

CH

B

AN

KS

3

2

4000 P

SI C

ON

CR

ET

E

ST

RA

DD

LE

B

LO

CK

PLA

N V

IE

W

GR

AD

E

WA

TE

R

M

AIN

4 X

P

IP

E D

IA

.

5

1

3

SID

E V

IE

W

1 1/2 X

P

IP

E D

IA

.

21 3 4 5 6

ME

CH

AN

IC

AL JO

IN

T F

IT

TIN

G, T

EE

, B

EN

D, V

ALV

E, E

TC

.

4 E

AC

H - # 4 B

AR

S

4 E

AC

H - # 4 B

AR

S

90° E

YE

B

OLT

- 3/4" U

NC

R

OLLE

D T

HR

EA

D

DU

CT

ILE

LU

GS

N

OT

A

CC

EP

TE

D

3/4" S

TA

IN

LE

SS

S

TE

EL A

LL T

HR

EA

D T

IE

R

OD

, N

.C

. T

HR

EA

D,

BE

ND

T

IE

R

OD

W

/ M

IN

6" A

FT

ER

90°

OP

TIO

N: U

SE

4" S

QU

AR

E P

LA

TE

W

/ N

UT

4" - 12"

NO

TE

S:

STRADDLE BLOCK DETAIL

1.

CO

NC

RE

TE

T

HR

US

T B

LO

CK

IN

G T

O B

E P

OU

RE

D A

GA

IN

ST

EA

RT

H &

C

OM

PA

CT

ED

C

ST

C O

N B

OT

TO

M.

2.

PLA

ST

IC

B

AR

RIE

R S

HA

LL B

E W

RA

PP

ED

A

RO

UN

D A

LL

FIT

TIN

GS

A

ND

P

IP

E T

O P

RO

VID

E A

B

ON

D B

RE

AK

ER

.

3.

AN

CH

OR

R

EB

AR

S

HA

LL B

E

5

8

" M

IN

IM

UM

D

IA

ME

TE

R.

4.

AN

CH

OR

R

EB

AR

S

HA

LL B

E T

IG

HT

LY

F

IT

TE

D A

GA

IN

ST

B

EN

D

OR

V

ALV

E.

5.

CIT

Y E

NG

IN

EE

R C

AN

W

AIV

E B

LO

CK

IN

G R

EQ

UIR

EM

EN

TS

IF

SU

FF

IC

IE

NT

R

ES

TR

AIN

T IS

P

RO

VID

ED

.

6.

ALL T

HR

US

T B

LO

CK

S T

O B

E C

LA

SS

4000 C

ON

CR

ET

E (3-D

AY

MIX

).

7. N

UM

BE

R O

F A

LL T

HR

EA

D R

OD

F

OR

R

ES

TR

AIN

T A

S N

OT

ED

.

8. R

ES

TR

AIN

T F

OR

S

IZ

ES

A

BO

VE

12" S

HA

LL B

E E

NG

IN

EE

RE

D.

9. M

EG

ALU

G T

O B

E U

SE

D O

N D

.I. O

NLY

. F

OR

C

.I. S

UB

MIT

A

LT

ER

NA

TIV

E M

ET

HO

D.

10. P

LA

CE

6" O

F C

ST

C C

OM

PA

CT

ED

T

O 95%

U

ND

ER

S

TR

AD

DLE

B

LO

CK

P

RIO

R T

O P

LA

CE

ME

NT

.

ST

AIN

LE

SS

S

TE

EL C

OU

PLE

RS

A

LLO

WE

D

7

7M

EG

ALU

G 1100S

DB

P

IP

E R

ES

TR

AIN

T

4 R

OD

S

10

10

STRADDLE BLOCK DETAIL

W - 210JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 17: WATER SUPPLY - mylongview.com

NOTES:

1. THRUST BLOCK SHALL BE ADEQUATE TO WITHSTAND FULL TEST PRESSURE.

2. POUR THRUST BLOCK AGAINST UNDISTURBED EARTH.

3. FITTINGS SHALL BE ISOLATED FROM CONCRETE THRUST BLOCK WITH 10 MIL

PLASTIC SHEETING.

4. ALL THRUST BLOCKS TO BE CLASS 4000 CONCRETE.

5. THRUST BLOCKS SHALL BE ALLOWED TO CURE 14 DAYS BEFORE PIPELINE

PRESSURE TEST UNLESS 3-DAY MIX IS USED.

6. CONCRETE BLOCK AREA MUST BE ADJUSTED FOR PIPE SIZE, FITTING PRESSURES

AND SOIL CONDITIONS AS NEEDED.

7. NO CONCRETE HAND MIXING ALLOWED, UNLESS APPROVED BY THE ENGINEER.

HAND MIXING BATCH SHALL NOT EXCEED

1

2

CY AND SHALL BE PER WSDOT STD.

SPECIFICATION SECTION 6-02.3(4)B.

TABLE 1: THRUST LOADS (T)

RESULTANT THRUST AT FITTINGS AT 200 PSI WATER PRESSURE

PIPE

DIAMETER

90

0

BEND 45

0

BEND 22-1/2 BEND 11-1/2 BEND

DEAD END

OR TEE

3"3,484 1,886

962 4822,464

4" 5,118 2,770 1,412 710 3,620

6" 10,576 5,724 2,918 1,466 7,478

8" 18,194 9,846 5,020 2,522 12,866

10" 27,370 14,812 7,552 3,794 19,354

12" 38,706 20,948 10,680 5,366 27,370

14" 52,002 28,144 14,348 7,208 36,770

16" 67,256 36,398 18,556 9,322 47,558

18" 84,470 45,716 23,306 11,710 59,730

20" 103,644 56,092 28,596 14,366 73,328

24" 147,868 80,026 40,796 20,498 104,558

30" 227,476 123,108 62,760 31,532 160,850

36" 325,862 176,354 89,904 45,170 230,418

42" 439,900 238,072 121,368 60,978 311,056

48" 573,274 310,254 158,166 79,466 405,366

54" 735,998 398,320 203,062 102,022 520,428

60" 843,212 456,344 232,642 116,884 596,242

64" 958,008 518,470 264,314 132,796 677,414

TABLE 2: SOIL BEARING CAPACITY (B)

SOIL BEARING LOAD TO BE DETERMINED PER SOILS REPORT OR

INFORMATION BELOW

SOIL TYPE

SOIL BEARING

CAPACITY (B) IN PSF

MUCK, PEAT, ETC. 0

SOFT CLAY 1,000

SAND 2,000

SAND AND GRAVEL 3,000

SAND AND GRAVEL CEMENTED WITH CLAY 4,000

HARD SHALE 10,000

EXAMPLE:

DESIGN TEST PRESSURE = 225 PSI

PIPE SIZE = 12"

FITTING TYPE = TEE

SOIL TYPE = SAND

FROM TABLE A, T = 27,370

FROM TABLE B, B = 2,000

A = (

27,370

2,000

) (

225

200

) = 15.40 SF (4' BY 4')

1. TO DETERMINE THE BEARING AREA OF THE THRUST BLOCK IN

SQUARE FEET (S.F.) USE THE FOLLOWING PROCEDURE:

A. DETERMINE THRUST (T) FOR TYPE AND SIZE OF FITTING

FROM TABLE 1

B. DETERMINE TEST DESIGN PRESSURE FROM STANDARD

SPECIFICATION OR SPECIAL PROVISIONS

C. DETERMINE SOIL BEARING CAPACITY (B) OF SOIL FROM

TABLE 2

D. DETERMINE REQUIRED BEARING AREA (A) IN SQ. FT. AS

FOLLOWS

THRUST BLOCK = A = (

T

B

) (

DESIGN TEST PRESSURE

TABLE PRESSURE

)

BEARING AREA

A = (X') (Y')

SIDE VIEW

TEE

TOP VIEW

BEARING

SURFACE X'

BEARING

SURFACE Y'

18-24"

18-24"

THRUST BLOCK

W - 220

DEC 2020

K.H.

AutoCAD SHX Text
PUBLIC WORKS DIRECTOR APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 18: WATER SUPPLY - mylongview.com

1. ALL WELDS SHALL BE

1

4

" FILLET WELDS FOR FULL LENGTH OF CONTACT

BETWEEN COMPONENTS.

2. DIAMETER OF CENTERLING PLATE ASSEMBLY SHALL BE

1

4

" LESS THAT THE

INSIDE DIAMETER OF THE VALVE BOX RISER SECTION.

3. SECURE TO OPERATING NUT WITH TWO

3

8

" SET SCREWS (STAINLESS STEEL).

NOTES:

2

1

2

" x 2

1

2

" x

3

8

" FLAT BAR

3" x 3" x

3

8

" x 2

1

2

" SQUARE TUBE

SOCKET ASSEMBLY:

FILLET WELDS

(SEE NOTE 1)

NUT: 2" SQUARE SOLID

MILD STEEL BAR STOCK

ROCK GUARD / CENTERING ASSEMBLY:

10 GAUGE OR

1

8

" STEEL PLATE

(SEE NOTE 2)

SHAFT: 1" MILD

STEEL BAR STOCK

OPERATING NUT HEIGHT

12" MIN. - 30" MAX.

