    Publication1734-IN002C-EN-E - Apri l 2005

    Installation Instructions

    POINT I/O 2 Current Output and 2 VoltageOutput Analog Modules

    Catalog Numbers 1734-OE2C and 1734-OE2V, Series C

    Inside

    For This Topic See Page

    Important User Informat ion 2

    Prevent ing Electrostat ic Discharge 3

    Environment and Enclosure 4

    Before You Begin 5

    Ident ify M odule Components 5

    Install the M ount ing Base 6

    Install the M odule 7

    Install the Removable Terminal Block (RTB) 8

    Remove a M ount ing Base 9

    Communicate w ith Your M odule 11

    W ire the M odule 12

    Troubleshoot w ith Indicators 15

    Nort h Am erican Hazardous Location A pproval 18

    European Hazardous Locati on Approval 19

    Specifications 20

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    2/24

    2 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Important User Information

    Solid state equipment has operational characteristics differing from those ofelectromechanical equipment. Safety Guidelines for the Appl ication, Install ation andM aintenance of Solid State Controls(Publicatio n SGI-1.1 availabl e f rom your l ocal Rockw ellAutomation sales off ice or online at http:// l i terature.rockw ellautomation.com) describessome important diff erences betw een solid state equipment and hard-w iredelectromechanical devices. Because of t his diff erence, and also because of t he w ide varietyof uses for solid state equipmen t, all persons responsible for applying thi s equipment mustsatisfy themselves that each intended application of this equipment is acceptable.

    In no event w ill Rockw ell Aut omati on, Inc. be responsible or liable for indirect or

    consequential damages resulting f rom the use or application of this equipment .The examples and diagrams in t his manual are included solely for i llustrat ive purposes.Because of the many variables and requirements associated w ith any particular installat ion,Rockw ell Aut omati on, Inc. cannot assume responsibilit y or liability f or actual use based onthe examples and diagrams.

    No patent l iabil i t y is assumed by Rockw ell Aut omation, Inc. w ith respect to use ofinformation, circuits, equipment, or software described in this manual.

    Reproduction of t he contents of this manual, in w hole or in part, w ithout w ritten permission

    of Rockw ell Aut omati on, Inc., is prohibited.Throughout t his manual, w hen necessary, w e use notes to make you aware of safetyconsiderations.

    WARNING Identifies information about practices or circumstances that can cause an explosion in ahazardous environment, w hich may lead to personal injury or death, property damage, oreconomic loss.

    IMPORTANTIdentifi es information t hat is critical for successful application and understanding of t heproduct.

    ATTENTION Identif ies informat ion about practices or circumstances that can lead to personal injury ordeath, property damage, or economic loss. Attentions help you:

    identi fy a hazard avoid a hazard recognize t he consequence

    SHOCK HAZARD Labels may be located on or inside t he equipment (e.g., drive or motor) to alert peopl ethat dangerous voltage may be present.

    BURN HAZARD Labels may be located on or inside t he equipment (e.g., drive or motor) to alert peopl ethat surfaces may be dangerous temperatures.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    3/24

    POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 3

    Publication 1734-IN 002C-EN-E - Apr il 2005

    ATTENTION Preventing Electrostatic DischargeThis equipm ent is sensitive to electrostatic

    discharge, w hich can cause internal dam age and

    affect norm al operation. Follow these guidelines

    w hen you handle this equipm ent:

    Touch a grounded object to discharge

    potential static.

    W ear an approved grounding w riststrap. D o not touch connectors or pins on

    com ponent boards.

    D o not touch circuit com ponents inside the

    equipm ent.

    If available, use a static-safe w orkstation.

    W hen not in use, store the equipm ent in

    appropriate static-safe packaging.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    4/24

    4 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    ATTENTION Environment and Enclosure

    This equipm ent is intended for use in a Pollution

    D egree 2 industrial environm ent, in overvoltage

    Category II applications (as defined in IEC

    publication 60664-1), at altitudes up to 2000 m eters

    w ithout derating.

