Upload
jojo-candari
View
838
Download
12
Tags:
Embed Size (px)
Citation preview
PreventaSafety Solutions
Product Substitution Details -Safety Modules
2PreventaSafety Solutions
Product Substitution Details - Safety Modules
ContentsIntroduction 3
Product Substitution List 4
XPS-AL 6
XPS-AX 8
XPS-AS 10
XPS-AM 18
XPS-AP 26
XPS-ASF 30
XPS-AMF 33
XPS-APF 36
XPS-CE 42
GSKC 44
GSKA 45
GNS 46
GTS, GEZ, GEZ-LB 47
GSK3LB 48 Stop of commercialisation is 30.06.2005
3PreventaSafety Solutions
Product Substitution Details - Safety Modules
Introduction
This document is intended as a guide for substitution of obsolete products in order to make the transition to the new Preventa range as easy as possible. In some customer applications, the recommended replacement given in this document may not be the most suitable.
It should also be noted that some of the replacement products are the closest equivalent and not exact replacements. This may mean, for example, that the customers electrical wiring or voltage supply to the monitor may need to be changed. It may also be possible that, depending on the safety function, more than one monitor in the current range is suitable as a replacement. In this case, it is then up to the customer to decide which reference is most suited to the application.
Stop of commercialisation is 30.06.2005
4PreventaSafety Solutions
Product Substitution Details - Safety Modules
PreventaProduct Subsitution List
24VDC
24VAC
48VDC
48VAC
120V
AC
230V
AC
N/O Safety
N/C Additional
Solid State
Time Delay
24VDC
24VAC
48VDC
48VAC
120V
AC
230V
AC
N/O Safety
N/C Additional
Solid State
Time Delay
XPS-AL 3 - - 2 - - -XPS-AX 3 - - - - 3 1 - -
XPS-AF 4 - - - - - 3 - - -XPS-AK 4 - - 3 1 4 -
XPS-AF 4 - - - - - 3 - - -XPS-AK 4 - - 3 1 4 -
XPS-AP 4 6 1 - - XPS-AR 4 - - 7 1 4 -
XPS-ASF 4 2 - 2 -XPS-AMF 4 3 1 2 -
XPS-AK 4 - - 3 1 4 -XPS-AR 4 - - 7 1 4 -
XPS-CE 2 - - - - 2 - 1 - XPS-CM 2 - - - - - 2 - 4 -
No. of OutputsVoltagesVoltagesObsolete Product
Safety Category
Reference
No. of Outputs
1 -XPS-AC 3 3 -
XPS-AK 4
Safety Category
XPS-APF 4 6
3
2 -1
-1
XPS-AS 4 2 - - -
XPS-AM 4 3 1 - -
Closest Equivalent Existing Product
Reference
- -
- - 4
Stop of commercialisation is 30.06.2005
5PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AL Replaced by XPS-AC
� XPS-AC has one extra N/O safety output� XPS-AC has a solid state output for PLC signalling� XPS-AC has choice of removable plug terminals
XPS-AL
A1
A2
XPS-AL Y1 Y2
Start
K1
K2
PE
L1 (+)
N (-)
S1 S2
13
14
A1
A2XPS-AC
XPS-AC Y1 Y2
PE
13
14
23
24
23
24
33
34 Y44
Y43
K1 K2
F1
24VDC
To PLC
Monitoring of E-stop with 2N/C contactsSchematic Comparison
Differentiation
6PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AL Replaced by XPS-AC
XPS-AL
A1
A2
XPS-AL Y1 Y2
Start
K1
K2
PE
L1 (+)
N (-)
S1 S2
13
14
A1
A2XPS-AC
XPS-AC Y1 Y2
PE
13
14
23
24
23
24
33
34 Y44
Y43
K1 K2
F1
24VDC
To PLC
Monitoring of E-stop with 1N/C contact
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AL5110 XPS-AC5121
48VAC - XPS-AC1321120VAC XPS-AL3410 XPS-AC3421230VAC XPS-AL3710 XPS-AC3721
*add P to reference for removable plug terminals
Cross Reference Table
7PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AX Replaced by XPS-AC
