Transformers & EM Conversion.pdf

Embed Size (px)

Citation preview

  • 1

    LECTURE NOTES FOR

    EE 162

    ELECTROMECHANICAL ENERGY

    CONVERSION & TRANSFORMERS

    COURSE LECTURER: DR. PHILIP YAW OKYERE

  • 2

    Course Outline

    EE 162 ELECTRICAL MACHINES I (3 0 3)

    Principles of Electromechanical Energy Conversion:

    Force and torque as rate of change of energy with position. Basic Transducers: Single

    Excitation, Alignment Force and Torque; Double Excitation, Alignment and Interaction

    Forces and torque

    Transformers:

    Construction; Basic theory; Phasor Diagram; Equivalent Circuits; No-load and Short-

    Circuit Tests; Voltage Regulation; Efficiency; Cooling methods; Polarity; Polyphase

    transformer Connections; Per-Unit Calculation; Parallel Operation of Transformers;

    Auto transformers; Tap-Changing transformers; Instrument Transformers.

  • 3

    CHAPTER ONE Transformers

    1. Introduction

    The transformer transfers electrical energy from one circuit to another via the medium of

    a pulsating magnetic field that links both circuits. The widespread development of ac

    power systems is principally due to the transformer. It enables us to produce and transmit

    power at economical voltages and to distribute it safely in factories and homes. In low-

    power low-current electronic and control circuits, it is used to provide impedance

    matching between a source and its load for maximum power transfer, to isolate one

    circuit from another, to isolate direct current while maintaining ac continuity between

    two circuits and to provide reduced ac voltages and currents for protection, metering,

    instrumentation and control.

    2. Principle of operation of a transformer

    The transformer is a straight-forward application of Faradays Law of Electromagnetic Induction. Consider the general arrangement of a single-phase transformer shown in Fig.

    1. An alternating voltage applied to coil 1, causes an alternating current to flow in the coil

    and this current produces an alternating flux in the iron core. A portion of the total flux

    links the second coil. The alternating flux induces a voltage in the second coil. If a load

    should be connected to the coil, this voltage would drive a current through it. Energy

    would then be transferred through the medium of magnetic field from coil 1 to coil 2. The

    combination of the two coils is called a transformer. The coil connected to the source is

    called the primary winding (or the primary) and the one connected to the load is called

    the secondary winding (or the secondary).

    V1

    I1

    E1 N1 N2 E2

    I2

    Load

    Coil 2Coil 1

    mSoft iron

    Fig. 1 An elementary transformer

    3. Polarity and terminal markings of a transformer Voltage E1 is induced in coil 1 and voltage E2 in coil 2. These voltages are in phase.

    Suppose at any given instant when the primary terminal 1 is positive with respect to

    primary terminal 2, the secondary terminal 3 is also positive with respect to secondary

    terminal 4 (See Fig. 2). Then terminals 1 and 3 are said to have the same polarity. To

  • 4

    indicate that their polarities are the same, a dot is placed beside primary terminal 1 and

    secondary terminal 3. Alternatively, letters of the same suffix, A1 (for the high-voltage

    winding) and a1 (for the low-voltage winding) say can be used. Current I1 entering coil 1

    through the dotted terminal 1 and current I2 entering coil 2 through the dotted terminal 3

    create fluxes in the same direction.

    1

    2

    3

    4

    A1

    A2

    a1

    a2

    1

    2

    3

    4

    A1

    A2

    a1

    a2

    (a) Magnetic Circuit (b) Electric Circuit

    Fig. 2 Polarity and terminal markings

    4.0 Ideal transformer

    An ideal transformer has no losses, no leakage flux and its core is infinitely permeable.

    An ideal transformer is shown in Fig. 3. The mutual flux m is confined to the iron.

    V1

    I1

    E1 N1 N2 E2

    I2

    m

    V2

    S

    (I1 = 0 on no load)

    Fig. 3 An ideal transformer

    4.1 Properties of an ideal transformer

    (a) Emf equation and voltage ratio (see Fig. 3): With the primary connected to an ac

    source V1, an alternating flux m is produced in the core. Let the flux be expressed as

    sinmax weberstm (1)

    The induced emf e1 as indicated in the figure is given by

    tNtdt

    dNN

    dt

    de m cossin max1max111

    Or

    90sinmax11 tNe (2)

    Hence

  • 5

    max1max1

    12

    2

    2

    fNNE

    Or

    max11 44.4 fNE (3)

    Similarly

    max2

    max2max2

    2 44.42

    2

    2

    fN

    fNNE

    (4)

    From (3) and (4), we obtain

    2

    1

    2

    1

    N

    N

    E

    E (5)

    The ratio a = N1/N2 is called the turns ratio. A step-up transformer has a < 1 and a step-

    down transformer has a > 1. In an ideal transformer, the applied voltage V1 and the

    induced voltage E1 must be identical. Hence we may write

    11 EV (6.a)

    And

    max11 44.4 fNV (6.b)

    Equation (6.b) indicates that for a given frequency, number of turns and voltage, the peak

    flux max must remain constant.

    (b) Current ratio and power equation: On no load I1 = 0. Now if a load is connected

    across the secondary terminals (i.e. switch S is closed) current I2 flows through the load.

    This current produces mmf N2I2 which if it acted alone would by Lenzs law, cause the mutual flux to reduce. Since when V1 is fixed the flux max is also fixed, the primary develops mmf N1I1 which is such that

    2211 ININ (7.a)

    Or

    aII 21 (7.b)

    In ideal transformer the secondary voltage

    22 EV (8)

    remains constant since E2 is fixed when the max is fixed. It can be deduced from above equations that for an ideal transformer

    2211 IVIV (9)

    That is there are no reactive and active losses in an ideal transformer.

  • 6

    (c) Phasor diagram of an ideal transformer (Fig. 4)

    E1

    E2

    m

    E1, V1

    E2, V2 I1

    I2

    m

    (a) No load (b) Load is resistive inductive

    Fig. 4 Phasor diagram of an ideal transformer

    Example 1

    An ideal transformer having 90 turns on the primary and 2250 turns on the secondary is

    connected to a 200-V, 50-Hz source. The load across the secondary draws a current of 2

    A at a power factor of 0.80 lagging. Calculate (a) the rms value of the primary current (b)

    the flux linked by the secondary winding (c) Draw the phasor diagram.

    Solution

    AIIININa 502225090)( 112211

    WbfN

    Vb 01.0

    905044.4

    200

    44.4)(

    1

    1max

    VEN

    NEc 5000)( 1

    1

    22

    36.9(0.8)cos is and between angle phase The -122 IV

    V2=E2 = 5000 V

    V1=E1= 200 V I2 = 2 A

    I1 = 50 A

    36.9

    m

    Example 2

    A 200-kVA, 6600-V / 400-V, 50-Hz 1-ph transformer has 80 turns on the secondary.

    Calculate (a) the approximate values of the primary and secondary currents (b) the

    approximate number of primary turns and (c) the maximum value of the flux.

  • 7

    Solution

    Aa 3.306600)1000200(current primary load-Full)(

    A500400)1000200(current secondary load-full and

    1320400)660080()( 1 Nb

    )]4([0225.0508044.4

    400)( max fromWbc

    (d) Impedance ratio (see Fig. 5): The impedance seen by the source

    ZaIEaaIaEIEIVZe2

    22

    2

    221111

    2ZaZe (10)

    V1 E1 E2 Z

    I2I1

    a : 1

    Fig. 5 impedance ratio

    (e)Equivalent circuits of an ideal transformer: From (10), we can represent the

    transformer in Fig. 5 by equivalent circuit shown in Fig. 6.a. We may also write

    aVaEEZI 1122

    Or

    21 ZI

    a

    V (11)

    and then represent the transformer by an equivalent circuit shown in Fig. 6.b

    V1 a

    2Z

    I1 I2

    a

    V1Z

    (a) Circuit referred to the primary side (b) circuit referred to the secondary side

    Fig. 6 Equivalent circuits of ideal transformer

  • 8

    Example 3 Calculate the voltage V and current I in the circuit of Fig. 7, knowing that the ideal

    transformer has a primary to secondary turns of 1:100 (i.e. a = 1/100).

    I5

    V1=10V 40k

    20k

    V

    Fig. 7 See Ex. 3

    Solution:

    We shall shift all impedances to the primary side

    10V

    5 2

    4 aVV

    Va

    VVvoltageactualTheVIRV

    AZ

    VI

    XXRZ

    e

    CLe

    8008100.842

    25

    10

    534

    1

    2222

    5.0 Practical single-phase transformer

    The windings of a practical transformer have both resistance and leakage inductance. The

    core is also imperfect: it has a core loss and finite permeability. The core loss has two

    components: hysteresis loss and eddy current loss.

    Hysteresis loss

    When ferromagnetic material is subjected to alternating magnetization, the energy put

    into the magnetic field when the flux is increasing is not completely given back when the

    flux dies away but a certain portion is wasted. The area of the hysteresis loop gives the

    value of the energy loss taking place for each complete cycle of magnetization. The loop

    area is found experimentally to vary as xBmax up to moderate values of flux density (1.0

    2.0 Wb/m2)

  • 9

    The index x is named after Steinmetz and is about 1.6 though it may be higher. In

    practice the hysteresis loss, for simplicity, is often taken as proportional to 2maxB

    If f = frequency of magnetization, the power wasted in magnetic hysteresis 3W/mHh fWP Or

    32

    max

    6.1

    max W/mfBfBPh (12)

    The hysteresis constant depends upon the magnetic material.

    Eddy-current loss

    When a changing magnetic flux permeates any mass of metal, eddy currents are induced.