    This equipm ent is considered G roup 1, Class A

    industrial equipm ent according to IEC/CISPR

    Publication 11. W ithout appropriate precautions,

    there m ay be potential difficulties ensuringelectrom agnetic com patibility in other environm ents

    due to conducted as w ell as radiated disturbance.

    This equipm ent is supplied as open type

    equipm ent. It m ust be m ounted w ithin an enclosure

    that is suitably designed for those specific

    environm ental conditions that w ill be present and

    appropriately designed to prevent personal injuryresulting from accessibility to live parts. The interior

    of the enclosure m ust be accessible only by the use

    of a tool. Subsequent sections of this publication

    m ay contain additional inform ation regarding

    specific enclosure type ratings that are required to

    com ply w ith certain product safety certifications.

    See N EM A Standards publication 250 and IEC

    publication 60529, as applicable, for explanations of

    the degrees of protection provided by different

    types of enclosure. Also, see the appropriate

    sections in this publication, as w ell as the

    Allen-Bradley publication 1770-4.1 (Industrial

    Autom ation W iring and G rounding G uidelines), for

    additional installation requirem ents pertaining to

    this equipm ent.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    5/24

    POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 5

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Before You Begin

    You can use these Series C m odules w ith D eviceN et and PRO FIBU S

    adapters. If you are using RSLogix 5000 softw are, version 11 orhigher, you can also use the Series C m odules w ith ControlN et and

    Ethernet adapters.

    Identify Module Components

    U se the figure to identify the external features of the m odules.

    Analog

    Volta

    ge

    Outp

    ut

    Mod

    ule

    Status

    Netw

    ork

    Status

    NOD

    E:

    0

    1

    The w iring base assembly includes t erminal base, 1734-TB or 1734-TBS,

    43931

    Interlocking

    Side Pieces

    DIN Rail

    Locking

    Screw

    (orange) Removable Terminal Block (RTB)

    Slide-in W ritable Label

    Insertable I/O M odule

    Module

    WiringDiagram

    M ounting Base

    RTB Removab le Handle

    Module

    Locking

    Mechanism

    Mechanical

    Keying(orange)

    w hich consists of mounting base, 1734-M B, and removable terminal block,1734-RTB or 1734-RTBS.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    6/24

    6 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Install the Mounting Base

    To install the m ounting base on the D IN rail, proceed as follow s.

    1. Position the m ounting base vertically above the installed units

    (adapter, pow er supply, or existing m odule).

    2. Slide the m ounting base dow n to m ake the interlocking side

    pieces engage the adjacent m odule or adapter.

    3. Press firm ly to seat the m ounting base on the D IN rail.

    The m ounting base w ill snap into place.

    ATTENTION PO IN T I/O is grounded through the D IN rail to

    chassis ground. U se zinc-plated, yellow -chrom ated

    steel D IN rail to assure proper grounding. The use

    of D IN rail m aterials (e.g., alum inum , plastic, etc.)

    that can corrode, oxidize, or are poor conductors

    can result in im proper or interm ittent grounding.

    Secure D IN rail to m ounting surface approxim atelyevery 200 m m .

    ATTENTION D o not discard the end cap supplied w ith an

    adapter or com m unication interface m odule.

    U se this end cap to cover the exposed

    interconnections on the last m ounting base on theD IN rail. Failure to do so could result in

    equipm ent dam age or injury from electric shock.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    7/24

    POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 7

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Install the Module

    Install the m odule before or after base installation. M ake sure that

    you:

    correctly keyed the m ounting base before installing the

    m odule into the m ounting base

    positioned the m ounting base locking screw horizontal w ithreference to the base

    To install the m odule proceed as follow s.

    1. U sing a bladed screw driver, rotate the keysw itch on the

    m ounting base clockw ise until the num ber required for the

    type of m odule you are installing aligns w ith the notch in the

    base.

    2. M ake certain the D IN rail locking screw is in the horizontal

    position.

    You cannot insert the m odule if you have unlocked the

    locking m echanism .

    3. Insert the m odule straight dow n into the m ounting base andpress to secure.

    The m odule w ill lock into place.

