Transmitter AccuFLo-P

DSIII series with HART-communication

Operating and mounting instructions

Page 2: Transmitter AccuFLo-P DSIII series with HART-communication

IntroductionIntroductionIntroductionIntroduction 1111

General safety notesGeneral safety notesGeneral safety notesGeneral safety notes 2222

DescriptionDescriptionDescriptionDescription 3333

InstallInstallInstallInstall 4444

ConnectingConnectingConnectingConnecting 5555

OperationOperationOperationOperation 6666

Operating functions through HARTOperating functions through HARTOperating functions through HARTOperating functions through HART 7777

Functional safetyFunctional safetyFunctional safetyFunctional safety 8888

CommissioningCommissioningCommissioningCommissioning 9999

Service and maintenanceService and maintenanceService and maintenanceService and maintenance 10101010

Technical dataTechnical dataTechnical dataTechnical data 11111111

Dimension drawingsDimension drawingsDimension drawingsDimension drawings 12121212

Spare parts/accessoriesSpare parts/accessoriesSpare parts/accessoriesSpare parts/accessories 13131313

AppendixAppendixAppendixAppendix 14141414

List of abbreviationsList of abbreviationsList of abbreviationsList of abbreviations 15151515

GlossaryGlossaryGlossaryGlossary 16161616

Source documentsSource documentsSource documentsSource documents 17171717

Page 3: Transmitter AccuFLo-P DSIII series with HART-communication

Safety GuidelinesSafety GuidelinesSafety GuidelinesSafety Guidelines

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring onlygraded according to the degree of danger.

DangerDangerDangerDanger

indicates that death or severe personal injury

WarningWarningWarningWarning

indicates that death or severe personal injury

CautionCautionCautionCaution

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.CautionCautionCautionCaution

without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.NoticeNoticeNoticeNotice

indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

If more than one degree of used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified PersonnelQualified PersonnelQualified PersonnelQualified Personnel

The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by this documentation qualified persons are defined as persdevices, systems and circuits in accordance with established safety practices and standards.

Prescribed UsagePrescribed UsagePrescribed UsagePrescribed Usage

Note the following:

WarningWarningWarningWarning

This device may only be used for the applications described with devices or components from other manufacturers which have been approved or recommended by S.K.I. Correct, reliable operation of the product requires proper transport, storage, positionmaintenance.

TrademarksTrademarksTrademarksTrademarks

All names identified by ®whose use by third parties for their own purposes could violate the rights of the owner.

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

indicates that death or severe personal injury willwillwillwill result if proper precautions are not taken.

that death or severe personal injury maymaymaymay result if proper precautions are not taken.

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property

only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnelqualified personnelqualified personnelqualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.

This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by S.K.I. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and

® are registered trademarks. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert

to property damage have no safety alert symbol. These notices shown below are

result if proper precautions are not taken.

result if proper precautions are not taken.

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property

only be set up and used in conjunction with this documentation. Commissioning and . Within the context of the safety notes in

ons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards.

in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by S.K.I. Correct, reliable

ing and assembly as well as careful operation and

are registered trademarks. The remaining trademarks in this publication may be trademarks

Page 4: Transmitter AccuFLo-P DSIII series with HART-communication

1111

IntroductionIntroductionIntroductionIntroduction

1.11.11.11.1 Objective of this documentationObjective of this documentationObjective of this documentationObjective of this documentation This programming manual contains all information that you will require to commission and use the device. It is aimed at persons who install the device mechanically, connect it electrically, parameterize and commission it, as well as at service and maintenance engineers. This document also contains special information and safety notes that you will require when

using an SIL-certified device in safety-instrumented systems.

1.21.21.21.2 HistoryHistoryHistoryHistory This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware: EditionEditionEditionEdition Firmware identification type Firmware identification type Firmware identification type Firmware identification type

plateplateplateplate System integrationSystem integrationSystem integrationSystem integration Installation path for PDMInstallation path for PDMInstallation path for PDMInstallation path for PDM

08/2007 FW: 11.03.03, FW: 11.03.04, FW: 11.03.05, FW: 11.03.06, FW: 11.03.07

PDM 6.01); Dev. R.3 DD Rev. 2

AccuFlo P DSIII.2

1) up to SP02

The most important changes in the documentation when compared with the respective

previous edition are given in the following table. EditionEditionEditionEdition RemarkRemarkRemarkRemark

Page 5: Transmitter AccuFLo-P DSIII series with HART-communication

EditionEditionEditionEdition RemarkRemarkRemarkRemark

06 08/2007

Illustrations of the device have been changed owing to the changes in the device housing. The following chapters have also been changed:

• Chapter "Description" > "Functional principle" has

new enhanced contents for the "flush mounted diaphragm" topic

• Chapter "Description" > "SIMATIC PDM" - NEW

• Chapter "Functional safety" - NEW

• Chapter "Technical data" has

new enhanced contents for the "flush mounted diaphragm" topic

• Chapter "Dimension drawings"

has new contents for the "flush mounted diaphragm" topic

• Chapter "Appendix"

has new contents for the "Functional safety" topic

1.31.31.31.3 Scope of this manualScope of this manualScope of this manualScope of this manual

Table1-1 "ACCU*33" stands for:

Order numberOrder numberOrder numberOrder number AccuFloAccuFloAccuFloAccuFlo P, DSP, DSP, DSP, DS III series forIII series forIII series forIII series for

ACCU033 Gauge pressure

ACCU233 Absolute pressure from the gauge pressure series

ACCU433 Differential pressure and flow rate, PN 32/160 (MWP 464/2320 psi)

Page 6: Transmitter AccuFLo-P DSIII series with HART-communication

1.41.41.41.4 Further informationFurther informationFurther informationFurther information InformationInformationInformationInformation

The contents of these instructions shall not become part of or modify any prior or existing agreement, commitment or legal relationship. All obligations on the part of S.K.I. GmbH are contained in the respective sales contract which also contains the complete and solely

applicable warranty conditions. Any statements contained herein do not create new warranties or modify the existing warranty. The content reflects the technical status at the time of printing. We reserve the right to make technical changes in the course of further development.

Worldwide contact personWorldwide contact personWorldwide contact personWorldwide contact person If you need more information or have particular problems which are not covered sufficiently by the operating instructions, get in touch with your contact person. You can find contact

information for your local contact person in the Internet.

Page 7: Transmitter AccuFLo-P DSIII series with HART-communication

2222 General safety notesGeneral safety notesGeneral safety notesGeneral safety notes

2.12.12.12.1 General informationGeneral informationGeneral informationGeneral information This device left the factory free from safety problems. In order to maintain this status and to ensure safe operation of the device, please observe the safety information and warnings

contained in these instructions. See alsoSee alsoSee alsoSee also

Safety-instrumented system

2.22.22.22.2 Correct usageCorrect usageCorrect usageCorrect usage The device may only be used for the purposes specified in these instructions. Insofar as they are not expressly stated in these instructions, all changes to the device are the

sole responsibility of the user.

2.32.32.32.3 Laws and directivesLaws and directivesLaws and directivesLaws and directives Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation. For hazardous areas, these are for example:

• IEC 60079-14 (international)

• National Electrical Code (NEC - NFPA 70) (USA)

• Canadian Electrical Code (CEC) (Canada)

• EN 60079-14 (formerly VDE 0165, T1) (EU, Germany)

• The working reliability regulation (Germany)

Page 8: Transmitter AccuFLo-P DSIII series with HART-communication

2.42.42.42.4 MeasuresMeasuresMeasuresMeasures For the sake of safety, the following precautions must be observed:

WarningWarningWarningWarning

"Intrinsically"Intrinsically"Intrinsically"Intrinsically safe" protection typesafe" protection typesafe" protection typesafe" protection type

"Intrinsically-safe" devices lose their certification as soon as they are operated on circuits which do not correspond with the test certification valid in their country. The "ia" protection level of the device

is decreased to the "iare connected.

WarningWarningWarningWarning

Exposure to aggressive and hazardous mediaExposure to aggressive and hazardous mediaExposure to aggressive and hazardous mediaExposure to aggressive and hazardous media

The device can be operated both at high pressure and with aggressive and hazardous media. Therefore, improper use of this device may lead to serious injury and or considerable damage to property. Above all, it must be noted when the device was in use and is to be exchanged.

CautionCautionCautionCaution

Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)

This device contains destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an assembly is touched by a person who is not grounded against static elecThe damage to a module as a result of overvoltage cannot usually be detected immediately. It may only become apparent after a long period of operation.

For the sake of safety, the following precautions must be observed:

safe" protection typesafe" protection typesafe" protection typesafe" protection type

safe" devices lose their certification as soon as they are operated on circuits which do not correspond with the test certification valid in their country. The "ia" protection level of the device

is decreased to the "ib" protection level when intrinsically safe circuits having the "ib" protection level

Exposure to aggressive and hazardous mediaExposure to aggressive and hazardous mediaExposure to aggressive and hazardous mediaExposure to aggressive and hazardous media

The device can be operated both at high pressure and with aggressive and hazardous media. Therefore, improper use of this device may lead to serious injury and or considerable damage to property. Above all, it must be noted when the device was in use and is to be exchanged.

Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)Electrostatic Sensitive Devices (ESD)

This device contains electrostatic sensitive devices. Electrostatic sensitive devices may be destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an assembly is touched by a person who is not grounded against static elecThe damage to a module as a result of overvoltage cannot usually be detected immediately. It may only become apparent after a long period of operation.

safe" devices lose their certification as soon as they are operated on circuits which do not correspond with the test certification valid in their country. The "ia" protection level of the device

b" protection level when intrinsically safe circuits having the "ib" protection level

The device can be operated both at high pressure and with aggressive and hazardous media. Therefore, improper use of this device may lead to serious injury and or considerable damage to property. Above all, it must be noted when the device was in use and is to be exchanged.

electrostatic sensitive devices. Electrostatic sensitive devices may be destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an assembly is touched by a person who is not grounded against static electricity. The damage to a module as a result of overvoltage cannot usually be detected immediately. It may

Page 9: Transmitter AccuFLo-P DSIII series with HART-communication

2.52.52.52.5 Qualified PersonnelQualified PersonnelQualified PersonnelQualified Personnel Qualified personnel are people who are familiar with the installation, mounting, commissioning, and operation of the product. These people have the following qualifications:

• They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures and aggressive as well as hazardous media.

• For explosion-proof devices: They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems.

• They are trained or instructed in maintenance and use of appropriate safety equipment according to the safety regulations.

Page 10: Transmitter AccuFLo-P DSIII series with HART-communication

3333 DescriptionDescriptionDescriptionDescription

3.13.13.13.1 System configurationSystem configurationSystem configurationSystem configuration

OverviewOverviewOverviewOverview The pressure transmitter can

• as a stand-alone version, supplied with the necessary auxiliary power

• as part of a complex system environment, e.g. SIMATIC S7

System communicationSystem communicationSystem communicationSystem communication

Communication is via the HART protocol, using:

• HART communicator with at least 4 MB available memory

• PC with HART modem, on which appropriate software is available, e.g. SIMATIC PDM

• Control system which is able to communicate via the HART protocol, e.g. SIMATIC S7 with ET 200M

Figure3-1 Possible

System configurationSystem configurationSystem configurationSystem configuration

The pressure transmitter can be used in a number of system configurations:

alone version, supplied with the necessary auxiliary power

as part of a complex system environment, e.g. SIMATIC S7

Communication is via the HART protocol, using:

communicator with at least 4 MB available memory

PC with HART modem, on which appropriate software is available, e.g. SIMATIC PDM

Control system which is able to communicate via the HART protocol, e.g. SIMATIC S7 with ET 200M

Possible system configurations

be used in a number of system configurations:

PC with HART modem, on which appropriate software is available, e.g. SIMATIC PDM

Control system which is able to communicate via the HART protocol, e.g. SIMATIC S7 with ET 200M

Page 11: Transmitter AccuFLo-P DSIII series with HART-communication

3.23.23.23.2 Application rangeApplication rangeApplication rangeApplication range OverviewOverviewOverviewOverview

Depending on the version, a transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids. It can be used for the following measurement types:

• Gauge pressure

• Absolute pressure

• Differential pressure

With appropriate parameterization, it can also be used for the following additional measurement types:

• Volume

• Mass

• Volume of flow

• Mass flow rate

The output signal is always a load-independent direct current between 4 and 20 mA.

You can install the "intrinsically-safe" version of the transmitter in hazardous areas. The devices have an EC type examination certificate and comply with the appropriate harmonized European CENELEC directives.

Transmitters with remote seals of different shapes can be delivered for special applications. For example, measuring high-viscosity substances is a special application.

Gauge pressureGauge pressureGauge pressureGauge pressure

This version measures aggressive, non-aggressive and hazardous gases, vapors and liquids.

The smallest measuring span is 0.01 bar g (0.145 psi g), and the largest 400 bar g (5802 psi g).

Differential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rate

This version measures corrosive, non-corrosive and hazardous gases, vapors and liquids.

You can use this version for the following measurement types:

Page 12: Transmitter AccuFLo-P DSIII series with HART-communication

• differential pressure, e.g. effective differential pressure

• small positive or negative overpressure

• in combination with a restrictor device: flow rate q ~

The smallest measuring span is 1 mbar (0.0145 psi), the largest 30 bar (435 psi).

Absolute pressureAbsolute pressureAbsolute pressureAbsolute pressure

This version measures the absolute pressure of aggressive, non-aggressive and hazardous gases, vapors and liquids.

There are two series: a "differential pressure" series and a "gauge pressure" series. The "differential pressure" series is distinguished by a high overload capability.

The smallest measuring span of the "differential pressure" series is 8.3 mbar a (0.12 psi a), and the largest is 100 bar a (1450 psi a).

The smallest measuring span of the "gauge pressure" series is 8.3 mbar a (0.12 psi a), and the largest is 30 bar a (435 psi a).

3.33.33.33.3 StructureStructureStructureStructure

Depending on a customer-specific order, the device comprises different parts. The electronic housing is made of aluminum die casting or stainless steel precision casting. The housing has a removable circular cover at the front and the back. Depending on the device version, the front cover ④ is designed as an inspection window. You can directly read the measured values on the digital display through this inspection window. The infeed ② for the electrical terminal compartment is provided on either side, optionally at the right or the left.

The corresponding unused opening is closed with a blanking plug ⑨. The protective conductor connection ⑪ is provided at the back of the housing. The electrical terminal compartment for power supply and shield is accessible when you remove the rear cover ⑩. The measuring cell with a process connection ⑧ is provided in the lower section of the housing. This measuring cell is secured against twisting using a

retaining screw ⑦. Thanks to the modular structure of the transmitter, the measuring cell, the electronic unit or the network card can be replaced if required.

Page 13: Transmitter AccuFLo-P DSIII series with HART-communication

A keyboard cover ③keypad is provided below this cover.

Figure3-2 Device view of the transmitter

① Type plate ② Infeed with a cable gland

③ Keyboard cover for accessing the buttons

④ Removable cover, optionally with an inspection window

⑤ Digital display

⑥ Measuring point label

⑦ Retaining screw

⑧ Process connection

⑨ Blanking plug

⑩ Removable cover for accessing the electrical terminal compartment

⑪ Protective conductor connection

⑫ Alternative measuring point label

⑬ Approval plate

See alsoSee alsoSee alsoSee also Safety notes for installation

③ is provided at the top of the housing. This cover can be opened. ad is provided below this cover.

Device view of the transmitter

Infeed with a cable gland Keyboard cover for accessing the buttons Removable cover, optionally with an inspection window Digital display

point label Retaining screw Process connection Blanking plug Removable cover for accessing the electrical terminal compartment Protective conductor connection Alternative measuring point label Approval plate

Safety notes for installation

is provided at the top of the housing. This cover can be opened. The

Page 14: Transmitter AccuFLo-P DSIII series with HART-communication

3.43.43.43.4 Structure of the type plate and approval plateStructure of the type plate and approval plateStructure of the type plate and approval plateStructure of the type plate and approval plate Structure of the type plateStructure of the type plateStructure of the type plateStructure of the type plate

The type plate which bears the order number and other important information such as design or technical data is provided at the side of the housing.

Figure3-3 Example of a type plate ① Order number (machine-readable product code) ② Serial number

Structure of the approval plateStructure of the approval plateStructure of the approval plateStructure of the approval plate The approval plate is provided on the opposite side. The approval plate has information about the version of the hardware and firmware.

Figure3-4 Example of an approval plate

Page 15: Transmitter AccuFLo-P DSIII series with HART-communication

3.53.53.53.5 Functional principleFunctional principleFunctional principleFunctional principle

3.5.13.5.13.5.13.5.1 Overview of mode of operationOverview of mode of operationOverview of mode of operationOverview of mode of operation

This chapter describes how the transmitter works.

First the electronics are described, then the physical principle of the sensors which are used with the various device versions for the individual measurement types.

3.5.23.5.23.5.23.5.2 Operation of the electronicsOperation of the electronicsOperation of the electronicsOperation of the electronics

DescriptionDescriptionDescriptionDescription

Figure3-5 Operation of the electronics with HART communication

① Measuring cell sensor ② Measuring amplifier ③ Analog-to-digital converter ④ Microcontroller ⑤ Digital-to-analog converter ⑥ Each with an EEPROM in the measuring cell and in the electronics ⑦ HART modem

Page 16: Transmitter AccuFLo-P DSIII series with HART-communication

⑧ Buttons (local operation)

⑨ Digital display

⑩ Connection for external ammeter

IA Output current

UH Auxiliary power

The input pressure is converted into an electrical signal by the sensor amplified by the measuring amplifier The digital signal is analyzed in a microcontroller

and thermal characteristics. It is then converted in a doutput current of 4 to 20 mA. A diode circuit provides reverse voltage protection. You can make an uninterrupted current measurement with a low resistance ammeter at the connection ⑩. The data specific to the measuring cstored in two EEPROMs

with the electronics.

The buttons ⑧ can be used to call up individual functions, sodevice with a digital display The basic mode settings can be changed with a computer via the HART modem

3.5.33.5.33.5.33.5.3 Measuring cell operationMeasuring cell operationMeasuring cell operationMeasuring cell operation

3.5.3.13.5.3.13.5.3.13.5.3.1 Functional principle of the measuring cellFunctional principle of the measuring cellFunctional principle of the measuring cellFunctional principle of the measuring cell

CautionCautionCautionCaution

If the measurement signal fails because of sensor breakage, the separating diaphragm may also be destroyed. In the worst case scenario, the process medium leaks from the reference pressure opening in the devices used for gauge pressure with a measuring spa

In the following sections, the process variable to be measured is called general input pressure.

OverviewOverviewOverviewOverview

The following modes of operation are described:

• Gauge pressure

Buttons (local operation) Digital display Connection for external ammeter Output current Auxiliary power

The input pressure is converted into an electrical signal by the sensor ①amplified by the measuring amplifier ② and digitized in an analog-to-digital converter The digital signal is analyzed in a microcontroller ④ and corrected with regard to linearity

and thermal characteristics. It is then converted in a digital-to-analog converter output current of 4 to 20 mA. A diode circuit provides reverse voltage protection. You can make an uninterrupted current measurement with a low resistance ammeter at the connection

. The data specific to the measuring cell, the electronic data and parameterization data are stored in two EEPROMs ⑥. The first memory is linked with the measuring cell, the second

with the electronics. can be used to call up individual functions, so-called modes. If you have a

evice with a digital display ⑨, you can track the mode settings and other messages on it. The basic mode settings can be changed with a computer via the HART modem

Measuring cell operationMeasuring cell operationMeasuring cell operationMeasuring cell operation

Functional principle of the measuring cellFunctional principle of the measuring cellFunctional principle of the measuring cellFunctional principle of the measuring cell

If the measurement signal fails because of sensor breakage, the separating diaphragm may also be destroyed. In the worst case scenario, the process medium leaks from the reference pressure opening in the devices used for gauge pressure with a measuring span of

In the following sections, the process variable to be measured is called general input

The following modes of operation are described:

①. This signal is digital converter ③.

and corrected with regard to linearity

analog converter ⑤ to the output current of 4 to 20 mA. A diode circuit provides reverse voltage protection. You can make an uninterrupted current measurement with a low resistance ammeter at the connection

ell, the electronic data and parameterization data are . The first memory is linked with the measuring cell, the second

called modes. If you have a , you can track the mode settings and other messages on it.

The basic mode settings can be changed with a computer via the HART modem ⑦.

If the measurement signal fails because of sensor breakage, the separating diaphragm may also be destroyed. In the worst case scenario, the process medium leaks from the reference pressure

n of ≤ 63 bar.

In the following sections, the process variable to be measured is called general input

Page 17: Transmitter AccuFLo-P DSIII series with HART-communication

• Absolute pressure

• Differential pressure and flow rate

• Level

The following process connections are available, for example:

• G½, ½-14 NPT

• EN61518 compliant flanged connection

• Flush mounted diaphragm

3.5.3.23.5.3.23.5.3.23.5.3.2 Measuring cell for gauge pressureMeasuring cell for gauge pressureMeasuring cell for gauge pressureMeasuring cell for gauge pressure

Figure3-6 Function chart of measuring cell for gauge pressure

① Reference pressure opening ② Measuring cell ③ Process connection ④ Separating diaphragm ⑤ Fill liquid ⑥ Gauge pressure sensor pe Input pressure

The input pressure (pe) is transferred to the gauge pressure sensor ⑥ via the separating diaphragm ④ and the fill fluid ⑤, displacing its measuring diaphragm. The displacement

changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the

Page 18: Transmitter AccuFLo-P DSIII series with HART-communication

input pressure. Transmitters with measuring span ≤ 63 bar measure the input pressure against atmosphere, those with spans ≥ 160 bar against vacuum.

3.5.3.33.5.3.33.5.3.33.5.3.3 Measuring cell for differential pressure and flow rateMeasuring cell for differential pressure and flow rateMeasuring cell for differential pressure and flow rateMeasuring cell for differential pressure and flow rate

Figure3-7 Function chart of the measuring cell for differential pressure and flow rate ① Input pressure P+ ② Pressure cap ③ O-ring ④ Measuring cell body ⑤ Silicon pressure sensor ⑥ Overload diaphragm ⑦ Fill liquid ⑧ Separating diaphragm ⑨ Input pressure P-

Differential pressure is transmitted to the silicon pressure sensor ⑤ through the separating diaphragms ⑦ and the fill fluid ⑧. When measuring limits are exceeded, the overload

diaphragm ⑥ is displaced until one of the separating diaphragms ⑦ rests on the measuring cell body ④. The separating diaphragm thus protects the silicon pressure sensor ⑤ from overload. The measuring diaphragm is displaced using differential pressure. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage

Page 19: Transmitter AccuFLo-P DSIII series with HART-communication

proportional to the differential pressure. 3.5.3.53.5.3.53.5.3.53.5.3.5 Measuring cell for absolute pressure from the differential pressure seriesMeasuring cell for absolute pressure from the differential pressure seriesMeasuring cell for absolute pressure from the differential pressure seriesMeasuring cell for absolute pressure from the differential pressure series

Figure3-9 Function chart of measuring cell for absolute pressure ① Pressure cap ② Separating diaphragm on the measuring cell ③ O-ring ④ Measuring cell body ⑤ Silicon pressure sensor ⑥ Overload diaphragm ⑦ Fill liquid of the measuring cell ⑧ Reference pressure pe Pressure input variable

Absolute pressure is transmitted to the silicon pressure sensor ⑤ through the separating diaphragm ② and the fill fluid ⑦. When measuring limits are exceeded, the overload diaphragm ⑥ is displaced until the separating diaphragm ② rests on the measuring cell body ④. The separating diaphragm thus protects the silicon pressure sensor ⑤ from

overload. The pressure difference between the input pressure (pe) and the reference pressure ⑧ on the negative side of the measuring cell displaces the measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the absolute pressure.

3.5.3.63.5.3.63.5.3.63.5.3.6 Measuring cell for absolute pressure from the gauge pressure seriesMeasuring cell for absolute pressure from the gauge pressure seriesMeasuring cell for absolute pressure from the gauge pressure seriesMeasuring cell for absolute pressure from the gauge pressure series

Page 20: Transmitter AccuFLo-P DSIII series with HART-communication

Figure3-10 Function chart of measuring cell for absolute pressure ① Measuring cell ② Process connection ③ Separating diaphragm ④ Fill liquid ⑤ Absolute pressure sensor pe Input pressure

The input pressure (pe) is transferred to the absolute pressure sensor ⑤ via the separating

diaphragm ③ and the fill fluid ④, displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.

3.5.3.73.5.3.73.5.3.73.5.3.7 Measuring cell for gauge pressure, frontMeasuring cell for gauge pressure, frontMeasuring cell for gauge pressure, frontMeasuring cell for gauge pressure, front----flush membraneflush membraneflush membraneflush membrane

Figure3-11 Function chart of the measuring cell for gauge pressure, flush mounted diaphragm

Page 21: Transmitter AccuFLo-P DSIII series with HART-communication

① Reference pressure opening ② Measuring cell ③ Process connection ④ Separating diaphragm ⑤ Fill liquid ⑥ Gauge pressure sensor pe Input pressure

The input pressure (pe) is transferred to the gauge pressure sensor ⑥ via the separating diaphragm ④ and the fill fluid ⑤, displacing its measuring diaphragm. The displacement changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the

input pressure. Transmitters with measuring span ≤ 63 bar measure the input pressure against atmosphere, those with measuring spans ≥ 160 bar against vacuum.

Page 22: Transmitter AccuFLo-P DSIII series with HART-communication

3.5.3.83.5.3.83.5.3.83.5.3.8 Measuring cell for absolute pressure, frontMeasuring cell for absolute pressure, frontMeasuring cell for absolute pressure, frontMeasuring cell for absolute pressure, front----flush membraneflush membraneflush membraneflush membrane

Figure3-12 Function chart of the measuring cell for absolute pressure, flush mounted diaphragm ① Measuring cell ② Process connection ③ Separating diaphragm ④ Fill liquid ⑤ Absolute pressure sensor pe Input pressure

The input pressure (pe) is transferred to the absolute pressure sensor ⑤ via the separating diaphragm ③ and the fill fluid ④, displacing its measuring diaphragm. The displacement

changes the resistance value of the four piezo resistors in the measuring diaphragm in a bridge circuit. The change in the resistance causes a bridge output voltage proportional to the input pressure.

3.63.63.63.6 Remote sealRemote sealRemote sealRemote seal Product descriptionProduct descriptionProduct descriptionProduct description

A remote seal measuring system comprises the following elements:

• Remote seal

• Transmission line, e.g. capillary line

Page 23: Transmitter AccuFLo-P DSIII series with HART-communication

• Measuring device

Do not separate these components under any circumstance. The measuring system based

on a hydraulic principle is used to transfer pressure. The capillary line and the remote separating diaphragm are the most sensitive components in the remote seal measuring system. The material thickness of the remote separating diaphragm is only ~0.1 mm. The smallest of leakages in the transmission system leads to the loss of transmission fluid. The loss of transmission fluid leads to inaccuracies in the measurement and the failure of the

measuring system. In order to avoid leakages and measuring errors, please observe the following general installation and maintenance instructions in addition to the safety notes.

3.73.73.73.7 SIMATIC PDMSIMATIC PDMSIMATIC PDMSIMATIC PDM

SIMATIC PDM is a software package for the configuration, paramaterization, commissioning, diagnostics, and servicing of the device and other process devices. SIMATIC PDM includes simple process monitoring of process values, alarms, and device

status information. Using SIMATIC PDM, you can do the following with process device data:

• display

• set

• change

• compare

• check for plausibility

• administer

• simulate

Page 24: Transmitter AccuFLo-P DSIII series with HART-communication

4444 InstallInstallInstallInstall

4.14.14.14.1 Safety Safety Safety Safety notes for installationnotes for installationnotes for installationnotes for installation

ConditionConditionConditionCondition You can install the transmitter in different areas of application.

Depending on the area of application and the system configuration, there may be differences

in the installation.

WarningWarningWarningWarning

Protection against incorrect Protection against incorrect Protection against incorrect Protection against incorrect

Take particular care to ensure that the selected materials for the wetted parts are suitable for the process media used.

Ignoring these safety measures may cause bodily and lifeenvironment.

WarningWarningWarningWarning

"Intrinsically"Intrinsically"Intrinsically"Intrinsically----safe" protection typesafe" protection typesafe" protection typesafe" protection type

Information for operating the intrinsically

Operation is only permissible in certified intrinsicallycategory 1/2 and may be installed in Zone 0.

The EC-type examination certificate applies to installation of the device in the walls of containers and pipes in which explosive gas/air or vapor/air mixtures occur only under atmospheric conditions

(pressure: 0.8 bar to 1.1temperature is -40 °

The operator may use the device under nonthe EC-type examination certificate (or the certification applicable in the country of use) at the operator's own risk if safety measures which may be necessary in accordance with use conditions (explosive mixture) have been taken. The limit values specifi

be complied with in all cases.Additional information for zone 0Additional information for zone 0Additional information for zone 0Additional information for zone 0

notes for installationnotes for installationnotes for installationnotes for installation

You can install the transmitter in different areas of application. Depending on the area of application and the system configuration, there may be differences Protection against incorrect Protection against incorrect Protection against incorrect Protection against incorrect use of the measuring deviceuse of the measuring deviceuse of the measuring deviceuse of the measuring device

Take particular care to ensure that the selected materials for the wetted parts are suitable for the process media used.

Ignoring these safety measures may cause bodily and life-threatening injury and be harmful to the

safe" protection typesafe" protection typesafe" protection typesafe" protection type

Information for operating the intrinsically-safe version in hazardous areas:

Operation is only permissible in certified intrinsically-safe circuits. The transmitter corresponds to may be installed in Zone 0.

type examination certificate applies to installation of the device in the walls of containers and pipes in which explosive gas/air or vapor/air mixtures occur only under atmospheric conditions

bar to 1.1 bar; temperature: -20 °C to +60 °C). The permissible range of ambient °C to +85 °C; -40 °C to a maximum of +85 °C (at T4) in hazardous areas.

The operator may use the device under non-atmospheric conditions outside the limits specified in type examination certificate (or the certification applicable in the country of use) at the

operator's own risk if safety measures which may be necessary in accordance with use conditions (explosive mixture) have been taken. The limit values specified in the general technical data are to

be complied with in all cases.

Additional information for zone 0Additional information for zone 0Additional information for zone 0Additional information for zone 0

Depending on the area of application and the system configuration, there may be differences

Take particular care to ensure that the selected materials for the wetted parts are suitable for the

threatening injury and be harmful to the

safe version in hazardous areas:

safe circuits. The transmitter corresponds to

type examination certificate applies to installation of the device in the walls of containers and pipes in which explosive gas/air or vapor/air mixtures occur only under atmospheric conditions

C). The permissible range of ambient C (at T4) in hazardous areas.

atmospheric conditions outside the limits specified in type examination certificate (or the certification applicable in the country of use) at the

operator's own risk if safety measures which may be necessary in accordance with use conditions ed in the general technical data are to

Page 25: Transmitter AccuFLo-P DSIII series with HART-communication

Additional requirements apply for installation in zone 0:

The installation must be sufficiently tight (IP67 according to EN 60 529). For instance, an istandard (e.g. DIN, NPT) threaded connector is suitable.

When operating intrinsically safe supply units of category "ib" or in the case of device version flameproof enclosure "Ex

transmitter depends on the tightness of the sensor diaphragm. Under these operating conditions, the transmitter may only be used for such combustible gases and liquids for which diaphragms are sufficiently resistant to chemicals and corrosion.

CautionCautionCautionCaution

Touch protection is required for surface temperatures >

The touch protection must be designed in such a way that, if there is a buildup of heat, the maximum permissible ambient temperature at the device is not exceeded.

The permissible ambieCautionCautionCautionCaution

The device may only be used within the measuring spans, overload pressure limits and

voltage limits dependent on the protection type specified on the type plate.NoticeNoticeNoticeNotice

Install the device such that automatic emptying is ensured. For example, do not install the device at the bottom of the tank, instead of its side.

External loads may not be allowed to affect the transmitter as this may result in an incorrect

measured value or even destruction of the device. In the worst case scenario, the process medium will escape.

Additional requirements apply for installation in zone 0:

The installation must be sufficiently tight (IP67 according to EN 60 529). For instance, an istandard (e.g. DIN, NPT) threaded connector is suitable.

When operating intrinsically safe supply units of category "ib" or in the case of device version flameproof enclosure "Ex d" and simultaneous use in zone 0, the protection against explosion o

transmitter depends on the tightness of the sensor diaphragm. Under these operating conditions, the transmitter may only be used for such combustible gases and liquids for which diaphragms are sufficiently resistant to chemicals and corrosion.