    The eddy currents cause the metal to heat. Eddy currents are also induced in a core

    revolving in a stationary or constant magnetic field. If iron or metal subjected to

    alternating magnetization is built up of laminations insulated from each other, the eddy

    current loss is reduced.

    The eddy current loss in a laminated core is given by 32

    max

    22 W/m/)( BtkfPe (13.a)

    Where

    t = thickness of the laminations

    = resistivity of the material k = a constant depends on the waveform of the alternating flux

    For a given thickness and waveform, (13.a) reduces to 32

    max

    2 / mWBfkPe (13.b)

    Example 4

    In a transformer core of volume 0.16 m3 the total iron loss was found to be 2170 W at 50

    Hz. The hysteresis loop of the core material, taken to the same maximum flux density,

    had an area of 9.0 cm2 when drawn to scales of 1 cm = 0.1 Wb/m

    2 and 1 cm = 250 AT/m.

    Calculate the total iron loss in the transformer core if it is energized to the same

    maximum flux density, but at a frequency of 60 Hz.

    Solution

    Hysteresis loss = area x scale factors = 9 x 0.1 x 250 = 225 J/m3

    At 50 Hz, hysteresis loss = 225 x 50 x 0.16 = 1800 W

    Therefore Eddy-current loss = 2170 1800 = 370 W At 60 Hz, hysteresis loss = 1800 x (60/50) = 2160 W and

    Eddy-current loss = 370 x (60/50)2 = 533 W

    Therefore total iron loss = 2160 + 533 = 2693 W

    Example 5

    For the same maximum flux density, the total core loss in a core is 500 W at 25 Hz and

    1400 W at 50 Hz. Find the hysteresis and eddy-current losses for both frequencies.

  • 10

    Solution

    Since Bmax is constant, the losses can have the following forms:

    AfPh ,2BfPe and

    2BfAfPPP ehc

    For a frequency of 25 Hz, the core loss = 500 = A(25) + B(25)2

    For a frequency of 50 Hz, the core loss = 1400 = A(50) + B(50)2

    Solving the two equations, we obtain A = 12, B = 0.32 and the individual losses

    Ph = 300 W, Pe = 200 W at 25 Hz and Ph = 600 W, Pe = 800 W at 50 Hz

    5.1 Phasor diagram on no load

    To furnish the power loss in the core (core loss), a small current must be drawn from the

    source. This current Ip must be in phase with induced voltage E1. Also to create the

    mutual flux m, a magnetizing current Im in phase with m and lagging 90 behind E1 must be drawn to produce the required mmf.

    Im

    IoIp

    E2

    V1=E1

    Fig. 8 Phasor diagram for practical transformer on no load

    We note that

    (i) the no-load current Io taken by the primary is the phasor sum of Ip and Im

    (ii) the difference between the value of the applied voltage V1 and that of the induced emf

    E1 is only about 0.05% when the transformer is on no load so the two can be considered

    to be equal

    (iii) Ip is very small compared with Im. Therefore the no-load power factor is very low.

    Example 4

    A 1-ph transformer has 480 turns on the primary and 90 turns on the secondary. The

    mean length of the flux path in the iron core is 1.8 m and the joints are equivalent to an

    air gap of 0.1 mm. If the peak value of the flux density is to be 1.1 T when a voltage of

    2200 V at 50 Hz is applied to the primary, find (a) the cross-sectional area of the core (b)

    the secondary voltage on no load (c) the primary current and power factor on no load.

    Assume the value of the magnetic field strength for 1.1 T in iron to be 400 A/m, the

    corresponding iron loss to be 1.7 W/kg at 50 Hz and the density of the iron to be 7800

    kg/m3.

  • 11

    Solution

    Wba 0206.05048044.42200)( maxmax

    20187.01.10206.0 core of area sectional-Cross m

    Vb 5.412480

    902200 load noon voltageSecondary )(

    Ammfc 7208.1400 coreiron for the required ofvaluePeak)(

    g

    o

    g

    gg lB

    lHAmmf

    5.870001.0104

    1.1 gapair for the ofvaluePeak

    7

    A5.8075.87720 produce torequired mmf totalofvaluePeak max

    AN

    mmftotalofvaluePeak682.1

    480

    5.807current gmagnetizin of Peak value

    1

    AIm 19.12

    682.1 sinusoidal be it to assuming valuerms Its

    30337.00187.08.1iron of Volume m kg26378000337.0density volumeiron of Mass

    W4477.1263 lossiron And

    AI p 203.02200447

    AIo 21.1203.019.1current load No22

    laggingNo 168.021.1203.0II factor power load op

    5.2 Mutual and leakage fluxes in a transformer (see Fig. 9) The actual flux linking a coil can be considered to have two components: the mutual flux

    m linking both coils and the leakage flux l. The reluctance of the paths of the leakage flux is almost entirely due to the long air paths and is therefore practically constant.

    Consequently, the value of the leakage flux is proportional to the current in the coil.

    V1

    I1

    Ep l1 l2 Es V2

    I2

    m

    Fig. 9 Ttransformer possessing two leakage fluxes and a mutual flux

    The secondary induced voltage Es is composed of two parts:

    (a) a voltage El2 induced by leakage flux l2 given by El2 = 4.44fN2l2,max (b) a voltage E2 induced by mutual flux m given by E2 = 4.44fN2max

  • 12

    Similarly, the primary induced voltage is composed of El1 =4.44fN1l1,max and El1 = 4.44fN1max

    We can segregate the four voltages E1, E2, El1 and El2 by rearranging the transformer

    circuit as shown in Fig. 10. The rearrangement of the transformer circuit makes it clear

    that El1 and El2 are voltage drops across reactances. These reactances called leakage

    reactances are given by 222111 and IEXIEX ll

    V1

    I1

    E1 E2

    I2

    m

    Es

    El2 Ep

    El1

    l1 l2

    Fig. 10 Separating out the various induced voltages

    5.3 Equivalent circuit of a practical transformer

    The behaviour of a practical transformer may be conveniently considered by assuming it

    to be equivalent to an ideal transformer and then allowing for the imperfections of the

    actual transformer by means of additional circuits or impedances inserted between the

    supply and the primary winding and between the secondary winding and the load. The

    complete equivalent circuit of this transformer is shown in Fig. 11. R1 and R2 are

    resistances of the primary and secondary windings. X1 and X2 are the leakage reactances.

    The reactance Xm is such that it takes a reactive current Im (i.e. the magnetizing current)

    of the actual transformer. The core loss is accounted for by the resistor Rm which takes

    the component Ip of the primary current.

    R1X1

    Rm

    Ip

    Io

    Im

    Xm E1 E2

    I21

    I2X2 R2

    Z

    Ideal

    transformer

    V1 V2

    Fig. 11 Complete equivalent circuit of a practical transformer

    Ideal transformer equations still apply: 2212 INNI and 2121 NNEE

  • 13

    5.4 Equivalent circuit referred to the primary side (Fig. 12a)

    R1X1

    Rm

    Ip

    Io

    Im

    Xm E1

    I21 X2

    1

    R21

    Z1 V2

    1

    Fig. 12.a.Exact equivalent circuit referred to the primary side

    Let 21 NNa (14.a)

    Then

    2

    2

    2

    2

    212 )( XaXNNX , 22

    2

    2

    212 )( RaRNNR , ZaZNNZ22

    21 )( (14.b)

    22212 )( aVVNNV

    , aII 22

    (14.c)

    It is worth noting that for a practical transformer, 1212 XXandRR

    5.5 Equivalent circuit referred to the secondary side

    R11 X1

    1

    Rm1

    Ip1

    Io1

    Im1

    Xm1

    I2 X2 R2

    Z V2a

    1V

    I11

    Fig. 12.b.Exact equivalent circuit referred to the secondary side

    etcaRRNNR ,)( 2112

    121

    (15.a)

    etcaIIorININ pppp

    12 (15.b)

  • 14

    5.5 Approximate equivalent circuits

    The exact equivalent circuit of the transformer is too exact for most practical

    applications. Consequently, we can simplify it to make calculations easier. Approximate

    equivalent circuits commonly used for power transformer calculations are given in Fig.

    13

    V1

    I1

    Rm

    Ip

    Io

    Im

    Xm

    I21 Xe1=X1+X2

    1

    Z1 V2

    1

    Re1=R1+R21

    (a) Voltage drop in the primary leakage impedance due to exciting or

    no load current Io is neglected.

    V1

    I1 = I21 Re1

    Xe1

    Z1

    V21

    (b) Exciting current is neglected entirely. Note that primary rated or

    full load current is at least 20 times larger than Io. This circuit may

    be used when I1 = 1.15xfull load current

    V1

    I1 = I21 Xe1

    Z1

    V21

    (c) For transformers above 500 kVA, Xe is at least 5 times

    greater than Re. This circuit can be used to calculate

    voltage regulation of such transformers.

    Fig.13 Approximate equivalent circuits

  • 15

    5.5 The complete phasor diagrams for loaded conditions

    They are shown in Fig. 15

    Fig. 15 Complete phasor diagrams for loaded conditions (drawn in two parts)

    5.6 Rating of transformers To keep the transformer temperature at an acceptable level, limits are set to both the

    applied voltage (this determines the iron loss at a given frequency) and the current drawn

    by the load (this determines copper loss). The limits determine the rated voltage and rated

    current of transformers.