BELOW FINISHED GRADE

VALVE OPERATING EXTENSION

W - 240

DEC. 2020

K.H.

AutoCAD SHX Text
PW DIRECTOR APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 19: WATER SUPPLY - mylongview.com

Wat

er

1. THE VALVE BOX ASSEMBLY SHALL CONSIST OF A

MAXIMUM OF 2 COMPONENTS; THE ADJUSTABLE

VALVE BOX (FRAME AND COVER), AND THE BASE

SECTION.

2. THE ADJUSTABLE VALVE BOX SHALL BE CAST IRON.

THE INTERMEDIATE RISER SECTION D3034 PVC.

3. ADJUSTABLE VALVE BOXES SHALL BE SUPPLIED

WITHOUT BOTTOM FLANGES.

4. THE ADJUSTABLE VALVE BOX, INTERMEDIATE RISER

SECTION, AND BASE SECTION SHALL BE INSTALLED

PLUMB AND CENTERED OVER THE OPERATING NUT

ON THE VALVE.

5. VALVE BOX TYPE SHALL BE A 910.

6. PLASTIC VALVE STACK SHALL EXTEND FROM TOP OF

VALVE BONNET TO MIDDLE OF CAST IRON VALVE

BOX.

7. A CONCRETE COLLAR SHALL BE INSTALLED AROUND

THE CAST IRON VALVE BOX.

8. COLLAR SHALL BE 24" x 24"L x 8"D.

9. COLLAR SHALL BE EDGED WITH

3

8

" FELT IF INSTALLED

IN A CONCRETE AREA.

10. LOCATE WIRE PER STANDARD PLAN W-280.

NOTES:

1. TOLERANCE =

1

8

"

2. EXTENSIONS SHALL BE 3034 PVC PIPE

(THICK WALL)

3. VALVE BOXES SHALL MEET SECTION 9-30.3

OF THE STD. SPECS.

4. MATERIAL: CAST IRON ASTM A-48, CL 30

APPROX. WEIGHT: VALVE BOX - 42 LBS.

COVER -14 LBS.

5. OLYMPIC FOUNDARY PART NO. VB910.

NOTES:

VALVE BOX

2

4

"

x

2

4

"

M

I

N

.

TOP VIEW

8"

12"

3

4

"

18"

7"

7

1

2

"

8" M

IN

.

DE

PT

H

CONCRETE

COLLAR

8"

12"

3

4

"

18"

7"

7

1

2

"

SIDE VIEW SIDE VIEW

7

3

4

"

5

1

8

"

9

16

"

HOOK PIN

TOP VIEW

LID:

LIFT POCKET

1" WIDE x 1" DEEP

12" MIN.

30" MAX

BASE SECTION

6" 3034

LOCATE WIRE

BACKFILL

VALVE BOX SHALL NOT

REST ON OPERATING

ASSEMBLY

2" VALVE OPERATING

NUT

CENTERING DEVICE

ON OPERATOR EXTENSION

ONE INTERMEDIATE RISER

SECTION D3034 PVC

(SEE NOTE 2)

C.I. ADJUSTABLE

VALVE BOX

FINAL SURFACE

GRADE

CAST IRON PICK-TYPE

COVER WITH "WATER" OR

"W" EMBOSSED ON TOP

LOCATE WIRE COIL TO

ALLOW 3' REACH ABOVE

FINISH GRADE

DIR

EC

TIO

N

OF

T

RA

VE

L

(4)

(SEE STD. DET. W-240)

11. STAMP COLLARS WITH CITY PROVIDED TOOLS AND

PER INSTRUCTIONS OF INSPECTOR.

VALVE BOX DETAIL

W - 250JAN 2017

C.B.

AutoCAD SHX Text
O
AutoCAD SHX Text
F
AutoCAD SHX Text
C
AutoCAD SHX Text
O
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 20: WATER SUPPLY - mylongview.com

FLANGE x MJ RSWGV

WITH GRIP RING OR APPROVED EQUAL

UNDISTURBED EARTH

THRUST BLOCK

UNDISTURBED

EARTH

SS TAPPING

SLEEVE

STANDARD CITY VALVE BOX

(SEE STANDARD DETAIL W-250)

SEE NOTE 3

1. TAPPING SLEEVE SHALL BE 304 STAINLESS STEEL WITH STAINLESS

STEEL FLANGE. JCM OR EQUIVALENT.

2. ALL BOLTS SHALL BE 304 STAINLESS STEEL OR APPROVED EQUAL.

3. TAPPING SLEEVE AND VALVE SHALL BE SUPPORTED BY 6" MIN CSTC

OR AS DETERMINED BY INSPECTOR & COMPACTED TO 95%.

4. TAPPING SLEEVE AND VALVE SHALL BE WRAPPED WITH 10 MIL

PLASTIC.

5. CITY MUST WITNESS AIR TEST AND BE PROVIDED WITH TAPPING

COUPON.

6. TAPPING SLEEVE EDGE SHALL BE A MINIMUM OF 18 INCHES FROM

BELL OR SPIGOT END OF EXISTING PIPE, AND A MINIMUM OF 18

INCHES FROM ANY OTHER TAP OR FITTING.

7. CONTRACTOR SHALL SCHEDULE THE HOT TAP WITH THE CITY

48 HOURS (2 WORKING DAYS) IN ADVANCE.

8. SIZE ON SIZE TAPS ARE NOT PERMITTED.

9. ALL THRUST BLOCKS TO BE CLASS 4000.

NOTES:

CSTC

HOT TAP OF EXISTING WATER MAIN

W - 260JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 21: WATER SUPPLY - mylongview.com

SK

ID D

ET

AIL

1

2

" S

S B

AN

DS

2' x 4" x 4" S

PA

CE

RS

I.D

. C

AR

RIE

R

PIP

E

O.D

. P

IP

E

BA

RR

EL

ST

EE

L C

AS

IN

G

O.D

. P

IP

E B

ELL

RE

DW

OO

D C

ED

AR

O

R

PR

ES

SU

RE

T

RE

AT

ED

FIR

O

R P

LA

ST

IC

S

KID

S

EN

D V

IEW

SK

ID

B

AN

DS

ST

RA

P W

OO

DE

N O

R P

LA

ST

IC

S

KID

S T

O P

IP

E,

3 S

KID

S P

ER

P

IP

E S

EC

TIO

N

CA

RR

IE

R P

IP

E A

S S

PE

CIF

IE

D

EN

D S

EA

L O

NT

O C

AS

IN

G T

O

SU

RR

OU

ND

C

AR

RIE

R P

IP

E (T

YP

.)

ST

EE

L C

AS

IN

G

EN

D V

IE

W

EN

D V

IE

W

ALL R

ES

TR

AIN

ED

JO

IN

TS

CASING DETAIL

W - 270JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 22: WATER SUPPLY - mylongview.com

MAIN

CONCRETE COLLARTOP VIEW

24"

24"

LOCATOR WIRE

CONCRETE COLLAR

24" x 24"

SNAKEPIT TRACING WIRE BOX

#31078 & BLUE IN COLOR

(OR APPROVED EQUAL)

8"

WIRE TO COME UP INSIDE ABS RISER

SECTION TO ATTACH TO TERMINALS

ON BOTTOM OF LID

1. A CONCRETE COLLAR SHALL BE INSTALLED

AROUND THE SNAKEPIT BOX, COLLAR SHALL BE

24"W x 24"L x 8"D. COLLAR SHALL BE EDGED WITH

3

8

" FELT IF INSTALLED IN A CONCRETE AREA.

2. WIRE SHALL BE 12 GAUGE SOFT DRAWN COPPER

WITH INSULATION.

3. INSULATION COLOR SHALL BE BLUE.

4. WIRE SHALL BE ATTACHED TO PIPE EVERY 20',

WIRE SHALL BE CENTERED ON TOP OF PIPE WITH

ONE FOOT OF SLACK FOR EVERY 20' OF PIPE.

5. 500 FEET MAXIMUM SPACING FOR VALVE BOXES.

NOTES:

LOCATOR BOX DETAIL

W - 280JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 23: WATER SUPPLY - mylongview.com

18' MINCENTERED ON WATERLINE

6"MIN

WATER MAIN

I.E.

SEWER MAIN ORSERVICE LATERAL

ROMAC 501 LONG BARREL COUPLING(OR APPROVED EQUAL)TYPICAL

CL 52 D.I.P. (EPOXY COATED)OR C-900 P.V.C. PIPE (C-905 FOR GREATER THAN 12" DIA.)

18' MINCENTERED ON WATERLINE

6"MIN

WATER MAIN

I.E.

SEWER MAIN ORSERVICE LATERAL

SECTION VIEW

SECTION VIEW

OPTION "A"CROSSING

OPTION "B"CROSSING

STANDARD GRAVITY SEWER MATERIAL CENTEREDON WATER MAIN SO THAT JOINTS ARE AS FAR AS

CLASS 3000 CONCRETE ENCASEMENT-MINIMUM6" THICKNESS AROUND THE WATERLINE(CONCRETE WILL ACHIEVE FINAL SET BEFORE BACKFILLING IS ALLOWED)WATER LINE TO BE WRAPPED IN 10 MIL PLASTIC SHEETING

18' MINCENTERED ON WATERLINE

6"MIN

WATER MAIN

I.E.

