9
Building and Environment 43 (2008) 569–577 Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters Yoshiyuki Shimoda , Tomoji Nagota, Naoaki Isayama, Minoru Mizuno Division of Sustainable Energy and Environmental Engineering, Graduate School of Engineering, Osaka University, 2-1, Yamada-oka, Suita, Osaka 565-0871, Japan Received 30 November 2005; accepted 27 March 2006 Abstract This paper aims to verify the advantages of district heating and cooling (DHC) systems in terms of energy efficiency. From the measurement data, the parameters that characterize the energy efficiency of a heating/cooling plant are identified for DHC and an individual building. A simulation model that considers the difference in these parameters is developed. This model examines both the advantages and disadvantages of DHC systems and the effect of each parameter. The results show that the energy efficiency for cooling in DHC systems is superior to that in the case of individual cooling systems because of the ‘‘concentration effect’’ and ‘‘grade of operation’’. r 2006 Published by Elsevier Ltd. Keywords: District heating and cooling; Energy efficiency; Individual heating and cooling plant; Simulation; Concentration effect; Grade of operation 1. Introduction In Japan, district heating and cooling (DHC) has a 35- year history. DHC has many advantages such as high- energy efficiency, prevention of air pollution, intensive use of chillers and machinery space, and improvement in landscape because they do not require cooling towers and chimneys at rooftops. In particular, energy efficiency has gained attention in recent years due to mitigation measures against global warming. The energy efficiency characteristics of DHC are based on the following two factors: Factor I: Economies of scale such as intensive operation of chillers and other equipments, introduction of highly efficient equipment and efficient operation and mainte- nance by well-trained operators. Factor II: Use of an environmentally sound heat source available only for DHC, for example, waste heat from incinerators, combined heat and power, and river and sea water as heat sink/source of heat pump. Since the advantage of the factor II is evident, we focus on the effect of the factor I in this paper. Shimoda et al. [1] have surveyed the energy efficiency of most of the Japanese DHC systems in a business district. Fig. 1 shows a comparison of the measured energy efficiency ratio (EER) between DHC and a conventional heat source system in individual buildings. EER is defined as follows. EER ¼ Total amount of supplied heat ðGJ=yearÞ Total primary energy consumption ðGJ=yearÞ . (1) On an average basis, the effects of factors I and II are evident for ‘‘absorption chiller and boiler type’’ and ‘‘electric driven heat pump type’’, respectively. However, as shown in Fig. 2, the EER distribution of each DHC system exhibits a wide dispersion even in the same category. This indicates that the energy efficiency of the DHC plant is affected by various kinds of factors such as the heat loss from pipeline, part-load operation of chillers, pumps and fans as well as the efficiency of the equipment. It should be noted that the actual operations of chillers and other equipment are usually different from the ARTICLE IN PRESS www.elsevier.com/locate/buildenv 0360-1323/$ - see front matter r 2006 Published by Elsevier Ltd. doi:10.1016/j.buildenv.2006.03.017 Corresponding author. Tel./fax: +81 6 6879 7665. E-mail address: [email protected] (Y. Shimoda).

Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

Embed Size (px)

Citation preview

Page 1: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

0360-1323/$ - se

doi:10.1016/j.bu

�CorrespondE-mail addr

Building and Environment 43 (2008) 569–577

www.elsevier.com/locate/buildenv

Verification of energy efficiency of district heating and cooling system bysimulation considering design and operation parameters

Yoshiyuki Shimoda�, Tomoji Nagota, Naoaki Isayama, Minoru Mizuno

Division of Sustainable Energy and Environmental Engineering, Graduate School of Engineering, Osaka University, 2-1, Yamada-oka,

Suita, Osaka 565-0871, Japan

Received 30 November 2005; accepted 27 March 2006

Abstract

This paper aims to verify the advantages of district heating and cooling (DHC) systems in terms of energy efficiency. From the

measurement data, the parameters that characterize the energy efficiency of a heating/cooling plant are identified for DHC and an

individual building. A simulation model that considers the difference in these parameters is developed. This model examines both the

advantages and disadvantages of DHC systems and the effect of each parameter. The results show that the energy efficiency for cooling

in DHC systems is superior to that in the case of individual cooling systems because of the ‘‘concentration effect’’ and ‘‘grade of

operation’’.

r 2006 Published by Elsevier Ltd.