    The power rating of transformer Srated = rated voltage x rated current can be expressed in

    VA, kVA or MVA depending on the size of the transformer. The rated kVA (i.e. the rated

    power), frequency and voltage are always shown on the name plate. In large

    transformers, the corresponding currents are also shown. We note that

    Rated kVA = V1r x I1fl x10-3

    = V2r x I2fl x10-3

    = V2n xI2fl x10-3

    =E2n x I2fl x10-3

    Where

    V1r = rated primary voltage

    I1fl = rated primary current = primary full load current

    V2r = rated secondary voltage = V2n (no load secondary voltage corresponding to the rated

    primary voltage) = E2n (no load induced secondary voltage corresponding to primary

    rated voltage)

    I2fl = rated secondary current = secondary full load current

    5.7 The turns ratio

    It is given by

    21 EEa

    rVE 11 on no load because ZI 1o is very small. Since V E 22 on no load

  • 16

    rrVVa

    21 (16.a)

    And aII flfl 21 (16.b)

    Example 7

    A transformer is rated 10 kVA, 2400 / 240 V, 60 Hz. The parameters for the approximate

    equivalent circuit of Fig. 14.a are Rm = 80 k, Xm = 35 k, Re1 = 8.4 and Xe1 = 13.7 . Determine the voltage to be applied to the primary to obtain the rated current in the

    secondary when the secondary terminal voltage is 240 V. What is the input power factor?

    The load power factor is 0.8 lagging.

    Solution

    AIaII flfl 17.4240010000122

    The power factor angle 9.368.0cos 1 If we choose the load current I2 as the reference phasor, then 9.362402V

    volts144019209.362400 ja

    22 VV

    The voltage across the equivalent leakage impedance is

    volts5735017.47.134.8 jjj 2e1IZ

    The primary voltage required

    voltsjjj 4.37246214971955 573514401920 2e121 IZVV

    mAjk

    j

    Rm7125.184375.24

    80

    14971955

    1p

    VI

    mAjkj

    j

    jX m8571.557714.42

    35

    14971955

    1m

    VI

    0558.00427.00187.00244.0017.4 jjj mp21 IIII Aj 50.0237.40371.02371.4

    9.3750.04.37 and between angle Phase IV 11 lagging79.09.37cosfactor power Input

    Example 8

    A 1-ph transformer operates from a 230-V supply. It has an equivalent resistance of 0.1 and an equivalent leakage reactance of 0.5 referred to the primary. The secondary is connected to a coil having a resistance of 200 and a reactance of 100 . Calculate the secondary terminal voltage. The secondary winding has four times as many turns as the

    primary.

  • 17

    Solution

    Refer to approximate equivalent circuit of Fig. 14.b

    25.65.12100200,100200,4

    1 2

    2

    1 jjajN

    Na ZZ

    75.66.1225.65.125.01.0impedanceTotal jjj ZZe1

    25.65.1275.66.12

    0230

    75.66.12

    0230j

    jand

    j

    22 VI

    voltsj

    j8719.224

    2941.14

    9754.13230

    75.66.12

    25.65.12230

    2V

    voltsa

    VV 8998719.224422

    5.8 Definition of per-unit impedances The leakage impedances Z1 and Z2 on the primary and secondary side are expressed in

    per unit as follows:

    2

    1

    1

    1

    1

    1

    1

    11

    r

    rated

    r

    fl

    base V

    SZ

    V

    IZ

    Z

    ZZ (17.a)

    2

    2

    2

    2

    2

    2

    2

    22

    r

    rated

    r

    fl

    base V

    SZ

    V

    IZ

    Z

    ZZ (17.b)

    rated

    rbase

    rated

    rbase

    S

    VZand

    S

    VZ

    22

    2

    21

    1

    where

    (17.c)

    The impedances are said to be expressed in per unit with reference to the bases V1r, Srated

    in the case of Z1 and V2r, Srated in the case of Z2. The total impedance of the transformer in

    per unit . 21 ZZ

    Example 5: A single-phase transformer that is rated 3000 kVA, 69 kV / 4.16 kV, 60 Hz

    has an impedance of 8 percent. Calculate the total impedance of the transformer referred

    to (a) the primary side (b) the secondary side

    Solution

    1587

    103000

    1069)(

    3

    622

    1

    rated

    rbase

    S

    VZa

    127158708.0 111 baseee ZZZ

    7685.5103000

    1016.4)(

    3

    6222

    2

    rated

    r

    baseS

    VZb

    46.07685.508.0 222 baseee ZZZ

  • 18

    Alternatively

    46.0127

    69

    16.42

    1

    2

    1

    22 ee Z

    N

    NZ

    5.9 Voltage regulation

    With the primary voltage maintained constant, the secondary terminal voltage at no load

    differs from the secondary voltage under load. The voltage regulation or simply

    regulation of a transformer is the change in secondary voltage which occurs when the

    rated kVA output at a specified power factor is reduced to zero, with the primary voltage

    maintained constant. It is usually expressed as a percentage (called percentage regulation)

    or a fraction of the rated no-load terminal voltage (in per unit).

    The equivalent circuit given in Fig. 14.b is used to calculate voltage regulation. The

    circuit may be either referred to the primary or the secondary side. The circuit in general

    form can thus be represented as shown in Fig. 16.

    If the circuit is referred to the primary side, then

    1121 ,, eeee XXandRRVVVE

    eReX

    Load VE

    Fig. 16 Circuit for computing voltage regulation

    Voltage regulation puV

    VV

    E

    VE

    1

    21

    (18.a)

    If the circuit is referred to the secondary side, then

    2221

    2 ,, eeeen XXandRRVVa

    VVE

    Voltage regulation puV

    VV

    n

    n

    2

    22 (18.b)

    It can be shown thatn

    n

    V

    VV

    V

    VV

    2

    22

    1

    21

    (19)

    And nVV 22 1 (20)

    In general, let the load current be I lagging behind the load voltage V by . Then taking

    the load voltage as the reference phasor, we can write

  • 19

    sincossincos

    sincos01

    eeee

    ee

    IRIXjIXIRV

    jIIjXRjV

    E

    And hence

    22 sincossincos eeee IRIXIXIRVE E

    The second term under the root is usually negligible except at low leading power factors.

    Considering the first term only gives

    sincos ee IXIRVE

    Or sincos ee IXIRVE (21)

    The angle is negative when current is leading and positive when current is lagging.

    The voltage regulation is maximum when = where

    e

    e

    R

    X1tan

    0cossin

    ee IXIRVE

    d

    dFrom

    Hence ee

    ee

    e

    ee

    e

    ee ZI

    Z

    XRI

    Z

    XIX

    Z

    RIRVE

    22

    max (22.a)

    Where22

    eee XRZ (22.b)

    From (21)

    sincos

    E

    IX

    I

    I

    E

    IR

    I

    I

    E

    VE

    fl

    fl

    fl

    fl Or

    sincos ........ upupupup XIRIE

    VE

    (23)

    Where

    etc,unitperiniresistanceunitperincurrent .... EIRRIII upflup

    We note the following:

    (i) Usually the quantities will be referred to the secondary side (ii) With (23), it is not necessary to refer quantities from primary to secondary side, for

    per-unit values of primary and secondary impedances can be added directly

    (iii)The equations are correct at any current or kVA and at rated current or kVA.

    (iv) At rated current or kVA, Ip.u.=1. (v) It is supposed that E is the rated voltage. When E is not the rated voltage, voltage

    regulation can still be calculated using (21).

  • 20

    Example 9

    A 100-kVA 1-ph transformer has 400 turns on the primary and 80 turns on the secondary.

    The primary and secondary resistances are 0.3 and 0.01 respectively, and the corresponding leakage reactances are 1.1 and 0.035 respectively. The supply voltage is 2200 V. Calculate (a) the equivalent impedance referred to the primary circuit and (b)

    the voltage regulation and the secondary terminal voltage for full load having a power

    factor of (i) 0.8 lagging and (ii) 0.8 leading (c) the maximum voltage regulation

    Solution

    55.0)80400(01.03.0)()( 222

    2111 RNNRRa e

    975.1)80400(035.01.1 21eX

    05.2975.155.0 21

    22

    1eZ

    6.0sin8.0cos)()( ib

    AI fl 45.452200101003

    1

    pu0336.02200

    6.0975.18.055.045.45

    VV n 440400

    8022002

    VVV n 2.4250336.01440122

    puii 0154.02200

    6.0975.18.055.045.45)(

    VV 8.4460154.014402

    .0424.02200

    05.245.45regulationvoltagemaximum)(

    1

    11

    max puV

    ZIc

    efl

    Example 10

    The primary and secondary windings of a 30-kVA, 6000-V / 230-V transformer have

    resistances of 10 and 0.016 respectively. The total reactance of the transformer referred to the primary is 23 . Calculate the percentage regulation of the transformer when supplying full load current at a power factor of 0.8 lagging.

    Solution

    89.20)2306000(016.010)( 222

    2111 RNNRRe ]

    231eX

    AI fl 5600010303

    1

    pu0254.06000

    6.0238.089.205

    %54.2regulationPercent

  • 21

    5.10Transformer output

    The transformer supply voltage and frequency are substantially constant; the heating

    therefore depends on the current taken by the load. Since the secondary voltage of the

    transformer is also substantially constant it means that the heating also depends on the

    load kVA. The transformer output is therefore usually quoted in kVA. The transformer

    load in kVA is given by

    kVA10 322 IVS (24)

    Where

    V2 = actual load voltage and

    I2 = actual load current.]

    When S is given and V2 is unknown the load current can be estimated using the

    approximate equation

    kVA10 322 IVS n (25)

    5.11 Efficiency

    The losses which occur in a transformer on load are composed of

    (i) Copper losses in primary and secondary windings, namely

    22

    212

    12221

    21 ee RIRIRIRI

    (ii) Iron losses in the core due to hysteresis and eddy currents. The iron losses depend on

    the peak value of the mutual flux m and frequency. It is therefore independent of load current if voltage and frequency are constant.

