1. Typical Channeled Adhesive
2. Typical Application
3. Typical Application over CMU
4. Typical Application over Brick
5. Typical Aesthetic Reveal
6. Typical Corner Mesh Application with Flexguard 4, Intermediate 6 or 12
7. Typical Pipe Penetration
8. Typical Light Fixture
9. Typical Expansion Joint
10. Typical Expansion Joint at Change in Substrate
11. Typical Expansion Joint at Floorline
12. Typical Drainage at Floorline
13. Typical Abutment to Brick with Drainage at Floorline
14. Typical Abutment to Brick
15. Typical Termination at Foundation
16. Typical Termination at Foundation (Flush)
17. Typical Window Head (Flush)
18. Typical Window Head with Weep Tubes (Flush)
19. Typical Window Head with Diverter Track (Flush)
20. Typical Window Head with Sealant End Dam
21. Typical Window Jamb (Flush)
22. Typical Window Sill (Flush)
23. Typical Window Head (Recessed)
24. Typical Window Jamb (Recessed)
25. Typical Window Sill (Recessed)
26. Typical Flanged Window Head (Recessed)
27. Typical Flanged Window Jamb (Recessed)
28. Typical Flanged Window Sill (Recessed)
29. Typical Coping
30. Typical Parapet Cap
31. Typical Kick-Out Flashing
32. Typical Roof Edge Flashing
33. Typical Section at Fascia/Soffit
34. Typical Core Mounted Railing Attachment
35. Typical Railing Attachment
36. Typical Sign Attachment
Continuously Insulated Wall System
Channeled Adhesive CI Design Details
TABLE OF CONTENTS
Notes:
Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
•
The details within represent BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. They are presented in good faith by BASF Wall Systems. The details are subject to change without notice. BASF Wall Systems accepts no liability for the end use of the details. For conditions not shown, consult BASF Wall Systems for review of specific detail.
•
Install BASF materials in accordance with current installation instructions.•
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-01 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• Apply mixed base coat to entire surface of insulation board using a stainless steel trowel with 1/2” x 1/2” (13 mm x 13 mm) notches spaced 2” (50 mm) apart. Ribbons of adhesive must be applied parallel to the 2’ (610 mm) dimension of the EPS insulation board to ensure they are vertical when the EPS insulation board is applied to the substrate.
• Set EPS insulation board into place and apply pressure over entire surface of board to ensure positive uniform contact and high initial grab. Do not slide board into place.
TYPICAL CHANNELED ADHESIVE
CA-01 Typical Channeled Adhesive
APPROVED EPS INSULATION BOARD
VERTICAL NOTCHES OF SENERGY ADHESIVE / BASE COAT APPLIED TO APPROVED EPS INSULATION BOARD
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-02 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination.
TYPICAL APPLICATION
CA-02 Typical Application
FRAMING*
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-03 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination.
TYPICAL APPLICATION OVER CMU
CA-03 Typical Application Over CMU
CONCRETE MASONRY UNITS*
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination.
CAD-04 180503
TYPICAL APPLICATION OVER BRICK
CA-04 Typical Application Over Brick
BRICK*
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-05 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• Maintain a minimum 3/4” (19 mm) thick EPS insulation board behind all reveals and aesthetic grooves.
• Reinforcing mesh shall be continuous and care shall be taken to ensure reinforcing mesh is not cut during base coat application.
• Horizontal reveals shall provide for outward positive drainage.
• Reveals must not occur at the abutment of two pieces of EPS insulation board.
TYPICAL AESTHETIC REVEAL
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
AESTHETIC REVEAL
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
(* NOTE: BY OTHERS)
Channeled Adhesive CI Design
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• Ensure FLEXGUARD 4, INTERMEDIATE 6 or 12 reinforcing mesh is lapped a minimum of 8” (203 mm) around corners.
CAD-06 180503
TYPICAL CORNER MESH APPLICATIONWITH FLEXGUARD 4, INTERMEDIATE 6 OR 12
CA-06 Typical Corner Mesh Application with Flexguard 4,Intermediate 6 or 12
FRAMING*
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERGY CORNER MESH EMBEDDED IN SENERGY BASE COAT
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-07 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced basecoat.