SEWER MAIN ORSERVICE LATERAL

SECTION VIEW

OPTION "C"CROSSING

STANDARD GRAVITY-SEWER MATERIAL ENCASED IN1/4" THICK CONTINUOUS STEEL*, CL 52 D.I., OR C-900P.V.C. PIPE WITH A DIMENSION RATIO (DR VALUE) OF18 OR LESS, WITH ALL VOIDS PRESSURE GROUTED WITHSAND-CEMENT GROUT OR BENTONITE.COMMERCIALLY AVAILABLE PIPE SKIDS AND END SEALS ARE ACCEPTABLE.

* STEEL PIPE TO HAVE COROSION PROTECTION.

USE THIS STANDARD PLAN WHEN SANITARY SEWER LINE IS BELOW WATER LINE & THERE IS LESS THAN 18"BETWEEN I.E. OF WATER AND CROWN OF SEWER LINE. CROSSING TYPE TO BE SPECIFIED ON CONSTRUCTIONPLAN OR AS DIRECTED BY THE ENGINEER.

POSSIBLE FROM THE WATER LINE

WATER-SEWER X-INGSEWER UNDER WATER-LESS THAN 18" SEPARATION

OR SERVICE

OR SERVICE

OR SERVICE

WATER-SEWER CROSSING

W - 290JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 24: WATER SUPPLY - mylongview.com

SANITARY SEWER PROTECTION PER OPTION "A", "B", OR "C"STD. PLAN NO. W-290 AS REQUIRED ON THE CONSTRUCTIONPLAN OR AS DIRECTED BY THE ENGINEER

WATERMAIN OR

PIPE PROTECTION TO BECENTERED AT PIPE X-ING

18" MIN

2

PROVIDE A MINIMUM OF 18" OF CLEARANCE BETWEEN CROWN OF WATER LINE AND INVERT OF SANITARY SEWER.WATER LINE SHALL RECEIVE ONE OF THE FOLLOWING PROTECTIVE TREATMENTS AS REQUIRED ON THE CONSTRUCTIONPLAN OR AS DIRECTED BY THE ENGINEER:1) A MINIMUM 18 FOOT LENGTH OF CLASS 3000 CEMENT CONCRETE ENCASEMENT FOR A MINIMUM 6" THICKNESS AROUND THE WATER LINE.

2) A 1/4" THICK CONTINUOUS STEEL*, DUCTILE IRON OR C-900 P.V.C. (C-905 FOR GREATER THAN 12" DIA) WITH A DR VALUE OF 18 OR LESS. PIPE SKIDS WILL BE USED AND ALL VOIDS PRESSURE GROUTED WITH SAND-CEMENT GROUT OR BENTONITE.

* STEEL CASING SHALL RECEIVE COROSION PROTECTIONOPTION 2 WATERLINE PROTECTION

SEWER PIPE TO BE CENTERED SOTHAT JOINTS ARE AS FAR AS POSSIBLEFROM WATER LINESERVICE

OPTION 1 WATERLINE PROTECTION

SANITARY SEWER PROTECTION PER OPTION "A", "B", OR "C"STD. PLAN NO. W-290 AS REQUIRED ON THE CONSTRUCTIONPLAN OR AS DIRECTED BY THE ENGINEER

WATERMAIN OR

18" MIN

1

SERVICE

PROVIDE A MINIMUM OF 18" OF CLEARANCE BETWEEN CROWN OF WATER LINE AND INVERT OF SANITARY SEWER.WATER LINE SHALL RECEIVE ONE OF THE FOLLOWING PROTECTIVE TREATMENTS AS REQUIRED ON THE CONSTRUCTIONPLAN OR AS DIRECTED BY THE ENGINEER:

PIPE PROTECTION TO BECENTERED AT PIPE X-INGSEWER PIPE TO BE CENTERED SOTHAT JOINTS ARE AS FAR AS POSSIBLEFROM WATER LINE

WATER LINE TO BE WRAPPED IN 10 MIL PLASTIC SHEETING

WATER-SEWER CROSSING

W - 295JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 25: WATER SUPPLY - mylongview.com

NORMAL PARALLEL CONDITION: A MINIMUM HORIZONTAL SEPARATION OF 10 FEET BETWEEN ANY SANITARY SEWER AND WATER LINES,AND A MINIMUM VERTICAL SEPARATION OF 18" BETWEEN THE BOTTOM OF THE WATER LINE AND THECROWN OF THE SEWER, SHALL BE MAINTAINED. THE DISTANCE SHALL BE MEASURED EDGE TO EDGE.LINES MUST BE LAID IN SEPARATE TRENCHES.

SEWERLINE

18" MIN

10' MIN

UNUSUAL PARALLEL CONDITIONS: WHEN SPECIAL CONDITIONS PREVENT THE SEPARATIONS DESCRIBED ABOVE, A SEWER MAY BEINSTALLED CLOSER THAN 10 FEET HORIZONTALLY OR 18" VERTICALLY TO A WATER LINE, PROVIDED:

1) LESS THAN 18" OF VERTICAL SEPARATION REQUIRES CL 52 D.I., OR C-900 P.V.C. FOR SEWER PIPE MATERIAL (C-905 FOR GREATER THAN 12" DIA). THE ENGINEER MAY APPROVE LESS THAN 10 FEET OF HORIZONTAL SEPARATION PROVIDED SEPARATE TRENCHES CAN BE MAINTAINED.2) IF SEWER AND WATER LINES MUST BE LOCATED IN THE SAME TRENCH, BOTH SEWER LINES AND WATER LINES SHALL INCLUDE A CASING PIPE OF PRESSURE RATED PIPE MATERIAL DESIGNED TO WITHSTAND A MINIMUM STATIC PRESSURE OF 150 P.S.I. COMMERCIAL PIPE SKIDS AND AN APPROVED END CLOSURE IS REQUIRED AS NEEDED. A MINIMUM OF 5 FEET HORIZONTAL AND 18" OF VERTICAL CLEARANCE IS REQUIRED. (SEE ILLUSTRATION BELOW)

SEWERLINE

5' MIN

18" MIN

UNDISTURBED EARTH

WATER-SEWER SEPARATIONREQUIREMENTS FOR PARALLELCONDITIONS

WATERMAIN ORSERVICE

WATERMAIN ORSERVICE

WATER-SEWER IN PARALLEL

W - 300JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 26: WATER SUPPLY - mylongview.com

6"

3"

6"

3"

6" MIN.

18" MAX.

RESILIENT SEATED

SHUTOFF VALVES

(2 REQ'D)

3"

6" MIN.

TEST COCKS

(4 REQ'D)

3"

UNIONS

(2 REQ'D)

CSTC

12" MIN.

BROOKS 66T BOX

WITH CI COVER

MIN

1. APPROVED DOUBLE CHECK VALVE ASSEMBLY TO LAY HORIZONTAL WITH GROUND.

2. DESIGNED FOR BACK SIPHONAGE AND BACK PRESSURE.

3. TEST COCKS TO EITHER FACE OUTWARDS OR UPWARDS FROM ASSEMBLY.

4. THOUGHOUGHLY FLUSH LINES PRIOR TO INSTALLATION OF BACKFLOW PREVENTER.

5. THE DCVA MAY BE INSTALLED ABOVE OR BELOW THE GROUND PROVIDED ALL CLEARANCES ARE MET.

6. DO NOT INSTALL IN AN AREA SUBJECT TO FLOODING.

7. MUST BE PROTECTED FROM FREEZING CONDITIONS.

8. THE BACKFLOW ASSEMBLY SHALL BE A STATE APPROVED MODEL.

NOTES:

P

L

9. FACTORY HEATERS IN HOT BOXES ARE REQUIRED.

10. FINAL GRADE ADJUSTMENT SHALL BE PERFORMED BY MODIFYING & STACKING BOXES.

11. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

TRACER WIRE

(SEE NOTE 11)

3' COIL

DOUBLE CHECK VALVE ASSEMBLY - 2" AND SMALLER

W - 310MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 27: WATER SUPPLY - mylongview.com

ELEVATION

PLAN

1. CONTRACTOR TO PROVIDE SITE SPECIFIC SHOP DRAWING FOR CITY ENGINEER APPROVAL PRIOR TO ANY CONSTRUCTION OF THIS ITEM.

2. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW PREVENTION ASSEMBLIES.

3. HATCH DRAINS TO BE PLUMBED TO DAYLIGHT OR STORM DRAIN AS DIRECTED BY THE CITY INSPECTOR.

4. KNOCKOUTS NOT ALLOWED IN VAULT, CORE SAW ONLY.

5. LINK SEALS TO BE USED FOR ALL VAULT PENETRATIONS.

6. PIPE STANDS TO BE STANDON S76 OR EQUIVALENT FLANGE STYLE STANDS, EITHER GALVANIZED OR MADE OF STAINLESS STEEL.

7. VAULT SHALL BE EQUIPPED WITH A LEAK PROOF, GASKETED, DOUBLE RAISE, ALUMINUM, AASHTO H20 RATED, HYDRAULIC ASSIST, LOCKING

HATCH, MIN. 36" x 60", LOCKING OPEN 90°.