    Let

    Pi = the iron losses (fixed loss) in kW and

    Pc = the copper loss with full-load S kVA in kW

    Then the total loss at any load xS kVA at power factor cos is Pi + x2 Pc and the

    efficiency is

    c

    ici xPx

    PS

    S

    PxPxS

    xS

    input

    output

    cos

    cos

    cos

    cos2

    For a given power factor, the efficiency is maximum when the expression in brackets is a

    minimum. Hence for a maximum efficiency, we have

    cic

    i

    c

    i

    c

    i PxPorPx

    PorxP

    x

    P

    dx

    dFrom

    P

    Px 2

    200 (26)

    i.e. efficiency is maximum when the copper loss, ic PPx 2 , the fixed loss or iron losses.

    The efficiency of a transformer is calculated using this form of efficiency equation:

    ci

    ci

    PxPxS

    PxP

    outputlosses

    losses2

    2

    cos11

    (27)

  • 22

    Example 13

    The primary and secondary windings of a 500-kVA transformer have resistances of 0.42

    and 0.0011 respectively. The primary and secondary voltages are 6600 V and 400 V respectively and the iron loss is 2.9 kW. Calculate the efficiency on full load at a power

    factor of 0.8.

    Solution

    AI fl 1250400

    1000500currentsecondary load-Full 2

    AI currentprimary load-Full fl 8.756600

    10005001

    W17200011.01250load fullon losscopper Secondary 2

    W241542.08.75load fullon losscopper Primary 2

    kW135.4W413524151720load fullon losscopper Total cP ,

    kW035.79.2135.4load fullon loss Total

    kW4008.0500pf 0.8at load fullon power Output

    %27.989827.0035.7400

    035.71

    load full on Efficiency

    Example 12

    Find the output, at which the efficiency of the transformer of example 11 is maximum

    and calculate its value assuming the power factor of the load to be 0.8.

    Solution

    837.0135.4

    9.2

    c

    i

    P

    Px

    kVA5.418500837.0efficiency maximumat output Therefore

    kW8.59.22loss total,efficiency maximumAt

    kW8.3348.05.418pf0.8at power output and

    %30.98983.08.3348.5

    8.51efficiency maximum Therefore,

    Example 13

    A 400-kVA transformer has an iron loss of 2 kW and the maximum efficiency at 0.8 pf

    occurs when the load is 240 kW. Calculate (a) the maximum efficiency at unity power

    factor and (b) the efficiency on full load at 0.71 power factor

    Solution

    kW422efficiency maximumat loss Total(a)

    kVA3008.0

    240 efficiency maximumat kVA Output

    kW3001300pfunity at efficiency maximumat power Output

  • 23

    %68.989868.03004

    41pfunity at efficiency Maximum

    75.0400

    300max is efficiency heat which tkVA load full of fraction x The)( b

    kW56.375.0

    2losscopper load Full

    2

    2

    ic

    x

    PP

    pf at efficiency load Full %08.989808.071.040056.32

    56.32171.0

    5.12 All-day efficiency

    Power transformers operate at substantially constant load. They are designed such that

    the maximum efficiency occurs at the normal operating load. Generally their efficiency

    varies little as the load varies from 50 to 130 % of its rated kVA.

    Distribution transformers on the other hand supplies load which varies widely over a 24-h

    period. The efficiency of these transformers is better assessed on energy basis. The

    output and losses are calculated in kW hours over a 24-hour day. The all-day efficiency is

    defined as

    kWhinoutputkWhinlosses

    kWhinlossesdayall

    1 (28)

    Example 14

    A 200-kVA 1-ph transformer has full load copper loss of 3.02 kW and iron loss of 1.6

    kW. The transformer is in circuit continuously. For a total of 8 hours, it delivers a load of

    160 kW at 0.8 pf. For a total of 6 hours, it delivers a load of 80 kW at unity power factor.

    For the remainder of the 24-h cycle, it is on no load. What is the all-day efficiency?

    Solution

    kWlossTotal

    kWlossiron

    kWlosscopper

    62.4

    60.1

    02.3load),(fullkVA200kVApf,0.8kW,160At

    kWlossTotal

    kWlossiron

    kWlosscopper

    08.2

    60.1

    48.002.3200

    80,kVA80kVAupf,kW,80At

    2

    kW loss Total 6.1load), noon losscopper no is (there load noOn

    kWhlosstotalkWhoutputtotal

    kWhlosskWh output

    kWhlosskWh output

    kWhlosskWh output

    5.651760h,24In

    16106.10100h 10For

    5.12608.2480680h 6For

    37862.412808160h 8For

  • 24

    %41.969641.017605.65

    5.651efficiencydayAll

    5.13 Open-circuit and short-circuit tests on a transformer

    These two tests enable the efficiency and voltage regulation to be calculated without

    actually loading the transformer.

    (a) Short-circuit test: This test is used to determine the leakage impedance. During this

    test, one winding is short-circuited and a reduced voltage Vsc applied to the other to cause

    rated current to flow. The test circuit and the equivalent circuit are shown in Fig. 18.a and

    Fig. 18.b respectively. The magnetizing branch is neglected because its current under

    this condition is less than 1 % of the total.

    Voltage Vsc, current Isc and power Psc measured by the instruments are used to make the

    following calculations.

    )()()()( 21211211

    cRZXcI

    PRb

    I

    VZa eee

    sc

    sce

    sc

    sce (29)

    We note that the following:

    (i) Isc need not be the rated current since the equivalent circuit is linear. However, it is desirable that it should be near to the rated value so that stray losses (they are due to

    eddy currents set up in large section conductors, tank and metallic supports by

    leakage fluxes) are normal.

    (ii) The supply could be fed to either winding. It is often convenient on the higher voltage transformers to supply the high-voltage winding, thus using a smaller current.

    Vsc which will be about 3-15 % of the rated value may also be more suitable for test

    facilities.

    (iii)In laboratory experiments using small transformers, the instruments positions shown

    minimize measurement errors.

    (iv) The circuit parameters obtained with (27) are referred to the side which the test voltage is applied.

    )()()()( 21211211

    cRZXcI

    PRb

    I

    VZa eee

    sc

    sce

    sc

    sce

    Fig. 18 Short-circuit test

    (b) Open-circuit test or no load test: During this test, one winding is open-circuited and

    rated voltage at rated frequency is applied to the other. Quite often the low-voltage side is

    supplied to reduce the test voltage required for safety reasons. As with the short-circuit

  • 25

    test, the equivalent circuit parameters will be referred to the side to which the test voltage

    is applied. The test circuit and equivalent circuit are shown in Fig. 19.a and b.

    The following calculations can be made

    2

    11122

    1

    )()()()()(V

    Vae

    I

    VXd

    I

    VRcIIIb

    V

    PIa

    m

    m

    p

    mpomo

    p (30)

    Psc and Po represent the full load copper loss and the core loss (or iron losses)

    respectively. They can be used directly to calculate efficiency.

    .

    2

    11122

    1

    )()()()()(V

    Vae

    I

    VXd

    I

    VRcIIIb

    V

    PIa

    m

    m

    p

    mpomo

    p

    Fig. 19 Open-circuit or no-load test

    Example 15

    The circuit shown below was used in a test on a 3-kVA transformer. A variable voltage

    supply of fixed frequency was connected to terminals A and B and two tests were

    performed:

    (a) The voltage was raised to normal rated voltage and the meter reading were then 200 V, 24 W, 1.2 A

    (b) The terminals C and D were short-circuited and the voltage was raised until the transformer full-load current was flowing. The meter readings were then 6.4 V, 28 W,

    15 A

    From the results of the tests, obtain:

    (i) the no-load current and its power factor (ii) the iron losses of the transformer at normal frequency and voltage (iii)the full-load copper loss

    (iv) the transformer resistances, Re1 and Rm and reactances Xe1 and Xm (v) the efficiency of the transformer at full load at a power factor of 0.8

  • 26

    A

    B

    V

    A C

    D Circuit diagram for Example 13

    Solution

    A1.2I i o current load-No )(

    W 24PP (ii) oi lossesIron

    W 28PP (iii) scc losscopper load Full

    :nscalculatiost circuit te-Open (iv)

    AIIIAV

    PI pom

    op 19.112.02.112.0

    200

    24 2222

    1

    16819.1

    20067.1

    12.0

    200 11

    m

    m

    p

    mI

    VXk

    I

    VR

    :nscalculatiost circuit te-Short

    12.015

    2843.0

    15

    4.6211 2

    sc

    sce

    sc

    sce

    I

    PR

    I

    VZ

    41.012.043.0 2221211 eee RZX

    %88.979788.02824)8.03000(

    28241)

    puEfficiencyv

    Example 16

    A 10-kVA 1-ph transformer has a voltage ratio 1100 / 250 V. On no load and at normal

    voltage (1100 V) and frequency the input current is 0.75 A at a pf of 0.2 lagging. With

    the secondary short-circuited, full-load currents flow when the primary applied voltage is

    77 V, the power input being 240 W. Calculate

    (a) the transformer equivalent resistance and reactance referred to the secondary side (b) the maximum value of the voltage regulation at full load and the load power factor at

    this regulation

    (c) the percentage of full-load current at which the transformer has maximum efficiency

  • 27

    Solution

    (a) Referring the circuit to the secondary side,

    V5.171100

    250771

    a

    V

    A40250

    00010

    2

    n

    rated

    V

    SI

    438.040

    5.172eZ , 15.0

    40

    24022e

    R and 41.015.0438.0 222eX

    (b) The maximum voltage drop at full load = 5.1722 efl ZI V

    The maximum regulation occurs when or when

    lagging342.0438.0

    15.0coscos

    2

    2 e

    e

    Z

    R

    (c) Maximum efficiency occurs when oc PPx 2 . Therefore

    %9.82or829.015.040

    2.075.011002

    x

    5.14 Construction of transformers

    Power transformers are designed so that their characteristics approach those of an ideal

    transformer

    (a) To attain high permeability and consequently a small magnetizing current, the core is

    made of iron and the core forms a closed magnetic circuit

    (b) To keep the hysteresis loss down, high-grade grain-oriented steel having a narrow

    hysteresis loop is used

    (c) To keep the eddy current loss down, the core is laminated and 3 to 4% silicon is added

    to increase the resistivity of the steel. The laminations (about 0.4mm thick) are insulated

    from each other by a thin layer of insulation, thus overall cross-sectional area is slightly

    greater than the actual cross-sectional area of the iron.