    WARNING W hen you insert or rem ove the m odule w hilebackplane pow er is on, an electrical arc can occur.

    This could cause an explosion in hazardous

    location installations.

    Be sure that pow er is rem oved or the area is

    nonhazardous before proceeding. Repeated

    electrical arcing causes excessive w ear to contacts

    on both the m odule and its m ating connector. W orn

    contacts m ay create electrical resistance that can

    affect m odule operation.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    8/24

    8 POINT I/ O 2 Current Output and 2 Voltage Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Install the Removable Terminal Block (RTB)

    A rem ovable term inal block com es w ith your w iring base assem bly.

    To rem ove, pull up on the RTB handle. You can now rem ove them ounting base and replace as necessary w ithout rem oving any of the

    w iring. To reinsert the rem ovable term inal block, proceed as follow s.

    1. Insert the end opposite the handle into the base unit.

    This end has a curved section that engages w ith the w iring

    base.

    2. Rotate the term inal block into the w iring base until it locks

    itself in place.

    3. If an I/O m odule is installed, snap th e RTB handle into place

    on the m odule.

    WARNING W hen you connect or disconnect the rem ovable

    term inal block (RTB) w ith field-side pow er

    applied, an electrical arc can occur. This could

    cause an explosion in hazardous location

    installations.

    Be sure that pow er is rem oved or the area is

    nonhazardous before proceeding.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    9/24

    POINT I/ O 2 Current Output and 2 Voltage Output A nalog M odules 9

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Remove a Mounting Base

    To rem ove a m ounting base, you m ust rem ove any installed m odule,

    and the m odule installed in the base to the right. Rem ove therem ovable term inal block, if w ired.

    1. U nlatch the RTB handle on the I/O m odule.

    2. Pull on the RTB handle to rem ove the rem ovable term inal

    block.

    3. Press on the m odule lock on the top of the m odule.

    4. Pull on the I/O m odule to rem ove from the base.

    WARNING W hen you connect or disconnect the rem ovable

    term inal block (RTB) w ith field-side pow er

    applied, an electrical arc can occur. This could

    cause an explosion in hazardous location

    installations.

    Be sure that pow er is rem oved or the area is

    nonhazardous before proceeding.

    WARNINGW hen you insert or rem ove the m odule w hile

    backplane pow er is on, an electrical arc can occur.

    This could cause an explosion in hazardous

    location installations.

    Be sure that pow er is rem oved or the area is

    nonhazardous before proceeding. Repeated

    electrical arcing causes excessive w ear to contacts

    on both the m odule and its m ating connector. W orn

    contacts m ay create electrical resistance that canaffect m odule operation.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    10/24

    10 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    5. Repeat steps 1, 2, 3, and 4 for the m odule to the right.

    6. U se a sm all-bladed screw driver to rotate the orange, baselocking screw to a vertical position.

    This releases the locking m echanism .

    7. Lift straight up to rem ove.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    11/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 11

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Communicate with Your Module

    PO IN T I/O m odules send (consum e) and receive (produce) I/O

    m essages. You m ap these m essages into the processors m em ory.

    These m odules produce 2 bytes of input data (scanner Rx) (fault

    status). These m odules consum e 4 bytes of output data (scanner Tx).

    Message size: 2 Bytes

    15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

    Produces

    (scanner Rx)

    High Byte - Channel 1 St atus Low Byte - Channel 0 Stat us

    Not used H

    C

    A

    L

    C

    A

    C

    M

    C

    F

    Not used H

    C

    A

    L

    C

    A

    C

    M

    C

    F

    Where:

    CF = Channel Fault st atus; 0 = no error, 1 = faultCM = Calibrati on M ode; 0 = normal, 1 = calibration mode

    HCA = High Clamp A larm ; 0 = no error, 1 = fault

    LCA = Low Clam p Alarm ; 0 = no error, 1 = fault

    Message size: 4 bytes

    15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

    Consumes

    (scanner Tx)

    Output Channel 0 High Byte Output Channel 0 Low Byte

    Output Channel 1 High Byte Output Channel 1 Low Byte

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    12/24

    12 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Wire the Module

    WARNING If you connect or disconnect w iring w hile the

    field-side pow er is on, an electrical arc can occur.

