UDT UDTX FILTRATION UNITS AND AIR TREATMENT MODULES ?· UDT UDTX FILTRATION UNITS AND AIR TREATMENT…

  • View
    212

  • Download
    0

Embed Size (px)

Transcript

  • UDT UDTX FILTRATION UNITS AND AIR TREATMENT MODULES

    UDT

    MF: Filtration Modules

    ME: Modules with electrically heated coils

    MA: Modules with water coils

    UDTX

    According EU Regulation

  • UDT

    UDTBox: Aluminiumprofilestructurewiththermal

    insulationandsoundproofing. Sideaccesspanelforcorrect

    maintenance. Modularconstruction,foraddingfilteror

    airtreatmentmodules. Stuffing-boxforcableinlet.

    Fan: Ventilationunits,equippedwith

    CBDseriesfans. Impellerswithforward-facingblades

    madefromgalvanisedsheetsteel.

    Motor: Single-phasetwo-speedmotorswithIE2

    efficiency,exceptforcapacitieslessthan0.75kW.

    ClassFmotors,withballbearings,IP54protection.

    Single-phase220240V50HzandThree-phase220-240/380415V50Hz.

    Max.airtemperaturetotransport:20C.+60C.

    Versions: MF:FiltrationModule.Standardversion

    F6+F8andoptionallyF7+F9. ME:Modulewithelectricallyheatedcoil.

    StandardversionG4andoptionallywithF6+F8orF7+F9filters.

    MA:Modulewithwatercoil.StandardversionG4andoptionallywithF6+F8orF7+F9filters.

    Onrequest: Verticaloutlet. Moduleinstalledasblower.

    Soundproofed air treatment units with direct drive motors, fitted with double-inlet fans and optional modules for filtration, electrical or hot-water heating

    Technical characteristics

    Order code

    UDT 7/7 4M 1/5 MF F6+F8

    Fanunitswithairtreatment

    Turbinesizeininches

    Numberofmotorpoles4=1400r/min.50Hz6=900r/min.50Hz

    Motorpower(HP)

    FilteroptionsforMFmodulesStandardversionF6+F8Option:G4+F7,F7+F9

    T=Three-phaseM=Single-phase

    AirtreatmentmodulesMF:filtrationmodule(standardversion)ME:modulewithelectricallyheatedcoil(G4filterincluded)MA:modulewithwatercoil(G4filterincluded)

    Model Speed Maximum admissible current (A) Installed powerMaximum

    airflow Sound Level Approx. weight

    (r/min) 230 V 400 V (kW) (m3/h) dB(A) (Kg)UDT-7/7-4M1/5 1230 1.4 0.15 1520 58 22.5UDT-9/9-4M1/2 1320 3.3 0.37 2800 66 31.8UDT-9/9-4M3/4 1310 4.5 0.55 3600 70 32.6UDT-10/10-4M1/2 1320 3.3 0.37 2800 65 37.3UDT-10/10-4M3/4 1310 4.5 0.55 3950 70 38.1UDT-12/12-6T11/2 850 6.6 3.8 1.1 7800 74 53.8UDT-12/12-6M3/4 850 5 0.55 4900 63 52.3UDT-12/12-6M1 850 6 0.75 6000 70 53.3UDT-15/15-6T3 890 10.9 6.3 2.2 11900 74 80

  • UDT

    Dimensions in mm

    Model A B C D1 D2 E L K

    Acoustic features

    Air treatment module options

    Model 63 125 250 500 1000 2000 4000 8000

    Sound power Lw(A) spectrum in dB(A) via frequency band in Hz

    Aluminiumprofilestructurewiththermalinsulationandsoundproofing.

    Sideaccesspanelforcorrectmaintenance.

    Modularconstruction,foraddingfilterorairtreatmentmodules.

    StandardversionmoduleF6+F8andoptionallyF7+F9.

    CompatiblewithseriesUDT,UDTX,CJBD/AL,CJBD/ALS,CJBX/ALandCJBX/ALS.

    MF: Filtration Modules

    Aluminiumprofilestructurewiththermalinsulationandsoundproofing.

    Sideaccesspanelforcorrectmaintenance.

    Modularconstruction,foraddingfilterorairtreatmentmodules.

    Stuffing-boxforcableinlet. StandardversionmoduleG4and

    optionallywithF6+F8orF7+F9filters. CompatiblewithseriesUDT,UDTX,

    CJBD/AL,CJBD/ALS,CJBX/ALandCJBX/ALS.

    ME: Modules with electrically heated coils

    Aluminiumprofilestructurewiththermalinsulationandsoundproofing.