    (d) To keep the leakage fluxes low, the windings are arranged as shown in Fig. 18 in the

    case of 1-ph transformers. Two main forms of magnetic circuits are used: core- and shell-

    type arrangements. The core-type construction has the primary and secondary windings

    distributed over both core legs in order to reduce the amount of copper (i.e. length of

    turns is reduced).

    The transformer windings are carefully insulated from each other and from the core.

    Winding resistances R1 and R2 are also minimized to minimize copper losses.

  • 28

    L L

    H H

    L LH H

    H L L H H L L H

    windingsconcentric

    on with constructi type-Core (a)

    windingssandwiched

    on with constructi type-Shell (b)

    LL

    Fig. 20 Common Single-phase transformer construction

    5.15 Polarity tests

    The four terminals of a single-phase transformer may be mounted so that it has either

    additive or subtractive polarity as shown in Fig. 21

    A2 a1

    A1 a2

    A2

    a1

    a2

    A1

    polarity additive (a) polarity esubtractiv (b)

    Fig. 21Two standard ways of mounting transformer terminals

    If it becomes necessary to determine whether a transformer has additive or subtractive

    polarity then either of the following polarity tests may be used:

    (a) Using a low-voltage ac source: Referring to Fig. 22,

    (i) Connect the HV winding to ac source

    (ii) Connect a jumper J between any two adjacent HV and LV terminals (1, 3)

    (iii) Connect a voltmeter (V2) between the other two adjacent HV and LV terminals (2, 4)

    (iv) Connect a voltmeter (V1) across the HV winding.

    Reading of voltmeter V2 = E1 E2 = V1 E2 if 1 and 3 possess the same polarity = E1 + E2 = V1 + E2 if they do not

    Therefore if V2 is lower than V1 then the polarity is subtractive and if V2 is higher than V1

    then the polarity is additive

    1 3

    2 4

    V1V2

    J

    Fig. 22 Polarity test using ac source

  • 29

    (b) Using dc source: Referring to Fig. 23,

    (i) Connect a dc source to LV winding

    (ii) Mark the terminal connected to the positive side of the source a2

    (iii) Connect a dc voltmeter across the HV winding

    (iv) Close the switch and observe the movement of the pointer of the voltmeter

    (v) If the pointer moves upscale, the transformer terminal connected to the (+)

    terminal of the voltmeter is marked A2 and the other marked A1.

    a2

    V+

    -

    Fig. 23 Polarity test using dc source

    5.15 Parallel Operation of single-phase transformers

    Parallel connection of several transformers is widely used in electrical systems for the

    following reasons:

    (a) In many cases, the amount of power to be transformed is greater than that which can be built into one transformer

    (b) Frequently, the growth of load requires that the installed transformers supply an output greater than their total kVA capacity. Additional transformers are then

    installed to run in parallel with the existing transformer.

    (c) It is sometimes found desirable to supply a load through two or more units in order to reduce the cost of the spare unit required to ensure continuity of service in case of

    damage.

    The following conditions must be fulfilled when operating two or more single-phase

    transformers in parallel:

    (a) The polarity should be the same. The polarity can be either right or wrong. A wrong polarity results in a severe short circuit. Terminals of the same markings are

    connected together to ensure correct polarity. See Fig. 24. If the polarity markings

    are either incorrect or not present, the polarity of the incoming transformer can be

    checked by connecting a voltmeter across the paralleling switch

    (b) The voltage ratio should be the same. This is to avoid no-load circulating current and also over-loading on one transformer when the paralleled transformers are loaded.

    (c) The per-unit impedances should be equal in magnitude and have the same angle. When they are equal in magnitude, the transformers share kVA loads in proportion to

    their respective ratings. If both their magnitudes and angles are the same they will not

    only share kVA loads in proportion to their respective ratings but also the combined

    load kVA will be the algebraic sum of the kVA carried by each transformer. If the

    angles are different, the resultant kVA capacity of the paralleled group will be slightly

    smaller than the sum of their individual ratings if none should be overloaded. It is not

    very necessary that the angles should be the same

  • 30

    A2 a2

    A1 a1

    Tx1

    Tx2

    A2

    A1

    a2

    a1

    Load

    Fig. 24 Connection ensuring correct polarity

    5.16 Load sharing of parallel-connected transformers The equivalent circuit of two transformers in parallel feeding a common load ZL is shown

    in Fig. 25. The voltage ratios are supposed to be equal and the magnetizing branch is

    neglected. The circuit is referred to the secondary side but it may also be referred to the

    primary side.

    a

    V1

    1I

    2I

    1Z

    2Z

    I

    VLZ

    Fig. 25 Equivalent circuit of two transformers in parallel

    Z1 is the impedance of transformer 1 referred to the secondary side and Z2 is the

    impedance of transformer 2 referred to the secondary side.

    The voltage drops across the impedances are the same. Therefore

    )( 21

    212211

    ZZ

    ZZIZIZI

    Or

    IZZ

    ZIandI

    ZZ

    ZI

    21

    12

    21

    21

    Multiplying by the terminal voltage V gives

    21

    21

    ZZ

    ZSS

    (31.a)

    21

    12

    ZZ

    ZSS

    (31.b)

  • 31

    Where

    loading 1r transforme11 VIS (32.a)

    loading 2r transformeS 22 VI (32.b)

    load combinedVIS (32.c)

    Equations (31) hold for per-unit impedances provided that all are expressed with

    reference to a common base power. The following equation can be used to obtain a new

    per unit value with reference to a new base power.

    old

    base

    new

    baseold

    pu

    new

    puS

    SZZ (33)

    Example 17

    A 500-kVA transformer (Transformer 1) is connected in parallel with a 250-kVA

    transformer (Transformer 2). The secondary voltage of each is 400 V on no load. Find

    how they share a load of 750 kVA at power factor of 0.8 lagging if

    pujZ

    andpupujZc

    pupujZ

    andpupujZb

    pupujZ

    andpupujZa

    62.6005095.00444.0025.0

    69.7805099.005.001.0)(

    69.7805099.005.001.0

    69.7805099.005.001.0)(

    44.6904272.004.0015.0

    69.7805099.005.001.0)(

    2

    1

    2

    1

    2

    1

    Solution

    If all the impedances are referred to a base power of 500 kVA, then only the impedances

    of transformer 2 will change.

    old

    pu

    old

    puold

    base

    new

    baseold

    pu ZZS

    SZ 2

    250

    500Znewpu

    Case (a)

    69.7805099.005.001.01 jZ and

    44.6908544.008.003.004.0015.022 jjZ

    Further

    90.721360.013.004.008.003.005.001.021 jjjZZ kVAS 9.367508.0cos750loadkVATotal 1

    kVAZZ

    ZSS

    36.40471

    9.72136.0

    44.6908544.09.36750

    21

    21

    lagging 762036.40cos offactor power at 471 .kVA

  • 32

    Similarly

    11.31281

    9.72136.0

    69.7805099.09.367502S

    lagging 8560 offactor power at 281 .kVA

    Remark: Transformer 1 with larger per-unit impedance is under-loaded whereas

    transformer 2 with lower per-unit impedance is overloaded.

    Case (b)

    pujjZ 69.7810198.01.002.005.001.022 pujZZ 69.7815297.015.003.021

    kVAS

    9.36500

    69.7815297.0

    69.7810198.09.367501

    lagging 80 offactor power at 500 .kVA

    kVA

    9.36250

    69.7815297.0

    69.7805099.09.36750S2

    laggging 80 offactor power at kVA 250 .

    Remark: Load shared in proportion to transformer ratings. Arithmetic sum of loadings is

    equal to the combined load. A shorter approach can be used on recognizing that

    pupu ZZ 21

    Case (c)

    pujjZ 62.601019.00888.005.00444.0025.022 62.661512.01388.006.021 jZZ

    9.42505

    62.661512.0

    62.601019.09.367501S

    lagging 7320 offactor power at 505 .kVA

    82.24253

    62.661512.0

    69.7805099.09.367502S

    lagging 910 offactor power at kVA 253 .

    Remark: Transformers are slightly overloaded when the combined load is equal to the

    sum of individual kVAs

  • 33

    6.0 Three-phase transformers

    These are required to transform 3-phase power. The three-phase transformer may be

    either of the following:

    (a) A three-phase transformer bank: This consists of three identical single-phase

    transformers having their windings externally connected for three-phase working. The

    single-phase transformers retain all their basic single-phase properties such as current

    ratio, voltage ratio and the flux in the core. The kVA capacity of the bank is the sum of

    their individual ratings. See Fig.26.

    (b) A three-phase transformer unit: This is a single unit of special construction for three-

    phase working. Modern large transformers are usually of the three-phase three-legged

    core type shown in Fig.27. A leg carries the primary and secondary windings of a phase.

    The windings are internally connected. For a given total capacity, 3-phase units are much

    cheaper in capital cost, lighter, smaller and more efficient.