    This could cause an explosion in hazardous

    location installations. Be sure that pow er is

    rem oved or the area is nonhazardous before

    proceeding.

    1734

    OE2C

    NODE:

    0

    1

    43962

    1734-OE2C POINT I/O 2 Current Output Analog Module

    M odule Status

    Network Status

    Status of Output 0Status of Output 1

    Output 0 Connection 0 1 Output 1 Connection

    5 CChas Gnd = Chassis Ground

    C = Common

    V = Supply

    3 Chas GndChas Gnd 2

    C 4

    V 6 7 V

    Module

    Status

    Network

    Status

    4-20mA

    Analog

    Output

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    13/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 13

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Channel CurrentOutput

    ChassisGround

    Common Supply

    0 0 2 4 6

    1 1 3 5 7

    12/ 24V dc pow er is provided by the internal f ield pow er bus.

    CurrentOutputDevice

    CurrentOutputDevice

    2-wire4-wire

    ac or dc

    43964

    Out = Output Channel

    Chas Gnd = Chassis Ground

    C= Common

    V = 12/ 24V dc supply

    0 1

    32

    Out0

    Out1

    ChasGnd

    ChasGnd

    54C C

    76

    VV

    1734-OE2C POINT I/O 2 Current Output Analog Module

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    14/24

    14 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    43963

    M odule Status

    Netw ork Status

    Status of Output 0

    Status of Output 1

    Output 0 Connection 0

    Chas Gnd 2

    C 4

    V 6

    5 C

    7 V

    Chas Gnd = Chassis g roundC = Comm onV = Supply

    1734-OE2V POINT I/O 2 Voltage Output Analog Module

    3 Chas Gnd

    1734

    OE2V

    NODE:

    0

    1

    1 Output 1 Connection

    Module

    Status

    Network

    Status

    Analog

    Voltage

    Output

    Out 0 Out 1

    ChasGndChasGnd

    C C

    VV

    VoltageOutput

    43965

    3

    5

    7

    0 1

    2

    4

    6

    VoltageOutput

    1734-OE2V POINT I/O 2 Voltage Output Analog Module

    Out = Output channelChas Gnd = Chassis GroundC = CommonV = 12/24V dc supply

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    15/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 15

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Troubleshoot with Indicators

    U se the status indicators and tables to troubleshoot your m odule.

    Channel Voltage Output Chassis Ground Common Supply0 0 2 4 6

    1 1 3 5 7

    12/24V dc pow er is provided by the internal f ield pow er bus.

    M odule Status

    Netw ork Status

    1734-OE2C

    POINT I/O 2 Current

    Output Analog Module

    NODE:

    0

    1

    43962

    ModuleStatus

    NetworkStatus

    4-20mAAnalogOutput

    Status of Output 0

    Status of Output 1

    1734-OE2V

    POINT I/O 2 Voltage

    Output Analog Module

    M odule Status

    Netw ork Status

    NODE:

    0

    143963

    ModuleStatus

    Network

    Status

    AnalogVoltageOutput

    Status of Output 0

    Status of Output 1

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    16/24

    16 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Indication Probable CauseModule Status

    Off No pow er is appl ied to device.

    Green Device is operat ing normal ly.

    Flash ing Green Device needs commission ing due to conf igura t ion missing,

    incomplet e, or incorrect.

    Flashing Red Recoverable fault is present .Red Unrecoverable fault may require device replacement .

    Flashing Red/ Green Device is in sel f -test .

    Indication Probable Cause

    Network StatusOff Device is not online.

    - Device has not completed dup_M AC_id test.

    - Device not pow ered. Check module stat us indicator.

    Flash ing Green Device i s onl ine but has no connect ions in the establ ished sta te .

    Green Device is online and has connect ions in the establ ished state.

    Fl ashi ng Re d One or m ore I/ O conne ct ions are i n t im ed-out st at e

    Red Crit ical l ink failure is present w ith failed communicat ion device.

    Device detected error that prevents it communicat ing on the

    network.