Touch protection is required for surface temperatures > 70 °C.

The touch protection must be designed in such a way that, if there is a buildup of heat, the maximum permissible ambient temperature at the device is not exceeded.

The permissible ambient temperature can be found in the technical data.

The device may only be used within the measuring spans, overload pressure limits and

voltage limits dependent on the protection type specified on the type plate.

Install the device such that automatic emptying is ensured.

For example, do not install the device at the bottom of the tank, instead of its side.

External loads may not be allowed to affect the transmitter as this may result in an incorrect

lue or even destruction of the device. In the worst case scenario, the process medium will escape.

The installation must be sufficiently tight (IP67 according to EN 60 529). For instance, an industry

When operating intrinsically safe supply units of category "ib" or in the case of device version d" and simultaneous use in zone 0, the protection against explosion of the

transmitter depends on the tightness of the sensor diaphragm. Under these operating conditions, the transmitter may only be used for such combustible gases and liquids for which diaphragms are

The touch protection must be designed in such a way that, if there is a buildup of heat, the maximum

nt temperature can be found in the technical data.

The device may only be used within the measuring spans, overload pressure limits and

voltage limits dependent on the protection type specified on the type plate.

For example, do not install the device at the bottom of the tank, instead of its side.

External loads may not be allowed to affect the transmitter as this may result in an incorrect

lue or even destruction of the device. In the worst case scenario, the process

Page 26: Transmitter AccuFLo-P DSIII series with HART-communication

4.24.24.24.2 InstallationInstallationInstallationInstallation

4.2.14.2.14.2.14.2.1 Instructions for installationInstructions for installationInstructions for installationInstructions for installation

ConditionsConditionsConditionsConditions

NoticeNoticeNoticeNotice

Compare the desired operating data with the data on the type plate.

NoticeNoticeNoticeNotice

The housing may only be opened for maintenance or to make electrical connections.

NoteNoteNoteNote

Protect the transmitter against:

• Direct heat radiation

• Rapid temperature fluctuations

• Heavy contamination

• Mechanical damage

The installation location is to be as follows:

• Easily accessible

• As close as possible to the measuring point

• Vibration-free

• Within the permitted ambient temperature values

Installation configurationInstallation configurationInstallation configurationInstallation configuration

The transmitter may in principle be configured above or below the pressure tapping point. The recommended configuration depends on the medium.

Installation configuration for gasesInstallation configuration for gasesInstallation configuration for gasesInstallation configuration for gases

Install the transmitter above the pressure tapping point.

Lay the pressure tubing with a constant gradient to the pressure tapping point, so that any condensate produced can drain in the main line and thereby avoid corruption of the measured values.

Installation configuration for vapor and liquidInstallation configuration for vapor and liquidInstallation configuration for vapor and liquidInstallation configuration for vapor and liquid

Page 27: Transmitter AccuFLo-P DSIII series with HART-communication

Install the transmitter below the pressure tapping point.

Lay the pressure tubing with a constant gradient to the pressure tapping point so that any gas pockets can escape in the main line.

4.2.24.2.24.2.24.2.2 InstallationInstallationInstallationInstallation

NoticeNoticeNoticeNotice

When installing the process connection of the pressure transmitter, do not turn it on the housing.

ProcedureProcedureProcedureProcedure

To install the transmitter for pressure or absolute pressure, proceed as follows:

Attach the transmitter to the process connection with an appropriate tool.

See alsoSee alsoSee alsoSee also

Introduction to commissioning

4.2.34.2.34.2.34.2.3 FasteningFasteningFasteningFastening

Fastening without the mounting bracketFastening without the mounting bracketFastening without the mounting bracketFastening without the mounting bracket

You can fasten the transmitter directly on the process connection.

Fastening with the mounting bracketFastening with the mounting bracketFastening with the mounting bracketFastening with the mounting bracket

You can fasten the mounting bracket as follows:

• On a wall or a mounting frame using two screws

• On a vertical or horizontal mounting tube (Ø 50 to 60 mm) using a tube bracket

Fasten the transmitter mounting bracket using the two screws provided.

Page 28: Transmitter AccuFLo-P DSIII series with HART-communication

Figure4-1 Fastening the transmitter on the mounting bracket

Figure4-2 An example of fastening the transmitter on the mounting bracket in the case of differential pressure and horizontal differential pressure lines

Page 29: Transmitter AccuFLo-P DSIII series with HART-communication

Figure4-3 An example of fastening on the mounting bracket in the case of differential pressure and vertical differential pressure lines

4.54.54.54.5 TurTurTurTurnnnning the measuring cell against housinging the measuring cell against housinging the measuring cell against housinging the measuring cell against housing

DescriptionDescriptionDescriptionDescription You can turn the measuring cell against the housing. Turning simplifies the transmitter operation in the case of an angled installation environment. The buttons and the current

connection can thus also be operated for an external measuring device. The digialso remains visible in the case of housing covers with an inspection window.

Only limited turning is permissible! The turning range electronic housing. An orientation mark This mark must remain in the marked section when turning.

Figure4-7 Example: turning range of transmitters for pressure and absolute pressure from the gauge pressure series

An example of fastening on the mounting bracket in the case of differential pressure and vertical differential pressure lines

ing the measuring cell against housinging the measuring cell against housinging the measuring cell against housinging the measuring cell against housing

You can turn the measuring cell against the housing. Turning simplifies the transmitter operation in the case of an angled installation environment. The buttons and the current

connection can thus also be operated for an external measuring device. The digialso remains visible in the case of housing covers with an inspection window.

Only limited turning is permissible! The turning range ① is marked at the foot of the electronic housing. An orientation mark ③ is provided at the throat of the measThis mark must remain in the marked section when turning.

Example: turning range of transmitters for pressure and absolute pressure from the gauge pressure series

An example of fastening on the mounting bracket in the case of differential pressure

You can turn the measuring cell against the housing. Turning simplifies the transmitter operation in the case of an angled installation environment. The buttons and the current

connection can thus also be operated for an external measuring device. The digital display also remains visible in the case of housing covers with an inspection window.

is marked at the foot of the is provided at the throat of the measuring cell.

Example: turning range of transmitters for pressure and absolute pressure from the

Page 30: Transmitter AccuFLo-P DSIII series with HART-communication

① Turning range ② Retaining screw ③ Orientation mark

The turning range for transmitters for differential pressure and flow rate, absolute pressure from the differential pressure series and level is identified in a similar manner.

ProcedureProcedureProcedureProcedure CautionCautionCautionCaution Follow the turning range, otherwise electrical connections of the measuring cell may get damaged.

1. Loosen the retaining screw ② (Allen screw 2.5 mm). 2. Turn the electronic housing against the measuring cell. Follow the marked turning range ① while

doing so. 3. Tighten the retaining screw (torque: 3.4 to 3.6 Nm).

Page 31: Transmitter AccuFLo-P DSIII series with HART-communication

4.64.64.64.6 Turning the digital displayTurning the digital displayTurning the digital displayTurning the digital display DescriptionDescriptionDescriptionDescription

You can rotate the digital display in the electronic housing. You can then read the digital display better when the device is not operated in a vertical installation position.

ProcedureProcedureProcedureProcedure

Proceed as follows:

1. Unscrew the housing cover of the electronic compartment.

2. Unscrew the digital display. Depending on the application position of the transmitter, you can reinstall it at four different positions. You can turn it by ±90° or ±180°.

3. Screw the housing cover back into place.

Page 32: Transmitter AccuFLo-P DSIII series with HART-communication

5555 ConnectingConnectingConnectingConnecting

5.15.15.15.1 Safety notes for connectionSafety notes for connectionSafety notes for connectionSafety notes for connection

WarningWarningWarningWarning

When connecting and installing, follow only the test certifications, stipulations and laws applicable in your country.

For example, for hazardous areas these are:

• IEC 60079-14 (international)

• National Electrical Code (NEC

• Canadian Electrical Code (CEC) (Canada)

• EN 60079-14 (earlier VDE

• Ordinance on Industrial Safety and Health

WarningWarningWarningWarning

If auxiliary power is required, check that it corresponds with that on the type plate and with the test certification valid for your country.

WarningWarningWarningWarning

Replace the sealing caps in cable entries with suitable cable glands or NoteNoteNoteNote

To improve the reliability:

• Install the signal cable separately from cables with voltages > 60 V.

• Use cable with twisted strands.

• Stay away from large electrical systems.

• Use shielded cable to guarantee the full specification

• Connect a load of at least 230 ohm into the signal circuit in sequence in order to guarantee faultHART communication. When using supply isolation for SMART transmitters, for example:

7NG4021 a load is already installed in the d

Safety notes for connectionSafety notes for connectionSafety notes for connectionSafety notes for connection

When connecting and installing, follow only the test certifications, stipulations and laws applicable in

hazardous areas these are:

14 (international)

National Electrical Code (NEC - NFPA 70) (USA)

Canadian Electrical Code (CEC) (Canada)

14 (earlier VDE 0165, T1) (EU, Germany)

Ordinance on Industrial Safety and Health (Germany)

If auxiliary power is required, check that it corresponds with that on the type plate and with the test certification valid for your country.

Replace the sealing caps in cable entries with suitable cable glands or blanking

To improve the reliability:

Install the signal cable separately from cables with voltages > 60 V.

Use cable with twisted strands.

Stay away from large electrical systems.

Use shielded cable to guarantee the full specification according to HART.

Connect a load of at least 230 ohm into the signal circuit in sequence in order to guarantee faultHART communication. When using supply isolation for SMART transmitters, for example:

7NG4021 a load is already installed in the device.

When connecting and installing, follow only the test certifications, stipulations and laws applicable in

If auxiliary power is required, check that it corresponds with that on the type plate and with the test

blanking.

Connect a load of at least 230 ohm into the signal circuit in sequence in order to guarantee fault-free HART communication. When using supply isolation for SMART transmitters, for example:

Page 33: Transmitter AccuFLo-P DSIII series with HART-communication

5.25.25.25.2 Connecting the deviceConnecting the deviceConnecting the deviceConnecting the device ProcedureProcedureProcedureProcedure

To connect the device, proceed as follows:

1. Unscrew the cover of the electrical cable compartment.

An identification text "FIELD TERMINAL" is provided at the side of the housing.

2. Insert the connecting cable through the cable gland.

3. Connect the wires to the connecting terminals "+" and "-".

Observe the polarity when doing this.

4. Place a shield on the shield support screw if required. This is electrically connected with the external protective conductor connection.

5. Screw the cover back into place.

Page 34: Transmitter AccuFLo-P DSIII series with HART-communication

Figure5-1 Schematic electrical connection

① Feed separator with integrated load

② Auxiliary power

③ Cable entry for auxiliary power/analog output

④ Connecting terminals

⑤ Test connector for

Schematic electrical connection

Feed separator with integrated load Auxiliary power Cable entry for auxiliary power/analog output Connecting terminals Test connector for direct current measuring device or connection for external display

direct current measuring device or connection for external display

Page 35: Transmitter AccuFLo-P DSIII series with HART-communication

⑥ Shield support ⑦ Protective conductor connection/equipotential bonding terminal ⑧ Cable entry for sensor signals

5.35.35.35.3 Connecting the Han plugConnecting the Han plugConnecting the Han plugConnecting the Han plug IntroductionIntroductionIntroductionIntroduction

The contact parts for the coupling socket are also supplied. ProcedureProcedureProcedureProcedure

To connect the plug, proceed as follows:

1. Slide the sleeve and the screwed joint on the cable.

2. Strip approx. 8 mm of the cable ends.

3. Crimp the contact parts on the cable ends.

4. Assemble the coupling socket.

Figure5-2 Connector pin

assignment with Han 7D or Han 8U plug

IA Output current UH Auxiliary power

5.45.45.45.4 Connecting the M12 connectorConnecting the M12 connectorConnecting the M12 connectorConnecting the M12 connector ProcedureProcedureProcedureProcedure

Page 36: Transmitter AccuFLo-P DSIII series with HART-communication

CautionCautionCautionCaution

A conductive connection should not exist between the shield and the

For devices in which a connector is already assembled on the housing, the connection is established using a jack coupling.

1. Thread the parts of the jack coupling as described by the connector manufacturer.

2. Strip approximately 18

3. Twist the shield.

4. Thread the shield in the insulating sleeve.

5. Draw 8 mm of shrink sleeve over the cable, wires and shield up to the reference edge

6. Screw the cable ends and the shield in the pin insert.

7. Fix the parts of the jack coupling as described by the connector manufacturer.

Figure5-3 Preparing the fieldbus cable

① Reference edge for stripping

② Reference edge for the dimension specifications for cable assembly

A conductive connection should not exist between the shield and the connector housing.

For devices in which a connector is already assembled on the housing, the connection is established using a jack coupling.

Thread the parts of the jack coupling as described by the connector manufacturer.

Strip approximately 18 mm of the bus cable ①.

Thread the shield in the insulating sleeve.

mm of shrink sleeve over the cable, wires and shield up to the reference edge

Screw the cable ends and the shield in the pin insert.

parts of the jack coupling as described by the connector manufacturer.

Preparing the fieldbus cable

Reference edge for stripping ③ Insulating sleeve over the shield

Reference edge for the dimension specifications for cable assembly

④ Shrink sleeve

connector housing.

For devices in which a connector is already assembled on the housing, the connection is

Thread the parts of the jack coupling as described by the connector manufacturer.

mm of shrink sleeve over the cable, wires and shield up to the reference edge ②.

parts of the jack coupling as described by the connector manufacturer.

Insulating sleeve over the shield

Page 37: Transmitter AccuFLo-P DSIII series with HART-communication

Pin assignmentPin assignmentPin assignmentPin assignment

Figure5-4 Layout for M12 connector

Figure5-5 Layout for M12 jack

① M12 x 1 thread ① Positioning slot ② Positioning catch 1 + 1 + 2 Not connected 2 Not connected 3 - 3 - 4 Shield 4 Shield

Middle jack not assembled

Page 38: Transmitter AccuFLo-P DSIII series with HART-communication

6666 OperationOperationOperationOperation

6.16.16.16.1 Overview of operationOverview of operationOverview of operationOverview of operation IntroductionIntroductionIntroductionIntroduction

The following description contains an overview of the operating functions that you can execute using the pressure transmitter, and the safety notes that are to be observed when

doing so. You can operate the transmitter on-site through HART communication. First, the on-site operation and then, the operating functions using HART are described.

Contents of the chapterContents of the chapterContents of the chapterContents of the chapter

• Safety information for operation

• Instructions for operation

• Digital display

• Local operation

Overview of operating functionsOverview of operating functionsOverview of operating functionsOverview of operating functions

You can configure basic settings of the pressure transmitter using the buttons on the device. You can configure all settings through HART communication.

The following table describes the basic operating functions. More operating functions for special applications are accessible through HART. Basic variablesBasic variablesBasic variablesBasic variables of the device are marked in bold.

Table6-1 Operating functions

FunctionFunctionFunctionFunction Using buttonsUsing buttonsUsing buttonsUsing buttons Using HARTUsing HARTUsing HARTUsing HART

Start of scale valueStart of scale valueStart of scale valueStart of scale value Yes Yes

Full scale valueFull scale valueFull scale valueFull scale value Yes Yes

Electrical damping Yes Yes

Blind adjustment of the start of scale Yes Yes

Page 39: Transmitter AccuFLo-P DSIII series with HART-communication

FunctionFunctionFunctionFunction Using buttonsUsing buttonsUsing buttonsUsing buttons Using HARTUsing HARTUsing HARTUsing HART

value

Blind adjustment of the full scale value Yes Yes

Zero point calibration (position Zero point calibration (position Zero point calibration (position Zero point calibration (position correction)correction)correction)correction)

Yes Yes

Current transmitter Yes Yes

Fault currentFault currentFault currentFault current Yes Yes

Keyboard lock and write protection Yes Yes, release except for write protection

Unit type, unit Yes Yes

Characteristic curve (lin., rad.)

(Not relevant for absolute

and gauge pressure)

Yes Yes

Customized characteristic curve No Yes

Diagnostic function No Yes

More operating functions for special applications are accessible through HART.

If a device that does not have a digital display, its operations are limited. This is however not applicable for selecting functions using HART.

6.26.26.26.2 Safety information for operationSafety information for operationSafety information for operationSafety information for operation

NoticeNoticeNoticeNotice If you have set the basic functions of the pressure transmitter as user defined, the display and measurement output terminal can be adjusted such that the true process pressure is not reproduced. The basic variables should therefore be checked prior to commissioning.

Page 40: Transmitter AccuFLo-P DSIII series with HART-communication

6.36.36.36.3 Instructions for operationInstructions for operationInstructions for operationInstructions for operation

The following rules are applicable for the operation of the pressure transmitter:

• The device counts numerical values always in anleast significant digit displayed.

If you keep the button pressed for a longer time, it counts the next higher digit displayed. This procedure is used for fast coarse adjustment over a wide number range. Relebutton again for fine adjustment. Press the button again.

Violations of the measured value limits are displayed on the digital display with

or

.

• The keyboard must have been unlocked in order to operate the device using the

• If you are operating the transmitter locally, write access is denied through HART during this time.

However, it is always possible to read the data, e.g. measured values.NoteNoteNoteNote

The setting is saved and the measured values are automatically than two minutes have passed after a button was pressed for the last time.

The operating instructions mentioned in the "Local operation without digital display" chapter are applicable if the device has been delivered with a blind co

6.46.46.46.4 Digital displayDigital displayDigital displayDigital display

Instructions for operationInstructions for operationInstructions for operationInstructions for operation The following rules are applicable for the operation of the pressure transmitter:

The device counts numerical values always in an ascending order step by step starting from the least significant digit displayed.

If you keep the button pressed for a longer time, it counts the next higher digit displayed. This procedure is used for fast coarse adjustment over a wide number range. Relebutton again for fine adjustment. Press the button again.

Violations of the measured value limits are displayed on the digital display with

The keyboard must have been unlocked in order to operate the device using the

If you are operating the transmitter locally, write access is denied through HART during this time.

However, it is always possible to read the data, e.g. measured values.

The setting is saved and the measured values are automatically displayed again if more than two minutes have passed after a button was pressed for the last time.

The operating instructions mentioned in the "Local operation without digital display" chapter are applicable if the device has been delivered with a blind co

The following rules are applicable for the operation of the pressure transmitter: ascending order step by step starting from the

If you keep the button pressed for a longer time, it counts the next higher digit displayed. This procedure is used for fast coarse adjustment over a wide number range. Release the [↑] or [↓]

Violations of the measured value limits are displayed on the digital display with

The keyboard must have been unlocked in order to operate the device using the keyboard.

If you are operating the transmitter locally, write access is denied through HART during this time.

displayed again if more than two minutes have passed after a button was pressed for the last time.

The operating instructions mentioned in the "Local operation without digital display" chapter are applicable if the device has been delivered with a blind cover.

Page 41: Transmitter AccuFLo-P DSIII series with HART-communication

6.4.16.4.16.4.16.4.1 Elements of the digital displayElements of the digital displayElements of the digital displayElements of the digital display

StructureStructureStructureStructure

Figure6-1 Structure of the digital display

① Measured value ⑤ Violation of lower limit ② Unit/bar graph ⑥ Symbol for measured value ③ Root display ⑦ Violation of higher limit ④ Mode/button lock ⑧ Communication display

DescriptionDescriptionDescriptionDescription The digital display is used for local display of the measured value ① with:

• Unit ②

• Mode ④

• Sign ⑥

• Statuses ⑤ and ⑦

Depending on the customer setting, the displayed measured value ① represents the following:

• The current emitted by the transmitter

• The percentage measurement value of the adjusted measurement type, e.g. level, related to the adjusted measurement range.

• The measurement value in a selectable physical unit

Page 42: Transmitter AccuFLo-P DSIII series with HART-communication

The Violation of lower limit ⑤ and Violation of upper limit ⑦ displays are also referred to as status since they have meanings dependent on the settings.

If the communication display ⑧ blinks, this indicates an active communication.

6.4.26.4.26.4.26.4.2 Units displayUnits displayUnits displayUnits display

DescriptionDescriptionDescriptionDescription

The unit display comprises five 14-segment fields for representing the unit as a percentage value, physical unit or current value. A bar graph showing the percentage measured value range from 0 to 100% can be displayed as an alternative to the unit. The bar graph function is

disabled by default.

DisplayDisplayDisplayDisplay

Figure6-2 Examples for measured value display for current and bar graph

The following messages may appear as a ticker in the bottom line of the digital display. They have no influence on the current output.

Table6-2 Message as ticker

TickerTickerTickerTicker MeaningMeaningMeaningMeaning

"DIAGNOSTIC WARNING" Is always displayed if:

• An event configured by the user is to be signaled with a warning.

― Limit reached

― Event counter for limit values exceeded

― Calibration time expired

― Current saturation reached

• The status of one of the device variables is "UNCERTAIN".

"SIMULATION" Is always displayed when the simulation of a pressure value or

Page 43: Transmitter AccuFLo-P DSIII series with HART-communication

TickerTickerTickerTicker MeaningMeaningMeaningMeaning

temperature value is active.

See alsoSee alsoSee alsoSee also

Measured value status

6.4.36.4.36.4.36.4.3 Error displayError displayError displayError display

DescriptionDescriptionDescriptionDescription

If hardware faults, software errors or diagnostic alarms occur in the transmitter, the message "Error" appears in the measured value display.

A ticker appears in the lower line of the digital display indicating the type of error. This

diagnostic information is also available via HART communication.

DisplayDisplayDisplayDisplay

Figure6-3 Example of error message

The following messages may appear as a ticker in the bottom line of the digital display.

TickerTickerTickerTicker MeaningMeaningMeaningMeaning

"HARDWARE FIRMWARE ALARM" Contains hardware faults such as:

• incorrect checksum

• incorrect EEPROM data

• Defective EEROM

• RAM fault

• ROM fault

• inconsistent data

• EEPROMs not initialized

Page 44: Transmitter AccuFLo-P DSIII series with HART-communication

TickerTickerTickerTicker MeaningMeaningMeaningMeaning

"DIAGNOSTIC ALARM" Is always displayed if

• an event configured by the user is to be signaled with an alarm.

For example:

― Limit reached

― Event counter for limit values exceeded

― Calibration time expired

― Current saturation reached

• the status of one of the device variables is "BAD".

"SENSOR BREAK" Appears when there is a sensor break.

See alsoSee alsoSee alsoSee also

Measured value status

6.4.46.4.46.4.46.4.4 Mode displayMode displayMode displayMode display

DescriptionDescriptionDescriptionDescription

The selected active mode is shown in the mode display.

DisplayDisplayDisplayDisplay

Figure6-4 Example for mode display

In the example, a damping of 0.2 seconds was set in mode 4.

6.4.56.4.56.4.56.4.5 Status displayStatus displayStatus displayStatus display

DescriptionDescriptionDescriptionDescription

The arrows of the status display have a different meaning depending on the mode setting. The table below shows the meanings of the arrows in the respective functions.

Page 45: Transmitter AccuFLo-P DSIII series with HART-communication

MeaningMeaningMeaningMeaning

Table6-3 Meaning of the arrow displays

FunctionFunctionFunctionFunction

Adjusting start of scale value

Adjusting full scale value

Adjusting damping

Blind adjustment of the start of scale value

Blind adjustment of the full scale value

Position correction

Root application point

Keyboard operation

Normal operation

6.4.66.4.66.4.66.4.6 Overflow rangeOverflow rangeOverflow rangeOverflow range

Meaning of the arrow displays

ModeModeModeMode DisplayDisplayDisplayDisplay

DisplayDisplayDisplayDisplay

2 if the upper current limit is exceeded if the value falls below the lower current limit

3 if the upper current limit is exceeded if the value falls below the lower current limit

4 if the upper damping value is exceeded

only for the pressure device version

if the value falls below the lower damping value only for the prversion

5 if the upper sensor limit is exceeded if the value falls below the lower sensor limit

6 if the upper sensor limit is exceeded if the value fallssensor limit

7 if the max span is exceeded by more than 5% of the upper current limit

if the value falls below the lower current limit

Root application point 12 if the root application point of 15% is exceeded

if the value falls below the root application point of 5%

2, 3, 5, 6

when the span to be adjusted is larger than the maximum span

when the span to be adjusted is smaller than the minimum span

Current exceeds the upper saturation limit

Pressure exceeds the upper sensor limit.

Current falls below the lower saturation limit Pressure falls below the lower sensor limit.

if the value falls below the lower current limit

if the value falls below the lower current limit

if the value falls below the lower damping value

only for the pressure device

if the value falls below the lower sensor limit

if the value falls below the lower sensor limit

if the value falls below the lower current limit

value falls below the root application point of 5%

when the span to be adjusted is smaller than the minimum span

Current falls below the lower saturation limit

Pressure falls below the lower sensor limit.

Page 46: Transmitter AccuFLo-P DSIII series with HART-communication

DescriptionDescriptionDescriptionDescription The output signal is divided into defined ranges:

• Measuring range

• Saturation limits

• Fault current

The transmitter emits the output current according to the device variables selected as primary

variable (PV). The working range of the current lies

MeaningMeaningMeaningMeaning

When the measurement limits are exceeded or not reached, the measured values are correctly displayed in the overflow range.

A ticker is displayed in the lower line of the digital display showing the message UNDER or OVER with respect to the selected unit. The possible overflow range can be adjusted via HART communication. If either of the overflow limits are violated, the outpu

constant. Violations of the measured value limits are displayed on the digital display with

or

.

NoteNoteNoteNote

The setting of the overflow range and the fault current range can be freely selected via HART communication.

ReferenceReferenceReferenceReference

NAMUR recommendation NE43 dated 03.02.2003

"Standardization of the signal level for the breakdown information of digital transmitters"

See alsoSee alsoSee alsoSee also

Fault current

Setting the current limits

The output signal is divided into defined ranges:

The transmitter emits the output current according to the device variables selected as primary

variable (PV). The working range of the current lies between 4 mA and 20 mA.

When the measurement limits are exceeded or not reached, the measured values are correctly displayed in the overflow range.

A ticker is displayed in the lower line of the digital display showing the message UNDER or OVER with respect to the selected unit. The possible overflow range can be adjusted via HART communication. If either of the overflow limits are violated, the outpu

constant. Violations of the measured value limits are displayed on the digital display with

The setting of the overflow range and the fault current range can be freely selected via HART

recommendation NE43 dated 03.02.2003

"Standardization of the signal level for the breakdown information of digital transmitters"

Setting the current limits

The transmitter emits the output current according to the device variables selected as primary

between 4 mA and 20 mA.

When the measurement limits are exceeded or not reached, the measured values are

A ticker is displayed in the lower line of the digital display showing the message UNDER or OVER with respect to the selected unit. The possible overflow range can be adjusted via HART communication. If either of the overflow limits are violated, the output current remain

constant. Violations of the measured value limits are displayed on the digital display with

The setting of the overflow range and the fault current range can be freely selected via HART

"Standardization of the signal level for the breakdown information of digital transmitters"

Page 47: Transmitter AccuFLo-P DSIII series with HART-communication

6.56.56.56.5 Local operationLocal operationLocal operationLocal operation

6.5.16.5.16.5.16.5.1 Local control elementsLocal control elementsLocal control elementsLocal control elements

IntroductionIntroductionIntroductionIntroduction

The transmitter can be operatedchoose and execute the functions described in the table. The number of functions is limited if the device does not have a digital display.

Control elementsControl elementsControl elementsControl elements

Figure6-5 Position of buttons and

➀ Digital display

➂ Mode button ➄ Decrement button

Operating functionsOperating functionsOperating functionsOperating functions NoticeNoticeNoticeNotice Zero point calibrationZero point calibrationZero point calibrationZero point calibration

For absolute pressure transmitters, the start of scale value is at

Local control elementsLocal control elementsLocal control elementsLocal control elements

The transmitter can be operated on-site using the buttons. Selectable modes can be used to choose and execute the functions described in the table. The number of functions is limited if the device does not have a digital display.

Position of buttons and digital display

Digital display ➁ Connecting plug for the digital display

➃ Increment button Decrement button

Zero point calibrationZero point calibrationZero point calibrationZero point calibration For absolute pressure transmitters, the start of scale value is at vacuum.

site using the buttons. Selectable modes can be used to choose and execute the functions described in the table. The number of functions is limited if

Connecting plug for the digital display

vacuum.

Page 48: Transmitter AccuFLo-P DSIII series with HART-communication

A zero point calibration with transmitters which do not measure absolute pressure leads to faulty settings.

Table6-4Operating functions using buttons

FunctionFunctionFunctionFunction ModeModeModeMode Button functionButton functionButton functionButton function Display, explanationsDisplay, explanationsDisplay, explanationsDisplay, explanations

[M][M][M][M] [[[[↑↑↑↑]]]] [[[[↓↓↓↓]]]] [[[[↑↑↑↑] and [] and [] and [] and [↓↓↓↓]]]]

Measured value The modes are selected here.

The current measured value is displayed as you have adjusted it in the "Measured value display, mode 13" function.

Start of scale value (only in "Pressure" measuring mode)

2 Current higher

Current lower

Set to 4 mA Output current in mA

Full scale value (only in "Pressure" measuring mode)

3 Current higher

Current lower

Set to 20 mA Output current in mA

Electrical damping 4 Damping higher

Damping lower

Set to 0 Time constant T63 in seconds

Adjustment range: 0.0 s to 100.0 s

Start of scale value in the so-called blind adjustment

5 Pressure higher

Pressure lower

Set the start of scale value to 0

Start of scale value in the selected pressure unit

Full scale value in the so-called blind adjustment

6 Pressure higher

Pressure lower

Set the full scale value to upper measuring limit

Full scale value in the selected pressure unit

Zero point calibration (position correction)

7 Correction value higher

Correction value lower

execute Ventilate the transmitter for gauge pressure, differential pressure, flow rate or level.

Evacuate the transmitter for absolute pressure (< 0.1 ‰ of the measuring span).

(Start of scale value remains unaffected)

Measured value in pressure unit

Page 49: Transmitter AccuFLo-P DSIII series with HART-communication

FunctionFunctionFunctionFunction ModeModeModeMode Button functionButton functionButton functionButton function Display, explanationsDisplay, explanationsDisplay, explanationsDisplay, explanations

[M][M][M][M] [[[[↑↑↑↑]]]] [[[[↓↓↓↓]]]] [[[[↑↑↑↑] and [] and [] and [] and [↓↓↓↓]]]]

Current transmitter 8 Current higher

Current lower

switch on constant output current in mA

"3.6"; "4", "12", "20" or "22.8"

Switch off using the [M] button.

Output current in case of fault

9 Switch between lower fault current and upper fault current.

lower fault current

selected output current possible: Fault current limits adjusted by user

Button lock or function lock

10 Switch between the five functions

– 0 None

LA all locked

LO all locked except for start of scale value

LS all locked except for start of scale value and full scale value

L Write protection

Operation via HART not possible.

Characteristic curve1) 11 Switch between the four functions

linear lin linear

srlin square root extracting (linear up to the application point)

sroff Square root extracting

(deactivated up to the application point)

srli2 square root extracting (linear up to the application point 10%)

Application point of the square root extracting characteristic curve1)

12 Greater Smaller 10% flow rate Adjustment range of 5 to 15% flow rate.

Measured value display

13 Select from three options.

• Display type (input value)

• Output current in mA

• Measured value in %

Page 50: Transmitter AccuFLo-P DSIII series with HART-communication

FunctionFunctionFunctionFunction ModeModeModeMode Button functionButton functionButton functionButton function Display, explanationsDisplay, explanationsDisplay, explanationsDisplay, explanations

[M][M][M][M] [[[[↑↑↑↑]]]] [[[[↓↓↓↓]]]] [[[[↑↑↑↑] and [] and [] and [] and [↓↓↓↓]]]]

Unit 14 Select from the table for measured value display.

In each case, the first value from the table of the physical unit

Physical unit

1) Not relevant for gauge and absolute pressure)

See alsoSee alsoSee alsoSee also

Overview of operation

Operating functions through HART communication

6.5.26.5.26.5.26.5.2 Operation using buttonsOperation using buttonsOperation using buttonsOperation using buttons

IntroductionIntroductionIntroductionIntroduction

This overview informs you about the most important safety notes to be observed when operating the pressure transmitter. Furthermore, the overview guides you in adjusting the operating functions on site.

ConditionConditionConditionCondition

The keyboard must have been unlocked in order to operate the device using the buttons.

ProcedureProcedureProcedureProcedure

In the default setting, the device is in the measured value display.

