TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12 ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 1 Aryabhatta Research Institute of Observational Sciences (ARIES) (An autonomous institute under Department of Science and Technology, Govt. of India) Manora Peak, Nainital, Uttarakhand 263129 INDIA Tel : +91-(5942) - 232655/ 233727/ 233734/ 233735/ 235583 FAX : +91-(5942) - 233439, Gram: astronomy Website: http://www.aries.res.in Part II BOQ For Supply, Installation, Testing and Commissioning of 750KVA Electric substation of ARIES ST Radar with remote monitoring including HT VCB, PCC Panel with LT ACB, Power factor Panel, AMF cum synchronizing with Distribution panel, LT Cable, Earthing, Lightening Arrester, fire system, etc. complete in all respect TENDER ENQUIRY NO: AO/4270/3-33(2)11-12 ISSUE OF TENDER DOCUMENT: 15 th March2012 9.00AM LAST DATE OF SUBMISSION OF BID: 17 th April 2012, 14.00 Hrs

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR … for 750 kva electric sub station for st radar 2011-12 aries manora peak nainital(uttarakhand)263129 page 4 1. 11 kv vacuum circuit breaker

  • Upload
    buianh

  • View
    218

  • Download
    3

Embed Size (px)

Citation preview

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 1

Aryabhatta Research Institute of Observational Sciences (ARIES)

(An autonomous institute under Department of Science and Technology, Govt. of India)

Manora Peak, Nainital, Uttarakhand 263129 INDIA

Tel : +91-(5942) - 232655/ 233727/ 233734/ 233735/ 235583

FAX : +91-(5942) - 233439, Gram: astronomy

Website: http://www.aries.res.in

Part II

BOQ For

Supply, Installation, Testing and Commissioning of 750KVA Electric substation of ARIES ST Radar with remote monitoring including HT VCB, PCC Panel with LT ACB, Power factor Panel, AMF cum synchronizing with Distribution panel, LT Cable, Earthing, Lightening Arrester, fire system, etc. complete in all respect

TENDER ENQUIRY NO: AO/4270/3-33(2)11-12

ISSUE OF TENDER DOCUMENT: 15th March2012 9.00AM LAST DATE OF SUBMISSION OF BID: 17th April 2012, 14.00 Hrs

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 2

Index S.No. Item Page No.

1. Index 2

2. Important Instructions 3

3. 11 KV VCB Panel 4-6

4. PCC panel with LT ACB 7-8

5. IPFC Panel 9-11

6. PLC based DG Synchronization with distribution Panel, SCADA Panel & Industrial computer

12-17

7. LT Cable 18

8. Earting 19-21

9. Lightening arrester 22-24

10. Surge Arrester 25-27

11. Fire Detection & Alarm 28-29

12. First Aid Box 30

13. Rubber Mat & Hand gloves 31

14. Instruction Chart 32

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 3

Important Instructions

1. Tender/BOQ depositions and Tender/BOQ enquiries, if any regarding clarifications/ interpretation in connection with this tender should be addressed to: Director(Kind attention Er. Chandra Prakash), Aryabhatta Research Institute of observational sciencES (ARIES), Manora Peak, Nainital – 263129, Uttarkhand INDIA Tel : +91-(5942) - 232655/ 233727/ 233734/ 233735/ 235583 FAX : +91-(5942) - 233439, Gram: astronomy Email: [email protected] 2. If any work is not specified in this document, that work shall be carried out as per CPWD General Specifications for Electrical works, CPWD General Specification for Electrical Works Part -I, II & IV, as amended upto date relevant IE rules, and as per directions of Engineer - in - Charge. For electrical panels, CPWD General Specification for Electrical Works Part -IV shall be applicable, for DG Set, Part VII (DG SET works) 2006 as amended up to date along with the changes upto date. 3. FRLS wiring shall be used everywhere inside/outside all panels/equipment/building 4. Copper material(strip, plate, etc.) shall have conductivity greater than 95% in all applications 5. Each Earth conductor(for earthing/surge arrester/lightening arrester) shall not left bare it will be through ISI mark GI pipes to avoid corrosion & mechanical injuries 6. All meters of whatever type shall be of digital type unless & otherwise specified. 7. The distribution system shall have automatic phase reversal switch so that in case of phase is reversed from transmitting substation of UPCL, it can adjust accordingly. 8. All Panels shall be of 14 SWG CRCA sheet with 7 tank treatment process. 9. Quotation for Turnkey project from a single company/vender will be preferred. Although whole SCADA system with display unit, lightening arrester, surge arrester, Fire Detection & Alarm, First Aid Box, Rubber Mat & Hand gloves, Instruction Chart can be quoted by independent company/venders. 10. Price for all items/parts/subparts/component shall be quoted separately. No lump sum price will be allowed. 11. ARIES has the right to add or delete any item or its part/subpart specified in tender/BOQ at any stage without prior information to successful vender.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 4