    Tx1

    Tx2

    Tx3

    1L

    2L

    3L

    1L

    2L

    3L

    2A

    1a1A

    2a

    2A

    2A

    1A

    1A

    2a

    2a

    1a

    1a

    ers transformphase-single of connectionStar -Delta 9 Fig.

    6.1 Winding arrangement

    The three windings, primary or secondary, can be connected in three different ways:

    (a) Star connection: For this connection %583 voltagelinevoltagephase of the

    line voltage. This enables the insulation of the winding to be reduced to a minimum for a

    given supply voltage. Line current = phase current. It is the most economical connection

    for a high-voltage winding.

    (b) Delta connection: Phase voltage = Line voltage. Therefore winding must be

    insulated for the full Line voltage. More turns are also required. With very high voltages

    a saving of 10 % may be achieved by using star-connection rather than delta connection

    on account of insulation. The saving is small, however, at voltages below 11 kV. For

    delta connection 3currentlinecurrentphase so the winding cross-sectional area is

  • 34

    58 % of that required for the star connection. Therefore it is the most economical for

    low-voltage winding.

    (c) Zigzag (or interconnected star) connection: It is a modification of the star

    connection. Each phase winding is divided into two sections and placed on two different

    legs. The two sections are then connected in phase opposition. The zigzag connection is

    restricted to the low-voltage winding. 15 % more turns are required for a given phase

    terminal voltage compared with a normal star.

    The three different winding arrangements give rise to several possible connection

    combinations: star-star, star-delta, star-zigzag, delta-star, delta-delta, etc

    1L 2L 3L

    2A2B

    1B

    2C

    1C

    2a

    1a

    2b

    1b

    2c

    1c

    1L

    2L

    3L

    1A

    Fig. 27 Delta-Star connection of three-phase, three-legged core-type transformer

    6.2 Phase groupings

    The voltage induced in a primary phase winding is in phase with its corresponding

    secondary phase winding. However, the phase angles of the primary and secondary line

    voltages may differ depending on the type of winding connection. Three-phase

    transformers are given symbol which indicates the type of connection used for the high-

    voltage and the low-voltage winding and the phase displacement between the high-

    voltage line phasor and its corresponding low-voltage line phasor. The symbol is in the

    form Xxn where X (the capital letter) and x (the small letter) indicate the type of

  • 35

    connection for the high-voltage and low-voltage windings respectively and n is a clock

    hour number which indicates the phase displacement. In this method of indicating the

    phase shift, the high-voltage line phasor is represented by the minute hand of a clock

    always set at 12 (or the zero hour) and the corresponding low-voltage line phasor by the

    hour hand. Thus when n = 11 it means the clock reads 11 Oclock and the low-voltage line phasor leads by 30

    o. The groups into which three-phase transformers are classified

    are as follows:

    Group Phase displacement Winding connections

    1 zero Yyo Ddo Dzo

    2 180o Yy6 Dd6 Dz6

    3 30o lag Dy1 Yd1 Yz1

    4 30o lead Dy11 Yd11 Yz11

    6.3 Three-phase transformer connections More common transformer connections are

    (a) Delta-Delta connection (Fig 28). : This connection is economical for large low

    voltage transformer. This connection is not often used because there is no neutral point

    and a four-wire supply cannot be given. It is used in a 3-phase transformer bank but

    rarely in 3-phase transformer unit. It is possible to use this arrangement to provide 3-

    phase power with one transformer removed. This connection, known as open-delta or

    vee connection, can supply up to 57.7 % of the load capacity of the delta-delta

    connection.

    1L

    2L

    3L

    LV phV

    phI

    LI

    1A 2A

    1B

    2B1C

    2C

    2L

    1L

    3L

    1a 2a

    1b

    2b1c

    2c

    phL

    phL

    II

    VV

    3

    Fig. 28 Delta-delta connection

    (b) Delta-Star (Fig. 29): It is commonly used to step up alternator voltage to

    transmission line voltage. Another common application is in distribution service where

    as a step-down transformer, the windings are not the most economical. The secondary

    star point can be earthed and a four-wire supply given.

    (c) Star-Delta: There is no secondary neutral and four-wire supplies cannot be given.

    The main use is as a step-down transformer at the load end of transmission line.

  • 36

    2A

    1B

    2B1C

    2C

    1A

    1L

    3L

    2L

    2c

    1c

    1b

    2b

    1a 2a

    phV

    phI

    LI 3L

    1L

    2L

    LV

    3

    Lph

    VV Lph II

    Fig. 29 Delta-star connection

    (d) Star-Star: This is economical for high-voltage transformer. However, the primary

    and secondary phase voltages contain pronounced third harmonic voltages, which cause

    the neutral point to oscillate at three times the line frequency. The effect of this

    oscillating neutral is to cause fluctuation in the line to star-point voltage. Also if the

    secondary load is unbalanced, the neutral point will be displaced and the line-to-neutral

    voltages will become unequal. To stabilize the neutral, the neutral of the primary and the

    neutral of the source are connected together usually by way of ground. Another way is to

    provide a third delta-connected winding called tertiary winding. Although it can be used

    to supply additional power, the tertiary winding generally has no external connection

    Example 18

    Three single-phase step-up transformers rated 40MVA, 13.2 kV / 80 kV are connected in

    delta-star on a 13.2 kV transmission line. If they feed a 90MVA load, calculate the

    following:

    (a) the secondary line voltage

    (b) the currents in the transformer windings

    (c) the incoming and outgoing transmission line currents.

    Assume transformers are ideal.

    Solution

    2.13

    801)(

    1

    2

    aV

    Va

    ph

    ph

    voltage)lineion(transmiss2.13But 1 kVVph

    kVVph 80Therefore

    kV138380sidesecondary on the voltageline theand

  • 37

    2phI

    2phV

    1phV

    1phI

    kV2.13

    MVA b 303

    90formereach transby carried load The)(

    AkV

    MVAI ph1 2272

    2.13

    30ndingprimary wi in theCurrent

    AkV

    MVAI ph2 375

    80

    30windingsecondary in theCurrent

    AIc ph 3932322723 line incominginCurrent)( 1

    AII Lph 375line outgoingin Current 2

    Example 19

    Three single-phase transformers have their primaries joined in delta to a 6600 V, three-

    phase, three-wire supply. Their secondaries are connected to give a three-phase, four-wire

    output at 415 V across lines. The total load on the transformers is a balanced load of 150

    kW at 0.8 pf lag. If the voltage per turn on the primaries is 4, find

    (a) the number of turns on the primary winding and the secondary winding

    (b) the currents and voltages in all windings and lines, including the neutral wire on the

    secondary side

    (c) kVA load on each transformer

    Assume transformers are ideal

    Solution

    turnsturnvolt

    Va

    ph1650

    4

    6600phaseperturnsPrimary)(

    1

    turnsturnvolt

    Vph60

    43

    415phaseperturnsSecondary

    2

  • 38

    kV6.61phV

    1phI

    1LI2LI

    V415

    Load2phV

    kW150

    laggingpf8.0

    AV

    PowerIIb

    L

    phL 2618.04153

    10150

    cos3Secondary)(

    3

    22

    balanced is load because0 AI N

    AN

    INI

    ph

    ph 5.91650

    26160

    1

    22

    1

    AIL 4.1635.9 .

    Example 20

    A three-phase 415 V load takes a line current of 800 A from a 3300 / 415 V delta/star

    transformer. The 3300 V system is supplied from an 11000/3300 star/star transformer.

    Draw the circuit diagram and assuming no losses, find both line and phase values of

    voltages and currents in each part of the circuit. What will be the turns ratios of both

    transformers?

    Solution

    110001 V

    1phV 1phI2phI 2ph

    V

    32 VV

    32 II

    3phI 3phV4phI

    4phV

    AI 8004

    V

    V

    415

    4

    1IArTransformeBrTransforme

    Solution

    Voltages:

    VV

    VVV ph 2403

    415

    3;415 444

    VVVVV ph 3300;3300 333

    VV

    VVVV ph 19053

    3300

    3;3300 2232

  • 39

    VV

    VV ph 63503

    11000

    3;11000 111

    Turn ratios:

    75.13240

    3300

    4

    3

    ph

    ph

    V

    VArTransforme

    33.31905

    6350

    2

    1

    ph

    ph

    V

    VBrTransforme

    Currents:

    AIIAI ph 800;800 444

    AAratioturns

    II

    ph

    ph 2.5875.13

    80043

    AIII ph 8.1002.5833 332

    AII ph 8.10022

    ABratioturns

    II

    ph

    ph 2.3033.3

    8.10021

    AII ph 2.3011

    Check:

    kVAVAIVkVAInput 5755750002.301100033 11

    kVAVAIVkVAOutput 57557500080041533 44

    6.4 Parallel operation of three-phase transformers (Fig. 30)

    Three-phase transformers operating in parallel should have

    (a) the same line voltage ratios

    (b) the same per-unit impedances, i.e., they are equal in magnitude and in phase

    (c) the same phase displacement between primary and secondary line voltages

    (d) the same phase sequence

    The last two conditions which are absolutely essential ensure that the secondary line

    voltages of the transformers are in phase. When these conditions are not fulfilled a

    potential difference appears across the paralleling switches S1 and S2.

    From the view point of phase sequence and phase displacement, three-phase transformers

    which can operate in parallel are:

  • 40

    (a) transformers of the same group. This case the terminals with the same letter must be

    connected to the same line as shown in Fig. 30.

    (b) transformers having -30o phase displacement (Group 3 transformers) and those having

    +30o phase displacement (group 4 transformers). In this case two of the high voltage

    connections and the corresponding low voltage connections are interchanged as shown in

    Fig. 31.

    Faulty internal connections in the transformer tank can cause the phase sequence of a

    transformer to be reversed. Voltage across paralleling switches should therefore be

    monitored before the switches are closed.