� XPS-AC has a solid state output for PLC signalling� XPS-AX has one additional N/C output� XPS-AC has choice of removable plug terminals� XPS-AC has larger range of supply voltage selection
L1 (+)Monitoring of E-stop with 2N/C contacts
Schematic Comparison
Differentiation
XPS-AX
A1
A2
XPS-AX Y1 Y2
Start
K1
K2
PE
N (-)
S1 S2
13
14
A1
A2XPS-AC
XPS-AC Y1 Y2
PE
13
14
23
24
23
24
33
34 Y44
Y43
K1 K2
F1
24VDC
To PLC
33
34
41
42
8PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AX Replaced by XPS-ACMonitoring of E-stop with 1N/C contact
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AX5120 XPS-AC5121
48VAC - XPS-AC1321120VAC - XPS-AC3421230VAC - XPS-AC3721
*add P to reference for removable plug terminals
Cross Reference Table
XPS-AX
A1
A2
XPS-AX Y1 Y2
Start
K1
K2
PE
L1 (+)
N (-)
S1 S2
13
14
A1
A2XPS-AC
XPS-AC Y1 Y2
PE
13
14
23
24
23
24
33
34 Y44
Y43
K1 K2
F1
24VDC
To PLC
41
42
33
34
9PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AS Replaced by XPS-AF
� XPS-AF has one extra N/O safety output� XPS-AF has choice of removable plug terminals� XPS-AF has 22.5mm width� XPS-AS has larger range of voltage selection� XPS-AS can be be used for Type III A two-hand control monitoring
Differentiation
10PreventaSafety Solutions
Product Substitution Details - Safety Modules
Monitoring of E-stop with 2N/C contactsSchematic Comparison
XPS-AS Replaced by XPS-AF
XPS-AS
A1
A2
XPS-AS S11 S12
L1 (+)
N (-)
13
14
A1
A2XPS-AF
XPS-AF S11 S12 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21
S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34S34
S12
Monitoring of E-stop with 1N/C contact
A1XPS-AS S11 S12
L1 (+) F1
B1 S21 S22
S1
A1XPS-AF S11 S12 S21 S22
L1 (+)
S1
11PreventaSafety Solutions
Product Substitution Details - Safety Modules
Monitoring of E-stops with 2N/C contacts in seriesSchematic Comparison
XPS-AS Replaced by XPS-AF
A1XPS-AS S11 S12
L1 (+)
A1XPS-AF S11 S12
F1
B1 S21
S21
S22
S22
S2
S1
Monitoring of a movable guard associated with 2 limit switches with 1contact each
Guard Closed
A1XPS-AS S11 S12
L1 (+)
A1XPS-AF S11 S12
F1
B1 S21
S21
S22
S22
12PreventaSafety Solutions
Product Substitution Details - Safety Modules
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AS5140 XPS-AF513048VAC/DC XPS-AS5340 -
120VAC XPS-AS3440 -230VAC XPS-AS3740 -
*add P to reference for removable plug terminals
Cross Reference Table
XPS-AS Replaced by XPS-AF
13PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AS Replaced by XPS-AK
� XPS-AK has 1 extra N/O safety output� XPS-AK has 1 extra additional N/C output� XPS-AK has 4 solid state output for PLC signalling� XPS-AK has choice of removable plug terminals� XPS-AS can be be used for Type III A two-hand control monitoring
Differentiation
14PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AS Replaced by XPS-AK
Monitoring of E-stop with 2N/C contacts
XPS-AS
A1
A2
XPS-AS S11 S12
L1
N
13
14
A1
A2XPS-AK
XPS-AK S31 S32 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21
S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34S34
S12
Monitoring of E-stop with 1N/C contact
S11 S12
XPS-AS S11 S12B1 S21 S22
S1
XPS-AK S11 S12 S21 S22 S31 S32
41
42
Y31
24VDC
Y74Y64Y54Y32K1/K2 FUSE Ch. A Ch. B
To PLC
B1
B2(-)2
4VD
C(+
)
15PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AS Replaced by XPS-AKSchematic Comparison