8. VAULT SHALL BE PRECAST CONCRETE, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE DETAIL.

9. VAULT SHALL GAVITY DRAIN TO DAYLIGHT OR A STORM DRAIN. IF THIS IS NOT POSSIBLE, A

1

4

HP MINIMUM SUMP PUMP SHALL BE INSTALLED

IN THE SUMP PIT OF THE VAULT AND SHALL DISCHARGE TO DAYLIGHT OR A STORM DRAIN. SAID PUMP SHALL AUTOMATICALLY PROTECT THE

VAULT FROM FLOODING AT ALL TIMES.

10. ALL TESTING, FLUSHING, & CHLORINATION SHALL BE PERFORMED PRIOR TO INSTALLATION OF THE BACKFLOW DEVICE.

11. TAMPER SWITCH REQUIRED WHEN SPECIFIED BY FIRE MARSHAL.

12. WATER METER SHALL INCLUDE A TOUCH READ PIT MODULE PLACED IN BROOKS 37 T BOX ON STREET SIDE.

13. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

NOTES:

SPOOL FLG x PE

PIPE STANDS

(TYP.)

12" - 18"

DRAIN TO DAYLIGHT

-- OR --

PROVIDE APPROVED SUMP

PUMP

SLOPE TO DRAIN

PER UPC

RODENT SCREEN

FLOW

INLET CHECK VALVE

-REQ'D ONLY IF SUMP

PUMP INSTALLED

ISOLATION BALL VALVE

-REQ'D ONLY IF SUMP

PUMP INSTALLED

DRAIN TO

DAYLIGHT OR

STORM DRAIN

3" - 6"

7"

24"

MIN.

DOOR SEAM

LADDER TO MEET

OSHA REQUIREMENTS

RETAINER

GLAND

THRUST

BLOCK

CITY PRIVATE

P

L

6" MIN. 6" MIN.

12" MIN.

FLOW

3" MIN. CLEARANCE ABOVE

FULLY OPENED VALVE

SHALL MEET

CITY STANDARDS

SHALL MEET

PLUMBING CODE

FINISHED GRADE

TRACER WIRE

(SEE NOTE 13)

3' COIL

DOUBLE CHECK ASSEMBLY, LARGE, BELOW GROUND

W - 320MARCH 2018

C.B.

AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 28: WATER SUPPLY - mylongview.com

SHALL MEET

CITY STANDARDS

SHALL MEET

PLUMBING CODECITY PRIVATE

P

L

3" MIN. CLEARANCE ABOVE

FULLY OPENED VALVE

90° BEND FLG

CASE IN PLACE PIPE

FLOOR SLEEVE

6" REINFORCED

CONCRETE SLAB

FLOW

90° BEND MJ

WITH MEGA-LUG

RETAINER GLANDS

12" - 18"

PIPE STANDS

(TYP.)

SEAL ANNULAR SPACE

W / SILICONE CAULK

24"

MIN.

6" MIN. 6" MIN.

FLOW

12" MIN.

1. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW

PREVENTION ASSEMBLIES.

2. ASSEMBLY SHALL BE INSTALLED ABOVE GROUND IN A HEATED AND / OR INSULATED ENCLOSURE CAPABLE OF

PROVIDING YEAR-ROUND FREEZE PROTECTION, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE

DETAIL.

3. PIPE STANDS TO BE STANDON S76 OR EQUIVALENT FLANGE STYLE, EITHER GALVANIZED OR MADE OF STAINLESS

STEEL.

4. VERTICAL UPRIGHTS SHALL BE FLANGED SPOOLS OR BE RESTRAINED JOINT WITH STAINLESS STEEL RODS.

5. SLAB SHALL EXTEND 12" LARGER THAN ENCLOSURE FOOTPRINT, ALL THE WAY AROUND.

NOTES:

3" - 6"

FINISHED

GRADE

USE #4 BAR

12" O.C.

CLASS 4000 CONCRETE THRUST BLOCKS

OR APPROVED EQUAL

6. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

3' COIL

TRACER WIRE

(SEE NOTE 6)

DOUBLE CHECK VALVE ASSEMBLY, LARGE, ABOVE GROUND

W - 330MARCH 2018

C.B.

AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 29: WATER SUPPLY - mylongview.com

1. R

EF

ER

T

O C

IT

Y S

TA

ND

AR

D D

ET

AIL W

-430 F

OR

IN

ST

ALLA

TIO

N R

EQ

UIR

EM

EN

TS

T

HA

T A

PP

LY

T

O A

LL B

AC

KF

LO

W P

RE

VE

NT

IO

N A

SS

EM

BLIE

S

2. A

SS

EM

BLY

S

HA

LL B

E IN

ST

ALLE

D A

BO

VE

G

RO

UN

D IN

A

H

EA

TE

D A

ND

/O

R IN

SU

LA

TE

D E

NC

LO

SU

RE

C

AP

AB

LE

O

F P

RO

VID

IN

G Y

EA

R-R

OU

ND

F

RE

EZ

E

P

RO

TE

CT

IO

N, S

IZ

ED

T

O M

EE

T T

HE

C

LE

AR

AN

CE

R

EQ

UIR

EM

EN

TS

S

HO

WN

IN

T

HE

D

ET

AIL

3. V

ER

TIC

AL U

PR

IG

HT

S S

HA

LL B

E F

LA

NG

ED

S

PO

OLS

O

R B

E R

ES

TR

AIN

ED

JO

IN

T W

TH

S

TA

IN

LE

SS

S

TE

EL R

OD

S

4. S

LA

B S

HA

LL E

XT

EN

D 12" LA

RG

ER

T

HA

N E

NC

LO

SU

RE

F

OO

TP

RIN

T, A

LL T

HE

W

AY

A

RO

UN

D

NO

TE

S:

CIT

YP

RIV

AT

EP

L

SH

ALL M

EE

T

CIT

Y S

TA

ND

AR

DS

SH

ALL M

EE

T

PLU

MB

IN

G C

OD

E

6" M

IN

.

6" M

IN

.

6" M

IN

.

12" - 18"

3" - 6"

FIN

IS

HE

D

GR

AD

E

FLO

W

6" R

EIN

FO

RC

ED

CO

NC

RE

TE

S

LA

B

CA

ST

IN

P

LA

CE

PIP

E F

LO

OR

S

LE

EV

E

12" M

IN

.

24" M

IN

.

3" M

IN

. C

LE

AR

AN

CE

WH

EN

V

ALV

E

FU

LLY

O

PE

NE

D

SE

AL A

NN

ULA

R S

PA

CE

W/ S

ILIC

ON

E C

AU

LK

MA

NU

FA

CT

UR

ER

'S

SE

TT

ER

R

EQ

UIR

ED

RE

ST

RA

IN

ED

JO

IN

TS

,

ME

GA

LU

G O

R E

QU

IV

ALE

NT

SID

E E

LEV

AT

ION

E

ND

ELE

VA

TIO

N

US

E #4 B

AR

12" O

.C

.

TR

AC

ER

W

IR

E

(S

EE

N

OT

E 5)

5. LO

CA

TE

W

IR

E IN

ST

ALLE

D T

O A

SS

EM

BLY

A

ND

C

OIL T

O A

LLO

W 3' R

EA

CH

A

BO

VE

F

IN

IS

H G

RO

UN

D

3' C

OIL

DOUBLE CHECK VALVE ASSEMBLY, N-PATTERN

W - 340MARCH 2018

C.B.

AutoCAD SHX Text
E
AutoCAD SHX Text
M
AutoCAD SHX Text
USA
AutoCAD SHX Text
I
AutoCAD SHX Text
E
AutoCAD SHX Text
D
AutoCAD SHX Text
A
AutoCAD SHX Text
H
AutoCAD SHX Text
T
AutoCAD SHX Text
N
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 30: WATER SUPPLY - mylongview.com

PRIVATEP

L

CITY

CITY APPROVED

BACKFLOW DEVICE

12" MIN.

CHECK VALVE

FIRE DEPARTMENT

CONNECTION

IF REQUIRED

DOOR SEAM

24" MIN.

6" MIN.

PLAIN END x FLANGE SPOOL

PIT READ MODULE

FLUSH WITH TOP

7"

FLOW

PLAN

NOT TO BE USED IN

TRAFFIC AREAS OR

PARKING LOTS

OPTIONAL VALVE

12" MIN.

18" MAX.

PIPE STAND

(TYP.)

PLAIN END x FLANGE SPOOL

3" MIN.

6" MAX.