    7. Cooling methods Cooling of transformer windings and core is provided to prevent rapid deterioration of

    the insulating materials. There are several methods of transformer cooling. Each method

    is described by a standard designation (or nomenclature) consisting of letter symbols.

    They are

    (a) Letters for medium: air A, gas G, synthetic oil L, mineral oil O, solid insulation S,

    water W

    (b) Letters for circulation: natural N, forced F

    Up to four letter symbols are used for each method for which the transformer is assigned

    a rating: some big transformers are designed to have a variable rating, depending on the

    method of cooling used. The order of the symbols is

    S2

    S1

    Transformer 2

    A2 a2

    B2 b2

    C2 c2

    Transformer 1

    A2 a2

    B2 b2

    C2 c2

    C B A a b c

    Fig. 30 Parallel operation of 3-phase transformers

  • 41

    (i) the medium and

    (ii) the circulation of the coolant in contact with the windings; and

    (iii) the medium and

    (iv) the circulation of the coolant in an external heat exchanger system.

    Common methods of cooling transformers are

    (a) Air Cooling (Dry type transformers)

    (i) AN: the ambient air as coolant and natural circulation by convection. The metallic

    housing is fitted with ventilating louvers. Ratings: up to 50 kVA (low-power

    transformers). Using high-temperature insulating materials (glass and silicone resins)

    make ratings up to 1.5 MVA possible. The low-power transformers are used inside

    buildings where the air is clean and high-power ones are for special conditions such as

    those in mines.

    (ii) AF: Forced air circulation is used to raise transformer loadings

    (b) Oil-immersed, Oil cooling: Oil is a much better insulator than air. Consequently, it is

    invariably used on high-voltage transformers

    (i) ONAN: natural oil circulation and natural air flow over the tank. It is very common

    for transformers rated up to 5 MVA. With radiators, it is possible to build units up to 40

    MVA. (Note that limit of output is determined by tank size and cost).

    (ii) ONAF: Cooling fans blow air over the radiators to enable a much bigger output from

    a transformer of a given size. With this method of cooling ratings up to about 75 MVA

    can be built.

    S2

    S1

    Transformer 2

    A2 a2

    B2 b2

    C2 c2

    Transformer 1

    A2 a2

    B2 b2

    C2 c2

    C B A a b c

    Fig. 31 Parallel operation of group 3 & 4 transformers

  • 42

    (iii) OFAF: Pumps are used to circulate the oil and cooling fans to blow air over

    radiators. This is the usual method for transformers of 30 MVA and upward. Both OFAF

    and ONAN may be used on a unit with ONAN up to 0.5 p.u. rating. Change over is

    initiated automatically by temperature-sensing elements. Three-phase type OFAF step-up

    transformer rated 1300 MVA installed at a nuclear power generating station is one of the

    largest units ever built.

    (c) Oil-immersed, Water cooling

    (i) ONWF: Copper cooling coils are mounted in the tank above the level of the

    transformer core, but below the oil surface.

    (ii) OFWF: Oil is circulated by pump from the top of the transformer tank to an external

    oil/water heat exchanger. Oil returns when cold to the bottom of the tank. Its advantages

    over ONWF include

    -The transformer is smaller and the tank does not have to contain the cooling coils.

    -Leakage of water into oil is improbable if oil pressure is greater than that of water

    This method is used for large installations. It is commonly used in generating stations,

    particularly hydro stations where ample supply of water is available.

    8.0 Tap-changing Transformers Most power transformers have tappings on coils brought out to terminals so that the

    number of turns on one winding can be changed. The turns ratios are changed in order

    (a) to maintain the secondary voltage at their rated value under the varying conditions of

    load and power factor. The secondary terminal voltage may vary with changes in load

    over an undesirably large range, because of changes in the impedance drop in the

    transmission lines and transformers

    (b) to control the flow of reactive power between two interconnected power systems or

    between component parts of the same system, at the same time permitting the voltages at

    specified points to be maintained at desired values.

    Tappings on power transformers permit voltage adjustment within %5 . Low- and medium-power transformers usually have three taps per phase: +5%, 0, and -5%

    variations in the turns ratio. Higher power ratings usually have five: +5%, +2.5%, 0, -

    2.5% and -5% variations in the turns ratio. The principal tapping 0 is that to which the rating of the winding is related. A positive tapping includes more, and a negative less

    turns than those of the principal tapping.

    Tappings are usually fitted on the higher voltage winding to obtain tappings within fine

    limits. Consider say, 11kV / 433 V, 600 kVA delta-star distribution transformer having

    volts / turn = 10. On the low-voltage side, 25310433 N . Adjustment can then be

    in steps of 4%. If 5 % and 10 % are required, we shall use 4 % and 8 % or 12 %.

    On the high-voltage side 11001011000 N and it is possible to make adjustment in

    steps of 0.09 %.

  • 43

    8.1 Changing the taps of transformers

    Tap-changing may be either on-load or off-load.tap-changing:

    (a) Off-load tap changing: the changes are made when the transformer is disconnected

    from the primary circuit. The most common off-load tap changing transformer has

    tappings inside the tank and connected to an internal switch which is operated by an

    external switch handle (usually by rotary movement of a handwheel). A three-phase star

    connected winding with taps made at the neutral is shown in Fig. 32.

    Fig. 32 Three-phase star connected winding with taps at the neutral point

    Off-load tap changing is simple and inexpensive and it is commonly used with

    distribution transformers where occasional adjustments are required..

    (b)On-load tap changing: Daily and short-time adjustment is generally by means of on-

    load tap-changing gear. Tap changing is done without breaking the circuit. Momentary

    connection must be made simultaneously to two adjacent taps during the transition, and

    the short-circuit current between them must be limited by some form of impedance

    known as transition impedance. Centre-tapped iron-core inductors (the reactor method) or

    resistors (the resistor method) are used for this purpose.

    (i) Reactor method: This method has now almost entirely been superseded by the resistor

    method. It is manufactured and used only in the USA.

    (ii) Resistor method: In modern designs the transition impedance is almost invariably

    obtained by means of a pair of resistors. An arrangement of such a tap changer for one

    phase is shown in Fig. 33. In this figure, the diverter switch and the even tap selector are

    shown in the position when the T2 tap is brought in circuit.

    To move to the next tap, T3, the odd tap selector should first be moved to that tap (see the

    dashed lines in Fig. 33), and the diverter switch may then be rotated clockwise. The

    ensuing sequence of events is as follows:

  • 44

    selector tapodd

    1TS1T

    3T

    5T

    7T

    2T

    4T

    6T

    8T

    2TS

    selector even tap

    1R 2R

    1

    2 3

    4

    I

    I

    Fig. 33.a. Resistor tap changer

    - contacts 3 and 4 break, contacts 1 and 4 make, Fig. 33.b

    1R 2R

    1

    2 3

    4

    I

    i-I2

    1iI

    2

    1i

    Fig 33.b

  • 45

    - contacts 1 and 4 break, and contacts 1 and 2 make, Fig. 33.c

    1R 2R

    1

    2 3

    4

    I

    Fig 33.c

    The tap selectors may be moved from tap to tap only when their circuits are de-energized.

    The resistors are short-time rated and it is essential to minimize their time of duty. For the

    same reason, means must be adopted to ensure that it cannot be inadvertently left in the

    bridging position.

    On-load tap changer control gear can vary from simple push-button initiation to a

    complex automatic control of as many as four transformers in parallel.

    9.0 Autotransformers

    An autotransformer has a single tapped winding which serves both primary and

    secondary functions as shown in Fig. 34. The circuit diagrams are shown in Fig. 35.

    1V

    1I A

    B

    1N

    2N

    2I C

    B

    2V Load

    1V 1N

    A

    B

    2N

    2I

    2V Load

    ormerautotransfdown -Step 34.a Fig. ormerautotransf up-Step 34.b Fig.

    C

    B

    1I

    9.1 Autotransformer equations If we neglect losses, leakage flux and magnetizing current then

    2

    1

    1

    2

    1

    2

    I

    I

    V

    V

    N

    Nn

    9.2 Advantages and disadvantages of autotransformer over two-winding

    transformer

    The main advantage gained in the use of autotransformer is the saving of copper. For a

    two-winding transformer and an autotransformer which can perform the same duty (they

  • 46

    1V

    1I

    S

    C

    2I C

    B

    2VLoad

    1V

    A

    B

    1I

    S

    C

    2VLoad

    C

    BB

    ormerautotransfofdiagramsCircuit35 Fig.

    dingcommon win C winding;series S

    should have the same voltage per turn and therefore the same flux. We can also assume

    the same mean length per turn)

    H

    L

    V

    V

    rtransforme winding-two in copper of Volume

    ormerautotransf in copper of Volume1

    Or

    ormerautotransf an using

    by effected copper of saving rtransforme windingtwo the in copper of Volume

    V

    V

    H

    L

    sidevoltage high on voltageV

    sidevoltage low the onvoltageV

    Where

    H

    L

    In practice, voltage ratios HL VV less than about 31 show little economic benefit over

    two-winding transformer because of other factors such as cost of insulation.

    The main disadvantage is that the primary and secondary circuits are not isolated from

    each other.

    Example 21

    An autotransformer is required to step up a voltage from 220 to 250 V. The total number

    of turns is 2000. Determine (a) the position of the tapping point (b) the approximate

    value of the current in each part of the winding when the output is 10 kVA and (c) the

    economy in copper over the two winding transformer having the same peak flux and the

    same mean length per turn.

  • 47

    Solution:

    1V

    1I

    2V

    2I

    1N

    2N

    17602000250

    220

    250

    220

    250

    220)( 21

    2

    1

    2

    1 NNorN

    N

    V

    Va

    Position is 240 turns from one end.

