11
Example Digit 0 =0° that the LV phasor is in phase with the HV phasor Digit 1 =30° lagging (LV lags HV with 30°) because rotation is anti-clockwise. Digit 11 = 330° lagging or 30° leading (LV leads HV with 30°) Digit 5 = 150° lagging (LV lags HV with 150°) Digit 6 = 180° lagging (LV lags HV with 180°) Six Ways to wire Star Winding :

Vector Group

Embed Size (px)

DESCRIPTION

Transformer Vector Group

Citation preview

Page 1: Vector Group

Example

Digit 0 =0° that the LV phasor is in phase with the HV phasor

Digit 1 =30° lagging (LV lags HV with 30°) because rotation is anti-clockwise.

Digit 11 = 330° lagging or 30° leading (LV leads HV with 30°)

Digit 5 = 150° lagging (LV lags HV with 150°)

Digit 6 = 180° lagging (LV lags HV with 180°)

Six Ways to wire  Star Winding :

Page 2: Vector Group

Six Ways to wire Delta Winding :

Page 3: Vector Group
Page 4: Vector Group

Vector Group Test of Power Transformer

http://www.electrical4u.com/vector-group-test-of-power-transformer/

The vector group of transformer is an essential property for successful parallel operation of transformers. Hence everyelectrical power transformer must undergo through vector group test of transformer at factory site for ensuring the customer specified vector group of transformer.

The phase sequence or the order in which the phases reach their maximum positive voltages, must be identical for two paralleled transformers. Otherwise, during the cycle, each pair of phases will be short circuited.

The several secondary connections are available in respect of various primary three phase connection in a the three phase transformer. So for same primary applied three phase voltage there may be different three phase secondary voltages with various magnitudes and phases for different internal connection of the transformer.Let's have a discussion in detail by example for better understanding.We know that, the primary and secondary coils on any one limb have induced emfs that are in time - phase. Let's consider two transformers of same number primary turns and the primary windings are connected in star. The secondary number of turns per phase in both transformers are also same. But the first transformer has star connected secondary and other transformer has delta connected secondary. If same voltages are applied in primary of both transformers, the secondary induced emf in each phase will be in same time-phase with that of respective primary phase, as because the the primary and secondary coils of same phase are wound on the same limb in the core of transformer. In first transformer, as the secondary is star connected, the secondary line voltage is √3 times of induced voltage per secondary phase coil. But in case of second transformer, where secondary is delta connected, the line voltage is equal to induced voltage per secondary phase coil. If we go through the vector diagram of secondary line voltages of both transformer, we will easily find that there will be a clear 30o angular difference between the line voltages of these transformers. Now, if we try to run these transformers in parallel then there will be a circulating current flows between the transformers as because there is a phase angle difference between their secondary line

Page 5: Vector Group

voltages. This phase difference can not be compensated. Thus two sets of connections giving secondary voltages with a phase displacement can not be intended for parallel operation of transformers.The following table gives the connections for which from the view point of phase sequence and angular divergences, transformer can be operated parallel. According to their vector relation, all three phase transformers are divided into different vector group of transformer. All electrical power transformers of a particular vector group can easily be operated in parallel if they fulfill other condition for parallel operation of transformers.GROUP CONNECTION CONNECTION

0

(0O)

YY0 DD0

1 YD1 DY1

Page 6: Vector Group

( 30O)

6

( 180O)YY6 DD6

Page 7: Vector Group

11

( - 30O)YD11 DY11

Page 8: Vector Group

Procedure of vector group test of transformer

Let’s have a YNd11 transformer.1) Connect neutral point of star connected winding with earth.

2) Join 1U of HV and 2W of LV together.3) Apply 415V, three phase supply to HV terminals. 

Page 9: Vector Group

4) Measure voltages between terminals 2U – 1N, 2V – 1N, 2W – 1N, that means voltages between each LV terminal and HV neutral. 5) Also measure voltages between terminals 2V – 1V, 2W – 1W and 2V – 1W.For YNd11 transformer, we will find, 2U – 1N > 2V – 1N > 2W – 1N

2V – 1W > 2V – 1V or 2W – 1WThe vector group test of transformer for other group can also be done in similar way.

Page 10: Vector Group