TESTING OF METAL OXIDE SURGE ARRESTER MONITORING
(MOSAM)
ZURAIDA BINTI ZAINOL
UNIVERSITI TEKNOLOGI MALAYSIA
iv
iii
TESTING OF METAL OXIDE SURGE ARRESTER MONITORING
(MOSAM)
ZURAIDA BINTI ZAINOL
A project report submitted in partial fulfillment of the
requirements for the award of the degree of
Master of Engineering (Electrical – Power)
Faculty of Electrical Engineering
Universiti Teknologi Malaysia
JANUARY 2015
vi
iii
Dedicate to my beloved family:
Mohammad Jailani bin A Jamil (husband)
Zainol bin Ahmad (father)
Zabidah binti Wahab (mother)
Zakiah binti Zainol (sister)
Zanariah binti Zainol (sister)
You are all my inspiration and my strength
What I have been through, you were there all the time.
and
All my friends in MEP programme
for their support and encouragement
iii
vii
iii
ACKNOWLEDGEMENT
Alhamdulillahirabilalamiin and thank to Allah SWT for blessing me
for ensuring myself to be healthy to carry out my study and to complete this
project. I wish to express my sincerest appreciation to my supportive
supervisor Associate Prof. Dr. Zulkurnain bin Abdul Malek for the guidance
and persistent help given throughout the progress of this project. I like to
express my thanks to Saaed Vahabi, Wooi Chin Leong and all IVAT staff and
technicians who were involved in this project. Finally, I would also like to
thank all my fellow friends for their support and assistance technically and
mentally in various occasions. All your kindness would not be forgotten. And
I am grateful to all my family members.
iv
viii
iii
ABSTRACT
Surge arrester is a device used to protect the transmission lines and
substations. It protects the power systems from lightning impulses and very fast
transient over voltage. The degradation of a metal oxide surge arrester can be
accomplished by using the measurement of its leakage current in particular, the third
harmonic resistive component. A significant change in the third harmonic level may
indicate a severe ageing of the arrester. Metal Oxide Surge Arrester Monitoring
(MOSAM) is a new smartphone based device capable of assessing the current status
of gapless MO arresters. This project aims to test and verify the MOSAM previously
developed in Institute of High Voltage and High Current (IVAT). Low voltage and
high voltage calibration were carried out. It is shown that the obtained calibration
results using the low voltage are consistent with those using the high voltage. Three
types of clamp meters were used. MOSAM is proven to work as designed for at least
one type of clamp meter.
v
ix
iii
ABSTRAK
Penangkap pusuan ialah alat yang digunakan biasanya untuk melindungi talian
penghantaran dan pencawang. Ia melindungi sistem kuasa dari impuls kilat dan voltan
fana yang sangat cepat. Degredasi penangkap pusuan oksida logam boleh dicapai
dengan menggunakan pengukuran arus bocor khususnya komponen rintangan
harmonik ketiga. Perubahan ketara dalam tahap harmonik ketiga mungkin
menunjukkan penuaan yang teruk ke atas penangkap. Pemantauan Penangkap Pusuan
Oksida Logam (MOSAM) adalah peranti baru berasaskan telefon pintar yang mampu
menilai status semasa penangkap pusuan oksida logam tanpa sela. Projek ini bertujuan
untuk menguji dan mengesahkan MOSAM yang sebelum ini dibangunkan di Institut
Voltan Tinggi dan Arus Tinggi (IVAT). Penentukuran voltan rendah dan voltan tinggi
telah dijalankan. Ia menunjukkan bahawa keputusan penentukuran diperolehi dengan
menggunakan voltan rendah adalah sejajar dengan menggunakan voltan tinggi. Tiga
jenis meter pengapit digunakan untuk ujian ini. MOSAM terbukti mampu beroperasi
seperti yang direka bentuk untuk sekurang-kurangnya satu jenis meter pengapit.
