16
(Thin) (Ultrathin) Suspended Air-handling Unit

(Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

  • Upload
    buithuy

  • View
    220

  • Download
    0

Embed Size (px)

Citation preview

Page 1: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

(Thin)

(Ultrathin)Suspended Air-handling Unit

Page 2: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

Contents

Model Number NomenclatureAir Volume

Features

Standard Condition

Fresh Air Condition

Select the performance of heating coil (2R)

Dimension of DBFP(X)

DBF(X) Ultrathin UnitDBF(X) Performance Table

Dimension of DBFP(X)

Installation Precautions

1

24

5

6

7

11

12

13

Carrier ChinaHeadquartered in Farmington, Connecticut, USA, Carrier Corporation is the world's largest provider of heating, air conditioning and refrigeration solutions, with operations in more than 170 countries including China.

Ever since Dr. Willis Carrier, founder of Carrier Corporation, invented modern air conditioning in 1902, Carrier has stayed at the forefront of the air-conditioning industry for more than 100 years. Regarded as the leader and expert in air conditioning, Carrier has several thousand patents in the air-conditioning industry and eleven lead design centers worldwide, including one in China.

Carrier's products are manufactured at numerous facilities on six continents. The company has approximately 41,000 employees around the world. In 2008, Carrier's revenues were US$14.9 billion, leading the Heating, Ventilation, Air-conditioning and Refrigeration (HVACR) industry.

Carrier set up its first joint venture in Shanghai in 1987. Now Carrier China has more than 2,200 employees. Carrier products are distributed in China through a network of more than 40 sales and service offices.

Page 3: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

01

Model Number Nomenclature

DIGIT NO. 1-4PRODUCT SERIES DBFP: AIR HANDLING UNIT DFP: ULTRA THIN AIR HANDLING UNIT

DIGIT NO. 5COOLING COIL ROW X : HIGH COOLING CAPACITY (OMISSIBLE): RATED COOLING CAPACITY

DIGIT NO. 6AIR VOLUME(AIR VOLUME=FIGURE × 1000 m3/h ) 1 : 1000 m3/h 2 : 2000 m3/h

DIGIT NO. 7STATIC PRESSURE I :STRENGTHEN MOTOR (HIGH STATIC PRESSURE) (OMISSIBLE):STANDARD MOTOR (RATED STATIC PRESSURE)(High static pressure is only available for DBFP series, DFP only has rated static pressure)

DIGIT NO. 8WATER DIRECTION (FACE TO RETURN AIR INLET) Y : RIGHT WATER IN Z : LEFT WATER IN

DIGIT NO.9CUSTOMER SOURCE & POWER 1 : EXPORT 240V-1Ph-50Hz (only for DBFP(X)1~DBFP(X)6, DFP(X)1~DFP(X)4) 2 : EXPORT 380V-3Ph-50Hz (for DBFP(X)1~DBFP(X)15, DFP(X)1~DFP(X)4)

DIGIT NO. 10CONTROL MODE 0 : NO CONTROL

DIGIT NO. 11HEATING COIL ROWS 0 : NO HEATING COIL 1 : 1 ROW HEATING COIL 2 : 2 ROW HEATING COIL

DIGIT NO. 12DRAIN PAN (WITH INNER INSULATION) 0: G.I DRAINPAN 1: STAINLESS DRAINPAN

Air Volume

DBFP: 1000~15000m3/h DFP: 1000~4000m3/h

DBFP/DFP SERIES –AIR HANDLING UNIT for ExportNOMENCLATURE

DIGIT NO. 1 2 3 4 5 6 7 8 9 10 11 12CODE D B F P X 1 I Y 1 0 1 1

PRODUCT SERIESCOOLING COIL ROWVOLUMESTATIC PRESSUREWATER DIRECTIONCUSTOMER SOURCE & POWERCONTROL MODEHEATIING COIL ROWSDRAIN PAN

Page 4: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

02

Features

DBFP(X) air handling unit is a thin low-noise air handling unit with variable air volumes specially designed and produced by our company to meet the tendency of compact storey height in China and the rest of world. Its major parts include the high efficiency coil, low-noise fan, casing, drain pan, pre filter and hanger:

The coil adopts the up-to-date high-efficiency heat transfer fin, whose heat transfer efficiency is increased by 60% as compared with the first generation fin. The main body of the coil is constructed of high-quality air-conditioning copper tubes and aluminum foils, and after being integrated through advanced mechanical expanders, it passes the sealing and pressure test at 2.8Mpa. The performance complies with the ARI standard of USA to ensure the excellent performance and reliable quality of the product.