Keywords: District heating and cooling; Energy efficiency; Individual heating and cooling plant; Simulation; Concentration effect; Grade of operation

1. Introduction

In Japan, district heating and cooling (DHC) has a 35-year history. DHC has many advantages such as high-energy efficiency, prevention of air pollution, intensive useof chillers and machinery space, and improvement inlandscape because they do not require cooling towers andchimneys at rooftops. In particular, energy efficiency hasgained attention in recent years due to mitigation measuresagainst global warming.

The energy efficiency characteristics of DHC are basedon the following two factors:

Factor I: Economies of scale such as intensive operationof chillers and other equipments, introduction of highlyefficient equipment and efficient operation and mainte-nance by well-trained operators.

Factor II: Use of an environmentally sound heat sourceavailable only for DHC, for example, waste heat fromincinerators, combined heat and power, and river and seawater as heat sink/source of heat pump.

e front matter r 2006 Published by Elsevier Ltd.

ildenv.2006.03.017

ing author. Tel./fax: +81 6 6879 7665.

ess: [email protected] (Y. Shimoda).

Since the advantage of the factor II is evident, we focuson the effect of the factor I in this paper.Shimoda et al. [1] have surveyed the energy efficiency of

most of the Japanese DHC systems in a business district.Fig. 1 shows a comparison of the measured energyefficiency ratio (EER) between DHC and a conventionalheat source system in individual buildings. EER is definedas follows.

EER ¼Total amount of supplied heat ðGJ=yearÞ

Total primary energy consumption ðGJ=yearÞ.

(1)

On an average basis, the effects of factors I and II areevident for ‘‘absorption chiller and boiler type’’ and‘‘electric driven heat pump type’’, respectively. However,as shown in Fig. 2, the EER distribution of each DHCsystem exhibits a wide dispersion even in the samecategory. This indicates that the energy efficiency of theDHC plant is affected by various kinds of factors such asthe heat loss from pipeline, part-load operation of chillers,pumps and fans as well as the efficiency of the equipment.It should be noted that the actual operations of chillers

and other equipment are usually different from the

Page 2: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

0.54

0.608

0.68

0.615

0.849

0.991

0

Absorption chiller and boiler:

individual (12).

Absorption chiller and boiler:

DHC (23).

Absorption chiller and boiler: DHC

with CHP (14).

Electric heat pump: individual(9).

Electric heat pump: DHC(15).

Electric heat pump: DHC with

unused heat source (5).

EER

0.2 0.4 0.6 0.8 1 1.2

Fig. 1. Average EER of DHC and individual system [() ¼ number of

sample].

0.2

0.4

0.6

0.8

1.0

1.2

1,000 10,000 100,000 1,000,000 10,000,000

Floor area [m2]

EE

R

Absorption chiller and boiler: DHC(23).Absorption chiller and boiler: DHC with CHP(14).Electric heat pump: DHC(15).Electric heat pump: DHC with unused heat source(5).

Fig. 2. Distribution of EER in DHC.

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577570

operation planned during the design stage. For example, ina multiple chiller plant, the number of operational chillersis usually greater than that required to meet the heatdemand; consequently, since the load factor of the chillersdecreases, the energy consumption of the chillers and thatof pumps increases.

However, since the conventional simulation program ofthe DHC plant did not consider these discrepancies thatoccurred during actual operation, the simulated energyefficiency was usually higher than the measured values.Therefore, a simulation model that considers thesediscrepancies is necessary not only for verifying theadvantages of DHC but also for improving the controlsystem of chillers in the individual plants of the buildings,as described by Chow et al. [2], Chang et al. [3] andSpethmann [4].