Monitoring of a movable guard associated with 2 limit switches with 1contact each
A1XPS-AS S11 S12
L1
A1XPS-AK S31 S32
F1
B1 S21
S21
S22
S22
S2
S1
S11 S12
Monitoring of E-stops with 2N/C contacts in series
Guard Closed
A1XPS-AS S11 S12
L1
A1XPS-AK S31 S32
F1
B1 S21
S21
S22
S22 S11 S12
B124VDC(+)
B124VDC(+)
16PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AS Replaced by XPS-AKCross Reference Table
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AS5140 XPS-AK31114448VAC/DC XPS-AS5340 -
120VAC XPS-AS3440 XPS-AK351144230VAC XPS-AS3740 XPS-AK371144
*add P to reference for removable plug terminals
17PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AF
� XPS-AF has choice of removable plug terminals� XPS-AF has 22.5mm width� XPS-AM has 1 extra additional N/C output� XPS-AM has larger range of supply voltage selection� XPS-AM can be be used for Type III A two-hand control monitoring
Differentiation
18PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AF
Monitoring of E-stop with 2N/C contactsSchematic Comparison
Monitoring of E-stop with 1N/C contact
XPS-AM
A1
A2
XPS-AM S11 S12
L1 (+)
N (-)
13
14
A1
A2XPS-AF
XPS-AF S11 S12 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21
S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34S34
S12
A1XPS-AM S11 S12
L1 (+) F1
B1 S21 S22
S1
A1XPS-AF S11 S12 S21 S22
L1 (+)
S1
41
42
33
34
19PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AF
Monitoring of E-stops with 2N/C contacts in seriesSchematic Comparison
Monitoring of a movable guard associated with 2 limit switches with 1 contact each
A1XPS-AM S11 S12
L1 (+)
A1XPS-AF S11 S12
F1
B1 S21
S21
S22
S22
S2
S1
Guard Closed
A1XPS-AM S11 S12
L1 (+)
A1XPS-AF S11 S12
F1
B1 S21
S21
S22
S22
20PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AF
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AM5140 XPS-AF513048VAC/DC XPS-AM5340 -
120VAC XPS-AM3440 -230VAC XPS-AM3740 -
*add P to reference for removable plug terminals
Cross Reference Table
21PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AK
� XPS-AK has 4 solid state output for PLC signalling� XPS-AK has choice of removable plug terminals� XPS-AK has 45mm width� XPS-AM can be be used for Type III A two-hand control monitoring
Differentiation
22PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AK
XPS-AM
A1
A2
XPS-AM S11 S12
L1
N
13
14
A1
A2XPS-AK
XPS-AK S31 S32 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34
33
34
41
42
S11 S12
K1
K2
S34S12
41
42
Y31
24VDC
Y74Y64Y54Y32K1/K2 FUSE Ch. A Ch. B
To PLC
Monitoring of E-stop with 2N/C contactsSchematic Comparison
Monitoring of E-stop with 1N/C contact
XPS-AM S11 S12B1 S21 S22
S1
XPS-AK S11 S12 S21 S22 S31 S32
B1
B2(-)2
4VD
C(+
)
23PreventaSafety Solutions
Product Substitution Details - Safety Modules
Monitoring of E-stops with 2N/C contacts in seriesSchematic Comparison
A1XPS-AM S11 S12
L1
A1XPS-AK S31 S32
F1
B1 S21
S21
S22
S22
S2
S1
XPS-AM Replaced by XPS-AK
S11 S12
Guard Closed
Monitoring of a movable guard associated with 2 limit switches with 1 contact each
A1XPS-AM S11 S12
L1
A1XPS-AK S31 S32
F1
B1 S21
S21
S22
S22 S11 S12
B124VDC(+)
B124VDC(+)
24PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AM Replaced by XPS-AK
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AM5140 XPS-AK31114448VAC/DC XPS-AM5340 -