    Sideaccesspanelforcorrectmaintenance.

    Modularconstruction,foraddingfilterorairtreatmentmodules.

    StandardversionmoduleG4andoptionallywithF6+F8orF7+F9filters.

    CompatiblewithseriesUDT,UDTX,CJBD/AL,CJBD/ALS,CJBX/ALandCJBX/ALS.

    MA: Modules with water coils

    UDT-7/7 981 490 490 428 428 91 226 247UDT-9/9 1041 550 550 488 488 86 279 317UDT-10/10 1096 605 605 543 543 88 306 343UDT-12/12 1171 680 680 618 618 84 360 404UDT-15/15 1346 855 855 793 793 119 423 490

    7/7-4M1/5 43 54 58 62 64 63 62 539/9-4M1/2 51 62 66 70 72 71 70 619/9-4M3/4 55 66 70 74 76 75 74 6510/10-4M1/2 50 61 65 69 71 70 69 6010/10-4M3/4 55 66 70 74 76 75 74 6512/12-6T11/2 59 70 74 78 80 79 78 6912/12-6M3/4 48 59 63 67 69 68 67 5812/12-6M1 55 66 70 74 76 75 74 6515/15-6T3 61 72 77 81 83 81 80 71

  • UDT

    7 7

    7

    7

    7

    9

    9

    9

    9

    910

    10

    10

    10

    1012

    12

    12

    12

    1215

    15

    15

    15

    15

    7= MF 7/79= MF 9/910= MF 10/1012= MF 12/1215= MF 15/15

    MF: Filtration module characteristics

    Head loss - filters

    ME: Technical characteristics of electrically heated coil

    Model Current(A)Installed power

    (kW) Maximum airflow Approx. weight

    400V Stage 1 Stage 2 Stage 3 (m3/h) (Kg)ME-7/7 13 3 3 3 1500 23ME-9/9 23 5.4 5.4 5.4 3300 33ME-10/10 33 7.7 7.7 7.7 4500 44ME-12/12 52 12 12 12 6000 61ME-15/15 81 18.8 18.8 18.8 10000 96

  • UDT

    MA: Characteristics of 90/70C water coil for air at 0C

    Head loss - water coil heaters

    Model Installed Maximum airflow Water flow Water head loss Connection Approx. weight

    (kW) (m3/h) (m3/h) (kPa) (in) (Kg)MA-7/7 23 1500 1.0 16.3 1/2 18MA-9/9 37 2500 1.7 26.6 1/2 25MA-10/10 46 3000 2.0 17.6 3/4 31MA-12/12 66 4500 2.9 29.8 3/4 39MA-15/15 108 5500 4.8 21.4 1 63

    MA: Characteristics of 80/60C water coil for air at 0C

    Model Installed Maximum airflow Water flow Water head loss Connection Approx. weight

    (kW) (m3/h) (m3/h) (kPa) (in) (Kg)MA-7/7 20 1500 0.9 13.0 1/2 18MA-9/9 33 2500 1.4 21.3 1/2 25MA-10/10 40 3000 1.7 14.0 3/4 31MA-12/12 58 4500 2.5 23.8 3/4 39MA-15/15 100 5500 4.2 17.5 1 63

    97 10 12 15

    MA MA

    Head loss - electrical coil heaters

    9

    710 12

    15

    ME ME

  • UDT

    Module Dimensions mm

    CompatiblewithseriesUDT,UDTX,CJBD/AL,CJBD/ALS,CJBX/ALandCJBX/ALS

    MF MODULES

    ME MODULES

    MA MODULES

    Model A B C D1 D2

    Model A B C D1 D2 E

    Model A B C D1 D2 E1 E2 G H

    Installation and filter position diagrams

    Moduleinstalledasextractor

    Filtration Module

    Heating Coil Modules

    Moduleinstalledasblower

    ME-7/7 490 490 490 428 428 245ME-9/9 550 550 550 488 488 275ME-10/10 605 605 605 543 543 302,5ME-12/12 680 680 680 618 618 340ME-15/15 855 855 855 793 793 427,5

    MA-7/7 490 490 490 428 428 267 224 334 60MA-9/9 550 550 550 488 488 297 254 410 57MA-10/10 605 605 605 543 543 324 281 452 54MA-12/12 680 680 680 618 618 362 319 527 79MA-15/15 855 855 855 793 793 460 395 671 42

    MF-7/7 490 490 490 428 428MF-9/9 550 550 550 488 488MF-10/10 605 605 605 543 543MF-12/12 680 680 680 618 618MF-15/15 855 855 855 793 793

  • UDT

    Characteristic curves - fans

  • UDTX

    UDTXBox: Aluminiumprofilestructurewiththermal

    insulationandsoundproofing. Sideaccesspanelforcorrect

    maintenance. Modularconstruction,foraddingfilteror

    airtreatmentmodules. Stuffing-boxforcableinlet.

