Installation and operating instructions for contractors
Vitobloc BACnet/IP Gateway
CHP unit accessory for VITOBLOC 200
50 to 530 kWel
5671 514-1 01/2015
Imprint
2 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
5671 5
14-1
NOTE
The Vitobloc 200 CHP unit is not suitable for 60 Hz operation. It is therefore not available for the American and Canadian markets in particular.
Note:
This technical guide contains instructions for design engineers regarding the design, use and operating conditions of a CHP unit.
For technical details please refer to the individual product catalogue, or for implementation planning, refer to the relevant technical unit description.
For assistance with preliminary work during the project planning phase please contact our advisers.
Subject to technical modifications.
Continuing development may result in minor differences in the illustrations, operating steps and specifications.
Updating the documentation
Please let us know if you have any suggestions for improving our documentation, or if you have noticed any errors.
Manufacturer’s address
Viessmann Werke GmbH & Co.KG D-35107 Allendorf Telephone +49 (0)6452 70-0 Fax: +49 (0)6452 70-2780 www.viessmann.de
Publication date: 01/2015
Table of contents
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 3
5671 5
14
-1
Table of contents
1. Safety instructions ................................................................................................................ 4
2. Function ................................................................................................................ 5
3. Type ................................................................................................................ 5
4. Installation 4.1 Mounting rail installation .................................................................. 6 4.2 Power supply ................................................................................... 8 4.3 Connecting the floating digital outputs ............................................. 9 4.4 Connecting the interfaces................................................................10
5. BACnet / IP 5.1 Data points.......................................................................................11 5.2 Sensor assignment by type of CHP unit .........................................16
6. Commissioning ...............................................................................................................18
7. Maintenance ...............................................................................................................18
8. Disposal ...............................................................................................................18
4 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Safety instructions
5671 5
14-1
1 Safety instructions
General These operating instructions contain general information that must be observed
during installation, operation and maintenance. They must therefore be read by the installer and relevant qualified technician(s) prior to installation and commissioning. They must always be available at the system.
Identification of safety instructions
Caution Note
Failure to observe the safety instructions identified with this hazard symbol in these installation and operating instructions may result in risks to personnel.
Failure to observe the safety instructions identified with this symbol may result in risks for the device or the system and its functions.
This symbol indicates information that will simplify work and ensure safe operation.
Personnel qualifications
The personnel designated to operate, maintain, inspect and install this equipment must have the appropriate qualifications for such work. The system operator is responsible for ensuring that this is the case.
The safety instructions listed in these operating instructions must be observed, as must all applicable national regulations for accident prevention and any in-house working, operating or safety instructions issued by the operator.
Risks from failure to observe the safety instructions
Safety instructions for the operator (risk analysis according to EN 12100)
Safety instructions for maintenance, inspection and installation work
Failure to observe the safety instructions may result in risks to personnel as well as to the environment and the system.
LIABILITY
The manufacturer will not accept any liability if these safety instructions are not observed.
In particular, failure to observe these instructions may pose the following risks:
Failure of important system functions
Failure of prescribed methods of service and maintenance
Risks to personnel due to electrical and mechanical effects
Electrical hazards
Hazards arising from electrical current, e.g. as a result of removing safety covers, must be prevented.
The operator must ensure that all maintenance, inspection and installation work is carried out by authorised, qualified personnel who have used the operating instructions to acquaint themselves with the device.
In principle, work may only be carried out on the device when the CHP unit is in an idle state and isolated from the power supply.
Directly after work has been completed, all safety and protective equipment must be replaced and returned to full function.
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 5
Function
5671 5
14
-1
Unauthorised modifications and production of spare parts
Alterations or modifications to the device are only permissible following consultation with the manufacturer. Original spare parts and accessories authorised by the manufacturer are important to ensure safety. Use of other parts can void the liability for any resulting losses.
Impermissible operation
The device may only be used for the specified purpose. Any installation for an unspecified purpose is strictly prohibited.
2 Function
General The device makes the data from a Vitobloc 200 CHP unit, which is read via the
RS-232, available on the BACnet/IP.
Fig. 1 Schematic diagram of the device
3 Version
Standard delivery The device is a compact unit for installation on a mounting rail.
The mounting rail and fittings are included in the standard delivery of the device.
On-site connection
(building management system)
CHP
unit
6 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Installation
5671 5
14-1
4 Installation
General operating conditions
The device is always installed in a de-energised state with the wiring disconnected.
In order to ensure fault-free operation of the device, the following conditions must be met and maintained:
Do not use in locations with aggravated operating conditions, such as
corrosive steam or gas, dust formation or high ionising radiation
Permissible ambient temperature during operation 0 °C to +55 °C
Any installation position
Permissible ambient temperature during storage -25 °C to +85 °C
Permissible relative humidity during storage 95 %, without condensation
Caution An earth terminal is required on the profile rail.