The precise dynamic balancing calibration for the low-noise high-efficiency external rotor fan (for DBFP(X)4 - 15 units) and compact straight-coupling fan (for DBFP(X)1- 3units) ensures the extremely stable operation of the unit, and enables the unit to be featured with low noise and higher static pressure.

Constructed of high-quality galvanized steel sheets, the casing structure is rust and erosion resistant, eye-pleasing and durable. The casing is internally lined with sound-absorbing and thermal insulation materials, and characterized with high strength, good thermal insulation and low noise.

The elaborately designed drain pan and thickly lined thermal insulation ensure the unit to be free of commonly-seen condensation under severe conditions, and thus they are especially fitted for suspended installation.

Page 5: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

03

The lug and hanger frame are designed reasonably for easy installation and saving the space height of buildings.

Since the specially designed removable filter can be easily drawn out from both sides of the unit in a folding way, it is most suitable for compact space and convenient to clean. (For DBFP(X)1 – 6, units with bottom drawn out filters are also available).

In general, it is characterized with excellent cooling performance, low noise, thin height, compact structure, light weight and easy installation. Furthermore, if equipped with a frequency or pressure regulating controller, it is able to run on the basis of variable air volume, according to different seasonal conditions and air-conditioning occasions. It is especially suitable for a variety of air-conditioning engineering applications where storey heights of buildings are compact. (Moreover, to meet the requirements of super compact air-conditioners, the latest DFP (X)1-4 ultrathin lifting unit is released, with the air volume range of 1000m3/h~4000m3/h and a height of only 380mm. For detailed performance and dimensions, see the following)

Page 6: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

04

Standard Condition

Unit Air Volumem3/h W×L×H Motor

kW-polesQuantity of Fans/Motors

Static pressure

Pa

Total Pressure

Pa

Cooling Capacity

kW

Heating Capacity

kW

Water FlowT/h

Water Pressure

DropkPa

NoisedB(A)