To adjust the operating functions, proceed as follows:

1. Loosen both the screws of the keyboard cover and lift it upwards.

2. Keep pressing the [M] button until the desired mode is displayed.

3. Keep pressing the [↑] or [↓] button until the desired value is displayed.

4. Press the [M] button.

Now you have saved the values and the device goes to the next mode.

5. Close the keyboard cover using the two screws.

Page 51: Transmitter AccuFLo-P DSIII series with HART-communication

NoteNoteNoteNote

The setting is saved and the measured values are automatically displayed again if more

than two minutes have passed after a button was pressed for the last time.

See alsoSee alsoSee alsoSee also

Releasing key lock or function lock

6.5.36.5.36.5.36.5.3 Start of scale value/full scale valueStart of scale value/full scale valueStart of scale value/full scale valueStart of scale value/full scale value

6.5.3.16.5.3.16.5.3.16.5.3.1 Difference between setting and adjustingDifference between setting and adjustingDifference between setting and adjustingDifference between setting and adjusting

IntroductionIntroductionIntroductionIntroduction

In "Pressure" measuring mode, you can set or adjust the start of scale value and full scale value using the buttons. Modes 2 and 3 are used for this. Rising and falling characteristic

curves can be realized with appropriate use of the buttons. If the transmitter is not in "Pressure" measuring mode, this mode is skipped in local operation.

DifferenceDifferenceDifferenceDifference

The difference between setting and adjusting lies in the calculation.

Setting with reference pressureSetting with reference pressureSetting with reference pressureSetting with reference pressure

Condition

Two reference pressures pr1 and pr2 are available. The reference pressures are initialized by the process or generated by a pressure sensor.

When setting, a desired start of scale value or a full scale value is allocated to the standard current values (4 mA or 20 mA). After setting, the measuring span entered on the type plate may no longer correspond with the adjustment.

Depending on the series and measuring range, a maximum downscaling of 1:100 can be achieved (measuring span ratio = r, turn down).

NoteNoteNoteNote

Setting the start of scale value does not change the measuring span. Setting the full scale value does not change the start of scale value.

The start of scale value should therefore be set first, then the full scale value.

Page 52: Transmitter AccuFLo-P DSIII series with HART-communication

The correlation between the measured pressure and the output current generated is linear.

The square root extracting characteristic curve for differential pressure transmitters is an exception. Calculate the output current using the following formula.

Figure6-6 Current calculation formula for setting

I Output current MAactual Old start of scale value p Pressure MEactual Old full scale value MA Start of scale value MAtarget New start of scale value ME Full scale value MEtarget New full scale value

Example of setting with reference pressureExample of setting with reference pressureExample of setting with reference pressureExample of setting with reference pressure A Initial situation

B Setting start of scale value C Setting full scale value

Explanations for the example of setting with reference pressure A The measuring range is from 0 to 16 bar. You are changing the start of scale value from 0 to 2 bar

and the full scale value from 16 to 14 bar. The measuring span is then 12 bar. B 2 bar process pressure is created.

Use the [M] button to set the transmitter to mode 2. To set the start of scale value, press the [↑]

Page 53: Transmitter AccuFLo-P DSIII series with HART-communication

and [↓] buttons simultaneously for 2 seconds. If there is 2 bar input pressure, the transmitter produces an output current of 4 mA.

C 14 bar process pressure is created. Use the [M] button to set the transmitter to mode 3. To set the full scale value, press the [↑] and [↓] buttons simultaneously for 2 seconds. If there is 14 bar input pressure, the transmitter produces an output current of 20 mA.

D The output current can be calculated for any input pressure using the "current calculation formula for setting".

NoteNoteNoteNote If the value exceeds or falls below the preset measuring limits by more than 20% when setting, the setting function is not carried out. The old value is retained in this case. With a marked elevation of the zero point, the full scale value must therefore previously be reduced such that it still lies within the permitted range after elevation of the zero point. This setting function is only possible in "Pressure" measuring mode.

Adjusting with reference pressureAdjusting with reference pressureAdjusting with reference pressureAdjusting with reference pressure Condition: The reference pressure, the adjusted start of scale value and adjusted full scale value are known. When adjusting, a start of scale value or a full scale value can be allocated to a desired current value with the aid of a reference pressure. This function is particularly suitable when the required pressures for the start of scale value and the full scale value are not available After adjustment, the measuring range specified on the type plate may no longer correspond with the setting. Using the formulae below, the current to be set for the desired start of scale value and the full scale value can be calculated. To calculate the output currents when setting the start of scale value or the full scale value, the reference pressure must be selected such that a value between 4 and 20 mA results for the current.

Page 54: Transmitter AccuFLo-P DSIII series with HART-communication

Figure6-7 Current calculation formula for setting with reference pressure I Output current MAactual Old start of scale value IMA Current to be adjusted with MAtarget MEactual Old full scale value IME Current to be adjusted with MEtarget MAtarget New start of scale value p Pressure MEtarget New full scale value pref Existing reference pressure

Example of adjusting with reference pressureExample of adjusting with reference pressureExample of adjusting with reference pressureExample of adjusting with reference pressure A Initial situation

B Calculating start of scale value C Calculating full scale value

Explanations for the example of adjusting with reference pressure A The measuring range is from 0 to 16 bar. You are changing the start of scale value from 0 to 2 bar

and the full scale value from 16 to 14 bar. The measuring span is then 12 bar. A reference pressure of 11 bar is created.

B Use the [M] button to set the transmitter to mode 2. The "Current calculation formula for adjusting with reference pressure" can be used to calculate

Page 55: Transmitter AccuFLo-P DSIII series with HART-communication

the current to be adjusted for the desired start of scale value IMA (13 mA at 2 bar) with the existing reference pressure. It can be adjusted with the [↑] or [↓] buttons IMA.

C Use the [M] button to set the transmitter to mode 3. The "Current calculation formula for adjusting" can be used to calculate the current to be adjusted for the desired full scale value IME (16 mA at 14 bar) with the existing reference pressure. It can be adjusted with the [↑] or [↓] buttons IM.

NoteNoteNoteNote If the preset measuring limits are exceeded or fallen below by more than 20% during adjustment, the resulting current cannot be set above these limits. With a marked elevation of the zero point, the full scale value must therefore previously be reduced such that it still lies within the permitted range after elevation of the zero point.

See alsoSee alsoSee alsoSee also Unit

6.5.3.26.5.3.26.5.3.26.5.3.2 Setting/adjusting the start of scale valueSetting/adjusting the start of scale valueSetting/adjusting the start of scale valueSetting/adjusting the start of scale value

IntroductionIntroductionIntroductionIntroduction Set or adjust the start of scale value of the pressure transmitter in mode 2. You can also adjust the start of scale value or the full scale value separately as well as adjust both these values one after the other.

ConditionConditionConditionCondition You are familiar with the correct operation of the transmitter and the associated safety notes. You have selected a reference pressure that corresponds to the start of scale value and is within the permissible tolerance range. The transmitter is in "Pressure" measuring mode.

Setting start of scale valueSetting start of scale valueSetting start of scale valueSetting start of scale value To set the output current of the start of scale value to 4 mA, proceed as follows:

1. Create the reference pressure.

2. Set mode 2.

Page 56: Transmitter AccuFLo-P DSIII series with HART-communication

3. Set the start of scale value to 4 mA.

4. Save with the [M] button.

Adjusting start of scale valueAdjusting start of scale valueAdjusting start of scale valueAdjusting start of scale value

If you do not set the output current but constantly adjust it, you need to calculate the currents to be adjusted mathematically.

To the adjust the output current of the start of scale value, proceed as follows:

1. Create the reference pressure.

2. Set mode 2.

3. Adjust the output current of the start of scale value to the calculated value.

4. Save with the [M] button.

Setting the start of scale value without a digital displaySetting the start of scale value without a digital displaySetting the start of scale value without a digital displaySetting the start of scale value without a digital display

You have a device with a cover that does not have an inspection window and you wish to set the start of scale value.

To set the output current of the start of scale value to 4 mA, proceed as follows:

1. Create the reference pressure.

2. Press the [↑] and [↓] buttons simultaneously.

The device has set the start of scale value to 4 mA.

3. When you release the buttons, the device saves the adjusted value automatically.

Adjusting the start of scale value without a digital displayAdjusting the start of scale value without a digital displayAdjusting the start of scale value without a digital displayAdjusting the start of scale value without a digital display

You have a device with a cover that does not have an inspection window and you do not wish to set the start of scale value, but adjust it.

You will need an ammeter for this purpose.

To the adjust the output current of the start of scale value, proceed as follows:

1. Connect the ammeter to the test connector.

2. Create the reference pressure.

3. Adjust the output current of the start of scale value using the [↑] or [↓] button.

Page 57: Transmitter AccuFLo-P DSIII series with HART-communication

4. When you release the button, the device saves the adjusted value automatically.

6.5.3.36.5.3.36.5.3.36.5.3.3 Setting/adjusting the full scale valueSetting/adjusting the full scale valueSetting/adjusting the full scale valueSetting/adjusting the full scale value

IntroductionIntroductionIntroductionIntroduction

Set or adjust the full scale value of the pressure transmitter in mode 3.

You can also adjust the start of scale value or the full scale value separately as well as adjust

both these values one after the other.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

You have selected a reference pressure that corresponds to the full scale value and is within the permissible tolerance range.

The transmitter is in "Pressure" measuring mode.

Setting full scale valueSetting full scale valueSetting full scale valueSetting full scale value

To set the output current of the full scale value to 20 mA, proceed as follows:

1. Create the reference pressure.

2. Set mode 3.

3. Set the full scale value to 20 mA.

4. Save with the [M] button.

Adjusting full scale valueAdjusting full scale valueAdjusting full scale valueAdjusting full scale value

If you do not set the output current but constantly adjust it, you need to calculate the currents to be adjusted mathematically.

To the adjust the output current of the full scale value, proceed as follows:

1. Create the reference pressure.

2. Set mode 3.

3. Adjust the output current of the full scale value to the calculated value.

4. Save with the [M] button.

Page 58: Transmitter AccuFLo-P DSIII series with HART-communication

Setting the full scale value without a digital displaySetting the full scale value without a digital displaySetting the full scale value without a digital displaySetting the full scale value without a digital display

You have a device with a cover that does not have an inspection window and you wish to set

the full scale value.

To set the output current of the full scale value to 20 mA, proceed as follows:

1. Create the reference pressure.

2. Press and hold the [M] button.

3. Also press the [↑] and [↓] buttons simultaneously.

The device has set the full scale value to 20 mA.

4. When you release the buttons, the device saves the adjusted value automatically.

Adjusting the full scale value without a digital displayAdjusting the full scale value without a digital displayAdjusting the full scale value without a digital displayAdjusting the full scale value without a digital display

You have a device with a cover that does not have an inspection window and you do not wish to set the full scale value, but adjust it continuously.

You will need an ammeter for this purpose.

To the adjust the output current of the full scale value, proceed as follows:

1. Connect the ammeter to the test connector.

2. Create the reference pressure.

3. Press and hold the [M] button.

4. Adjust the output current of the full scale value to the calculated value using the [↑] or [↓] button.

5. When you release the button, the device saves the adjusted value automatically.

6.5.46.5.46.5.46.5.4 Setting/adjusting electrical dampingSetting/adjusting electrical dampingSetting/adjusting electrical dampingSetting/adjusting electrical damping

Difference between setting and adjustingDifference between setting and adjustingDifference between setting and adjustingDifference between setting and adjusting

You can set or adjust the time constant of electrical damping using the buttons. Setting

means that the time constant is automatically set to 0 seconds. Adjusting means that the time constant is adjusted between 0 and 100 seconds using the steps of 0.1 seconds. This electrical damping also has an effect on the built-in basic damping of the device.

Condition for "setting"Condition for "setting"Condition for "setting"Condition for "setting"

You are familiar with the correct operation of the transmitter and the associated safety notes.

Page 59: Transmitter AccuFLo-P DSIII series with HART-communication

Setting electrical dampingSetting electrical dampingSetting electrical dampingSetting electrical damping

To set electrical damping to 0 seconds, proceed as follows:

1. Set mode 4.

2. Press the [↑] and [↓] buttons simultaneously.

3. Save with the [M] button.

ResultResultResultResult

Electrical damping has been set to 0 seconds.

Condition for "adjusting"Condition for "adjusting"Condition for "adjusting"Condition for "adjusting"

The default setting of steps is an interval of 0.1 seconds. If you press the [↑] or [↓] button for

a longer time, the step is increased.

Adjusting electrical dampingAdjusting electrical dampingAdjusting electrical dampingAdjusting electrical damping

To adjust electrical damping, proceed as follows:

1. Set mode 4.

2. Adjust the desired damping.

3. Save with the [M] button.

ResultResultResultResult

Electrical damping has been set to the desired time constant.

6.5.56.5.56.5.56.5.5 Blind start of scale value/full scale valueBlind start of scale value/full scale valueBlind start of scale value/full scale valueBlind start of scale value/full scale value

6.5.5.16.5.5.16.5.5.16.5.5.1 Difference between setting/adjusting and blind setting/adjustingDifference between setting/adjusting and blind setting/adjustingDifference between setting/adjusting and blind setting/adjustingDifference between setting/adjusting and blind setting/adjusting

DifferencesDifferencesDifferencesDifferences

In contrast to setting/adjusting with a reference pressure, you do not need a reference pressure for blind setting/adjusting. You can adjust a value in the physical variable "pressure" without a reference pressure, and an output current with a reference pressure.

Blind adjustingBlind adjustingBlind adjustingBlind adjusting

First select the desired physical unit. Then, adjust two pressure values using the [↑] and [↓]

Page 60: Transmitter AccuFLo-P DSIII series with HART-communication

buttons and save them in the device. These theoretical pressure values are allocated to the standard current values 4 mA and 20 mA.

Depending on the series and measuring range, a maximum downscaling of 1:100 can be achieved (measuring span ratio = r, turn down).

The correlation between the measured pressure and the output current generated is linear.

The square root extracting characteristic curve for differential pressure transmitters is an exception.

Example of bliExample of bliExample of bliExample of blind adjustingnd adjustingnd adjustingnd adjusting

A Initial situation B Blind adjustment of the start of

scale value C Blind adjustment of the full scale

value

I Output current p Pressure MAactual Old start of scale value MAtarget New start of scale value MEactual Old full scale value MEtarget New full scale value

Explanations for the blind adjusting example A The measuring range is from 0 to 16 bar. You are changing the start of scale value from 0 to 2 bar

and the full scale value from 16 to 14 bar. The measuring span is then 12 bar. In this example you create no pressure.

Page 61: Transmitter AccuFLo-P DSIII series with HART-communication

B Use the [M] button to switch the transmitter to mode 5. To adjust the start of scale value to 2 bar, press one of the [↑] or [↓] buttons. If there is 2 bar input pressure, the transmitter produces an output current of 4 mA.

C Use the [M] button to switch the transmitter to mode 6. To adjust the full scale value to 14 bar, press one of the [↑] or [↓] buttons. If there is 14 bar input pressure, the transmitter produces an output current of 20 mA.

NoteNoteNoteNote If the preset measuring limits are exceeded or fallen below by more than 20% during adjustment, the resulting current cannot be set above these limits. With a marked elevation of the zero point, the full scale value must therefore previously be reduced such that it still lies within the permitted range after elevation of the zero point.

Setting without reference pressureSetting without reference pressureSetting without reference pressureSetting without reference pressure Blind setting resets the start of scale value to the lower sensor limit and the full scale value to the upper sensor limit. NoteNoteNoteNote If the value exceeds or falls below the preset measuring limits by more than 20% when setting, the setting function is not carried out. The old value is retained in this case. With a marked elevation of the zero point, the full scale value must therefore previously be reduced such that it still lies within the permitted range after elevation of the zero point.

6.5.5.26.5.5.26.5.5.26.5.5.2 Blind setting of start of scale valueBlind setting of start of scale valueBlind setting of start of scale valueBlind setting of start of scale value IntroductionIntroductionIntroductionIntroduction

Blind setting resets the start of scale value to the lower sensor limit. NoteNoteNoteNote Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect the scaling for level or customized characteristic curve. Therefore, only measured pressure values and pressure units are displayed in these modes.

Page 62: Transmitter AccuFLo-P DSIII series with HART-communication

ConditionConditionConditionCondition You are familiar with the correct operation of the transmitter and the associated safety notes. You have not created any reference pressure and have selected a pressure unit.

ProcedureProcedureProcedureProcedure To the set the start of scale value blindly, proceed as follows:

1. Set mode 5.

2. Press the [↑] and [↓] buttons simultaneously for 2 seconds.

6.5.5.36.5.5.36.5.5.36.5.5.3 Blind setting of full scale valueBlind setting of full scale valueBlind setting of full scale valueBlind setting of full scale value

IntroductionIntroductionIntroductionIntroduction

Blind setting resets the full scale value to the upper sensor limit.

NoteNoteNoteNote

Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect the scaling for level or customized characteristic curve. Therefore, only measured pressure

values and pressure units are displayed in these modes.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

You have not created any reference pressure and have selected a pressure unit.

ProcedureProcedureProcedureProcedure

To the set the full scale value blindly, proceed as follows:

1. Set mode 6.

2. Press the [↑] and [↓] buttons simultaneously for 2 seconds.

6.5.5.46.5.5.46.5.5.46.5.5.4 Blind adjusting of the start of scale valueBlind adjusting of the start of scale valueBlind adjusting of the start of scale valueBlind adjusting of the start of scale value

IntroductionIntroductionIntroductionIntroduction

In the case of blind adjustment, adjust the pressure value of the start of scale value continuously and without a reference pressure.

Page 63: Transmitter AccuFLo-P DSIII series with HART-communication

NoteNoteNoteNote

Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect the scaling for level or customized characteristic curve. Therefore, only measured pressure values and pressure units are displayed in these modes.

You can toggle between rising and falling characteristic curves.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

You have not created any reference pressure and have selected a pressure unit.

ProcedureProcedureProcedureProcedure

To the adjust the pressure value of the start of scale value blindly, proceed as follows:

1. Set mode 5.

2. Adjust the pressure value of the start of scale value.

3. Save with the [M] button.

6.5.5.56.5.5.56.5.5.56.5.5.5 Blind adjustment of the full scale valueBlind adjustment of the full scale valueBlind adjustment of the full scale valueBlind adjustment of the full scale value

IntroductionIntroductionIntroductionIntroduction

In the case of blind adjustment, adjust the pressure value of the full scale value continuously and without a reference pressure.

NoteNoteNoteNote

Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not affect

the scaling for level or customized characteristic curve. Therefore, only measured pressure values and pressure units are displayed in these modes.

You can toggle between rising and falling characteristic curves by swapping the start of scale value and the full scale value.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

Page 64: Transmitter AccuFLo-P DSIII series with HART-communication

You have not created any reference pressure and have selected a pressure unit.

ProcedureProcedureProcedureProcedure

To the adjust the pressure value of the full scale value blindly, proceed as follows:

1. Set mode 6.

2. Adjust the pressure value of the full scale value.

3. Save with the [M] button.

6.5.66.5.66.5.66.5.6 Trimming the zero pointTrimming the zero pointTrimming the zero pointTrimming the zero point

IntroductionIntroductionIntroductionIntroduction

The zero point is calibrated in mode 7. Zero point calibration corrects zero point errors

resulting from the installation position of the pressure transmitter. The device type determines the way in which you proceed.

SIMATIC PDM or the HART communicator will display the total of all zero point corrections.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

Zero point calibration for gauge pressure transmitterZero point calibration for gauge pressure transmitterZero point calibration for gauge pressure transmitterZero point calibration for gauge pressure transmitter

To calibrate the zero point, proceed as follows:

1. Pressurize the transmitter.

2. Set mode 7.

3. Press the [↑] and [↓] buttons simultaneously.

4. Save with the [M] button.

Zero point calibration for absolute pressure transmitterZero point calibration for absolute pressure transmitterZero point calibration for absolute pressure transmitterZero point calibration for absolute pressure transmitter

NoteNoteNoteNote

You need a reference pressure known to you which lies within the measuring limits.

To calibrate the zero point, proceed as follows:

Page 65: Transmitter AccuFLo-P DSIII series with HART-communication

1. Create the reference pressure.

2. Set mode 7.

3. Set the reference pressure on the digital display.

4. Save with the [M] button.

6.5.76.5.76.5.76.5.7 Current transmitterCurrent transmitterCurrent transmitterCurrent transmitter

IntroductionIntroductionIntroductionIntroduction

In mode 8, switch the pressure transmitter into the constant current operation. You can connect an external current transmitter in the constant current operation. The current then no longer corresponds to the process variable. The following output current can be adjusted

irrespective of the input pressure:

• 3.6 mA

• 4.0 mA

• 12.0 mA

• 20.0 mA

• 22.8 mA

You can use HART communication to adjust intermediate values.

ProcedureProcedureProcedureProcedure

To switch on the constant current operation, proceed as follows:

1. Set mode 8.

"Cur" in the digital display stands for current.

2. Press the [↑] and [↓] buttons simultaneously.

3. Select constant current.

Switching off the constant current operationSwitching off the constant current operationSwitching off the constant current operationSwitching off the constant current operation

To switch off the constant current operation, proceed as follows:

Press the [M] button in mode 8.

6.5.86.5.86.5.86.5.8 Output current in case of faultOutput current in case of faultOutput current in case of faultOutput current in case of fault

Page 66: Transmitter AccuFLo-P DSIII series with HART-communication

IntroductionIntroductionIntroductionIntroduction

When a fault occurs, the lower fault current is displayed in the basic setting. In mode 9, you

can choose between the output of the upper and lower fault current. The standard values 3.6 mA and 22.8 mA are set.

The standard values of the upper and lower fault current can be changed via HART communication.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

ProcedureProcedureProcedureProcedure

To change the fault current, proceed as follows:

1. Set mode 9.

2. Select the fault current.

3. Save with the [M] button. NoteNoteNoteNote

If a current saturation interrupt is active, the setting of the output current may deviate from your setting in the case of a fault.

Resetting fault currentResetting fault currentResetting fault currentResetting fault current

To reset the fault current to the basic setting, proceed as follows:

Press the [↑] and [↓] buttons simultaneously.

Fault causesFault causesFault causesFault causes

Fault currents may be triggered by:

• FW alarm

• HW alarm

• Diagnostic interrupt

• Sensor breakage

• Measured value status BAD

Page 67: Transmitter AccuFLo-P DSIII series with HART-communication

ReferenceReferenceReferenceReference

NAMUR recommendation NE43 dated 03.02.2003

"Standardization of the signal level for the breakdown information of digital transmitters"

6.5.96.5.96.5.96.5.9 buttons and function lockbuttons and function lockbuttons and function lockbuttons and function lock

IntroductionIntroductionIntroductionIntroduction

In mode 10, you can disable the functions that can be executed using buttons. Application

example for a lock is e.g. safeguarding the saved parameters.

Lock optionsLock optionsLock optionsLock options

You have the following lock options on the pressure transmitter:

Table6-5 Meaning of lock modes

Lock modeLock modeLock modeLock mode MeaningMeaningMeaningMeaning

0 The device can be operated by means of the keys and HART communication.

LA Keys on the transmitter are locked.

Exception:

• Releasing key lock

The device can be operated by means of HART communication.

LO Keys on the transmitter are partially locked.

Exception:

• Setting start of scale value

• Releasing key lock

The device can be operated by means of HART communication.

LS Keys on the transmitter are partially locked.

Exception:

• Setting start of scale value

• Setting full scale value

• Releasing key lock

The device can be operated by means of HART communication.

Page 68: Transmitter AccuFLo-P DSIII series with HART-communication

Lock modeLock modeLock modeLock mode MeaningMeaningMeaningMeaning

L Write protection

Operation via keys and HART communication is blocked.

Exception:

• Releasing key lock

NoteNoteNoteNote

If you want to select the LO or LS lock, we recommend you

display of "Current" in "mA" or "%" in mode 13. Otherwise, a change in the output variable using the [↑] and [↓

If the blind cover is provided, the LS lock mode is effective, i.e. only the zero poinspan can be changed. If you continuously operate the device with the blind cover, ensure that the LS lock mode is constantly set.

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.NoteNoteNoteNote

In the measured value display function, check whether the desired setting is displayed.

ProcedureProcedureProcedureProcedure

To disable the buttons, proceed as follows:

1. Set mode 10.

2. Select the desired lock mode.

3. Confirm the lock mode with the [M] button.

6.5.106.5.106.5.106.5.10 Releasing Releasing Releasing Releasing key lock or function lockkey lock or function lockkey lock or function lockkey lock or function lock

Releasing key lockReleasing key lockReleasing key lockReleasing key lock

WarningWarningWarningWarning

In the case of devices used for safetythe key lock, e.g. overflow protection.

MeaningMeaningMeaningMeaning

Write protection

Operation via keys and HART communication is blocked.

Exception:

Releasing key lock

If you want to select the LO or LS lock, we recommend you first select the measured value

display of "Current" in "mA" or "%" in mode 13. Otherwise, a change in the output variable ↓] buttons is not detected.

If the blind cover is provided, the LS lock mode is effective, i.e. only the zero poinspan can be changed. If you continuously operate the device with the blind cover, ensure that the LS lock mode is constantly set.

You are familiar with the correct operation of the transmitter and the associated safety notes.

the measured value display function, check whether the desired setting is displayed.

To disable the buttons, proceed as follows:

Select the desired lock mode.

Confirm the lock mode with the [M] button.

key lock or function lockkey lock or function lockkey lock or function lockkey lock or function lock

In the case of devices used for safety-relevant applications, only authorized personnel may release the key lock, e.g. overflow protection.

first select the measured value

display of "Current" in "mA" or "%" in mode 13. Otherwise, a change in the output variable

If the blind cover is provided, the LS lock mode is effective, i.e. only the zero point and the span can be changed. If you continuously operate the device with the blind cover, ensure that

You are familiar with the correct operation of the transmitter and the associated safety notes.

the measured value display function, check whether the desired setting is displayed.

relevant applications, only authorized personnel may release

Page 69: Transmitter AccuFLo-P DSIII series with HART-communication

To release a set key lock (LA, LO, LS) using buttons, proceed as follows:

Press the [M] button for 5 seconds.

Releasing the write protectionReleasing the write protectionReleasing the write protectionReleasing the write protection

To release a write protection for HART (L) using buttons, proceed as follows:

Press the [M] button for 5 seconds.

6.5.116.5.116.5.116.5.11 Flow rate measurementFlow rate measurementFlow rate measurementFlow rate measurement

IntroductionIntroductionIntroductionIntroduction

The characteristic curve representing the relationship between the output current and input pressure can be adjusted in mode 11. Adjust the root application point in mode 12.

You can select the following characteristic curve types of the output current:

• linear "lin": proportional to differential pressure

• square root extracting "sroff": proportional to flow rate, deactivated up to the application point

• square root extracting "srlin": proportional to flow rate, linear up to the application point

• square root extracting "srli2": proportional to flow rate, two-step linear up to the application point

Variable application pointVariable application pointVariable application pointVariable application point

The output current for the "srlin" and "sroff" functions can be displayed linearly or set to zero below the application point of the square root extracting characteristic curve.

Fixed application pointFixed application pointFixed application pointFixed application point

The "srli2" function has a permanently defined application point of 10%. The range up to this point contains two linear characteristic curve sections. The first section ranges from the zero

point to 0.6% of the output value and 0.6% of the pressure value. The second section has a higher gradient and it goes up to the root application point at 10% of the output value and 1% of the pressure value. See the following figure for this purpose.

ProcedureProcedureProcedureProcedure

Proceed as follows to set or adjust the type of characteristic curve:

1. Set mode 11.

Page 70: Transmitter AccuFLo-P DSIII series with HART-communication

2. Select the type of characteristic curve.

To set the characteristic curve to "linear", press the [↑] and [↓] buttons simultaneously.

3. Save with the [M] button.

Proceed as follows to set or adjust the root application point: This procedure is not applicable for "srli2":

1. Set mode 12.

2. Select an application point between 5 and 15%.

To set the application point to 10%, press the [↑] and [↓] buttons simultaneously.

3. Save with the [M] button. NoteNoteNoteNote

Mode 12 cannot be selected if the "linear" or "srli2" measuring mode has been adjusted in mode 11.

If the square root extracting characteristic curve has been adjusted in mode 11 and if the

measured value display has been set to "Pressure" in mode 13, the root sign and the differential pressure corresponding to the flow rate are displayed.

Figure6-8 Characteristic curves and application point of

square root extracting characteristic curves

The dotted rectangle has been magnified in the form of the following characteristic curves in order to show the behavior of characteristic curves.

Page 71: Transmitter AccuFLo-P DSIII series with HART-communication

Figure6-9 Characteristic curve "lin":

Figure6-10 Square root extracting

characteristic curve "srlin"

Figure6-11 Characteristic curve "sroff"

Figure6-12 Characteristic curve "srli2"

6.5.126.5.126.5.126.5.12 Measured value displayMeasured value displayMeasured value displayMeasured value display

IntroductionIntroductionIntroductionIntroduction In mode 13, adjust the following types of measured value display:

• mA

• %

• Display of the selected measuring mode. See the following table.

Table6-6 Display of measuring mode/device variables

Digital displayDigital displayDigital displayDigital display DVDVDVDV MeaningMeaningMeaningMeaning

P 0 Pressure

Page 72: Transmitter AccuFLo-P DSIII series with HART-communication

Digital displayDigital displayDigital displayDigital display DVDVDVDV MeaningMeaningMeaningMeaning

t-SE 1 Sensor temperature

t-EL 2 Electronics temperature

P-UNC 3 Pressure (untrimmed)

LEVEL 4 Level

Vol 5 Volume

MASS 6 Mass

V-Flo 7 Volume of flow (not relevant for gauge and absolute pressure)

M-Flo 8 Mass flow rate (not relevant for gauge and absolute pressure)

CUSt 9 Users

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

ProcedureProcedureProcedureProcedure

To select the display type, proceed as follows:

1. Set mode 13.

2. Select the measured value display.

3. Save with the [M] button.

See alsoSee alsoSee alsoSee also

Measured value display

6.5.136.5.136.5.136.5.13 UnitUnitUnitUnit

IntroductionIntroductionIntroductionIntroduction

In mode 14, select the physical unit in which the measured value display of the device should be shown.

Page 73: Transmitter AccuFLo-P DSIII series with HART-communication

ConditionConditionConditionCondition

You are familiar with the correct operation of the transmitter and the associated safety notes.

You have already selected the desired measured value display in mode 13.

ProcedureProcedureProcedureProcedure

To adjust the physical unit, proceed as follows:

1. Set mode 14.

2. Select a unit.

Press the [↑] and [↓] buttons simultaneously to set the unit to the first value in the following table depending on the measuring mode set.

3. Save with the [M] button.

Instructions for selecting the unitInstructions for selecting the unitInstructions for selecting the unitInstructions for selecting the unit

• The unit is selected depending on the measurement type set. For example, only pressure units are made available in "Pressure" measuring mode and only level unit are made available in the "Level" measuring mode.

• The displayed measured value is always converted into the new unit. When the display capacity of the digital display is exceeded, "9.9.9.9.9" appears on the display.

• The selected unit is visible on the display in the measuring mode only if you have selected the display of a physical unit in mode 13. If you have not selected mode 13, "mA" or "%" is displayed.