In this paper, we first identify the parameters thatcharacterize the energy efficiency of the heating/coolingplant on the basis of the measurement data for DHC andindividual buildings. These parameters are the efficiency ofthe equipment and the grade of operation and main-

tenance. A simulation model that considers the differencein these parameters is developed and the advantages anddisadvantages of the DHC system are examined by usingthis model. Fig. 3 shows the flow diagram of this study.

2. Simulation model

2.1. Heating/cooling plant model

This study examines the plant consisting of absorptionchillers and boilers, which use city gas as the main energysource. In a DHC plant of this type, steam boilers anddouble-effect absorption chillers are employed. In theindividual building plant, direct-fired double-effect absorp-tion water chiller boilers are generally used. Fig. 4 showsthe system configuration of the DHC plant.An existing DHC plant in Japan (A-Plant) is modeled in

this study. This DHC area consists of 13 office andcommercial buildings. In the ‘‘DHC’’ case, the energyconsumption of the DHC plant is simulated by using totalheating/cooling load data including heat loss from thepipeline and internal use (heat produced by the A-Plant) asinput data. In the ‘‘individual heating/cooling’’ case, theenergy consumption of the heating/cooling plant in eachbuilding is simulated respectively by using heat load data(measured heat supplied to each building from the DHCplant) as input data. The simulated energy consumption ofthe 13 individual heating/cooling plants are summed andcompared with energy consumption in the DHC case.

2.2. Factors considered in the simulation

In order to precisely simulate the difference betweenDHC plant and individual building plants, the difference inthe following parameters is determined by means of themeasured data of nine DHC plants and 19 individualbuildings.

2.2.1. Heating and cooling load

In this simulation, cooling load data is supplied as themeasured flow rate of cold water and the measuredtemperature difference between the supply and returnwater in order to correctly simulate the chiller sequencecontrol.

2.2.2. Efficiency of chiller and boiler

The efficiency of the steam boiler used in the DHC plantis set at 0.820 on the primary energy basis. This valueincludes the power consumption of accessories in the boilersystem. Considering the economy of scale, the efficiency ofwater boiler used in each individual building plant is set as0.791.The coefficient of performance (COP) of the double-

effect absorption chiller used in the DHC plant is set as1.2[ ¼ (cold heat)/(steam)] at the rated condition. Changein the COP caused by part-load operation and the coolingwater temperature are modeled as shown in Figs. 5 and 6,

Page 3: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

Heating and cooling demand data of

existing DHC plant (A-Plant).

Heating and cooling

demand data of DHC plant

(Including heat loss).

Heating and cooling demand

data of each building in the

DHC area.

Parameters of DHC plant.

• Heat loss

• Efficiency of chiller and boiler

• Efficiency of pumps, etc.

• Multiple chiller control sequences

Parameters of Individual

plant.

• Capacity of chillers

• Efficiency of chiller and boiler

• Efficiency of pumps, etc.

• Multiple chiller control sequences

Seasonal energy efficiency

of DHC plant.

Seasonal energy efficiency

of Individual plant.

Comparison

Fig. 3. Flow of the study.

Gas Boiler

Supply Header

Return Header

P

AR

CWP

Cooling Tower

AR

PP

CWP

AR

CWP

SteamCity gas

AR: absorption chiller, P: cold water pump, CWP: cooling water pump

(Bypass)

Cold water

Buildings

Fig. 4. District heating and cooling plant.

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577 571

respectively. The cooling COP of the direct-fired double-effect absorption water chiller boiler is set as 1.0[ ¼ (coldheat)/(city gas)]. Changes in the COP are modeled as samecharacteristic as that adopted for the double-effectabsorption chiller in the DHC case.

2.2.3. Cooling capacity of the plant

In the individual building case, there are three chillers ineach building. The total capacity of the chillers is equal tothe product of the peak load and ‘‘safety factor’’ ( ¼ 1.2).Therefore, the load factor of the chiller never reaches 1.0even at the peak load. The capacities of the three chillers

are set in the ratio of 1:2:2. In the DHC case, the capacitiesof all the chillers are set as 4220 kW.