1. 11 KV VACUUM CIRCUIT BREAKER PANEL Motorized Operated, charged independent spring closing tripping, having option of manual closing and tripping push buttons and mechanical breaker ‘Closed / Open’, Spring charged / discharged, indication, Vacuum Circuit Breaker, incorporating mechanical as well as Electrical ON/OFF indicator, the closing mechanism shall be motorized and manually closed 630 Amp Air insulated but encapsulated Aluminium Bus Bars.

Bill of Quantity of VCB for 750 KVA Electric sub-station for ST Radar

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1. H.T. Substation A VCB: Supply, installation,

testing and commissioning of indoor type cubicle single panel, 630A ,11 kV, 3 Phase, 50 Hz., metal clad, dead front, floor mounted, vertical isolation, Horizontal drawout, 250 MVA rupturing capacity Vacuum Circuit Breaker Incoming & Outgoings as per the detailed specifications given in tender document including all connections, etc., with POWER PACK door interlocking panel and should be expendable type complete in all respect as per technical specifications and as required and having following:

1 set

a) 1 No. 630A, 11kV, 3 Phase, 50Hz., metal clad, dead front, 250 MVA rupturing capacity, Fully Drawout type, Vacuum Circuit Breaker (VCB)

b) 1 set of 11kV/110V, 150VA Potential Transformers with protection MCB

c) 1 Set of Phase indicating lamps with protection MCB

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 5

d) 1 set of indicating lamps to indicate OPEN, CLOSE, TRIP, SPRING CHARGED, TRIP CIRCUIT.

e) 1 set of 100/5-5A Current Transformer for metering and protection 15 VA burden with class 0.5-1.0 accuracy

f) 1 Set of IDMT Relay with i) 1 no. Digital Tri vector meter

containing HT voltage, ampere, frequency, Power factor, KW, KVA, KVAR, KVAH, KWH, KVARH, Avg pf, avg voltage, avg frequency, run hours, no. of interruptions, % total harmonics distortion of all 3 phases voltages & current, KVA, instant & maximum demand with day, date & time of maximum demand occurrence, High-low profile records with 4 peaks & 4 lows for V,A,F & PF and all power parameters with day, date & time of occurrence.

ii) Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU/equivalent protocol using inbuilt RS485 port up to the required destination.

g) Trip circuit supervision relay, Auxiliary relays with shunt trip coil as per requirement

h) 1No. Master Trip relay i) Transformer protection for

Bucholtz relay, Oil temperature, & Winding Temerature with alarm & trip provision

j) 8 stage annunciator window shall be provided with VCB for all relays

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 6

k) Mechanical operation counter i) Electrical release coil of 24V. ii) Shunt trip coil of 24V. B BUSBARS : a) 11kV, 250 MVA, 630 Amps

Three Phase busbars of aluminium with Rear cable termination i.e. Provision for terminating 1 X 3C X 240 sq mm. XLPE Cable

C 1 no. 230V AC single phase 80 W rates strip type heater.