UnitsUnitsUnitsUnits

Table6-7 Units available for pressure

Pressure unitsPressure unitsPressure unitsPressure units DisplayDisplayDisplayDisplay

mbar mbar

bar bar

mm water column (20°C / 68°F) mmH2O

Inch water column (20°C / 68°F) inHG

Feet water column (20°C / 68°F) FTH2O

Page 74: Transmitter AccuFLo-P DSIII series with HART-communication

Pressure unitsPressure unitsPressure unitsPressure units DisplayDisplayDisplayDisplay

mm mercury column mm_HG

Inch mercury column in_HG

mm water column (4°C / 39°F) m4H2O

Inch water column (4°C / 39°F) i4H2O

Psi PSi

Pa Pa

KPa² KPa

MPa MPa

g/cm2 Gcm2

Kg/cm2 KGcm2

Torr TORR

ATM ATM

Table6-8 Units available for volume

Volume unitVolume unitVolume unitVolume unit DisplayDisplayDisplayDisplay

m3 m3

Liter L

Hectoliter Hl

US gallon Gal

British gallon in Gal

British barrel bbl

British barrel liquid bblli

Buschels buShl

yard3 Yd3

Page 75: Transmitter AccuFLo-P DSIII series with HART-communication

Volume unitVolume unitVolume unitVolume unit DisplayDisplayDisplayDisplay

Feet3 FT3

inch3 in3

Standard l STdl

Standard m3 STdm3

Standard feet3 STFT3

Table6-9 Units available for mass

Mass unitMass unitMass unitMass unit DisplayDisplayDisplayDisplay

Gram G

Kilogram KG

Ton T

Short ton STon

Long ton lTon

Pound lb

Ounce OZ

Table6-10 Units available for volume of flow

Unit for volume of flowUnit for volume of flowUnit for volume of flowUnit for volume of flow DisplayDisplayDisplayDisplay

m3 / second m3/S

m3 / minute m3/M

m3 / hour m3/H

m3 / day m3/D

Liter / second L/S

Liter / minute L/M

Liter / hour L/H

Page 76: Transmitter AccuFLo-P DSIII series with HART-communication

Unit for volume of flowUnit for volume of flowUnit for volume of flowUnit for volume of flow DisplayDisplayDisplayDisplay

Million liter / day ml/ D

Feet3 / second FT3/S

Feet3 / minute FT3/M

Feet3 / hour FT3/H

Feet3 / day FT3/D

Gallon / second Gal/S

Gallon / minute Gal/M

Gallon / hour Gal/H

Gallon / day Gal/D

Million gallon / day MGl/D

British gallon / second iGL/S

British gallon / minute iGL/M

British gallon / hour iGL/H

British gallon / day iGL/D

Standard m3 / hour Sm3/H

Standard l / hour STI/H

Standard feet3 / minute SFT3M

British barrel liquid / second bbl/S

British barrel liquid / minute bbl/M

British barrel liquid / hour bbl/H

British barrel liquid / day bbl/D

Table6-11 Units available for mass flow rate

Mass flow rate unitMass flow rate unitMass flow rate unitMass flow rate unit DisplayDisplayDisplayDisplay

Page 77: Transmitter AccuFLo-P DSIII series with HART-communication

Mass flow rate unitMass flow rate unitMass flow rate unitMass flow rate unit DisplayDisplayDisplayDisplay

g / s G_S

g / min G_MIN

g / h G_H

Kg / s KG/S

Kg / min KG/M

Kg / h KG/H

Kg / d KG/D

T / min T/M

T / h T/H

T / d T/D

Pound / s P/S

Pound / min lb/M

Pound / h lb/H

Pound / d lb/D

Short ton / min ShT/M

Short ton / h ShT/H

Short ton / d ShT/D

Long ton / h lT/H

Long ton / d lT/D

Table6-12 Units available for level

Level unitLevel unitLevel unitLevel unit DisplayDisplayDisplayDisplay

Feet FT

Inch inch

Page 78: Transmitter AccuFLo-P DSIII series with HART-communication

Level unitLevel unitLevel unitLevel unit DisplayDisplayDisplayDisplay

m m

cm cm

mm mm

Table6-13 Units available for temperature

Temperature unitTemperature unitTemperature unitTemperature unit DisplayDisplayDisplayDisplay

° Celsius ° / C

° Fahrenheit ° / F

Kelvin K

Rankine R

See alsoSee alsoSee alsoSee also

Selection of the physical unit

Page 79: Transmitter AccuFLo-P DSIII series with HART-communication

7777 Operating functions through HARTOperating functions through HARTOperating functions through HARTOperating functions through HART

7.17.17.17.1 Operating functions through HART Operating functions through HART Operating functions through HART Operating functions through HART communicationcommunicationcommunicationcommunication ConditionConditionConditionCondition

You can operate the transmitter through HART communication. The following is required for this purpose:

• A HART communicator or PC software such as SIMATIC PDM.

• A HART modem to connect a PC with the transmitter or a lead to connect a HART communicator with the transmitter.

IntroductionIntroductionIntroductionIntroduction

The full functionality of the transmitter is available via HART communication. The HART communicator and PC software are not supplied with the transmitter. How to connect and

operate a HART communicator or the PC software is described in separate operating instructions or in the online help for both these tools.

Fundamental descriptionFundamental descriptionFundamental descriptionFundamental description

The input signal is provided in the form of digital information in the following variables through HART communication:

• Pressure

• Level

• Volume

• Mass

• Volume of flow

• Mass flow rate

• User programmable "characteristic curve"

As soon as you have set up the HART communication and the transmitter, you can adapt the transmitter to your relevant measuring task. When doing so you are assisted by the selectable measuring modes "Pressure", "Level", "Flow rate" and a user programmable

Page 80: Transmitter AccuFLo-P DSIII series with HART-communication

"Characteristic curve". One or more device variables are permanently allocated to each measuring mode in order to execute corresponding measuring tasks.

See alsoSee alsoSee alsoSee also

Overview of operation

7.27.27.27.2 Process tag dataProcess tag dataProcess tag dataProcess tag data

You can store your process tag data in user definable fields. The following table contains

information about the structure of these fields and the format in which you can enter information in these fields: Table7-1 Process tag data

FieldFieldFieldField ExplanationsExplanationsExplanationsExplanations

Tag designation Eight characters

Date Day:Month:Year

Description 16 characters

Message 32 characters

Works number Integer number

Tag designation long 32 characters

Freely definable material parameter 21 x 16 characters

7.37.37.37.3 Selecting the measuring modesSelecting the measuring modesSelecting the measuring modesSelecting the measuring modes

7.3.17.3.17.3.17.3.1 Overview of measuring modesOverview of measuring modesOverview of measuring modesOverview of measuring modes

OverviewOverviewOverviewOverview

The transmitter can be set for the corresponding measuring task using a few parameters. You can select the following measuring modes:

Page 81: Transmitter AccuFLo-P DSIII series with HART-communication

• Pressure

• Level

• Flow rate

• Users: user programmable characteristic curve

You can use the measuring mode selector to activate measuring modes "Level", "Flow rate"

and "User".

Selecting the device variablesSelecting the device variablesSelecting the device variablesSelecting the device variables

One or more device variables are permanently allocated to each measuring mode. The following device variables are always active and are therefore always displayed:

• Pressure

• Sensor temperature

• Electronics temperature

• Pressure (untrimmed)

The following device variables are activated only when the allocated measuring mode is

activated and parameterized simultaneously:

• "Level", "Volume" and "Mass" are allocated to the "Level" measuring mode.

• "Volume of flow" and "Mass flow rate" are allocated to the "Flow rate" measuring mode.

• "User" is allocated to the "User" measuring mode.

The inactive device variables have the CONSTANT status.

7.3.27.3.27.3.27.3.2 Measuring mode selectorMeasuring mode selectorMeasuring mode selectorMeasuring mode selector

You can use this switch to toggle between measuring modes "Pressure", "Level", "Flow rate"

and a characteristic curve programmable by a "User".

If a measuring mode has been selected using the measuring mode selector, it has to be configured. This does not mean that this block has an automatic effect on the current output (4 to 20 mA). For that, you need to switch the corresponding device variable to the primary variable (PV) using a so-called variable mapper.

7.3.37.3.37.3.37.3.3 Variable mapperVariable mapperVariable mapperVariable mapper

Page 82: Transmitter AccuFLo-P DSIII series with HART-communication

IntroductionIntroductionIntroductionIntroduction

In this transmitter, the dynamic variable that determines the behavior of current output is

always called the primary variable (PV). You need to use the variable mapper for a number of purposes, including selecting which device variable is to be switched to PV. The variable selected as PV using a PC program such as SIMATIC PDM or using the HART Communicator is scaled once again in the analog output stage to a zero value and a limit value. These two values then correspond to the current values 4 and 20 mA.

As soon as the PV is switched over using the variable mapper, the start of scale value and full scale value in the analog output stage are preset to the limit values of the new device variables. You can define these limit values within the individual block functions.

The dynamic variables "Primary", "Secondary", "Tertiary" and "Quarternary" (PV, SV, TV, QV) can be interconnected with any active device variables. Various different measuring mode examples are conceivable with a 4 bar pressure transmitter.

See alsoSee alsoSee alsoSee also

Measured value status

7.3.47.3.47.3.47.3.4 Measuring mode "Pressure"Measuring mode "Pressure"Measuring mode "Pressure"Measuring mode "Pressure"

The "Pressure" measuring mode contains the "Sensor trim" function, and is always active

since it is the standard measuring mode. When the measuring mode selector is set to "Off", further measuring variables are not derived from the "Pressure" measuring variable. Except the first four variables, all other device variables are marked as inactive and have the CONSTANT status. These four variables are mapped with dynamic variables PV, SV, TV and QV by default.

Switching an inactive device variable to the primary variable (PV) generates an error message since the variable currently does not have a valid measured value. This message is displayed in SIMATIC PDM or the HART communicator.

Page 83: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-1 Measuring mode "Pressure"

DV Device variable

MA Start of scale value

ME Full scale value

PV Primary variable

QV Quarternary variable

SV Secondary variable

TV Tertiary variable

7.3.57.3.57.3.57.3.5 Customized characteristic curveCustomized characteristic curveCustomized characteristic curveCustomized characteristic curve

IntroductionIntroductionIntroductionIntroduction The customized "characteristic curve" is continuously active as an identical function in the three following measuring modes "Level", "Flow rate" and "User".

customized "characteristic curve" always provides a result for the following function, thus also influencing the measured value status of the affected device variables.

In the device, the characteristic curve vertices are only provided Therefore, if the measuring mode is changed, you will usually need to adjust the characteristic curve accordingly.

Measuring mode "Pressure"

Device variable Start of scale value Full scale value Primary variable Quarternary variable Secondary variable Tertiary variable

Customized characteristic curveCustomized characteristic curveCustomized characteristic curveCustomized characteristic curve

The customized "characteristic curve" is continuously active as an identical function in the three following measuring modes "Level", "Flow rate" and "User". This means that the

customized "characteristic curve" always provides a result for the following function, thus also influencing the measured value status of the affected device variables. In the device, the characteristic curve vertices are only provided once in the EEPROM. Therefore, if the measuring mode is changed, you will usually need to adjust the characteristic curve accordingly.

The customized "characteristic curve" is continuously active as an identical function in the This means that the

customized "characteristic curve" always provides a result for the following function, thus also

once in the EEPROM. Therefore, if the measuring mode is changed, you will usually need to adjust the

Page 84: Transmitter AccuFLo-P DSIII series with HART-communication

The characteristic curve function expects at least two and at the most 30vertices as input parametex %;y %. The values for the xmonotonically. The ywill however be issued by the configuring device, which you as the user have to recognize

and acknowledge. The output of the characteristic curve is not explicitly stored in a device variable, but rather is directly interconnected with the input of the next function blocase. The pairs of values 0%;0% and 100%;100% are set as default values. In principle, rising and falling characteristic curves can be configured. With regard to the device variable status, rising characteristic curves are however preferred. Oth

LIMIT and LOW LIMIT are swapped.

See alsoSee alsoSee alsoSee also Measured value status

7.3.77.3.77.3.77.3.7 Measuring mode "Flow rate"Measuring mode "Flow rate"Measuring mode "Flow rate"Measuring mode "Flow rate"

DescriptionDescriptionDescriptionDescription

When you activate the "Flow rate" measuring mode, only two other device variables are active: Volume of flow and Mass flow rate. If another block was active earlier, the corresponding device variables remain inactive and have the "CONSTANT" sta

rate" block here represents a series of permanently interconnected functions which you need to configure with appropriate parameters.

Figure7-4 Measuring mode "Flow rate"

The characteristic curve function expects at least two and at the most 30vertices as input parameters. Characteristic curve vertices are entered in pairs of values

%. The values for the x-coordinate are only accepted by the device when they run monotonically. The y-coordinates, on the other hand, may also be non-monotonic. A warning

e issued by the configuring device, which you as the user have to recognize

and acknowledge. The output of the characteristic curve is not explicitly stored in a device variable, but rather is directly interconnected with the input of the next function blocase. The pairs of values 0%;0% and 100%;100% are set as default values. In principle, rising and falling characteristic curves can be configured. With regard to the device variable status, rising characteristic curves are however preferred. Otherwise the meanings of HIGH

LIMIT and LOW LIMIT are swapped.

Measured value status

Measuring mode "Flow rate"Measuring mode "Flow rate"Measuring mode "Flow rate"Measuring mode "Flow rate"

When you activate the "Flow rate" measuring mode, only two other device variables are active: Volume of flow and Mass flow rate. If another block was active earlier, the corresponding device variables remain inactive and have the "CONSTANT" sta

rate" block here represents a series of permanently interconnected functions which you need to configure with appropriate parameters.

Measuring mode "Flow rate"

The characteristic curve function expects at least two and at the most 30 characteristic curve rs. Characteristic curve vertices are entered in pairs of values

coordinate are only accepted by the device when they run monotonic. A warning

e issued by the configuring device, which you as the user have to recognize

and acknowledge. The output of the characteristic curve is not explicitly stored in a device variable, but rather is directly interconnected with the input of the next function block in each case. The pairs of values 0%;0% and 100%;100% are set as default values. In principle, rising and falling characteristic curves can be configured. With regard to the device variable

erwise the meanings of HIGH

When you activate the "Flow rate" measuring mode, only two other device variables are active: Volume of flow and Mass flow rate. If another block was active earlier, the corresponding device variables remain inactive and have the "CONSTANT" status. The "Flow

rate" block here represents a series of permanently interconnected functions which you need

Page 85: Transmitter AccuFLo-P DSIII series with HART-communication

DV Device variable

MA Start of scale value

ME Full scale value

Functions of the "Flow rate" blockFunctions of the "Flow rate" blockFunctions of the "Flow rate" blockFunctions of the "Flow rate" block The "Input scaling, pressure" function defines the pressure range of 0 to 2interpreted as 0 and 100% by the following square root extracting function. A process pressure of 0.5 bar has been assumed in the fol

In the "Flow rate" measuring mode, a square root extracting characteristic curve "srlin2" is

plotted with a fixed root application point of 10%. In the calculation example, the input value for the "square root extracting function" is approximately 25% at a process pressure of 0.5NoteNoteNoteNote When using the "Flow rate" block, other square root extracting characteristic curves must be

deactivated if required.

Figure7-5 Functions of the "Flow rate"

DV [x] Device variable x MA Start of scale value ME Full scale value

In the calculation example, the two pairs of values 0%;0the customized "characteristic curve". This setting corresponds to a bisection of the input value for all output values.

Configure the "Output scaling, volume of flow" with a unit from the volume of flow range and

Device variable Start of scale value Full scale value

The "Input scaling, pressure" function defines the pressure range of 0 to 2interpreted as 0 and 100% by the following square root extracting function. A process

bar has been assumed in the following figure. In the "Flow rate" measuring mode, a square root extracting characteristic curve "srlin2" is

plotted with a fixed root application point of 10%. In the calculation example, the input value for the "square root extracting function" is

roximately 25% at a process pressure of 0.5 bar. The output value is approximately 50%.

When using the "Flow rate" block, other square root extracting characteristic curves must be

deactivated if required.

Functions of the "Flow rate" block

MF Mass flow rate p Pressure VF Volume of flow

In the calculation example, the two pairs of values 0%;0% and 100%;50 % are configured for the customized "characteristic curve". This setting corresponds to a bisection of the input value for all output values. Configure the "Output scaling, volume of flow" with a unit from the volume of flow range and

The "Input scaling, pressure" function defines the pressure range of 0 to 2 bar that is interpreted as 0 and 100% by the following square root extracting function. A process

In the "Flow rate" measuring mode, a square root extracting characteristic curve "srlin2" is

In the calculation example, the input value for the "square root extracting function" is bar. The output value is approximately 50%.

When using the "Flow rate" block, other square root extracting characteristic curves must be

% and 100%;50 % are configured for the customized "characteristic curve". This setting corresponds to a bisection of the input

Configure the "Output scaling, volume of flow" with a unit from the volume of flow range and

Page 86: Transmitter AccuFLo-P DSIII series with HART-communication

the measuring limits for the device variable "Volume of flow". In the calculation example, 0 l/s and 1000 l/s are defined as lower and upper measuring limits. The volume of flow is thus 250 l/s at a process pressure of 0.5 bar. The "Mass flow rate" device variable is automatically activated when the "Flow rate" block is configured. If you have not yet configured a value for the density, the initial value of 1 kg/l is

preset. In the calculation example, a mass of 1000 kg/s is derived for the "Mass flow rate" device variable at a value of 4 kg/l. The value of density entered is used only to calculate the mass flow rate. The entered value of density has no effect on the diaphragm calculation that is to be carried out by the user. In SIMATIC PDM or the HART communicator, the "Flow rate" block is configured in an online dialog box in an extremely compact manner. In this online dialog box, you can compile all values in a menu and transfer them to the device collectively.

7.3.87.3.87.3.87.3.8 Measuring mode "User"Measuring mode "User"Measuring mode "User"Measuring mode "User"

DescriptionDescriptionDescriptionDescription

The "User" measuring mode is the simplest of the measuring modes that you can select with the measuring mode selector. Only one further device variable, "User", is activated in this measuring mode in addition to the four standard device variables. The variables "Level", "Volume", "Mass", "Volume of flow" and "Mass flow rate" are marked as inactive and are

given the status CONSTANT.

In the "User" measuring mode, you have an option to define a customized unit for output scaling. This customized unit is, e.g. a specific quantity of liquid. This quantity of liquid depends on the input process pressure.

Example: Fill the beverages in cans having a capacity of 0.33 l. You can now define a customized unit "Can" that is exactly equal to 0.33 l. The quantity of "cans" depends on the

input process pressure.

NoteNoteNoteNote

Permissible input valuesPermissible input valuesPermissible input valuesPermissible input values

All alphabetic a...z, A...Z and numeric 0...9 inputs are allowed for the customized unit. The following characters are also allowed:

° " $ / < > * , _ + - = @

Page 87: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-6 Measuring

DV Device variable PV Primary variable SV Secondary variable TV Tertiary variable QV Quarternary variable

Functions of the "User" blockFunctions of the "User" blockFunctions of the "User" blockFunctions of the "User" block The first function, "Input scaling, pressure", defines the pressure range which is used by the customized characteristic curve. Ideally, this range corresponds to the sensor limits. In the calculation example, 0 and 2

of 0.5 bar, there is a value of 25% on the characteristic curve.

Figure7-7 Functions of the "User" block

Measuring mode "User"

MA Start of scale value ME Full scale value

The first function, "Input scaling, pressure", defines the pressure range which is used by the customized characteristic curve. Ideally, this range corresponds to the sensor limits. In the calculation example, 0 and 2 bar are assumed. This means that wi

bar, there is a value of 25% on the characteristic curve.

Functions of the "User" block

The first function, "Input scaling, pressure", defines the pressure range which is used by the customized characteristic curve. Ideally, this range corresponds to the sensor limits.

bar are assumed. This means that with process pressure

Page 88: Transmitter AccuFLo-P DSIII series with HART-communication

DV [x] Device variable x MA Start of scale value p Pressure ME Full scale value

In the calculation example, the two pairs of values 0%;0% and 100%;100% are configured for the customized "characteristic curve". Any curve shapes can be calculated with the help of 30 characteristic curve vertices. These curve shapes can be stored in the device using

SIMATIC PDM or the HART communicator. In the calculation example, the value at the input of the characteristic curve is transferred 1:1 to the output. In the calculation example, a number of filled cans is set for the output scaling. You can enter up to five characters for any given unit. Do not confuse this with the user-programmable

display unit of the "Analog output" block. In the calculation example, you have a start of scale value of 0 cans and a full scale value of 1000 cans. At a process pressure of 0.5 bar, you get a value of 250 cans for the "User" device variable.

See alsoSee alsoSee alsoSee also Analog output Measured value status

7.3.97.3.97.3.97.3.9 Measured value statusMeasured value statusMeasured value statusMeasured value status

IntroductionIntroductionIntroductionIntroduction

Every device variable is assigned a status byte to indicate the quality of the measured values. This status byte can have the following values:

• BAD

• GOOD

• MANUAL

• UNCERTAIN

The following values are also possible:

• CONSTANT

• HIGH LIMIT

Page 89: Transmitter AccuFLo-P DSIII series with HART-communication

• LOW LIMIT

A higher-level diagnosis program can display and analyze these states.

GOOD statusGOOD statusGOOD statusGOOD status

During smooth, uninterrupted operation, the measured value status of all active device variables is GOOD.

BAD/CONSTANT statusBAD/CONSTANT statusBAD/CONSTANT statusBAD/CONSTANT status

All inactive device variables have CONSTANT/BAD status.

If a variable having the BAD status is an output value for calculation, the measured value is BAD.

The basic measured values, namely pressure and temperatures, have the BAD status in the

following cases:

• The analog-to-digital converter does not function.

• Linearization values in the EEPROM are defective.

• If the two end points of the customized characteristic curve are exceeded for the status of the device variables of the following function.

UNCERTAIN statusUNCERTAIN statusUNCERTAIN statusUNCERTAIN status

If a pressure value exceeds or falls below the sensor limits of the device by more than 20%, the corresponding measured value and the variables inferred from it are UNCERTAIN.

If the analog-to-digital converter for pressure control is over/underrange, the status is

UNCERTAIN.

HIGH LIMIT and LOW LIMITHIGH LIMIT and LOW LIMITHIGH LIMIT and LOW LIMITHIGH LIMIT and LOW LIMIT

If the analog-to-digital converter is overrange, the HIGH LIMIT label is allocated. If the analog-to-digital converter is underrange, the LOW LIMIT label is allocated.

Change in statusChange in statusChange in statusChange in status

If the status of a device variable changes and it was right at the front of the sequence of operations for a block, e.g. pressure, then all variables that are derived from it will take on the same status. In the following example, the device variable "Pressure" has the BAD status.

Page 90: Transmitter AccuFLo-P DSIII series with HART-communication

Since the measuring mode selector is set to "USER", the device variable "User" is also given the BAD status.

The reasons for changes in the status of a device variable are summarized in the table. If there were several reasons for a change in status, MANUAL always has the BAD has the second highest and UNCERTAIN the third highest priority.

Figure7-8 Device status dependency

DV Device variable PV Primary variable SV Secondary variable TV Tertiary variable QV Quarternary variable

Table7-2Events which result in a change of status

DVDVDVDV Measuring Measuring Measuring Measuring modemodemodemode

BADBADBADBAD MANUALMANUALMANUALMANUAL

0 Pressure DV3 = BAD, fault in linearization

When DV0 is simulated

1 Sensor DV2 = BAD, When DV1

ng mode selector is set to "USER", the device variable "User" is also given

The reasons for changes in the status of a device variable are summarized in the table. If there were several reasons for a change in status, MANUAL always has the BAD has the second highest and UNCERTAIN the third highest priority.

Device status dependency

MA Start of scale value ME Full scale value

2Events which result in a change of status

MANUALMANUALMANUALMANUAL UNCERTAINUNCERTAINUNCERTAINUNCERTAIN CONSTANTCONSTANTCONSTANTCONSTANT HIGH LIMITHIGH LIMITHIGH LIMITHIGH LIMIT

When DV0

simulated

DV3 = UNCERTAIN - DV3 =

HIGH LIMIT

When DV1 DV1 more than 20% - Analog-to-

ng mode selector is set to "USER", the device variable "User" is also given

The reasons for changes in the status of a device variable are summarized in the table. If there were several reasons for a change in status, MANUAL always has the highest priority. BAD has the second highest and UNCERTAIN the third highest priority.

HIGH LIMITHIGH LIMITHIGH LIMITHIGH LIMIT LOW LIMITLOW LIMITLOW LIMITLOW LIMIT

HIGH LIMIT

DV3 =

LOW LIMIT

-digit Analog-to-digit

Page 91: Transmitter AccuFLo-P DSIII series with HART-communication

DVDVDVDV Measuring Measuring Measuring Measuring modemodemodemode

BADBADBADBAD MANUALMANUALMANUALMANUAL UNCERTAINUNCERTAINUNCERTAINUNCERTAIN CONSTANTCONSTANTCONSTANTCONSTANT HIGH LIMITHIGH LIMITHIGH LIMITHIGH LIMIT LOW LIMITLOW LIMITLOW LIMITLOW LIMIT

temperature analog-to-digital converter in over/underrange, fault in linearization

is simulated

outside the sensor limits

DV2 = UNCERTAIN

DV2 = MANUAL

al converter in overrange

al converter in underrange

2 Electronics temperature

Analog-to-digital converter in over/underrange, fault in linearization

When DV2 is simulated

DV2 more than 20% outside the sensor limits

- Analog-to-digital converter in overrange

Analog-to-digital converter in underrange

3 Pressure (untrimmed)

Analog-to-digital converter in over/underrange, DV1 sensor breakage,

DV2 = BAD, fault in linearization

- Analog-to-digital converter in overrange/underrange, DV3 more than 20% outside the sensor limits

DV2 = MANUAL

- Analog-to-digital converter in overrange

Analog-to-digital converter in underrange

4 Level If DV0 = BAD When DV0 is simulated

DV0= UNCERTAIN DV not active

DV0 =

HIGH LIMIT

DV0 =

LOW LIMIT

5 Volume DV0 = BAD,

Characteristic curve is faulty

When DV0 is simulated

DV0 = UNCERTAIN, input value is outside the specified characteristic curve range

Characteristic curve is faulty

DV not active

DV4 =

HIGH LIMIT,

Characteristic curve for maximum value with gradient 0

DV4 =

LOW LIMIT,

Characteristic curve for minimum value with gradient 0

6 Mass DV5 = BAD When DV0 is simulated

DV5= UNCERTAIN DV not active,

DV5 = CONSTANT

DV5 =

HIGH LIMIT

DV5 =

LOW LIMIT

7 Volume of flow DV0 = BAD, When DV0 DV0 = UNCERTAIN, Characteristi DV4 = DV4 =

Page 92: Transmitter AccuFLo-P DSIII series with HART-communication

DVDVDVDV Measuring Measuring Measuring Measuring modemodemodemode

BADBADBADBAD MANUALMANUALMANUALMANUAL UNCERTAINUNCERTAINUNCERTAINUNCERTAIN CONSTANTCONSTANTCONSTANTCONSTANT HIGH LIMITHIGH LIMITHIGH LIMITHIGH LIMIT LOW LIMITLOW LIMITLOW LIMITLOW LIMIT

(not absolute and gauge pressure)

characteristic curve is faulty

is simulated

input value is outside the specified characteristic curve range

c curve is faulty,

DV not active

HIGH LIMIT,

Characteristic curve for maximum value with gradient 0

LOW LIMIT,

Characteristic curve for minimum value with gradient 0

8 Mass flow rate

(not absolute and gauge pressure)

DV5 = BAD When DV0 is simulated

DV5= UNCERTAIN DV not active

DV5 = CONSTANT

DV5 =

#HIGH LIMIT

DV5 =

LOW LIMIT

9 Users DV0 = BAD,

Characteristic curve is faulty

When DV0 is simulated

DV0 = UNCERTAIN,

input value is outside the specified characteristic curve range

Characteristic curve is faulty

DV not active

DV0 =

HIGH LIMIT,

Characteristic curve for maximum value with gradient 0

DV0 =

LOW LIMIT,

Characteristic curve for minimum value with gradient 0

If you use falling characteristic curves in the blocks, the meanings of HIGH LIMIT and LOW LIMIT are swapped around.

If you mix falling and rising characteristic curves, the meanings will be swapped each time a falling characteristic curve is run.

7.3.107.3.107.3.107.3.10 Analog outputAnalog outputAnalog outputAnalog output

IntroductionIntroductionIntroductionIntroduction

The "Analog output" block converts the value provided by the dynamic primary variable (PV) into a current value of 4 to 20 mA. When you actuate the measuring mode selector, you automatically define the start of scale value and the full scale value to the current values 4 and 20 mA, respectively. Limit values of corresponding device variables are used for scaling the analog output by default. You have entered these limits when setting the parameters of

your measuring mode.

Page 93: Transmitter AccuFLo-P DSIII series with HART-communication

Example for measuring mode "Level"Example for measuring mode "Level"Example for measuring mode "Level"Example for measuring mode "Level"

This means that for a "Level" device variable as PV, 10

and 20 m corresponds to the value for 20"Analog output" block. This is done by restricting the range of the "Level" device variable for scaling the output current to e.g. 12 to 18block scaling. In this case, a current of 4 mA is output for a measured height of 12current of 20 mA for 18 m.

Figure7-9 "Analog output" scaling

DV Device variable PV Primary variable SV Secondary variable TV Tertiary variable QV Quarternary variable

Example for measuring mode "Level"Example for measuring mode "Level"Example for measuring mode "Level"Example for measuring mode "Level"

This means that for a "Level" device variable as PV, 10 m corresponds to the value for 4

m corresponds to the value for 20 mA. You can change this presetting again in the "Analog output" block. This is done by restricting the range of the "Level" device variable for scaling the output current to e.g. 12 to 18 m. This downscaling has no effect on the previous block scaling. In this case, a current of 4 mA is output for a measured height of 12

mA for 18 m.

"Analog output" scaling

MA Start of scale value ME Full scale value

m corresponds to the value for 4 mA

mA. You can change this presetting again in the "Analog output" block. This is done by restricting the range of the "Level" device variable for

effect on the previous block scaling. In this case, a current of 4 mA is output for a measured height of 12 m, and a

Page 94: Transmitter AccuFLo-P DSIII series with HART-communication

Description of measuring mode "Level"Description of measuring mode "Level"Description of measuring mode "Level"Description of measuring mode "Level"

Figure7-10 "Analog output" block

MA Start of scale value

ME Full scale value

NoteNoteNoteNote If, when setting the analog output, the values for the start of scale value zero and the full scale value are more than 20% below or above the limit values of the set PV (set using the variable mapper), the values will be rejected by the device. The values configured previretained. Similarly, the span must not fall below the minimum.

Minimum span = ME

The square root extracting function can only be selected in the "Pressure" measuring mode.

The "srlin2" square root extracting function is set as default in themode.

7.3.117.3.117.3.117.3.11 Scaling the digital display valueScaling the digital display valueScaling the digital display valueScaling the digital display value

IntroductionIntroductionIntroductionIntroduction You can freely scale the value shown in the digital display and allocate any unit of 5 characters to it. The scaling of the value is independent of the selection of the mode selector, the primary variable (PV) and the display unit defined. Use the "Digital display settings" item in SIMATIC

The percent value of the PV is the basis for this scaling. This percent value

scale the current output. In SIMATIC

Description of measuring mode "Level"Description of measuring mode "Level"Description of measuring mode "Level"Description of measuring mode "Level"

"Analog output" block

Start of scale value p Pressure Full scale value PV Primary variable

the analog output, the values for the start of scale value zero and the full scale value are more than 20% below or above the limit values of the set PV (set using the variable mapper), the values will be rejected by the device. The values configured previretained. Similarly, the span must not fall below the minimum. Minimum span = ME - MA The square root extracting function can only be selected in the "Pressure" measuring mode.

The "srlin2" square root extracting function is set as default in the "Flow rate" measuring

Scaling the digital display valueScaling the digital display valueScaling the digital display valueScaling the digital display value

You can freely scale the value shown in the digital display and allocate any unit of 5 characters to it. The scaling of the value is independent of the selection of the mode selector, the primary variable (PV) and the display unit defined. Use the "Digital display settings" item in SIMATIC PDM or the HART communicator for this purpose.

The percent value of the PV is the basis for this scaling. This percent value

scale the current output. In SIMATIC PDM, this item is referred to as "Setting the PV output

the analog output, the values for the start of scale value zero and the full scale value are more than 20% below or above the limit values of the set PV (set using the variable mapper), the values will be rejected by the device. The values configured previously are

The square root extracting function can only be selected in the "Pressure" measuring mode. "Flow rate" measuring

You can freely scale the value shown in the digital display and allocate any unit of 5 characters to it. The scaling of the value is independent of the selection of the measuring mode selector, the primary variable (PV) and the display unit defined. Use the "Digital display

PDM or the HART communicator for this purpose. The percent value of the PV is the basis for this scaling. This percent value is also used to

PDM, this item is referred to as "Setting the PV output

Page 95: Transmitter AccuFLo-P DSIII series with HART-communication

scaling". After selecting the "Digital display settings" menu command, you must enter a start-of-scale value, full scale value and a unit string.

This display option has the highest priority amongst all options. A switch over to %, mA or any other unit is not possible in this status. You need to deactivate the LCD scaling again for this purpose.

ExampleExampleExampleExample In the Level measuring mode, the start of scavalue as 10 m in the example illustrated in the following picture. The value of 2at a process pressure of 0.4

Figure7-11 Free LCD scaling

DV Device variable PV Primary variable SV Secondary variable TV Tertiary variable QV Quarternary variable

7.47.47.47.4 Setting zero point and limit pointSetting zero point and limit pointSetting zero point and limit pointSetting zero point and limit point

scaling". After selecting the "Digital display settings" menu command, you must enter a scale value, full scale value and a unit string.