2.2.4. Power consumption of pumps, accessories and cooling

tower

By comparing the actual data obtained from DHCsystems and individual buildings, the power consumptionof the cooling water pump, cold water pump, accessories ofabsorption chillers and cooling tower are set as follows:The power consumption of the cooling water pump per

unit capacity of the chiller is set to the same value for DHCand the individual buildings.

Page 4: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

0

20

20 40 60 80 100

40

60

80

100

120

0

load factor [%]

CO

P c

ha

ng

e r

ate

[%

]

Fig. 5. COP variation by load factor.

0.0

0.2

0.4

0.6

0.8

1.0

Cold heat demand

Load

fa

cto

r o

f c

hill

er

2nd chiller

3rd chiller

Margin of load factor M

1st chiller

Fig. 7. Margin of load factor.

0

20

40

60

80

100

120

15 20 25

Cooling water temperature [°C]

CO

P c

hange r

atio [%

]

30 35

Fig. 6. COP variation by cooling water temperature. 0.0

0.2

0.4

0.6

0.8

1.0

0.0 0.2 0.4 0.6 0.8 1.0

Load factor of DHC plant

Avera

ge load facto

r of chill

ers

Fig. 8. Multiple chiller sequence in DHC plant.

0.0

0.2

0.4

0.6

0.8

1.0

0.0 0.2 0.4 0.6 0.8 1.0

Load factor of the plant

Ave

rag

e lo

ad

fa

cto

r o

f ch

ille

rs

Fig. 9. Multiple chiller sequence in individual plant.

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577572

The power consumption of the cold water pump per unitcapacity of the chiller in DHC is set to be larger than that in theindividual buildings since there is a pressure loss in the pipeline.

The power consumption of accessories of the absorptionchiller Pa is modeled as a function of the cooling capacityof the chiller, R (kW), as follows:

Pa ðkWÞ ¼ �1:05� 10�2Rþ 0:0276. (2)

The power consumption of the abovementioned ma-chines is set to a constant value during the operation of thechiller that they are connected.

The power consumption of the cooling tower per unitwaste heat from the chiller in DHC is set to be smaller thanthat in the individual building due to the economy of scale.

2.2.5. Multiple chiller control sequence

The chiller control sequence which determines thenumber of operational chillers is determined on the basisof the total heat load and flow rate of cold water as follows:

In order to respond to the sudden increase in the coolingload and avoid short-cycling of the chiller operation,

chillers are operated in a manner such that they have amargin of load factor as shown in Fig. 7. Johnson termedthis margin as ‘‘dead band’’ [5]. Owing to the difference inthe operator’s skill, the measured value of the margin M inDHC is lower than that in an individual plant, as shown inFigs. 8 and 9. The results of this survey also indicate that

Page 5: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

Table 1

Parameters used in the base case

DHC Individual plant

in the building

Safety factor of the chiller

capacity

— 120%

Cooling water pump (kW/kW

of chiller capacity)

0.038 0.038

Cold water pump (kW/kW of

chiller capacity)

0.021 0.015

Cooling tower (kW/kW of waste

heat)

0.0058 0.0078

Margin of load factor M 10% 30%

Minimum flow rate of bypass

pipe (% of the flow rate of

smallest chiller)

20% 50%

Energy efficiency of the boiler 0.820 0.791

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577 573

the chiller sequence was not controlled in two-thirds of theindividual cooling plants.

In addition, in order to respond to a sudden increase inthe flow rate of cold water, the flow rate in the bypass pipeshown in Fig. 4 should be larger than a certain value.Therefore, the total flow rate of chillers must be larger thanthe sum of the supplied flow rate and the minimum bypassflow rate (Fig. 10). If valuable water volume (VWV)control in the building always functions properly, arestriction in the cooling water volume has the same effectas the restriction in the cooling load. However, since thetemperature difference between the supply and returnwater becomes smaller with decreasing cooling load, asshown in the Fig. 11, an increased flow rate and morechillers are necessary to meet the heat demand. Therefore,both types of restrictions are necessary as described byShimoda et al. [6].

Table 1 lists the parameters used in the simulation.