• Ensure all penetrations into the system are properly sealed.
• Provide continuous air seal around perimeter of penetration prior to EPS insulation board application.
• Do not apply finish to areas that will receive sealant.
TYPICAL PIPE PENETRATION
CA-07 Typical Pipe Penetration
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
SEALANT AT PERIMETER OF PENETRATION*
PIPE*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-08 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure all penetrations into the system are properly sealed.
TYPICAL LIGHT FIXTURE
CA-08 Typical Light Fixture
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
SET FLANGE IN SEALANT*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
LIGHT HOUSING*
LIGHT FIXTURE*
SEALANT*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-09 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Do not apply finish to areas that will receive sealant.
• Ensure drainage plane is continuous and unobstructed at expansion joint.
• Install expansion joints in the system at all changes in substrate, through existing expansion joints, floor lines in multi-level wood frame construction, and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.
TYPICAL EXPANSION JOINT
FRAMING*
ACCEPTABLE SHEATHING*
BASF WS FLASH WITH FLASHING PRIMER
APPROVED EPS INSULATION BOARD
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
COLOR COAT
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERSHIELD-R/-RS/-VB
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-10 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Do not apply finish to areas that will receive sealant.
• Ensure drainage plane is continuous and unobstructed at expansion joint.
• Install expansion joints in the system at all changes in substrate, through existing expansion joints, floor lines in multilevel wood frame construction, and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.
TYPICAL EXPANSION JOINT AT CHANGE IN SUBSTRATE
CA-10 Typical Expansion Joint at Change in Substrate
ACCEPTABLE SHEATHING*
ACCEPTABLE SUBSTRATE*
BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
COLOR COAT
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
APPROVED EPS INSULATION BOARD
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-11 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Do not apply finish to areas that will receive sealant.
• Install expansion joints in the system at all changes in substrate, through existing expansion joints, floor lines in multilevel wood frame construction, and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.
• It is recommended that a means for drainage is provided at every third floor. (See TYPICAL DRAINAGE AT FLOORLINE detail).
TYPICAL EXPANSION JOINT AT FLOORLINE
FLOOR SLAB*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
COLOR COAT
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
SENERGY FAUX BRICK
BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-12 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Do not apply finish to areas that will receive sealant.
• Install expansion joints in the system at all changes in substrate, through existing expansion joints, floor lines in multilevel wood frame construction, and where movement is anticipated. It is the sole responsibility of the design professional to determine specific expansion joint location, placement and design.
• It is recommended that a means for drainage is provided at every third floor.
TYPICAL DRAINAGE AT FLOORLINE
FLOOR SLAB*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
BASF METALLIC EFFECTS
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
BASF WS FLASH WITH FLASHING PRIMER
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
COLOR COAT
SENERSHIELD-R/-RS/-VB
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
(* NOTE: BY OTHERS)
Channeled Adhesive CI Design
CAD-13 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at brick.
• Brick ties not shown for clarity.
• Brick must be installed per local code requirements.
TYPICAL ABUTMENT TO BRICKWITH DRAINAGE AT FLOORLINE
CA-13 Typical EIFS Abutment to Brick with Drainage at Floorline
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
BRICK*
BASF WS FLASH W/ FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-14 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a continuous drainage plane is maintained at system abutment to brick.
• Brick ties not shown for clarity.
• Brick must be installed per local code requirements.
TYPICAL ABUTMENT TO BRICK
CA-15 Typical EIFS Abutment to Brick
FRAMING*
ACCEPTABLE SHEATHING*
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
BASF MAXFLASH OR BASF SHEATHING FABRIC OR BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALANT*
BRICK*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-15 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at foundation.
• Terminate system a minimum of 8” (203 mm) above grade.
• Extend system a minimum of 2” (50 mm) and a maximum of 12” (305 mm) at the sole plate foundation transition.
TYPICAL TERMINATION AT THE FOUNDATION
CA-14 Typical Termination at Foundation
FRAMING*
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
SEALANT*
FOUNDATION*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-16 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at foundation.
• Place weep tubes a minimum of 24” (610 mm) on center.
• Do not apply finish to areas that will receive sealant.