This display option has the highest priority amongst all options. A switch over to %, mA or any other unit is not possible in this status. You need to deactivate the LCD scaling again for this

In the Level measuring mode, the start of scale value is assumed as 0 m and the full scale m in the example illustrated in the following picture. The value of 2

at a process pressure of 0.4 bar.

Free LCD scaling

MA Start of scale value ME Full scale value

Setting zero point and limit pointSetting zero point and limit pointSetting zero point and limit pointSetting zero point and limit point

scaling". After selecting the "Digital display settings" menu command, you must enter a

This display option has the highest priority amongst all options. A switch over to %, mA or any other unit is not possible in this status. You need to deactivate the LCD scaling again for this

m and the full scale m in the example illustrated in the following picture. The value of 2 m is displayed

Page 96: Transmitter AccuFLo-P DSIII series with HART-communication

You can set the zero point and the limit point using the SIMATICCommunicator. You can use this

The pressure unit can be set separately for the display and for HART communication.

See alsoSee alsoSee alsoSee also Difference between setting and adjusting

7.57.57.57.5 Blind setting of zero point and limit pointBlind setting of zero point and limit pointBlind setting of zero point and limit pointBlind setting of zero point and limit point

• The start of scale value and the full scale value can be set without creating a reference pressure.

• Both values can be selected as any point

• The maximum downscaling is 1:100, depending on the series and the measuring range.

7.67.67.67.6 Zero point calibrationZero point calibrationZero point calibrationZero point calibration

DescriptionDescriptionDescriptionDescription A zero point calibration is used to correct a zero point error resulting from the installation

position. ProcedureProcedureProcedureProcedure

• Pressurize the device or evacuate it (at absolute pressure, < 0.1

• Perform the zero point calibration using

• If you do not have a vacuum, perform a trimming of the lower sensor calibration point at a known reference pressure.

CautionCautionCautionCaution

For absolute pressure transmitters, the zero point is at vacuum. A zero point calibrati

pressurized transmitter will lead to faulty settings!NoteNoteNoteNote

The effective measuring range is reduced by the amount of the upstream pressure.

Example:

You can set the zero point and the limit point using the SIMATIC PDM or HART Communicator. You can use this function to realize rising or falling characteristic curves.

The pressure unit can be set separately for the display and for HART communication.

Difference between setting and adjusting

Blind setting of zero point and limit pointBlind setting of zero point and limit pointBlind setting of zero point and limit pointBlind setting of zero point and limit point The start of scale value and the full scale value can be set without creating a reference pressure.

Both values can be selected as any point within the sensor limits.

The maximum downscaling is 1:100, depending on the series and the measuring range.

Zero point calibrationZero point calibrationZero point calibrationZero point calibration

A zero point calibration is used to correct a zero point error resulting from the installation

Pressurize the device or evacuate it (at absolute pressure, < 0.1 ‰ of the measuring span).

Perform the zero point calibration using SIMATIC PDM or the HART Communicator.

If you do not have a vacuum, perform a trimming of the lower sensor calibration point at a known reference pressure.

CautionCautionCautionCaution

For absolute pressure transmitters, the zero point is at vacuum. A zero point calibrati

pressurized transmitter will lead to faulty settings!

The effective measuring range is reduced by the amount of the upstream pressure.

PDM or HART function to realize rising or falling characteristic curves.

The pressure unit can be set separately for the display and for HART communication.

The start of scale value and the full scale value can be set without creating a reference pressure.

The maximum downscaling is 1:100, depending on the series and the measuring range.

A zero point calibration is used to correct a zero point error resulting from the installation

of the measuring span).

PDM or the HART Communicator.

If you do not have a vacuum, perform a trimming of the lower sensor calibration point at a known

For absolute pressure transmitters, the zero point is at vacuum. A zero point calibrati

The effective measuring range is reduced by the amount of the upstream pressure.

Page 97: Transmitter AccuFLo-P DSIII series with HART-communication

With an upstream pressure of 100 mbar, the effective measuring range of a 1-bar transmitter is reduced to a point between 0 and 0.9 bar.

See alsoSee alsoSee alsoSee also

Trimming of the sensor trim point

7.77.77.77.7 Electrical dampingElectrical dampingElectrical dampingElectrical damping DescriptionDescriptionDescriptionDescription

You can set the time constant of electrical damping to a point within a range from 0 to 100 s. It

always applies to the "Pressure" device variable (DV0) and thus to the measured values derived from it.

7.87.87.87.8 Fast response modeFast response modeFast response modeFast response mode DescriptionDescriptionDescriptionDescription

This mode is only intended for special applications such as fast recognition of jumps in pressure, e.g. pressure drop in the event of pipe breakage. The internal recording of

measured values is sped up at the cost of accuracy. From your point of view, an increased low-frequency noise is caused for the measured value. For this reason, good accuracy can only be achieved by setting the measuring span to the maximum.

7.97.97.97.9 Current sensorCurrent sensorCurrent sensorCurrent sensor DescriptionDescriptionDescriptionDescription

The transmitter can be switched to constant current operation for test purposes. In that case, the current no longer corresponds to the process variable. A "C" appears in the mode display

of the digital display.

Page 98: Transmitter AccuFLo-P DSIII series with HART-communication

7.107.107.107.10 Fault currentFault currentFault currentFault current DescriptionDescriptionDescriptionDescription

You can use this function to set the size of the lower (< 4 mA) and upper (> 20 mA) fault current. Both signal a hardware/firmware fault, sensor breakage, or that the alarm limit has been reached (diagnostic interrupt). In that case, ERROR appears in the digital display. You can obtain a detailed guide to the display using SIMATIC PDM or the HART Communicator.

ReferenceReferenceReferenceReference NAMUR recommendation NE43 dated 03.02.2003 "Standardization of the signal level for the breakdown information of digital transmitters"

See alsoSee alsoSee alsoSee also Error display Limit modules

7.117.117.117.11 Setting the current limitsSetting the current limitsSetting the current limitsSetting the current limits DescriptionDescriptionDescriptionDescription

The level of the upper and lower fault current and the upper and lower saturation limits can be

freely selected within the preset limits of the current output signal. The specified accuracy of the current output signal is only valid within the current limits 4 to 20 mA.

Page 99: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-12 Current limits ① Linear control range ② Lower saturation limit (default value) ③ Upper saturation limit (default value) ④ Lower fault current value (default value) ⑤ Upper fault current value (default value) ⑥ Recommended setting range for lower fault current range and lower control range limit ⑦ Recommended setting range for upper fault current range and upper control range limit

7.127.127.127.12 Key lock and write Key lock and write Key lock and write Key lock and write protectionprotectionprotectionprotection IntroductionIntroductionIntroductionIntroduction

You can use this function to lock the keys or activate write protection to safeguard the saved parameters.

Lock optionsLock optionsLock optionsLock options You have the following lock options:

Page 100: Transmitter AccuFLo-P DSIII series with HART-communication

Table7-3 Meaning of the HART lock modes

Lock modeLock modeLock modeLock mode MeaningMeaningMeaningMeaning

0 The device can be operated by means of the keys and HART communication.

LA Keys on the transmitter are locked.

Exception:

• Releasing key lock

The device can be operated by means of HART communication.

LO Keys on the transmitter are partially locked.

Exception:

• Setting start of scale value

• Releasing key lock

The device can be operated by means of HART communication.

LS Keys on the transmitter are partially locked.

Exception:

• Setting start of scale value

• Setting full scale value

• Releasing key lock

The device can be operated by means of HART communication.

LL Write protection

You can now only release the lock using HART communication.

See alsoSee alsoSee alsoSee also

buttons and function lock

Releasing key lock or function lock

7.137.137.137.13 Measured value displayMeasured value displayMeasured value displayMeasured value display

Page 101: Transmitter AccuFLo-P DSIII series with HART-communication

IntroductionIntroductionIntroductionIntroduction You can use this function to set one of three options for the device display:

• Display in mA

• Display in % (of the set measuring range)

• Display in terms of a

DescriptionDescriptionDescriptionDescription

If the Primary Variable is mapped to the "Pressure" device variable, you can configure the displayed pressure unit with an add

the real measured value

To do so, select the option Gauge or Absolute under the "Pressure display type" menu command.

There are two options for the display:

• If the pressure unit is < 5 characters, an A or a G is added at the end, respectively.

• If the pressure unit is unit.

Figure7-13 AddNoteNoteNoteNote

The change of the display with GAUGE or ABS does not change the physical pressure used by the transmitter, rather only the nature

See alsoSee alsoSee alsoSee also

Measured value display

You can use this function to set one of three options for the device display:

Display in % (of the set measuring range)

Display in terms of a physical unit, e.g. bar, l, m3/ h etc.

If the Primary Variable is mapped to the "Pressure" device variable, you can configure the displayed pressure unit with an add-on, GAUGE (G) or ABS (A). The add

the real measured value.

To do so, select the option Gauge or Absolute under the "Pressure display type" menu

There are two options for the display:

If the pressure unit is < 5 characters, an A or a G is added at the end, respectively.

If the pressure unit is ≥ 5 characters, the letters GAUGE or ABS flash alternately with the pressure

Add-on with example GAUGE

The change of the display with GAUGE or ABS does not change the physical pressure used by the transmitter, rather only the nature of the display.

Measured value display

You can use this function to set one of three options for the device display:

If the Primary Variable is mapped to the "Pressure" device variable, you can configure the on, GAUGE (G) or ABS (A). The add-on has no effect on

To do so, select the option Gauge or Absolute under the "Pressure display type" menu

If the pressure unit is < 5 characters, an A or a G is added at the end, respectively.

5 characters, the letters GAUGE or ABS flash alternately with the pressure

The change of the display with GAUGE or ABS does not change the physical pressure

Page 102: Transmitter AccuFLo-P DSIII series with HART-communication

7.147.147.147.14 Selection of the physical unitSelection of the physical unitSelection of the physical unitSelection of the physical unit IntroductionIntroductionIntroductionIntroduction

You can use this function to select a unit from a table with predefined units. DescriptionDescriptionDescriptionDescription

The only units available will be those of the device variable that was mapped as the Primary Variable (PV). The unit can be set separately for the display and for HART communication. You can also

choose to link the setting of the two units. See alsoSee alsoSee alsoSee also

Unit

7.157.157.157.15 Bar graphBar graphBar graphBar graph DescriptionDescriptionDescriptionDescription

You can use this to switch on the "Bar graph" function in the device display as an alternative to the unit display. The "Bar graph" function is disabled in the factory state.

See alsoSee alsoSee alsoSee also Elements of the digital display

7.167.167.167.16 Sensor calibrationSensor calibrationSensor calibrationSensor calibration

7.16.17.16.17.16.17.16.1 Sensor trimSensor trimSensor trimSensor trim

DescriptionDescriptionDescriptionDescription

The sensor trim can be used to set the characteristic curve of the transmitter at two sensor trim points. The results are then correct measured values at the sensor trim points. The sensor trim points can be selected as any points within the nominal range.

Page 103: Transmitter AccuFLo-P DSIII series with HART-communication

Devices that are not turned down prior to delivery are trimmed at 0 bar and the upper limit of the nominal range; devices that are turned down prior to delivery are trimmed at the lower and upper limits of the set pressure measuring range.

Application exApplication exApplication exApplication examplesamplesamplesamples

• For a particular device that is not turned down (e.g. 63 bar), the typical measured value is 50 bar. To attain the highest possible accuracy for this value, set the upper sensor calibration at 50 bar.

• A 63-bar transmitter is turned down to 4 to 7 bar. You can attain the highest possible accuracy by selecting 4 bar for the lower sensor calibration point and 7 bar for the upper.

• A 250-mbar absolute pressure transmitter shows 25 mbar at 20 mbar (abs). A reference pressure of 100 mbar is available. You can carry out zero point correction by performing a lower sensor trim at 100 mbar. NoteNoteNoteNote

The accuracy of the test device should be at least three times as high as that of the transmitter.

7.16.27.16.27.16.27.16.2 Trimming of the sensor trim pointTrimming of the sensor trim pointTrimming of the sensor trim pointTrimming of the sensor trim point

Trimming the Trimming the Trimming the Trimming the lower sensor trim pointlower sensor trim pointlower sensor trim pointlower sensor trim point

The pressure at which the lower sensor trim is to be performed is applied at the transmitter. Via SIMATIC PDM or the HART Communicator, you instruct the transmitter to accept this

pressure.

This represents an offset shift of the characteristic curve.

Trimming the upper sensor trim pointTrimming the upper sensor trim pointTrimming the upper sensor trim pointTrimming the upper sensor trim point

The pressure at which the upper sensor trim is to be performed is applied at the transmitter. Via SIMATIC PDM or the HART Communicator, you instruct the transmitter to accept this pressure.

A gradient correction is thereby applied to the characteristic curve. The lower sensor trim point is not affected by this. The upper trim point needs to be greater than the lower trim point.

Page 104: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-14 Sensor calibration

A Output characteristic curve

B Characteristic curve after lower sensor trim

C Characteristic curve after upper sensor trim

7.177.177.177.17 Current sensor trimCurrent sensor trimCurrent sensor trimCurrent sensor trim

DescriptionDescriptionDescriptionDescription The current that is output by the transmitter can be trimmed independently of the pressure measuring circuit. This function is designed for compensating inaccuracies in the processing chain following the transmitter.

Example of an applicationExample of an applicationExample of an applicationExample of an application The current is to be measured as a voltage drop from 1 to 55%. To trim the tolerance of the resistance, set the current transmitter so that the voltage drop

at 4 mA is exactly 1

• Trim at 4 mA:

Use the current transmitter trim menu option to instruct the transmitter to output 4measured value from the ammeter and enter it, via SIMATIC PDM for example. The transmitter uses

Sensor calibration

Output characteristic curve Characteristic curve after lower sensor trim Characteristic curve after upper sensor trim

Current sensor trimCurrent sensor trimCurrent sensor trimCurrent sensor trim

The current that is output by the transmitter can be trimmed independently of the pressure measuring circuit. This function is designed for compensating inaccuracies in the processing chain following the transmitter.

is to be measured as a voltage drop from 1 to 5 V at a resistance of 2505%. To trim the tolerance of the resistance, set the current transmitter so that the voltage drop

V and at 20 mA is exactly 5 V. current transmitter trim menu option to instruct the transmitter to output 4

measured value from the ammeter and enter it, via SIMATIC PDM for example. The transmitter uses

The current that is output by the transmitter can be trimmed independently of the pressure measuring circuit. This function is designed for compensating inaccuracies in the processing

V at a resistance of 250 Ohm +/- 5%. To trim the tolerance of the resistance, set the current transmitter so that the voltage drop

current transmitter trim menu option to instruct the transmitter to output 4 mA. Read the measured value from the ammeter and enter it, via SIMATIC PDM for example. The transmitter uses

Page 105: Transmitter AccuFLo-P DSIII series with HART-communication

this value for offset correction of the current.

• Trim at 20 mA:

Use the current transmitter trim menu option to instruct the transmitter to output 20 mA. Read the measured value from the ammeter and enter it, via SIMATIC PDM for example. The transmitter uses this value for gradient correction of the current. The value for 4 mA is not affected by this. NoteNoteNoteNote

If a multimeter is used, it must always be sufficiently accurate.

Figure7-15 Current transmitter trim

A Output characteristic curve B Characteristic curve after current transmitter trim 4 mA C Characteristic curve after current transmitter trim 20 mA

7.187.187.187.18 Factory calibrationFactory calibrationFactory calibrationFactory calibration IntroductionIntroductionIntroductionIntroduction

You can use factory calibration to reset the transmitter to the factory state.

Page 106: Transmitter AccuFLo-P DSIII series with HART-communication

DescriptionDescriptionDescriptionDescription You can use the menu-guided interface of SIMATIC PDM or HART Communicator to select

the range of parameters to be reset:

1. Current trim

2. Sensor zero point calibration (position correction)

3. Pressure corrections (zero point calibration and sensor trim)

4. All parameters relevant for the processing of measured values, such as zero point, limit point, electrical damping, display unit, current trim, zero point calibration (position correction), sensor trim, measuring speed, interrupt current limits, interrupt setting, overflow ranges of current.

5. Variable mapper. This performs the following setting:

PV= Pressure, SV= Sensor temp., TV= Electronics temp., QV= Non-linearized pressure

PV Primary variable SV Secondary variable TV Tertiary variable QV Quarternary variable

7.197.197.197.19 Static configuration dataStatic configuration dataStatic configuration dataStatic configuration data DescriptionDescriptionDescriptionDescription

A further menu command in the corresponding operating program allows you to read and also write a series of sensor-specific material data. With the factory state, this data is pre-allocated

according to the particular device model. These values are not contained in the "Factory calibration" function; in other words, changes in the device are permanently saved. List of variable material parameters:

• Flange type

• Flange material

• Remote seal type

• Filling medium

Page 107: Transmitter AccuFLo-P DSIII series with HART-communication

• O-ring material

• Remote seal

• Remote seal diaphragm material

• Number of remote seals

• Sensor filling medium

• Sensor seal diaphragm material

• Transmitter model

• Housing material

• Tube length

• Process connection

• Electrical connection

• Material of pressure cap screws

• Vent valve position

For a series of these material data items, you can enter any designation of your choice under

the option "Special". This applies to the following parameters:

• Process connection

• Flange type

• Pressure cap screws

• O-ring material

• Material of vent valve

• Vent valve position

• Remote seal type

• Remote seal

• Diaphragm material

• Remote seal filling medium

You can use up to 16 characters for each entry.

Page 108: Transmitter AccuFLo-P DSIII series with HART-communication

7.207.207.207.20 Flow rate measurementFlow rate measurementFlow rate measurementFlow rate measurement DescriptionDescriptionDescriptionDescription

For the "Differential pressure and flow rate" device version, you can select the characteristic curve of output current as follows without actuating the measuring mode selector:

• linear "lin": proportional to differential pressure

• square root extracting "sroff": proportional to flow rate, deactivated up to the application point

• square root extracting "srlin": proportional to flow rate, linear up to the application point

• square root extracting "srlin2": proportional to flow rate, two-step linear up to the application point

Variable application pointVariable application pointVariable application pointVariable application point

The output current for the "srlin" and "sroff" functions can be displayed linearly or set to zero below the application point of the square root extracting characteristic curve.

Fixed application pointFixed application pointFixed application pointFixed application point

The "srlin2" function has a permanently defined application point of 10%. The range up to this point contains two linear characteristic curve sections. The first section ranges from the zero point to 0.6% of the output value and 0.6% of the pressure value. The second section has a higher gradient and it goes up to the root application point at 10% of the output value and 1%

of the pressure value.

See alsoSee alsoSee alsoSee also

Flow rate measurement (only differential pressure)

7.217.217.217.21 Diagnostic functionsDiagnostic functionsDiagnostic functionsDiagnostic functions

7.21.17.21.17.21.17.21.1 OverviewOverviewOverviewOverview

DescriptionDescriptionDescriptionDescription

HART communication allows you to activate and evaluate a wide range of diagnostic functions from a central control room or onsite:

• Calibration/service timer

Page 109: Transmitter AccuFLo-P DSIII series with HART-communication

• Min/max indicator

• Limit monitoring modules

• Simulation of measured pressure and temperature values

• Limit monitoring of all device variables

The diagnostics strategy employed for the transmitter incorporates a diagnostic warning and

a diagnostic interrupt for diagnostic functions for monitoring limit values, e.g. for monitoring current saturation. This warning and interrupt can be configured:

• Diagnostic warning: The device transmits via HART communication the diagnostic event that has occurred. The current output value is unaffected. The message "Diagnostic Warning" alternates with the unit on the display.

• Diagnostic interrupt: The device goes into the fault current state. The message "Diagnostic Warning" or "Diagnostic Alarm" appears on the display, along with the message ERROR. In addition, the diagnostic event is made available via HART communication.

In the default settings, all warnings and alarms are switched off. You can choose to set either the diagnostic warning only or the diagnostic interrupt and warning. For HART communication, use the HART Communicator or PC software such as SIMATIC PDM. To see the steps required, refer to the attached table for operation of the HART Communicator or the help functions in the SIMATIC PDM software.

7.21.27.21.27.21.27.21.2 Operating hours counterOperating hours counterOperating hours counterOperating hours counter

DescriptionDescriptionDescriptionDescription

An operating hours counter can be read via HART communication for the electronics and another for the sensor. For HART communication, use the HART Communicator or PC

software such as SIMATIC PDM. The counters are activated the first time the transmitter is put into operation. If the device is separated from its power supply, the counter readings are automatically stored in the non-volatile memories. That means that the current counter readings can be accessed at the next restart. The operating hours counters cannot be reset.

7.21.37.21.37.21.37.21.3 Calibration timer and service timerCalibration timer and service timerCalibration timer and service timerCalibration timer and service timer

DescriptionDescriptionDescriptionDescription

To guarantee regular calibration of the electronics and for servicing work on the sensor, you can fit a two-stage timer to each. After the first time period has elapsed, a calibration or

Page 110: Transmitter AccuFLo-P DSIII series with HART-communication

service warning will be issued. After a second time period, which can be configured as a time differential, a diagnostic interrupt is reported and fault current is output.

To perform calibration work, you need to acknowledge warnings and interrupts. You can then reset the timers and switch off the monitoring function. The calibration intervals for the electronics are calculated using the following formula:

For operating/acknowledging the warnings and interrupts in SIMATIC PDM and via the HART

Communicator, the following applies:

As long as the warning/interrupt limit has not been reached, the following applies:As long as the warning/interrupt limit has not been reached, the following applies:As long as the warning/interrupt limit has not been reached, the following applies:As long as the warning/interrupt limit has not been reached, the following applies:

• "Reset" resets the timer and starts again from count 0. Monitoring remains active.

• "Acknowledge" has no effect; the timer continues running and monitoring remains active.

• "Reset and deactivate" stops the timer, resets it, and deactivates monitoring.

When the warning/interrupt limit has been reached, the following applies:When the warning/interrupt limit has been reached, the following applies:When the warning/interrupt limit has been reached, the following applies:When the warning/interrupt limit has been reached, the following applies:

• "Acknowledge" resets the warning/interrupt message, but allows the timer to keep running. In this state, a new interrupt or warning is not possible since the time limits have already been exceeded.

• "Reset" resets the warning/interrupt message and the timer. It acknowledges the interrupt or warning at the same time. The timer immediately starts running again from zero and will report again when the warning/interrupt limit is next reached. The next calibration interval is therefore immediately active.

• "Reset and deactivate W/I" resets the warning/interrupt message and the timer and deactivates it.

7.21.47.21.47.21.47.21.4 Min/max indicatorMin/max indicatorMin/max indicatorMin/max indicator

DescriptionDescriptionDescriptionDescription

The measuring transmitter provides three min/max indicator pairs, which you can use to monitor the three measured variables Pressure, Sensor temperature, and Electronics temperature for negative and positive peak values. For each measured value, a resettable min/max indicator saves the maximum and minimum peak values in long-term storage in the

two non-volatile memories. Consequently, the values are available even after the device is restarted. The min/max indicators are also updated during a simulation.

Page 111: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-16 Basic representation of min/max indicators

p Pressure

7.21.57.21.57.21.57.21.5 Limit modulesLimit modulesLimit modulesLimit modules

IntroductionIntroductionIntroductionIntroduction The diagnostic functions of this device give you an option to monitor the measured values in

programmable limits. If the limits are not adhered HART communication or notifies a higher

Monitoring of current saturationMonitoring of current saturationMonitoring of current saturationMonitoring of current saturation You can monitor the current output in the saturation range using a simple limit module. This limit module is configured and activated via HART communication. For HART communication, use a HART communicator or PC software such as SIMATIC PDM.

You need to set two time periods to configure the limit module: The first time period specifies how long the can interrupt is triggered and the device outputs its set fault current. This first time period is the response time. The second time period specifies the duration of the interrupt. This second time perstop time. Different outputs of the fault current corresponding to the set response and stop times are

Basic representation of min/max indicators

t Time

The diagnostic functions of this device give you an option to monitor the measured values in

programmable limits. If the limits are not adhered to, the device sends a warning through HART communication or notifies a higher-level instance about an analog fault current.

You can monitor the current output in the saturation range using a simple limit module. This module is configured and activated via HART communication. For HART communication,

use a HART communicator or PC software such as SIMATIC PDM. You need to set two time periods to configure the limit module: The first time period specifies how long the current output is allowed to be in saturation before an interrupt is triggered and the device outputs its set fault current. This first time period is the

The second time period specifies the duration of the interrupt. This second time per

Different outputs of the fault current corresponding to the set response and stop times are

The diagnostic functions of this device give you an option to monitor the measured values in

to, the device sends a warning through level instance about an analog fault current.

You can monitor the current output in the saturation range using a simple limit module. This module is configured and activated via HART communication. For HART communication,

urrent output is allowed to be in saturation before an interrupt is triggered and the device outputs its set fault current. This first time period is the

The second time period specifies the duration of the interrupt. This second time period is the

Different outputs of the fault current corresponding to the set response and stop times are

Page 112: Transmitter AccuFLo-P DSIII series with HART-communication

shown in the following example.

Configuring the direction of fault currentConfiguring the direction of fault currentConfiguring the direction of fault currentConfiguring the direction of fault current The current value is proportional to pressure within the saturation limits. When the saturation limits are exceeded, the direction of fault current can however vary from the direction of saturation. The upper or the lower fault current is displayed depending on the parameter settings of the direction of fault current. You can configure the direction of fault current for a current saturation interrupt depending on your requirements. The following settings are possible under the current saturation menu: Active interrupt value The applicable settings are those under the current interrupt type menu

command. Inverse interrupt value The applicable settings are the inverse settings under the current

interrupt type menu command. Saturated interrupt value The fault current is output in the direction of current saturation. Inverse saturated interrupt value

The fault current is output in the opposite direction to current saturation.

The difference between different settings is evident in examples 3 and 4 in the following figure. Example 3 shows the direction of fault current with the "Saturated current value" setting. Example 4 shows the direction of fault current with the "Active upper interrupt value"

setting.

ExampleExampleExampleExample The configured saturation limits in the following figures are 3.8 mA and 20.5 mA. Example 1Example 1Example 1Example 1: the response time starts at t1. At t1, current reaches the configured saturation limit of 20.5 mA for the first time. At t2, the response time ends. The stop time begins and the interrupt is triggered. Time t3 is the configured end of the stop time. At t3, the interrupt is

immediately revoked even if the current then drops below the saturation limit again. Example 2Example 2Example 2Example 2: the duration of the current saturation is shorter than the response time (t1, t2). In that case, the device does not go into "fault current" state. Example 3Example 3Example 3Example 3: the current drops below the lower saturation limit only for a short time. The fault

Page 113: Transmitter AccuFLo-P DSIII series with HART-communication

current is not switched off until after the end of the stop time (tcorresponds to the "Saturated interrupt value" setting. Thdirection of current saturation.

Example 4Example 4Example 4Example 4: the current drops below the lower saturation limit only for a short time. The fault current is not switched off until after the end of the stop time (t

corresponds to the "Active upper interrupt value" setting. The upper fault current is outputted although the direction of current saturation is downward.

Figure7-17 Four examples of saturation monitoring

See alsoSee alsoSee alsoSee also Fault current

7.227.227.227.22 SimulationSimulationSimulationSimulation

7.22.17.22.17.22.17.22.1 Overview of simulationOverview of simulationOverview of simulationOverview of simulation

DescriptionDescriptionDescriptionDescription

With the "Simulation" diagnostic function, you can receive and process simulated measurement data onsite or in the control room without having process pressure or a

temperature value. This allows you to run individual process sequences in the "cold" state and thus simulate process states. In addition, if you inject simulation values you can test the

current is not switched off until after the end of the stop time (t3). The direction of fault current corresponds to the "Saturated interrupt value" setting. The fault current is output in the direction of current saturation.

: the current drops below the lower saturation limit only for a short time. The fault current is not switched off until after the end of the stop time (t3). The direction of fault c

corresponds to the "Active upper interrupt value" setting. The upper fault current is outputted although the direction of current saturation is downward.

Four examples of saturation monitoring

Overview of simulationOverview of simulationOverview of simulationOverview of simulation

With the "Simulation" diagnostic function, you can receive and process simulated measurement data onsite or in the control room without having process pressure or a

temperature value. This allows you to run individual process sequences in the "cold" state and thus simulate process states. In addition, if you inject simulation values you can test the

). The direction of fault current e fault current is output in the

: the current drops below the lower saturation limit only for a short time. The fault ). The direction of fault current

corresponds to the "Active upper interrupt value" setting. The upper fault current is outputted

With the "Simulation" diagnostic function, you can receive and process simulated measurement data onsite or in the control room without having process pressure or a

temperature value. This allows you to run individual process sequences in the "cold" state and thus simulate process states. In addition, if you inject simulation values you can test the

Page 114: Transmitter AccuFLo-P DSIII series with HART-communication

line routing from the control room to the individual transmitter.

The value to be simulated can be provided as a fixed value or in the form of a ramp function.Simulation of pressure and temperature values is handled in the same way in terms of parameter settings and function, so the following will only deal with the general simulation procedures "Fixed value" and "Ramp function".

For reasons of safety, all simmeans that when the device is restarted any simulation which may be active will be shut down. You can simulate the pressure and both temperature values. It should be noted here that changing the temperatures by simulation will have no effect on the measured pressure value.

Figure7-18 Block diagram of simulation

7.22.27.22.27.22.27.22.2 Simulation as fixed valueSimulation as fixed valueSimulation as fixed valueSimulation as fixed value

DescriptionDescriptionDescriptionDescription

Taking the physical unit into account you can set a fixed simulation value for all three possible simulation paths. You can simulate the pressure value and both temperature values

simultaneously. While pressure simulation is activated, the transmitter willchanges in the process pressure. The output value for the current adjusts itself in accordance with the preset pressure value. Simulation of the temperature values has no effect on the current output. It can only be observed via HART communic

line routing from the control room to the individual transmitter.

The value to be simulated can be provided as a fixed value or in the form of a ramp function.Simulation of pressure and temperature values is handled in the same way in terms of parameter settings and function, so the following will only deal with the general simulation procedures "Fixed value" and "Ramp function".

For reasons of safety, all simulation data are held only in the non-volatile user memory. This means that when the device is restarted any simulation which may be active will be shut down. You can simulate the pressure and both temperature values. It should be noted here

the temperatures by simulation will have no effect on the measured pressure

Block diagram of simulation

Simulation as fixed valueSimulation as fixed valueSimulation as fixed valueSimulation as fixed value

Taking the physical unit into account you can set a fixed simulation value for all three possible simulation paths. You can simulate the pressure value and both temperature values

simultaneously. While pressure simulation is activated, the transmitter willchanges in the process pressure. The output value for the current adjusts itself in accordance with the preset pressure value. Simulation of the temperature values has no effect on the

It can only be observed via HART communication.

The value to be simulated can be provided as a fixed value or in the form of a ramp function. Simulation of pressure and temperature values is handled in the same way in terms of parameter settings and function, so the following will only deal with the general simulation

volatile user memory. This means that when the device is restarted any simulation which may be active will be shut down. You can simulate the pressure and both temperature values. It should be noted here

the temperatures by simulation will have no effect on the measured pressure

Taking the physical unit into account you can set a fixed simulation value for all three possible simulation paths. You can simulate the pressure value and both temperature values

simultaneously. While pressure simulation is activated, the transmitter will not react to changes in the process pressure. The output value for the current adjusts itself in accordance with the preset pressure value. Simulation of the temperature values has no effect on the

Page 115: Transmitter AccuFLo-P DSIII series with HART-communication

7.22.37.22.37.22.37.22.3 Simulation with a ramp functionSimulation with a ramp functionSimulation with a ramp functionSimulation with a ramp function

DescriptionDescriptionDescriptionDescription

In addition to the adjustable fixed values for all three simulation paths, you can, as a second option, also configure one ramp function in each case. Adjustable lower and upper values together determine the limits between which the simulation values with a rising or falling tendency can move. The step width can be calculated with the step number, which is also

adjustable. You can specify the rate of rise of the ramp via the duration of the individual ramp steps.