AR1

AR2

AR3

AR4

AR5

AR6

AR7

AR8

AR9

AR10

AR11

00 400 900 1400 1900 2400 2900 3400 3900 4400 4900 5400

1,000

2,000

3,000

4,000

5,000

6,000

Total flow rate demand from the buildings [m3/h]

Dem

and +

bypass [m

3/h

]

Fig. 10. Chiller control sequence by flow rate.

0

1

2

3

4

5

6

7

8

0.0 0.2 0.4 0.6 0.8 1.0

Load factor of plant

Te

mp

era

ture

diffe

ren

ce

of

co

ld w

ate

r [°

C]

Fig. 11. Relationships between cooling load and temperature difference in

cold water in the A-Plant.

Table 2

Simulated annual primary energy consumption in the base case

DHC case

(GJ)

Individual

case (GJ)

Energy

conservation

ratio

Cooling

Chiller 216,476 203,940 �0.06

Accessories 7516 12,824 0.41

Cooling tower 6472 8899 0.27

Cooling water pump 41,881 68,212 0.39

Cold water pump 23,459 26,979 0.13

Sub-total 295,803 320,853 0.08

Heating

Boiler 117,173 89,790 �0.30

Accessories 1431 1057 �0.35

Sub-total 118,604 90,847 �0.31

Total

Total 414,407 411,700 �0.01

EER 0.69 0.69 —

3. Simulation results

3.1. Base case result

Table 2 lists the simulation result of the annual primaryenergy consumption in the DHC case and the individualheating/cooling case. The simulated EER of the DHC caseis 0.69, which is close to the simulated EER of 0.64measured at the A-Plant.This result indicates that the energy efficiency in the

DHC case is almost the same as that in the individual case.A summary of this result follows.

The COP of the chiller at the rated condition (loadfactor ¼ 100%, cooling water temperature ¼ 32 1C) ofthe DHC case is slightly smaller than that of theindividual case. In this rated condition, the conversionefficiency of gas to cold heat in the individual case is 1.0,
Page 6: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

0

4

8

12

16

20

1 3 5 7 9 11 13 15 17 19 21 23

Prim

ary

energ

y [G

J] Acc. (Ind)

CT (Ind)

CWP (Ind)

CP (Ind)

Acc. (DHC)

CT (DHC)

CWP (DHC)

CP (DHC)

Ind: Individual building plant DHC: DHC system Acc. Accessories of absorption chiller

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577574

while it is equal to 0.82 (boiler)� 1.2 (absorptionchiller) ¼ 0.984 in the DHC case. Additionally, sincethe COP of the absorption chiller is not affected by thepart-load ratio to a significant extent, as shown in Fig. 5,the energy consumption of the chiller itself is notaffected by parameters related to the operation. How-ever, since the energy consumption of accessories andpumps is in proportion with the operational hours of thechiller, their energy consumption becomes smaller in theDHC case. In total, the energy consumption for coolingin the DHC case is lower than that in the individualcooling case by 8%.

CT: Cooling tower

� CWP: Cooling water pump CP: Cold water pump

Fig. 13. Hourly change of energy consumption of pumps and other

machines.

0

500

1,000

1,500

2,000

2,500

3,000

3,500

4,000

4,500

5,000

1 5 9 13 2117

Hour

Excess c

apacity in the

Indiv

idual case [G

J/h

]

Concentration of cooling load

Operation effect

Fig. 14. Breakdown of the operation effect.

On the basis of the survey result of the DHC andindividual plants, the energy efficiencies of the boilerand its accessories does not vary with part load andfurther, these efficiencies are almost constant. Therefore,the difference in operation between the DHC andindividual plants does not affect the amount of energyconsumption for heating. On the other hand, there is alarge amount of heat loss in the DHC plant. Since thereis a small heating demand in the A-Plant, i.e., theheating demand is one-third of the cooling demand, theratio of the heat loss to heating demand reaches 35%.Therefore, the total energy consumption of the DHCcase does not show the advantage over that in theindividual case.