120VAC XPS-AM3440 XPS-AK351144230VAC XPS-AM3740 XPS-AK371144
*add P to reference for removable plug terminals
Cross Reference Table
25PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AP Replaced by XPS-AR
� XPS-AR has one extra N/O safety output� XPS-AR has one extra additional N/C output� XPS-AR has 4 solid state output for PLC signalling� XPS-AR has choice of removable plug terminals� XPS-AP can be be used for Type III A two-hand control monitoring
Differentiation
26PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AP Replaced by XPS-AR
Monitoring of E-stop with 2N/C contactsSchematic Comparison
XPS-AP
A1
A2
XPS-AP S11 S12
L1
N
13
14
A1
A2XPS-AR
XPS-AR S11 S52 13
14
K1
K2
F1
B1 S21S21
S22
S22
S1
S34
StartS2
Y1 Y2 S12S11 S12
K1
K2
Y1S34
Y31
24VDC
Y74Y64Y35Y32K1/K2 FUSE Ch. A Ch. B
To PLC
23
24
23
24
33
34
33
34
43
44
43
44
53
54
53
54
63
64
63
64
73
747282
7181
92
91
Monitoring of E-stop with 1N/C contact
XPS-AP S11 S12B1 S21 S22
S1
XPS-AR S11 S12 S21 S22S52
Y2 S33
B1
B2(-)2
4VD
C(+
)
27PreventaSafety Solutions
Product Substitution Details - Safety Modules
Monitoring of E-stops with 2N/C contacts in seriesSchematic Comparison
A1XPS-AP S11 S12
L1
A1XPS-AR S11 S52
F1
B1 S21
S21
S22
S22
S2
S1
S11 S12
Guard Closed
Monitoring of a movable guard associated with 2 limit switches with 1 contact each
A1XPS-AP S11 S12
L1
A1XPS-AR S11 S52
F1
B1 S21
S21
S22
S22 S11 S12
XPS-AP Replaced by XPS-AR
B124VDC(+)
B124VDC(+)
28PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AP Replaced by XPS-AR
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AP5140 XPS-AR31114448VAC/DC XPS-AP5340 -
120VAC XPS-AP3440 XPS-AR351144230VAC XPS-AP3740 XPS-AR371144
*add P to reference for removable plug terminals
Cross Reference Table
29PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-ASF Replaced by XPS-AK
� XPS-AK has one extra N/O safety output� XPS-AK has one extra additional N/C output� XPS-AK has 2 extra solid state output for PLC signalling� XPS-AK has choice of removable plug terminals� XPS-ASF can be be used for Type III A two-hand control monitoring
Differentiation
30PreventaSafety Solutions
Product Substitution Details - Safety Modules
Monitoring of E-stop with 2N/C contactsSchematic Comparison
XPS-ASF Replaced by XPS-AK
Y3141
XPS-ASF
A1
A2
XPS-ASF S11 S12
L1
N
13
14
A1
A2XPS-AK
XPS-AK S31 S32 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34S11 S12
K1
K2
S34S12
42
24VDC
Y74Y64Y54Y32K1/K2 FUSE Ch. A Ch. B
To PLC
Y33
Y44 Y34S33 S42
S32
B1
B2(-)2
4VD
C(+
)
31PreventaSafety Solutions
Product Substitution Details - Safety Modules
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-ASF5142 XPS-AK31114448VAC/DC XPS-ASF5342 -
120VAC XPS-ASF3442 XPS-AK351144230VAC XPS-ASF3742 XPS-AK371144
*add P to reference for removable plug terminals
Monitoring of safety mat with E-stop buttonSchematic Comparison
Cross Reference Table
XPS-ASF Replaced by XPS-AK
A1XPS-ASF S11 S12
L1
A1XPS-AK S11 S12
F1
B1 S21/S31S21
S22
S22
S1
S32
S31S41
S32
S42
S2
B124VDC(+)
32PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AMF Replaced by XPS-AK
� XPS-AK has 2 extra solid state output for PLC signalling� XPS-AK has choice of removable plug terminals� XPS-AMF can be be used for Type III A two-hand control monitoring