vi
x
iii
TABLE OF CONTENTS
CHAPTER TITLE PAGE
DECLARATION ii
DEDICATION iii
ACKNOWLEDGEMENT iv
ABSTRACT v
ABSTRAK vi
TABLE OF CONTENTS vii
LIST OF TABLES x
LIST OF FIGURES xi
LIST OF ABBREVIATIONS xiv
LIST OF SYMBOLS xv
LIST OF APPENDICES xvi
1 INTRODUCTION 1
1.1 Project Background 1
1.2 Problem Statements 4
1.3 Objectives of Project 4
1.4 Scope of project 4
1.5 Methodology 5
1.6 Thesis Outline 5
2 LITERATURE REVIEW 6
2.1 Introduction to surge arrester 6
2.2 Development of surge arrester 7
vii
xi
iii
2.2.1 Silicon carbide drawback 8
2.2.2 Design of metal oxide surge arrester 8
2.3 Surge arrester failure 9
2.3.1 Sealing problem 9
2.3.2 Internally humidity 10
2.3.3 Arrester degradation 10
2.3.4 Arrester displacement 11
2.3.5 Superficial pollution 11
2.3.6 Irregular voltage distribution 12
2.4 Degradation of metal oxide surge arrester 12
2.5 Moisture ingress problem 14
2.6 Performance monitoring of surge arrester 14
2.7 Metal oxide surge arrester leakage current 16
3 LOW VOLTAGE CALIBRATION AND TESTING 18
3.1 Introduction 18
3.2 Overview of MOSAM 18
3.2.1 Low voltage calibration 19
3.2.2 Regression analysis 20
3.2.2 Low voltage calibration set up 20
3.3 Low voltage testing 23
4 HIGH VOLTAGE CALIBRATION AND TESTING 25
4.1 Introduction 25
4.2 High voltage calibration set up and testing 25
4.3 Determine the third harmonic of leakage current
using Matlab 27
4.4 High voltage testing when clamp meter is 3
meter distance from the bottom of arrester 27
5 RESULTS AND ANALYSIS 28
5.1 Introduction 28
5.2 Low voltage calibration results 28
5.3 Low voltage testing results 33
viii
xii
iii
5.4 Low voltage mixture testing results 37
5.5 High voltage calibration results 38
5.6 High voltage testing results 44
5.6.1 High voltage testing with the clamp meter
is at the bottom near to arrester 45
5.6.2 High voltage testing when clamp meter
is 3meter distance from the bottom of arrester 49
6 CONCLUSION AND FUTURE WORKS 49
6.1 Summaries 49
6.2 Future works 50
REFERENCES 56
Appendices A - B 59- 60
ix
xiii
iii
LIST OF TABLES
TABLE NO. TITLE PAGE
3.1 Ratio of 50 Hz and third harmonic for C1, C2 and C3 23
5.1 Summarize of clamp meter ratios for low voltage
calibration results 33
5.2 Summarize of low voltage testing results 37
5.3 Summarize of mixture testing results 38
5.4 Total RMS current for C1 39
5.5 Total RMS current for C2 40
5.6 Total RMS current for C3 41
and compensated value zero offset 48
5.7 RMS current of high voltage testing after
compensated and compensated value zero offset 43
5.8 Summarize of clamp ratio in high voltage calibration 44
x
xiv
iii
LIST OF FIGURES
FIGURE NO. TITLE PAGE
1.1 Voltages and overvoltages in electric power system 2
1.2 (a) Simplified model representation of surge arrester
and (b) Vector diagram of Ix, Ic and I 3
2.1 The design of Silicon Carbide Arrester and Metal
Oxide Surge Arrester [1] 8
2.2 Electrical discharge due to humidity level [3] 10
2.3 Salty pollution over arrester housing 11
2.4 Current puncture in arrester 12
2.5 Types of degradation of metal oxide surge
arresters and background of diagnostic [8] 13
2.6 Simplified model representation of MO surge arrester 17
3.1 Display of MOSAM applications from smart phone 19
3.2 Low voltage calibration set up 21
3.3 Ratio and accuracy captured bu MOSAM smartphone 22
3.4 Three types pf clamp meters used in the experiment 22
3.5 Mixture testing low voltage set up 23
3.6 Clamp ratio setting and required arrester information
need to key in in the MOSAM 24
4.1 High voltage testing set up with the clamp meter at the
bottom near to the arrester 26
4.2 High voltage testing with clamp at 3 meter distance
bottom of arrester 28
5.1 50 Hz RMS current of ammeter vs. 50 Hz RMS
xi
xv
iii
current of MOSAM for C1 30
5.2 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C1 30
5.3 50 Hz RMS current of ammeter vs.50 Hz RMS
current of MOSAM for C2 31
5.4 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C2 31
5.5 50 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C3 32
5.6 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C3 32
5.7 50 Hz RMS current of ammeter vs. 50 Hz RMS current
of MOSAM for C1 34
5.8 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C1 34
5.9 50 Hz RMS current of ammeter vs. 50 Hz RMS
current of MOSAM for C2 35
5.10 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C2 35
5.11 50 Hz RMS current of ammeter vs. 50 Hz RMS
current of MOSAM for C3 36
5.12 150 Hz RMS current of ammeter vs. 150 Hz RMS
current of MOSAM for C3 36