3.2. Effect of operation on cooling energy efficiency

As mentioned previously, the energy consumption forcooling in the DHC case is lower than that in the individualcase by 8%. Fig. 12 shows the hourly change in the totalcapacity of operational chillers and their average part-loadfactor on 15th June. This figure shows that the part-loadfactor of chillers in the DHC plant is maintained higherthan that in the individual plant by 60–100% all through-out the day. This fact brings about the difference in theenergy consumption of the pumps and that of accessories,as shown in Fig. 13.

By comparing this result with the optional simulationresult of the individual case in which the parameters‘‘margin of load factor’’ and ‘‘minimum flow rate of bypasspipe’’ are set to the same values as in the DHC case, the

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1 3 5 7 9 11 13 15 17 19 21 23

load facto

r

0

2,000

4,000

6,000

8,000

10,000

12,000

14,000

Tota

l capacity o

f chill

ers

[R

T]

Individual (total capacity)

DHC (total capacity)

Individual (load factor)

DHC (load factor)

Fig. 12. Hourly change of chiller sequence on 15th June.

effect of operation on the total energy efficiency can beevaluated as shown in the Fig. 14. This result demonstratesthat 32% of the reduction in the total operating chillercapacity is due to the difference in operation. The reminderis due to the concentration of the cooling load in one DHCplant. In particular, at midnight, at least one chiller mustbe operated at a very small cooling load in each building inthe individual cooling case, whereas in the DHC case,cooling loads are concentrated into the DHC plant andhandled by one or a few chillers.

3.3. Factorial experiment

In order to clarify the effect of each factor on the totalenergy efficiency, optional simulations as shown in Table 3are performed.

(a)

The difference between RUN-0 and RUN-1 indicatesthe ‘‘concentration effect’’, which refers to the con-centration of the heat load of multiple buildings in one
Page 7: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

Table 3

Details of the optional simulation for the factorial experiment

RUN-0 (base case of

individual plant)

RUN-1 RUN-2 RUN-3 RUN-4

(base case of DHC)

Modela Individual DHC DHC DHC DHC

Chiller and boiler Direct-fired double-

effect absorption

water chiller boiler

Direct-fired double-

effect absorption

water chiller boiler

Direct-fired double-

effect absorption

water chiller boiler

Double-effect

absorption chiller and

steam boiler

Double-effect

absorption chiller and

steam boiler

Heat loss Not included Not included Included Included Included

Cold water pump

(kW/kW of chiller

capacity)

0.015 0.015 0.021 0.021 0.021

Cooling tower (kW/

kW of waste heat)

0.0078 0.0078 0.078 0.058 0.058

Margin of load factor

M

20% 20% 20% 20% 10%

Minimum flow rate of

bypass pipe (% of the

flow rate of smallest

chiller)

50% 50% 50% 50% 20%

aDHC model: simulation of the one plant that handles total heating/cooling load for all of the building. Individual model: Simulation of 13 plants that

handle each building’s load individually.

30,000

40,000

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577 575

plant. This effect is peculiar to district heating andcooling systems.

20,000

(b)

0

10,000

vin

g [G

J]

The difference between RUN-1 and RUN-2 indicatesthe ‘‘heat transportation loss’’, which includes the heatloss from the pipeline and the additional powerconsumption of the cold water pump.

-10,000

Sa

(c)

-40,000

-30,000

-20,000

Energ

y

The difference between RUN-2 and RUN-3 indi-cates the ‘‘economy of scale’’ of the DHC systemsplant. This includes the difference in the efficiency ofmachine.

-50,000

(d)

-60,000

The difference between RUN-3 and RUN4 indicatesthe difference in the ‘‘grade of operation’’.

Co

nce

ntr

atio

n e

ffe

ct

Heat tr

ansport

ation loss

Econom

y o

f scale

gra

de o

f opera

tion

Fig. 15. Effects of the factors on cooling.

Figs. 15–17 exhibit the effects of these differences oncooling, heating and total energy consumption, respec-tively. The results indicate that the concentration effect isthe most prominent advantage of the DHC system. In thecase of cooling, the grade of operation also has a largeeffect.