Unit Weight

kg

DBFP11000 680×986×380

0.20-41/1

145 1605.1 9.7 0.87 10.1

52 54

DBFP1I 0.25-4 235 250 55 55

DBFP1.51500 875×986×380

0.25-41/1

130 1657.8 14.9 1.32 9.2

55 66

DBFP1.5I 0.32-4 225 260 58 68

DBFP22000 872×986×500

0.32-41/1

220 26011.1 21.1 1.93 7.6

56.5 79

DBFP2I 0.55-4 300 342 59.5 84

DBFP2.52500 1018×986×500

0.45-41/1

205 30013.9 26.4 2.41 13.4

60 88

DBFP2.5I 0.55-4 290 352 61 91

DBFP33000 1166×986×500

0.55-41/1

150 24016.9 32.1 2.93 21.8

62 96

DBFP3I 0.55-4 230 321 62 98

DBFP44000 1458×986×500

0.32-42/2

220 26022.3 42.4 3.88 24.6

58 128

DBFP4I 0.55-4 300 342 61 134

DBFP55000 1752×986×500

0.45-42/2

235 30028.9 54.8 5.01 35.0

60.5 149

DBFP5I 0.55-4 290 352 61.5 149

DBFP66000 2044×986×500

0.55-42/2

150 24034.5 65.6 5.97 42.6

62.5 167

DBFP6I 0.55-4 230 321 63.5 167

DBFP88000 1710×1413×595

0.8-62/2

130 17546.9 89.1 8.11 40.6

64 224

DBFP8I 1.0-4 210 319 65.5 230

DBFP1010000 1970×1413×595

1.1-62/2

110 18059.6 113.2 10.31 46.0

67.5 240

DBFP10I 1.8-4 350 423 72.5 245

DBFP1212000 1970×1546×675

1.5-62/2

140 22570.8 134.5 12.25 42.0

68 320

DBFP12I 2.2-4 420 510 72 325

DBFP1515000 2060×1595×712

1.5-42/2

85 21588.5 168.2 15.32 49.3

67.5 342

DBFP15I 3.0-4 310 454 74.5 362

DBFPX11000 680×986×380

0.20-41/1

95 1106.4 11.3 1.1 8.3

52 57

DBFPX1I 0.20-4 185 200 55 58

DBFPX1.51500 875×986×380

0.20-41/1

85 11510.2 17.4 1.72 10.9

55 69

DBFPX1.5I 0.27-4 180 210 58 71

DBFPX22000 872×986×500

0.32-41/1

185 22512.1 21.7 2.1 8.6

56.5 84

DBFPX2I 0.55-4 265 307 59.5 89

DBFPX2.52500 1018×986×500

0.45-41/1

175 26016.0 28.6 2.78 18.8

60 94

DBFPX2.5I 0.55-4 250 312 61 97

DBFPX33000 1166×986×500

0.55-41/1

115 20520.2 36.2 3.51 28.3

62 105

DBFPX3I 0.55-4 195 286 62 107

DBFPX44000 1458×986×500

0.32-42/2

185 22527.2 48.7 4.73 31.3

58 137

DBFPX4I 0.55-4 265 307 61 143

DBFPX55000 1752×986×500

0.45-42/2

195 26037.5 67.1 6.52 42.7

60.5 162

DBFPX5I 0.55-4 250 312 61.5 168

DBFPX66000 2044×986×500

0.55-42/2

115 20545.0 80.6 7.79 51.6

62.5 180

DBFPX6I 0.55-4 195 286 63.5 180

DBFPX88000 1710×1413×595

0.8-62/2

95 14061.5 110 10.64 49.4

64 244

DBFPX8I 1.0-4 175 284 65.5 250

DBFPX1010000 1970×1413×595

1.1-62/2

35 10576.8 137.5 13.29 51.2

67.5 265

DBFPX10I 1.8-4 275 348 72.5 270

DBFPX1212000 1970×1546×675

1.5-62/2

95 18092.3 165.2 15.97 59.2

68 345

DBFPX12I 2.2-4 375 465 72 350

DBFPX1515000 2060×1595×712

1.5-42/2

45 170115.3 206.4 19.95 65.0

67.5 367

DBFPX15I 3.0-4 265 409 74.5 387

Page 7: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

05

Fresh Air Condition

Unit Air Volume m3/h W×L×H Motor

kW-polesQuantity of Fans/Motors

Static pressure

Pa

Total Pressure

Pa

Cooling Capacity

kW

Heating Capacity

kW

Water FlowT/h

Water Pressure

DropkPa

Noise dB(A)