D 1 no. H.T Danger Plate

E 1 no. Battery Charger 24 V DC with battery suitable for VCB operation

F CAT-6 Ethernet cable as per requirement

m

G All wiring necessary for the above including interconnection to trip coil. The wire should be FRLS type in all panels

Note: All Switchgear Panels shall be complete with all internal wiring and circuit labels, Epoxy sealing kits, cable lugs, cable clamps and cable glands should be included in the scope of VCB panel.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 7

2. PCC Panel with LT ACB

Bill of Quantity of PCC Panel with LT ACB for 750 KVA Electric sub-station for ST Radar

S.No.Description Qty Unit Rate in Figures

Rate in words

Amount

1. Incomer 1600A from 750 KVA 3phase Transformer

a) ACB 1600A, 4 Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR with 50 KA

1

No.

b) Multifunction Meter with Parameters (V,A,F, KW, KWH, KVA, KVAH, KVAR, KVARH, PF, etc) along with CT 1600/5 A

1

No.

c) Phase Indicator R,Y,B 1 No.

2. Outgoings 1600A, 3 pole (For APFC)

a) ACB 1600A, 50 KA 3 Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

b) Digital VAF Meter CT 1600/5 A 1 No.

3. Outgoings 1600A, 4 pole a) ACB 1600A, 4 Pole, EDO Draw-out

type 50 KA circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

b) Power Monitor with Parameters(V,A,F, KW, KWH, KVA, KVAH, KVAR, KVARH, PF etc) along

1 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 8

with CT 1600/5 A

4. Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU/equivalent protocol using inbuilt RS485 port up to the required destination.

5. Electrical Panel Size approx 2800mm*2100mm*1000mm

1 No.

6. CAT-6 Ethernet cable as per requirement

m

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 9

3. IPFC Relay Control Panel 700 KVAR

Fabrication, supplying, installation, testing & commissioning of intelligent power factor correction panel of 700 KVAR capacity suitable for operation on 440 V, 50 Hz, 3 Phase, mains made out of 14 gauge M.S sheet for power factor improvement including supplying & installation of 12 Nos. Capacitor banks in the following capacities:

Bill of Quantity for 700KVAR IPFC panel for 750 KVA Electric sub-station for ST Radar

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1 Mains Incomer a) ACB 1600A 3 Pole,

50kA, EDO Type with O/L Protection 1

No.

b) Digital VAF Meter with CT 1600A 1

No.

c) IPFC Relay 12 stage 1 No.

d) Phase Indicator R,Y,B 1 No.

2 Capacitor Banks

a) Prismatic APP 100 KVAr 5

No.

b) Prismatic APP 50 KVAr 3 No.

c) Prismatic APP 20 KVAr 1 No.

d) Prismatic APP 15 KVAr 1 No.

e) Prismatic APP 10 KVAr 1 No.

f) Prismatic APP 5 KVAr 1 No.

3 Contactor for Capacitor Banks

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 10

a) 150 A contactor 3pole ,with coil voltage 230 volt 10

No.

b) 150 A contactor 3pole ,with coil voltage 230 volt 3

No.

c) 50 A contactor 3pole ,with coil voltage 230 volt 1

No.

d) 40 A contactor 3pole ,with coil voltage 230 volt 1

No.

e) 32 A contactor 3pole ,with coil voltage 230 volt 1

No.

f) 18 A contactor 3pole ,with coil voltage 230 volt 1

No.

4 MCB/MCCB for Capacitor Banks

a) MCCB 160A , 3 Pole, 25kA 10

No.

b) MCCB 160A , 3 Pole, 25kA 3

No.

c) MCB 63A , 3 Pole, 10kA 1

No.

d) MCB 40A, 3 Pole, 10kA 1 No.

e) MCB 32A, 3 Pole, 10kA 1 No.

f) MCB 16A, 3 Pole, 10kA 1 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 11

5 Fully Wired Panel size: Approx 2000mm x 2000mm x 1000mm, with Individual Auto/ Manual selection for each bank, with Phase failure relay, with delay timer for the protection of capacitors, with fuse terminal for each capacitor bank contactor, with individual indication of ON for each bank etc. 1

No.

6 CAT-6 Ethernet cable as per requirement

m

7 Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU/ equivalent protocol using inbuilt RS485 port up to the required destination.