    Flashing

    Red/Green

    Communi cation faul ted device is present.

    The device detected a net w ork access error and is in communicati on

    faulted state.

    Device received and accepted an Identif y Communicat ion Faulted

    Request - l ong protocol m essage.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    17/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 17

    Publication 1734-IN 002C-EN-E - Apr il 2005

    Indication Probable Cause1734-OE2C Probable Cause1734-OE2V

    Channel Status

    Off M odule is in CAL mode.

    Green N ormal operat ion is present w ith channel act ively controll ing

    outputs.

    Flashing Green Channel is be ing cal ib ra ted.

    Flashing Red Open w i re or no f ield pow er is

    present.

    A low or high clamp is present.

    Red - No f ield pow er is present .

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    18/24

    18 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    North American Hazardous Location Approval

    The following information applies whenoperating this equipment in hazardouslocations:

    Informations sur lutilisation de cet quipementen environnements dangereux:

    Products marked CL I, DIV 2, GP A, B, C, D are suit ablefor use in Class I Division 2 Groups A , B, C, D, HazardousLocations and nonhazardous locations only. Each productis supplied w ith markings on the rating nameplateindicating the hazardous location temperature code. W hencombining products w ithin a system, t he most adversetemperature code (low est T number) may be used tohelp determine the overall temperature code of thesystem. Combinations of equipment in your system are

    subject t o investigation by the local Aut hority HavingJurisdiction at the time of i nstallation.

    Les produits marqus CL I, DIV 2, GP A, B, C, D neconviennent qu une uti lisatio n en environnements de Classe IDivision 2 Groupes A, B, C, D dangereux et non dangereux.Chaque produit est l ivr avec des marquages sur sa plaquedidentification qui indiquent le code de temprature pour lesenvironnement s dangereux. Lorsque plusieurs produits sontcombins dans un systme, le code de temprature le plusdfavorable (code de temprature le plus faible) peut treutil is pour dterminer le code de temprature global du

    systme. Les combinaisons dquip ements dans le systmesont sujettes inspection par les autorits locales qualifiesau moment de l installation.

    EXPLOSION HAZARD - Do not disconnect equipment unless

    pow er has been removed or t he areais know n to be nonhazardous.

    Do not disconnect connections tothis equipment unless power hasbeen removed or the area is knownto be nonhazardous. Secure anyexternal connections that mate tothis equipment by using screws,sliding latches, threadedconnectors, or other means providedw ith this product.

    Substitut ion of components mayimpai r suitabili ty for Class I, Division2.

    If t his product contains batteries,they must onl y be changed in anarea known to be nonhazardous.

    RISQUE DEXPLOSION Couper le courant ou sassurer que

    lenvironnement est class nondangereux avant de dbrancherl'quipement.

    Couper le courant ou s'assurer quelenvironnement est class nondangereux avant de dbrancher lesconnecteurs. Fixer t ous lesconnecteurs externes relis cetquipement l'aide de vis, loquetscoulissants, connecteurs filets ouautres moyens fourni s avec ceproduit.

    La substitution de composants peutrendre cet quipement inadapt uneutil isation en environnement deClasse 1, Division 2.

    Sassurer que lenvironnement estclass non dangereux avant dechanger les piles.

    WARNING AVERTISSEMENT

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    19/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 19

    Publication 1734-IN 002C-EN-E - Apr il 2005

    European Hazardous Location Approval

    European Zone 2 Certification (The following applies when the product bears theEEx marking)This equipment is intended f or use in potentiall y explosive atmospheres as defined by

    European Union Direct ive 94/ 9/ EC.

    DEM KO certif ies that thi s equipment has been found to comply wi th the Essential Health

    and Safety Requirement s relating to t he design and construction of Category 3 equipment

    intended f or use in potenti ally explosive atmospheres, given in Annex II to thi s Directive.

    The examinat ion and test results are recorded in confident ial report N o 03NK30347.

    Compliance w ith t he Essential Health and Safet y Requirements has been assured bycompliance with EN 50021.