Unit Weight

kg

DBFP11000 680×986×380

0.20-41/1

145 16012.3 14.5 2.11 47.5

52 54

DBFP1I 0.25-4 235 250 55 55

DBFP1.51500 875×986×380

0.25-41/1

130 16518.5 21.8 3.18 43.2

55 66

DBFP1.5I 0.32-4 225 260 58 68

DBFP22000 872×986×500

0.32-41/1

220 26025.1 27.4 4.36 23.4

56.5 79

DBFP2I 0.55-4 300 342 59.5 84

DBFP2.52500 1018×986×500

0.45-41/1

205 30031.7 34.5 5.5 42.5

60 88

DBFP2.5I 0.55-4 290 352 61 91

DBFP33000 1166×986×500

0.55-41/1

150 24039.1 42.6 6.79 57.0

62 96

DBFP3I 0.55-4 230 321 62 98

DBFP44000 1458×986×500

0.32-42/2

220 26054.3 59.2 9.44 41.2

58 128

DBFP4I 0.55-4 300 342 61 134

DBFP55000 1752×986×500

0.45-42/2

235 30065.9 71.8 9.44 55.7

60.5 149

DBFP5I 0.55-4 290 352 61.5 149

DBFP66000 2044×986×500

0.55-42/2

150 24077.1 84.0 11.04 64.1

62.5 167

DBFP6I 0.55-4 230 321 63.5 167

DBFP88000 1710×1413×595

0.8-62/2

130 175105.3 114.8 12.58 56.7

64 224

DBFP8I 1.0-4 210 319 65.5 230

DBFP1010000 1970×1413×595

1.1-62/2

110 180130.0 141.7 13.98 71.5

67.5 240

DBFP10I 1.8-4 350 423 72.5 245

DBFP1212000 1970×1546×675

1.5-62/2

140 225156.0 170.0 15.78 67.6

68 320

DBFP12I 2.2-4 420 510 72 325

DBFP1515000 2060×1595×712

1.5-42/2

85 215199.5 217.5 20.18 78.0

67.5 342

DBFP15I 3.0-4 310 454 74.5 362

DBFPX11000 680×986×380

0.20-41/1

95 11015.5 16.9 2.66 39.3

52 57

DBFPX1I 0.25-4 185 200 55 58

DBFPX1.51500 875×986×380

0.20-41/1

85 11523.8 25.4 4.08 49.8

55 69

DBFPX1.5I 0.32-4 180 210 58 71

DBFPX22000 872×986×500

0.32-41/1

185 22530.6 35.1 5.31 32.6

56.5 84

DBFPX2I 0.55-4 265 307 59.5 89

DBFPX2.52500 1018×986×500

0.45-41/1

175 26038.3 44.0 6.65 59.9

60 94

DBFPX2.5I 0.55-4 250 312 61 97

DBFPX33000 1166×986×500

0.55-41/1

115 20550.1 57.7 8.71 67.6

62 105

DBFPX3I 0.55-4 195 286 62 107

DBFPX44000 1458×986×500

0.32-42/2

185 22566.6 76.6 9.54 51.4

58 137

DBFPX4I 0.55-4 265 307 61 143

DBFPX55000 1752×986×500

0.45-42/2

195 26082.2 94.5 11.4 59.6

60.5 162

DBFPX5I 0.55-4 250 312 61.5 168

DBFPX66000 2044×986×500

0.55-42/2

115 20596.2 110.6 11.5 73.8

62.5 180

DBFPX6I 0.55-4 195 286 63.5 180

DBFPX88000 1710×1413×595

0.8-62/2

95 140131.4 151.2 14.1 63.4

64 244

DBFPX8I 1.0-4 175 284 65.5 250

DBFPX1010000 1970×1413×595

1.1-62/2

35 105161.0 185.2 16.3 72.6

67.5 265

DBFPX10I 1.8-4 275 348 72.5 270

DBFPX1212000 1970×1546×675

1.5-62/2

95 180194.0 222.9 19.6 83.6

68 345

DBFPX12I 2.2-4 375 465 72 350

DBFPX1515000 2060×1595×712

1.5-42/2

45 170241.5 277.7 23.1 98.0

67.5 367

DBFPX15I 3.0-4 265 409 74.5 387

Page 8: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

06

Select the performance of heating coil (2R)