Page 116: Transmitter AccuFLo-P DSIII series with HART-communication

7.237.237.237.23 Limit monitorLimit monitorLimit monitorLimit monitor DescriptionDescriptionDescriptionDescription

You can activate up to three limit monitors in order to monitor any of the device variables. The limit monitor monitors a value at an upper or lower limit value. If this limit is violated it sends a diagnostic warning or a diagnostic interrupt. Select the "Limit Monitor" menu command in

SIMATIC PDM or in the HART communicator. You can program the following values for each of the three limit monitors:

Table7-4Parameter of the limit monitor

Monitoring variable You will be shown a list of the active device variables. This list is independent of the measuring mode selected.

Limit monitoring: warning / interrupt Select whether a warning or a warning plus an interrupt should be triggered when a limit is violated.

Limit monitoring: upper / lower Specify here whether a device variable monitors the upper limit, the lower limit, or both limits.

Upper limit value Upper limit value in the unit of the device variable.

Lower limit value Lower limit value in the unit of the device variable.

Hysteresis Operating point for chatter suppression in the case of small pressure changes.

Response time The time which must pass after the limit is violated before this violation is registered.

Stop time The time for which a limit interrupt or warning will always be sustained even when the event which triggered it is no longer present.

Page 117: Transmitter AccuFLo-P DSIII series with HART-communication

Figure7-19 Trip levels for the limit monitor

You can count the limit violations for each limit monitor by activating an event counter that provides separate, cumulative totals of upper and lower limit violations. A diagnostic warning

and / or a diagnostic interrupt can be issued once a certain numbernumber which you can also program. You can program the following values for the event counter:

Table7-5Parameters of the event counter

Event counter: upper limit

Event counter: lower limit

Comparison value: upper limit

Comparison value: upper limit

Limit monitoring, warning/interrupt: upper limit

Limit monitoring, warning/interrupt: lower limit

Trip levels for the limit monitor

You can count the limit violations for each limit monitor by activating an event counter that provides separate, cumulative totals of upper and lower limit violations. A diagnostic warning

and / or a diagnostic interrupt can be issued once a certain number of violations is reached, a number which you can also program. You can program the following values for the event

Select here whether a warning or a warning plus an interrupt shotriggered when the comparison value is exceeded.

Select here whether a warning or a warning plus an interrupt should be triggered when the comparison value is not met.

Specify here the number of overflows at which a warning or a warning plus an interrupt should be triggered.

Specify here the number of underflows at which a warning or a warning plus an interrupt should be triggered.

g/interrupt: upper limit Select whether a warning or a warning plus an interrupt should be triggered when the event counter upper limit is violated.

Limit monitoring, warning/interrupt: lower limit Select whether a warning or a warning plus an interrupt striggered when the event counter lower limit is violated.

You can count the limit violations for each limit monitor by activating an event counter that provides separate, cumulative totals of upper and lower limit violations. A diagnostic warning

of violations is reached, a number which you can also program. You can program the following values for the event

Select here whether a warning or a warning plus an interrupt should be triggered when the comparison value is exceeded.

Select here whether a warning or a warning plus an interrupt should be

number of overflows at which a warning or a warning

Specify here the number of underflows at which a warning or a warning

Select whether a warning or a warning plus an interrupt should be triggered when the event counter upper limit is violated.

Select whether a warning or a warning plus an interrupt should be triggered when the event counter lower limit is violated.

Page 118: Transmitter AccuFLo-P DSIII series with HART-communication

Reset event counter upper limit Here you can reset the upper limit counter to zero. A new event is not possible until the counter has been reset.

Reset event counter lower limit Here you can reset the lower limit counter to zero. A new event is not possible until the counter has been reset.

Warning/interrupt acknowledgement Here you can acknowledge each warning or interrupt separately.

Figure7-20 Limit monitor and event counter

Messages from the limit monitor and from the event counter can be acknowledged separately. Resetting the event counter starts a new monitoring interval.

Page 119: Transmitter AccuFLo-P DSIII series with HART-communication

8888 Functional safetyFunctional safetyFunctional safetyFunctional safety

8.18.18.18.1 General safety instructionsGeneral safety instructionsGeneral safety instructionsGeneral safety instructions

8.1.18.1.18.1.18.1.1 SafetySafetySafetySafety----instrumented systeminstrumented systeminstrumented systeminstrumented system

This chapter describes the functional safety in general and not specific to a device. The devices in the examples are selected as representative examples. The device-specific information follows in the next chapter.

DescriptionDescriptionDescriptionDescription

The sensor, logic unit/control system and final controlling element combine to form a safety-instrumented system, which executes a safety function.

Figure8-1 Example of a safety-instrumented system

SF Failure signal

Page 120: Transmitter AccuFLo-P DSIII series with HART-communication

Functioning of the system as shown Functioning of the system as shown Functioning of the system as shown Functioning of the system as shown

The transmitter generates a process

monitors this signal to ensure that it does not fall below or exceed a set limit value. In case of a fault, the control system generates a failure signpositioner, which switches the associated valve to the specified safety position.

8.1.28.1.28.1.28.1.2 Safety Integrity LevelSafety Integrity LevelSafety Integrity LevelSafety Integrity Level

The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability range for the failure of a safety function.

DescriptionDescriptionDescriptionDescription

The following table shows the dependency of the SIL on the "average probability of

dangerous failures of a safety function of the entire safetytable deals with "Low demand mode", i.e. the safety function is required a maximum of once per year on average.

Table8-1 Safety Integrity Level

SILSILSILSIL

4

3

2

1

The "average probability of dangerous failures of the entire safety(PFDAVG) is normally split between the three sub

Figure8-2 Example of PFD distribution

The following table shows the achievable Safety Integrity Level (SIL) for the entire

Functioning of the system as shown Functioning of the system as shown Functioning of the system as shown Functioning of the system as shown in the examplein the examplein the examplein the example The transmitter generates a process-specific analog signal. The downstream control system

monitors this signal to ensure that it does not fall below or exceed a set limit value. In case of a fault, the control system generates a failure signal of < 3.6 mA or > 22 mA for the connected positioner, which switches the associated valve to the specified safety position.

The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from to SIL 4. Each level corresponds to the probability range for the failure of a safety

The following table shows the dependency of the SIL on the "average probability of

dangerous failures of a safety function of the entire safety-instrumented system" (PFDtable deals with "Low demand mode", i.e. the safety function is required a maximum of once per year on average.

Safety Integrity Level

IntervalIntervalIntervalInterval

10-5 ≤ PFDAVG < 10-4

10-4 ≤ PFDAVG < 10-3

10-3 ≤ PFDAVG < 10-2

10-2 ≤ PFDAVG < 10-1

The "average probability of dangerous failures of the entire safety-instrumented system" ) is normally split between the three sub-systems in the following figure.

Example of PFD distribution

The following table shows the achievable Safety Integrity Level (SIL) for the entire

specific analog signal. The downstream control system

monitors this signal to ensure that it does not fall below or exceed a set limit value. In case of al of < 3.6 mA or > 22 mA for the connected

positioner, which switches the associated valve to the specified safety position.

The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from to SIL 4. Each level corresponds to the probability range for the failure of a safety

The following table shows the dependency of the SIL on the "average probability of

trumented system" (PFDAVG) The table deals with "Low demand mode", i.e. the safety function is required a maximum of once

instrumented system" systems in the following figure.

The following table shows the achievable Safety Integrity Level (SIL) for the entire

Page 121: Transmitter AccuFLo-P DSIII series with HART-communication

safety-instrumented system for type B subsystems depending on the safe failure fraction (SFF) and the hardware fault tolerance (HFT). Type B subsystems include analog transmitters and shut-off valves without complex components, e.g. microprocessors (also see IEC 61508, Section 2).

SFFSFFSFFSFF HFTHFTHFTHFT

0000 1 (0) 1 (0) 1 (0) 1 (0) 1)1)1)1) 2 (1) 2 (1) 2 (1) 2 (1) 1)1)1)1)

< 60 % Not permitted SIL 1 SIL 2

60 to 90 % SIL 1 SIL 2 SIL 3 90 to 99 % SIL 2 SIL 3 SIL 4

> 99 % SIL 3 SIL 4 SIL 4

1) As per IEC 61511-1, Section 11.4.4 According to IEC 61511-1, Section 11.4.4, the hardware fault tolerance (HFT) can be reduced by one (values in brackets) for sensors and final controlling elements with complex

components if the following conditions are applicable for the device:

• The device is proven-in-use.

• The user can configure only the process-related parameters, e.g. control range, signal direction in case of a fault, limiting values, etc.

• The configuration level of the firmware is blocked against unauthorized operation.

• The function requires SIL of less than 4.

The device fulfills these conditions.

See alsoSee alsoSee alsoSee also

Safety characteristics

Page 122: Transmitter AccuFLo-P DSIII series with HART-communication

8.28.28.28.2 DeviceDeviceDeviceDevice----specific safety instructionsspecific safety instructionsspecific safety instructionsspecific safety instructions

8.2.18.2.18.2.18.2.1 Safety functionSafety functionSafety functionSafety function

Safety function for pressure transmittersSafety function for pressure transmittersSafety function for pressure transmittersSafety function for pressure transmitters

Measuring pressures is the safety function for from 4 to 20 mA and ensures an accuracy of safety function ensures that the diagnosis function responds within 4 seccase scenario.

WarningWarningWarningWarning

The binding settings and conditions are listed in the "Settings" and "Safety characteristics" sections.

These conditions must be met in order to fulfil the safety function.

The calculated Mean Time Betweenis approximately 400 years.

See alsoSee alsoSee alsoSee also

Safety characteristics

8.2.28.2.28.2.28.2.2 RequirementsRequirementsRequirementsRequirements

RequirementsRequirementsRequirementsRequirements

Functional safety has the following requirements:

• Functional safety to SIL 2 under IEC 61508 or IEC 6151111/02/03

• Explosion protection for corresponding versions

• Electromagnetic compatibility in

8.2.38.2.38.2.38.2.3 SettingsSettingsSettingsSettings

The following settings must be adhered to after installing and commissioning as per the Operating Instructions:

Operation/configurationOperation/configurationOperation/configurationOperation/configuration

While operating/configuring, ensure that the technical data of the pressure transmitter are adhered to in their respective version.

specific safety instructionsspecific safety instructionsspecific safety instructionsspecific safety instructions

Safety function for pressure transmittersSafety function for pressure transmittersSafety function for pressure transmittersSafety function for pressure transmitters

Measuring pressures is the safety function for AccuFlo P. It is applicable for output current mA and ensures an accuracy of ± 2% of the measured value in this range. The

safety function ensures that the diagnosis function responds within 4 sec

The binding settings and conditions are listed in the "Settings" and "Safety characteristics" sections.

These conditions must be met in order to fulfil the safety function.

The calculated Mean Time Between Failures (MTBF) for the AccuFlo P pressure transmitter is approximately 400 years.

Safety characteristics

Functional safety has the following requirements:

Functional safety to SIL 2 under IEC 61508 or IEC 61511-1, from firmware version FW: from

Explosion protection for corresponding versions

Electromagnetic compatibility in compliance with EN 61326

The following settings must be adhered to after installing and commissioning as per the Operating Instructions:

While operating/configuring, ensure that the technical data of the pressure transmitter are adhered to in their respective version.

P. It is applicable for output current 2% of the measured value in this range. The

safety function ensures that the diagnosis function responds within 4 seconds in the worst

The binding settings and conditions are listed in the "Settings" and "Safety characteristics" sections.

P pressure transmitter

1, from firmware version FW: from

The following settings must be adhered to after installing and commissioning as per the

While operating/configuring, ensure that the technical data of the pressure transmitter are

Page 123: Transmitter AccuFLo-P DSIII series with HART-communication

Checking the safety functionChecking the safety functionChecking the safety functionChecking the safety function

We recommend that:

• You check the status for warnings and alarms.

• You check the measurement value limits.

• You simulate different current values.

• You check the measuring accuracy that must be in the range of ± 2% for the safety function.

― You check the zero point, e.g. in a pressure-less state, for gauge and differential pressure.

― You check the zero point, e.g. with a defined pressure, for absolute pressure.

Protection against configuration changesProtection against configuration changesProtection against configuration changesProtection against configuration changes

After parameterizing/commissioning:

1. Set the lock mode in Mode 10 to write protection "L".

Operation via keys and HART communication is blocked.

2. Protect the keys from unintended change in the parameters, e.g. by lead-sealing.

8.2.48.2.48.2.48.2.4 Behavior in case of faultsBehavior in case of faultsBehavior in case of faultsBehavior in case of faults

RepairsRepairsRepairsRepairs

Defective devices should be sent in to the repair department with details of the fault and the cause. When ordering replacement devices, please specify the serial number of the original device. The serial number can be found on the rating plate.

The address of the responsible S.K.I. repair center, contacts, spare parts lists, etc. can be found on the Internet.

Page 124: Transmitter AccuFLo-P DSIII series with HART-communication

8.2.58.2.58.2.58.2.5 Maintenance/CheckingMaintenance/CheckingMaintenance/CheckingMaintenance/Checking

IntervalIntervalIntervalInterval

We recommend that the functioning of the pressure transmitter be checked at regular intervals of one year.

Checking the safety functionChecking the safety functionChecking the safety functionChecking the safety function

We recommend that:

• You check the status for warnings and alarms.

• You check the measurement value limits.

• You simulate different current values.

• You check the measuring accuracy that must be in the range of ± 2% for the safety function.

― You check the zero point, e.g. in a pressure-less state, for gauge and differential pressure.

― You check the zero point, e.g. with a defined pressure, for absolute pressure.

Checking safetyChecking safetyChecking safetyChecking safety

You should regularly check the safety function of the entire safety circuit in line with IEC 61508/61511. The testing intervals are determined during the calculation for each individual safety circuit in a system (PFDAVG).

ElectronicsElectronicsElectronicsElectronics

The safety function of the transmitter is ensured only with the electronics delivered by the factory. It cannot be replaced.

8.2.68.2.68.2.68.2.6 Safety characteristicsSafety characteristicsSafety characteristicsSafety characteristics

The safety characteristics necessary for using the system are listed in the "SIL declaration of

conformity". These values apply under the following conditions:

• The AccuFlo P pressure transmitter is only used in applications with a low demand rate for the safety function (low demand mode).

• Communication with the HART protocol is used only for the following:

― Device configuration

Page 125: Transmitter AccuFLo-P DSIII series with HART-communication

― Reading diagnostic values

― However, it is not used for operations critical to safety. In particular, the trace function must not be activated in safety related operation.

• The safety-related parameters/settings have been entered by local operation or HART communication before commencing safety-instrumented operation. They are checked on the local display.

(see "Settings" section)

• The safety function test is concluded successfully.

• The transmitter is blocked against unwanted and unauthorized changes/operation.

• The current signal of 4 to 20 mA of the transmitter is evaluated by a safe system.

• The calculation of fault rates is based on a Mean Time To Repair (MTTR) of eight hours.

See alsoSee alsoSee alsoSee also

Settings

Page 126: Transmitter AccuFLo-P DSIII series with HART-communication

9999 CommissioningCommissioningCommissioningCommissioning

9.19.19.19.1 Safety notes for commissioningSafety notes for commissioningSafety notes for commissioningSafety notes for commissioning

WarningWarningWarningWarning

Hazardous areasHazardous areasHazardous areasHazardous areas

If the transmitters are to be used as category 1/2 operational resources, please observe the type examination certificates or the test certifications applicable in your country.

WarningWarningWarningWarning

Incorrect or improper use of the shut

considerable damage to property.

WarningWarningWarningWarning

Using toxic substancesUsing toxic substancesUsing toxic substancesUsing toxic substances

The transmitter should not be depressurized if toxic substances are being used.

WarningWarningWarningWarning

Intrinsically safe circuitsIntrinsically safe circuitsIntrinsically safe circuitsIntrinsically safe circuits

With intrinsically-safe circuits, use only certified ammeters appropriate for the transmitter."Intrinsically safe""Intrinsically safe""Intrinsically safe""Intrinsically safe"

If a non-conforming supply unit is used, the "failand the approval certification will be invalid.

WarningWarningWarningWarning

Laying of cablesLaying of cablesLaying of cablesLaying of cables

Connect the devices that are operated in hazardous areas as per the stipulations applicable in your

country.

NoticeNoticeNoticeNotice

Before commissioning, check the basic parameters. Due to changes in the operating functions, the display and the measurement output could be

set such that the actual process pressure is not reproduced.

CommissioningCommissioningCommissioningCommissioning

Safety notes for commissioningSafety notes for commissioningSafety notes for commissioningSafety notes for commissioning

If the transmitters are to be used as category 1/2 operational resources, please observe the type examination certificates or the test certifications applicable in your country.

Incorrect or improper use of the shut-off modules can lead to serious physical injuries or

considerable damage to property.

Using toxic substancesUsing toxic substancesUsing toxic substancesUsing toxic substances

The transmitter should not be depressurized if toxic substances are being used.

Intrinsically safe circuitsIntrinsically safe circuitsIntrinsically safe circuitsIntrinsically safe circuits

safe circuits, use only certified ammeters appropriate for the transmitter.

conforming supply unit is used, the "fail-safe" type of protection will no longer be and the approval certification will be invalid.

Connect the devices that are operated in hazardous areas as per the stipulations applicable in your

Before commissioning, check the basic parameters.

Due to changes in the operating functions, the display and the measurement output could be

set such that the actual process pressure is not reproduced.

If the transmitters are to be used as category 1/2 operational resources, please observe the type examination certificates or the test certifications applicable in your country.

off modules can lead to serious physical injuries or

The transmitter should not be depressurized if toxic substances are being used.

safe circuits, use only certified ammeters appropriate for the transmitter.

safe" type of protection will no longer be effective

Connect the devices that are operated in hazardous areas as per the stipulations applicable in your

Due to changes in the operating functions, the display and the measurement output could be

Page 127: Transmitter AccuFLo-P DSIII series with HART-communication

9.29.29.29.2 Notes on commissioningNotes on commissioningNotes on commissioningNotes on commissioning

NoteNoteNoteNote In order to obtain stable measured values, the transmitter must be allowed to warm up for at least 5 minutes after the power supply is switched on. The order data must match with the values given on the type plate. The transmitter is in operation as soon as the power supply is switched on. The following cases of commissioning can be taken as the typical examples. Changing the arrangements specified here may be practical depending on the system configuration.

9.39.39.39.3 Introduction to commissioningIntroduction to commissioningIntroduction to commissioningIntroduction to commissioning Following commissioning, the transmitter is immediately ready for use. To obtain stable measured values, the transmitter needs to be allowed to warm up for five minutes or so after the power supply is switched on. The measuring span which can be set corresponds to the information on the nameplate. Even in the case of a customer-specific setting configured in the factory, the zero point and the limit point will appear on the nameplate. If need be, you can change the parameters by simple user operations on the device even during commissioning.

Page 128: Transmitter AccuFLo-P DSIII series with HART-communication

9.49.49.49.4 gauge pressure, absolute pressure from the differential pressure series gauge pressure, absolute pressure from the differential pressure series gauge pressure, absolute pressure from the differential pressure series gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure seriesand absolute pressure from the gauge pressure seriesand absolute pressure from the gauge pressure seriesand absolute pressure from the gauge pressure series

9.4.19.4.19.4.19.4.1 Commissioning for gasesCommissioning for gasesCommissioning for gasesCommissioning for gases

OverviewOverviewOverviewOverview

Usual arrangement Special arrangement

Measuring gases above the pressure tapping point

Measuring gases below the pressure tapping point

① Pressure transmitter ② Shut-off module

Page 129: Transmitter AccuFLo-P DSIII series with HART-communication

③ Shut-off valve to process ④ Shut-off valve for test connection or for bleed screw ⑤ Pressure line ⑥ Shut-off valve ⑦ Shut-off valve (optional) ⑧ Condensation vessel (optional) ⑨ Drain valve

ConditionConditionConditionCondition All valves are closed.

ProcedureProcedureProcedureProcedure To commission the transmitter for gases, proceed as follows:

1. Open the shut-off valve for the test connection ③.

2. Via the test connection of the shut-off module ②, apply the pressure corresponding to the start of scale value to the pressure transmitter ①.

3. Check the start of scale value.

4. If the start of scale value differs from the value desired, correct it.

5. Close the shut-off valve for the test connection ④..

6. Open the shut-off valve ⑥ at the pressure tapping point.

7. Open the shut-off valve for the process ③.

9.4.29.4.29.4.29.4.2 Commissioning with steam or liquidCommissioning with steam or liquidCommissioning with steam or liquidCommissioning with steam or liquid

Page 130: Transmitter AccuFLo-P DSIII series with HART-communication

OverviewOverviewOverviewOverview

Figure9-1 Measuring steam

① Pressure transmitter ② Shut-off module ③ Shut-off valve to process ④ Shut-off valve for test connection or for bleed screw ⑤ Pressure line ⑥ Shut-off valve ⑦ Drain valve ⑧ Compensation vessel (steam only)

ConditionConditionConditionCondition All valves are closed.

ProcedureProcedureProcedureProcedure To commission the transmitter for steam or liquid, proceed as follows:

1. Open the shut-off valve for the test connection ④.

Page 131: Transmitter AccuFLo-P DSIII series with HART-communication

2. Via the test connection of the shutscale value to the pressure transmitter

3. Check the start of scale value.

4. If the start of scale value differs from the value desired, correct it.

5. Close the shut-off valve for the test connecti

6. Open the shut-off valve

7. Open the shut-off valve for the process

9.59.59.59.5 Differential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rate

9.5.19.5.19.5.19.5.1 Safety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rate

WarningWarningWarningWarning

Ensure that the locking screw and/or the vent valve are connected and adequately fixed.

Ensure that the valves are operated correctly and properly.

If the lock screws are missing or are not sufficiently tight, and/or if the valves are operated incorrectly or improperly, it could lead to serious physical injuries or considerable damage to property.

WarningWarningWarningWarning

Hot mediumsHot mediumsHot mediumsHot mediums

In the case of hot mediums, the individual operational steps should be carried out one after the

other. Otherwise, it could lead to excessive heatransmitter.

9.5.29.5.29.5.29.5.2 Commissioning in gaseous environmentsCommissioning in gaseous environmentsCommissioning in gaseous environmentsCommissioning in gaseous environments

OverviewOverviewOverviewOverview

Usual arrangement

Via the test connection of the shut-off module ②, apply the pressure corresponding to the start of scale value to the pressure transmitter ①.

Check the start of scale value.

If the start of scale value differs from the value desired, correct it.

off valve for the test connection ④.

off valve ⑥ at the pressure tapping point.

off valve for the process ③.

Differential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rateDifferential pressure and flow rate Safety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rate

that the locking screw and/or the vent valve are connected and adequately fixed.

Ensure that the valves are operated correctly and properly.

If the lock screws are missing or are not sufficiently tight, and/or if the valves are operated operly, it could lead to serious physical injuries or considerable damage to

In the case of hot mediums, the individual operational steps should be carried out one after the

other. Otherwise, it could lead to excessive heating, thus causing damage to the valves and the

Commissioning in gaseous environmentsCommissioning in gaseous environmentsCommissioning in gaseous environmentsCommissioning in gaseous environments

Special arrangement

, apply the pressure corresponding to the start of

Safety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rateSafety notes for commissioning with differential pressure and flow rate

that the locking screw and/or the vent valve are connected and adequately fixed.

If the lock screws are missing or are not sufficiently tight, and/or if the valves are operated operly, it could lead to serious physical injuries or considerable damage to

In the case of hot mediums, the individual operational steps should be carried out one after the

ting, thus causing damage to the valves and the

Page 132: Transmitter AccuFLo-P DSIII series with HART-communication

Transmitter aboveaboveaboveabove the differential pressure transducer

Transmitter belowbelowbelowbelow the differential pressure transducer

① Pressure transmitter ② Stabilizing valve ③,④ Differential pressure valves ⑤ Differential pressure lines ⑥ Shut-off valves ⑦ Blowout valves ⑧ Condensation vessels (optional) ⑨ Differential pressure transducer

Page 133: Transmitter AccuFLo-P DSIII series with HART-communication

ConditionConditionConditionCondition All shut-off valves are closed.

ProcedureProcedureProcedureProcedure To commission the transmitter for gases, proceed as follows:

1. Open both the shut-off valves ⑥ at the pressure tapping point.

2. Open the stabilizing valve ②.

3. Open the differential pressure valve (③ or ④).

4. Check and if required correct the zero point when the start of scale value is 0 mbar (4 mA).

5. Close the stabilizing valve ②.

6. Open the other differential pressure valve (③ or ④).

9.5.39.5.39.5.39.5.3 Commissioning for liquidsCommissioning for liquidsCommissioning for liquidsCommissioning for liquids

OverviewOverviewOverviewOverview

Usual arrangement Special arrangement

Page 134: Transmitter AccuFLo-P DSIII series with HART-communication

Transmitter belowbelowbelowbelow the differential pressure transducer ① Pressure transmitter

② Stabilizing valve

③,④ Differential pressure valves

⑤ Differential pressure lines

⑥ Shut-off valves

⑦ Blowout valves

⑧ Gas collector vessels (optional)

⑨ Differential pressure transducer

⑩ Vent valves

ConditionConditionConditionCondition All valves are closed.

ProcedureProcedureProcedureProcedure

WarningWarningWarningWarning

The transmitter should not be depressurized if toxic substances are being used.

To commission the transmitter with liquids, proceed as follows:

1. Open both the shut

2. Open the stabilizing valve

3. In the case of Transmitter below the differential pressure transducerTransmitter below the differential pressure transducerTransmitter below the differential pressure transducerTransmitter below the differential pressure transducerone after the other In the case of a transmitter above the differential pressure transducertransmitter above the differential pressure transducertransmitter above the differential pressure transducertransmitter above the differential pressure transducerafter the other ⑩

4. Close both the blowout valves

5. Open the differential pressure valve until the liquid emerges.

the differential pressure Transmitter aboveaboveaboveabove the differential pressure transducer

Pressure transmitter Stabilizing valve Differential pressure valves Differential pressure lines

off valves Blowout valves Gas collector vessels (optional) Differential pressure transducer

All valves are closed.

The transmitter should not be depressurized if toxic substances are being used.

To commission the transmitter with liquids, proceed as follows:

Open both the shut-off valves ⑥ at the pressure tapping point.

Open the stabilizing valve ②.

Transmitter below the differential pressure transducerTransmitter below the differential pressure transducerTransmitter below the differential pressure transducerTransmitter below the differential pressure transducer Open both the blowout valves one after the other ⑦ until the air-free liquid emerges.

transmitter above the differential pressure transducertransmitter above the differential pressure transducertransmitter above the differential pressure transducertransmitter above the differential pressure transducer, open both the vent valves one until the liquid emerges.

Close both the blowout valves ⑦ or vent valves ⑩.

Open the differential pressure valve ③ and the vent valve at the plus chamber of the transmitter until the liquid emerges.

differential pressure transducer

The transmitter should not be depressurized if toxic substances are being used.

Open both the blowout valves

, open both the vent valves one

and the vent valve at the plus chamber of the transmitter ①

Page 135: Transmitter AccuFLo-P DSIII series with HART-communication

6. Close the vent valve.

7. Open the vent valve at the minus chamber of the transmitter ① until the liquid emerges.

8. Close the differential pressure valve ③.

9. Open the differential pressure valve ④ until the liquid emerges and then close it.

10. Close the vent valve at the minus chamber of the transmitter ①.

11. Open the differential pressure valve ③ by rotating it in half a turn.

12. Check and if required correct the zero point in case of start of scale value 0 bar (4 mA).

13. Close the stabilizing valve ②.

14. Open the differential pressure valves (③ and ④) completely.

9.5.49.5.49.5.49.5.4 Commissioning with vaporCommissioning with vaporCommissioning with vaporCommissioning with vapor

OverviewOverviewOverviewOverview

Figure9-2 Measuring steam

① Pressure transmitter ② Stabilizing valve ③,④ Differential pressure valves

Page 136: Transmitter AccuFLo-P DSIII series with HART-communication

⑤ Differential pressure lines ⑥ Shut-off valves ⑦ Blowout valves ⑧ Condensate pots ⑨ Differential pressure transducer ⑩ Insulation

ConditionConditionConditionCondition All valves are closed.

ProcedureProcedureProcedureProcedure CautionCautionCautionCaution The measuring result is error-free only if the differential pressure lines ⑤ have equally high condensate columns with the same temperature. The zero calibration must be repeated if required if these conditions are fulfilled. If the shut-off valves ⑥ and the differential pressure valves ③ are open at the same time and the stabilizing valve ② is opened, there is a possibility of the transmitter ① being damaged due to the streaming vapor.

To commission the transmitter for vapor, proceed as follows:

1. Open both the shut-off valves ⑥ at the pressure tapping point.

2. Open the stabilizing valve ②.

3. Wait till the vapor in the differential pressure lines ⑤ and in the condensate pots ⑧ condenses.

4. Open the differential pressure valve ③ and the vent valve at the plus chamber of the transmitter ①till the air-free condensate.

5. Close the vent valve.

6. Open the vent valve at the minus chamber of the transmitter ① till the air-free condensate goes out.

7. Close the differential pressure valve ③.

8. Open the differential pressure valve ④ till the air-free condensate goes out and then close it.

9. Close the vent valve at the minus chamber ①.

Page 137: Transmitter AccuFLo-P DSIII series with HART-communication

10. Open the differential pressure valve ③ by rotating it in half a turn.

11. Check and if required correct the zero point in case of start of scale value 0 bar (4 mA).

12. Close the stabilizing valve ②.

13. Open the differential pressure valve ③ and ④ completely.

Page 138: Transmitter AccuFLo-P DSIII series with HART-communication

10101010 Service and maintenanceService and maintenanceService and maintenanceService and maintenance

10.110.110.110.1 Notes for servicingNotes for servicingNotes for servicingNotes for servicing

NoteNoteNoteNote Depending on the use of the device and certain empirical values, determine a maintenance

interval for the tests to be carried out repeatedly. The maintenance interval is influenced by the corrosion resistance depending on the site of use. NoteNoteNoteNote Checking the gasketsChecking the gasketsChecking the gasketsChecking the gaskets Check the gaskets of the pressure transmitter at regular intervals. Grease or replace the gaskets if required.

10.210.210.210.2 Display in case of a faultDisplay in case of a faultDisplay in case of a faultDisplay in case of a fault Check the start of scale value of the device from time to time. Differentiate between the following in case of a fault:

• The internal self test has detected a fault, e.g. sensor break, hardware fault/Firmware fault.

Displays:

― Digital display: "ERROR" display and ticker with an error text

― Analog output: Factory setting: Failure current 3.6 or 22.8 mA

Or depending on the parameterization

― HART: detailed error breakdown for display in the HART communicator or SIMATIC PDM

• Grave hardware faults, the processor is not functioning.

Displays:

― Digital display: no defined display

― Analog output: failure current < 3.6 mA

Page 139: Transmitter AccuFLo-P DSIII series with HART-communication

In case of defect, you can replace the electronic unit by following the warning notes and the provided instruction manual.

See alsoSee alsoSee alsoSee also

Modular structure

Error display

10.310.310.310.3 Modular structureModular structureModular structureModular structure Safety noteSafety noteSafety noteSafety note

NoticeNoticeNoticeNotice The structure of this device is modular. You can thus replace different parts with original spare parts. When replacing components, always adhere to the notes provided with the components to be replaced. This is especially applicable for devices that are used in hazardous areas.

RelatedRelatedRelatedRelated Both the individual components "Measuring cell" and "Electronics" always have a non-volatile

memory (EEPROM). Every EEPROM has a data structure that is permanently allocated to the measuring cel, or the electronics. Measuring cell data (e.g.: measuring range, measuring cell material, oil filling) are stored in the EEPROM of the measuring cell. Data of the electronics (e.g.: downscaling, electrical additional damping) is located in the EEPROM of the electronics. It is thus ensured that the data that is relevant for the remaining components is

retained when replacing the electronic unit. Before starting the replacement work, you have the following setting options via HART:

• After replacement, the common measuring range settings from the measuring cell or from the electronic unit are adopted.

• A standard parameterization is carried out.

The measuring accuracy in the specified measuring limits with a 1:1 downscaling can be reduced by the temperature error in unfavorable cases.

In the course of further technical development, it is possible to implement advanced functions

Page 140: Transmitter AccuFLo-P DSIII series with HART-communication

in the measuring cell or the electronic unit. This is indicated by modified Firmware statuses (FW). The Firmware status does not have an effect on the replaceability. The scope of functions however is limited to the functioning of the older components.

If a combination of certain Firmware statuses of measuring cell and electronic unit is not possible due to technical reasons, the device identifies this status and goes into the "Fault

current" status. This information is provided via the HART interface.