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 12

4.PLC based DG Synchronization with distribution Panel

D.G. Synchronization Panel for 2 X 415 KVA D.G. Sets as per technical detail, with AMF, Auto synchronizing, Manual synchronizing, auto load sharing, priority based load shedding, auto change-over of Main & D.G. to Load and Inter posing relay, Active & Reactive power management with protection such as U/V, O/V, E/F, O/C IDMT and Reverse power, Motorized Pot (If required), SMPS, UPS 2KVA, Inter connecting cables and other accessories complete in all respect.

Bill of Quantity for PLC based DG synchronization panel for 2x415 KVA DG Sets & 750 KVA Electric sub-station for ST Radar

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1. 16/32 Bit PLC with Min 16 K Memory with Ethernet communication Port

1 No.

2. 16 Channel Digital Input for DG and Mains Monitoring

2

No.

3. 16 Digital output for DG and Mains Control

2 No.

4. 4 Channel Analog Input Card for Phase Angle Transducer

1

No.

5. 4 Channel Analog Output Card for Voltage and Frequency

1 No.

6. 1500 Tag SCADA software compatible for above PLC

1 No.

7.

Interconnecting Cables for above system

As per requirement

m

8. Power Monitors Cl 1.0 3 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 13

9. Phase Angle Transducer 1 No.

10 CAT-6 Ethernet cable as per requirement

m

11. Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU/equivalent protocol using inbuilt RS485 port up to the required destination.

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

The PLC panel shall have all digital outputs through interposing relays. All the field signals should connect on suitable terminals. No field signal should have direct connections on PLC system.

The SCADA system shall have facility to show all DG parameters, DG Master selection, Electrical SLD system, Various parameters Trends(graphs), DG running hours (Shiftwise, Daily, monthly and yearly), all electrical parameters etc.

The PLC system shall have flexibility of programming as per site requirement.

The system shall have 2KVA Online UPS power for PLC panel and one no. PC suitable for SCADA system with latest specifications.

Manual DG Synchronisation panel Specifications

The Maual synchronizing system should be based on 3 lamps method. The system should have Double Volt, And Double Frequency Meter, Synchroscope and check synchronizing relay.

Bill of Quantity of Manual Panel for 2x415 KVA DG Sets & 750 KVA Electric sub-station for ST Radar

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1. Double frequency meter 1 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 14

2. Double Voltmeter 1 No. 3. Snchroscope 1 No. 4. Candescent lamps with

holder 1 set

5. Motorised Potentiometer as per AVR

1 set

6. Motorised Potentiometer as per governer

1 set

7. Sel. Switch for I/C selection

1 set

8. Sel switch for synchronization On/Off selection

1 set

9. Check synchronizing relay

1 Set

10. Auto manual selection 1 set

Bill of Quantity of DG Synchronization Panel for 2x415 KVA DG Sets & 750 KVA Electric sub-station for ST Radar

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1 Mains Incomer 1600A Main Transformer

a) ACB 1600A, 50 kA, 4 Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

b) Load Manager with Parameters(V,A,F, KW, KWH, KVA, KVAH PF etc) along with CT 1600/5 A

1

No.

c) Phase Indicator R,Y,B 1 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 15

2 DG Incomer-1 1000A for 415 KVA DG set

a) ACB 1000A, 50kA, 3 Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

b) Neutral Contactor 225A, 3 Pole

1 No.

c) U/V Relay and Reverse power Relay

1 No.

d) Load Manager with Parameters(V,A,F, KW, KWH, KVA, KVAH PF etc) along with CT 1000/5 A

1

No.

3 DG Incomer-2 1000A for 415 KVA DG set

a) ACB 1000A, 50kA, 3 Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

b) Neutral Contactor 225A, 3 Pole

1 No.

c) U/V Relay and Reverse power Relay

1 No.

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 16

d) Load Manager with Parameters(V,A,F, KW, KWH, KVA, KVAH PF etc) along with CT 1000/5 A

1

No.

4 Bus Coupler 1600A a) ACB 1600A, 50kA, 3

Pole, EDO Draw-out type circuit breaker with microprocessor based ET6G trip system with O/L, U/V, EFR

1

No.

