©John Roberts DESIGN EXAMPLE V1 Design vertical load = 180 kN/m with no applied eccentricity of loading Find the characteristic strength (f k ) of masonry made from Group 1 clay brick masonry units of standard format size (width 102.5mm) with a normalised compressive strength (f b ) of 42,5 N/mm 2 . The attestation of conformity (manufacturing control) is Category II and the masonry will be constructed using an M4 general purpose mortar using Class 2 execution control. Check that the load capacity of such a wall is sufficient to withstand the loading applied. Recalculate the above using Group 1 concrete block masonry units with a normalised compressive strength (f b ) of 20 N/mm 2 . The masonry units are 140mm in thickness. Ignore the self weight of the wall. 3000mm End conditions Wall part of 4 storey building

V1 Design Ex

Embed Size (px)

DESCRIPTION

Masonry Wall _V1

Citation preview

  • John Roberts

    DESIGN EXAMPLE V1

    Design vertical load = 180 kN/m with no applied eccentricity of loading Find the characteristic strength (fk) of masonry made from Group 1 clay brick masonry units of standard format size (width 102.5mm) with a normalised compressive strength (fb) of 42,5 N/mm

    2. The attestation of conformity (manufacturing control) is Category II and the masonry will be constructed using an M4 general purpose mortar using Class 2 execution control. Check that the load capacity of such a wall is sufficient to withstand the loading applied. Recalculate the above using Group 1 concrete block masonry units with a normalised compressive strength (fb) of 20 N/mm

    2. The masonry units are 140mm in thickness. Ignore the self weight of the wall.

    3000mm End conditions

    Wall part of 4 storey

    building