10.410.410.410.4 Notes for servicing of the remote sealNotes for servicing of the remote sealNotes for servicing of the remote sealNotes for servicing of the remote seal

The remote seal measuring system usually does not need servicing. If the mediums are contaminated, viscous or crystallized, it could be necessary to clean the diaphragm from time to time. Use only a soft brush and a suitable solvent to remove the

deposits from the diaphragm. Do not use corrosive cleaning agents. Prevent the diaphragm from getting damaged due to sharp-edged tools.

Page 141: Transmitter AccuFLo-P DSIII series with HART-communication

11111111 Technical dataTechnical dataTechnical dataTechnical data

11.111.111.111.1 Overview of technical dataOverview of technical dataOverview of technical dataOverview of technical data IntroductionIntroductionIntroductionIntroduction

The following overview of technical data provides you with a quick and easy access to relevant data and characteristic numbers. Remember that the tables partially contain the data of the three communication types HART, PROFIBUS and FoundationFieldbus. This data deviates in many cases. Therefore, adhere to the communication type used by you when using the technical data.

Contents of the chapterContents of the chapterContents of the chapterContents of the chapter

• Input point

• Output

• Measuring accuracy

• Operating conditions

• Construction

• Display, keyboard and auxiliary power

• Certificates and approvals

• HART communication

11.211.211.211.2 Input pointInput pointInput pointInput point

DSDSDSDS III input with PMC connectionIII input with PMC connectionIII input with PMC connectionIII input with PMC connection

HARTHARTHARTHART Measured variable Gauge pressure

Page 142: Transmitter AccuFLo-P DSIII series with HART-communication

DSDSDSDS III input with PMC connectionIII input with PMC connectionIII input with PMC connectionIII input with PMC connection

HARTHARTHARTHART Measuring span (continuously adjustable) or measuring range, max permissible operating pressure and max. permissible test pressure

Measuring range

Maximum permissible operating pressure

Maximum permissible test pressure

0.01 … 1 bar g (0.15 … 14.5 psi g) 1)

4 bar g (58 psi g)

6 bar g (87 psi g)

0.04 … 4 bar g (0.58 … 58 psi g)

7 bar g (102 psi g)

10 bar g (145 psi g)

0.16 … 16 bar g (2.3 … 232 psi g)

21 bar g (305 psi g)

32 bar g (464 psi g)

Lower measuring limit

• Measuring cell with silicon oil filling

100 mbar a (1.45 psi a)

• Measuring cell with inert liquid

100 mbar a (1.45 psi a)

• Measuring cell with neobee

30 mbar a (0.44 psi a)

Upper measuring limit 100 % of the max. measuring range

1) 1 bar g (14.5 psi g) only in PMC-Style Standard, not in Minibolt

2) For PMC-Style Minibolt, the measuring span should not be less than 500 mbar

Gauge pressure inputGauge pressure inputGauge pressure inputGauge pressure input

HARTHARTHARTHART Measured variable Gauge pressure

Measuring span (continuously adjustable)

Measuring range

Maximum permissible

Maximum permissible

Page 143: Transmitter AccuFLo-P DSIII series with HART-communication

Gauge pressure inputGauge pressure inputGauge pressure inputGauge pressure input

HARTHARTHARTHART or measuring range, max permissible operating pressure (as per 2014/68/EU pressure device guideline) and max. permissible test pressure (as per DIN 16086) (for oxygen measurement max. 160 bar)

operating pressure

test pressure

0.01 … 1 bar g (0.15 … 14.5 psi g)

4 bar g (58 psi g)

6 bar g (87 psi g)

0.04 … 4 bar g (0.58 … 58 psi g)

7 bar g (102 psi g)

10 bar g (145 psi g)

0.16 … 16 bar g (2.3 … 232 psi g)

21 bar g (305 psi g)

32 bar g (464 psi g)

0.63 … 63 bar g (9.1 … 914 psi g)

67 bar g (972 psi g)

100 bar g (1450 psi g)

1.6 … 160 bar g (23 … 2321 psi g)

167 bar g (2422 psi g)

250 bar g (3626 psi g)

4 … 400 bar g (58 … 5802 psi g)

400 bar g (5802 psi g)

600 bar g (8702 psi g)

Lower measuring limit

• Measuring cell with silicon oil filling

30 mbar a (0.44 psi a)

• Measuring cell with inert liquid

30 mbar a (0.44 psi a)

Upper measuring limit 100 % of the max. measuring range (for oxygen measurement max. 160 bar g (2321 psi g))

Start of scale value between the measuring limits (continuously adjustable)

Page 144: Transmitter AccuFLo-P DSIII series with HART-communication

gauge pressure input, with flush mounted diaphragmgauge pressure input, with flush mounted diaphragmgauge pressure input, with flush mounted diaphragmgauge pressure input, with flush mounted diaphragm

HARTHARTHARTHART Measured variable Gauge pressure

Measuring span (continuously adjustable) or measuring range, max permissible operating pressure and max. permissible test pressure

Measuring range

Maximum permissible operating pressure

Maximum permissible test pressure

8 … 250 mbar g (0.12 … 3.6 psi g)

4 bar g (58 psi g)

6 bar g (87 psi g)

0.01 … 1 bar g (0.15 … 14.5 psi g)

4 bar g (58 psi g)

6 bar g (87 psi g)

0.04 … 4 bar g (0.58 … 58 psi g)

7 bar g (102 psi g)

10 bar g (145 psi g)

0.16 … 16 bar g (2.3 … 232 psi g)

21 bar g (305 psi g)

32 bar g (464 psi g)

0.6 … 63 bar g (9.1 … 914 psi g)

67 bar g (972 psi g)

100 bar g (1450 psi g)

Lower measuring limit

• Measuring cell with silicon oil filling

100 mbar a (1.45 psi a)

• Measuring cell with inert liquid

100 mbar a (1.45 psi a)

• Measuring cell with neobee

30 mbar a (0.44 psi a)

Upper measuring limit 100 % of the max. measuring range

Page 145: Transmitter AccuFLo-P DSIII series with HART-communication

Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)

HARTHARTHARTHART Measured variable Absolute pressure

Measuring span (continuously adjustable) or measuring range, max permissible operating pressure (as per 2014/68/EU pressure device guideline) and max. permissible test pressure (as per DIN 16086)

Measuring range

Maximum permissible operating pressure

Maximum permissible test pressure

8.3 … 250 mbar a (0.12 … 3.6 psi a)

1.5 bar a (21.8 psi a)

6 bar a (87 psi a)

43 … 1300 mbar a (0.62 … 18.9 psi a)

2.6 bar a (37.7 psi a)

10 bar a (145 psi a)

160 … 5000 bar a (2.32 … 72.5 psi a)

10 bar a (145 psi a)

30 bar a (435 psi a)

1 … 30 bar a (14.5 … 435 psi a)

45 bar a (653 psi a)

100 bar a (1450 psi a)

Lower measuring limit

• Measuring cell with silicon oil filling

0 mbar a (0 psi a)

• Measuring cell with inert liquid

0 mbar a (0 psi a)

for process temperature -20°C < ϑ ≤ 60°C (-4°F < ϑ ≤ +140°F)

30 mbar a (0.44 psi a)

for process temperature 60°C < ϑ

30 mbar a + 20 mbar a • (ϑ - 60°C)/°C

(0.44 psi a + 0.29 mbar a • (ϑ - 108°F)/°F)

Page 146: Transmitter AccuFLo-P DSIII series with HART-communication

Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)Absolute pressure input (from the gauge pressure series)

HARTHARTHARTHART ≤ 100°C (max. 85°C for measuring cell 30 bar) (140°F < ϑ ≤ 212°F (max. 185°F for measuring cell 435 psi))

Upper measuring limit 100 % of the max. measuring range (for oxygen measurement max. 160 bar g (2321 psi g))

Start of scale value between the measuring limits (continuously adjustable)

Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)

HARTHARTHARTHART Measured variable Absolute pressure

Measuring span (continuously adjustable) or measuring range and max permissible operating pressure (as per 2014/68/EU pressure device guideline)

Measuring range Overload limits 8.3 … 250 mbar a (0.12 … 3.6 psi a)

32 bar a (464 psi a)

43 … 1300 mbar a (0.62 … 18.9 psi a)

32 bar a (464 psi a)

160 … 5000 bar a (2.32 … 72.5 psi a)

32 bar a (464 psi a)

1 … 30 bar a (14.5 … 435 psi a)

160 bar a (2320 psi a)

5.3 … 100 bar a (76.9 … 1450 psi a)

160 bar a (2320 psi a) (for connection thread M10 and 7/16-20 UNF in the pressure caps)

Page 147: Transmitter AccuFLo-P DSIII series with HART-communication

Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)Absolute pressure input (from the differential pressure series)

HARTHARTHARTHART Lower measuring limit

• Measuring cell with silicon oil filling

0 mbar a (0 psi a)

• Measuring cell with inert liquid

for process temperature -20°C < ϑ ≤ 60°C (-4°F < ϑ ≤ +140°F)

30 mbar a (0.44 psi a)

for process temperature 60°C < ϑ ≤ 100°C (max. 85°C for measuring cell 30 bar) (140°F < ϑ ≤ 212°F (max. 185°F for measuring cell 435 psi))

30 mbar a + 20 mbar a • (ϑ - 60°C)/°C

(0.44 psi a + 0.29 mbar a • (ϑ - 108°F)/°F)

Upper measuring limit 100 % of the max. measuring range (for oxygen measurement max. 160 bar g (2321 psi g))

Start of scale value between the measuring limits (continuously adjustable)

Differential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate input

HARTHARTHARTHART Measured variable Differential pressure and flow rate Measuring span (continuously adjustable) or measuring range and max permissible operating

Measuring range Maximum permissible operating pressure

1 … 20 mbar (0.4015 … 8.031 inH2O)

32 bar (464 psi)

Page 148: Transmitter AccuFLo-P DSIII series with HART-communication

Differential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate input

HARTHARTHARTHART pressure (as per 2014/68/EU pressure device guideline)

1 … 60 mbar (0.4015 … 24.09 inH2O)

160 bar (2320 psi)

2.5 … 250 mbar (1.004 … 100.4 inH2O)

6 … 600 mbar (2.409 … 240.9 inH2

O)

16 … 1600 mbar (6.424 … 642.4 inH2O)

50 … 5000 mbar (20.08 … 2008 inH2O)

0.3 … 30 bar (4.35 … 435 psi)

2.5 … 250 mbar (1.004 … 100.4 inH2O)

420 bar (6091 psi)

6 … 600 mbar (2.409 … 240.9 inH2

O)

16 … 1600 mbar (6.424 … 642.4 inH2O)

50 … 5000 mbar (20.08 … 2008 inH2O)

0.3 … 30 bar (4.35 … 435 psi)

Page 149: Transmitter AccuFLo-P DSIII series with HART-communication

Differential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate inputDifferential pressure and flow rate input

HARTHARTHARTHART Lower measuring limit

• Measuring cell with silicon oil filling

-100% of the max. measuring range (-33% for measuring cell (435 psi)) or 30 mbar a (0.44 psi a)

• Measuring cell with inert liquid

for process temperature -20°C < ϑ ≤ 60°C (-4°F < ϑ ≤ +140°F)

-100% of the max. measuring range (-33% for measuring cell (435 psi)) or 30 mbar a (0.44 psi a)

for process temperature 60°C < ϑ ≤ 100°C (max. 85°C for measuring cell 30 bar) (140°F < ϑ ≤ 212°F (max. 185°F for measuring cell 435 psi))

• -100% of the max. measuring range (-33% for measuring cell (435 psi))

• 30 mbar a + 20 mbar a • (ϑ - 60°C)/°C

(0.44 psi a + 0.29 mbar a • (ϑ - 108°F)/°F)

Upper measuring limit 100 % of the max. measuring range (for oxygen measurement max. 160 bar g (2321 psi g))

Start of scale value between the measuring limits (continuously adjustable)

11.311.311.311.3 OutputOutputOutputOutput

OutputOutputOutputOutput

HARTHARTHARTHART Output signal 4 … 20 mA

• Lower limit (continuously adjustable)

3.55 mA, set to 3.84 mA in the factory

Page 150: Transmitter AccuFLo-P DSIII series with HART-communication

OutputOutputOutputOutput

HARTHARTHARTHART

• Upper limit (continuously adjustable)

2322.0

• Ripple (without HART communication)

ISS

settable time constants (T63) 0

set to 0.1

• Current transmitter

3.55

• Failure signal

3.55

Load Resistor R [

• Without HART communication

UH

• With HART communication

HART communicator R =230

SIMATIC PDM R =230

Characteristic curve

Bus physics –

Polarity-independent –

HARTHARTHARTHART 23 mA, set to 20.5 mA or optionally 22.0 mA in the factory

SS ≤ 0.5 % of the max. output current

0 … 100 s, in steps of 0.1 s

set to 0.1 s in the factory

3.55 … 23 mA

3.55 … 23 mA

Resistor R [Ω]

H Power supply in V

R =230 … 500 Ω

R =230 … 1100 Ω

Linearly increasing or linearly decreasing

Linear increase or decrease or square root extracting increasing (only for DSand flow rate)

Linear increase or decrease or square root extracting increasing (only for DS III

Page 151: Transmitter AccuFLo-P DSIII series with HART-communication

11.411.411.411.4 Measuring accuracyMeasuring accuracyMeasuring accuracyMeasuring accuracy

Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770----1) DS1) DS1) DS1) DS III with PMC connectionIII with PMC connectionIII with PMC connectionIII with PMC connection

HARTHARTHARTHART Reference conditions

• Rising characteristic curve

• Start of scale value 0 bar

• Seal diaphragm: stainless steel

• Measuring cell with silicon oil filling

• Room temperature 25°C (77°F)

• Measuring span ratio r

r = maximum measuring span or set measuring span

Measurement deviation with cut-off point setting, including hysteresis and repeatability.

Linear characteristic curve

• r ≤ 10

≤ (0.0029 • r + 0.071) %

• 10 < r ≤ 30

≤ (0.0045 • r + 0.071) %

• 30 < r ≤ 100 *)

≤ (0.005 • r + 0.05) %

Repeatability Included in the measuring deviation

Hysteresis Included in the measuring deviation

Settling time T63 without electrical damping

approx. 0.2 s

Long-term drift at ±30°C (±54°F) In 5 years

≤ (0.25 • r) %

Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g))

As percentage

Page 152: Transmitter AccuFLo-P DSIII series with HART-communication

Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770----1) DS1) DS1) DS1) DS III with PMC connectionIII with PMC connectionIII with PMC connectionIII with PMC connection

HARTHARTHARTHART

• at -10 … +60°C (14 … 140°F)

≤ (0.1 • r + 0.1) %

• at -40 … -10°C and

+60 … +85°C

(-40 … 14°F and 140 … 185°F)

≤ (0.1 • r + 0.15) % per 10 K

Process temperature influence In pressure per temperature change

• Temperature difference between process temperature and ambient

3 mbar per 10 K (0.04 psi per 10 K)

Influence of mounting position In pressure per change in angle

≤ 0.1 mbar g (0.00145 psi g) per 10° inclination

correction via zero offset

Power supply influence In percent per change in voltage

0.005 % per 1 V

Measuring value resolution –

*) not for 4 bar PMC Minibolt

Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770----1) gauge pressure1) gauge pressure1) gauge pressure1) gauge pressure

HARTHARTHARTHART Reference conditions

• Rising characteristic curve

• Start of scale value 0 bar

• Seal diaphragm: stainless steel

• Measuring cell with silicon oil filling

• Room temperature 25°C (77°F)

• Measuring span ratio r

r = maximum measuring span or set measuring span

Measurement deviation with cut-off point setting, including hysteresis and

Page 153: Transmitter AccuFLo-P DSIII series with HART-communication

Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770Measuring accuracy (as per EN 60770----1) gauge pressure1) gauge pressure1) gauge pressure1) gauge pressure

HARTHARTHARTHART repeatability.

Linear characteristic curve

• r ≤ 10

≤ (0.0029 • r + 0.071) %

• 10 < r ≤ 30

≤ (0.0045 • r + 0.071) %

• 30 < r ≤ 100

≤ (0.005 • r + 0.05) %

Repeatability Included in the measuring deviation

Hysteresis Included in the measuring deviation

Settling time T63 without electrical damping

approx. 0.2 s

Long-term drift at ±30°C (±54°F) In 5 years

≤ (0.25 • r) %

Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g))

As percentage

• at -10 … +60°C (14 … 140°F)

≤ (0.1 • r + 0.1) %

• at -40 … -10°C and

+60 … +85°C

(-40 … 14°F and 140 … 185°F)

≤ (0.1 • r + 0.15) % per 10 K

Influence of mounting position ≤ 0.05 mbar g (0.000725 psi g) per 10° inclination

correction via zero offset

Power supply influence In percent per change in voltage

0.005 % per 1 V

Measuring value resolution –

Page 154: Transmitter AccuFLo-P DSIII series with HART-communication

Gauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragm

HARTHARTHARTHART Reference conditions

• Rising characteristic curve

• Start of scale value 0 bar

• Seal diaphragm: stainless steel

• Measuring cell with silicon oil filling

• Room temperature 25°C (77°F)

• Measuring span ratio r

r = maximum measuring span or set measuring span

Measurement deviation with cut-off point setting, including hysteresis and repeatability.

Linear characteristic curve

• r ≤ 10

≤ (0.0029 • r + 0.071) %

• 10 < r ≤ 30

≤ (0.0045 • r + 0.071) %

• 30 < r ≤ 100

≤ (0.005 • r + 0.05) %

Settling time T63 without electrical damping

approx. 0.2 s

Long-term drift at ±30°C (±54°F) In 5 years

≤ (0.25 • r) %

Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g))

As percentage

• at -10 … +60°C (14 … 140°F)

≤ (0.1 • r + 0.2) %

• at -40 … -10°C and

+60 … +85°C

(-40 … 14°F and 140 … 185°F)

≤ (0.1 • r + 0.15) % per 10 K

Page 155: Transmitter AccuFLo-P DSIII series with HART-communication

Gauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragmGauge pressure measuring accuracy, with flush mounted diaphragm

HARTHARTHARTHART Process temperature influence In pressure per temperature change

• Temperature difference between process temperature and ambient temperature

3 mbar per 10 K (0.04 psi per 10 K)

Influence of mounting position In pressure per change in angle

0.4 mbar (0.006 psi) per 10° inclination

Correction via zero offset

Power supply influence In percent per change in voltage

0.005 % per 1 V

Measuring value resolution –

Absolute Absolute Absolute Absolute pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)

HARTHARTHARTHART Reference conditions

• Rising characteristic curve

• Start of scale value 0 bar

• Seal diaphragm: stainless steel

• Measuring cell with silicon oil filling

• Room temperature 25°C (77°F)

• Measuring span ratio r

r = maximum measuring span or set measuring span

Measurement deviation with cut-off point setting, including hysteresis and repeatability.

Linear characteristic curve

• r ≤ 10

≤ 0.1 %

• 10 < r ≤ 30

≤ 0.2 %

Page 156: Transmitter AccuFLo-P DSIII series with HART-communication

Absolute Absolute Absolute Absolute pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)pressure measuring accuracy (from gauge and differential pressure series)

HARTHARTHARTHART Settling time T63 without electrical damping

approx. 0.2 s

Long-term drift at ±30°C (±54°F) per year ≤ (0.1 • r) %

Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g))

As percentage

• at -10 … +60°C (14 … 140°F)

≤ (0.1 • r + 0.2) %

• at -40 … -10°C and

+60 … +85°C

(-40 … 14°F and 140 … 185°F)

≤ (0.1 • r + 0.15) % per 10 K

Influence of mounting position In pressure per change of angle

• for absolute pressure (from the gauge pressure series): 0.05 mbar (0.000725 psi) per 10

• for absolute pressure (from the differential pressure series): 0.7 mbar (0.001015 psi) per 10inclination

Correction via zero offset

Power supply influence In percent per change in voltage

0.005 % per 1 V

Measuring value resolution –

Differential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracy

HARTHARTHARTHART Reference conditions

• Rising characteristic curve

• Start of scale value 0 bar

• Seal diaphragm: stainless steel

• Measuring cell with silicon oil filling

• Room temperature 25°C (77°F)

Page 157: Transmitter AccuFLo-P DSIII series with HART-communication

Differential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracy

HARTHARTHARTHART

• Measuring span ratio r

r = maximum measuring span or set measuring span

Measurement deviation with cut-off point setting, including hysteresis and repeatability.

Linear characteristic curve

• r ≤ 10

≤ (0.0029 • r + 0.071) %

• 10 < r ≤ 30

≤ (0.0045 • r + 0.071) %

• 30 < r ≤ 100

≤ (0.005 • r + 0.05) %

Square root extracting characteristic curve (flow rate > 50%)

• r ≤ 10

≤ 0.1 %

• 10 < r ≤ 30

≤ 0.2 %

square root extracting characteristic curve (flow rate 25 … 50%)

• r ≤ 10

≤ 0.2 %

• 10 < r ≤ 30

≤ 0.4 %

Settling time T63 without electrical damping

• approx. 0.2 s

• approx 0.3 s for measuring cell 20 and 60 mbar (0.29 and 0.87 psi)

Long-term drift at ±30°C (±54°F) ≤ (0.25 • r) % per five years

static pressure max. 70 bar g (1015 psi g)

• Measuring cell 20 mbar (0.29 psi)

≤ (0.2 • r) % per year

Page 158: Transmitter AccuFLo-P DSIII series with HART-communication

Differential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracyDifferential pressure and flow rate measuring accuracy

HARTHARTHARTHART Effect of the ambient temperature (double values for measuring cell 20 mbar g (0.29 psi g))

As percentage

• At -10 … +60°C (14 … 140°F)

≤ (0.08 • r + 0.1) %

• At -40 … -10°C and

+60 … +85°C

(-40 … 14°F and 140 … 185°F)

≤ (0.1 • r + 0.15) % per 10 K

Effect of static pressure

• At the start of scale value

≤ (0.15 • r) % per 100 bar (1450 psi)

Measuring cell 20 mbar (0.29 psi) ≤ (0.15 • r) % per 32 bar (464 psi)

• On the measuring span

≤ 0.2 % per 100 bar (1450 psi)

Measuring cell 20 mbar (0.29 psi) ≤ 0.2 % per 32 bar (464 psi)

Influence of mounting position In pressure per change of angle

≤ 0.7 mbar (0.001015 psi) per 10° inclination

Correction via zero offset

Power supply influence In percent per change in voltage

0.005 % per 1 V

Measuring value resolution –

Page 159: Transmitter AccuFLo-P DSIII series with HART-communication

11.511.511.511.5 Operating conditionsOperating conditionsOperating conditionsOperating conditions

Rated conditions DSRated conditions DSRated conditions DSRated conditions DS III with PMC connectionIII with PMC connectionIII with PMC connectionIII with PMC connection Installation conditions Ambient temperature Note Observe the temperature class in hazardous areas.

• Measuring cell with silicon oil filling

-20 … +85°C (-4 … 185°F)

• Digital display

-30 … +85°C (-22 … 185°F)

• Storage temperature

-50 … +85°C (-58 … 185°F)

Climate class

• Condensation

permitted

Degree of protection (as per EN 60529)

IP65

Electromagnetic Compatibility

• Interference emission and interference

As per EN 61326 and NAMUR NE 21

Medium conditions

• Process temperature

-20 … +100°C (-4 … +212°F)

Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)

Installation conditions

• Installation instruction

Process connection vertically downward

Ambient conditions

• Ambient temperature

Note Observe the temperature class in hazardous areas.

Page 160: Transmitter AccuFLo-P DSIII series with HART-communication

Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)Rated conditions for gauge pressure and absolute pressure (from the gauge pressure series)

Measuring cell with silicon oil filling

--40 … +100°C (-40 … 212°F)

Measuring cell with inert liquid -20 … +100°C (-40 … 212°F)

Digital display -30 … +85°C (-22 … 185°F)

Storage temperature -50 … +85°C (-58 … 185°F)

• Climate class

Condensation Permitted

• Degree of protection (as per EN 60529)

IP65

• Electromagnetic Compatibility

Interference emission and interference immunity

As per EN 61326 and NAMUR NE 21

Medium conditions

• Process temperature

Measuring cell with silicon oil filling

-40 … +100°C (-40 … 212°F)

Measuring cell with inert liquid -20 … +100°C (-40 … 212°F)

in conjunction with dust explosion protection

-20 … +60°C (-4 … 140°F)

Gauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragm

Installation conditions Ambient temperature Note Observe the temperature class in hazardous areas.

• Measuring cell with silicon oil filling

-40 … +85°C (-40 … 185°F)

• Measuring cell with inert liquid

-40 … +85°C (-40 … 185°F)

Page 161: Transmitter AccuFLo-P DSIII series with HART-communication

Gauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragmGauge pressure rated conditions, with flush mounted diaphragm

• Measuring cell with neobee

-10 … +85°C (+14 … 185°F)

• Digital display

-30 … +85°C (-22 … 185°F)

• Storage temperature

-50 … +85°C (-58 … 185°F)

Climate class

• Condensation

permitted

Degree of protection

In accordance with EN 60 529

IP65, IP68

Electromagnetic Compatibility

• Interference emission and interference immunity

As per EN 61326 and NAMUR NE 21

Medium conditions

Process temperature

• Measuring cell with silicon oil filling

-40 … +150°C (-40 … 302°F)

-40 … +200°C (-40 … 392°F) with temperature decoupler

-10 … +250°C (+14 … 482°F) with temperature decoupler

• Measuring cell with inert liquid

-40 … +150°C (-40 … 302°F)

-40 … +200°C (-40 … 392°F) with temperature decoupler

• Measuring cell with neobee

-10 … +150°C (+14 … 302°F)

-40 … +200°C (-40 … 392°F) with temperature decoupler

Rated conditions for Rated conditions for Rated conditions for Rated conditions for absolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rate

Installation conditions

• Installation instruction

any

Ambient conditions

• Ambient temperature

Page 162: Transmitter AccuFLo-P DSIII series with HART-communication

Rated conditions for Rated conditions for Rated conditions for Rated conditions for absolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rateabsolute pressure (from the differential pressure series), differential pressure and flow rate

Note Observe the temperature class in hazardous areas.

Measuring cell with silicon oil filling

-40 … +100°C (-40 … 212°F)

• Measuring cell 30 bar (435 psi)

• -40 … +85°C (-40 … +185°F)

• for flow rate: -20 … +85°C (-4 … +185°F)

Measuring cell with neobee -20 … +100°C (-4 … 212°F)

Digital display -30 … +85°C (-22 … 185°F)

Storage temperature -50 … +85°C (-58 … 185°F)

• Climate class

Condensation Permitted

• Degree of protection (as per EN 60529)

IP65

• Electromagnetic Compatibility

Interference emission and interference immunity

As per EN 61326 and NAMUR NE 21

Medium conditions

• Process temperature

Measuring cell with silicon oil filling

-40 … +100°C (-40 … 212°F)

• Measuring cell 30 bar (435 psi)

• -40 … +85°C (-40 … +185°F)

• for flow rate: -20 … +85°C (-4 … +185°F)

Measuring cell with inert liquid -20 … +100°C (-40 … 212°F)

• Measuring cell 30 bar (435 psi)

• -40 … +85°C (-40 … +185°F)

• for flow rate: -20 … +85°C (-4 … +185°F)

In conjunction with dust explosion protection

-20 … +60°C (-4 … +140°F)

Page 163: Transmitter AccuFLo-P DSIII series with HART-communication

11.611.611.611.6 ConstructionConstructionConstructionConstruction

DSDSDSDS III construction with PMC connectionIII construction with PMC connectionIII construction with PMC connectionIII construction with PMC connection

Weight approx 1.5 kg (3.3 lb)

Material

• Wetted parts materials

Gasket (standard) PTFE flat gasket

O-ring (minibolt)

• FPM (Viton)

• FFPM or NBR (optional)

• Non-wetted parts materials

Electronics housing

• Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

• Lacquer on polyester base

• Type plate made of stainless steel

Mounting bracket Steel, zinc plated and yellow chrome plated or stainless steel

Measuring cell filling

• Silicone oil

• Neobee M20

• Inert liquid

Process connection

• Standard

• Flush mounted

• 11/2''

• PMC Standard design

• Minibolt

• Flush mounted

• 1''

• PMC Minibolt design

Electrical connection Cable inlet using the following screwed joints:

Page 164: Transmitter AccuFLo-P DSIII series with HART-communication

DSDSDSDS III construction with PMC connectionIII construction with PMC connectionIII construction with PMC connectionIII construction with PMC connection • Pg 13.5 (adapter)

• M20 x 1.5

• ½-14 NPT

• Han 7D/Han 8U plug connector

• M12 connector

Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the gauge pressure series)gauge pressure series)gauge pressure series)gauge pressure series)

Weight approx 1.5 kg (3.3 lb)

Material

• Wetted parts materials

Connection pins Stainless steel, mat. no. 1.4404/316L or Hastelloy C4, mat. no. 2.4610

Oval flange Stainless steel, mat. no. 1.4404/316L

Seal diaphragm Stainless steel, material no. 1.4404/316L or Hastelloy C276, material no. 2.4819

• Non-wetted parts materials

Electronics housing

• Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

• Lacquer on polyester base

• Type plate made of stainless steel

Mounting bracket Steel, zinc plated and yellow chrome plated or stainless steel

Measuring cell filling

• Silicone oil

• Neobee M20

• Inert liquid

(max. 160 bar g (2320 psi g) for oxygen measurement)

Process connection Connection pin G1/2A as per DIN EN 837-1; female thread 1/2-14 NPT or oval flange (PN 160 (MWP 2320 psi g)) with fastening screw thread M10 as per DIN 19213 or 7/16-20 UNF as per EN 61518

Electrical connection Screw terminals

Page 165: Transmitter AccuFLo-P DSIII series with HART-communication

Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the Construction for gauge pressure and absolute pressure (from the gauge pressure series)gauge pressure series)gauge pressure series)gauge pressure series)

Cable inlet using the following screwed joints:

• Pg 13.5 (adapter)

• M20 x 1.5

• ½-14 NPT or Han 7D/Han 8U plug connector

• M12 connector

Construction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragm Weight approx. 1.5 … 13.5 kg (3.3 … 30 lb)

Material

• Wetted parts materials

Process connection Stainless steel, mat. no. 1.4404/316L

Seal diaphragm Stainless steel, mat. no. 1.4404/316L

• Non-wetted parts materials

Electronics housing

• Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

• Lacquer on polyester base

• Type plate made of stainless steel

Mounting bracket Steel, zinc plated and yellow chrome plated or stainless steel

Measuring cell filling

• Silicone oil

• Neobee M20

• Inert liquid

Process connection

• Flanges as per EN and ASME

• F&B and pharma flange

• Bioconnect/Biocontrol

• PMC style

Electrical connection Cable inlet using the following screwed joints:

Page 166: Transmitter AccuFLo-P DSIII series with HART-communication

Construction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragmConstruction for gauge pressure, with flush mounted diaphragm • Pg 13.5 (adapter)

• M20x1.5

• ½-14 NPT

• Han 7D/Han 8U plug connector

• M12 connector

Construction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rate

Weight approx. 4.5 kg (9.9 lb)

Material

• Wetted parts materials

Seal diaphragm Stainless steel, mat. no. 1.4404/316L, Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold

Pressure caps and locking screw Stainless steel, mat. no. 1.4408 to PN 160, mat. no. 1.4571/316Ti for PN 420, Hastelloy C4, 2.4610 or Monel, mat. no. 2.4360

O-ring FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR

• Non-wetted parts materials

Electronics housing

• Non-copper aluminum die casting GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

• Lacquer on polyester base

• Type plate made of stainless steel

Pressure cap screws Steel, zinc plated and yellow chrome plated or stainless steel

Mounting bracket Steel, zinc plated and yellow chrome plated or stainless steel

Measuring cell filling

• Silicone oil

• Neobee M20

• Inert liquid

(max. 160 bar g (2320 psi g) for oxygen measurement)

Process connection Female thread 1/4-18 NPT and flat connection with fastening screw thread M10 as

Page 167: Transmitter AccuFLo-P DSIII series with HART-communication

Construction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rateConstruction for absolute pressure (from the gauge pressure series), differential pressure and flow rate per DIN 19213 (M12 for PN 420 (MWP 6092 psi)) or 7/16-20 UNF as per EN 61518

Electrical connection Screw terminals

Cable inlet using the following screwed joints:

• Pg 13.5 (adapter)

• M20 x 1.5

• ½-14 NPT or Han 7D/Han 8U plug connector

• M12 connector

11.711.711.711.7 Display, keyboard and auxiliary powerDisplay, keyboard and auxiliary powerDisplay, keyboard and auxiliary powerDisplay, keyboard and auxiliary power