Unit Air Volume m3/h

Heating CapacitykW

Water FlowT/h

Water Pressure DropkPa

Water Air Pressure DropPa

DBFP11000 4.1 0.72 0.1 10

DBFP1IDBFP1.5

1500 6.5 1.12 0.6 10DBFP1.5IDBFP2

2000 9.0 1.55 0.6 10DBFP2IDBFP2.5

2500 11.4 1.98 1.2 10DBFP2.5IDBFP3

3000 13.9 2.38 2.2 10DBFP3IDBFP4

4000 18.7 3.24 5.5 10DBFP4IDBFP5

5000 23.5 4.07 11.0 10DBFP5IDBFP6

6000 28.4 4.90 19.3 10DBFP6IDBFP8

8000 35.9 6.19 16.0 15DBFP8IDBFP10

10000 44.0 7.60 28.1 15DBFP10IDBFP12

12000 56.6 9.76 26.2 15DBFP12IDBFP15

15000 68.1 11.74 34.0 15DBFP15IDBFPX1

1000 4.1 0.72 0.1 10DBFPX1IDBFPX1.5

1500 6.5 1.12 0.6 10DBFPX1.5IDBFPX2

2000 9.0 1.55 0.6 10DBFPX2IDBFPX2.5

2500 11.4 1.98 1.2 10DBFPX2.5IDBFPX3

3000 13.9 2.38 2.2 10DBFPX3IDBFPX4

4000 18.7 3.24 5.5 10DBFPX4IDBFPX5

5000 23.5 4.07 11.0 10DBFPX5IDBFPX6

6000 28.4 4.90 19.3 10DBFPX6IDBFPX8

8000 35.9 6.19 16.0 15DBFPX8IDBFPX10

10000 44.0 7.60 28.1 15DBFPX10IDBFPX12

12000 56.6 9.76 26.2 15DBFPX12IDBFPX15

15000 68.1 11.74 34.0 15DBFPX15I

Working Condition: Inlet Air 15˚C DBEnt. Water Temperature 60˚CWater Temperature Rise 5˚C

Page 9: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

07

P

Dimension of DBFP(X)

Note: for DBFP1~6 units, the lug is located on the top of the unit

Each model of unit has the same top views and sizes.d10 is a drainage outlet for the external drain pan, which is connected to ZG1 condensate drain pipe. For method of installation, see the Manual for Installation, Operation and Maintenance.

DBFP(X) 1/1.5

DBFP 2/2.5/3DBFPX 2/2.5/3

DBFP 4/5/6DBFPX 4/5/6

286

N

M

A

M

B

G G

C

DD/2

148

60

31

942

105

315

986

500

64 H

N

892

385

320

11640

40

60

40

2-ø25

2-ZG11/4�ZG1�

4-ø13.2×30

5Power Holes

Lifting Holes

UnitSize Dimension

A B C D G H M N

DBFP4DBFPX4 1458 1307 1386 728

303 225

66 13688 114

DBFP5DBFPX5 1752 1601 1680 875

66 13688 114

DBFP6DBFPX6 2044 1893 1972 1021

66 13688 114

DBFP4IDBFPX4I 1458 1307 1386 728

301 229

66 13688 114

DBFP5IDBFPX5I 1752 1601 1680 875

66 13688 114

DBFP6IDBFPX6I 2044 1893 1972 1021

66 13688 114

Unit

Unit

Size Dimension

Size DimensionPower Holes

Lifting Holes

Page 10: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

08

Note: for DBFP 8-15 units, the lug is located at the bottom of the unit. When preparing a hanging bar, take into account its length

DBFP 8/10DBFPX 8/10

Dimension of DBFP(X)

M

C

H51

D/2

D B E

6010

0

62

2-ø2

5

31

48

1300

40

GG

A

1360

4-ø15 Lifting Holes

Pow

er H

oles

UnitSize Dimension

A B C D E G H M N

DBFP8DBFPX8 1710 1645 595 834 1553

383 334

105 24171 268

DBFP10DBFPX10 1970 1905 595 964 1813

105 24171 268

DBFP8IDBFPX8I 1710 1645 595 834 1553 328 256

105 24171 268

DBFP10IDBFPX10I 1970 1905 595 964 1813 383 334

105 24171 268

1.5

N

Page 11: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

09

Dimension of DBFP(X)

DBFP 12DBFPX 12

489

111

561805

13861546

H

675

I

482

964

1890

1813

6010

0

62

2-ø2

5

31

48

1435

40

G

1970

1493

4-ø20 Lifting Holes

Pow

er H

oles

UnitSize Dimension

G H I M N

DBFP12DBFPX12 434 329 60

105 24170 268

DBFP12IDBFPX12I 383 354 50

105 24170 268

Page 12: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

10

DBFP 15DBFPX 15

Dimension of DBFP(X)

504

1008

1980

1903

6010

0

62

2-ø2

5

31

48

1485

40

G

2060

1544

4-ø20 Lifting Holes

Pow

er H

oles

UnitSize Dimension

G H I M N

DBFP15DBFPX15 434 329 80

105 24170 268

DBFP15IDBFPX15I 383 354 50

105 24170 268

529

111

612856

14361595

H

712

I

Page 13: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

11

DFP(X) Ultrathin Unit

DFP(X) Performance Table

Unit W×L×H Air Volumem3/h

Unit Static Pressure Pa

Unit Total PressurePa

Number of Motors kW

Unit Weightkg

NoisedB(A)