5 Outgoings 630A, 4 pole

a) MCCB 630A, 4 Pole, 36 kA, Motorised

2 No.

b) Digital VAF Meter with 600/5 A CT

2 No.

6 Outgoings 200A, 4 pole

a) MCCB 200A, 4 Pole, 36 kA, Motorised

2 No.

b) Digital VAF Meter with 600/5 A CT

2 No.

c) Have a provision for diesel sensor and DG sets shall be stopped before consuming the entire fuel.

As required

d) CAT-6 Ethernet cable as per requirement

m

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 17

7 Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU or equivalent protocol using inbuilt RS485 port upto the required destination.

4.1 SCADA Panel & Software

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1 Supply, Installation, testing & commissioning of PLC/SCADA panel, required sensors, alarms, etc. with modifiable software without time bound license as per all item of E.11 of tender document Part I, complete in all respect

1 No

2 CAT-6 Ethernet cable as per requirement

m

4.2 Industrial computer

S.No. Description Qty Unit Rate in Figures

Rate in words

Amount

1. Supply, Installation, testing & commissioning of Industrial computer as per E.11.2.19 of tender document Part I, complete in all respect

1 No

2. CAT-6 Ethernet cable as per requirement

m

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 18

5. LT cable

The cable shall be laying in cemented trench provided by ARIES

Bill of Quantity of LT cable for 750 KVA Electric sub-station for ST Radar:

S.No. Description Unit Qty Rate in Figures

Rate in words

Amount

1. LT Cable Supplying & Laying(in

a trench provided by ARIES) of following sizes of 1.1 kV grade multicore XLPE aluminium conductor armoured AYFY cable as per IS 1554.(Actual quantity may be approved from engineer incharge before procurement)

a) 3.5 Core, XLPE, Armoured 400 Sqmm Aluminium Conductor electric power cable with lugs as required.

meter 900

Note: If any item is not included in this table that shall be included and no extra

cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 19

6. EARTHING Bill of Quantity of earthing for 750 KVA Electric sub-station for ST Radar

S.No. Description Unit Qty Rate in

Figures Rate in words

Amount

1 Supply, Installation, Testing & Commissioning of whole Earthing Protection System complete in all respect with:

a) Maintenance free Earthing with Copper plate 600mmX600mmX3mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. , having soil treatment material(but without charcoal or coke and salt) complete as per CPWD general specifications for electrical works Part-1, Internal - 2005 and IS:3043-1987. Earthing shall be continuously less than 2 ohms throughout the Warrantee period. Copper plate should have conductivity greater than 95%.

No. 14

b) Maintenance free Earthing points for the installation of a low impedance earthing system with earth

No. 12

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 20

enhancing compounds for the treatment of soil in and around an earthing system to reduce the soil resistivity and lower ground impedance. (Earth resistance of both earth point should be less than 1 ohm throughout warrantee period) Backfill compound should be eco-frendly, and non radioactive and having RoHs certification. Earthing should be maintenance free and does not required regular manual addition of water. Electrode Shall be tested from CPRI. The earthing rod should be corrosion/ Erosion proof. The earting pit should be cover with FRP cover ,of 300 x 300 mm

c) Providing & Fixing 25mm x3mm copper strip in 40mm size medium class G.I. Pipe from earth electrode in Ground to desired equipments/panel, as required. Copper strip should have conductivity greater than 95%

m 400

d) Providing and fixing M.V. danger notice plate of

No 10

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 21

200mmX150mm made of mild steel, atleast 2mm thick and vitreous enammelled white on both sides and with inscription in signal red colour on front side as required.

Note: If any item is not included in this table that shall be included and no extra

cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 22

7. LIGHTENING ARRESTRER

Bill of Quantity of LIGHTENING ARRESTRER for 750 KVA Electric sub-station for ST Radar

S.No. Description Unit Qty Rate in Figures

Rate in words

Amount

1. Supply, Installation, Testing & Commissioning of whole Lightning Protection System with:

Set 1

a) External Lightning radial protection system, device shall emit corona in the form of a streamer into the air few microseconds earlier than naturally formed streamers. Device confirming to NFC 17-102 Standards. Device must be CPRI tested. Appropriate mounting arrangement should be there. The device shall be mounted at least 5 meters clear to the highest point on the roof top.