5.13 Total RMS current for C1 39
5.14 Total RMS current for C2 40
5.15 Total RMS current for C3 42
5.16 Current zero offset for C3 42
5.17 Ammeter current and current compensated value 43
5.18 Total RMS current of high voltage testing for C1 45
5.19 Total peak current of high voltage testing for C1 46
5.20 Current 50 Hz of high voltage testing for C1 46
5.21 Third harmonic current of high voltage testing for C1 47
5.22 Total peak current of high voltage testing for C2 47
5.23 Total RMS current of high voltage testing for C2 48
xii
xvi
iii
5.24 Current 50 Hz of high voltage testing for C2 48
5.25 Third harmonic current of high voltage testing for C2 49
5.26 Total RMS current of high voltage testing when clamp
3 meter from arrester for C1 50
5.27 Third harmonic current of high voltage testing when
clamp 3 meter from arrester for C1 50
5.28 Total RMS current of high voltage testing when clamp
3 meter from arrester C2 51
5.29 Third harmonic current of high voltage testing when
clamp 3 meter from arrester for C2 51
xiii
xvii
iii
LIST OF ABBREVIATIONS
MO - Metal oxide
RMS - Root Mean Square
MOSAM Metal Oxide Surge Arrester
MOSA Metal Oxide Surge Arrester
TOV Temporary Over Voltage
Si Switching Impulse
VFTOs Very Fast Transient Over Voltage
ZnO Zinc Oxide
Hz Hertz
Ref Reference
IRMS Current Root Mean Square
3rd
Third
IVAT Institute of High Voltage and High Current
Min Minimum
Max Maximum
xiv
xviii
iii
LIST OF SYMBOLS
V Voltage
I Current
kV kilo volt
k constant
coefficient
micro
A Ampere
m mili
C1 Clamp 1
C2 Clamp 2
C3 Clamp 3
vs versus
xv
xix
iii
LIST OF APPENDICES
APPENDIX TITLE PAGE
A Surge Arrester Status 59
B MATLAB Programming to determine the
Third Harmonic Leakage Current Measured
by Oscilloscope 60
xvi
xx
iii
CHAPTER 1
INTRODUCTION
1.1 Project background
Surge arresters are widely used to help damage of apparatus due to high voltage.
It has been used in service since 1970’s. It protects the power systems from temporary
over voltage, switching impulses, lightning impulses and very fast transient over
voltage as shown in Figure 1.1. This arrester has two functions which are to provide a
point in the circuit where an over voltage pulse can pass to ground and to prevent any
follow up current from flowing to ground. It’s provides a low impedance path to
ground for the current from a lightning strike or transient voltage and then restore to a
normal operating condition.
xxi
iii
Figure 1.1 Voltages and overvoltages in electric power system
The Metal Oxide (MO) was based on metal block and not require series gap
and hence is referred as a gapless metal oxide arrester. The metal oxide surge arrester
is a non linear resistor. It consists of disc of metal oxide arranged in a stack inside in
suitable insulator. The construction of metal oxide blocks with a highly non-uniform
current voltage (I-V) is appropriate for over voltage suppression.
Many researchers have been done to study the performance and monitor the
condition of the metal oxide surge arrester. One of that is measurement on leakage
current. Metal Oxide Surge arrester has small leakage current mainly comprises the
capacitive current and the resistive part of the current flowing through it due to its
gapless construction. The surge arrester performance is evaluated by measuring the
resistive part of the leakage current, which is proportional to the watt loss of the
arrester. The increase of in watt loss is a direct measure of deterioration.
The total leakage current mainly comprises of the capacitive component and
resistive component. The capacitive and resistive component leakage current differs
in phase by 90. Therefore, a large increase in the resistive current of the non-linear
metal oxide resistor is needed to observe a significant change in the total leakage
current level. Online measurement of the leakage current are extremely used in
2
xxii
iii
practice to show the root means square (r.m.s), mean or peak value of the leakage
current.
Figure.1.2 (a) Simplified model representation of surge arrester and (b) Vector
diagram of IX, IC and IR
The surge arrester performance is evaluated by measuring the resistive
component of the leakage current, which is proportional to the watt loss of the arrester
(Figure 1.2). The increase the watt loss means the increase of deterioration. The
resistive component consists of third harmonic leakage current when the waveform
shown not purely sinusoidal. These harmonics increase with the increase of resistive
leakage current.