380V/3P 240V/1P 380V/3P 240V/1P

DFP1DFPX1 680×986×380 1000 200

150200135

220170

220155

0.18×10.18×1

5760

5252

DFP1.5DFPX1.5 875×986×380 1500 185

14514075

230190

185120

0.25×10.25×1

6972

5555

DFP2DFPX2 1018×986×380 2000 95

6510540

180150

190125

0.32×10.32×1

7886

58.558.5

DFP3DFPX3 1458×986×380 3000 140

110185125

190160

235175

0.32×20.32×2

114124

58.558.5

DFP4DFPX4 1752×986×380 4000 85

5510540

170140

190125

0.32×20.32×2

128140

6060

For cooling capacity and heating capacity under mixed conditions and fresh air condition, refer to DBFP(X) units of the same air flow.

Page 14: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

12

Each model of unit has the same top views and sizes. d10 is a drainage outlet for the external drain pan, which is connected to ZG1 condensate drain pipe. For method of installation, see the Manual for Installation, Operation and Maintenance.

Dimension of DFP(X)

DFP 1/1.5DFP 2DFP X2

DFP 3/4DFP X3/4

286

264

200

34

158

44

E

380

54

Size Dimension

Size Dimension

Unit

Unit

Power Holes

Power Holes

Lifting Holes

Lifting Holes

Page 15: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

13

Installation Precautions

1. When moving, lifting and installing the equipment, be sure to observe applicable safety specifications to

prevent personnel from injury and equipment from damage.

2. Prior to installation, first check whether the exterior of the unit is intact, and rotate the fan impeller manually

through the unit outlet to listen carefully whether there is any metal friction noise from the inside If any

abnormal noise is heard, adjust till it does not collide with the casing.

3. Install the unit in a horizontal way, keep the hanging bar perpendicular to the bottom slot iron or lug of the unit,

and be sure to lock the up and down nuts (For details, see the Instructions on IOM). The unit shall not be

subjected to the weight of the external water pipe and air duck, and the inlet and outlet of the unit must be

flexibly connected to the air supply and return duck.

4. All pipes connected to the unit must be provided with adjusting valves (add danpers except condensation

pipes) to adjust the water flow and air flow and must ensure cutting off the power supply in maintenance.

The external water pipes and supply air ducks must be thermally insulated.

5. Given the negative pressure, the condensate drain pipe must be provided with a U-shaped trap into the

sewage. To ensure smooth discharge of condensate, the drain pipe must have 1/25-1/50 gradient.

6. Open the side panel with a nameplate and connect to the power supply, according to the wiring diagram,

start the fan after power-on; inspect whether the impeller rotates in the arrow direction on the fan.

7. Some space for maintenance must be retained around the unit to facilitate maintenance and repair.

Use Precautions

1. Prior to starting the unit fan, be sure to remove all irrelative objects in the unit and air ducts, and check that all

valves are in good condition.

2. When starting the unit, have the unit run under rated air flow through adjusting dampers in the air duct; never

have the unit run at excessive air flow and over-current. For the electric controlling box, the incoming line of

each motor of the unit is separately provided with a proper thermal relay to protect the unit. (For DBFP(X)1 – 3

units DFP(X)1 – 4 units three phase only)

3. Standard condition for using the product: 7°C enter water for cooling, and 60°C enter water for heating. It is

required that the water should be clear and have working pressure ≤1.6MPa; fresh air condition and mix

condition comply with chinese standerd.

4. In a season when the equipment is not used, discharge the water in the coil to reduce pipe rust and erosion.

In winter, special care must be given to prevent the copper pipes from frost crack.

Page 16: (Thin) (Ultrathin) Suspended Air-handling Unit - CARRIERcarrier.com.hk/comm/comm_new2010/2012 Cat/Air Handling Unit/DBFP... · 02 Features DBFP(X) air handling unit is a thin low-noise

T-DBFP(X)-1011-01(E)-CHK

Reliability Product/system efficiency

Environmental protection refrigerant Reducing operating noise Indoor air quality Best air distribution

Welcome to Visit Our Website www.carrier.com.cn

All Rights Reserved Carrier

Carrier Corporation identified six specific areas of concentration that directly impact howwe, as a world manufacturer, balance our curtomer' needs for comfort with the environment'sneeds for responsible consumption.