4.1 Mounting rail installation
General After removing the packaging, check the device for any transport damage.
Mount the top-hat rail on a clean surface and do not place it under stress.
Caution Drilling swarf, screws and other foreign bodies must be prevented from entering the device.
Install it away from thoroughfares, but ensure there is still easy access.
Protect the device from direct insolation.
Caution Ensure there is adequate heat transfer.
Installing the mounting rail With unit types EM-18/36, EM-20/39, EM-50/81 and EM-70/115, the Vitobloc Gateway must be installed in an external terminal box.
With larger CHP units that have ratings of 140 kWel or more, the mounting rail may be installed in the control panel of the CHP unit.
Fig. 2 Gateway on the side panel of the EM-140/207 CHP unit control panel
Fig. 3 Gateway in the control panel door of the EM-238/363 CHP unit
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 7
Installation
5671 5
14
-1
Installing the Gateway Pull the white tabs on the underside of the device downwards until they latch
into place
Push the device onto the top-hat rail
Do not apply pressure to the display as this risks Caution damaging it
Push the white tabs back into their original positions
Once the device has been successfully installed, connect it according to the connection diagram, taking account of the safety instructions
Removing the Gateway The Vitobloc Gateway is always removed in a de-energised state with the wiring disconnected.
Pull the white tabs on the underside of the device downwards until they
unlock
Pull out the orange tabs on the right-hand side of all the terminals in order to release them from the mounting rail
Grip the terminals simultaneously with your thumb and index finger at the top and bottom of the ribbed casing surfaces and pull from the mounting rail
8 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Installation
5671 5
14-1
4.2 Power supply
Before switching on the power supply, ensure that the components are clean and have been mounted in the correct order on the top-hat rail.
Order from left to right:
CX 9000
KL 2794
KL 9010
Fig. 4 BACnet / IP Gateway
Caution The device requires a voltage of 24 V DC (-15 %/+20 %), connected to an isolated power source protected by a max. 4 A fuse.
Connecting the power supply
Fig. 5 Power supply of the Vitobloc BACnet / IP Gateway
The 24 V DC power supply for the Gateway is connected via the contacts labelled 24 V and 0 V as well as the + and - contacts.
The spring-loaded terminals are designed for wires with a cross-section of between 0.08 and 2.5 mm² (stripped back by 8 to 9 mm).
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 9
Installation
5671 5
14
-1
4.3 Connecting the floating digital outputs
KL 2794 The KL 2794 has 4 floating digital outputs. Output 1 switches terminals 1 and 2;
output 2 terminals 5 and 6; output 3 terminals 3 and 4; and output 4 terminals 7 and 8 to continuity. The 4 outputs can be used freely (e.g. for calling the CHP unit)
Fig. 6 KL 2794
Signal-LED1
Contact allocation Plan view
Output 3
Power contact 0 V Output 3
Power contact + 24 V
Output 1
Output 4
Output 4
Output 2
Output 2 Output 1
Signal-LED4
Signal-LED2
Signal-LED3
10 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
Installation
5671 5
14
-1
4.4 Connecting the interfaces
RS232 interface The RS232 interface is marked COM1 and is connected with the RS232
interface of the CHP unit via the null modem cable provided.
Connecting cable between CHP unit and Gateway
CHP unit Sub-D 9-pole socket
GATEWAY Sub-D 9-pole socket
2: RxD
3: TxD
3: TxD
2: RxD
5: GND
5: GND
Tab. 1 Connecting cable between CHP unit and Gateway
Note Cable to RS232 standard.
Ethernet interface The CHP unit data is supplied to the BACnet / IP via the Ethernet interface. The device has 2 RJ-45 Ethernet ports, designated X001 and X002. The two ports behave like a switch. Thus the Ethernet cable can be routed further to an additional device. A commercially available Ethernet cable can be used to make the connection (4x2 Category 5 twisted pair copper cable – max. cable length 100 m).
The following IP settings are factory-set:
IP address: 192.168.4.78
Subnet mask: 255.255.255.0
To change the IP settings, the "cerhost" program is required; this can be downloaded from the Beckhoff website.
Link to the latest version: ftp://ftp.beckhoff.com/Software/embPC-Control/CE/Solutions/RemoteDisplay/CeRemDispHost.zip
This is a remote desktop software program which enables the installed Windows Ce user interface to be operated. The network settings in Windows Ce are performed in exactly the same way as in Windows XP.
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 11
BACnet / IP
5671 5
14
-1
5 BACnet / IP
The Gateway makes all data points of the CHP unit's RS232 interface available on the BACnet / IP. Four floating digital outputs for switching purposes (e.g. for calling the CHP unit) are also provided.