3" MIN. CLEARANCE

ON OPENED VALVE

VAULT SHALL BE EQUIPED WITH HYDRAULIC ASSIST

LOCKING HATCH (MIN. 30" x 60") LOCKING OPEN 90°

LEAK PROOF GASKETED. LW HHD-1 (HS20) ALUMINUM DOORS

FLOW

ELEVATION

5. LINK SEALS FOR ALL VAULT PENETRATIONS.

3. HATCH DRAINS TO BE PLUMBED TO DAYLIGHT OR STORM DRAIN AS DIRECTED BY THE CITY INSPECTOR.

4. KNOCKOUT NOT ALLOWED IN VAULT, CORE SAW ONLY.

NOTES:

THRUST BLOCK

10. ALL TESTING, FLUSHING, & CHLORINATION SHALL BE PERFORMED PRIOR TO INSTALLATION OF THE BACKFLOW DEVICE.

11. TAMPER SWITCH REQUIRED WHEN SPECIFIED BY FIRE MARSHAL.

1. CONTRACTOR TO PROVIDE SITE SPECIFIC SHOP DRAWING FOR CITY ENGINEER APPROVAL PRIOR TO ANY CONSTRUCTION OF THIS ITEM.

2. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW PREVENTION ASSEMBLIES.

12. WATER METER SHALL INCLUDE A TOUCH READ PIT MODULE PLACED IN 37 ARMOR CAST BOX ON STREET SIDE.

6. PIPE STANDS TO BE STANDON S76 OR APPROVED EQUIVILANT FLANGE STYLE STANDS, EITHER GALVANIZED OR MADE OF STAINLESS STEEL.

7. VAULT SHALL BE EQUIPPED WITH A LEAK PROOF, GASKETED, DOUBLE RAISE, ALUMINUM, AASHTO H20 RATED, HYDRAULIC ASSIST,

LOCKING HATCH, MIN. 36" x 60", LOCKING OPEN 90°.

8. VAULT SHALL BE PRECAST CONCRETE, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE DETAIL.

9. VAULT SHALL GRAVITY DRAIN TO DAYLIGHT OR A STORM DRAIN. IF THIS IS NOT POSSIBLE, A 1/4 HP MINIMUM SUMP PUMP SHALL BE INSTALLED

IN THE SUMP PIT OF THE VAULT AND SHALL DISCHARGE TO DAYLIGHT OR A STORM DRAIN. SAID PUMP SHALL AUTOMATICALLY

PROTECT THE VAULT FROM FLOODING AT ALL TIMES.

13. CONFIRM LOCATION WITH CITY PRIOR TO INSTALLATION.

14. METER SHALL BE A TOUCH READ THAT IS COMPATIBLE WITH ITRON HANDHELD DATA COLLECTOR - FC300.

15. SUPPLY BADGER OR SENSUS METER WITH 12' CORD.

16. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' TO REACH ABOVE FINISH GROUND.

TRACER WIRE

(SEE NOTE 16)

3' COIL

DOUBLE CHECK DETECTOR ASSEMBLY

W - 350MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 31: WATER SUPPLY - mylongview.com

SHALL MEET

CITY STANDARDS

SHALL MEET

PLUMBING CODECITY PRIVATE

P

L

1. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW PREVENTION

ASSIMBLIES.

2. ASSEMBLY SHALL BE INSTALLED ABOVE GROUND IN A HEATED AND/OR INSULATED ENCLOSURE CAPABLE OF PROVIDING

YEAR-ROUND FREEZE PROTECTION, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE DETAIL.

3. DCDA GATE VALVES SHALL HAVE SUPERVISED TAMPER SWITCHES IF REQUIRED BY FIRE MARSHALL.

4. PIPE STANDS TO BE STANDON S76 OR EQUIVALENT FLANGE STYLE STANDS, EITHER GALVANIZED OR MADE OF STAINLESS

STEEL.

5. WATER METER SHALL INCLUDE A TOUCH READ PIT MODULE INSTALLED ON THE STREET SIDE OF THE ENCLOSURE.

6. VERTICAL UPRIGHTS SHALL BE FLANGED SPOOLS OR BE RESTRAINED JOINT WITH STAINLESS STEEL RODS.

7. SLAB SHALL EXTEND 12" LARGER THAN ENCLOSURE FOOTPRINT, ALL THE WAY AROUND.

NOTES: FLOW

FLOW

12" - 18"

6" REINFORCED

CONCRETE SLAB

CAST IN PLACE PIPE

FLOOR SLEEVE

90° BEND FLG

PIPE STANDS

(TYP.)

90° BEND MJ

WITH MEGA-LUG

RETAINER GLANDS

SEAL ANNULAR SPACE

W/ SILICONE CAULK

3" - 6"

FINISHED

GRADE

3" MIN. CLEARANCE ABOVE

FULLY OPENED VALVE

24" MIN.

6" MIN. 6" MIN.

12" MIN.

PLAN

ELEVATION

USE #4 BAR

12" O.C.

8. METER SHALL BE A TOUCH READ THAT IS COMPATIBLE WITH ITRON HANDHELD DATA COLLECTOR - FC300.

9. SUPPLY BADGER OR SENSUS METER WITH 12' CORD.

3' COIL

TRACER WIRE

(SEE NOTE 10)

10. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

DOUBLE CHECK DETECTOR ASSEMBLY, LARGE, ABOVE GROUND

W - 370MARCH 2018

C.B.

AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
N
AutoCAD SHX Text
C
AutoCAD SHX Text
L
AutoCAD SHX Text
O
AutoCAD SHX Text
P
AutoCAD SHX Text
E
AutoCAD SHX Text
O
AutoCAD SHX Text
S
AutoCAD SHX Text
E
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 32: WATER SUPPLY - mylongview.com

CIT

YP

RIV

AT

EP

L

SH

AL

L M

EE

T

CIT

Y S

TA

ND

AR

DS

SH

AL

L M

EE

T

PL

UM

BIN

G C

OD

E

1. R

EF

ER

T

O C

IT

Y S

TA

ND

AR

D D

ET

AIL

W

-4

30

F

OR

IN

ST

AL

LA

TIO

N R

EQ

UIR

EM

EN

TS

T

HA

T A

PP

LY

T

O A

LL

B

AC

KF

LO

W P

RE

VE

NT

IO

N A

SS

EM

BL

IE

S.

2. A

SS

EM

BL

Y S

HA

LL

B

E IN

ST

AL

LE

D A

BO

VE

G

RO

UN

D IN

A

H

EA

TE

D A

ND

/O

R IN

SU

LA

TE

D E

NC

LO

SU

RE

C

AP

AB

LE

O

F P

RO

VID

IN

G Y

EA

R-R

OU

ND

F

RE

EZ

E

P

RO

TE

CT

IO

N, S

IZ

ED

T

O M

EE

T T

HE

C

LE

AR

AN

CE

R

EQ

UIR

EM

EN

TS

S

HO

WN

IN

T

HE

D

ET

AIL

.

3. D

CD

A G

AT

E V

AL

VE

S S

HA

LL

H

AV

E S

UP

ER

VIS

ED

T

AM

PE

R S

WIT

CH

ES

IF

R

EQ

UIR

ED

B

Y F

IR

E M

AR

SH

AL

L.

4. W

AT

ER

M

ET

ER

S

HA

LL

IN

CL

UD

E A

T

OU

CH

R

EA

D P

IT

M

OD

UL

E IN

ST

AL

LE

D O

N T

HE

S

TR

EE

T S

ID

E O

F T

HE

E

NC

LO

SU

RE

.

5. V

ER

TIC

AL

U

PR

IG

HT

S S

HA

LL

B

E F

LA

NG

ED

S

PO

OL

S O

R B

E R

ES

TR

AIN

ED

JO

IN

IT

W

IT

H S

TA

IN

LE

SS

S

TE

EL

R

OD

S.

6. S

LA

B S

HA

LL

E

XT

EN

D 1

2" L

AR

GE

R T

HA

N E

NC

LO

SU

RE

F

OO

TP

RIN

T, A

LL

T

HE

W

AY

A

RO

UN

D.

NO

TE

S:

12

" - 1

8"

3" - 6

"

FIN

IS

HE

D

GR

AD

E

6" M

IN

.

6" M

IN

.

6" R

EIN

FO

RC

ED

CO

NC

RE

TE

S

LA

B

MA

NU

FA

CT

UR

ER

'S

SE

TT

ER

R

EQ

UIR

ED

RE

ST

RA

IN

ED

JO

IN

TS

,

ME

GA

-L

UG

O

R

EQ

UIV

AL

EN

T

CA

SE

IN

P

LA

CE

PIP

E F

LO

OR

S

LE

EV

E

3" M

IN

C

LE

AR

AN

CE

WH

EN

V

AL

VE

FU

LL

Y O

PE

NE

D

24

" M

IN

.

12

" M

IN

.

SID

E E

LEV

AT

ION

E

ND

ELE

VA

TIO

N

6" M

IN

.

US

E #

4 B

AR

12

" O

.C

.

7. M

ET

ER

S

HA

LL

B

E A

T

OU

CH

R

EA

D T

HA

T IS

C

OM

PA

TIB

LE

W

IT

H IT

RO

N H

AN

DH

EL

D D

AT

A C

OL

LE

CT

OR

- F

C3

00

.

8. S

UP

PL

Y B

AD

GE

R O

R S

EN

SU

S M

ET

ER

W

IT

H 1

2' C

OR

D.