Display and user interfaceDisplay and user interfaceDisplay and user interfaceDisplay and user interface

Keys 3 for on-site programming directly at the device Digital display

• Installed

• Cover with inspection window (optional)

Auxiliary power UAuxiliary power UAuxiliary power UAuxiliary power UHHHH

HARTHARTHARTHART Terminal voltage at transmitter

• DC 10.5 V … 45 V

• In the case of intrinsically safe operation 10.5

Ripple USS ≤ 0.2 V (47 … 125 Hz)

Noise Ueff ≤ 1.2 V (0.5 … 10 Hz)

Auxiliary power –

Separate supply voltage –

Bus voltage

• Not –

Page 168: Transmitter AccuFLo-P DSIII series with HART-communication

Auxiliary power UAuxiliary power UAuxiliary power UAuxiliary power UHHHH

HARTHARTHARTHART

• For intrinsically safe operation

Current consumption

• Max. basic current

• Starting current ≤ basic current

• Max. current in event of fault

Error shut-down electronics (FDE) present

11.811.811.811.8 Certificates and approvalsCertificates and approvalsCertificates and approvalsCertificates and approvals

Certificates and approvalsCertificates and approvalsCertificates and approvalsCertificates and approvals

HARTHARTHARTHART

Classification according to Pressure Equipment Directive (PED 2014/68/EU)

Water, waste water In preparation

Explosion protection

• Intrinsic safety "i"

PTB

Identifier

HARTHARTHARTHART

Certificates and approvalsCertificates and approvalsCertificates and approvalsCertificates and approvals

HARTHARTHARTHART

for gases of Fluid Group 1 and liquids of Fluid Group 1; meets requirements of Article 3 Para. 3 (good engineering practice)

only for flow rate:

for gases of Fluid Group 1 and liquids of Fluid Group 1; fulfills the basic safety requirements as per article 3, Para 1 (appendix 1); classified as category III, module H conformity evaluation by TNord

In preparation

PTB 99 ATEX 2122

for gases of Fluid Group 1 and liquids of Fluid Group 1; meets requirements of Article 3 Para. 3

Fluid Group 1; fulfills the basic safety requirements as per III, module H conformity evaluation by T

Page 169: Transmitter AccuFLo-P DSIII series with HART-communication

Certificates and approvalsCertificates and approvalsCertificates and approvalsCertificates and approvals

HARTHARTHARTHART II 1/2 G EEx ia/ib IIB/IIC T6

Permissible ambient temperature -40 … +85°C (-40 … +185°F) temperature class T4

-40 … +70°C (-40 … +158°F) temperature class T5

-40 … +60°C (-40 … +140°F) temperature class T6

Connection To a certified intrinsically safe circuit with the max. values:

Ui = 30 V, Ii = 100 mA,

Pi = 750 mW, Ri = 300 Ω

Effective inner capacitance: Ci = 6 nF

Effective inner inductance: Li = 0.4 mH

11.911.911.911.9 HART communicationHART communicationHART communicationHART communication

HART communicationHART communicationHART communicationHART communication

Load for a

• HART communicator connection

230 … 1100 Ω

• HART modem

230 … 500 Ω

Cable 2-wire, shielded: ≤ 3.0 km (1.86 miles), multi-wired, shielded: ≤ 1.5 km (0.93 miles)

Protocol HART Version 5.x

PC/laptop requirements IBM-compatible, user memory > 32 MB, hard disk > 70 MB, depending on the type of modem: RS 232 interface or USB connection, VGA graphic

Software for computer SIMATIC PDM

Page 170: Transmitter AccuFLo-P DSIII series with HART-communication

12121212 Dimension drawingsDimension drawingsDimension drawingsDimension drawings

12.112.112.112.1 AccuFloAccuFloAccuFloAccuFlo P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure

from the gauge pressure seriesfrom the gauge pressure seriesfrom the gauge pressure seriesfrom the gauge pressure series

Figure12-1 Pressure transmitter pressure series, dimensions in mm (inch)

① Electronic side,

② Process connection:

• 1/2-14 NPT,

• Connection pin G

• Oval flange

③ Connection side

④ Electrical connection:

• Screwed point Pg

• Screwed point

• Screwed point

• Han 7D/Han

Dimension drawingsDimension drawingsDimension drawingsDimension drawings

P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure from the gauge pressure seriesfrom the gauge pressure seriesfrom the gauge pressure seriesfrom the gauge pressure series

Pressure transmitter AccuFlo P, DS III HART series for absolute pressure, from gauge pressure series, dimensions in mm (inch)

Electronic side, digital display (greater design length for cover with inspection window)

Process connection: NPT,

Connection pin G1/2A or

Oval flange

Connection side

Electrical connection:

Screwed point Pg 13,5 (adapter)2)3),

Screwed point M20 x 1,53),

Screwed point 1/2-14 NPT

7D/Han 8U2)3) plug connector

P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure P, DS III series for gauge pressure and absolute pressure

P, DS III HART series for absolute pressure, from gauge

digital display (greater design length for cover with inspection window)

Page 171: Transmitter AccuFLo-P DSIII series with HART-communication

• M12 connector

⑤ Protective cap of the operating buttons

⑥ Blanking plug

⑦ Screw cover - drawing)

⑧ Mounting bracket (optional)

1) Take additional 20 mm (0.79 inch) thread length into account

2) Not with "Explosion

3) Not for "FM +

4) For Pg 13,5 with adapter approx 45

5) Minimum distance when rotating

12.212.212.212.2 AccuFloAccuFloAccuFloAccuFlo P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute

pressure from the differential pressure seriespressure from the differential pressure seriespressure from the differential pressure seriespressure from the differential pressure series

Figure12-2 Pressure transmitter rate, dimensions in mm (inch)

M12 connector

Protective cap of the operating buttons

lock bracket (only for "explosion-proof" type of protection, not shown in the

Mounting bracket (optional)

Take additional 20 mm (0.79 inch) thread length into account

Not with "Explosion-proof" type of protection

CSA [is + XP]" type of protection

13,5 with adapter approx 45 mm (1.77 inch)

Minimum distance when rotating

P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute pressure from the differential pressure seriespressure from the differential pressure seriespressure from the differential pressure seriespressure from the differential pressure series

Pressure transmitter AccuFlo P, DS III HART series for differential pressure and flow rate, dimensions in mm (inch)

proof" type of protection, not shown in the

P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute P, DS III series for differential pressure, flow rate and absolute

P, DS III HART series for differential pressure and flow

Page 172: Transmitter AccuFLo-P DSIII series with HART-communication

① Electronic side, digital display (greater design length for cover with inspection window) ② Connection side ③ Electrical connection:

• Screwed point Pg 13,5 (adapter)2)3),

• Screwed point M20 x 1,53),

• Screwed point 1/2-14 NPT

• Han 7D/Han 8U2)3) plug connector

• M12 connector

④ Protective cap of the operating buttons

⑤ Blanking plug

⑥ Screw cover - lock bracket (only for "explosion-proof" type of protection, not shown in the drawing)

⑦ Mounting bracket (optional)

⑧ Electrical connection:

• Screwed point Pg 13,5 (adapter)2)3),

• Screwed point M20 x 1,53),

• Screwed point 1/2-14 NPT or

• Han 7D/Han 8U2)3) plug connector

⑨ Lateral ventilation for gas measurement (addition H02)

⑩ Sealing plug, with valve (optional)

⑪ Lateral ventilation for liquid measurement

⑫ Process connection: 1/4-18 NPT (EN 61518)

1) Take additional 20 mm (0.79 inch) thread length into account

2) Not with "Explosion-proof" type of protection

3) Not for "FM + CSA [is + XP]" type of protection

4) 92 mm (3.62 inch) minimum distance for rotating the pointer

5) For Pg 13,5 with adapter approx 45 mm (1.77 inch)

Page 173: Transmitter AccuFLo-P DSIII series with HART-communication

Figure12-3 Pressure transmitter rate with caps for vertical differential pressure lines, dimensions in mm (inch)

① Electronic side, digital display (greater design length for cover with inspection window)

② Connection side

③ Electrical connection:

• Screwed point Pg

• Screwed point M20

• Screwed point

• Han 7D/Han

④ Protective cap of the operating buttons

⑤ Blanking plug

⑥ Screw cover - drawing)

⑦ Sealing plug, with valve (optional)

⑧ Process connection:

1) Take additional 20 mm (0.79 inch) thread length into account

2) Not with "Explosion

3) Not for "FM +

Pressure transmitter AccuFlo P, DS III HART series for differential pressure and flow rate with caps for vertical differential pressure lines, dimensions in mm (inch)

Electronic side, digital display (greater design length for cover with inspection window)

Connection side Electrical connection:

Screwed point Pg 13,5 (adapter)2)3),

Screwed point M20 x 1,53),

Screwed point 1/2-14 NPT or

7D/Han 8U2)3) plug connector

Protective cap of the operating buttons

lock bracket (only for "explosion-proof" type of protection, not shown in the

Sealing plug, with valve (optional)

Process connection: 1/4-18 NPT (EN 61518)

Take additional 20 mm (0.79 inch) thread length into account

Not with "Explosion-proof" type of protection

CSA [is + XP]" type of protection

P, DS III HART series for differential pressure and flow rate with caps for vertical differential pressure lines, dimensions in mm (inch)

Electronic side, digital display (greater design length for cover with inspection window)

proof" type of protection, not shown in the

Page 174: Transmitter AccuFLo-P DSIII series with HART-communication

4) 92 mm (3.62 inch) minimum distance for rotating the pointer

5) 74 mm (2.9 inch) for PN

6) 91 mm (3.6 inch) for PN

7) 219 mm (8.62

8) For Pg 13,5 with adapter approx 45

12.412.412.412.4 AccuFloAccuFloAccuFloAccuFlo P, DS III seriesP, DS III seriesP, DS III seriesP, DS III series

12.4.112.4.112.4.112.4.1 AccuFloAccuFloAccuFloAccuFlo P, DS III seriesP, DS III seriesP, DS III seriesP, DS III series

Figure12-5 AccuFlo

① Electronics side, "digital display" option

② Connection side, "analog display" option

③ Cable gland

1) Take additional 20 mm (approx.) thread length into account

4) Minimum distance for turning without display and [

inch) minimum distance for rotating the pointer

inch) for PN ≥ 420 (MWP ≥ 6092 psi)

91 mm (3.6 inch) for PN ≥ 420 (MWP ≥ 6092 psi)

inch) for PN ≥ 420 (MWP ≥ 6092 psi)

13,5 with adapter approx 45 mm (1.77 inch)

P, DS III seriesP, DS III seriesP, DS III seriesP, DS III series P, DS III seriesP, DS III seriesP, DS III seriesP, DS III series

AccuFlo P DS III (flush mounted)

Electronics side, "digital display" option ④ Protective caps for buttons Connection side, "analog display" option ⑤ Blanking plug

⑥ Screw cover - lock bracket, only for flameproof encapsulation, not shown in the dimension drawings

⑦ Process connection

(approx.) thread length into account Minimum distance for turning without display and [ ] with display

lock bracket, only for flameproof encapsulation, not shown in the dimension drawings

Page 175: Transmitter AccuFLo-P DSIII series with HART-communication

The screen consists of a AccuFlo P DS III with an example flange. On this screen, the height is divided into H1 and H2. H1 Height of the device up to a defined cut H2 Height of the flange up to this defined cut

In the flange dimensions, only the height H2 is specified.

12.4.212.4.212.4.212.4.2 Note 3A and EHDGNote 3A and EHDGNote 3A and EHDGNote 3A and EHDG

NoteNoteNoteNote

The AccuFlo P, DS III series is approved by "EHEDG". The AccuFlo P300 is approved by "EHEDG" and "3A" for example.

The same flanges and flush mounted connections are used for both the pressure

transmitters. The connections for both the abovementioned approvals are thus specified.

Since the AccuFlo P, DS III series transmitter is not approved by "3A", the connections marked with "3A" are not applicable for the AccuFlo P, DS III series.

12.4.312.4.312.4.312.4.3

Connections as per EN and ASMEConnections as per EN and ASMEConnections as per EN and ASMEConnections as per EN and ASME Flange as per ENFlange as per ENFlange as per ENFlange as per EN

EN 1092EN 1092EN 1092EN 1092----1111

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

Page 176: Transmitter AccuFLo-P DSIII series with HART-communication

EN 1092EN 1092EN 1092EN 1092----1111

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 40 115 mm (4.5'')

Approx. 52 mm (2'')

25 100 140 mm (5.5'')

40 40 150 mm (5.9'')

40 100 170 mm (6.7'')

50 16 165 mm (6.5'')

50 40 165 mm (6.5'')

80 16 200 mm (7.9'')

80 40 200 mm (7.9'')

Threaded connectionsThreaded connectionsThreaded connectionsThreaded connections G2" as per DIN 3852G2" as per DIN 3852G2" as per DIN 3852G2" as per DIN 3852

Page 177: Transmitter AccuFLo-P DSIII series with HART-communication

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

2'' 63 78 mm (3.1'')

Approx. 52 mm (2'')

Flanges as per ASMEFlanges as per ASMEFlanges as per ASMEFlanges as per ASME ASME B 16.5ASME B 16.5ASME B 16.5ASME B 16.5

DNDNDNDN CLASSCLASSCLASSCLASS ⊘⊘⊘⊘DDDD HHHH2222

1'' 150 110 mm (4.3'')

Approx. 52 mm (2'')

1'' 300 125 mm (4.9'')

1 1/2'' 150 130 mm (5.1'')

1 1/2'' 300 155 mm (6.1'')

2'' 150 150 mm

Page 178: Transmitter AccuFLo-P DSIII series with HART-communication

ASME B 16.5ASME B 16.5ASME B 16.5ASME B 16.5

DNDNDNDN CLASSCLASSCLASSCLASS ⊘⊘⊘⊘DDDD HHHH2222

(5.9'') 2'' 300 165 mm

(6.5'')

3'' 150 190 mm (7.5'')

3'' 300 210 mm (8.1'')

4'' 150 230 mm (9.1'')

4'' 300 255 mm (10.0'')

12.4.412.4.412.4.412.4.4 F&B and pharma flangeF&B and pharma flangeF&B and pharma flangeF&B and pharma flange

Connections as per DINConnections as per DINConnections as per DINConnections as per DIN DIN 11851DIN 11851DIN 11851DIN 11851

Page 179: Transmitter AccuFLo-P DSIII series with HART-communication

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 40 63 mm (2.5'')

Approx. 52 mm (2'')

32 40 70 mm (2.8'')

40 40 78 mm (3.1'')

50 25 92 mm (3.6'')

80 25 127 mm (5'')

Approvals 3A1) 1) If the transmitter is approved by 3A, use only 3A-approved sealing rings. DIN 11864DIN 11864DIN 11864DIN 11864----1111

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 40 52 mm (2'') Approx. 52 mm (2'') 40 40 65 mm

(2.6'')

Page 180: Transmitter AccuFLo-P DSIII series with HART-communication

DIN 11864DIN 11864DIN 11864DIN 11864----1111

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

50 40 78 mm (3.1'')

100 40 130 mm (5.1'')

Approvals 3A, EHEDG DIN 11864DIN 11864DIN 11864DIN 11864----2222

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 40 70 mm (2.8'')

Approx. 52 mm (2'')

40 40 82 mm (3.2'')

50 40 94 mm (3.7'')

100 40 159 mm (6.3'')

Approvals 3A, EHEDG

Page 181: Transmitter AccuFLo-P DSIII series with HART-communication

DIN 11864DIN 11864DIN 11864DIN 11864----3333

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 40 50.5 mm (2'')

Approx. 52 mm (2'')

40 40 64 mm (2.5'')

50 40 77.5 mm (3.1'')

100 40 130 mm (5.1'')

Approvals 3A, EHEDG TriTriTriTri----Clamp as per DINClamp as per DINClamp as per DINClamp as per DIN 32676326763267632676

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

20 16 34 mm (1.3'')

Approx. 52 mm (2'')

Page 182: Transmitter AccuFLo-P DSIII series with HART-communication

TriTriTriTri----Clamp as per DINClamp as per DINClamp as per DINClamp as per DIN 32676326763267632676

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 16 50.5 mm (2'')

32 16 50.5 mm (2'')

40 16 50.5 mm (2'')

50 16 64 mm (2.5'')

65 10 91 mm (3.6'')

80 10 106 mm (4.2'')

100 40 119 mm (4.7'')

Approvals 3A

Other connectionsOther connectionsOther connectionsOther connections VariventVariventVariventVarivent® connectorconnectorconnectorconnector

Page 183: Transmitter AccuFLo-P DSIII series with HART-communication

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25-32 40 66 mm (2.6'')

Approx. 52 mm (2'')

40-125 40 84 mm (3.3'')

Approvals 3A, EHEDG

12.4.512.4.512.4.512.4.5 Bioconnect/BiocontrolBioconnect/BiocontrolBioconnect/BiocontrolBioconnect/Biocontrol

BioconnectBioconnectBioconnectBioconnectTMTMTMTM connectorconnectorconnectorconnector BioconnectBioconnectBioconnectBioconnectTMTMTMTM screwed jointscrewed jointscrewed jointscrewed joint

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 16 55 mm (2.2'') Approx. 52 mm (2'') 50 16 82 mm (3.2'') 100 16 145 mm

(5.7'')

Approvals 3A, EHEDG BioconnectBioconnectBioconnectBioconnectTMTMTMTM flange connectorflange connectorflange connectorflange connector

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

Page 184: Transmitter AccuFLo-P DSIII series with HART-communication

25 16 85 mm (3.3'') Approx. 52 mm (2'') 50 16 110 mm

(4.3'')

100 16 175 mm (6.9'')

Approvals 3A, EHEDG BioconnectBioconnectBioconnectBioconnectTMTMTMTM clamp connectorclamp connectorclamp connectorclamp connector

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 16 50.4 mm (1.9'')

Approx. 52 mm (2'')

40 16 64 mm (2.5'') 50 16 77.4 mm (3'') 65 10 90.9 mm

(3.6'')

80 10 106 mm (4.2'')

100 10 119 mm (4.7'')

Approvals 3A, EHEDG

Page 185: Transmitter AccuFLo-P DSIII series with HART-communication

Other connectionsOther connectionsOther connectionsOther connections BiocontrolBiocontrolBiocontrolBiocontrolTMTMTMTM connectorconnectorconnectorconnector

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

50 16 90 mm (3.5'') Approx. 52 mm (2'') 65 16 120 mm

(4.7'')

80 16 140 mm (5.5'')

Approvals 3A, EHEDG ConnectConnectConnectConnect SSSSTMTMTMTM flanged jointflanged jointflanged jointflanged joint

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

25 16 97 mm (3.8'') Approx. 52 mm (2'') 32 16 105 mm

(4.1'')

40 16 115 mm (4.5'')

Page 186: Transmitter AccuFLo-P DSIII series with HART-communication

ConnectConnectConnectConnect SSSSTMTMTMTM flanged jointflanged jointflanged jointflanged joint

50

65

80

100

Approvals

12.4.612.4.612.4.612.4.6 PMC StylePMC StylePMC StylePMC Style

Connections for the paper industryConnections for the paper industryConnections for the paper industryConnections for the paper industry PMC Style StandardPMC Style StandardPMC Style StandardPMC Style Standard

flanged jointflanged jointflanged jointflanged joint

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH

16 125 mm

(4.9'')

10 145 mm (5.7'')

10 155 mm (6.1'')

10 180 mm (7.1'')

3A, EHEDG

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH

– 40.4 mm (1.6'')

Approx. 52 mm (2'')

HHHH2222

HHHH2222

Page 187: Transmitter AccuFLo-P DSIII series with HART-communication

PMC Style StandardPMC Style StandardPMC Style StandardPMC Style Standard

M44x1.25 cap nut

PMCPMCPMCPMC----Style MiniboltStyle MiniboltStyle MiniboltStyle Minibolt

12.4.712.4.712.4.712.4.7 Special connectionsSpecial connectionsSpecial connectionsSpecial connections

Tank connectionTank connectionTank connectionTank connection TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150

TG52/50

25

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH

– 26.3 mm (1'')

Approx. 52 mm (2'')

TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH

40 63 mm

(2.5'') Approx. 63 mm (2.5'')

HHHH2222

HHHH2222

HHHH2222

Page 188: Transmitter AccuFLo-P DSIII series with HART-communication

TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150TG52/50 and TG52/150

DNDNDNDN PNPNPNPN ⊘⊘⊘⊘DDDD HHHH2222

TG52/150 25 40 63 mm

(2.5'') Approx. 170 mm (6.7'')

Page 189: Transmitter AccuFLo-P DSIII series with HART-communication

13131313 Spare parts/accessoriesSpare parts/accessoriesSpare parts/accessoriesSpare parts/accessories

13.113.113.113.1 Order dataOrder dataOrder dataOrder data

In order to ensure that the ordering data you are using is not outdated, the latest ordering data is always available on the Internet:

13.213.213.213.2 Spare parts/accessories for DS III and P300Spare parts/accessories for DS III and P300Spare parts/accessories for DS III and P300Spare parts/accessories for DS III and P300 Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no. CDCDCDCD " AccuFlo p - pressure transmitters" with documentation in German/English/French/Spanish/Italian, etc.

A5E00090345

HART modemHART modemHART modemHART modem

• With serial interface RS232

ACCU997-1DA1) D)

• With USB interface

ACCU997-1DB1) D)

WeldWeldWeldWeld----in support for PMC connectionin support for PMC connectionin support for PMC connectionin support for PMC connection

For DS III and P300 series

• PMC Style Standard: Thread 1½"

ACCU997-2HA

• PMC-Style Minibolt: flush mounted 1"

ACCU997-2HB

Gaskets for PMC connectionGaskets for PMC connectionGaskets for PMC connectionGaskets for PMC connection, (1 set = 5 pieces)

• PTFE gasket for PMC Style Standard: Thread 1½"

ACCU997-2HC

• Viton gasket for PMC Style Minibolt: flush mounted 1"

ACCU997-2HD

WeldWeldWeldWeld----in adapter for PMC connectionin adapter for PMC connectionin adapter for PMC connectionin adapter for PMC connection

Page 190: Transmitter AccuFLo-P DSIII series with HART-communication

Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no.

For connection of weld-in support delay during welding for:

• PMC Style Standard: Thread 1½"

ACCU997-2HE

• PMC-Style Minibolt: flush mounted 1"

ACCU997-2HF

13.313.313.313.3 Spare parts/accessories for DS IIISpare parts/accessories for DS IIISpare parts/accessories for DS IIISpare parts/accessories for DS III

Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no. Mounting Mounting Mounting Mounting bracket and fastening partsbracket and fastening partsbracket and fastening partsbracket and fastening parts For DS III, DS III PA and DS III FF series For gauge pressure transmitter (ACCU03.-.....-..C.) For transmitter for absolute pressure (ACCU23.-.....-..C.)

• Made of steel

ACCU997-1AB

• Made of stainless steel

ACCU997-1AH

Mounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening parts

For DS III, DS III PA and DS III FF series

For gauge pressure transmitter (ACCU03.-.....-..A., -..B. and -..D.)

For transmitter for absolute pressure (ACCU23.-.....-..A., -..B. and -..D.)

• Made of steel

ACCU997-1AC

• Made of stainless steel

ACCU997-1AJ

Mounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening parts

For DS III, DS III PA and DS III FF series

Page 191: Transmitter AccuFLo-P DSIII series with HART-communication

Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no.

Differential pressure transmitter with flange thread

• Made of steel

For thread M10 (ACCU33.-... and ACCU43.-...) ACCU997-1AD

For thread M12 (ACCU53.-...) ACCU997-1AE

• Made of stainless steel

For thread M10 (ACCU33.-... and ACCU43.-...) ACCU997-1AK

For thread M12 (ACCU53.-...) ACCU997-1AL

Mounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening partsMounting bracket and fastening parts

For DS III, DS III PA and DS III FF series

Differential and absolute transmitter with

flange thread 7/16-20 UNF

(ACCU33.-..., ACCU43.-... and ACCU53.-...)

• Made of steel

ACCU997-1AF

• Made of stainless steel

ACCU997-1AM

CoverCoverCoverCover

For DS III, DS III PA and DS III FF series

• Made of aluminum die casting, including gasket

Without inspection window ACCU997-1BB

With inspection window ACCU997-1BE

• Made of stainless steel, including gasket

Without inspection window ACCU997-1BC

With inspection window ACCU997-1BF

Analog displayAnalog displayAnalog displayAnalog display

Page 192: Transmitter AccuFLo-P DSIII series with HART-communication

Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no.

• Scale 0 ... 100%

ACCU997-1BN

• Customer-specific scale division as per the plain text specifications

ACCU997-1BP-Z

Y20: ................

Digital displayDigital displayDigital displayDigital display

For DS III, DS III PA and DS III FF series

Including the fastening material ACCU997-1BR

Measuring point labelMeasuring point labelMeasuring point labelMeasuring point label

• not labelled (five pieces)

ACCU997-1CA

• labelled (one piece)

Specifications as per Y01 or Y02, Y15 and Y16

(refer to AccuFlo P transmitter)

ACCU997-1CB-Z

Y..: ................

Fastening screwsFastening screwsFastening screwsFastening screws, 50 pieces for:

• Measuring point label

• Earthing and connecting terminals

• Digital display

ACCU997-1CD

Locking screwsLocking screwsLocking screwsLocking screws, (1 set = 2 pieces) for pressure cap

• Made of stainless steel

ACCU997-1CG

• Made of Hastelloy

ACCU997-1CH

Vent valvesVent valvesVent valvesVent valves, complete (1 set = 2 pieces)

• Made of stainless steel

ACCU997-1CP

• Made of Hastelloy

ACCU997-1CQ

ElectronicElectronicElectronicElectronic

• For DS III series

ACCU997-1DK

Page 193: Transmitter AccuFLo-P DSIII series with HART-communication

Selection and order dataSelection and order dataSelection and order dataSelection and order data Order no.Order no.Order no.Order no.

• For DS III PA series

ACCU997-1DL

• For DS III FF series

ACCU997-1DM

Network cardNetwork cardNetwork cardNetwork card

• For DS III series

ACCU997-1DN

• For DS III PA and DS III FF series

ACCU997-1DP

Sealing rings for pressure caps offSealing rings for pressure caps offSealing rings for pressure caps offSealing rings for pressure caps off

• FPM (Viton)

ACCU997-2DA

• PTFE (Teflon)

ACCU997-2DB

• FEP (with silicon core, suitable for food)

ACCU997-2DC

• FFPM (Kalrez, Compound 4079)

ACCU997-2DD

• NBR (Buna N)

ACCU997-2DE

1) Available from stock D) Subject to export regulations AL: N, ECCN, EAR99H

Page 194: Transmitter AccuFLo-P DSIII series with HART-communication

14141414

AppendixAppendixAppendixAppendix

14.514.514.514.5 Overview of HART operating structureOverview of HART operating structureOverview of HART operating structureOverview of HART operating structure

The following overview applies to the HART communicator operating structure.

Overview of HART operating structureOverview of HART operating structureOverview of HART operating structureOverview of HART operating structure The following overview applies to the HART communicator operating structure. The following overview applies to the HART communicator operating structure.

Page 195: Transmitter AccuFLo-P DSIII series with HART-communication
Page 196: Transmitter AccuFLo-P DSIII series with HART-communication

14.614.614.614.6 Pressure equipment directivePressure equipment directivePressure equipment directivePressure equipment directive

The monitoring of the design, dimensioning, testing and manufacture to ensure it is in

accordance with Module H (comprehensive quality appointed body.

Pressure equipment directivePressure equipment directivePressure equipment directivePressure equipment directive The monitoring of the design, dimensioning, testing and manufacture to ensure it is in

accordance with Module H (comprehensive quality assurance) by TÜV North as the

The monitoring of the design, dimensioning, testing and manufacture to ensure it is in

V North as the

Page 197: Transmitter AccuFLo-P DSIII series with HART-communication

Figure14-1 Pressure equipment directive, sheet 1Pressure equipment directive, sheet 1

Page 198: Transmitter AccuFLo-P DSIII series with HART-communication

Figure14-2 Pressure equipment directive, sheet 2Pressure equipment directive, sheet 2

Page 199: Transmitter AccuFLo-P DSIII series with HART-communication

Figure14-3 Pressure equipment directive, sheet 3Pressure equipment directive, sheet 3

Page 200: Transmitter AccuFLo-P DSIII series with HART-communication

15151515 List of abbreviationsList of abbreviationsList of abbreviationsList of abbreviations

15.115.115.115.1 Pressure transmitter abbreviationsPressure transmitter abbreviationsPressure transmitter abbreviationsPressure transmitter abbreviations List of abbreviationsList of abbreviationsList of abbreviationsList of abbreviations Table15-1Variables

AbbreviationAbbreviationAbbreviationAbbreviation In fullIn fullIn fullIn full MeaningMeaningMeaningMeaning

PV Primary variable

SV Secondary variable

TV Tertiary variable

QV Quarternary variable

Table15-2Units

AbbreviationAbbreviationAbbreviationAbbreviation In fullIn fullIn fullIn full MeaningMeaningMeaningMeaning

bar a bar absolute Unit of pressure for absolute pressure

bar g bar gauge Unit of pressure for gauge pressure

lb Pfund (engl.: Pound) Unit of weight

psi a psi absolute Unit of pressure for absolute pressure

psi g psi gauge Unit of pressure for gauge pressure

Table15-3Other abbreviations

AbbreviationAbbreviationAbbreviationAbbreviation In fullIn fullIn fullIn full MeaningMeaningMeaningMeaning

PED Pressure equipment directive

HART Highway Addressable Remote Transducer

Standard protocol for the transmission of information between field device and automation system

Page 201: Transmitter AccuFLo-P DSIII series with HART-communication

AbbreviationAbbreviationAbbreviationAbbreviation In fullIn fullIn fullIn full MeaningMeaningMeaningMeaning

MA Start of scale value

ME Full scale value

NFPA National Fire Protection Association

F&B Food and beverage industry

PDM Engl.: Process Device Manager

15.215.215.215.2 Functional safetyFunctional safetyFunctional safetyFunctional safety

AbbreviationAbbreviationAbbreviationAbbreviation Full term in EnglishFull term in EnglishFull term in EnglishFull term in English MeaningMeaningMeaningMeaning

FIT Failure in Time Frequency of failure Number of faults withing 109 hours

HFT Hardware Fault Tolerance Hardware fault tolerance: Capability of a function unit to continue executing a required function in the presence of faults or deviations.

MooN "M out of N" voting Classification and description of the safety-instrumented system in terms of redundancy and the selection procedures used. A safety-instrumented system or part that consists of "N" independent channels. The channels are connected to each other in such a way that "M" channels are in each case sufficient for the device to perform the safety instrumented function. Example: Pressure measurement: 1oo2 architecture. A safety-instrumented system decides that a specified pressure limit has been exceeded if one out of two pressure sensors reaches this limit. In a 1oo1 architecture, there is only one pressure sensor.

MTBF Mean Time Between Failures Average period between two failures

Page 202: Transmitter AccuFLo-P DSIII series with HART-communication

AbbreviationAbbreviationAbbreviationAbbreviation Full term in EnglishFull term in EnglishFull term in EnglishFull term in English MeaningMeaningMeaningMeaning

MTTR Mean Time To Restoration Average period between the occurrence of a fault in a device or system and restoration of functionality

PFD Probability of Failure on Demand Probability of dangerous failures of a safety function on demand

PFDAVG Average Probability of Failure on Demand

Average probability of dangerous failures of a safety function on demand

SFF Safe Failure Fraction Proportion of safe failures: Proportion of failures without the potential to bring the safety-instrumented system into a dangerous or non-permissible functional status.

SIL Safety Integrity Level The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL 1 to SIL 4). Each level corresponds to a range of probability for failure of a safety function. The higher the Safety Integrity Level of the safety-instrumented system, the lower the probability that it will not execute the required safety functions.

SIS Safety Instrumented System A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic unit/control system and final controlling element.

TI Test Interval Testing interval of the protective function

Page 203: Transmitter AccuFLo-P DSIII series with HART-communication

S.K.I. Schlegel & Kremer Industrieautomation GmbH

Postfach 41 01 31 D 41241 Mönchengladbach

Hanns-Martin-Schleyer-Str. 22 D 41199 Mönchengladbach

Phone: ++49 (0)2166-62317-0

Fax: ++49 (0)2166-611681 Web: www.ski-gmbh.com e-mail: [email protected]

Trademarks and logos are the property of their owners

Subject to technical changes. Illustrations may contain options