TYPICAL TERMINATION AT FOUNDATION (FLUSH)CA-16 Typical Termination at Foundation (Flush)
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BASF WS FLASH WITH FLASHING PRIMER
BACKER ROD AND SEALANT (WIDTH PER DESIGN)*
WEEP TUBE*
FOUNDATION*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-17 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at window head.
• Provide end-dams at flashing terminations.
• Provide continuous air seal around interior perimeter of window. Contact window manufacturer for specific installation instructions.
TYPICAL WINDOW HEAD (FLUSH)CA-17 Typical Window Head (Flush)
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
WINDOW*
SEALANT*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-18 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at window head.
• Provide end-dams at flashing terminations.
• Provide continuous air seal around interior perimeter of window. Contact window manufacturer for specific installation instructions.
• Do not apply finish to areas that will receive sealant.
TYPICAL WINDOW HEAD (FLUSH) WITH WEEP TUBES
CA-18 Typical Window Head (Flush) with Weep Tubes
FRAMING*
ACCEPTABLE SHEATHING*
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALANT*
WEEP TUBES*
FLASHING*
SEALANT*
WINDOW*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-19 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Provide continuous air seal around interior perimeter of window. Contact window manufacturer for specific installation instructions.
• Ensure that the diverter flashing extends 6” (152 mm) beyond opening on either side of the opening to allow potential moisture to drain down the wall to the side of the opening. BASF MAXFLASH or SHEATHING FABRIC embedded in SENERSHIELD-R/-RS/-VB or WS FLASH must be extended over flange of flashing. Maintain a minimum of 3/4” (19 mm) EPS insulation thickness. Ensure the diverter track flashing is sloped to provide a means for drainage.
TYPICAL WINDOW HEAD (FLUSH) WITH DIVERTER TRACK
CA-19 Typical Window Head (Flush) with Diverter Track
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
DIVERTER TRACK*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALANT
WINDOW*
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-20 180503
TYPICAL WINDOW HEAD WITH SEALANT END DAM
CA-33 Window Head Flashing w/ Sealant End Dam
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
ACCEPTABLE SEALANT*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
FLASHING*
SEALANT*
WINDOW*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-21 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.
• Do not apply finish to areas that will receive sealant.
• Provide a back wrapped type joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).
• Provide continuous air seal around interior perimeter of interior window. Contact window manufacturer for specific installation instructions.
TYPICAL WINDOW JAMB (FLUSH)
CA-21 Typical Window Jamb (Flush)
FRAMING*
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
COLOR COAT
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BACKER ROD*
SEALANT*
WINDOW*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-22 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.
• Do not apply finish to areas that will receive sealant.
• Provide a back wrapped type joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).
• Provide continuous air seal around interior perimeter of interior window. Contact window manufacturer for specific installation instructions.
TYPICAL WINDOW SILL (FLUSH)
CA-22 Typical Window Sill (Flush)
WINDOW*
SEALANT*
COLOR COAT
BACKER ROD*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
ACCEPTABLE SHEATHING*
FRAMING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Do not apply finish to areas that will receive sealant.
• Ensure a means for drainage is provided at system termination at soffit/fascia transition.
• Provide a back wrapped type joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).
• Provide continuous air seal around interior perimeter of interior window. Contact window manufacturer for specific installation instructions.
CAD-23 180503
TYPICAL WINDOW HEAD (RECESSED)
CA-20 Typical Window Head Recessed
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALANT*
WINDOW*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-24 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.
• Do not apply finish to areas that will receive sealant.
• Provide a back wraptped type joint with backer rod and sealant at system terminations to dissimilar materials, ensuring that a water tight seal is achieved (width per design).
• Provide continuous air seal around interior perimeter of interior window. Contact window manufacturer for specific installation instructions.
TYPICAL WINDOW JAMB (RECESSED)
CA-23 Typical Window Jamb (Recessed)
FRAMING*
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
BACKER ROD AND SEALNT*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WINDOW*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure water-resistive barrier is properly applied into the rough openings in accordance with application guidelines and code requirements prior to EPS insulation board application.
• Ensure that metal pan flashing extends onto the system a minimum of 2” (50 mm) down the face and that end dams are provided.