9. L

OC

AT

E W

IR

E IN

ST

AL

LE

D T

O A

SS

EM

BL

Y A

ND

C

OIL

T

O A

LL

OW

3

' R

EA

CH

A

BO

VE

F

IN

IS

H G

RO

UN

D.

TR

AC

ER

W

IR

E

(S

EE

N

OT

E 9

)

3' C

OIL

DOUBLE CHECK DETECTOR ASSEMBLY, N-PATTERN

W - 380MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 33: WATER SUPPLY - mylongview.com

P

L

12"

IN

TE

RN

AL

AN

CH

OR

(T

YP

. O

F 4)

36" M

IN

.

FR

OM

C

IT

Y

MA

IN

/ M

ET

ER

14"

MA

NU

FA

CT

UR

ER

S

SE

TT

ER

R

EQ

UIR

ED

RE

ST

RA

IN

ED

JO

IN

TS

ME

GA

LU

G O

R E

QU

IV

.

FLO

W

6" R

EIN

FO

RC

ED

CO

NC

RE

TE

S

LA

B

12"

12" M

IN

.

18" M

AX

.

12"

11"

MIN

.

12"

1. R

ED

UC

ED

P

RE

SS

UR

E B

AC

KF

LO

W A

SS

EM

BLY

S

HA

LL B

E IN

ST

ALLE

D IN

A

LO

CA

TIO

N A

PP

RO

VE

D B

Y T

HE

C

IT

Y.

2. R

ED

UC

ED

P

RE

SS

UR

E B

AC

KF

LO

W A

SS

EM

BLY

S

HA

LL B

E IN

ST

ALLE

D H

OR

IZ

ON

TA

L A

ND

P

LU

MB

.

3. A

SS

EM

BLY

S

HA

LL B

E IN

ST

ALLE

D A

BO

VE

G

RO

UN

D IN

A

H

EA

TE

D A

ND

/O

R IN

SU

LA

TE

D E

NC

LO

SU

RE

NO

TE

S:

CA

PA

BLE

O

F P

RO

VID

IN

G Y

EA

R-R

OU

ND

F

RE

EZ

E P

RO

TE

CT

IO

N, S

IZ

ED

T

O M

EE

T T

HE

C

LE

AR

AN

CE

RE

QU

IR

EM

EN

TS

S

HO

WN

IN

T

HE

D

ET

AIL.

US

E #4 B

AR

12" O

.C

.

11"

MIN

.

6"

MIN

.

6"

MIN

.

6"

MIN

.

4. LO

CA

TE

W

IR

E IN

ST

ALLE

D T

O A

SS

EM

BLY

A

ND

C

OIL T

O A

LLO

W 3' R

EA

CH

A

BO

VE

F

IN

IS

H G

RO

UN

D.

TR

AC

ER

W

IR

E

(S

EE

N

OT

E 4)

N-PATTERN REDUCED PRESSURE BACKFLOW ASSEMBLY

W - 390MARCH 2018

C.B.

AutoCAD SHX Text
XXX
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 34: WATER SUPPLY - mylongview.com

NOTES:

6" TYP

EACH SIDE

SEE

NOTE 3

18" MIN

2" MIN

PROFILE

4

10

2

9

5

2

9

9

5

1

6

7

8

8

3

3

11 11

NOTICE: OUTSIDE-INSTALLED RPBA IS NOT ALLOWED IN BURIED VAULTS. DEVELOPER SHALL

PROVIDE UTILITIES WITH A DESIGN FOR AN ABOVE-GROUND ENCLOSURE THAT DRAINS

TO DAY LIGHT FOR APPROVAL. CLEARANCES SHOWN BELOW SHALL APPLY TO THE

ENCLOSURE.

STATE APPROVED REDUCED PRESSURE BACKFLOW ASSEMBLY, COMPLETE WITH (2) RESILIENT SEATED O.S.&Y. GATE

VALVES (2" AND SMALLER: FULL FLOW RESILIENT SEATED BALL VALVES) AND (4) RESILIENT SEATED TEST COCKS.

MEGAFLANGE. (2" AND SMALLER: BRASS UNION, M.I.P.T. x F.I.P.T.).

4" MIN CONC. (2000 PSI) SLAB EXTENDED 6" BEYOND ENCLOSURE (ALL DIRECTIONS). REINFORCED WITH 6x6

W2.9xW2.9 WWF.

APPROVED ENCLOSURE. CONTRACTOR TO VERIFY REQUIRED SIZE.

90° BEND, FL (2" AND SMALLER: BRASS, F.I. P.T.).

ENCLOSURE DRAIN, SIZED IN ACCORDANCE WITH PNWS-AWWA CROSS CONNECTION CONTROL MANUAL (7TH

EDITION) fIGURE 6-1.

TWO ADJUSTABLE PIPE STANCHIONS, BOLTED TO SLAB FOR 1-1/2" & 2".

PVC SLEEVE THROUGH SLAB.

CL. 52 D.I., PExFL

(2" AND SMALLER: BRASS NIPLE, M.I.P.T.)

EACH VALVE SHALL BE MARKED WITH MODEL NUMBER WITH DESIGNATION OF RESILIENT SEAT: SUCH AS "RS" OR "R",

WHICH MUST BE CAST, MOLDED, OR AFFIXED ONTO THE BODY OR BONNET OF THE VALVE. ALL FERROUS BODIED

VALVES SHALL BE COATED WITH A MINIMUM OF 4 MILS. OF EPOXY OR EQUIVALENT POLYMERIZED COATING.

90° BEND, RESTRAINED JOINT (2" AND SMALLER: BRASS, COMPRESSION x F.I.P.T.).

1

2

3

4

5

6

7

8

9

10

11

1. PROVIDE ELECTRICAL HEAT TAPE FREEZE PROTECTION.

2. WHEN THE REDUCED PRESSURE ASSEMBLY IS LOCATED INSIDE A BUILDING A SIZED DRAIN LINE SHALL BE PROVIDED

FOR RELIEF PORT. THERE MUST BE AN APPROVED AIR GAP BETWEEN THE RELIEF PORT AND DRAIN.

3. ALLOW 12"+ NOMINAL DIAMETER OF ASSEMBLY CLEARANCE BELOW RELIEF PORT FOR REPAIR. ALSO PROVIDE 12"

MIN. AIR GAP CLEARANCE FROM TOP OF DRAIN PIPE.

4. REDUCED PRESSURE BACKFLOW ASSEMBLY WILL BE ALLOWED TO BE INSTALLED IN VAULTS ONLY IN CASES WHERE

NO OTHER MEANS OF INSTALLATION IS AVAILABLE AND AS APPROVED BY A CITY OF LONGVIEW WATER QUALITY

TECHNICIAN.

5. TESTING IS REQUIRED BY A WASHINGTON STATE DEPARTMENT OF HEALTH CERTIFIED BACKFLOW ASSEMBLY TESTER

UPON INSTALLATION AND ANNUALLY THEREAFTER. ASSEMBLY TO BE MAINTAINED BY OWNER.

6. ALL CLEARANCES SHOWN ARE MINIMUM.

7. ENCLOSURES SHALL NOT BE INSTALLED IN AREAS WITH VEHICULAR TRAFFIC.

8. TEE AND GATE VALVES REQUIRED ON MAIN.

9. IN CENTRAL BUSINESS DISTRICT, 3" THROUGH 6" ASSEMBLIES SHALL CONNECT TO WATER MAIN WITH 8" PIPE.

10. MINIMUM 2' OF LEVEL, UNOBSTRUCTED AREA AROUND ENCLOSURES.

11. RPBA INSTALLATIONS THAT DIFFER FROM THE STANDARD DETAIL MUST BE APPROVED BY THE CROSS CONNECTION

PROGRAM ADMINISTRATOR (360) 442-5700 AND WILL BE REVIEWED ON A CASE-BY-CASE BASIS TO ENSURE THEY MEET

CURRENT MINIMUM REQUIREMENTS FOR INSTALLATION AND FREEZE PROTECTION.

12. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

TRACER WIRE

(SEE NOTE 12)

3' COIL

2" & SMALLER REDUCED PRESSURE BACKFLOW ASSEMBLY FOR

W - 400MARCH 2018

C.B.

DOMESTIC AND IRRIGATION SERVICE (OUTSIDE INSTALLATION)

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 35: WATER SUPPLY - mylongview.com

1. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW

PREVENTION ASSEMBLIES.

2. ASSEMBLY SHALL BE INSTALLED ABOVE GROUND IN A HEATED AND/OR INSULATED ENCLOSURE CAPABLE OF PROVIDING

YEAR-ROUND FREEZE PROTECTION, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE DETAIL.

3. DO NOT INSTALL IN AN AREA SUBJECT TO FLOODING.

4. ENCLOSURE SHALL BE EQUIPPED WITH A BORE-SIGHTED DRAIN TO DAYLIGHT, CAPABLE OF HANDLING THE VOLUME OF

WATER THAT POTENTIALLY COULD BE DISCHARGED FROM THE RELIEF VALVE PORT.