5.1 Data points
Designation BACnet type Content / remark
Mode Multistate input 1: OFF 2: manual 3: auto
Status Multistate input 1: OFF 2: ready 3: start 4. operation 5: fault
Operating mode Multistate input 1: OFF 2: manual 3: mains substitute 4: --- 5: selection 100 % 6: set value 0-100 %
Set_value_modulating_operation Analogue input
Fault
Multistate input The first fault reported during a malfunction until all faults have been acknowledged again.
Hours run Analogue input
Minutes run Analogue input
Starts Analogue input
Maintenance interval Analogue input
Unit lockout Analogue input
Advance warning time Analogue input
Next_service
Analogue input Indicates when the next service is due, expressed in hours run. (Next_service - hours run = number of hours run until next service)
NiCrNi_A Analogue input *1
NiCrNi_B Analogue input *1
NiCrNi_C Analogue input *1
NiCrNi_D Analogue input *1
12 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
BACnet / IP
5671 5
14-1
Designation BACnet type Content / remark
PT100_1 Analogue input *1
PT100_2 Analogue input *1
PT100_3 Analogue input *1
PT100_4 Analogue input *1
PT100_5 Analogue input *1
PT100_6 Analogue input *1
Battery voltage Analogue input
Oil pressure Analogue input
Lambda probe voltage Analogue input
Speed Analogue input
Temperature_controller Analogue input
Temperature_enabling Analogue input
Mains_voltage_L1 Analogue input
Mains_voltage_L2 Analogue input
Mains_voltage_L3 Analogue input
Gen._voltage_L1 Analogue input
Gen._voltage_L2 Analogue input
Gen._voltage_L3 Analogue input
Gen._current_L1 Analogue input
Gen._current_L2 Analogue input
Gen._current_L3 Analogue input
Mains_voltage_total Analogue input
Generator_voltage_total Analogue input
Gen._current_total Analogue input
Output Analogue input
Mains frequency Analogue input
Gen._frequency Analogue input
CosPhi Analogue input
Communication fault Binary input
Digital_output1 Binary output Freely usable floating digital output
Digital_output2 Binary output Freely usable floating digital output
Digital_output3 Binary output Freely usable floating digital output
Digital_output4 Binary output Freely usable floating digital output
*1 The temperatures for NiCrNi and PT 100 are assigned differently, depending on the unit type. (See chapter "Sensor assignment by type of CHP unit")
Tab. 2 BACnet data point list
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 13
BACnet / IP
5671 5
14
-1
5.1.1 Multistate faults
Value Designation Comments
1 No fault
2 Emergency stop
3 Min. oil level
4 Min. coolant pressure
5 Min. gas pressure
6 Safety temperature
7 Generator temperature
8 Silencer hood temperature
9 Fan fault
10 Coolant pump fault
11 Max. exhaust gas back pressure
12 Feed-in switch
13 External fault
14 Speed too high
15 Coolant temperature
16 Max. exhaust gas temperature
17 Min. exhaust gas temperature
18 Min. oil pressure
19 Max. gas pressure
20 Heating water pump fault
21 Start-up speed <50 rpm
22 Ignition speed
23 Speed window
24 Speed <1200 rpm
25 Start-up fault
26 Synchronisation fault
27 Speed <50 per pickup
28 Max. oil level
29 Max. temperature Pt100_2
30 Max. temperature Pt100_3
31 Max. output
32 Reverse output
33 Output controller fault
34 Lambda controller fault
35 Generator contactor fault
36 Ignition fault
14 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway • VITOBLOC 200
BACnet / IP
5671 5
14
-1
Message Designation Comments
37 Oil pressure fault
38 Lambda start position
39 Knocking ON
40 Knocking OFF
41 Time switch deselection Disabled
42 Time switch enabling Disabled
43 Mains fault F < Disabled
44 Mains fault F > Disabled
45 Mains fault U+F <> Disabled
46 Min. knocking output
47 Max. knocking output
48 Mains coupling switch
49 Knocking fault
50 Mains OK Disabled
51 Mains fault Disabled
52 Temperature deselection Disabled
53 Temperature enabling Disabled
54 Service overdue
55 Safety shutdown
56 Engine not idle
57 Battery undervoltage
58 Generator undervoltage
59 Generator overvoltage
60 Generator overcurrent
61 Generator out-of-balance load
62 Tightness test fault
63 Mains circuit breaker fault
64 Sensor fault
65 Max. exhaust gas temperature A
66 Min. exhaust gas temperature A
67 Max. exhaust gas temperature B
68 Min. exhaust gas temperature B
69 Max. exhaust gas temperature C
70 Min. exhaust gas temperature C
71 Max. exhaust gas temperature D
72 Min. exhaust gas temperature D
73 Exhaust gas temp. differential A/B
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 15
BACnet / IP
5671 5
14
-1
Message Designation Comments
74 Reserve
75 Max. return temp. PT100/2
76 Max. heating water temp. PT100/3
77 Max. engine oil temp.
78 Max. gas mixture temp.
79 Max. coolant mixture temp.
Tab. 3 Fault messages
5.1.2 EDE files
The EDE files are available on request.