• Provide continuous air seal around interior perimeter of interior window. Contact window manufacturer for specific installation instructions.
TYPICAL WINDOW SILL (RECESSED)
CAD-25 180503
CA-24 Typical Window Sill (Recessed)
WINDOW*
PAN FLASHING WITH END DAMS*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SEALANT*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
APPROVED EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
ACCEPTABLE SHEATHING*
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
TYPICAL FLANGED WINDOW HEAD
CAD-26 180503
CA-17A Typical Flanged Window Head
FRAMING*
ACCEPTABLE SHEATHING*
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
FLASHING*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
WINDOW*
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-27 180503
TYPICAL FLANGED WINDOW JAMB
TYPICAL FLANGED WINDOW JAMB
CA-21A Typical Flanged Window Jamb (Flush)
FRAMING*
ACCEPTABLE SHEATHING*
SENERSHIELD-R/-RS/-VB
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
BACKER ROD AND SEALANT
WINDOW*
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-28 180503
TYPICAL FLANGED WINDOW SILL
CA-22A Typical Flanged Window Sill
WINDOW*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
BACKER ROD AND SEALANT*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
APPROVED EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
FRAMING*
ACCEPTABLE SHEATHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-29 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure that metal coping/ flashing extends onto the system a minimum of 2” (50 mm) down the face.
TYPICAL COPING
METAL COPING*
ROOF SYSTEM*
CLEAT*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
SEALANT*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
APPROVED EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
ACCEPTABLE SHEATHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-30 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• Provide a minimum 6:12 slope for all horizontal surfaces. Senergy requires the use of a roofing system or metal cap flashing for sloped surfaces over 24” (610 mm).
• Additional layers of mesh reinforced base coat is recommended when sloped surfaces exceed 12” (305 mm).
• Ensure a means for drainage is provided at system termination.
• Terminate system a minimum of 8” (203 mm) above roof.
• Maintain a minimum 1” (25 mm) thick EPS insulation board.
TYPICAL PARAPET CAP
CA-26 Typical Parapet Cap
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
ACCEPTABLE SHEATHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
APPROVED EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
BOND BREAKER TAPE*
SEALANT*
TERMINATION BAR*
COUNTER FLASHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-31 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure a means for drainage is provided at system termination at roof.
• Terminate system a minimum of 2” (50 mm) above roof.
• Ensure step flashing is a minimum of 2” (50 mm) behind system.
• Kick-out flashing shall be a minimum of 4” (102 mm) in height.
• Do not apply finish to areas that will receive sealant.
TYPICAL KICK-OUT FLASHINGCA-27 Typical Kick-Out Flashing
ACCEPTABLE SUBSTRATE*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
SENERSHIELD-R/-RS/-VB
APPROVED EPS INSULATION BOARD
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
FLASHING*
BASF MAXFLASH OR BASF SHEATHING FABRIC EMBEDDED IN SENERSHIELD-R/-RS/-VB OR BASF WS FLASH WITH FLASHING PRIMER
STEP FLASHING*
ROOF SHINGLES*
BACKER ROD AND SEALANT*
KICK OUT FLASHING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-32 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure that metal coping/flashing extends onto the system a minimum of 2” (50 mm) down the face.
TYPICAL ROOF EDGE FLASHING
CA-28 Typical Roof Edge Flashing
ROOF SYSTEM*
ROOF EDGE FLASHING*
CLEAT*
SEALANT*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERSHIELD-R/-RS/-VB
ACCEPTABLE SHEATHING*
APPROVED EPS INSULATION BOARD
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-33 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with installation instructions and applicable code.
• Verify substrate is flat, free of fins or planar irregularities greater than 1/4” in 10”.
• Install wall system first followed by lamina application at soffit.
TYPICAL APPLICATION AT SOFFIT / FASCIACA-33 Fascia / Soffit
FRAMING*
EIFS OR OTHER CLADDING AS SPECIFIED*
SEALANT*
SOFFIT*
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
ACCEPTABLE SUBSTRATE*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-34 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure all penetrations into the system are properly sealed.