3.4. The effect of the other potential parameters

From the base case result, it can be seen that theenergy efficiency of the DHC system is almost the sameas that in the case of the individual heating and cooling.However, the average EER measured in the DHC systemis higher than that measured in the individual heatingand cooling plant, as shown in Fig. 1. One of the reasonsfor this is the existence of other factors which affectthe difference in the energy efficiency. In addition,there is a possibility of reducing the heat loss, whichis the main reason that the energy efficiency of thedistrict heating is inferior to that of the individual heatingplant.

In this part, the effects of the other factors, which werenot observed in our analysis of measurement data, arediscussed.

3.4.1. Allocation of cooling capacity to chillers in the

individual cooling plant

In the well-designed cooling plant employed in the indi-vidual building, cooling capacities of chillers are allocatedunevenly to ensure efficient operation at a small load asbase case of this study. However, this differentiation in

Page 8: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

-60,000

-50,000

-40,000

-30,000

-20,000

-10,000

0

10,000

20,000

30,000

40,000

Concentr

ation e

ffect

Heat tr

ansport

ation loss

Econom

y o

f scale

gra

de o

f opera

tion

Energ

y S

avin

g [G

J]

Fig. 16. Effects of the factors on heating.

-60,000

-50,000

-40,000

-30,000

-20,000

-10,000

0

10,000

20,000

30,000

40,000

Concentr

ation e

ffect

Heat tr

ansport

ation loss

Econom

y o

f scale

gra

de o

f opera

tion

Energ

y s

avin

g [G

J]

Fig. 17. Effects of the factors on total heat supply.

0

20

20 0 60 80 100

40

60

80

100

120

0

Load factor [%]

CO

P c

ha

ng

e r

atio

[%

]

Fig. 18. Relationships between the COP and load factor [7].

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577576

cooling capacity is not common in most of the individualbuildings. The case wherein the cooling capacity isallocated as 1:1:1 is simulated (RUN-A).

3.4.2. Decrease in COP of absorption chiller at low load

factor

In the base case, the COP of the chiller when the loadfactor is less than 20% is considered to be the same as theCOP at a load factor of 20%. However, Takahashi et al. [7]pointed out that the COP, when the load factor is less than20% is lower, as shown in Fig. 18, since a large energy loss

occurs due to the repeated on and off operations of thechiller. Therefore, the case wherein the relationshipbetween the load factor and COP is modeled as shown inFig. 18 is also simulated (RUN-B).

3.4.3. Difference in the degree of maintenance

In this study, the degradation in the energy efficiencies ofthe chiller and boiler is not considered. However, ingeneral, the degree of maintenance in the DHC plant ishigher than that in the individual buildings. Therefore, thecase wherein the chiller’s COP of the individual plantdecreases by 20% and the efficiency of the water boiler inthe individual plant also decreases by 10% as a result ofaged deterioration is simulated (RUN-C).

3.4.4. Capacity of first order chiller

As well as the individual building plant, capacity of thechiller which works in small cooling load hours may affectthe energy efficiency of the DHC system. Therefore, thecapacity of the chiller which is operated first in the chillersequence (‘‘AR1’’ in the Fig. 10) is reduced to the half ofthe other chillers ( ¼ 2110 kW). This small chiller is set tobe operated only in the case that the cooling load is smalland the other chillers are not operated. Energy consump-tion of pumps and minimum bypass flow rate of the chillerare also reduced (RUN-D).

3.4.5. Improvement in the heat loss ratio of the DHC plant

In the A-Plant, the heat loss in heating reaches 35% ofthe heating demand. In addition to the low heat demand(denominator of heat loss ratio) in the A-Plant, the totalheat loss in heating is 23,555GJ/yr, which is considerablygreater than the ideal value of 2619GJ/yr; this ideal valueis calculated from the standard size of the pipe andinsulation in the A-Plant. Therefore, the case wherein theheat loss reduces to this ideal value is simulated (RUN-E).Furthermore, the case wherein the total heat demand is