    Fan: Ventilationunits,equippedwithfansfrom

    theCBX,CBXCorCBXRseries Impellerswithforward-facingblades

    madefromgalvanisedsheetsteel.

    Motor: Single-phasetwo-speedmotorswithIE-2

    efficiency,exceptforcapacitieslessthan0.75kW.

    ClassFmotors,withballbearings,IP54protection.

    Three-phase230/400V-50Hz.(upto5.5HP)and400/690V-50Hz(capacityover5.5HP).

    Max.airtemperaturetotransport:-20C+60C

    Versions: MF:FiltrationModule.Standardversion

    F6+F8andoptionallyF7+F9. ME:Modulewithelectricallyheatedcoil.

    StandardversionG4andoptionallywithF6+F8orF7+F9filters.

    MA:Modulewithwatercoil.StandardversionG4andoptionallywithF6+F8orF7+F9filters.

    Onrequest: Verticaloutlet. Beltdriveonleft. Moduleinstalledasblower.

    Soundproofed belt-driven air treatment units, fitted with double-inlet fans and optional modules for filtration, electrical or hot-water heating

    Technical characteristics

    Order code

    UDTX 15/15 2 MF F6+F8

    Fanunitswithairtreatment

    Turbinesizeininches

    Motorpower(HP)

    FilteroptionsforMFmodulesStandardversionF6+F8Option:G4+F7,F7+F9

    AirtreatmentmodulesMF:filtrationmodule(standardversion)ME:modulewithelectricallyheatedcoil(G4filterincluded)MA:modulewithwatercoil(G4filterincluded)

    Model Speed Maximum admissible current (A)Installed power

    Maximum airflow Sound Level

    Approx. weight

    Assembly version

    (r/min) 230 V 400 V 690V (kW) (m3/h) dB(A) (Kg)UDTX-7/7-0.25 1090 1.23 0.71 0.18 1050 48 37 AUDTX-7/7-0.33 1220 1.66 0.96 0.25 1100 50 37.8 AUDTX-7/7-0.5 1420 2.02 1.17 0.37 1250 53 39 AUDTX-7/7-0.75 1600 2.92 1.69 0.55 1450 56 41 AUDTX-7/7-1 1790 3.1 1.79 0.75 1500 58 42.5 AUDTX-9/9-0.25 825 1.23 0.71 0.18 1700 45 48 AUDTX-9/9-0.33 920 1.66 0.96 0.25 1800 48 50 AUDTX-9/9-0.5 1020 2.02 1.17 0.37 2200 51 51.5 AUDTX-9/9-0.75 1050 2.92 1.69 0.55 2900 55 54.5 AUDTX-9/9-1 1070 3.1 1.79 0.75 3200 56 56 AUDTX-9/9-1.5 1260 4.03 2.32 1.1 3750 60 59 AUDTX-10/10-0.5 845 2.02 1.17 0.37 2950 52 55 A

  • UDTX

    Dimensions in mm

    UDTX-7/7 1321 490 490 428 428 91 226 247UDTX-9/9 1411 550 550 488 488 86 279 317UDTX-10/10 1461 605 605 543 543 88 306 343UDTX-12/12 1541 680 680 618 618 84 360 404UDTX-15/15 1711 855 855 793 793 119 423 490UDTX-18/18 1847 1000 1000 938 938 137 498 554

    Model A B C D1 D2 E L K

    Technical characteristics

    Model Speed Maximum admissible current (A)Installed power

    Maximum airflow Sound Level

    Approx. weight

    Assembly version

    (r/min) 230 V 400 V 690V (kW) (m3/h) dB(A) (Kg)UDTX-10/10-0.75 845 2.92 1.69 0.55 3800 56 57 AUDTX-10/10-1 960 3.1 1.79 0.75 4175 58 58.5 AUDTX-10/10-1.5 1070 4.03 2.32 1.1 4800 61 61.3 AUDTX-10/10-2 1140 5.96 3.44 1.5 5400 63 64.6 AUDTX-12/12-0.5 595 2.02 1.17 0.37 4200 52 69 AUDTX-12/12-0.75 675 2.92 1.69 0.55 4800 54 71 AUDTX-12/12-1 765 3.1 1.79 0.75 5400 57 72.4 AUDTX-12/12-1.5 855 4.03 2.32 1.1 5800 59 75.3 AUDTX-12/12-2 9