TYPICAL CORE MOUNTED RAILING ATTACHMENT
RAILING*
FILLET BEAD OF SEALANT AT PERIMETER OF BASE COVER*
RAILING BASE COVER SET IN SEALANT*
BACKER ROD AND SEALANT*
WRAP SENERGY BASE COAT AND SENERGY REINFORCING MESH
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
APPROVED EPS INSULATION BOARD
SENERSHIELD-R/-RS/-VB
ACCEPTABLE SUBSTRATE*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-35 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure all penetrations into the system are properly sealed.
TYPICAL RAILING ATTACHMENT
FRAMING*
ACCEPTABLE SUBSTRATE*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
SLEAVE SET IN SEALANT*
WOOD BLOCKING*
MECHANICAL FASTENER SET IN SEALANT*
RAILING*
Channeled Adhesive CI Design
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255] www.senergy.basf.com
* NOTE: BY OTHERS
This detail represents BASF Corporation - Wall Systems (hereinafter BASF Wall Systems) latest recommendations. It is presented in good faith by BASF Wall Systems. The detail is subject to change without notice. BASF Wall Systems accepts no liability for the end use of the detail. For conditions not shown, consult BASF Wall Systems for review of specific detail. For the most current version of this literature, please visit our website at www.senergy.basf.com.
CAD-36 180503
• Install BASF materials in accordance with current installation instructions.
• Unsatisfactory conditions shall be reported to the General Contractor and corrected before the application of BASF products.
• Verify all materials are installed in accordance with current installation instructions.
• All terminations must be fully encapsulated with mesh reinforced base coat.
• Ensure all penetrations into the system are properly sealed.
• Blocking or other structural support required for sign attachment.
TYPICAL SIGN ATTACHMENT
CA-36 Typical Sign Attachment
FRAMING*
ACCEPTABLE SUBSTRATE*
SENERSHIELD-R/-RS/-VB
SENERGY ADHESIVE / BASE COAT APPLIED TO EPS INSULATION BOARD
APPROVED EPS INSULATION BOARD
SENERGY LAMINA: SENERGY BASE COAT SENERGY REINFORCING MESH SENERGY FINISH COAT
SIGN*
SEALANT AT PERIMETER OF PENETRATION*
SLEAVE SET IN SEALANT*
WOOD BLOCKING*
MOUNTING BRACKET*
MECHANICAL FASTENER SET IN SEALANT*
WASHER*
WarrantyBASF warrants this product to be free from manufacturing defects and to meet the technical properties on the current Product Bulletin, if used as directed within shelf life. Satisfactory results depend not only on quality products but also upon many factors beyond our control. BASF MAKES NO OTHER WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO ITS PRODUCTS. The sole and exclusive remedy of Purchaser for any claim concerning this product, including but not limited to, claims alleging breach of warranty, negligence, strict liability or otherwise, is shipment to purchaser of product equal to the amount of product that fails to meet this warranty or refund of the original purchase price of product that fails to meet this warranty, at the sole option of BASF. In the absence of an extended warranty issued by BASF, any claims concerning this product must be received in writing within one (1) year from the date of shipment and any claims not presented within that period are waived by Purchaser. BASF WILL NOT BE RESPONSIBLE FOR ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL (INCLUDING LOST PROFITS) OR PUNITIVE DAMAGES OF ANY KIND. Purchaser must determine the suitability of the products for the intended use and assumes all risks and liabilities in connection therewith. This information and all further technical advice are based on BASF’s present knowledge and experience. However, BASF assumes no liability for providing such information and advice including the extent to which such information and advice may relate to existing third party intellectual property rights, especially patent rights, nor shall any legal relationship be created by or arise from the provision of such information and advice. BASF reserves the right to make any changes according to technological progress or further developments. The Purchaser of the Product(s) must test the product(s) for suitability for the intended application and purpose before proceeding with a full application of the product(s). Performance of the product described herein should be verified by testing and carried out by qualified experts.
BASF Corporation - Wall Systems | 3550 St Johns Bluff Rd South Jacksonville, Florida 32224 P: 800.221.9255 F: 904.996.6300 www.senergy.basf.com© 2018 BASF Corporation rev 180503
For the most current version of this literature, please visit our website at www.senergy.basf.com.