Metal Oxide Surge Arrester Monitoring (MOSAM) is a new smart phone
based device capable of assessing the current status of gapless MO arrester. However,
being developed within the institute, the device lacks data from field testing. This
project requires data measurement from low voltage testing and high voltage testing
to calibrate the MOSAM. The correlation between the measurement parameter and
age or condition of arrester can be established. Accurate reading of the arrester
leakage current is required in order to obtain real physical condition of the MOSA
insulation.
(a) (b)
3
xxiii
iii
1.2 Problem statement
There are several available metal oxide surge arrester condition monitoring
device. An example of these devices is the SCAR-10 manufactured by ISA ITALY.
However, there are still a lot of implements that can be made on these devices. This
project aims to test and verify a new device previously developed in Institute of High
Voltage and Current (IVAT). The device is named is named is Metal Oxide Surge
Arrester (MOSAM).
Among the tasks need to be carried out are the calibration of MOSAM and the
performance checking against electromagnetic and high voltage interferences.
1.3 Objectives of Project
There are three main objectives that have been achieved in this project:
a) To do calibration on MOSAM
b) To carry out testing of MOSAM
c) To finalize the MOSAM configuration based on the testing data.
1.4 Scope of Project
This scope will cover to 132kV system MO gapless polymeric housed
arresters.
4
xxiv
iii
1.5 Thesis Outline
This thesis has been divided into five chapters. All contents about some basic
or generally principles, theories, formula, previous studies references, methodology of
the project, experimental results and discussions are included based on contents
requirement.
Chapter 1 contains of projects overview and the objectives of conducting the
project. Chapter 2 is discussing about the background information of the project such
as the history of the surge arrester, and design of MOSA. This chapter discussed
briefly on cause of the surge arrester failure and the degradation of MOSA.
In chapter 3, presents the methodology of calibration and testing on MOSAM.
The process and the experimental procedure to carry out the MOSAM were explained
in this chapter. Then, the results and discussion are covered in Chapter 4.
Summarize of all the studies and procedures of works from previous four
chapters discussed in Chapter 5. Besides, future works and recommendation are
recommended at the end of the chapter.
5
lxxiv
iii
REFERENCES
1. Keith Hill, “Surge Arrester and Testing”, Double Engineering Company
2 K. Izumi, H. Honma, and J. Tanaka, “Deterioration of metal oxide surge
arrester element caused by internal partial discharges under polluted
conditions,” in Proc. 3rd Int. Conf. Properties and Applications of Dielectric
Materials, Tokyo, Japan, Jul. 8–12, 1991, pp. 517–520.
3. L. Chrzan, “Concentrated discharges and dry bands on polluted outdoor
insulators”. 13th International Symposium on High Voltage Engineering,
Delft, Netherlands, August 25 – 29, 2003.
4. K. Eda et al., “Degradation Mechanism of Nonohmic Zinc Oxide Ceramics”,
J,Appl, Plyrs,vol. 51, pp 26782684, 1980.
5. H. R Phillip and L. M Levinson, “Degradation phenomena in Zinc Oxide
Varistor: A Review,” Advanced in Ceramics, vol. 7, pp.1, 21 1983.
6. T.Nilla and Y. Fujiwara,”Stability of Metal Oxide Surge Arrester under
Continuous Operating Voltage,” Cigre 33 87, 1987.
7. K-II Weck, W. Hei, V. Hinrichsen and II.-B Solobach, “Beurteilung der
Nutzungsdauer von Uberspannungsableitern,” ETG Fachtagung, 1995.
8 Christian Heinrich and Volker Hinrincsen, “ Diagnostic and Monitoring of
Metal Oxide Surge Arrester in High Voltage Networks – Comparison of
Existing and Newly Developed Procedures”, IEEE Trans. on Power Delivery,
vol. 16, no. 1, Jan 2001.
9. http://en.wikipedia.org/wiki/Regression_analysis
10. E. T. Wanderley Neto, E. G. da Costa, T. V. Ferreira, and M. J. A. Maia,
“Failure Analysis in ZnO Arresters Using Thermal Images” IEEE PES
Transmission and Distribution Conference and Exposition Latin America,
Venezuela, 2006
56
lxxv
iii
11. B. Weise, C. Heinrich, L. Klingbeil, W. Kalkner, “High Energy Lightning
Impulse Stress on MO Arresters and their Degradation”. 25th International
Conference on Lightning Protection. September 18 – 22, 2000. Rhodos,
Greece.