BACnet / IP
16 CHP unit accessory • Vitobloc BACnet/IP Gateway
5671 5
14
09/2
012
5.2 Sensor assignment by type of CHP unit
Sensor
EM-18/36 / EM-20/39
EM-50/81
EM-70/115
EM-140/207
NiCrNi / A
Exhaust gas temperature Exhaust gas temperature
Exhaust gas temperature
Exhaust gas temperature
NiCrNi / B
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
NiCrNi / C
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
NiCrNi / D
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 1
Coolant
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
Heating water
PT 100 / 4
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 5
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 6
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Tab. 4 Sensor assignment overview
Sensor
EM-199/263
EM-199/293
EM-238/363
EM-363/498
NiCrNi / A
Exhaust gas upstream of turbo
Exhaust gas upstream
of turbo
Exhaust gas A
Exhaust gas upstream
of turbo A
NiCrNi / B
Exhaust gas downstream of turbo
Exhaust gas downstream
of turbo
Exhaust gas B
Exhaust gas upstream
of turbo B
NiCrNi / C
Exhaust gas downstream of cat.
Exhaust gas downstream
of cat.
Exhaust gas downstream
of cat.
Exhaust gas upstream
of cat.
NiCrNi / D
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Exhaust gas downstream of cat.
PT 100 / 1
Coolant
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
Heating water
PT 100 / 4
Engine oil temperature
Engine oil temperature
Engine oil temperature
Engine oil temperature
PT 100 / 5
Gas mixture temperature
Gas mixture temperature
- - - - - - - - - - - - - -
Gas mixture temperature
PT 100 / 6
Coolant mixture inlet
Coolant mixture inlet
- - - - - - - - - - - - - -
Coolant mixture inlet
Tab. 5 Sensor assignment overview
ESS Energie Systeme & Service GmbH Amendments a
BACnet / IP
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 17
5671 5
14-1
Sensor
EM-401/549
BM-36/66
BM-55/80
NiCrNi / A
Exhaust gas upstream of turbo A
Exhaust gas temperature
Exhaust gas temperature
NiCrNi / B
Exhaust gas upstream of turbo B
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
NiCrNi / C
Exhaust gas upstream of cat.
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
NiCrNi / D
Exhaust gas downstream of cat.
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 1
Coolant
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
Heating water
PT 100 / 4
Engine oil temperature
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 5
Gas mixture temperature
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 6
Coolant mixture inlet
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
Tab. 6 Sensor assignment overview
Sensor
BM-190/238
BM-366/437
NiCrNi / A
Exhaust gas upstream of turbo
Exhaust gas upstream of turbo A
NiCrNi / B
Exhaust gas downstream of turbo
Exhaust gas upstream of turbo B
NiCrNi / C
- - - - - - - - - - - - - -
Exhaust gas downstream of turbo
NiCrNi / D
- - - - - - - - - - - - - -
- - - - - - - - - - - - - -
PT 100 / 1
Coolant
Coolant
PT 100 / 2
Heating water return
Heating water return
PT 100 / 3
Heating water
Heating water
PT 100 / 4
Engine oil temperature
Engine oil temperature
PT 100 / 5
Gas mixture temperature
Gas mixture temperature
PT 100 / 6
Coolant mixture inlet
Coolant mixture inlet
Tab. 7 Sensor assignment overview
18 CHP unit accessory • Vitobloc BACnet/IP Gateway
Commissioning
5671 5
14
09/2
012
6 Commissioning
The device is commissioned as part of the general commissioning of the CHP plant or, in the case of retrofitting, by the CHP unit manufacturer's technical service personnel.
7 Maintenance
This accessory is maintenance-free.
8 Disposal
This product and its components must be disposed of in an environmentally responsible manner. Use public or private waste disposal companies.
ESS Energie Systeme & Service GmbH Amendments a
VITOBLOC 200 CHP unit accessory • Installation and operating instructions • BACnet/IP Gateway 19
Notes
5671 5
14
-1
! n e lt a h e b r o v n e g n u r e d n Ä e h c is n h c Te
5671 5
14-1
S
ubje
ct to
technic
al m
odific
atio
ns.
Viessmann Werke GmbH & Co KG D-35107 Allendorf Telephone +49 (0)6452 70-0 Fax: +49 (0)6452 70-2780 www.viessmann.de
20
Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Tel: +44 1952 675000 Fax: +44 1952 675040 E-mail: [email protected]