5. PIPE STANDS TO BE STANDON S76 OR EQUIVALENT FLANGE STYLE, EITHER GALVANIZED OR MADE OF STAINLESS STEEL.

6. VERTICAL UPRIGHTS SHALL BE FLANGED SPOOLS OR BE RESTRAINED JOINT WITH STAINLESS STEEL RODS.

7. SLAB SHALL EXTEND 12" LARGER THAN ENCLOSURE FOOTPRINT, ALL THE WAY AROUND.

NOTES:

FLOW

6" MIN.6" MIN.

12" MIN.

24" MIN.

3" MIN CLEARANCE ABOVE

FULLY OPENED VALVE

12" - 18"

PIPE STANDS

(TYP.)

90° BEND MJ

WITH MEGA-LUG

RETAINER GLANDS

ELEVATION

3" - 6"

FINISHED

GRADE

SEAL ANNULAR SPACE

W/ SILICONE CAULK

SHALL MEET

CITY STANDARDS

SHALL MEET

PLUMBING CODECITY PRIVATE

P

L

BORE SIGHTED

DRAIN TO

DAYLIGHT

6" REINFORCED

CONCRETE SLAB

CAST IN PLACE PIPE

FLOOR SLEEVE

90° BEND FLG

FLOW

USE #4 BAR

12" O.C.

MIN. MAX.

HOT BOX

8. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GROUND.

3' COIL

TRACER WIRE

(SEE NOTE 8)

REDUCED PRESSURE BACKFLOW ASSEMBLY, LARGE

W - 410MARCH 2018

C.B.

AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
O
AutoCAD SHX Text
E
AutoCAD SHX Text
P
AutoCAD SHX Text
O
AutoCAD SHX Text
L
AutoCAD SHX Text
C
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
O
AutoCAD SHX Text
L
AutoCAD SHX Text
C
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
P
AutoCAD SHX Text
O
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 36: WATER SUPPLY - mylongview.com

SHALL MEET

CITY STANDARDS

SHALL MEET

PLUMBING CODECITY PRIVATE

P

L

1. REFER TO CITY STANDARD DETAIL W-430 FOR INSTALLATION REQUIREMENTS THAT APPLY TO ALL BACKFLOW

PREVENTION ASSEMBLIES.

2. ASSEMBLY SHALL BE INSTALLED ABOVE GROUND IN A HEATED AND/OR INSULATED ENCLOSURE CAPABLE OF PROVIDING

YEAR-ROUND FREEZE PROTECTION, SIZED TO MEET THE CLEARANCE REQUIREMENTS SHOWN IN THE DETAIL.

3. DO NOT INSTALL IN AN AREA SUBJECT TO FLOODING.

4. ENCLOSURE SHALL BE EQUIPPED WITH A DRAIN TO DAYLIGHT, CAPABLE OF HANDLING THE VOLUME OF WATER THAT

POTENTIALLY COULD BE DISCHARGED FROM THE RELIEF VALVE PORT.

5. PIPE STANDS TO BE STANDON S76 OR EQUIVALENT FLANGE STYLE, EITHER GALVANIZED OR MADE OF STAINLESS STEEL.

6. RPDA GATE VALVES SHALL HAVE SUPERVISED TAMPER SWITCHES IF REQUIRED BY FIRE MARSHALL.

7. WATER METER SHALL INCLUDE A TOUCH READ PIT MODULE INSTALLED ON THE STREET SIDE OF THE ENCLOSURE.

8. VERTICAL UPRIGHTS SHALL BE FLANGED SPOOLS OR BE RESTAINED JOINT WITH STAINLESS STEEL RODS.

9. SLAB SHALL EXTEND 12" LARGER THAN ENCLOSURE FOOTPRINT, ALL THE WAY AROUND.

NOTES:

FLOW

6" MIN.6" MIN.

12" MIN.

24" MIN.

3" MIN. CLEARANCE ABOVE

FULLY OPENED VALVE

12" - 18"

PIPE STANDS

(TYP.)

90° BEND MJ

WITH MEGA-LUG

RETAINER GLANDS

ELEVATION

3" - 6"

FINISHED

GRADE

SEAL ANNULAR SPACE

W/ SILICONE CAULK

BORE SIGHTED

DRAIN TO

DAYLIGHT

6" REINFORCED

CONCRETE SLAB

CAST IN PLACE PIPE

FLOOR SLEEVE

90° BEND FLG

FLOW

SIZED FOR 3 PIPE

SIZE LARGER THAN

RELIEF VALVE

USE #4 BAR

12" O.C.

MIN. MAX.

10. METER SHALL BE A TOUCH READ THAT IS COMPATIBLE WITH ITRON HANDHELD DATA COLLECTOR - FC300.

11. SUPPLY BADGER OR SENSUS METER WITH 12' CORD.

12. LOCATE WIRE INSTALLED TO ASSEMBLY AND COIL TO ALLOW 3' REACH ABOVE FINISH GRADE.

TRACER WIRE

(SEE NOTE 12)

3' COIL

REDUCED PRESSURE DETECTOR ASSEMBLY, LARGE

W - 420MARCH 2018

C.B.

AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
O
AutoCAD SHX Text
E
AutoCAD SHX Text
P
AutoCAD SHX Text
O
AutoCAD SHX Text
L
AutoCAD SHX Text
C
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
O
AutoCAD SHX Text
L
AutoCAD SHX Text
C
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
P
AutoCAD SHX Text
O
AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 37: WATER SUPPLY - mylongview.com

GROUND

3

4

" 90° BENDS

4"

BALL VALVE

3

4

" SCH. 80 OR BETTER

TO DECHLORINATION VESSEL

OR 2" GALVANIZED INDUCTOR

PUMP.

2" GALVANIZED PIPE

2" BALL VALVE

2" GALVANIZED PIPE

REDUCER (2" 90°)

VALVE BOX

BLOW-OFF

1. USE

3

4

", CLEAN, SCH. 80 OR BETTER PVC MATERIAL FOR PIPE AND BENDS.

2. CONTRACTOR TO ASSEMBLE FOR SAMPLING TO OBTAIN BACTERIA TEST.

3. TEST STATION TO BE INSTALLED AFTER FLUSHING AND TESTING IS COMPLETE.

4. CONTRACTOR IS RESPONSIBLE TO SUPPLY, INSTALL AND REMOVE TEST STATION.

5. TO BE FLUSHED WITH A MINIMUM OF 50 mg/L OF CHLORINATED WATER PRIOR TO INSTALLING.

NOTES:

3' MIN - 4' MAX

REDUCER AND INSTALL

1" METER NUT.

TEST STATION DETAIL

W - 660JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 38: WATER SUPPLY - mylongview.com

WATER NOTES:

7-09 WATER MAINSSection 7-09.2; MaterialsParagraph 1 is replaced with the following:

Materials shall meet the following sections:Pipe 9-30.1Ductile Iron Pipe (Restrained Joint) 9-30.1(1)Fittings 9-30.2Ductile Iron Pipe 9-30.2(1)Restrained Joints 9-30.2(6)Bolted Sleeve-Type Couplings for Plain End Pipe 9-30.2(7)Valves 9-30.3Gate Valves (3 inches to 10 inches) 9-30.3(1)Butterfly Valves (12 inches and greater) 9-30.3(3)Valve Boxes 9-30.3(4)Valve Marker Posts 9-30.3(5)Valve Stem Extension 9-30.3(6)Combination Air Release Valves 9-30.3(7)Tapping Sleeve and Valve Assembly 9-30.3(8)Hydrants (All bolts and nuts to be stainless steel with 9-30.5

Anti-seize Compound)Service Connections (2 inches and Smaller) 9-30.6

All Ductile Iron Pipe, fittings and appurtenances shall have restrained joints by the use of Mega-Lugs,Romac Grip Rings, Field-Lock gaskets, or approved equal.

Bolts and nuts for flanged pipe and fittings shall conform in size and length with ANSI/AWWAC115/A21.15. All bolts and nuts shall be made from COR-TEN steel in accordance with ANSI/AWWAC111/A21.11.

All fittings to have thrust blocks as indicated in City Standard Plans.

Note: The City reserves the right for any or all salvage rights to any existing materials removedincluding but not limited to fire hydrants, crosses, tees, gate valves or pipe.

It shall be determined by the City as to what materials will be salvaged.

Any material requested for salvage will be delivered by the contractor to the City's operation center asdirected by the City.

All costs associated with delivery or removal and disposal shall be borne by the contractor.

7-09.3 Construction RequirementsSection 7-09.3(5); Grade and AlignmentThis section is supplemented with the following:

A minimum horizontal separation of 10 feet between sanitary sewers and any existing potable waterlines, and a minimum vertical separation of 18 inches between the bottom of the water line and thecrown of the sewer, shall be maintained. The distance shall be measured edge to edge. Sewer lineshould be lower than water line and installed in separate trenches.

WATER SPECIFICATIONS (1 OF 5)

W - 700JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 39: WATER SUPPLY - mylongview.com

Section 7-09.3(9); Bedding the PipeSentence 1 is replaced with the following:

Bedding material shall be select granular material free from wood waste, organic material, and otherextraneous or objectionable materials and shall be CSTC.