increases to 300% of the present amount and accordingly

Page 9: Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters

ARTICLE IN PRESS

Table 4

Results of simulation with the additional parameters

RUN Energy consumption (GJ) EER

Cooling Heating Total

Individual (base case) 320,853 90,847 411,700 0.69

Individual (RUN-A) 324,449 90,847 415,295 0.69

Individual (RUN-B) 329,861 90,847 420,708 0.68

Individual (RUN-C) 366,419 102,617 469,036 0.61

DHC (base case) 295,803 118,604 414,407 0.69

DHC (RUN-D) 291,172 118,604 409,776 0.70

DHC (RUN-E) 296,959 90,795 387,754 0.74

Individual (RUN-F) 320,853 272,541 593,394 0.72

DHC (RUN-F) 295,803 293,806 589,609 0.73

Since heat load of RUN-F is different from other case, energy

consumption in RUN-F is not comparable with other case.

Y. Shimoda et al. / Building and Environment 43 (2008) 569–577 577

the heat loss ratio decreases to 12% is also simulated(RUN-F).

The results of these simulations are presented in Table 4.These results show that the advantage of DHC becomesevident when one of the parameters is considered,especially the difference in the degree of maintenance orthe improvement in the heat loss. If the heating demandbecomes almost the same as the cooling load, the EER ofthe DHC plant exceeds that of the individual plant.

4. Conclusion

In this study, the energy efficiency of the district heatingand cooling plant is examined. The results of this study areas follows:

The advantage of district cooling is verified quantita-tively by simulation using realistic parameters obtainedfrom the measurement data. The reasons for advantagesare categorized as the concentration effect, grade of thechillers and pumps, and grade of operation. The effectsof these factors are quantified by simulations. � Furthermore, the result also indicates the importance of

improving the operation of the individual cooling plant,such as the chiller sequence by Building EnergyManagement Systems (BEMS). The introduction ofthe valuable speed pump can alleviate the disadvantagescaused by the concentration effect of the DHC plant.

The magnitude of the effect of each factor depends onthe cooling and heating load profile of the DHC plant.The fact that the concentration effect is the largestamong the factors suggests that the number of thebuildings is also an important factor. Therefore, it isnecessary to conduct sensitivity analysis on the loadprofile and the scale of the DHC system by thissimulation model in order to determine the ideal loadprofile and scale for obtaining the maximum energyefficiency. � In the DHC plant, improvement in the heat loss is

important for energy efficiency.

� Due to insufficient data, it is very difficult to define

‘‘standard’’ parameters for individual heating and cool-ing plants. Therefore, further field survey is necessary.

Acknowledgements

This work is as a cooperative research with the JapanHeat Service Utilities Association. The authors wish tothank the members of Special Committee on the Evalua-tion Method for Energy Efficiency of District Heating andCooling, Society of Heating, Air-conditioning and SanitaryEngineers of Japan (SHASE) for their valuable advice.

References

[1] Shimoda Y, Sadohara S, Fukushima T. Survey Research of Energy

Conservation and CO2 Reduction of District Heating and Cooling,

Summaries of Technical Papers of Annual Meeting, Architectural

Institute of Japan, 2003;D-1:531–38 (In Japanese).

[2] Chow TT, Zhang GQ, Lin Z, Song CL. Global optimization of

absorption chiller system by genetic algorithm and neural network.

Energy and Buildings 2002;34:103–9.

[3] Chang YC, Lin JK, Chuang MH. Optimal chiller loading by genetic

algorithm for reducing energy consumption. Energy and Buildings

2005;37:147–55.

[4] Spethmann DH. Optimized control of multiple chillers. ASHRAE

Transactions 1985;91(2):848–56.

[5] Johnson GA. Optimization techniques for a centrifugal chiller plant

using a programmable controller. ASHRAE Transactions 1985;91(2):

835–47.

[6] Shimoda Y, Mizuno M, Kametani S, Kawamura S. Evaluation of

distribution system performance in district heating and cooling system.

In: Proceedings of sixth international IBPSA conference, 1999.

p. 839–46.

[7] Takahashi J, Kobayashi H, Kondo M, Oka T. Analysis on the co-

efficient of performance of a hybrid energy source system with thermal

storage. Transactions of SHASE 1999;74:91–100 [in Japanese].