    IMPORTANT O bserve the follow ing additional Zone 2 certification

    requirem ents.

    This equipm ent is not resistant to sunlight or

    other sources of U V radiation.

    The secondary of a current transform er shall not

    be open-circuited w hen applied in Class I, Zone

    2 environm ents.

    Equipm ent of lesser Enclosure Type Rating m ust

    be installed in an enclosure providing at least

    IP54 protection w hen applied in Class I, Zone 2

    environm ents. This equipm ent shall be used w ithin its specified

    ratings defined by Allen-Bradley.

    Provision shall be m ade to prevent the rated

    voltage from being exceeded by transient

    disturbances of m ore than 40% w hen applied in

    Class I, Zone 2 environm ents.

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    20/24

    20 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    Specifications

    Output Specifications 1734-OE2C 1734-OE2V

    Number of Outputs 2 single-ended, non-isolated

    Resolut ion 13 bits - over 0-21mA

    2.5A/ cnt (average value -

    typical range:

    2.3...2.7A/cnt)

    14 bits

    (13 plus sign)

    1.28mV/cnt in unipolar or

    bipolar mode

    Output Current 0mA output unt i l

    communication

    established

    4-20mA user configurable

    0-20mA user configurable

    -

    Output Voltage - 0V output unt i l

    communication

    established

    0-10V (user configurable)

    (-0.0V under, +0.5V over)

    +10V user configurable

    (-0.5V under, +0.5V over)

    Absolute A ccuracy1 Current Output

    0.1% Full Scale @ 25oC

    Voltage Output

    0.1% Full Scale @ 25oC

    Accuracy Drift w/Temp. 30ppm/ oC 5ppm/ oC

    Step Response to 63% of FS 24 sCurrent Load on

    Voltage Output

    - 3mA

    Resisti ve Load on

    Current Output

    0...750 -

    Conversion Type Digital to analog converter

    Conversion Rate 16s 20s

    Data Format Signed Integer

    Calibrat ion Factory Calibrated

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    21/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 21

    Publication 1734-IN 002C-EN-E - Apr il 2005

    General Specifications 1734-OE2C 1734-OE2V

    M odule Locat ion 1734-TB, 1734-TBS, 1734-TB3, 17340TB3S

    w iring base assembly

    POINTBus Current 75 mA @5V dc

    Pow er Dissipation -

    M aximum at 28.8V

    750 load on each output

    - 1.23 W

    0 load on each output

    - 1.83 W

    1.0W

    Thermal Dissipation -

    M aximum at 28.8V

    75 0load on each output

    - 4.19 BTU/hr

    0 load on each output

    - 6.24 BTU/ hr

    3.4BTU/hr

    Isolation Voltage

    (Continuous-voltage

    W ithstand Rating)

    50V Continuous

    Tested to w ithst and 2200V dc for 60 sNo isolation betw een individual channels

    External dc pow er

    Supply Voltage

    Voltage Range

    Supply Current

    24V dc nominal

    10...28.8V dc

    70 mA @ 24V dc (including

    outputs @20 mA)

    24V dc nominal

    10...28.8V dc

    35 mA @ 24V dc (including

    outputs @3 mA)

    Indicators 1 green/ red module status indicator, logic side

    1 green/ red netw ork stat us indicator, logic side

    2 green/ red output stat us indicators, logic side

    Keysw itch Posit ion 4

    Dimensions H x W x L

    56 x 12 x 75.5 mm (2.21 x 0.47 x 2.97 in)

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    22/24

    22 POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules

    Publication1734-IN 002C-EN-E - Apri l 2005

    General Specifications(Continued)

    1734-OE2C 1734-OE2V

    Operat ional Temperature IEC 60068-2-1 (Test Ad, Operat ing Cold),

    IEC 60068-2-2 (Test Bd, Operating Dry Heat),

    IEC 60068-2-14 (Test Nb , Operati ng Thermal Shock):

    -20 55 C (-4 131 F)

    Storage Temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperat i ng Co ld ),

    IEC 60068-2 -2 (Test Bb, Unpackaged N onopera ti ng Dry

    Heat),

    IEC 60068-2 -14 (Test N a, Unpackaged N onopera ti ng

    Thermal Shock):