Differentiation
33PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AMF Replaced by XPS-AK
Monitoring of E-stop with 2N/C contactsSchematic Comparison
Y3141
XPS-AMF
A1
A2
XPS-AMF S11 S12
L1
N
13
14
A1
A2XPS-AK
XPS-AK S31 S32 13
14
23
24
23
24
33
34
K1 K2
F1
B1 S21S21
S22
S22
S1
S33
StartS2
Y1 Y2 S34S11 S12
K1
K2
S34S12
42
24VDC
Y74Y64Y54Y32K1/K2 FUSE Ch. A Ch. B
To PLC
Y53
Y64 Y54S41 S42
S31 S32 33
34
41
42
B1
B2(-)2
4VD
C(+
)
34PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-AMF Replaced by XPS-AK
Monitoring of safety mat with E-stop buttonSchematic Comparison
A1XPS-AMF S11 S12
L1
A1XPS-AK S11 S12
F1
B1 S21S21
S22
S22
S1
S32
S31S41
S32
S42
S2
S31
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-AMF5142 XPS-AK31114448VAC/DC XPS-AMF5342 -
120VAC XPS-AMF3442 XPS-AK351144230VAC XPS-AMF3742 XPS-AK371144
*add P to reference for removable plug terminals
Cross Reference Table
B124VDC(+)
35PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-APF Replaced by XPS-AK
� XPS-AK has 2 extra solid state output for PLC signalling� XPS-AK has choice of removable plug terminals� XPS-APF has 3 extra N/O safety outputs� XPS-APF can be be used for Type III A two-hand control monitoring
Differentiation
36PreventaSafety Solutions
Product Substitution Details - Safety Modules
Schematic Comparison
XPS-APF Replaced by XPS-AK
Monitoring of E-stop with 2N/C contacts
Y64XPS-APF
A1
A2
XPS-APF S11 S12
L1
N
13
14
A1
A2XPS-AK
XPS-AK S31 S32 13
14
K1
K2
F1
B1 S21S21
S22
S22
S1
S34
StartS2
Y1 Y2 S12S11 S12
K1
K2
S33S34
Y31
24VDC
Y74Y64Y54Y32K1/K2 FUSE Ch. A Ch. B
To PLC
23
24
23
24
33
34
33
34
43
44
53
54
63
64 4282
7141
Y53
Y54
S41 S42
S31 S32
B1
B2(-)2
4VD
C(+
)
37PreventaSafety Solutions
Product Substitution Details - Safety Modules
Schematic Comparison
XPS-APF Replaced by XPS-AK
A1XPS-APF S11 S12
L1
A1XPS-AK S11 S12
F1
B1 S21S21
S22
S22
S1
S32
S31S41
S32
S42
S2
S31
Monitoring of safety mat with E-stop button
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-APF5142 XPS-AK31114448VAC/DC XPS-APF5342 -
120VAC XPS-APF3442 XPS-AK351144230VAC XPS-APF3742 XPS-AK371144
*add P to reference for removable plug terminals
Cross Reference Table
B124VDC(+)
38PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-APF Replaced by XPS-AR
� XPS-AR has 2 extra solid state outputs for PLC signalling� XPS-AR has choice of removable plug terminals� XPS-AR has 1 extra N/O satety outputs� XPS-AR cannot monitor safety mats or edges� XPS-APF can be used for Type III A two-hand control monitoring
Differentiation
39PreventaSafety Solutions
Product Substitution Details - Safety Modules
Schematic Comparison
XPS-APF Replaced by XPS-AR
Monitoring of E-stop with 2N/C contacts
Y64XPS-APF
A1
A2
XPS-APF S11 S12
L1
N
13
14
A1
A2XPS-AR
XPS-AR S11 S52 13
14
K1
K2
F1
B1 S21S21
S22S22
S1
S34
StartS2
Y1 Y2 S12
K1
K2
Y1S34
Y31
24VDC
Y74Y64Y35Y32K1/K2 FUSE Ch. A Ch. B
To PLC
23
24
23
24
33
34
33
34
43
44
53
54
63
64 7282
7181
Y53
Y54
S41 S42
S31 S32
43 53 63
44 54 64
73
74 92
91
Y2 S33 S11 S12
B1B2
(-)2
4VD
C(+
)
40PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-APF Replaced by XPS-AR
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-APF5142 XPS-AR31114448VAC/DC XPS-APF5342 -
120VAC XPS-APF3442 XPS-AR351144230VAC XPS-APF3742 XPS-AR371144