Trace WireTrace wire shall be installed on all water mains and smaller service lines with a lay length of more than6 feet. The wire shall be attached to the lines at 15 foot intervals and shall be brought to the surface atall junctions and termini using methods approved by the Engineer. Trace wire material for water linesshall be 12 Gauge, soft drawn, insulated, and shall be blue in color.

Splices shall be made with a kit containing a "T" shaped open cell centering device and a plastic bag ofurethane and hardener which is mixed at the time of installation or heat shrinkable insulating tubing.Heat shrinking insulating tubing shall consist of a mastic lined heavy wall polyolefin cable sleeve. Theresin used with the "T" shaped open cell centering device shall be a quick curing flexible compoundwith an approximate set-up time of 4 minutes at 72° F.A continuity test shall be performed on tracer wire with inspector present prior to paving roadway.

7-09.3(19) ConnectionsSection 7-09.3(19) A; Connections to Existing MainsParagraphs 1, 4, 5, and 6 are replaced with the following:

Connections to the existing water main shall not be made without first making the necessaryarrangements with the City Water/Sewer Department in advance. Work shall not be started until theexisting main has been potholed to determine the materials, equipment, and labor necessary to properlycomplete the work. All the materials, equipment, and labor necessary to properly complete the workshall be assembled on the site before work is started. Torque tighten all non-test bolts.

Once work is started on a connection, it shall proceed continuously without interruption, and as rapidlyas possible until completed. No shutoff of mains will be permitted overnight, over weekends, onMondays or Fridays, or on holidays. The Water/Sewer Superintendent must be notified a minimum of48 hours prior to any shutoff and must give approval prior to the shutoff taking place.

If the connection to the existing system involves turning off the water, the Contractor shall beresponsible for notifying the residents affected by the shutoff a minimum of 48 hours prior to theshutoff. The Water/Sewer Superintendent will advise which property owners are to be notified.

Connections must be performed between 8:00 a.m. and 4:00 p.m. Tuesday through Thursdays unlessother arrangements have been made with the Water/Sewer Superintendent. Any overtime cost by citystaff will be incurred by the contractor.

All waterlines and services shall be abandoned at the main and provide a one foot separation from thewatermain. Flushing may be required to be performed at night (per City direction) during non-peakflows.

Section 7-09.3(21); Concrete Thrust BlockingThis section is supplemented with the following:

All forms for concrete and deformed rebar thrust blocking must be approved by the City Engineer prior topouring the concrete.

WATER SPECIFICATIONS (2 OF 5)

W - 701JAN 2017

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 40: WATER SUPPLY - mylongview.com

Once work is started on a connection, it shall proceed continuously without interruption, and as rapidlyas possible until completed. No shutoff of mains will be permitted overnight, over weekends, onMondays or Fridays, or on holidays. The Water/Sewer Superintendent must be notified a minimum of48 hours prior to any shutoff and must give approval prior to the shutoff taking place.

If the connection to the existing system involves turning off the water, the Contractor shall beresponsible for notifying the residents affected by the shutoff a minimum of 48 hours prior to theshutoff. The Water/Sewer Superintendent will advise which property owners are to be notified.

Connections must be performed between 8:00 a.m. and 4:00 p.m. Tuesday through Thursdays unlessother arrangements have been made with the Water/Sewer Superintendent. Any overtime cost by citystaff will be incurred by the contractor.

All waterlines and services shall be abandoned at the main and provide a one foot separation from thewatermain. Flushing may be required to be performed at night (per City direction) during non-peakflows.

Section 7-09.3(21); Concrete Thrust BlockingThis section is supplemented with the following:

All forms for concrete and deformed rebar thrust blocking must be approved by the City Engineer prior topouring the concrete.

Section 7-09 .3(23); Hydrostatic Pressure TestParagraphs 1, 4, and 5 are replaced with the following:

All water mains and appurtenances shall be tested in sections of convenient length under a hydrostaticpressure equal to 1.5 times that under which they will operate or 200 psi whichever is greater. Allpumps, gauges, plugs, saddles, corporation stops, miscellaneous hose and piping, and measuringequipment necessary for performing the test shall be furnished and operated by the Contractor. TheEngineering Department must be notified a minimum of 48 hours prior to testing and must be presentwhen tests are performed.

The mains shall be filled with water and allowed to stand under pressure a sufficient length of time toallow the escape of air and allow the lining of the pipe to absorb water. The Contractor shall beresponsible for providing the water necessary to fill the pipelines for testing purposes.

The test shall be accomplished by pumping the main up to the required pressure, stopping the pump for2 hours, and then pumping the main up to the test pressure again. During the test, the section beingtested shall be observed to detect any visible leakage. A clean container shall be used for holding waterfor pumping up pressure on the main being tested. This makeup water shall be sterilized by theaddition of chlorine to a concentration of 50 mg/l. In accordance with AWWA Standards.

WATER SPECIFICATIONS (3 OF 5)

W - 702MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 41: WATER SUPPLY - mylongview.com

Disinfection of Water MainsSection 7-09.3(24)A; FlushingParagraph 1 is replaced with the following:

Sections of pipe to be disinfected shall first be flushed to remove any solids or contaminated materialthat may have become lodged in the pipe. Tap shall be provided large enough to develop a velocity ofat least 6 fps in the main. Hydrants are not to be used for pipe flushing; only approved blow offassemblies are to be used. Connecting to city mains or flushing may be required at night depending onsystem conditions as determined by the engineer.

Contractor to provide sampling station point per City standards.

Section 7-09.3(24)D; Dry Calcium HypochloriteThis section is deleted in it's entirety.

7-12 VALVES FOR WATER MAINSConstruction RequirementsSection 7-12.3(1); Installation of Valve Marker PostThis section is replaced with the following:

Where required, a valve marker post shall be furnished and installed with each valve. Valve markerposts shall be placed at the edge of the right-of-way opposite the valve and be set with a minimum of48" of the post exposed above grade. The post shall have a blue reflective "water valve" decal placedwithin 3" of the top of the post. The post shall be carsonite. The post shall face on coming traffic at 4feet away from the valve.

A concrete collar shall be poured around valve boxes that are to grade. A two headed arrow stamp willbe used to stamp the concrete collar to show direction of flow for the water main.

All operators for Butterfly Valves shall be on centerline of street side of the main.

The contractor shall not operate any city valve. The city must be contacted to turn all city valves for allphases of construction.

7-14 HYDRANTSConstruction RequirementsSection 7-14.3(6); Hydrant ExtensionsThis section is supplemented with the following:

Hydrant extensions will not be allowed for newly constructed hydrants. The large port on the hydrantshall face the road.

7-15 SERVICE CONNECTIONSSection 7-15.3; Construction RequirementsParagraph 1 is replaced with the following:

All service connections to water mains shall be made using saddles as specified and be of the size andtype suitable for use with the pipe being installed. Service pipelines shall be installed perpendicular tothe main, unless otherwise shown in the plans.

WATER SPECIFICATIONS (4 OF 5)

W - 703MARCH 2018

C.B.

AutoCAD SHX Text
CITY ENGINEER APPROVAL:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
Longview:
AutoCAD SHX Text
STANDARD PLAN:
Page 42: WATER SUPPLY - mylongview.com

Water meter service shall not conflict with electric/gas services, required 4' horizontal and 12" verticalseparation from other utilities for Longview (5' horz. and 18" vert. for Kelso). (10' horizontal and 18"vertical from sanitary sewer)

PERMISSABLE HYDRANT METER LOCATION NOTE (construction water)

Contractor shall apply for hydrant permit thru the City Water Department if construction water isneeded. No meters installed without fee's being paid in full. City to determine location for all hydrant meters.

WATER NOTES ADDITIONAL1. Connection to the Water System shall be inspected by Public Works Department. 48 Hours (2

working days) notice for inspection.2. All water system flushing, including fire lines, shall be scheduled through the Public Works

Department who will in turn schedule the water department to be present to record water used and tooperate city valves.

3. Utility permits must be applied and paid for prior to any connections being made to either the wateror sewer system.

4. All backflow devices must be tested and certified by a stated certified tester prior to the waterservices being activated for use.

5. Only City Water Department personnel shall operate city valves.6. Shut downs of the water system for connections will be done between Tuesday and Thursday from 8

AM and 4 PM. Max time the water may be off is 4 hours without prior approval.7. Submittals and shop drawings must be approved before the shut down is scheduled. Contractor is

required to notify the customers affected 2 working days in advance in writting with city approvedletter.

8. Meters larger than 1" will be supplied by the contractor.a. Must be delivered to the Water Department shop for accuracy testing at least one

week prior to installation date.b. Must be installed by the contractor.c. Must have approved submittal

All backfill shall be 5

8" minus (CSTC).

Foundation material & Geo grid shall be installed as directed by the City of Longview & to the depth asdirected.

All pavement patches shall be 2" plus existing in depth or as directed by the City of Longview.

All pavement shall be full depth sawcut & replaced per the limits as marked by the City of Longview afterconstruction.

WATER SPECIFICATIONS (5 OF 5)

W - 704MARCH 2018

C.B.

AutoCAD SHX Text