    AIIVb 40250

    10101010)(

    3

    23

    22

    AIIV 45.45220

    10101010

    3

    1

    3

    11

    Therefore current in series winding is 40 A and current in common

    winding A45.54045.45

    %8888.0250

    220)( orpu

    V

    VcopperinSavingc

    H

    L of copper used in the two-

    winding transformer

    9.3 Two-winding transformer connected as an autotransformer

    A two-winding transformer can be changed into an autotransformer by connecting the

    primary and secondary windings in series. The following rules apply whenever a two-

    winding transformer is connected as autotransformer:

    (a) the current in any winding should not exceed its current rating

    (b) the voltage across any winding should not exceed its voltage rating

    (c) rated current in one winding gives rise to rated current in the other

    (d) rated voltage across one winding gives rise to rated voltage across the other

    (e) if current in one winding flows from say A2 to A1, then current in the other winding

    must flow from a1 to a2 and vice versa

    (f) the voltages add when terminals of opposite polarity (A1 and a2 or A2 and a1) are

    connected together by a jumper. The voltages subtract when A1 and a1 (or A2 and a2) are

    connected together.

  • 48

    Example 22

    A two-winding single-phase transformer rated 15 kVA, 600 V / 120 V, 60 Hz. We wish

    to reconnect it as an autotransformer in three different ways to obtain three different

    voltage ratios:

    (a) 600 V primary to 480 V secondary (b) 600 V primary to 720 V secondary (c) 120 V primary to 480 V secondary Calculate the maximum load the transformer can carry in each case.

    Solution

    (a) The secondary voltage 120 V must be subtracted from the primary voltage to obtain

    the 480 V.

    %8888.0250

    220)( orpu

    V

    VcopperinSavingc

    H

    L

    (b) The secondary voltage 120 V must be added to the 600 V to obtain 720 V

    %8888.0250

    220)( orpu

    V

    VcopperinSavingc

    H

    L

  • 49

    (c) The 120 V becomes the primary of the autotransformer and the 120 V is subtracted

    from the 600 V to obtain its secondary

    %8888.0250

    220)( orpu

    V

    VcopperinSavingc

    H

    L

    9.4 Applications of autotransformers

    They are mainly used for

    (a) variac

    (b) interconnecting power systems that are operating at roughly the same voltage (eg. 132

    kV, 275 kV, 400 kV) and

    (c) starting squirrel-cage induction motors.

    10.0 Instrument transformers

    They are used in ac circuits to serve these purposes:

    (a) to make possible the measurement of high voltages with low-voltage instruments or

    large currents with low current ammeters

    (b) to insulate high voltage circuits being monitored from measuring circuit in order to

    protect the measuring apparatus and operator

    (c) to energize relays for the operation of protective and automatic control devices

    The load on the secondary of an instrument transformer is called its burden and is

    expressed in volt-amperes (VA). There are two types of instrument transformers: the

    voltage (or potential) transformer and the current transformer

    10.1 The voltage or potential transformers (VTs or PTs) The construction is similar to a power transformer. The primary is connected directly to

    the power circuit either between two phases or between a phase and ground and the

    secondary is connected to instruments and coils of relays. Sufficient insulation is

    provided between the primary and the secondary to withstand the full line voltage as well

    as the very high impulse voltage. Voltage transformers are designed to step down the

    primary voltage to a nominal or rated voltage of 110 V so that standard instruments and

    relays can be used. They introduce errors of two kinds into measurement being made: the

    ratio errors (the ratio between input and output voltages is not constant under all

    conditions of load) and the phase angle errors (the phase shift between input and output

    voltages is not zero). These errors are due to the exciting current and the equivalent

  • 50

    series impedance of the transformer and they are kept low by using high quality iron

    (high permeability and low loss) and operating it at low flux densities so that the exciting

    current is very small. The resistance and reactance of the windings are also made very

    low.

    Fig. 36 shows the circuit for a potential transformer. One terminal of the secondary

    winding is always earthed. The windings though insulated from each other, are

    connected invisibly together by distributed capacitance between them. By earthing one

    of the secondary terminals, the highest voltage between the secondary lines and earth can

    never rise above that of the secondary voltage.

    V

    V1500

    V110

    PT

    circuit ac H.V.

    Fig. 36 Potential transformer installed on H.V. circuit

    10.2 Current transformers (CTs)

    Their primary consists of small number of turns connected in series with the power

    circuit load. The secondary consists of a larger number of turns and it is connected to

    ammeter, current coils of other instruments or current coils of relays. Current

    transformers have the ratio of primary to secondary current approximately constant. The

    nominal or rated secondary currents are usually 5 A or 1 A, irrespective of the primary

    current rating. The transformer ratio is usually stated to include the secondary current

    rating. Current transformers also introduce two errors in measurement: the ratio error

    (the ratio between primary and secondary currents is not constant) and phase angle error

    (the phase angle between the primary and secondary currents is not zero. The basic cause

    of ratio and phase angle errors is the exciting current. To keep the exciting current small,

    a high quality iron operating at very low flux densities is used as in PTs. In Cts the

    secondary leakage impedance and impedances of the secondary leads and instruments

    should also be very low; for any increase in these impedances increases the core flux and

    therefore the exciting current. The tansformer is connected in the power circuit as shown

    in Fig. 37 As in the case of PT (and for the same reasons) one of the secondary terminals

    is always earthed

    Current transformer secondary circuit must not be opened while current is flowing in the

    primary. Without opposing ampere-turns the line current, which may be 100 to 200 times

    the normal exciting current, becomes the exciting current. The iron core becomes.

  • 51

    A

    AorA 51

    Load

    currentLoad

    supplyac

    AorA 51ammeter

    CT

    Fig. 37 Current transformer intalled in H.V. circuit

    saturated and very high voltage spikes (several thousand volts) are induced across the

    open-circuited secondary. These voltages are dangerous to life and to the transformer

    insulation. The core when it becomes saturated can also cause excessive heating of the

    core and windings. Therefore when it is desired to remove a load from the secondary

    circuit, the secondary winding must first be short circuited.

    When the line current exceeds 100 A we can sometimes use a toroidal or bar-primary

    (N1=1) transformer shown in Fig. 38. It consists of a laminated ring-shaped core which

    carries the secondary winding. The primary is composed of a single conductor that

    simply passes through the centre of the ring as shown in the figure. Toroidal CTs are

    simple and inexpensive and are widely used in HV and MV indoor installations.

    AAI 32

    AI 6001

    11

    N

    primaryBar

    Fig. 38 Toroidal or bar-primary transformer having a ratio 1000A / 5A connected to

    measure a current in a line

  • 52

    Current transformers are also commonly used for the measurements of large currents

    even when the circuit voltage is not dangerously high. This avoids bringing heavy leads

    to the instrument panels. Whereas instrument CTs have to remain accurate up to 12 %

    rated current, protection CTs must retain proportionality up to 20 times normal full load

    Example 23

    A potential transformer rated 14400 V / 115 V and a current transformer rated 75 A / 5 A

    are used to measure the voltage and current in a transmission line. If the voltmeter

    indicates 111 V and the ammeter reads 3 A, calculate the voltage and current in the line.

    Solution

    VV is line the on voltage The 13900115

    14400111

    AI is line the in currentThe 455

    753

    Example 24

    The toroidal current transformer of Fig. 38 has a ratio of 1000 A / 5 A. The line

    conductor carries a current of 600 A.

    (a)Calculate the voltage across the secondary winding if the ammeter has an impedance

    of 0.15 (b) Calculate the voltage drop the transformer produces on the line conductor

    (c) If the primary conductor is looped four times through the toroidal opening, calculate

    the new current ratio

    Solution

    AI secondarythe in Current (a) 36001000

    52

    V burden the across drop Voltage 45.015.03

    mVVI

    IVor

    I

    I

    N

    N

    V

    V b 25.245.0

    1000

    5)( 2

    1

    21

    1

    2

    2

    1

    2

    1

    41)( 1122 xIxINIc

    AIthatimpliesThis 2501

    AAratiocurrentnewtheTherefore 5250

  • 53

    Exercises One

    (1) A single-phase transformer has a primary winding with 1,500 turns a nd a secondary

    winding with 80 turns. If the primary winding is connected to a 2300-V, 50-Hz supply,

    calculate (a) the secondary voltage (b) the maximum value of the core flux. Neglect the

    primary impedance

    (2) A single-phase 2,300/230-V, 500-kVA, 50-Hz transformer is tested with the

    secondary open-circuited. The following test results were obtained: V1 = 2,300 V, Io =

    10.5 A, and Po = 2,300 W. Calculate (a) the power factor (b) the core-loss current Ip (c)

    the magnetizing current Im.

    (3) A 150-kVA, 2,400/240-V, 50-Hz single-phase transformer has the following

    resistances and reactances: R1 =0.225 , Xl1 = 0.525 , R2 = 0.00220 and Xl2 = 0.0445 . Calculate the transformer equivalent values (a) referred to the primary (b) referred to the secondary.

    (4) A 150-kVA, 2,400/240-V, 50-Hz single-phase transformer has the following

    resistances and reactances: R1 =0.225 Xl1 = 0.525 , R2 = 0.00220 , Xl2 = 0.00445 , Rm = 10 k and Xm = 1.5 k . The transformer is supplying full-rated load at 0.85 lagging power factor and rated secondary terminal voltage. Calculate (a) I2 (b) Ip (c) Im

    (d) Io (e) I1 (f) V1. Use the exact equivalent circuit referred to the primary side.

    (5) The results of open- and short-circuit tests carried out on a 230/115-V, 60-Hz single phase transformer are

    Cal