*add P to reference for removable plug terminals
Cross Reference Table
41PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-CE Replaced by XPS-CM
� XPS-CM has 3 extra solid state outputs for PLC signalling� XPS-CM has choice of removable plug terminals� XPS-CM has muting lamp error detection� XPS-CM has only one muting lamp connection� XPS-CM uses 4 muting sensors
Differentiation
42PreventaSafety Solutions
Product Substitution Details - Safety Modules
Z2
MB
Y33
XPS-CE
A1
A2
XPS-CE U+ T1
L1 (+)
N (-)
13
14
A1
A2XPS-CM
XPS-CM U+ T1 13
14
23
24
23
24
F1
U- Z1Z1
Z3
Z3
U+ U- T2Z2 Z4U+
24VDC
Y64Y54Y44Y34Fuse
Start req’dOSSD Mute Fault
Y33
Y34Z4
H1 H2
Schematic Comparison
XPS-CE Replaced by XPS-CM
Monitoring of 4 XU2-S single beam detectors with muting function
U-
T2U-
Sensors 1 and 3
Sensors 2 and 4
H1 UV
MAM1
Y1 Y2Y1 Y2
K1
K2
S1
UV
U+
MutingSensor 1
MutingSensor 2
Y5Y3
43PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS-CE Replaced by XPS-CM
Supply Voltage Obsolete Reference Existing Reference *24VAC/DC XPS-CEP5141 -
24VDC - XPS-CM1144*add P to reference for removable plug terminals
Cross Reference Table
44PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS modules - Replacement of the GSKC by the XPSAK unit
GSKCGSKC
XPSAKXPSAK
A2 T11/33 T34 14 24 Y1 Y2
A2 B2 S33 S34 14 24 34 42 Y31 Y32 Y54
S2
startstart
K1
K2
K1 K2
NN (-)
L2
GSKCGSKCXPSAKXPSAK
A1 T11/33 B1 T12 T21 T22 13 23
A1 B1 S31 S32 S11 S12 S21 S22 13 23 33 41 Y64 Y74
L1 (+)
F1 F2
S1
External jumperExternal jumper
K1-K2 fuse
InputA InputB
+24Vdc
F3to PLC
(+) (-)
45PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS modules - Replacement of the GSKA by the XPSAR unit
46PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS modules - Replacement of the GNS by the XPSNS unit
47PreventaSafety Solutions
Product Substitution Details - Safety Modules
SC DAS-CI / Market Op / JYLS / 10-97
Substitution du GEZ ou GEZ-LB par XPS-BCReplacement of GEZ or GEZ-LB by XPS-BC
Substitution du GTS par XPS-BCReplacement of GTS by XPS-BC
! Après remplacement du produit, vérifier la compatibilité de la distance d'arrêt à videAfter product replacement, check by measurement the overtravel is correct
L1 (+)
XPS-BC
XPS-BC
GTS
GTS
A1
A1
F1
A2
A2
K1
1 3 2
11 13 12
13 23 31
14 24 32
K2
Y1 Y2
8 9
T22 T23 T21
T13 T12 T11
7 6 5
16 17 15
N (-)
K1
K2
S1
S2
S1-S2 : pupitre de commande bimanuelletwo-hand control station
L1 (+)
N (-)
XPS-BC
XPS-BC
GEZ / GEZ-LB
GEZ / GEZ-LB
A1
A1
F1
A2
A2
K1
1 3 4 2
11 13 14 12
13 23 31
14 24 32
K2
Y1 Y2
8 9
T22 T23 T21
T13 T12 T11
57
16 15
(1)
(1)
(1) Ajouter un contact supplémentaire sur chaque bo utonAdd an additionnal contact in each button
K1
K2
S1
S2
S1-S2 : pupitre de commande bimanuelletwo-hand control station
XPS modules - Replacement of the GTS, GEZ, GEZ-LB by the XPSBC unit
48PreventaSafety Solutions
Product Substitution Details - Safety Modules
XPS modules - Replacement of the GSK3LB by the XPSAK unit
L2
GSK3LBGSK3LBXPSAKXPSAK
A1 T11/33 B1 T12 T21 T22 13 23 33 41
A1 B1 S31 S32 S11 S12 S21 S22 13 23 33 41
GSK3LBGSK3LB
XPSAKXPSAK
A2 T11/33 T34 14 24 34 42
A2 B2 S33 S34 14 24 34 42
S2
startstart
K1
K2
K1 K2
NN (-)
L1 (+)
F1 F2S1
49PreventaSafety Solutions
Product Substitution Details - Safety Modules
PreventaSafety Solutions