b) High Voltage Shielded Cable (HVSC) insulated down copper conductor for reducing the risk of side flashing about 70 sqmm

c) 6 digit Lightning Strike Recorder to effectively count strikes captured

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 23

by the lightening System without any power supply.

d) Lightning Warning System

e) Protection Level Very High(Degree of Isolation greater than 22) with Protection Radius 110 m

f) SS Mast with height greater than 6m, Bar Saddle, Top clamp, nuts & bolts ,Anchor fasteners, Tester to completely install the system

g) Two maintenance free Earthing points for the installation of a low impedance earthing system with earth enhancing compounds for the treatment of soil in and around an earthing system to reduce the soil resistivity and lower ground impedance. (Earth resistance of both earth point should be less than 1 ohm) Backfill compound should be eco-frendly, and non radioactive and having RoHs certification. Earthing should be maintinance free and does not required regular manual addition of water. Electrode Shall be tested from CPRI. The

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 24

earthing rod should be corrosion/ Erosion proof. The earting pit should be cover with FRP cover ,of 300 x 300 mm.

h) CAT-6 Ethernet cable as per requirement

m

i) Shall be capable to communicate all parameters using SCADA s/w with MODBUS RTU/equivalent protocol using inbuilt RS485 port up to the required destination.

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 25

8. SURGE ARRESTRER Bill of Quantity of SURGE ARRESTRER for 750 KVA Electric sub-station for

ST Radar

S.No. Description Unit Qty Rate in Figures

Rate in words

Amount

1. Supply, Installation, Testing & Commissioning of whole transient/surge Protection System complete in all respect with:

a) Encapsulated Class B surge arrester for single/three phase two/four wire system with discharge impulse current(Iimp as per IEC61643-1 65KA (for 10/350µs) between phase to neutral & 100KA (for 10/350µs) between Neutral to earth. Maximum continuous operating voltage should be 320V for Phase to neutral and 500V for Phase to phase. Response time (ta) should be less than 100ns for phase to neutral & Voltage protection level should be less than 1.3 KV

No. 4

b) Encapsulated Class C surge arrester for three phase four wire system with nominal discharge

No. 4

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 26

current(In as per IEC 61643-1) 20KA (for 8/20µs) between phase to neutral & 40KA (for 8/20µs) between neutral to earth. Maximum continuous operating voltage is 320V. Response time (ta) should be less than 25ns for phase to neutral. Voltage protection level should less than 1.3KV.

c) PROTECTION FOR TELECOMMUNICATION, ETHERNET, RF COMMUNICATION SYSTEM:

i) Protection against lightning impulse: Class D Surge arrester for 10 double core system for Switching Equipment, Measuring equipment Data line system, etc With Maximum Continuous voltage Vc 180V. Impulse Current (10/350µs) Iimp should be 1 KA and nominal discharge current In (8/20 µs) should be 5KA. Voltage Protection Level should be less than 0.7KV

No. 2

ii) At EPABX input for protection against surges: class D surge arrester (RJ11-tele) for data line protection device for analogue/ digital

No. 2

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 27

telecommunication system. With impulse current (Iimp) 1.5 kA And nominal discharge current In 7.5KA. Insertion loss (a/db) 0.5 a/db at 36Khz.

iii) At network Switching port/system having RJ 45 connector for protection against surges: Class D surge arrester for data line Protection Device for Ethernet, twisted pair, Cat 6 or equivalent network system with RJ45 connector having nominal discharge current 3 KA and response time <1 ns.

No. 2

iv) At RF equipment with co-axial connector (for BNC, N, F, D type connector): class D data line surge protection device for coaxial communication provides lightning potential equalization between PE/Screen and data line at the building entrance. It shall reduce over voltage to safe protection level. The protection devices shall be used for direct insertion into the data lines and can be easily retrofitted into the existing system.

No. 2

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 28

9. ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Bill of Quantity of ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM for 750 KVA Electric sub-station for ST Radar

S.No. Description Unit Qty Rate in Figures

Rate in words

Amount

1 FIRE DETECTION AND ALARM SYSTEM

a) Supply, installation, testing and commissioning of the following intelligent, addressable type fire detection and alarm accessories as per technical specification & complete in all respect with connections etc. as required(for14x5.75 sqm building & 7x6 sqm)

Set 2

b) Optical type Smoke Detector

No. 6

c) Heat Detector No. 6 d) Manual Break Glass

Unit in MS enclosure No. 2

e) Fire Alarm Bell / Hooter of suitable range to cover the complete floor, in MS enclosure.