    -40 85 C (-40 185 F)

    Relat ive Humidity IEC 60068-2-30

    (Test Db, Unpackaged Nonoperating Damp Heat):

    5 95% noncondensing

    Vibrat ion IEC60068-2-6 (Test Fc, Operat ing)

    5 g @ 10...500 Hz

    Shock

    Operating

    Non-Operating

    IEC 60068-2-27 (Test Ea, Unpackaged Shock)

    30 g

    50 g

    Emissions CISPR 11: Group 1, Class A

    ESD Immunity IEC6100-4-2

    6 kV contact di scharges

    8 kV air discharges

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    23/24

    POINT I/ O 2 Current Output and 2 Volt age Output Analog M odules 23

    Publication 1734-IN 002C-EN-E - Apr il 2005

    General Specifications(Continued)

    1734-OE2C 1734-OE2V

    Radiated RF Immunity IEC 61000-4-3:

    10 V/ m w ith 1kHz sine-wave 80% AM from 30 M Hz to

    2000 M Hz

    10 V/ m w ith 200 Hz 50% Pulse 100% AM at 900 M hz

    10 V/ m w ith 200 Hz 50% Pulse 100% AM at 1890 M Hz

    EFT/ B Immunit y IEC 61000-4-4:3 kV at 2.5 kHz on signal port s

    Surge Transien t Immuni ty IEC 61000-4 -5:

    2 kV line-earth(CM ) on shielded ports

    Conduct ed RF Immunit y IEC61000-4-6

    10 Vrms w ith 1 kHz sine-w ave 80% AM

    from 150 kHz to 80 M Hz

    Enclosure Type Rat ing N one (open-style)

    W ire Size 14 AW G (2.5mm2) - 22 AW G (0.25mm 2) solid or stranded

    copper w ire rated at 75 oC or greater

    3/ 64 inch (1.2 mm) insulation m aximum

    W ire Category2 1 - on signal ports

    Terminal Base Screw Torque 0.6 Nm (7 lb-in)

    W eight 0.036 kg (0.08 lb)

    Publ ica ti ons - User M anua l 1734-UM 001

  • 7/25/2019 Ult REL Output Analog Modules 1734-In002 En

    24/24

    Publication1734-IN002C-EN-E - April 2005 PN 957955-48Supersedes Publication 1734-IN002B-EN-P - April 2002 and

    Certification3 (When Product is Marked) 1734-OE2C 1734-OE2V

    c-UL-us UL Listed Industrial Control Equipment ,

    certif ied for U.S. and Canada

    c-UL-us UL Listed for Class I, Divi sion 2 Group A,B,C,D

    Hazardous Locati ons, certif ied for U.S. and Canada

    CE European Union 89/ 336/EEC EM C Directive,

    compliant w ith:

    EN 50082-2; Industrial Immuni ty EN 61326; M eas./Control/ Lab., Industrial

    Requirements

    EN 61000-6-2; Industrial Immuni ty

    EN 61000-6-4; Industrial Emissions

    C-Tick Austral ian Radiocommuni cations Act ,

    compliant w ith:

    AS/ NZS CISPR 11, Industri al Emi ssions

    EEX European Union 94/ 9/ EC ATEX Direct ive,

    compliant w ith: EN 50021; Potent iall y Explosive At mospheres,

    Protecti on n (Zone 2)

    X

    X

    X

    X

    X

    X

    X

    X

    X

    1. Includes off set, gain, non-linearit y and repeatabil ity error terms.2. Use this Category information for planning routing. Refer to Industrial Automation W iring and Grounding Guidelines, publicati on 1770-4.1.3. See the Product Certification l ink at w w w.ab.com f or Declarations of Conformity, Certificates, and other certification details.

    PO IN T I/O , PO IN TBus, and RSLogix 5000 are tradem arks of Rockw ell Autom ation.ControlN et is a tradem ark of ControlN et International, Ltd.D eviceN et is a tradem ark of O pen D eviceN et Vendor Association.