12. A Bargigia et. al, “Study of The Performance of The Metal Oxide Arrester For
The High Voltage System”, in Proc. Int. Conf. Large High Voltage Electric
System, Paris France 1986, pp 33.14.1 – 33.14.12.
13. Tong Zhao, Qing Min Li (Member IEEE), and Jiali Qian, “Investigation on
Digital Algorithm For On-Line Monitoring and Diagnostics of Metal Oxide
Surge Arrester Based On An Accurate Model”, Power Delivery Transaction,
Vol. 20, No. 2, April 2005.
14. L. Zhou, et al “A Study On Variable Coefficient Compensation Method and
Performance Diagnostic of Metal Oxide Arrester’s Operating State
Detection”, Electric Technology Transaction, Vol. 13. No. 6 Dec 1998.
15 Peng Hui, Lou Xiaowen, “A High Precision Calibrator For Metal Oxide
Surge Arrester On-Line Monitor”, in Hubei China, ICEMI 2009.
16. Vivek Johri, M. Mohana Rao, “Handbook of Switchgears”.
17. M.Nju, S.H Myung, J.B Lee, Y.G Cho, B.Y Lee, S.H Chang, S. Shenderey,
“Evaluation of The Resistive Current of The Metal Oxide Surge Arrester
Using The Differential Method”.
18 Volker Hinrichsen, Gerd Scholl, Matthias Schubert, Thomas Ostertag, “
Online Monitoring of High Voltage Metal Oxide Surge Arrester By Wireless
Passive Surface Acoustic Wave (SAW) Temperature Sensors”.
19. Zulkurnain Abdul Malek, Novizon Yusoff, Mohd Fairouz Mohd Yousuf,
“Field Experience on Surge Arrester Condition Monitoring – Modified Shifted
Current Method”, Johor Bahru, Malaysia, UPEC2010.
20. Volker Hinrichen, “Monitoring of High Voltage Metal Oxide Surge Arrester”,
Berlin, Germany.
21. Zulkurnain Abdul Malek, Novizon Yusof, Aulia, “ Portable Device to Extract
Resistive Component of the Metal Oxide Surge Arrester Leakage Current”,
UTM Johor Bahru, Johor Malaysia, AUPEC08.
22. T. Klein, K. Feser, W. Schmidt, R.Bebensee, “A New Monitoring System For
Metal Oxide Surge Arresters”, Stuttgart Germany, 22-27 Aug 1999.
57
lxxvi
iii
23. Kai Steinfield, “Design of Metal Oxide Surge Arresters with Polymeric
Housings” Siemen AG, Germany.
24. K.L. Wong, “Electromagnetic Emission Based Monitoring Technique for
Polymer ZnO Surge Arresters”, Deakin University,Victoria Australia,
Dielectric and Electrical Insulation Transaction , Vol. 13, No. 1, Feb 2006.
25. Volker Hinrichsen, “Metal Oxide Surge Arrester in High Voltage
Transmission and Distribution Systems, Effective and Reliable Devices
Increasing System Availability and Reducing Maintenance Costs”, Siemen
PTD, Berlin Germany.
26 K. Kannus, K. Lahti and K Nousiainen, “Aspects of The Performance of Metal
Oxide Surge Arresters in Different Environmental Conditions”, Tempere
University of Technology, Finland, CIRED 97, June 1997.
27. E.T. Wanderley Neto, E.G. da Costa and M.J.A Maia, “Artificial Neural
Networks Used for ZnO Arrester Diagnosis”, Power Delivery Transaction,
Vol. 24, No. 3, July 2009.
28 E.T. Wanderley Neto, E.G. da Costa, M.J.A Maia, T. C. L Galindo and A.H.S
Costa, “ Electro-thermal Simulation of ZnO Arresters for Diagnosis Using
Thermal Analysis”, Transmission& Distribution, 2004.
20. Dr. Ahmad Zahedi MIEEE Ceng.MIEE, “Effect of Dry Band on Performance
of UHV Surge Arrester and Leakage Current Monitoring, Using New
Development Model”, Monash Uni, Australia, July 1994.
30. M. Jaroszewski, P. Kostyla, K.Wieczorek, “Effect of Voltage Harmonics
Contenton Arrester Diagnostic Results”, Poland, Solid Dielectric, 2004.
58