No. 2

f) Response indicator No. 2

g) Supply, Installation, testing and commissioning of 4 loop microprocessor based addressable type networkable Fire Detection & Alarm control Panel complete with inbuilt power supply, battery charger with SMF batteries for minimum 24Hrs

Set 1

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 29

backup. The panel shall have communication module and can communicate with PLC/SCADA Panel. The panel should have rectifier, loop card, 80 character LCD unit to indicate fire/fault signals with addresses including external/ internal printer to print the details complete system as per technical specifications and requirement of Local Fire Authority and as required.

h) Design, manufacture, supply and installation of Fire Buckets 13 litre capacity, duly filled with sand and GI pipe support stand for these buckets including painting etc. complete as required

No. 4

i) Supplying and fixing Foam type 9 ltrs capacity fire extinguishers as approved by ISI complete as required.

No. 4

j) Supplying and fixing CO2 type 4.5 ltrs capacity fire extinguishers as approved by ISI complete as required.

No. 4

Note: If any item is not included in this table that shall be included and no extra

cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 30

10. FIRST AID BOX Standard first aid box with all standard contents shall be supplied. Bill of Quantity of FIRST AID BOX for 750 KVA Electric sub-station for ST Radar

S.No. Description Unit Qty Rate in

Figures Rate in words

Amount

1. Supplying, storing, handling and fixing in position in electrical room for 10 person first aid in handy polypropylene box with carrying handle and internal partition .The design protect contents from dust and water penetration complete as per tech. specifications as required

No. 1

Contents a) First aid guidance leaflets b) 20 adhesive plaster (sterile) c) Two eye pads d) 4 triangular bandages e) 6 safety pins f) 6 HSE medium dressing 12 x12

sqcm

g) 2HSE large dressing h) 18x18 sq cm i) 6 individual wrapped bites j) One pair disposable gloves 2. Supply, Install Eye washes with

solution in electrical room Lot 1

a) Sterile single use emergency eye wash Solution Sodium

b) chloride 0.9% w/v sterile water for ocular and tropical irritation and wound cleansing 1 Pack of 25x20 ml pod.

Note: If any item is not included in this table that shall be included and no extra

cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 31

11. RUBBER MAT & Hand Gloves Corrugated rubber insulating matting shall be provided in front of all power & motor control centers, push button station and distribution board in the electrical rooms. The width of matting shall be one meter. It shall be as ISI mark. Hand Gloves shall be of highly insulating material with ISI Mark and can be able to use for both L.T. & H.T

Bill of Quantity of RUBBER MAT & Hand Gloves for 750 KVA Electric sub-station for ST Radar S.No. Description Unit Qty Rate in

Figures Rate in words

Amount

1. Supplying and laying of 1.1kV grade 1 metre wide, 2m in length and 6mm(or greater) thick ISI mark anti skid chequered type Corrugated rubber mat.

No. 10

2. Supplying Hand Gloves of highly insulating material with ISI Mark and can be able to use for both L.T.(500V) & H.T(12000V)

Pairs 5

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item

TENDER FOR 750 KVA ELECTRIC SUB STATION FOR ST RADAR 2011-12

ARIES MANORA PEAK NAINITAL(UTTARAKHAND)263129 Page 32

12. INSTRUCTION CHART Printed instruction chart both in English and Hindi and duly framed with front glass, prescribing treatment to be given to persons having Electric shock, shall be supplied. Bill of Quantity of INSTRUCTION CHART for 750 KVA Electric sub-station for ST Radar

S.No. Description Unit Qty Rate in Figures

Rate in words

Amount

1. Supply and fixing shock treatment chart in English and Hindi mounted on 5mm thick Plywood and 3mm thick plain glass front complete as required.

No. 2

Note: If any item is not included in this table that shall be included and no extra cost will be paid for that item